Line Interactive UPS 325A/425A/525A/625A
Line Interactive Network UPS 425AP/525AP/625AP
USER‘S MANUAL

This manual provides safety, installation and operating instructions that will help you derive the fullest performance and service life that the UPS has to offer.
It includes important instructions for the safe use of this UPS and for obtaining factory service should the proper operation of the UPS come into question.
The UPS‘s shipping materials were designing with great care to provide protection from transportation related damage. These materials are invaluable if you ever have to return the UPS for service. Damage sustained during transit is not covered under the warranty.



The product is line interactive UPS with the newest technology and powerful function. The LINE INTERACTIVE ups is with AVR function allows input voltage range from 75% to 125%, including on line voltage boost-up & buck down. An ideal protection equipment for critical connected loads. It is based on microprocessor controls, with utility power connected, the charging is ongoing, no need to switch ON the UPS and at back-up mode, UPS can be automatically turned OFF if none of the connected loads is operating to save the battery energy. The indicator will be ON when battery needs replacement and a cyclic self-testing function is included in order to verify both the operation of the UPS and the condition of the battery.
In addition, This UPS provides advanced single telephone line or modem surge suppression through the modular connectors on the back panel.
The LINE INTERACTIVE UPS and UPSMON monitoring software (optional kits) makes your computer operate intelligent and provides you with the ability of perfect protection of your critical devices.


3.1 "REPLACE BATTERY" indicator (RED LED) The LED illuminates when the UPS's battery is no longer useful and must be replaced.
3.2 "BACK UP" indicator (YELLOW LED) The LED illuminates when the UPS is supplying battery power to the loads.
3.3 "LINE NORMAL" indicator (GREEN LED) The LED illuminates when the line input voltage is normal.
3.4 "ON/OFF/TEST/SILENCE" button Press the button more than 3 seconds to turn the UPS on or off, press the button less than 1 second to activate the UPS's self-testing or silence the back up alarm.


3.5 COMPUTER INTERFACE (425AP/525AP/625AP models only) Provide both RS-232 and relay signal to support NOVELL, UNIX, DOS, WINDOWS and other operating systems.
3.7 AC INPUT POWER RECEPTACLE
3.8 TEL./MODEM SURGE PROTECTION (425AP/525AP/625AP models only) Surge protection for telephone and modem line to have the complete safety connection for INTERNET service.

4.0 Inspection Inspect the UPS upon receipt. The packaging is recyclable; save it for reuse or dispose of it properly.
4.1 Placement Install the UPS in a protected area with adequate air flow and free of excessive dust. Do not operate the UPS where the temperature and humidity is outside the specified limits.
4.2 Connect Computer Interface (425AP/525AP/625AP models only) UPSMON (or other power management software) and an interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9 pin computer interface port on the back panel of the UPS. Note: Computer interface connection is optional. The UPS works properly without a computer interface connection.
4.3 Connect to Utility Connect the AC input power connector to utility power to power up the UPS.
4.4 Charge the battery The UPS charges its battery whenever it is connected to utility power. For best results, charge the battery for 4 hours in the initial use.


4.5 Connect the loads Plug the loads into the output connectors on the rear of the UPS. To use the UPS as a master on/off switch, make sure all of the loads are switched on. Caution: Never connect a laser printer or plotter to the UPS with other computer equipment. A laser printer or plotter periodically draws significantly more power than when idle, and may overload the UPS. 4.6 Connect the telephone/modem lines (425AP/525AP/625AP models only) Connect a single line telephone or a modem line into the telephone/modem surge protection sockets on the back of the UPS. The RJ-45/RJ-11 modular sockets accept standard single line telephone connections. This connection will require another length of telephone cable (supplied).

5.1 Switch on With the UPS plugged in, press and hold the on/off/test/silence button more than 1 second until "LINE NORMAL" LED lit to switch the ups on. The UPS will perform self-testing each time when it is switched on.
5.2 Switch off By pressing and hold the on/off/test/silence button more than 3 seconds until the "LINE NORMAL" or "BACK UP" LED off.
5.3 SELF-TEST Use the self-test to verify both the operation of the UPS and the condition of the battery. In normal utility power, push the on/off/test/silence button less than 1 second and UPS performs a self-test function. During the self-test, the UPS operates a back up mode.
Note: During the self-test, the UPS briefly operates the loads on-battery (the on-battery LED comes on). If the UPS passes the self-test, it returns to on-line operation. The on- battery LED does off and the on-line LED goes on steady. If the UPS fails the self-test it immediately returns to on-line operation and lights the replace battery LED. The loads are not affected. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, ask our nearest dealer to replace battery.
5.4 SILENCE In "BACK UP" mode, push on/off/test/silence less than 1 second to silence the audible alarm. (The function is void when under condition of "LOW BATTERY" or "OVERLOAD")

6.1 "BACK UP" (slow alarm) When in BACK UP mode, the YELLOW LED illuminates and the UPS sounds an audible alarm. The alarm stops when the UPS returns to LINE NORMAL operation. Press the on/off/test/silence button during on-battery alarms to stop the beeping.
6.2 "LOW BATTERY" (rapid alarm) In BACK UP mode, when the battery energy runs low, the UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to LINE NORMAL operation.
6.3 "OVERLOAD" (continuous alarm) When the UPS is overloaded (the connected loads exceed the maximum rated capacity) the UPS emits continuous alarm to warn a overload condition. Disconnect nonessential load equipment from UPS to eliminate the overload.

