12.5. Cross Flow Fan and Indoor Fan Motor Removal
10 Installation And Servicing Air Conditioner Using R410A 52
© 2003 Matsushita Industrial Corp. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.






Indoor Fan Speed Selection FAN SPEED
Operation OFF / ON
Operation Mode Selection
Room Temperature Setting
TIMER
ON
Powerful Mode Operation
OFF
∧ ∨
Time / Timer Setting
Ion Mode Operation
CANCEL
Timer Operation Set / Cancel
AIR SWING
CLOCK
Clock Setting
Check Point
Illuminable · buttons


Five Operation Modes
Automatic and 5 Manual Vertical Airflow Directions
Automatic and 5 Manual Horizontal Airflow Directions
Powerful Mode
Operation Indication Lamps (LED)
Mode Operation. Blinks in Ionizer error. • POWER (Green) Lights up in operation,
Automatic Restart Control
Mode Operation. • TIMER (Orange) Lights up in Timer
Setting. Blinks in Self Diagnosis Control.



Cooling Capacity kW kcal/h BTU/h
5.30 (0.90 - 6.00) 4,560 (770 - 5,160) 18,100 (3,070 - 20,500)
Heating Capacity kW kcal/h BTU/h
6.60 (0.90 - 8.00) 5,680 (770 - 6,880) 22,500 (3,070 - 27,300)
Moisture Removal l/h Pint/h
2.9 (6.1)
TOP VIEW


Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 12.5 (440) — Heating; 13.9 (490)
Indoor Air (Me) m3/min (cfm) Cooling; 14.0 (490) — Heating; 15.5 (540)
Indoor Air (Hi) m3/min (cfm) Cooling; 15.6 (550) 40.0 (1,410) Heating; 17.1 (600)
dB (A) Cooling; High 44, Low 37 Cooling; 47 Heating; High 44, Low 37 Heating; 47 Noise Level
Power level dB Cooling; High 57 Cooling; High 60 Heating; High 57 Heating; High 60
Electrical Data Input Power W Cooling; 1,650 (240 - 2,050) Heating; 1,790 (280 - 2,650)
Running Current A Cooling; 7.4 Heating; 8.0
EER W/W Cooling; 3.21 (3.75 - 2.93) BTU/hW Cooling; 11.0 (12.8 - 10.0) COP W/W Heating; 3.69 (3.21 - 3.02) BTU/hW Heating; 12.6 (11.0 - 10.3) Starting Current A 8.0 Piping Connection Port (Flare piping)
G ; Half Union 1/2”
G ; 3-way valve 1/2”
L ; Half Union 1/4”
L ; 2-way valve 1/4”


Cooling Capacity kW kcal/h BTU/h
6.30 (0.90 - 7.10) 5,420 (770 - 6,110) 21,500 (3,070 - 24,200)
Heating Capacity kW kcal/h BTU/h
7.20 (0.90 - 8.50) 6,190 (770 - 7,310) 24,600 (3,070 - 29,000)
Moisture Removal l/h Pint/h
3.5 (7.4)
TOP VIEW


Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 12.6 (440) — Heating; 14.0 (490)
Indoor Air (Me) m3/min (cfm) Cooling; 14.5 (510) — Heating; 15.8 (560)
Indoor Air (Hi) m3/min (cfm) Cooling; 16.6 (590) Cooling; 42.8 (1,510) Heating; 17.7 (620) Heating; 41.5 (1,460)
dB (A) Cooling; High 45, Low 37 Cooling; 48 Heating; High 45, Low 37 Heating; 49 Noise Level
Power level dB Cooling; High 58 Cooling; High 61 Heating; High 58 Heating; High 62
Electrical Data Input Power W Cooling; 2,210 (240 - 2,540) Heating; 2,100 (280 - 2,750)
Running Current A Cooling; 9.9 Heating; 9.4
EER W/W Cooling; 2.85 (3.75 - 2.80) BTU/hW Cooling; 9.7 (12.8 - 9.5) COP W/W Heating; 3.43 (3.21 - 3.09) BTU/hW Heating; 11.7 (11.0 - 10.5) Starting Current A 9.4 Piping Connection Port (Flare piping)
G ; Half Union 1/2”
G ; 3-way valve 1/2”
L ; 2-way valve 1/4” Pipe Size (Flare piping)
L ; Half Union 1/4”
G (gas side) ; 1/2” L (liquid side) ; 1/4”
G (gas side) ; 1/2” L (liquid side) ; 1/4”












8.1. BASIC FUNCTION
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air temperature.
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes. These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.



Mode: Fan Speed: Temperature Shift (°C) Cooling Lo -0.25 Me-, Me, Me+, Auto 0.00 Hi +0.25 Soft Dry All +0.25 Heating Lo +1.50 Me-, Me, Me+, Auto +0.75 Hi +0.75
Mode within 60 Minutes from Start-up: Temperature Shift (°C) Cooling/Soft Dry -1.0 Heating +2.0

Intake Air Temperature - Internal Setting Temperature (°C) Freq. H Zone Cooling & Soft Dry Heating Cooling Soft Dry Heating Remark 1 -2.0 1.5 1 1 1 2 -1.5 1.0 1 1 1 3 -1.0 0.5 14 8 11 4 -0.5 0.0 20 8 15 5 0.0 -0.5 27 8 22 6 0.5 -1.0 35 11 27 7 1.0 -1.5 43 11 36 8 1.5 -2.0 46 11 39 Fc, Fh 9 2.0 -2.5 46 11 39 Fc, Fh 10 2.5 -3.0 46 11 39 Fc, Fh 11 Nil -3.5 Nil Nil 39 Fh 12 Nil -4.0 Nil Nil 39 Fh
Operating Frequency Calculation Formula:
CompHz = Freq. A × Freq. H + Freq. C
Cooling & Soft Dry E18CK E21CK Freq. A Freq. C Freq. A Freq. C Low Load (Freq. H
Example Calculation:
Heating E18CK E21CK Freq. A Freq. C Freq. A Freq. C Low Load (Freq. H
Model No.: E18CK
When Intake Air Temperature - Internal setting Temperature: 1.5°C
Freq. Range E18CK E21CK Cooling Fc 72 96 Operation Range 12 ~ 86 12 ~ 102 Heating Fh 86 92 Operation Range 14 ~ 128 14 ~ 128
CompHz = Freq. A × Freq. H + Freq. C = 1.53 × 46 + 2.5 = 72 Hz (It cuts down less than a decimal point)
Remarks:
When Freq. H is equal to 46 (Cooling), 39 (Heating) or above, the Comp. may run at the freq. higher than Fc or Fh up to max. freq. operation.
Every 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc (46), Fh (39).
8.1.3.1. Thermostat control
point +0.5°C.

