MODELS: PM401211
AND PM400911
Stationary Standby Electric Generator - 11,200 WATTS - MODEL PM401211 Stationary Standby Electric Generator - 9,7 00 WATTS - MODEL PM400911
IMPORTANT SAFETY INSTRUCTIONS – Please make certain that persons who are to install, operate and maintain this equipment thoroughly read and understand these instructions prior to operation. SAVE THESE INSTRUCTIONS — This manual contains important instructions that should be followed during installation and maintenance of the generator and battery.
Read and understand all safety precautions in this manual and other manuals included with this product before installing, operating and maintaining this equipment. Failure to comply with instructions in this manual could result in personal injury, property damage, and/or voiding of your warranty. Coleman Powermate WILL NOT be liable for any damage because of failure to follow these instructions.
Record the model and serial numbers of your generator below:
© Coleman Powermate, Inc. 10-06



The following information relates to protecting YOUR SAFETY and PREVENTING EQUIPMENT PROBLEMS. To help you recognize this information, we use the following symbols. Please read the manual and pay attention to these sections. Also read and follow all safety labels on the engine/generator set. If labels are damaged or unreadable, contact product service for replacements.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
Ground Location.
– A POTENTIAL HAZARD THAT WILL CAUSE SERIOUS INJURY OR LOSS OF LIFE.
– A POTENTIAL HAZARD THAT COULD CAUSE SERIOUS INJURY OR LOSS OF LIFE.
– A POTENTIAL HAZARD THAT MAY CAUSE MODERATE INJURY OR DAMAGE TO
personal injury or death. Installation MUST be performed by a licensed electrician and licensed plumber, or gas technician. Installation MUST comply with all applicable building and electrical codes. Some areas may require building permits and/or detailed sight inspections prior to approving the unit for operation. NOTE: The important safety instructions appearing in this manual are not meant to cover all possible
conditions and situations that may occur. It must be understood that common sense, caution, and care are factors which are not built into a generator, but are supplied by the person(s) installing, maintaining, and operating it.
circuits at the same time. A properly connected transfer switch helps to prevent backfeed of generator power into commercial lines while the standby generator is operating.
Do not attempt to install the generator yourself. Extremely high and dangerous electrical voltages are present in utility power source lines and in generator load leads when the unit is running. Therefore, be sure to turn OFF all power voltage supplies at their source before attempting to complete electrical connections. Only qualified installation contractors or electrician’s who are familiar with applicable codes, standards, regulations and procedures should install the system. Improper or unauthorized installation, operation, or service of this equipment is extremely hazardous and may result in serious personal injury or death.
This generator supplies extremely high and dangerous power voltages. Any contact with high voltage electrically "hot" components will result in extremely hazardous, and possibly LETHAL, electrical shock. Use care to avoid contact with live terminals, bare connectors, bare wires, etc. Disconnect all power before performing maintenance or service.
Generator exhaust air contains carbon monoxide, a deadly odorless, colorless and tasteless gas. Breathing carbon monoxide causes severe nausea, fainting or death. Install the generator set outdoors only. Do not use exhaust air to heat a room. Do not allow exhaust air to enter a building through windows, doors, air intakes or other means. Avoid breathing exhaust air while installing, operating or servicing generator set. The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
It is NOT intended that the information in this manual be used by any unqualified persons for the purpose of installing a standby electric power system. This equipment must be installed, inspected, tested and adjusted only by qualified personnel. These people must be familiar with the equipment and installation requirements.
The installation of this unit must comply with the regulations of the United States National Electric Code (NEC) as well as state and local codes and Occupational Safety and Health Administration (OSHA) established in the United States.
Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry, make sure clothing and shoes are dry and stand on a dry wooden platform while adjustments are made. Remove wristwatch, rings, and jewelry that can cause short circuits.
This equipment, when installed as part of a standby electric power system, must be installed in conjunction with an approved transfer switch. The transfer switch serves to prevent both generator and utility power from being connected to the load
200-2341 3

Units with broken or missing parts, without
The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground.
protective housing or covers should never be operated. Contact your service center for replacement parts.
Inspect the generator regularly, and contact your nearest Authorized Dealer for parts needing repair or replacement.
Keep a fire extinguisher near the generator at all times. Extinguishers rated "ABC" by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. If you have any question pertaining to fire extinguishers, consult your local fire department.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions form leaking exhaust gases, fuel leakage, oil leakage, etc.
Generator/engine noise can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system. Always wear hearing protection when near or operating the generator.
Thoroughly read the OPERATORS MANUAL before operating the generator. Safe operation and top performance can be obtained only when equipment is operated and maintained properly.
DO NOT permit anyone to operate the standby electric system without proper instruction.
Ensure that enclosure doors are closed and locked at all times other than during service.
4 200-2341

After inspecting the generator, engine and enclosure for physical damage, finish reading the Operating and Maintenance Instructions. These manuals contain important safety information.
The stationary standby electric generator is manufactured for our customers to supply reliable backup power. The generator is a compact unit, designed to supply the power for your needs when utility power fails.
The standby generator runs on Liquid Propane Vapor or Natural Gas allowing flexibility for getting the power you need. Fuel lines should be installed by a licensed plumber or licensed gas technician.
DANGER
Taking a few moments to pre-plan before beginning installation of the generator can provide significant savings in materials and labor and lower future maintenance. Some items to consider in planning generator installation are safe generator operation, use of an Automatic Transfer Switch, load requirements, generator location, fuel supply, environmental conditions and applicable local, regional or national codes. Some areas may require building permits and/or detailed site inspections prior to approving the unit for use. Check with local authorities before starting installation.
Immediately inspect the generator carefully for freight loss or damage upon arrival. If loss or damage is noted at the time of delivery, require the person making the delivery to note the loss or damage on the freight bill, or affix his signature under the consignor’s memo of the loss or damage. Contact the carrier for claim procedures.
Installation of a standby engine/generator system is complex and should not be considered a Do-It-Yourself project. Safe installation requires the skill and knowledge of licensed electricians, plumbers, and professional generator contractors. Contact an authorized dealer for assistance with installation planning and referral to properly qualified, licensed installing contractors.
When loss or damage is noted after delivery, segregate the damaged material, and contact the carrier for claim procedures. Be sure to retain the packaging material for carrier inspection.
“Concealed Damage” is understood to mean damage to the contents of a package which is not evident at the time of delivery by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in transit. The title to goods rests with the consignee when generators are shipped F.O.B. factory, and only the consignee can legally file a claim.
200-2341 5

Proper location of the generator set is important to insure safe and reliable operation and can aid in the installation of the generator. When selecting a site for the generator, first ensure that the pad is outdoors in a well ventilated area to allow for proper cooling and proper removal of deadly exhaust fumes created during operation. Consider the direction of the engine exhaust exiting the cabinet and orient the generator on the site with the exhaust away from any windows, doors, ventilation intakes or other openings that can allow engine exhaust fumes to collect in a confined area. In addition, take into account any prevailing winds or other air currents that could carry engine exhaust fumes in unintended directions.
For minimum installation costs, plan to locate the generator outside at a position adjacent to the electrical service distribution panel and close to the intended fuel supply.
To assure adequate cooling air and access for maintenance, plan to locate the generator so that a minimum of three (3) feet of clear, unobstructed space is available on all sides of the cabinet, including above the lid. If landscaping is used to mask the generator from view or further control sound, leave enough room so that the mature plants still allow three feet of clear space around all sides. If necessary, place a screen style fence around the site to prevent grass, leaves or other combustible debris from gathering around the generator, creating a fire risk.
6 200-2341

