2 Functionsp.3Remote Controlp.3OFF/ONp.3Indoor Fan Speed Selection FAN SPEEDp.3Operation OFF / ONp.3MODEp.3Operation Mode Selectionp.3TEMPp.3Room Temperature Settingp.3POWERFULp.3TIMERp.3ONp.3Powerful Mode Operationp.3OFFp.3Quiet Mode Operation QUIETp.3∧ ∨p.3Time / Timer Settingp.3Ion Mode Operationp.3SETp.3CANCELp.3Timer Operation Set / Cancelp.3AIR SWINGp.3Airflow Direction Controlp.3CLOCKp.3Clock Settingp.3CHECKp.3Check Pointp.3Reset Point RESETp.3Indoor Unitp.4Automatic Operation Switchp.4Five Operation Modesp.4Automatic and 5 Manual Indoor Fan Speedsp.4Automatic and 5 Manual Vertical Airflow Directionsp.4Automatic and 5 Manual Horizontal Airflow Directionsp.4Powerful Modep.4Operation Indication Lamps (LED)p.4Quiet Modep.4Ionizer Controlp.4Delay ON Timer and OFF Timerp.4Automatic Restart Controlp.4Microcomputer-controlled Room Temperature Controlp.43 Product Specificationsp.6SIDE VIEWp.6TOP VIEWp.6INTAKEp.64 Dimensionsp.105 Refrigeration Cycle Diagramp.126 Block Diagramp.137 Wiring Diagramp.148 Operation Detailsp.158.1. BASIC FUNCTIONp.158.1.1. Internal Setting Temperaturep.158.1.2. Compressor Operation Frequencyp.178.1.3. Cooling Operationp.178.1.3.1. Thermostat controlp.178.1.4. Soft Dry Operationp.188.1.4.1. Thermostat controlp.188.1.5. Heating Operationp.188.1.5.1. Thermostat controlp.188.1.6. Automatic Operationp.188.1.7. Indoor Fan Motor Operationp.19ON OFF ONp.238.1.8. Outdoor Fan Motor Operationp.238.1.9. Airflow Directionp.248.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)p.268.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)p.268.1.10.2. Quiet operation (Heating)p.278.1.11. Powerful Mode Operationp.288.1.12. Delay ON Timer Controlp.288.1.13. Delay OFF Timer Controlp.288.1.14. Auto Restart Controlp.298.1.15. Indication Panelp.298.1.16. Auto Operation Switchp.298.1.17. Indoor Power Relay Controlp.308.1.18. Ionizer Operationp.308.1.18.1. Ionizer Problem Detection Controlp.31ERROR PROTECTIONp.31BREAKDOWN PROTECTIONp.318.1.18.2. Ionizer Operation case studyp.318.2. Protection Control Featuresp.32
Page 1 of the Panasonic CS-E18CKE user manual
Page 1 · click to enlarge
Page 1
Panasonic CS-E18CKE diagram (page 1)
Fig. 1

12.5. Cross Flow Fan and Indoor Fan Motor Removal

10 Installation And Servicing Air Conditioner Using R410A 52

© 2003 Matsushita Industrial Corp. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.

Page 2 of the Panasonic CS-E18CKE user manual
Page 2 · click to enlarge
Page 2
Panasonic CS-E18CKE diagram (page 2)
Fig. 2
Page 3 of the Panasonic CS-E18CKE user manual — Reset Point RESET
Page 3 · click to enlarge
Page 3
Panasonic CS-E18CKE — 2 Functions diagram (page 3)
Fig. 3 · 2 Functions

2 Functions

Remote Control

Panasonic CS-E18CKE — Remote Control diagram (page 3)
Fig. 4 · Remote Control
Panasonic CS-E18CKE — Remote Control diagram (page 3)
Fig. 5 · Remote Control

OFF/ON

Indoor Fan Speed Selection FAN SPEED

Operation OFF / ON

  • Low
  • Medium-
  • Medium
  • Medium+
  • High
  • AUTO Automatic Fan Speed FAN

MODE

Operation Mode Selection

  • a Automatic Operation
  • HEAT Heating Operation
  • COOL Cooling Operation
  • DRY Soft Dry Operation
  • FAN Fan Operation

TEMP

Room Temperature Setting

  • Increase or decrease set temperature. (16°C to 30°C)

POWERFUL

TIMER

ON

Powerful Mode Operation

OFF

  • 24-hour, OFF / ON Real Timer Setting. Timer Setting

Quiet Mode Operation QUIET

∧ ∨

Time / Timer Setting

Ion Mode Operation

  • Hours and minutes setting.