Best Amenity Control

8.1.4.1. Thermostat control
point.

8.1.5.1. Thermostat control
point -0.5°C.

This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.


Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the above operation mode chart, every 30 minutes.
Remote Control Setting Temperature (°C) T1 T2 T3 16 ~ 18 +10 +8 -5 19 ~ 22 +8 +7 -7 23 ~ 26 +7 +6 -7 27 ~ 30 +6 +5 -8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice verse.
Operation Mode change from Temperature shifts (°C) Cooling/Soft Dry →Heating -2 Heating →Cooling/Soft Dry +2
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made.

A. Basic Rotation Speed (rpm)
Remote Control — O — — — Tab (rpm) SHI Hi Me+ Me Me- Lo Lo- SLo SSLo E18CK 1530 1440 1360 1290 1220 1150 850 760 630 E21CK 1610 1520 1420 1330 1240 1150 890 800 630
Remote Control — O — — — Tab (rpm) SSHI SHi Me+ Me Me- Lo Lo- SLo SSLo E18CK 1590 1560 1480 1410 1340 1270 850 400 300 E21CK 1640 1610 1520 1440 1350 1270 890 400 300
[Cooling, Dry, Fan] · [Heating]

B. Indoor Fan Control
i. Indoor fan control operation outline



ii. Auto Fan Speed


a. UP:
b. DOWN:
c. Current Output Fixed:
d. Instantaneous Maximum:
e. Temperature in ( ) is for Powerful Mode operation.

iii. Max Capacity Condition
a) During Cooling operation, if all to the following condition is fulfilled, the indoor fan speed is set to Shi.
24°C.
30°C.
within 30 minutes.
* If any of above conditions is not valid, the condition is ended.
b) During Heating operation, if all to the following condition is fulfilled, the indoor fan speed is set to SSHi.
2 hours.
* If any of above conditions is not valid, the condition is ended.
C. Fan Motor Control
i. Motor specification
High voltage PWM Motor
ii. Feedback Control
Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed.
iii. Abnormal Detection
iv. Restart Prohibition Control
Prohibit to restart within 5s after fan stop. (except when power is ON)

D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON 1 →2 →3 (Shift to 4 when COMP is OFF) * When COMP is OFF 4 →5 →4 ←→5 (Shift to 1 when COMP is ON) * Start from 4 if the Thermostat is OFF during the start operation.
Odor Status 1 2 3 4 5 4 5 4.5.4... 1 Status Shift according to COMP
zone 40 50 — 20 90 20 90 to time (s) Dry zone ON
OFF
SLo OFF Dry zone OFF SLo OFF

Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.



and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Operation Mode Airflow Direction Vane Angle (°) 1 2 3 4 5 Heating Auto with Heat Exchanger 17 Temperature 58 7 Manual 7 17 33 49 67 Cooling, Soft Dry and Fan, Ion Auto 7 ~ 37 Manual 7 17 25 33 41 Mode Judgment in Auto Auto 7 Manual 7 17 25 33 41
Basic Rotation Speed · Vertical Airflow

above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below. When the air conditioner is stopped using remote control, the vane will shift to close position.
positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
Operation Mode Vane Angle (°) Heating, with heat exchanger temperature A 55 ~ 125 B 90 Cooling, Soft Dry and Fan, Ion 55 ~ 125

positions of the vane are as Figure 2 above.
Pattern 1 2 3 4 5 Airflow Direction Patterns at Remote Control
Vane Angle (°) 90 55 70 110 125
Horizontal Airflow

A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
Quiet LED illuminates.
b. Quiet operation stop condition
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. When change mode to fan only mode.
e. Quiet button is pressed again.
D. Control contents
This is to reduce sound of Hi, Me, Lo for 3dB.
Automatic Fan Speed (Dry operation)

Manual Fan Speed (Dry operation)


A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
Quiet LED illuminates.
b. Quiet operation stop condition
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. When change mode to fan only mode.
e. Quiet button is pressed again.
C. Control contents
a. Fan Speed manual
This is to reduce sound of Hi, Me, Lo for 3dB.
-100 rpm reduce from normal Heating Auto Fan Speed
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
Lo · Lo · maintain RPM

When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.

(b) Soft Dry Operation


Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time.
Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.

Delay OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
(a) Cooling Operation · (c) Heating Operation

minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.

LED POWER MONITOR POWER QUIET TIMER POWERFUL ION Color Green Green Orange Orange Orange Green Light ON Compressor ON Operation ON Quiet Mode ON Timer Setting ON Powerful Mode ON Ion Mode ON Light OFF Compressor OFF Operation OFF Quiet Mode OFF Timer Setting OFF Powerful Mode OFF Ion Mode OFF
judgment, or delay ON timer sampling.
Power Monitor LED Control Frequency
Lighting of 3 LED base on instructed running frequency from indoor unit to compressor at cool, dry & heating operation.
Cool, Dry Instructed Hz No
Heat Instructed Hz No

changed to different controlling setting (4 type of transmission codes).
receiving sound can be cancelled or turned on.

Power relay will turn on during operation or in progress of stopping operation. Although operation stops, the power relay continues on for three minutes.
However, during instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 2 minutes after power recover and the unit will operate as previous operation condition.
To provide fresh air effect to users by discharging minus ion to air.

a. Ionizer Only Operation.
Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1 →2)
However, fan speed can be adjusted later by customer during this operation.