Figure 2 Example of Alternative Transfer
When connecting the generator to a building electrical distribution system, use of a transfer switch is recommended to isolate the normal utility source from the generator supply. By preventing backfeed of the generator power into the utility lines during a utility power outage, the switch provides a level of safety for electrical line workers. An automatic transfer switch listed to Underwriters Laboratories Standard 1008 performs this function while also supplying a method to automatically start and stop the generator set and transfer power to the building electrical system from an appropriate source.
Switch Installation (Main Panel Load)
B
When planning for a transfer switch/generator installation, it is necessary to know the method of interconnection to the building system. As illustrated, it is recommended to connect the generator to power only circuits that are necessary during a power outage. When following this method, the transfer switch feeds an electrical sub-panel containing only the necessary circuits (see figure 1). Another option is to connect the transfer switch directly to the entire building electrical distribution system. In this case, all circuits or loads must be controlled to avoid overloading and possibly damaging the generator set (see figure 2).
Switch Installation (Essential Sub-panel Load)
Switch selection is based on factors such as the size of the building distribution system, available generator power and required generator control system. Due to the complex nature of electrical distribution systems, the sizing, selection and installation of a switch is best handled by a licensed electrician or qualified standby generator dealer. Any switch installation must be performed by a licensed electrician to the instructions of the switch manufacturer and any applicable local, regional or national codes.
B
D E A Utility Power
C Main Circuit Panel
D Automatic Transfer Switch
E Essential Loads Sub-panel
B Standby Generator · 200-2341 7

Once installation planning is complete and all necessary local permits are granted, installation of the generator may begin. Within the following section general recommendations are given for installing the generator. However, installations are affected by local site conditions, regional construction practices, material availability, local or regional codes and/or other variables. Therefore, recommendations included in this manual are provided as a guide only and are not meant to serve as detailed installation plans. All decisions regarding installation and materials are at the discretion of the licensed electricians and licensed plumbers performing the installation and/or the inspector performing the final inspection as required by local or regional code. Additionally, illustrations provided in this manual are subject to ongoing revisions and shall not be construed as blueprints.
The generator is supplied with an integral molded plastic base for use as an installation pad. Use of this base is intended to minimize installation cost by eliminating the need for a poured concrete pad.
A pad of crushed gravel a minimum of three inches thick is recommended as a base to set the generator on. Compact the gravel and ensure that the pad is level in all directions, making sure that the overall pad height is greater than the surrounding grade with a slope to carry water away from all sides of the pad. Pad dimensions at least six inches larger than the base size in all directions are recommended.
It is possible to use a standard concrete pad if desired. When using this method, a lightly steel reinforced pad a minimum of 2 inches thick, poured to local codes is recommended. Ensure the pad extends past the generator pallet and is high enough to promote drainage of water away from the generator.
After preparing the base pad, position the generator directly on the pad (A), complete with the wooden skids supplied for shipping. Remove the lag bolts (B) fastening the wood to the pallet from all six positions. Using a pry bar with a block of wood as a pivot, carefully lift one end of the pallet and remove the wooden skids from both that end and the center of the pallet (C). Lower the pallet to the pad, then pry the other end up and remove the skid from that end (D). Check the generator with a level in all directions, placing material under the base as required.
Although the weight of the generator is adequate to prevent movement during normal operation, anchoring of the generator is recommended. To anchor the generator on a gravel pad, drive a minimum of four (4) spikes through the anchoring tabs located on the outside corners of the pallet. If a concrete pad is used, anchor the pallet at the same points using appropriate concrete fasteners.
8 200-2341

200-2341 9

MAIN LINE OUTPUT POWER
Once the generator is anchored in its final position, it is ready for electrical connections. The generator is supplied with two terminal blocks for connection of three distinct electrical circuits; main line output power, GFCI power input and remote start signal. Main line output power is the electrical output of the generator, GFCI input powers the battery charger and optional block heater devices and the remote start signal is the interface with an Automatic Transfer Switch that allows the generator to operate automatically upon a utility power outage.
The output circuit of the generator is 4-wire, 240V, rated for the amperage as shown on the generator nameplate. Connection to the transfer switch requires two leads, commonly referred to as "hot" leads (L1 & L2), a neutral (N), and ground lead. Positions of these leads are labeled on the main line output terminal block, also shown in Fig. B. Select proper power output wire sizes according to allowable ampacities given in Table 310-16 of the latest revision of The National Electric Code(NFPA 70). To connect the wires, strip the insulation back approximately ½" from the end of the wire, insert the stripped end into the terminal block, then torque the terminal block screw to 35 in-lbs (4.0 N-m).
(CONNECT TO
To access the wiring connection terminal blocks, open the generator lid (A) and place the lid prop rod (B) into the slot (C) on the underside of the lid. Remove the three screws (D) from the access panel, then open the hinged access panel (E) as shown in Fig A. The access panel is removable by pulling the pins from the panel hinges. Locate the two terminal blocks (F) on the lower right corner of the engine partition panel.
TRANSFER
SWITCH)
NEUTRAL
FIG. A
GROUND
DANGER
10 200-2341

GENERATOR START SIGNAL
A ground fault circuit interrupting (GFCI) receptacle is provided with the generator to power the battery charger for reliable starting. It is also intended to power an optional block heater if that option is desired. Connection of this circuit to a power supply that is only present when normal utility power is supplied is recommended. By connecting the GFCI in this fashion, it is possible to insure that neither the battery charger or block heater are on while the engine is running. Precautions are engineered into the generator to prevent these occurances but connection of the circuit in this fashion provides an additional fail-safe method of engine and battery protection.
When the control panel mode switch is placed in the AUTO position, generator starting and stopping is controlled by the opening or closing of a set of voltage free contacts. Two wires from those contacts are connected to the generator through the auxiliary connection block shown in Fig. D. Use of a twisted pair of stranded copper wire no smaller than AWG 18 gage is recommended. To insure proper operation of the auto start feature, use a transfer switch offering “close-to-run control contacts. To connect the wires, strip the insulation back approximately ¼" from the end of the wire, insert the stripped end under the screw and washer on the terminal block, then torque the terminal block screw to 20 in-lbs (2.3 N-m).
Input to the GFCI circuit is 3-wire, 120V, 15A. Connections include a "hot" lead (L1), neutral (N) and ground lead. Positions of the incoming wire connections are labeled at the auxiliary connection block, shown in Fig.C. Select proper GFCI supply wire size according to allowable ampacities given in Table 310-16 of the latest revision of The National Electric Code(NFPA 70). To connect the wires, strip the insulation back approximately ¼" from the end of the wire, insert the stripped end under the screw and washer on the terminal block, then torque the terminal block screw to 20 in-lbs (2.3 N-m).
FIG. C
GENERATOR START SIGNAL
ATS1
(CONNECT TO
AUTOMATIC
ATS2
TRANSFER
SWITCH)
GFCI CIRCUIT SUPPLY (CONNECT TO
NEUTRAL
120V UTILITY POWER)
200-2341 11

RELAY PIN WIRE NUMBER
RELAY WIRING INFORMATION WIRE
30 1 85 13 86 9 87 13
3 GENERATOR GROUND 13 STARTER SHIFT SIGNAL 23 LOW OIL SENDER 33 120V UTILITY NEUTRAL
2 SWITCHED BATTERY POSITIVE 12 REMOTE START + 22 HIGH TEMPERATURE SENDER 32 120V UTILITY HOT
1 BATTERY POSITIVE 11 IGNITION TIMING INPUT 21 NOT ASSIGNED 31 NOT ASSIGNED
5 GENERATOR LINE 1 15 MODE SWITCH RUN 25 NOT ASSIGNED 35 CT 1 COMMON
7 GENERATOR LINE 3 17 LED TEST 27 NOT ASSIGNED 37 CT 2 COMMON
9 BATTERY GROUND 19 NOT ASSIGNED 29 NOT ASSIGNED 39 CT 3 COMMON
8 GENERATOR NEUTRAL 18 NOT ASSIGNED 28 NOT ASSIGNED 38 CT 3
4 CONTROLLER START SIGNAL 14 MODE SWITCH AUTO 24 NOT ASSIGNED 34 CT 1
6 GENERATOR LINE 2 16 MODE SWITCH COMMON 26 NOT ASSIGNED 36 CT 2
10 IGNITION SPARK SIGNAL 20 NOT ASSIGNED 30 NOT ASSIGNED
NO. WIRE NAME/ DESCRIPTION WIRE
NO. WIRE NAME/ DESCRIPTION WIRE
12 200-2341