SET

CANCEL

Timer Operation Set / Cancel

AIR SWING

  • ON Timer and OFF Timer setting and cancellation.

Airflow Direction Control

CLOCK

Clock Setting

  • Vertical Automatic Airflow Direction Control and Manual Airflow Direction Control (5 stages of adjustment).
  • Horizontal Automatic Airflow Direction Control and Manual Airflow Direction Control (5 stages of adjustment).
  • Current time setting.

CHECK

Check Point

  • Breakdown self diagnosis function.

Reset Point RESET

  • Clear memory data.

Illuminable · buttons

Page 4 of the Panasonic CS-E18CKE user manual — Microcomputer-controlled Room Temperature Control
Page 4 · click to enlarge
Page 4

Indoor Unit

Panasonic CS-E18CKE — Indoor Unit diagram (page 4)
Fig. 6 · Indoor Unit

Automatic Operation Switch

Five Operation Modes

  • Press for < 5s to run Automatic Operation. (Used when the remote control cannot be used.)
  • Press continuously for 5s and < 8s to run Forced Cooling Operation.
  • Press continuously for 8s and < 11s to run Forced Heating Operation.
  • Press continuously for 11s and < 16s to change different remote controlling setting (4 type of transmission code).
  • Press continuously for 16s or < 21s to switch OFF / ON Remote Control Receiving Sound or H14 Abnormality Detection Mode.
  • Automatic, Heating, Cooling, Soft Dry and Fan Operation.

Automatic and 5 Manual Indoor Fan Speeds

Automatic and 5 Manual Vertical Airflow Directions

Automatic and 5 Manual Horizontal Airflow Directions

Powerful Mode

Operation Indication Lamps (LED)

  • For quick cooling or heating.
  • POWER (Green) ...... Lights up during MONITOR compressor operation.
  • (Green) ............ Lights up in Ionizer

Quiet Mode

  • To provide extra quiet operation.

Mode Operation. Blinks in Ionizer error. • POWER (Green) Lights up in operation,

Ionizer Control

  • Ionizer control for generate negative ion in discharge air.
  • blinks in Automatic Operation Mode judging, deice, On Timer sampling and Hot Start operation.
  • POWERFUL (Orange) ... Lights up when Powerful Mode is selected.
  • QUIET (Orange) .... Lights up in Quiet

Delay ON Timer and OFF Timer

Automatic Restart Control

  • Operation is restarted after power failure at previous setting mode.

Mode Operation. • TIMER (Orange) Lights up in Timer

Microcomputer-controlled Room Temperature Control

Setting. Blinks in Self Diagnosis Control.

Page 5 of the Panasonic CS-E18CKE user manual — Indoor Unit
Page 5 · click to enlarge
Page 5
Panasonic CS-E18CKE — Indoor Unit diagram (page 5)
Fig. 7 · Indoor Unit
Page 6 of the Panasonic CS-E18CKE user manual — INTAKE
Page 6 · click to enlarge
Page 6

3 Product Specifications

Cooling Capacity kW kcal/h BTU/h

5.30 (0.90 - 6.00) 4,560 (770 - 5,160) 18,100 (3,070 - 20,500)

Heating Capacity kW kcal/h BTU/h

6.60 (0.90 - 8.00) 5,680 (770 - 6,880) 22,500 (3,070 - 27,300)

Moisture Removal l/h Pint/h

2.9 (6.1)

SIDE VIEW

TOP VIEW

Panasonic CS-E18CKE — SIDE VIEW diagram (page 6)
Fig. 8
Panasonic CS-E18CKE — SIDE VIEW diagram (page 6)
Fig. 9