Airflow direction (Horizontal Vane) control:
Follow vane direction control at cooling mode.
Horizontal vane can be changed by customer during ion only operation.
b. Operation Mode + Ionizer Operation.
When air conditioner unit is in “ON” condition (Heat, Cool, Dry, Fan, Auto mode) and ION operation button at remote control is pressed. Ionizer on & ION LED illuminates. (3 →4)
Power LED also illuminates.
When one of the following condition is satisfied, ION operation stops.
a. Stopped by ON/OFF switch.
b. Timer OFF activates.
c. ION operation button is pressed again.
d. ION feedback signal shows error.
Purpose · Control Condition

without ionizer operation.
c. Timer during ionizer operation
Refer to case study in next page for detail.
i. Purpose
To inform user of ionizer problems and detection.
ii. Two types of problem detection control:
Control Detection Method Protection Recovery
(i) Actual ion is permanently OFF & ion
(i) Press ON/OFF button
30 min. continuously for 24 times (approx. 11 hr. 30 min.)
LED is blinking.
(ii) ion feedback signal:
0V (ii) Within 24 counts, if anytime
(ii) Press remote control ion button for
CONDITION becomes false then count is cleared.
a) ON: Ion LED blink & buzzer = beep b) OFF: Ion LED OFF & buzzer = beep
Off by force operation
Case 1: During Air-Con. ON. Air-Cond OFF with abnormal no. H26 is activated with timer LED is blinking permanently.
(i) Actual ion OFF
CONDITION becomes false.
Case 2: During Air-Con. OFF. Abnormal no. H26 is activated with timer LED is blinking permanently for both cases 1 & 2.
(ii) Once recovered, ion &
Timer LED stops blinking permanently. (ii) Press remote control ion button for
(iii) Main power reset.
(iii) Press any remote control button to


8.2.1.1. Time Delay Safety Control
decreased.
E21CK E18CK Operation Mode X (A) Y (A) X (A) Y (A) Cooling/Soft Dry (A) 11.0 15.0 8.8 15.0 Cooling/Soft Dry (B) 9.6 15.0 7.7 15.0 Heating 11.5 17.0 10.8 17.0


A. Overheating Prevention Control
B. DC Peak Current Control
after three minutes.
minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
Instructed frequency for compressor operation will be regulated by compressor top temperature. The changes of frequency are as below figure.

Conditions E18CK E21CK Cooling/Soft Dry Heating Cooling/Soft Dry Heating 1. Compressor frequency (Hz)
93 2. Outdoor total running current (A)
1.5 3. Indoor heat exchanger temperature (°C)

a. Total Current is below 0.74 ~ 0.94 Amp.
b. Operating Frequency is 72 Hz (E18CK), 95 Hz (E21CK) +1 and above.
c. Continuously for 20s.
a. Abnormal signal transmitted to indoor unit after 3 minutes outdoor power is supplied. (Indoor unit stop)
Starting condition, (1) is not fulfilled.
When the compressor operate at frequency lower than 22 Hz for 240 minutes, the operation frequency will be increased to 22 Hz for two minutes.
When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz.
28 Outdoor air (°C) T
24 Indoor heat exchanger (°C) T
30 T
8.2.1.10. Minimum Frequency Protection Control
Indoor Fan Speed Above Hi minHz = 21 Above Me- minHz = 21 Less than Me- minHz = 18 Auto minHz = 16
However, when less than thermo OFF for 120 sec. continuously, the above control will be cancel.
Indoor Fan Speed Above Hi minHz = 30 Above Lo minHz = 25 Less than Lo minHz = 15
However, when less than thermo OFF for 100 sec. continuously, the above control will be cancel.

8.2.2.1. Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.

i. Pipe temperature limitation/restriction

ii. Electrical part temperature rise protection control
Outdoor fan speed (switch to zone A and B minimum fan speed).
Outdoor total current (zone C) higher than the specified.



than Me.

Horizontal vane shift to 2nd position and Vertical vane shift to center position.
a) Control 1 · b) Control 2

8.2.3.1. Anti Cold Draft Control
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown below.



a. UP:
b. DOWN:
c. Current Output Fixed:
d. Instantaneous Maximum:
e. Temperature in ( ) is for Powerful Mode operation.
Compressor will operate at maximum of 128 Hz respectively if either one of the below conditions occur:
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This control will begin one minute after the compressor starts.


The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.



A. Deice operation (Normal Deice Operation)
Outdoor heat exchanger temperature sensor, timer.

a. During deice operation, the relationship between outdoor pipe temperature and time T1 is such operation will
proceed to next stage.
b. The deice will be performed only after 1 hour from when the operation has started.
c. When Comp. OFF by the sequence No. 1, 6, 7 compressor can restart back without 3 minutes waits (immediate
restart).

Outdoor heat exchanger temperature
a 15°C b 18°C c 25°C

When any of below a, b, c, d condition is satisfied, deice signal is produced.
a. Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature
-5°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
b. Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature < -
6°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
c. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -
7°C and outdoor air temperature
-3°C for 3 minutes and Comp. is ON.
d. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -
8°C for 3 minutes and outdoor air temperature < -3°C and Comp. is ON.
However, the first deice will start only after minimum of 60 minutes in operation.
(2nd deice and onward shall follow above conditions)
B. Auto clean deice
To improve heating start-up operation by detecting the residual ice on OD heat exchanger and perform deice operation automatically before operation is started by ON Timer.
1). Auto deice is performed 15 min. before standby operation (pre-deice operation in 15 min.).
2). When below deice conditions are fulfilled, auto clean deice operation will start.
3). After auto clean deice is completed, standby operation is performed as per load.
4). When deice conditions are not fulfilled, auto clean deice will not happen and will continue with standby operation.

OD air temp. t
0°C.
OD heat exchanger temp.
0°C for 14 min.
OD heat exchanger temp.
-8°C for 10 min.

Similar to deice operation 2 except for frequency values.
a. Detection methods
Outdoor heat exchanger temp. sensor, timer, indoor air temp. sensor.
b. Deice operation control time chart.


operation.

Outdoor heat exchanger pipe temperature
a 15°C b 18°C c 25°C






or Set time Confirm OFF or Set time Confirm ON & OFF Timer Timer Timer








Do NOT pull out the plug by the cable
Do NOT insert finger or other objects into the unit! —> especially dangerous for children!