The engine driving the generator is engineered to provide reliable power on either Liquefied Propane Vapor (LPG) or Natural Gas. For proper operation on these fuels, it is important to deliver gas with adequate energy content, at sufficient pressure and flow rate. This is designed to operate on Liquefied Propane Vapor (LPG) with a minimum energy content of 2500 BTU per cubic foot or Natural Gas with a minimum energy content of 1000 BTU per cubic foot. This generator is designed to operate with a fuel pressure at the inlet of the unit between 7 and 11 inches of water column (4-6 ounces).
Required fuel flow rates for specific models are given in the table below. To insure correct sizing of the piping supplying fuel to the generator set, provide the flow and pressure requirements of this section to a fuel supplier or licensed plumber during the installation planning stage. If the fuel supplier cannot guarantee delivery of fuel with these properties, the generator may not perform as advertised.
Due to differences in the energy content of fuel used, it is necessary to derate the output of the generator when connected to Natural Gas. Additionally, regional and/or seasonal variations in the makeup of the fuel can further affect output of the engine/generator system. When using Natural Gas fuel with minimum properties as defined, engine output can fall approximately 10% below that of the same set using Propane Vapor.
PM401211 81 2.2 186
PM409011 79 2.1 176
All values reflect consumption at 100% rated output.
Per the National Gas Code (NFPA 54 - ANSI 2223.1), a manual shutoff valve in the fuel supply line to the generator is recommended.

After electrical connections are complete, the next installation step is to connect a fuel supply to the unit. The fuel inlet fitting supplied with the generator is male ½" NPT and is located adjacent to a fuel access hole in the lower engine end panel as illustrated in Fig E. To accommodate potential settling of the generator relative to rigid supply pipeline, use of a flexible line to make the final connection in the supply line is suggested. When making flexible connections, use only materials rated for the fuel supplied and approved for use by local, regional or national codes and/or regulatory agencies.
When supplying natural gas as the operating fuel,
provide fuel with a minimum of 1000 BTU/ft3 at inlet pressures between 7" and 11" of water column (4 - 6 oz). Failure to meet these minimums will cause the generator to run poorly and/or may limit output to values below nameplate value. If fuel with these qualities is not available, a low calorific fuel system kit may be required, at additional cost. Contact the customer service center to determine if a kit is required in cases of inadequate fuel quality.
Refer to the Fuel Consumption Table on page 13 for fuel flow requirements for the unit installed. Size all feeding piping to deliver sufficient flow above the minimum pressure of 7" water column (4 oz).
Per the National Gas Code (NFPA 54 - ANSI 2223.1), a manual shutoff valve in the fuel supply line to the generator is recommended.
Once all external connections are complete, check the position of the flexible engine supply hose, as shown in Fig F. When configuring a generator to run on a specific fuel, it is necessary to verify correct positioning of the hose on the fuel pressure regulator outlet. The factory default position is for natural gas (NG), as indicated in Fig F. If the fuel hose is not in the proper position, move it to the tee branch labeled NG, making sure the brass cap is placed securely on the opposite branch. With fuel supply attached and the flexible engine supply hose on the proper branch of the regulator output, the fuel hookup is complete. The generator is supplied with a fixed orifice tuned to provide proper fuel flow and no further adjustment of the fuel system is possible or required.
14 200-2341

In cases where liquefied propane vapor is selected as the fuel of choice, insure fuel delivery in the gaseous
state, with a minimum energy content of 2500 BTU/ft3, at inlet pressures between 7" and 11" of water column (4 - 6 oz). Fuel below these specifications may cause improper engine operation and/or failure to deliver rated generator output. Size all fuel system plumbing to provide fuel flow as given in the Fuel Consumption Table on page 13, at a minimum pressure of 7" water column (4 oz).
After completing external supply connections, verify proper positioning of the flexible engine supply hose on the fuel pressure regulator output, as shown in Fig F. The factory default position is for natural gas (NG), requiring a change for liquefied propane vapor (LPG) operation. If the fuel hose is not in the proper position, move it to the tee branch labeled LPG, making sure the brass cap is placed securely on the opposite branch. With fuel supply attached and the flexible engine supply hose on the proper branch of the regulator output, the fuel hookup is complete. The generator is supplied with a fixed orifice tuned to provide proper fuel flow and no further adjustment of the fuel system is possible or required.
200-2341 15

BATTERY REQUIREMENTS
To insure reliable starting in most weather conditions, it is important to properly match a battery to the requirements of the generator. The generator uses a 12 Volt, direct current, negative ground control system powered by an automotive style lead acid battery. Successful engine starting is dependent upon the cranking speed of the engine, which in turn is affected by the cranking capacity of the battery. When selecting a battery, choose the model that provides the highest available cold cranking amperes (CCA) within a given size range, as specified by the Battery Council International (BCI). The battery tray and cables supplied with the generator are sized to accept either a BCI Group 26 or 26R battery, with a minimum recommended rating of 450 CCA.
A battery presents a risk of electrical shock and a high short circuit current. The following precautions are to be observed when working on batteries:
Lead-acid batteries present a risk of fire because lead-acid batteries generate flammable hydrogen gas.
CONNECTION
The next step in installation of the generator is placement and connection of the engine cranking battery. Provided battery cables and battery rack are sized to accept a BCI Group 26 or 26R automotive style battery. A battery with a minimum of 450 CCA (cold cranking amperes) in this size range is recommended to assure reliable engine starting. The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed.
16 200-2341

that the charger is connected by checking to see that it is plugged into a powered GFCI receptacle, and that the positive (+) and negative (-) charger cables are connected to their respective battery cables.
To install the battery, begin by placing the battery (A) into the battery rack as shown in Fig G. Orientation of the battery terminals is according to installer preference as the supplied battery cables are of adequate length to reach terminals regardless of battery direction. Secure the battery to the rack using the J-bolts (B), nuts (C) and battery strap (D) packed in the literature bag packed with the unit, as illustrated by Fig G.
Once all connections are made, the final installation step is verification of proper engine oil level. The engine is factory filled and shipped with approximately 1.5 qt (1.4 liters) of SAE 10W-30 weight oil. Begin the level check by removing the dipstick (K), wiping it clean, then reinserting it into the engine. Remove the dipstick a second time, checking that the oil level falls between the upper and lower limit marks (see Fig A ,page 26) on the end of the dipstick. Adjust engine oil level as required so the level is at the upper limit mark on the dipstick, adding oil to the engine through the oil fill cap (L) as shown in Fig H.
FIG. H
K
After the battery is tight in the rack, begin attaching the battery cables to the battery posts, starting with the positive (+), or red, cable (E). Loosen the bolt (F) on the post clamp slightly to allow the clamp to expand, then firmly push the clamp onto the battery post marked positive (+) until the top of the post extends past the top of the clamp. Rotate the clamp around the post as required to insure the clamp cannot contact any metal components, then tighten the clamp bolt (F) until snug. Finally,slide the post boot (G) down the cable and place it entirely over the clamp.
Finish connecting the battery by placing the negative (-), or black, battery cable (H) to the battery post marked negative (-). Push the clamp firmly over the post until the post extends past the top of the clamp, then rotate the clamp to avoid contact with any metal parts. Tighten the battery clamp bolt (I) until snug.
The final step of battery installation is to verify proper connection of all battery charger connections. A battery charging system (J) is included with the engine/generator set to maintain the battery charge during extended periods of generator inactivity, therefore providing consistent starting. A quick check of charger connections will verify that factory connections are correct so the charger can function as intended. Insure
200-2341 17