INTAKE

Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 12.5 (440) — Heating; 13.9 (490)

Indoor Air (Me) m3/min (cfm) Cooling; 14.0 (490) — Heating; 15.5 (540)

Indoor Air (Hi) m3/min (cfm) Cooling; 15.6 (550) 40.0 (1,410) Heating; 17.1 (600)

dB (A) Cooling; High 44, Low 37 Cooling; 47 Heating; High 44, Low 37 Heating; 47 Noise Level

Power level dB Cooling; High 57 Cooling; High 60 Heating; High 57 Heating; High 60

Electrical Data Input Power W Cooling; 1,650 (240 - 2,050) Heating; 1,790 (280 - 2,650)

Running Current A Cooling; 7.4 Heating; 8.0

EER W/W Cooling; 3.21 (3.75 - 2.93) BTU/hW Cooling; 11.0 (12.8 - 10.0) COP W/W Heating; 3.69 (3.21 - 3.02) BTU/hW Heating; 12.6 (11.0 - 10.3) Starting Current A 8.0 Piping Connection Port (Flare piping)

G ; Half Union 1/2”

G ; 3-way valve 1/2”

L ; Half Union 1/4”

L ; 2-way valve 1/4”

Show 6 more labels / short text on this page
Unit CS-E18CKE CU-E18CKE · Power Source Phase · Single · V Cycle · Airflow Method OUTLET · inch inch
Page 7 of the Panasonic CS-E18CKE user manual — 3 Product Specifications
Page 7 · click to enlarge
Page 7
UnitCS-E18CKECU-E18CKE Pipe Size (Flare piping)inch inchG (gas side) ; 1/2” L (liquid side) ; 1/4”G (gas side) ; 1/2” L (liquid side) ; 1/4” Drain HoseInner diametermm12— Lengthm0.65— Power Cord Length Number of core-wire2.1 m 3 core wires × 1.5 mm2— — DimensionsHeightinch (mm)10 - 13/16 (275)29 - 17/32 (750) Widthinch (mm)39 - 9/32 (998)34 - 7/16 (875) Depthinch (mm)8 - 9/32 (210)13 - 19/32 (345) Net Weightlb (kg)24 (11)108 (49) CompressorType—Involute scroll MotorType—Brushless (4-pole) RatedOutputW—900 Air CirculationTypeCross-flow FanPropeller Fan MaterialASHT-18P.P MotorTypeTransistor (8-poles)Transistor (8-poles) Rate OutputW3040 Fan SpeedLo (Cool/Heat)rpm1,150 / 1,270— Me (Cool/Heat)rpm1,290 / 1,410— Hi (Cool/Heat)rpm1,440 / 1,560660 Heat ExchangerDescriptionEvaporatorCondenser Tube materialCopperCopper Fin materialAluminium (Pre Coat)Aluminium (Blue Coated) Fin TypeSlit FinCorrugated Fin Row / Stage(Plate fin configuration, forced draft) 2 / 152 / 34 FPI2116 Size (W × H × L)mm810 × 315 × 25.4849.3 878× 714 × 36.4 Refrigerant Control Device—Expansion Valve Refrigeration Oil(c.c)—RB68A (360) Refrigerant (R410A)kg (oz)—1.18 (41.7) ThermostatElectronic Control— Protection DeviceElectronic ControlElectronic Control Lengthmm—— Capillary TubeFlow Ratel/min—— Inner Diametermm—— Air FilterMaterial StyleP.P. Honeycomb—
  • Specifications are subjected to change without notice for further improvement.
Page 8 of the Panasonic CS-E18CKE user manual — INTAKE
Page 8 · click to enlarge
Page 8

Cooling Capacity kW kcal/h BTU/h

6.30 (0.90 - 7.10) 5,420 (770 - 6,110) 21,500 (3,070 - 24,200)

Heating Capacity kW kcal/h BTU/h

7.20 (0.90 - 8.50) 6,190 (770 - 7,310) 24,600 (3,070 - 29,000)

Moisture Removal l/h Pint/h

3.5 (7.4)