10.1. OUTLINE
Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction. The R22 refrigerant which has conventionally been used in ACs is an HCFC refrigerant and, therefore, possesses this ozone- destroying potential. International regulations (the Montreal Protocol Ozone-Damaging Substances) and the domestic laws of various countries call for the early substitution of R22 by a refrigerant which will not harm the ozone layer.
of R410A is approximately 1.6 times as high at the same refrigerant temperature, but the energy efficiency is about the same. Consisting of hydrogen (H), fluorine (F) and carbon (C), R410A is an HFC refrigerant. Another typical HFC refrigerant is R407C. While the energy efficiency of R407C is some what inferior to that of R410A, it offers the advantage of having pressure characteristics which are about the same as those of R22, and is used mainly in packaged ACs.
a. Chemical characteristics
The chemical characteristics of R410A are similar to those of R22 in that both are chemically stable, non-flammable refrigerants with low toxicity. However, just like R22, the specific gravity of R410A gas is heavier than that of air. Because of this, it can cause an oxygen deficiency if it leaks into a closed room since it collects in the lower area of the room. It also generates toxic gas when it is directly exposed to a flame, so it must be used in a well ventilated environment where it will not collect.
Table 1 Physical comparison of R410A and R22
R410A R22 Composition (wt%) R32/R125 (50/50) R22 (100) Boiling point (°C) -51.4 -40.8 Vaporizing pressure (25°C) 1.56 Mpa (15.9 kgf/cm2) 0.94 Mpa (9.6 kgf/cm2) Saturated vapor density 64.0 kg/m3 44.4 kg/m3
Flammability Non-flammable Non-flammable Ozone-destroying point (ODP) 0 0.005 Global-warming point (GWP) 1730 1700
b. Compositional change (pseudo-azeotropic characteristics)
R410A is a pseudo-azeotropic mixture comprising the two components R32 and R125. Multi-component refrigerants with these chemical characteristics exhibit little compositional change even from phase changes due to vaporization 9or condensation), which means that there is little change in the circulating refrigerant composition even when the refrigerant leaks from the gaseous section of the piping. Accordingly, R410A can be handled in almost the same manner as the single-component refrigerant R22. However, when charging, because there is a slight change in composition between the gas phase and the liquid phase inside a cylinder or other container, charging should basically begin with the liquid side.
c. Pressure characteristics
As seen in Table 2, the gas pressure of R410A is approximately 1.6 times as high as that of R22 at the same refrigerant temperature, which means that special R410A tools and materials with high-pressure specifications must be used for all refrigerant piping work and servicing.
Table 2 Comparison of R410A and R22 saturated vapor density
Unit: MPa Refrigerant Temperature (°C) R410A R22 -20 0.30 0.14 0 0.70 0.40 20 1.35 0.81 40 2.32 1.43 60 3.73 2.33 65 4.15 2.60

d. R410A refrigerating machine oil
Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have a high compatibility with R410A are used as refrigerating machine oil. Because of the high hygroscopic property of synthetic oil, more care must be taken in its handling than was necessary with conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene, causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.
Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake in installation or servicing could result in a major accident. It is essential that you use R410a tools and materials, and that you observe the following precautions to ensure safety.
to a direct flame.
it does, the pressure in the refrigeration cycle can become abnormally high, possibly causing an explosion and/or injury.
result in an abnormal refrigeration cycle or water leakage, electric shock, fire, etc.
repairs can result in an water leakage, electric shock, fire, etc.
In order to prevent an R410A AC from mistakenly being charged with any other refrigerant, the diameter of the 3-way valve service port on the outdoor unit has been changed. Also, to increase its ability to withstand pressure, the opposing dimensions have been changed for the refrigerant pipe flaring size and flare nut. Accordingly, when installing or servicing refrigerant piping, you must have both the R410A and ordinary tools listed below.
Table 3 Tools for installation, transferring or replacement Type of work Ordinary tools R410A tools Flaring Flaring tool (clutch type), pipe cutter, reamer
Copper pipe gauge for clearance Adjustment, flaring tool (clutch type)*1) Bending, connecting pipes Torque wrench (nominal diameter 1/4, 3/8,1/2) Fixed spanner (opposing sides 12 mm, 17 mm, 19 mm)Adjustable wrench, Spring bender Air purging Vacuum pump Hexagonal wrench (opposing sides 4 mm)
Manifold gauge, charging hose, vacuum pump adaptor Gas leak inspection Gas leak inspection fluid or soapy water Electric gas leak detector for HFC refrigerant*2)
*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.
*2) Use when it is necessary to detect small gas leaks.
For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.
Table 4 Tools for serving Type of work Ordinary tools R410A tools Refrigerant charging Electronic scale for refrigerant charging Refrigerant cylinder Charging orifice and packing for refrigerant cylinder Brazing (Replacing refrigerating cycle part*1)
Nitrogen blow set (be sure to use nitrogen blowing for all brazing), and brazing), and brazing machine
*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming operation within 2 hours.


(used when flaring with the conventional flaring tool (clutch type))
copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.
Fig. 1 Copper tube gauge for clearance adjustment

clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the pipe- expanding torque. This flaring tools can also be used with R22 piping, so we recommend that you select it if you are buying a new flaring tool.
Fig. 2 Flaring tool (clutch type)

Fig. 3 Torque wrenches
Table 5 Conventional wrenches R410A wrenches For 1/4 (opposite side x torque) 17 mm x 18 N.m (180 kgf.cm) 17 mm x 18 N.m (180 kgf.cm) For 3/3 (opposite side x torque) 22 mm x 42 N.m (180 kgf.cm) 22 mm x 42 N.m (180 kgf.cm) For 1/2 (opposite side x torque) 24 mm x 55 N.m (180 kgf.cm) 26 mm x 55 N.m (180 kgf.cm)
Table 6 Difference between R410A and conventional high / low-pressure gauges
Conventional wrenches R410A wrenches High-pressure gauge (red) -76 cmHg - 35 kgf/cm3 -0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm3
High-pressure gauge (blue) -76 cmHg - 17 kgf/cm3 -0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm3
refrigerant.
Table 7 Difference between R410A and conventional manifold port size
Conventional gauges R410A gauges Port size 7/6 UNF 20 threads 1/2 UNF 20 threads


raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.
Fig. 4 Manifold gauge charging hose
Table 8 Difference between R410A and conventional charging hoses
Conventional hoses R410A hoses Pressure resistance
Working pressure 3.4 MPa (35 kgf/cm3) 5.1 MPa (52 kgf/cm3) Bursting pressure 17.2 MPa (175 kgf/cm3) 27.4 MPa (280 kgf/cm3) Material NBR rubber HNBR rubber Nylon coating inside

to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the vacuum pump oil (mineral oil) becomes mixed with R410A, it will damage the unit.
Fig. 5 Vacuum pump adaptor

CFC and HCFC cannot be used with R410A (because there is no chlorine in the refrigerant).
detection sensitivity will be lower (setting the sensitivity for R134a at 1, the level for R410A will drop to 0.6).
electric gas leak detector for HFC refrigerant. (Detection sensitivity with R410A is about 23 g/year).
Fig. 6 Electric gas leak detector for HFC refrigerant


of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinder cannot be used because of the differences in the pressure resistance, scale gradation, connecting port size, etc.)
structure in which the weight detector for the refrigerant cylinder is held by four supports. It is also equipped with two connection ports, one for R22 *7/16 UNF, 20 threads) and one for R410A (1/2 UNF, 20 threads), so it can also be used for conventional refrigerant charging.
Fig. 7 Electronic scale for refrigerant charging
cylinders and one for 20-kg cylinders. (The 10-kg cylinder is recommended.)
Refrigerant charging is done manually by opening and closing the valve.