After completing all installation procedures, read and understand the operating instructions for the generator controller. Know how the control panel operates, what to expect when activating control panel switches and how to shut the generator off in the event of an emergency. Before starting the generator for the first time, check off all items on the following list, then follow the given procedure to verify correct operation of the generator. Is unit level? Is adequate free air space (3 feet minimum) available on all sides of the enclosure? Are all cabinet openings free from blockage? Is the exhaust directed away from dwellings, dwelling air intakes, or combustible materials? Are the fuel supply lines and internal generator fuel connections leak-free? Is fuel supply pressure within specifications? Is the regulator connection properly configured for the fuel supplied? Is an approved transfer switch used to prevent backfeed into utility lines? Are electrical connections tight, and properly connected? Are electrical conductors sized properly? Is the engine filled to the proper level with the correct type of oil? Is a properly sized engine cranking battery correctly installed? Is the battery maintenance charger plugged in and operating correctly? Are all protective covers installed and tightened? Are all tools clear of moving or electrically live parts? Is the installation inspected and approved as required by local or regional code?
Once all items on the checklist are marked off, complete the initial startup using the listed steps.
18 200-2341

PM401211 PM400911 Rated Output
Propane Vapor 11.2 kW 9.7 kW Natural Gas 9.5 kW 8.2 kW Rated Amperage
Propane Vapor 46.7 A 40.4 A Natural Gas 39.6 A 34.2 A Rated Voltage 240 V 240 V Frequency 60 Hz 60 Hz Phase Single Single Circuit Breaker Size 50 Amp 45 Amp Rated Operating Temperature -20°F to 104°F (-29°C to 40°C) -20°F to 104°F (-29°C to 40°C) Cooling Airflow 977 ft3/min 977 ft3/min Full Load Sound Level 69 dB(A)* 68 dB(A)* Overall Dimensions 42 1/2 in x 32 in x 27 in 42 1/2 in x 32 in x 27 in Weight 478 lb 476 lb
PM401211 PM400911 Manufacturer Honda Honda Manufacturer Engine Model VXC-GDACM VXC-GDADM Style Air cooled, V-twin, 2-cylinder Air cooled, V-twin, 2-cylinder Block Aluminum Aluminum Displacement 670 cc (40.9 in3) 614 cc (37.5 in3) Bore 3.0 in (77 mm) 3.0 in (77 mm) Stroke 2.8 in (72 mm) 2.6 in (66 mm) Compression Ratio 8.3:1 8.3:1 Exhaust Flow 102 ft3/min 93 ft3/min Exhaust Temperature 1007 °F 1007 °F Oil capacity
without filter 1.2 US qt (1.1 l) 1.2 US qt (1.1 l) with filter 1.5 US qt (1.4 l) 1.5 US qt (1.4 l) Oil Filter Honda # 15400-P0H-305PE Honda # 15400-P0H-305PE Air Filter (paper element) Honda # 17210-ZJ1-841 Honda # 17210-ZJ1-841 Spark plugs NGK # ZGR5A or Denso # J16CR-U NGK # ZGR5A or Denso # J16CR-U Spark plug gap 0.12 - 0.16 in (0.30 – 0.40 mm) 0.12 - 0.16 in (0.30 – 0.40 mm) Valve Clearance
Intake 0.005 - 0.007 in (0.13 - 0.17 mm) 0.005 - 0.007 in (0.13 - 0.17 mm) Exhaust 0.007 - 0.009 in (0.18 - 0.22 mm) 0.007 - 0.009 in (0.18 - 0.22 mm)
* Average @ 7 m
200-2341 19

PM401211 PM400911 Style 2 pole, brushless 2 pole, brushless Synchronous Speed 3600 RPM 3600 RPM Excitation Self regulated Self regulated Motor Starting Capacity 12 sKVA† 12 sKVA†
Stator 0.30 – 0.50 W 0.30 – 0.50 W Excitation 1.4 – 1.6 W 1.4 – 1.6 W Rotor 5.9 – 6.0 W 5.9 – 6.0 W Capacitors 40mF, 500V 40mF, 500V
PM401211 PM400911 Battery 12 VDC, BCI Group 26 or 26R 12 VDC, BCI Group 26 or 26R Minimum CCA 450 450 Maintenance charger 6 Amp, 3 stage 6 Amp, 3 stage Fuse 14 Amp, 32 VDC, Type SFE 14 Amp, 32 VDC, Type SFE Engine Alternator 10 Amp regulated 10 Amp regulated Fuse 25 Amp, 32 VDC, Type 3AG 25 Amp, 32 VDC, Type 3AG Fuel Solenoids
Opening Voltage 9.5 VDC 9.5 VDC Coil Resistance 29.1 - 29.8 W 29.1 - 29.8 W
Oil Pressure Switch 14 psi 14 psi Normally open, close on rise Normally open, close on rise High Temp Switch 285°F, Normally open, close on rise 285°F, Normally open, close on rise
PM401211 PM400911 Fuel Pressure 7 – 11 inches water (4 – 6 oz) 7 – 11 inches water (4 – 6 oz) Fuel Consumption (100% load)
Propane Vapor 81 ft3/hr (2.2 Gal/hr) 79 ft3/hr (2.1 Gal/hr) Natural Gas 186 ft3/hr 176 ft3/hr Min Energy Content
Propane Vapor 2500 BTU/ft3 2500 BTU/ft3
Natural Gas 1000 BTU/ft3 1000 BTU/ft3
† Measured @ 30% instantaneous voltage dip
Winding Resistances · 20 200-2341

periods of inactivity to insure reliable, consistent starting. 6. BATTERY CHARGING CIRCUIT FUSE
Before installing, operating or maintaining the generator, take a few moments to become familiar with the features of the generator as illustrated.
Protects engine - mounted battery charging circuit against damage from electrical faults. 7. FUEL REGULATOR/LOCKOFF SOLENOIDS
Controls fuel flow to engine. 8. INTERCONNECTION TERMINAL BLOCKS
Controls the operation of the generator and communicates system status. 2. MAIN LINE CIRCUIT BREAKER
Provided for quick connection of generator wiring to transfer switch during generator installation. 9. OIL LEVEL DIPSTICK
Protects generator and connected loads from electrical faults. Used to isolate output power from operating generator.
High visibility yellow dipstick for checking for proper engine lubricating oil level. 10. OIL FILL PLUG Add fresh engine oil here as required. 11. SPIN ON OIL FILTER Replaceable, disposable filter to remove contaminant's from engine oil to prolong engine life. 12. OIL DRAIN VALVE Quick turn ball valve with extended drain hose to speed up maintenance and eliminate mess. 13. ENGINE AIR FILTER 14. LID SUPPORT ROD 15. FRONT SERVICE ACCESS PANEL Remove to drain oil and change oil filter. 16. CONTROL PANEL CIRCUIT FUSE Protects control panel against damage from electrical faults.
Supplies power to at-rest battery charger and optional block heater. Standard plug receptacle also allows convenient location to power a light or tools during maintenance. 4. CRANKING BATTERY (not included)
Supplies power to start engine and keep control panel active. 5. CRANKING BATTERY CHARGER
Maintains cranking battery at proper level during
200-2341 21

the AUTO position sets the generator for unattended operation under the control of properly matched automatic transfer switch.
A standby generator is an engine driven air cooled system to convert the energy contained in either liquid propane vapor or natural gas to electrical power. When coupled with an automatic transfer switch to monitor for failure of utility power, the unattended system can start, stop and transfer between sources to insure a nearly seamless supply of power. The generator is housed in a weather resistant, sound attenuated enclosure for outdoor installation only.
B. Main Line Circuit Breaker
A Main Line Circuit Breaker is provided to protect the generator from damage caused by electrical faults within the attached electrical distribution system. It is also used to isolate the output of the generator from the connected electrical distribution system by moving the breaker handle to the OFF position. Placing the breaker in this position does not prevent startup of the generator.
Before installing and starting the generator, become familiar with the controls and operational features of the generator. Know how the control panel operates, what to expect when activating control panel switches and how to shut the generator off in the event of an emergency.
C. Status Indicator Lights
Status indicator lights are provided to communicate the status of the generator to the user. Under normal running conditions, only the green Generator On light is lit. Function of all other lights are described on page 24.
B . CIRCUIT BREAKER
D. Generator Hour Meter
The Generator Hour Meter is provided to track the total numbers of hours of operation. The hour meter runs whenever the engine is running and the alternator is producing electricity. Placing the main line circuit breaker in the OFF position while the engine is running does not stop the meter from counting hours.
E . LAMP TEST SWITCH
D
E. Lamp Test Switch
A lamp test switch is provided to check for function of all indicator lights. Press the lamp test switch while the engine is at rest, with the control panel mode switch in the OFF position to illuminate all status lights.
F. Engine Charging Circuit Fuse
The Engine Charging Circuit Fuse provides protection to the engine mounted alternator in the event of electrical faults in the positive (+) battery circuit. Failure of this fuse prevents charge from reaching the battery when the generator is running, leading to early battery failure. Replace the fuse only with an equivalent size and style of fuse to prevent damage to the generator electrical control system.
CONTROL PANEL SWITCHES
A. Mode Switch
The Mode switch is used to set the operating state of the generator. Placing the switch in the OFF position prevents engine operation or stops the engine if it is already running. Moving the switch to the RUN position immediately starts the generator. Putting the switch in
22 200-2341