7.1 UPSMON Software The UPSMON software is applied standard RS-232 interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, UPSMON displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, Battery level and so on..
The software is available for DOS, Windows 3.1x, Windows 95 & Windows NT V3.5 or later.
7.2 Interface Kits A series of interface kits is available for operation systems that provide UPS monitoring. Each interface kit includes the special interface cable required to convert status signals from the UPS into signals which individual operating system recognize. The interface cable at UPS side must be connected to REMOTE PORT , at computer side can be either COM 1 or COM 2. The other installation instructions and powerful features please refer to READ.ME file.

The computer interface port has the following characteristics:




PROBLEM POSSIBLE CAUSE ACTION TO TAKE On/off/test/silence button not pushed or push too short
Battery voltage less than 10V Recharge the ups at least 4 hours
Power cord lose Replug the power cord AC FUSE burn out Replace the AC fuse Line voltage too high, too low or black out
PCB failure Replace PCB, call for service battery not fully charged Recharge the UPS at least 4 hours Back up time too short PCB failure Replace PCB, call for service Buzzer continuous beeping
RED LED light Battery failure Replace battery, call for service

10.1 Storage conditions Store the UPS covered and upright in a cool , dry location, with its battery fully charged. Before storing, charger the UPS for at least 4 hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessary draining the battery.
10.2 Extended storage During extended storage in environments where the ambient temperature is -15 to +30 ℃ (+5 to +86 ℉), charge the UPS‘s battery every 6 months. During extended storage in environments where the ambient temperature is +30 to +45 ℃ (+86 to +113 ℉), charge the UPS‘s battery every 3 months.
MODEL 325A 425A(P) 525A(P) 625A(P) Capacity 325VA 425VA 525VA 625VA Voltage 100V, 110V, 120V, 220V, 232V, 240V, +/-25% INPUT
Frequency 50 or 60Hz +/-5% (auto sensing) Voltage (on battery)
Simulated sine wave at Line Input +/-5%
50 or 60Hz +/-0.5%
AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output voltage
13% below input voltage if+9% to 25% of nominal
Transfer Time 2/4 milliseconds, including detection time Spike Protection 320 joules, 2ms
EMI/RFI filter 10dB at15MHz, 50dB at 30MHz (for xxxAP models only) Overload Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
60 second and 130% at 3 seconds. Unit Input Fuse for overload & short circuit protection 10Baase-T Cable Port
Network (UTP, RJ-45) compatible jacks
(for xxxAp models only)
Short Circuit UPS output cut off immediately or input fuse protection BATTERY Type Sealed, maintenance-free lead acid
Frequency (on battery) · Voltage Regulation AVR · and FILTERING


indicator Back up Time 10 - 30 minutes (depending on computer load) Net Weight
6,000 meters max. elevation, 0-95% humidity non-condensing 0-48 deg C Audible noise
©1997 Powercom Co., Ltd. All right Reserved. All trademarks are property of their respective owners. Specifications subject to change without notice.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS not on LED not light | On/off/test/silence button not pushed or push too short | Press the on/off/test/silence button more than 1 second | p.15 |
| UPS not on LED not light | Battery voltage less than 10V | Recharge the ups at least 4 hours | p.15 |
| UPS not on LED not light | PCB failure | Replace the PCB, call for service | p.15 |
| UPS not on LED not light | Load less than 20W at battery mode | Normal condition | p.15 |
| UPS always at battery mode | Power cord lose | Replug the power cord | p.15 |
| UPS always at battery mode | AC FUSE burn out | Replace the AC fuse | p.15 |
| UPS always at battery mode | Line voltage too high, too low or black out | Normal condition | p.15 |
| UPS always at battery mode | PCB failure | Replace PCB, call for service | p.15 |
| Back up time too short | battery not fully charged | Recharge the UPS at least 4 hours | p.15 |
| Back up time too short | PCB failure | Replace PCB, call for service | p.15 |
| Buzzer continuous beeping | Overload | Remove the noncritical loads | p.15 |
| RED LED light | Battery failure | Replace battery, call for service | p.15 |