name, and the coating color of the cylinder protector is pink, which is the color stipulated by ARI of the U.S.
allow the cylinder to stand upright for liquid refrigerant charging.
Fig. 8 Refrigerant cylinders

hose fitting (1/2 UNF, 20 threads).
material.
Fig. 9 Charging orifice and packing
Table 9 R410A tools which are usable for R22 models
R410A tools Usable for R22 models (1) Copper tube gauge for clearance adjustment OK (2) Flaring tool (clutch type) OK (3) Manifold gauge NG (4) Charging hose NG (5) Vacuum pump adaptor OK (6) Electric gas leak detector for HFC refrigerant NG (7) Electronic scale for refrigerant charging OK (8) Refrigerant cylinder NG (9) Charging orifice and packing for refrigerant cylinder NG

It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not used pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries. Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materials that are appropriate for these standards. The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing with a thickness of only 0.7 mm is also available on the market, but this should never be used.
Table 10 Difference between R410A and conventional copper tube Soft pipe Thickness (mm) Nominal diameter Outside diameter (mm) R410A (Reference) R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.7 0.80 0.80
When working with refrigerant piping, the following points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks.

a. Cut the pipe
Use a pipe cutter, and cut slowly so the pipe will not be deformed.
b. Remove burrs and clean shavings from the cut surface
If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may lead to refrigerant leaks. To prevent this, turn the cut surface downward and remove burrs, then clean the surface, carefully.
Fig. 10 Flaring dimensions
c. Insert the flare nut (be sure to used the same nut that is
used on the AC unit)
d. Flaring
Check the clamp bar and the cleanliness of the copper pipe. Be sure to sued the clamp bar to do the flaring with accuracy. Use either an R410A flaring tool, or a conventional flaring tool. flaring tools come in different sizes, so be sure to check the size before using. When using a conventional flaring tool, use the copper pipe gauge for clearance adjustment, etc., to ensure the correct A dimension (see Fig. 10)

Fig. 11 Relation between the flare nut structure and flaring tool end

Table 11 R410A flaring dimensions Nominal diameter
A (mm) R410A flaring tool, clutch type
Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 3/8 9.52 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 1/2 12.70 0.8 0 - 0.5 1.0 - 1.5 2.0 - 2.5
Table 12 R410A flaring dimensions Nominal diameter
A (mm) R410A flaring tool, clutch type
Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 3/8 9.52 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 1/2 12.70 0.8 0 - 0.5 0.5 - 1.0 1.5 - 2.0
Table 13 R410A flaring and flare nut dimensions Unit: mm Nominal diameter
A +0, -0.4 B dimension
width 1/4 6.35 0.8 9.1 9.2 6.5 13 17 3/8 9.52 0.8 13.2 13.5 9.7 20 22 1/2 12.70 0.8 16.6 16.0 12.9 23 26
Table 14 R410A flaring and flare nut dimensions Unit: mm Nominal diameter
A +0, -0.4 B dimension
width 1/4 6.35 0.8 9.0 9.2 6.5 13 17 3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24
a. Check to make sure there are no scratches, dust, etc., on the flare and union.
b. Align the flared surface with the axial center of the union.
c. Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional
torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split the flare nut or make it impossible to remove the flare nut.
Table 15 R410A tightening torque Nominal diameter
Torque wrench tightening torque
N.m (kgf.cm) 1/4 6.35 14 - 18 (140 - 180) 18 (180) 3/8 9.52 33 - 42 (330 -420) 42 (420) 1/2 12.70 55 (550) 55 (550)
N.m (kgf.cm)
The following is a general classification of the refrigerant pipe materials used for ACs.

Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.
a. Sheathed copper pipes and copper-element pipes
When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit.

b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.
Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and dust is even more important that in conventional piping).
a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.
b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil,
and lead to malfunctions in the equipment.
c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing
the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
10.4.1. Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New Refrigerant Piping)
a. Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way
valve. (1)
b. Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge
instantly reaches vacuum, re-check step a).)
c. Continue the vacuum process for at least 15 minutes, then check to make sure the low-pressure gauge has reached -0.1
MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)
d. Turn the valve stem of the 2-way valve 90 counter-clockwise to open it, then, after 10 seconds, close it and inspect for a gas
e. Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn
the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).
f. Tighten the service port cap with a torque wrench (18 N.m (1.8 kgf.m)). (5) Then tighten the 2-way valve and 3-way valve
caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)).
g. After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)

vacuum pump adaptor and manifold gauge prior to use, and follow the instructions carefully.
the designated line on the oil gauge.
charging hose is generally open during use. When you are removing the charging hose from the service port, it will come off more easily if you close this valve.
Fig. 12 Vacuum pump air purging configuration
leak (4) · Precautions

a. Collecting the refrigerant into the outdoor unit by pumping down
The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.
clockwise. (Remove the valve stem caps and check to see that the valve stems are fully opened position. Always use a hex wrench (with 4-mm opposing sides) to operate the valve stems.)
the clockwise direction.
way valve quickly in the clockwise direction to close it, then stop the operation.
Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor and outdoor units, and the pipes of the indoor unit, and check for gas leaks.
When replacing and R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil is different. When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section 10.1.1.(2)). In this case, you should use new refrigerant piping rather than the existing piping.
Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times different. the wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections of the piping also cannot be checked.
A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is difficult with the present technology.
Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.
When recharging is necessary, insert the specified amount of new refrigerant in accordance with the following procedure.
at least one hour.
vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge has not returned. See Fig. 13 for the remaining steps of this procedure.

electronic scale. (1)(2)
Precaution:
Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid without having to turn the cylinder around
electronic scale. (2)(3)
manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.)
with the liquid refrigerant. (2)(5) (Be sure to read the operating instructions for the electronic scale.)
(about 150 g/time as a guideline). If the charging amount is insufficient from one operation, wait about one minute, then use the same procedure to do the liquid charging again.
Precaution:
Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit.
manifold gauge, and stop the operation of the unit. (2)(5)
be discharged.