fault is declared or until the mode switch is moved to the OFF position. Once the switch is shifted to the OFF position, the engine is shut off.
Two methods are available to start the generator. The automatic, or AUTO mode is for use with an automatic transfer switch. With the control panel mode switch set to this position, the generator waits for an external signal to start. This signal is supplied by the transfer switch when utility power is of unacceptable quality. Since utility power can fail at any time, be aware the generator can start unexpectedly whenever in the AUTO position. Keep away from moving parts at all times. Once utility power is once again acceptable, the signal from the transfer switch is removed, the generator shuts off, then returns to waiting for another signal to start.
When operating with the control panel switch in the AUTO position, the generator continues to run until a fault light is declared or the run signal is removed. Once the signal is removed, the engine shuts down and the controller returns to waiting for a start signal.
The other method for starting the generating is to place the mode switch into the RUN position. This mode is intended for generator control during maintenance or if an automatic transfer switch is not used. With the control panel switch shifted to this position, the generator will immediately attempt to start after a brief pause. Upon starting, the generator runs until the switch is moved from the RUN position, at which time the generator will shut off.
To insure the generator starts without damaging the starter motor, cranking of the engine is performed in a cyclic manner. When the generator is started from either the AUTO or RUN positions, the controller alternates between 10 seconds of engine cranking, followed by 10 seconds of engine rest. If the engine starts during any of the cranking periods, crank attempts are halted and the controller begins monitoring for proper function of the generator. In the event that three 10 second start attempts occur without the engine starting, cranking attempts are halted and the Overcrank light is lit.
After the engine is started and the generator is producing electrical power, the controller begins operation in a monitoring state. In this state, several generator functions are continuously checked to ensure proper operation of the generator. If functions are determined unacceptable, a fault is declared, the engine is shut down and a status light is lit to communicate the reason for the shutdown.
When operating with the control panel switch in the RUN position, the generator will continue to run until a
200-2341 23

the engine. Once the light is on, the generator does not attempt to start until the fault is reset. When the Overcrank light is on , verify fuel is available at the inlet to the unit, then check the condition of the cranking battery.
Status indicator lights relay conditions of generator function for user or service technician convenience. Illumination of these indicator lights communicate conditions that require generator service but are not severe enough to cause damage if the generator is allowed to operate. Contact a qualified service technician immediately for service if any of the listed lights are lit, even if the generator appears to function normally.
The Low Oil light turns on and the engine is shut off if the engine oil level falls too low. To avoid engine damage, engine oil pressure is monitored to determine the amount of oil in the engine. When pressure falls below a preset level, a Low Oil fault occurs. Check for proper oil level if the generator shuts down due to a Low Oil alarm.
The Low Battery light is lit when the cranking battery voltage falls below 11.0 volts. At this level, the battery begins to lose the ability to consistently start the engine. Causes of low battery voltage may include a failing battery, failed battery charger or failed engine alternator.
The High Temperature light illuminates if the temperature of the engine becomes too high. Engine oil temperature is monitored while the engine is active and the engine is shut off to avoid damage if the oil temperature becomes too high. When operating the generator in temperatures above the maximum listed on the nameplate, it is necessary to reduce the load connected to the generator to avoid overheating. If high ambient temperatures or excessive loads are eliminated as possible causes of High Temperature shutdown, check to insure cabinet openings are not restricted by debris.
The Not In Auto light is lit whenever the control panel mode switch is not placed in the AUTO position. This light is provided to call attention to this condition since the generator cannot start automatically during a power outage without the switch in the AUTO position. It is normal for this lamp to light when the generator is running with the mode switch in the RUN position, or if the switch is in the OFF position. To turn the light off, move the mode switch to the AUTO position.
F. OVERSPEED
The Generator On light illuminates when the generators engine is running. This is the only light lit when the generator is supplying power as intended.
The Overspeed light is turned on if the generator engine is running too fast. Electrical output of the generator at high speeds may damage loads connected to the generator output and/or engine failure may occur at excessive speeds. If the generator shuts down on an Overspeed error, seek assistance from a qualified generator service technician.
Fault lights relay conditions that may cause damage to the generator and/or loads connected to the output of the generator. When any of the listed situations occur while the generator is running, the generator is shut down and the fault light associated with the shutdown cause is lit. Once the light is lit, it remains on until it is cleared by moving the control panel mode switch to the OFF position. If a fault light is lit, determine and correct the cause of the problem before restarting the generator. During generator starting, the controller ignores fault conditions until 15 seconds after the generator starts, then uncleared faults will once again cause the generator to shut off. To determine possible fault causes, refer to the troubleshooting section of this manual or contact a qualified service technician for assistance.
The Underspeed light is turned on if the generator engine is running too slow. Electrical output of the generator at low speeds can damage loads connected to the generator output and/or generator failure may occur due to excessive heating in the generator head. If the generator turns off due to an Underspeed error, check to see that the connected loads do not exceed the nameplate rating of the generator.
The Overcrank light is lit if all three 10 second cyclic crank attempts are unsuccessful in starting
24 200-2341

To ensure reliable generator operation, it is critical to periodically inspect all components. The following chart is provided as a guide for service check intervals. When the generator is operated under excessively hot, or dusty conditions, shorten service intervals according to the severity of the conditions encountered. To perform periodic inspections or maintenance, refer to the
procedures listed in the following sections. A qualified generator service technician should perform inspections or adjustments requiring specialized tools or training. Users unfamiliar with any of the listed procedures should contact an authorized dealer for servicing assistance.
300 hours Every 2 years
Engine Oil Check X
Engine Oil Filter Change X
Oil Cooler Check and Clean X
Engine Air Filter Check X
Battery Check and Clean X
Battery Charger Check X
Spark Arrestor Check and Clean X
Spark Plugs Check X
Valve Clearance Check and Adjust X
Generator Output Frequency Check and Adjust X
Fuel System Check X
Cooling Air Openings Check X

ENGINE OIL LEVEL CHECK
Prior to checking the oil level, start the generator by moving the Mode switch on the control panel to the RUN position. Allow the generator to run for one or two minutes, then shut it down by returning the switch to the OFF position. After the engine comes to a stop let the engine set for a couple of minutes before checking the oil level. Begin the level check by removing the dipstick (A), wiping it clean, then reinserting it into the engine. Remove the dipstick a second time, checking that the oil level falls between the upper and lower limit marks on the end of the dipstick, as shown in Fig. A. Adjust engine oil level as required so the level is at the upper limit mark on the dipstick, adding oil to the engine through the oil fill cap (B) as shown in Fig B. Add only oil of the same specification as the oil already in the engine.
Fig. A

Fig. B
26 200-2341

Selection of the correct grade and type of engine oil greatly affects the performance of the generator, especially when starting. Before selecting replacement oil for an oil change, consider the anticipated operating conditions the generator may be exposed to. Choose the appropriate weight of oil for anticipated temperatures from Chart C. If temperatures are expected to fluctuate between extremes prior to the next oil change interval, use of synthetic oil is recommended. Use of oil meeting a minimum American Petroleum Institute (API) classification of SJ is advised.
oF -20 0 20 40 60 80 100
oC -30 -20 -10 0 10 20 30 40
Engine oil changes are recommended at the maximum intervals given in the Periodic Maintance Table. When operating in hot or dusty conditions shorter change intervals may be necessary. To change the engine oil and oil filter, the listed procedure is recommended.
AND CLEANING
At the intervals given in the maintenance schedule table, check the oil cooler and lines for leaks. If leaks are detected, replace clamps, fittings or hoses as necessary. Also visually inspect the oil cooler for debris clogging the cooler fins. If the cooler is blocked, use low pressure air or water to dislodge the blocking material.
Chart C · 200-2341 27