Fig. 13 Re-charging refrigerant

As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N2) flow.
<Brazing Method for Preventing Oxidation>
from flowing backward.
which pipes are touchable with finger).

a. The brazing strength should be high as required.
b. After operation, airtightness should be kept under pressurized condition.
c. During brazing do not allow component materials to become damaged due to overheating.
d. The refrigerant pipe work should not become blocked with scale or flux.
e. The brazed part should not restrict the flow in the refrigerant circuit.
f. No corrosion should occur from the brazed part.
Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So, make brazing at adequate brazing temperature and with minimum of heating area.
In order to prevent components near the brazed part from overheating damaged or quality deterioration due to flame or heat, take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means of heat absorbent.
Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.
In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.
The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has leaked completely. (Applicable for drier models only)

Required tools for Installation Works 1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter 2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench 18 NGm (1.8 kgfGm) 55 NGm (5.5 kgfGm) 65 NGm (6.5 kgfGm) 3. Electric drill, hole core drill (ø70 mm)
for the model to be installed.
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire. 2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock. 4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. 5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 6. Use the specified cable (2.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. 8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
mm.

1. Selection of the installation location. Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance. 2. Power supply connection to the room air conditioner. Connect the power supply cord of the room air conditioner to the mains using one of the following method. Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the receptacle using a power plug.
Use an approved 16A power plug with earth pin for 2.0HP (E18CK, E21CK) for the connection to the socket.
E21CK) for the permanent connection. It must be a double pole switch with a minimum 3 mm contact gap. 3. Do not release refrigerant. Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite. 4. Installation work. It may need two people to carry out the installation work. 5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.



Indoor/Outdoor Unit Installation Diagram

SELECT THE BEST LOCATION
INDOOR UNIT
unit.
circulation.
ceiling, fence or other obstacles.
at least 2.3 m.
sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
affected by hot air discharged.
fence or other obstacles.
circuit of the discharged air.
The indoor unit will actually face a different way.
be added as shown in the table.
Attached accessories · Applicable piping kit

11.2.3. TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING
The mounting wall is strong and solid enough to prevent it from the vibration.
When the wall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable.


The centre of installation plate should be at more than 550 mm at right and left of the wall.
The distance from installation plate edge to ceiling should more than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
:
For left side piping, piping connection for liquid should be about 126 mm from this line. For left side piping, piping connection for gas should be about 174 mm from this line. For left side piping, piping connecting cable should be about 984 mm from this line.
:
:

more. (If mounting the unit on the concrete wall consider using anchor bolts.)
aligning the marking-off line with the thread and using a level gauge.
and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively.

hole should be slightly slanted to the outdoor side.






(This can be used for left rear piping & left bottom piping also.)








without removing the front grille.
shall be approved polychloroprene sheathed 4 × 2.5 mm2
(E18CK, E21CK) flexible cord, type designation 245 IEC 57 or heavier cord.

terminal Nos. are the same to the indoor’s respectively.
as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage.
(clamper).
INSTALLATION OF AIR PURIFYING FILTERS
Please follow the steps below to take out front grille if necessary such as when servicing.
a. Open the front panel.
b. Remove the air filters.
a. Open the intake grille and remove the screw at the front
c. Put air purifying filters (left) and triple deodorizing filter
of the front grille.
(right) into place as shown in illustration below.
b. Set the vertical airflow direction louver to the horizontal

position.
c. Slide down the 3 caps on the front grille as shown in the
illustration below, and then remove the 3 mounting screws.
d. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.


The below operations will be performed by pressing the “AUTO” switch.
The Auto operation will be activated immediately once the Auto Switch is pressed.
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 8 sec. A “beep” sound will occur at the fifth sec., in order to identify the starting of Test Run operation
Press the AUTO Switch continuously for more than 8 sec. to below 11 sec. and release when a “beep beep” sound is occurred at eighth sec. (However, a “beep” sound is occurred at fifth sec.)
The ON/OFF of Remote Control receiving sound can be changed over by following steps:
a. Press “AUTO” switch continuously for more than 16 sec. to below 21 sec. A “beep” sound will occur
at sixteenth sec.
b. Press the “Check” button once at Remote Control. A “beep” sound will occur.
c. Press the “AUTO” switch once to select Remote Control receiving sound ON/OFF. A “beep” sound indicates receiving sound
ON, and a “beep” sound indicates receiving sound OFF.

11.3.2. INSTALL THE OUTDOOR UNIT

to Indoor/Outdoor Unit Installation Diagram.
by bolt nut. (ø10 mm).
earthquake. Please fasten the installation stand firmly with bolt or nails.
Connecting The Piping To Indoor Unit

Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)
nut with fingers.
MODEL Piping size (Torque) Gas Liquid E18CK, E21CK 1/2” (55 N.m) 1/4” (18 N.m)
torque as stated in the table.
Connecting The Piping to Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
Connect the piping


removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
copper pipes.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.

-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
move after approximately five minutes.
wrench (4 mm).
frostbite.

E21CK) flexible cord, type designation 245 IEC 57 or heavier cord.

the insulated piping end to prevent water from going inside the piping.
with thickness 6 mm or above.
EVALUATION OF THE PERFORMANCE
stand which is taller than 3 cm.
minutes or more.
0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.
the discharge is more than 8°C.


Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut connection?
Is the connecting cable being fixed to terminal board firmly?
(Drainage checking can be carried out without removing the front grille.)
Is the connecting cable being clamped firmly?
Is the drainage OK? (Refer to “Check the drainage” section)
unit.

Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the air purifying filter installed?

a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the specification and technical data. Below are the methods used to obtain rated compressor operating specification.
(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.
(“beep” will be heard at the 5th second.)

(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.

Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated frequency. (“beep” “beep” will be heard at the 8th second.)
(a) Cooling · (b) Heating


In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.

Refrigeration cycle system

Cooling Mode Heating Mode Condition of the air
conditoner Low Pressure High Pressure Electric current during operation
Low Pressure High Pressure Electric current during operation
Insufficient refrigerant (gas leakage)
Clogged capillary tube or Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the outdoor unit
Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below breakdown diagnosis method:
displayed at remote control.
” button once, next error code will be displayed; press “V” button once, previous error code will be displayed.
and Power LED will light on. Otherwise, one “beep” sound is heard.
If “CHECK” button is press again during Cooling operation using test run operation mode for 30 seconds, the diagnosis mode will turn off.
Inefficient compression

Abnormality / Protection control Abnormality
Primary location to verify
H11 Indoor / outdoor abnormal communication
> 1 min after starting operation
Continue for 5 sec. — • Intake air temperature sensor
(defective or disconnected) H15 Outdoor compressor temperature sensor abnormality
Continue for 5 sec. — • Compressor temperature sensor
(defective or disconnected) H16 Outdoor Current Transformer open circuit
— — • Outdoor PCB
Continue for 5 sec. O (Cooling only)
(defective or disconnected) H26 Ion abnormality — — • Indoor PCB
Continue for 5 sec. O • Outdoor temperature sensor
(defective or disconnected) H28 Outdoor heat exchanger temperature sensor abnormality
Continue for 5 sec. O • Outdoor heat exchanger
temperature sensor (defective or disconnected) H30 Discharge temperature sensor abnormality
Continue for 5 sec. — • Discharge temperature sensor
— — • Insufficient refrigerant
4 times occurance within 30 minutes
— • 4-way valve
— • Voltage at PFC
F91 Refrigeration cycle abnormality 7 times occurance continuously
— • No refrigerant
(3-way valve is closed) F93 Outdoor compressor abnormal revolution 4 times occurance within 20 minutes
— • Outdoor compressor
F95 Cool high pressure protection 4 times occurance within 20 minutes
— • Outdoor refrigerant circuit
F96 IPM (power transistor) overheating protection
— — • Excess refrigerant
4 times occurance within 20 minutes
— • Insufficient refrigerant
— • Excess refrigerant
7 times occurance continuously
— • Outdoor PCB
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “RESET” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is changed from one “beep” to four “beep” sounds.


When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work.
If this happen, remove the cover of the remote control and push the reset point once to clear the memory data.

When there are more than one indoor units installed in the same room, it is possible to set different remote control receiving signal by modifying the jumpers inside Remote Control.

code


of the Front Grille. (Fig. 1).
Front Grille. (Fig. 1)
top of the Front Grille. (Fig. 1)

Control Board Cover. (Fig. 2)

(Fig. 3)



Motor, Control Board need to be taken out by releasing all the connectors as indicated below.
a. Release the Earth Wire screw. (Fig. 5)
b. Release the Intake Air Sensor. (Fig. 5)
c. Release the Piping Sensor. (Fig. 5)
d. Release the CN-REC connectors. (Fig. 5)
e. Release the CN-STM1. (Fig. 5)
f. Release the CN-STM2. (Fig. 5)
g. Release connectors generator Ionizer. (Fig. 5)

Grille. (Fig. 6)

hook at the right, you will be able to remove the Control Board. (Fig. 7)




from shaft. By then, Fan Motor can be taken out. (Fig. 10).
REMINDER - To reinstall the Fan Motor, put it back in place, adjust the position of the Fan Motor’s leadwire appropriately as shown in the Fig. 8 before installing the Cross Flow Fan.


sink cover so never touch the interior during operation. Wait at least two minutes after power has been turned off.









Outdoor Temp. (°C) Indoor wet bulb temp.
30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 5.26 3.99 1.51 4.91 3.82 1.63 4.57 3.67 1.74 4.16 3.49 1.88 19.0°C 5.30 1.65 19.5°C 5.77 4.17 1.54 5.40 4.01 1.66 5.02 3.86 1.77 4.56 3.67 1.91 22.0°C 6.29 4.33 1.57 5.88 4.16 1.69 5.47 4.01 1.80 4.97 3.83 1.95
Outdoor Temp. (°C) Indoor wet bulb temp.
30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 6.25 4.74 2.02 5.84 4.54 2.18 5.43 4.37 2.33 4.94 4.15 2.51 19.0°C 6.30 2.21 19.5°C 6.86 4.96 2.06 6.41 4.77 2.22 5.97 4.59 2.37 5.42 4.37 2.56 22.0°C 7.48 5.14 2.10 6.99 4.95 2.26 6.50 4.77 2.42 5.91 4.55 2.61
TC - Total Cooling Capacity (kW) Indoor 27°C/19°C SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C IP - Input Power (kW)


The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.

REF. NO. PART NAME & DESCRIPTION QTY. CS-E18CKE CS-E21CKE REMARKS 1 CHASSY COMPLETE 1 CWD50C1293 ← 2 FAN MOTOR 1 CWA981056 ← 0 3 CROSS FLOW FAN COMPLETE 1 CWH02C1010 ← 4 SCREW - CROSS FLOW FAN 1 CWH4580304 ← 5 BEARING ASS’Y 1 CWH64K007 ← 6 EVAPORATOR 1 CWB30C1387 CWB30C1336 7 FLARE NUT 1 CWT25086 (7/16”) ← 8 FLARE NUT 1 CWT25096 (3/4”) ← 9 INTAKE AIR SENSOR HOLDER 1 CWH32142 ← 10 DISCHARGE GRILLE COMPLETE 1 CWE20C2240 ← 11 VERTICAL VANE 15 CWE241088 ← 12 CONNECTING BAR 2 CWE261025 ← 13 AIR SWING MOTOR 1 CWA98260 ← 0 14 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3849 ← 15 AIR SWING MOTOR 1 CWA981041 ← 0 16 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3731 ← 17 HORIZONTAL VANE 1 CWE241136 ← 18 CAP - DRAIN TRAY 1 CWH52C1001 ← 19 PARTICULAR PIECE 1 CWD932162 ← 20 CONTROL BOARD 1 CWH102103 ← 21 TERMINAL BOARD COMPLETE 1 CWA28C2128 ← 0 22 POWER SUPPLY CORD 1 CWA20C2328 ← 23 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1456 CWA73C1457 0 24 ELECTRONIC CONTROLLER - POWER 1 CWA743304 ← 0 25 P.C.B. RECEIVER 1 CWA742724 ← 26 ELECTRONIC CONTROLLER - INDICATOR 1 CWE39C1102 ← 0 28 INDICATOR HOLDER 1 CWD932163 ← 29 SENSOR COMPLETE 1 CWA50C2122 ← 0 30 CONTROL BOARD TOP COVER 1 CWH131091 ← 31 CONTROL BOARD FRONT COVER 1 CWH131090 ← 32 REMOTE CONTROL COMPLETE 1 CWA75C2401 ← 0 33 FRONT GRILLE COMPLETE 1 CWE11C2843 ← 34 INTAKE GRILLE 1 CWE22C1105 ← 35 GRILLE DOOR 1 CWE141033 ← 36 CONTROL PANEL 1 CWE312291 ← 37 DECORATION BASE (R) 1 CWE351067 ← 38 DECORATION BASE (L) 1 CWE351068 ← 39 AIR FILTER 2 CWD001049 ← 40 SCREW - FRONT GRILLE 4 XTT4+16C ← 41 CAP - FRONT GRILLE 3 CWH521062 ← 42 DRAIN HOSE 1 CWH85285 ← 43 AIR PURIFYING FILTER 1 CWMD00C0001 ← 0 44 TRIPLE DEODORIZING FILTER 1 CWMD00C0004 ← 0 45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ← 46 INSTALLATION PLATE 1 CWH36K1007 ← 47 FULCRUM 2 CWH621013 ← 48 ELECTRONIC CONTROLLER - IONIZER 1 CWA743099 ← 0 49 CASING - IONIZER 1 CWD932228 ← 50 ION - GENERATOR 1 CWH94C0001 ←
(Note)


The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.