BATTERY MAINTENANCE
The generator engine is equipped with a dry element air filter to block particles in the combustion air from getting into the engine and causing excessive engine wear. Over time this dirt builds-up on the filter, restricting the amount of combustion air available to the engine, in turn leading to a loss of generator power output. To avoid these problems, periodic replacement of the engine air filter is recommended at the intervals outline in the service schedule table on page 25. To change the air filter, follow the listed steps.
Correctly maintaining the battery at regular intervals is vital to ensure consistent engine starting. Poorly maintained batteries loose charge over time and may not provide enough power to crank the engine fast enough for reliable starts. The steps below are suggested to care for the battery and charger.
Fig. E

Fig. D
FOAM FILTER ELEMENT
PAPER FILTER
ELEMENT
FILTER COVER
SNAPS
AIR CLEANER
BASE
FILTER COVER
SNAPS
28 200-2341

Fig. F
Display Operating Condition
200-2341 29

spark plugs. If a torque wrench is available, tighten all plugs to 13 in-lbs (18 N-m). 9. Finish the procedure by reassembling the enclosure front panel (I), spark plug access cover (F), exhaust chamber (D) and enclosure lid (B).
Engine spark plugs are an important part of the engine ignition system. Worn or incorrectly adjusted spark plugs can negatively affect engine starting and operation. Therefore, it is important to inspect and regap, or replace the engine spark plugs as indicated in the service interval table. The listed steps are recommended to access and service the engine spark plugs.
Fig. G
1. To gain access to the spark plug on the rear side of the engine, some disassembly of the generator cabinet is required. Begin the disassembly by carefully removing the lid from the enclosure. First remove the ground strap by removing the screw holding it to the lid. Push in the hinge retaining stop (A), then slide the lid (B) to the left to free it from the rest of the enclosure as shown in Fig G. Set the lid aside on a soft surface to avoid scratching the paint. 2. Open the battery access panel by removing the 3 screws and rotating the panel outward (see Fig. E on page 28). 3. Remove the 2 screws (C) fastening the exhaust chamber to the rear engine firewall (see Fig H). Slide the exhaust chamber panel (D) upward to free it from the enclosure and carefully set it aside. 4. Locate and remove the screws (E) retaining the spark plug access cover (F). Remove the cover to gain access to the rear spark plug (G) as shown in Fig H. 5. Remove the enclosure inlet fasteners (H) and front panel (I) as indicated in Fig I to access the front engine spark plug (J). 6. Pull the spark plug boots loose, then clean any dirt from the area around the spark plugs. Remove the spark plugs with a 13/16" spark plug wrench. 7. Inspect the spark plugs for fouling or abnormal wear like excessively worn electrodes or cracked or chipped insulator material. If abnormal wear is indicated, replace the spark plugs. Fouled plugs indicate the need for engine service by a qualified engine service technician. New spark plugs or plugs that do not display any abnormal characteristics should be checked for proper gap using a suitable spark plug gauge. Adjust the gap to 0.012 - 0.016 inches (0.30 - 0.40 mm) by carefully bending the grounding electrode. 8. Reinstall the spark plugs by hand until they begin to seat to avoid cross-threading. After the plugs begin to seat, tighten used plugs an additional ¼ turn or 13/16" spark plug wrench to avoid damage to the
Fig. H
Fig. I
30 200-2341

Fig. GG
In some areas of the United States, a USDA Forest Service approved exhaust spark arrestor is legally required. This optional accessory is added to the generator during initial installation. To identify whether the generator is equipped with a spark arrestor, inspect the exhaust tailpipe opening for a screen. If a screen is present in the tailpipe, the spark arrestor option is installed.
Spark arrestors require periodic inspection and cleaning as indicated in the recommended service interval table on page 25. To maintain the spark arrestor, the following steps are recommended.
1. To gain access to the spark arrestor assembly inside the exhaust chamber, some disassembly of the generator cabinet is required. Begin the disassembly by carefully removing the lid from the enclosure. First push in the hinge retaining stop (A), then slide the lid (B) to the left to free it from the rest of the enclosure as shown in Fig GG. Set the lid aside on a soft surface to avoid scratching the lid paint. 2. Open the battery access panel by removing the 3 screws and rotating the panel outward (see Fig. E on page 28). 3. Remove the 2 screws (C) fastening the exhaust chamber panel (D) to the rear engine firewall (see Fig HH). Slide the exhaust chamber panel (D) upward to free it from the enclosure and carefully set it aside. 4. Remove the spark arrestor assembly by loosening the screw holding the arrestor to the muffler. 5. Use a low pressure stream of compressed air or water to blow particles from the spark arrestor screen. Ensure that all particles are completely flushed from the tailpipe. 6. Visually inspect the spark arrestor screen to for holes or breaks in the screen. If any are found, replace the spark arrestor assembly. 7. Reinstall the spark arrestor on the muffler outlet and replace the clamp. 8. Slide the exhaust chamber panel (D) back into place and install the screws (C) holding it to the rear engine firewall. 9. Slide the lid (B) back onto the hinges and reinstall the retaining clip to secure the lid place.
Fig. HH
200-2341 31

CAUTION
Proper cooling of the generator is vital to maintain performance and prevent equipment failure. Blocked cabinet openings or other airflow obstructions are potential fire hazards and can cause failures. Periodically inspect generator cabinet openings and the engine oil cooler for blockages. Do not allow leaves, grass, dirt, snow or other objects to build up around the cabinet. Keep plants and other landscaping groomed to allow a minimum of three (3) feet of open space around all sides of the generator. Do not place a cover over the generator.
Fig. K
The engine governor is set at the factory to maintain generator output frequency within specifications and is readjusted if required during installation. However, engine wear may cause frequency to vary as the generator accumulates hours. Periodic checking and adjustment of generator frequency by a qualified generator technician is recommended as outlined in the table on page 25. If speed adjustment is necessary, follow the listed procedure to set the correct engine speed.
32 200-2341

ADJUSTMENT
Over time, normal engine operation leads to wear in the engine valve train which decreases generator output. To restore generator output, it is necessary to check and adjust the engine valve lash at regular intervals throughout the life of the engine. However, proper valve lash adjustments require specialized training and tools. Adjustment by persons unfamiliar with the procedure can cause damage to the engine not covered under warranty. Contact an authorized generator dealer for assistance in locating qualified service personnel.
Avoid explosive and potentially lethal fuel leaks by inspecting the complete generator fuel supply system at intervals no greater than those listed in the Maintenance Table on page 25. Visually inspect all hoses for cracks, splits, or brittleness and replace hoses that show these or other signs of wear. Check all connections for tightness and cracks, replacing any broken fittings or clamps. Check all connections for leaks, while the generator is running, using approved equipment and methods. DO NOT use a flame to check for leaks.
200-2341 33

Engine starts then immediately shuts down
34 200-2341

Shutdown due to high engine temperature
pressure · 200-2341 35

Torque to 8.5 lbs-ft
Torque to 15 lbs-in
Torque to 16 lbs-ft
Torque to 17 lbs-ft
Torque to 20 lbs-ft
Item Part No Qty Description 1 N/A 9 Screw, 10-16 x .50” lg 2 N/A 9 Star washer, #10 3 N/A 2 Rivet 4 Not replaceable 1 Label, hot, stamped steel 5 115-0262 1 Cover, muffler (includes items 3, 4, 6 & 7) 6 094-0069 1 Insulation 7 094-0073 1 Insulation 8 N/A 2 Nut, 5/16-18 9 0056767 1 Clamp, saddle (includes (2) item #8) 10 019-0214 1 Exhaust manifold muffler, Honda 11 N/A 1 Nut, 1/4-20, Nylon stop 12 094-0093 1 Isolator, muffler bracket to panel 13 145-0418 1 Tail pipe 14 N/A 6 Lock washer, 5/16”
Item Part No Qty Description 15 N/A 2 Screw, m8 x 13 mm lg 16 N/A 4 Nut (see Honda manual) 17 094-0070 1 Insulation 18 094-0072 1 Insulation 19 094-0071 1 Insulation 20 115-0263 1 Muffler box (includes items 17, 18, 19 & 22) 21 N/A 1 Bolt, 1/4-20 x 1.25” lg 22 094-0094 1 Insulation
*N/A - These are standard parts available at your local hardware store.
36 200-2341