REF NO. DESCRIPTION & NAME QTY. CU-E18CKR CU-E21CKR REMARKS 1 CHASSY ASSY 1 CWD50K2085 ← 2 ANTI-VIBRATION BUSHING 3 CWH50077 ← 3 COMPRESSOR 1 5CS130XAC03 ← O 4 NUT-COMPRESSOR MOUNT 3 CWH56000 ← 5 SOUND PROOF MATERIAL 1 CWG302111 ← 6 FAN MOTOR BRACKET 1 CWD541054 ← 7 FAN MOTOR 1 CWA981110 ← O 8 SCREW - FAN MOTOR BRACKET 2 CWH551060 ← 9 SCREW - FAN MOTOR MOUNT 3 CWH551109 ← 10 PROPELLER FAN ASSY 1 CWH03K1016 ← 11 NUT - PROPELLER FAN 1 CWH56053 ← 12 CONDENSER 1 CWB32C1317R CWB32C1324R 14 TUBE ASS’Y COMPLETE (VALVE/RECEIVER) 1 CWT01C2900 CWT01C2901 O 15 4 WAYS VALVE 1 CWB001027 ← 16 STRAINER 1 CWB11094 ← 18 HOLDER - COUPLING 1 CWH351035 ← 19 3 WAYS VALVE (GAS) 1 CWB011170 ← O 20 2 WAYS VALVE (LIQUID) 1 CWB021135 ← O 21 DRYER 1 CWB101015 ← O 22 SOUND PROOF BOARD 1 CWH151050 ← 23 TERMINAL COVER 1 CWH171001 ← 24 NUT-TERMINAL COVER 1 CWH7080300 ← 25 SENSOR COMPLETE (COMP. TOP) 1 CWA50C2168 ← 26 HOLDER SENSOR 3 CWH321010 ← 27 V-COIL COMPLETE (4-WAYS VALVE) 1 CWA43C2098 ← 28 V-COIL COMPLETE (EXPAND VALVE) 1 CWA43C2058 ← 29 SENSOR COMPLETE (COMP. DISC.) 1 CWA50C2169 ← 30 SENSOR COMPLETE 1 CWA50C2120 ← 31 REACTOR 1 CWA421069 ← 32 CONTROL BOARD (SIDE) 1 CWH102122 ← 33 TERMINAL BOARD ASSY 1 CWA28K1036 ← 34 FUSE HOLDERS 1 - - 35 FUSE 1 - - 36 CONTROL BOARD (TOP) 1 CWH102204 ← 37 CONTROL BOARD (BOTTOM) 1 CWH102205 ← 38 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1464 CWA73C1465 40 CONTROL BOARD COVER (TOP) 1 CWH131167 ← 41 CABINET SIDE PLATE (LEFT) 1 CWE041082A ← 42 HANDLE 1 CWE161010 ← 43 CABINET SIDE PLATE (RIGHT) 1 CWE041083A ← 44 HANDLE 1 - - 45 CABINET FRONT PLATE CO. 1 CWE06K1043 ← 46 WIRE NET 1 CWD041041A ← 47 CABINET TOP PLATE 1 CWE031031A ← 48 CONTROL BOARD COVER (BOTTOM) 1 CWH131168 ← 49 CONTROL BOARD COVER (TOP) 1 CWH131169A ← 50 OPERATING INSTRUCTION 1 CWF563989 ← 51 OPERATING INSTRUCTION 1 CWF563990 ← 52 OPERATING INSTRUCTION 1 CWF563991 ← 53 INSTALLATION INSTRUCTION 1 CWF612433 ← 54 INSTALLATION INSTRUCTION 1 CWF612434 ← 55 INSTALLATION INSTRUCTION 1 CWF612435 ← 56 DRAIN HOSE 1 CWH5850080 ← 57 PACKING 1 CWB81012 ←
(Note)


6 5 4 3 2 1 CN-MAIN 7 10 9 8
C9 0.01µ R20 10kΩ R21 1kΩ
R45 270Ω R46 270Ω R47 270Ω
R49 330Ω R50 330Ω R51 270Ω
R33 10kΩ R34 10kΩ R35 10kΩ R36 10kΩ C20 0.01µ


64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
(20k 3950) PIPE TEMP. SENSOR R22 15kΩ 1%


3 4 5 6 7 8 9 10 11






R212 10k R213 10k R214 10k R215 10k R216 10k R217 10k
100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85
41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26







How to use electronic circuit diagram

Test mode Name Time (When test point
Short-circuited) 4 way valve abnormality 4 min. 24 sec. Outdoor air temp. for Hz No. decision 30 min. 0 sec. Anti-dew formation control 20 min. 0 sec. Anti-freezing control 6 min. 0 sec. Thermo OFF delay 3 min. 0 sec. Low pressure control (gas leakage) compressor OFF time 3 min. 0 sec. Time delay safety control 2 min. 58 sec. 0 sec. 20 sec. Odour timer status shift time 90 sec. 0 sec. 20 sec. 120 sec. Intake air temp. sampling time 2 min. 0 sec. Self diagnosis display time 10 sec. 0 sec. Auto mode judgement sampling time 20 sec. 0 sec. 24 hours Real Timer 1 hour 1 min. Heating SSHi fan speed shift 120 min. 12 sec. Cooling SHi fan speed shift 30 min. 3 sec. Hot start forced completion 4 min. 0.4 sec. Auto mode judgement interval 30 min. 3 sec. After Hot start / Deice 2 min. 12 sec.
Test mode Name Time (When test point
Short-circuited) DC PEAK 30 sec. 3 sec. 120 min. 24 sec. Deice detection 80 min. 16 sec. 40 min. 8 sec. 40 min. 8 sec. Hz lock time 30 sec. 0 sec. Outdoor fan delay operation control 30 sec. 3 sec. 4 way valve delay operation control 3 min. 18 sec.






100 [MAICO] Printed in Malaysia