Torque to 15 lbs-in
Item Part No Qty Description 1 N/A 14 Screw, 10-16 x .50” lg 2 N/A 14 Star washer, #10 3 115-0264 1 Side panel, left side (includes item 16) 4 S115-0242 1 Prop arm, lid 5 S115-0240 1 Lid assembly, complete (see page 38 for separate parts) 6 115-0265 1 Panel, back (includes items 11 & . 19) 7 115-0266 1 Access panel, top portion (includes items 13, 14 & 17) 8 107-0061 2 Hinge, swivel 9 115-0267 1 Access panel, bottom portion (includes item 15 & 18) 10 S115-0218 1 Door assembly, (includes inner door panel) 11 094-0075 1 Insulation (not shown)
Item Part No Qty Description 12 103-0121 1 Clip, hood rod 13 098-2758 1 Warning label 14 094-0084 1 Insulation (not shown) 15 094-0076 1 Insulation (not shown) 16 094-0083 1 Insulation (not shown) 17 098-2856 1 Warning label 18 098-2759 1 Fuel label 19 094-0078 1 Insulation, exhaust top (not shown) Not shown 094-0108 1 Weather seal (3/16” h x 1/2” w x 12’ lg) Not shown 094-0107 1 Weather seal (1/8” h x 1/2” w x 12’ lg)
*N/A - These are standard parts available at your local hardware store.
200-2341 37

Torque to 7 lbs-ft
Torque to 15-20 lbs-in
Torque to 24 lbs-in
Item Part No Qty Description 1 0056765 1 Lock (includes 1A, 1B, 1C & 1D) 1A 146-0023 1 Key 1B Order item # 1 1 Washer 1C Order item #1 1 Bolt 1D Order item #1 1 Nut 2 0056761 1 Handle 3 S115-0251 1 Lid weldment (order S115-0240 for complete lid assembly) 4 N/A 2 Nut, 10-32 5 0056766 1 Lock, hooked pawl 6 114-0571 1 Bracket, lid stop 7 0058221 4 Screw, M5-.8 x 8MM 8 N/A 2 Nut, 1/4-20 Nylon stop
Item Part No Qty Description 9 026-0535 1 Ground strap, 17” lg 10 107-0062 2 Hinge (includes (4) item #7) 11 N/A 2 Rivet 12 094-0106 1 Weather seal (1/4 h x 3/4 w x 12’ lg) 13 094-0077 1 Insulation -- S115-0240 1 Lid assembly, complete (includes all of the items listed above)
*N/A- These are standard parts available at your local hardware store.
38 200-2341


Item Part No Qty Description 1 0056629 1 Discharge louvered cover 2 0056623 1 Engine adapter 3 160-0311 1 Rotor assembly 4 100-0003 2 Diode/varistor assembly 5 059-0348 1 Rotor bolt 6 160-0312 1 Stator assembly 7 166-0133 2 Capacitor, 40F, 500V 8 077-0168 1 Terminal box cover 9 098-2827 1 Warning label
Item Part No Qty Description 10 026-0515 1 Wiring harness, generator neutral 11 026-0514 1 Wiring harness, generator power -- 160-0309 1 Complete generator assembly

Torque to 8.5 lbs-ft
Torque to 15 lbs-in
Torque to 40 lbs-ft
For Oil Filter and Air Filter part numbers, see page 19 of this manual.
Item Part No Qty Description 1 094-0091 1 Insulation 2 115-0268 1 Panel, left side (includes item 1) 3 N/A 4 Screw, 10-32 x .50” lg 4 N/A 1 Bolt, 5/16 NC x 1.25” lg 5 N/A 1 Lock washer, 5/16” 6 N/A 1 Washer, 5/16” 7 160-0309 1 Generator assembly 8 N/A 4 Bolt, 3/8-16 x .75” lg 9 N/A 2 Bolt, 5/16 NC x 1.50” lg 10 N/A 2 Lock washer, 5/16” 11 025-0063 1 Engine, Honda, GX620 (muffler ... not incl. - see page 36 for details) or 025-0059 1 Engine, Honda, GX670 (muffler ... not incl. - see page 36 for details) 12 N/A 12 Lag screw, 5/16 x 2” lg w/washer 13 094-0074 1 Insulation 14 115-0269 1 Exhaust access panel (includes item 15) 15 094-0081 1 Insulation 16 094-0080 1 Insulation 17 115-0270 1 Back panel (includes items 13 & . 16) 18 115-0245 1 Engine panel assembly (see pages 41, 42 & 43 for details) 19 094-0095 2 Spacer 20 N/A 2 Screw, #10 x 1/2” sheet metal
Item Part No Qty Description 21 109-0100 1 Base, plastic 22 071-0031 1 Hose clamp 23 N/A 1 Screw, 10-14 x .63” lg 24 S108-0160 1 Engine pan 25 094-0068 3 Vibration isolator 26 115-0271 1 Crossbrace assembly (includes items 27, 28, 35, 35A & 36) 27 098-2828 1 Warning label 28 098-2821 1 Warning label 29 068-0084 1 Fitting, hose barb 1/8 x 3/8 30 012-0094 1 Hose, oil drain 31 012-0098 1 Hose clamp, .50-1.2 32 0057747 1 Fitting, barb 3/8 x 1/2 33 0057746 1 Valve ball, 3/8 M/F 34 063-0042 1 Adapter, oil drain 35 026-0309 1 Fuse holder 35A 026-0518 1 Fuse, type 3AG, 25 Amp 32V 36 026-0547 1 Relay DC, 12V, COIL 37 S0049224 1 Ground strap, 12GA, 5.50” lg
*N/A - These are standard parts available at your local hardware store.
Detail A · See detail A · 40 200-2341

Torque to 8.5 lbs-ft
Torque to 15 lbs-in
Item Part No Qty Description 1 094-0096 1 Insulation 2 N/A 6 Hose clamp, 23/32” I.D. 3 S012-0106 1 Hose, high temp oil, 3/8” x 26.5” lg 4 N/A 10 Nut, 1/4-20, Nylon stop 5 026-0338 1 GFCI Receptacle 6 See page 42 1 Control panel assy, CP200 7 N/A 2 Screw, 10-16 x .50” lg 8 094-0095 4 Spacer, .75 O.D. 9 N/A 4 Screw, 1/4-20 x .75” lg 10 S115-0238 1 Control box frame 11 115-0272 1 Panel, right hand (includes items 1 & 22) 12 N/A 2 Screw, 6-32 x .50” lg 13 026-0460 1 Terminal block, ground lug 14 026-0472 1 Terminal block 15 N/A 1 Screw, torx 8-32 x 1.25” lg 16 N/A 2 Screw, 8-32 x 1.25” lg 17 N/A 5 Nut, #8-32 (not shown - for items 15, 16 and 20) 18 N/A 1 Rectifier shipped with engine (Contact Honda Service Center) 19 N/A 2 Bolt, 1/4-20 x 1 20 N/A 1 Screw, 8-32 x .75” lg 21 026-0539 1 Terminal block, 2 row 20A 4-pole 22 098-2800 1 Warning label 23 N/A 1 Elbow, 1/2 NPT x 1/2 NPT
Item Part No Qty Description 24 019-0211 1 Regulator assy, GX670 (PM401211) or 019-0213 1 Regulator assy, GX620 (PM400911) 25 N/A 2 Bolt, 1/4-20 x 1.75” lg 26 0057079 1 Oil cooler 27 N/A 4 Bolt, 1/4-20 x .63” lg 28 S114-0564 1 Bracket, oil cooler 29 Order S012-0106 1 Hose, high temp oil, 3/8” x 3” lg 30 069-0022 1 Tee, adapter oil temp 31 Order S012-0106 1 Hose, high temp oil, 3/8” x 13” lg 32 034-0162 1 Switch, oil temp 33 051-0091 2 Bushing, snap .875 ID 34 093-0053 1 Rubber grommet 35 026-0512 1 Wire harness, engine control 36 012-0120 1 Vapor hose assembly 37 026-0516 1 Wire harness, terminal block power 38 093-0054 1 Fuel grommet, .84 ID x 1.875 OD 39 N/A 1 Nipple, 3” lg, 1/2 NPT 40 098-2826 1 Warning label 41 026-0309 1 Fuse holder 42 N/A 1 Fuse, 5A Type 3AG 43 098-2850 1 Fuse label
*N/A - These are standard parts available at your local hardware . store.
200-2341 41

Torque to 10 lbs-in
Torque to 15 lbs-in
Item Part No Qty Description 1 N/A 2 Screw #8-32 x .75 phillips hd 2 034-0161 1 Switch, toggle 3 032-0067 1 Hourmeter, 120V AC 60HZ 4 (see #8) 1 Not available separately 5 N/A 4 Screw, 6-32 x .38”lg 6 N/A 4 Lock washer #6 7 115-0273 1 Control box top (includes item 14) 8 0056884 1 Switch, momentary 9 060-0175 4 Standoff, 6-32 x .75”lg 10 026-0534 1 Controller board, CP200 11 N/A 4 Nut #6-32, Nylon stop
Item Part No Qty Description 12 002-0060 1 Circuit breaker, 50 Amp, 120/240V (PM401211) or 002-0061 1 Circuit breaker, 45 Amp, 120/240V (PM400911) 13 0058069 1 Circuit breaker mount 14 098-2820 1 Control panel label, CP200 15 026-0537 1 Wire harness
*N/A - These are standard parts available at your local hardware store.
42 200-2341

Torque to 7 lbs-ft
Torque to 8.5 lbs-ft
Item Part No Qty Description 1 N/A 2 Nut, 1/4-20 2 S114-0563 1 Bracket, battery hold down 3 026-0480 1 Battery cable, positive 4 026-0481 1 Battery cable, negative 5 N/A 1 Battery, BCI Group 26 or 26R 6 059-0344 2 J-bolt, 1/4-20 7 S115-0229 1 Battery shelf 8 0057024 4 Battery standoff, rubber 9 N/A 2 Bolt, 1/4-20 x .625” lg 10 N/A 2 Screw, 1/4-20 x 1” lg 11 026-0696 1 Battery charger 11A N/A 1 Fuse, type 3AG, 25 Amp, 32V 12 N/A 2 Nut, nylon stop 1/4-20 13 N/A 2 Nut, 1/4-20 nyloc
*N/A - These are standard parts available at your local hardware store.
200-2341 43





3-Year or 1500 Hour Limited Warranty
Your Coleman PowerStation™ emergency back up power system generator has been manufactured to stringent guidelines & standards for years of dependable operation & service. Coleman Powermate warrants this product to the original consumer against defects in material and workmanship for a period of 3-Years or 1500 hours, whichever occurs first, from the date of purchase and is not transferable.
Coverage: Replacement parts & labor, including travel time & mileage, for defects in product found to be properly installed, maintained & operated in accordance with Coleman Powermate & supplied component operator's manuals are eligible for warranty coverage. A Coleman Powermate Authorized Master Representative, their dealer or their agent must perform warranty service. Items not covered under the warranty are:
 Normal engine wear, tune-ups, and routine service.  Damage caused by shipping, accidents, improper installation or handling, improper storage, or repairs not performed by a Coleman Powermate authorized Master Representative, their dealer or their agent.  Damage caused by operation with improper fuel or at speeds, loads, conditions, modifications, or installation contrary to published specifications or recommendations.  Damage caused by negligent maintenance such as: - Failing to provide the specified type and sufficient quantity of
 Parts purchased for a replacement of a failed Coleman Powermate part with a non-Coleman Powermate part voids warranty on that part.  Fuel injection pumps not repaired locally by an authorized servicing dealer.  Non-Coleman Powermate-authorized repair shop labor without prior approval from Coleman Powermate Warranty Department.  Engine fluids such as fuel, oil, or coolant/antifreeze.  Expenses incurred investigating performance complaints unless defective Coleman Powermate materials or workmanship is the cause of the problem.  Maintenance items such as fuses lamps, filters, spark plugs and adjustments.  Sales outside the U.S. or Canada  Telephone charges or transportation charges in connection with the repair of defective parts.  Overtime labor charges incurred at the request of owner unless prior approval is obtained by Coleman Powermate.  Air freight charges or shipping charges outside of Coleman Powermate shipping practices  Any other expense including consequential damages, incidental damages, or incidental expenses, including damage to property. Some states do not allow the exclusion or limitation of incidental damages, so the limitation may not apply to you.
lubricating oil. - Failing to keep the air intake and cooling areas clean. - Failing to service the air cleaner. - Failing to provide sufficient coolant. - Failing to perform scheduled maintenance as recommended
by Coleman Powermate or by supplied component manufacturers. - Failing to regularly exercise the generator set. Â Original installation charges and startup costs. Â Starting batteries, travel & labor associated with battery failure. Â Rental of equipment during performance of warranty repairs. Â Engines, or other components, which are covered exclusively by the warranty of their manufacturer. Â Altered, tampered or improperly maintained emission control system components.
Implied Warranties: Any implied warranties, including the Implied Warranties of Merchantability and Fitness For A Particular Purpose, are limited in duration to 3-Years or 1500 Hours from the date of consumer purchase. Some states do not allow limitations on how long an implied warranty lasts, so the limitation may or may not apply to you.
How To Obtain Warranty Performance: Replacement parts & service are available from Coleman Powermate's Master Representative service network. Locate the nearest service location by calling 1-800-445-1805, or write: Coleman Powermate Inc., 4970 Airport Road, PO Box 6001, Kearney NE 68848.
To the extent any provision of this warranty is prohibited by federal, state, or municipal law, and cannot be preempted, it shall not be applicable. This warranty gives you specific rights, and you may have other rights which may vary from state to state.
Coleman® is a registered trademark of the Coleman Company, Inc. used under license. © 2001 Coleman Powermate, Inc.
46 200-2341

1-800-445-1805 to obtain warranty service information or to order replacement parts or accessories.
HOW TO ORDER REPLACEMENT PARTS Even quality built equipment such as the Coleman Powermate standby generator you have purchased, might need occasional replacement parts to maintain it in good condition over the
years. To order replacement parts, please give the following information:
des informations sur le service de garantie ou pour commander des pièces ou des accessoires.
COMMENT COMMANDER DES PIÈCES DE RECHANGE Même l'équipement de première qualité, comme la génératrice de réserve Coleman Powermate que
vous avez achetée, peut nécessiter occasionnellement des pièces de rechange pour demeurer en
parfait état de marche au fil des années. Pour commander des pièces, veuillez indiquer les
renseignements suivants :
POWERMATE EN EL TELÉFONO
1-800-445-1805 para obtener información sobre servicios de garantía o para pedir piezas de repuesto o
accesorios.
CÓMO PEDIR PIEZAS DE REPUESTO Incluso los equipos de calidad como el generador de emergencia Coleman Powermate que ha comprado necesitan ocasionalmente piezas de repuesto para mantenerlos en buenas condiciones a
través de los años. Para pedir piezas de repuesto, sírvase entregar la información siguiente:
Coleman Powermate, Inc.
1-800-445-1805 1-308-237-2181 Fax 1-308-234-4187
200-2341 47


200-2341
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Fig. D NER COVER ER ELEMENT PAP E FILTE S ER | p.28 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.