SIDE VIEW

TOP VIEW

Panasonic CS-E18CKE — SIDE VIEW diagram (page 8)
Fig. 10
Panasonic CS-E18CKE — SIDE VIEW diagram (page 8)
Fig. 11

INTAKE

Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 12.6 (440) — Heating; 14.0 (490)

Indoor Air (Me) m3/min (cfm) Cooling; 14.5 (510) — Heating; 15.8 (560)

Indoor Air (Hi) m3/min (cfm) Cooling; 16.6 (590) Cooling; 42.8 (1,510) Heating; 17.7 (620) Heating; 41.5 (1,460)

dB (A) Cooling; High 45, Low 37 Cooling; 48 Heating; High 45, Low 37 Heating; 49 Noise Level

Power level dB Cooling; High 58 Cooling; High 61 Heating; High 58 Heating; High 62

Electrical Data Input Power W Cooling; 2,210 (240 - 2,540) Heating; 2,100 (280 - 2,750)

Running Current A Cooling; 9.9 Heating; 9.4

EER W/W Cooling; 2.85 (3.75 - 2.80) BTU/hW Cooling; 9.7 (12.8 - 9.5) COP W/W Heating; 3.43 (3.21 - 3.09) BTU/hW Heating; 11.7 (11.0 - 10.5) Starting Current A 9.4 Piping Connection Port (Flare piping)

G ; Half Union 1/2”

G ; 3-way valve 1/2”

L ; 2-way valve 1/4” Pipe Size (Flare piping)

L ; Half Union 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

G (gas side) ; 1/2” L (liquid side) ; 1/4”

Show 7 more labels / short text on this page
Unit CS-E21CKE CU-E21CKE · Power Source Phase · Single · V Cycle · Airflow Method OUTLET · inch inch · inch inch
Page 9 of the Panasonic CS-E18CKE user manual — 3 Product Specifications
Page 9 · click to enlarge
Page 9
UnitCS-E21CKECU-E21CKE Drain HoseInner diametermm12— Lengthm0.65— Power Cord Length Number of core-wire2.1 m 3 core wires × 1.5 mm2— — DimensionsHeightinch (mm)10 - 13/16 (275)29 - 17/32 (750) Widthinch (mm)39 - 9/32 (998)34 - 7/16 (875) Depthinch (mm)8 - 9/32 (210)13 - 19/32 (345) Net Weightlb (kg)24 (11)112 (51) CompressorType—Involute scroll MotorType—Brushless (4-pole) RatedOutputW—900 Air CirculationTypeCross-flow FanPropeller Fan MaterialASHT-18P.P MotorTypeTransistor (8-poles)Transistor (8-poles) Rate OutputW3040 Fan SpeedLo (Cool/Heat)rpm1,150 / 1,270— Me (Cool/Heat)rpm1,330 / 1,440— Hi (Cool/Heat)rpm1,520 / 1,610700 / 680 Heat ExchangerDescriptionEvaporatorCondenser Tube materialCopperCopper Fin materialAluminium (Pre Coat)Aluminium (Blue Coated) Fin TypeSlit FinCorrugated Fin Row / Stage(Plate fin configuration, forced draft) 2 / 152 / 34 FPI2118 Size (W × H × L)mm810 × 315 × 25.4849.3 878× 714 × 36.4 Refrigerant Control Device—Expansion Valve Refrigeration Oil(c.c)—RB68A (360) Refrigerant (R410A)kg (oz)—1.29 (45.5) ThermostatElectronic Control— Protection DeviceElectronic ControlElectronic Control Lengthmm—— Capillary TubeFlow Ratel/min—— Inner Diametermm—— Air FilterMaterial StyleP.P. Honeycomb—
  • Specifications are subjected to change without notice for further improvement.
Page 10 of the Panasonic CS-E18CKE user manual — 4 Dimensions
Page 10 · click to enlarge
Page 10

4 Dimensions

Panasonic CS-E18CKE — 4 Dimensions diagram (page 10)
Fig. 12 · 4 Dimensions
Page 11 of the Panasonic CS-E18CKE user manual — 4 Dimensions
Page 11 · click to enlarge
Page 11
Panasonic CS-E18CKE — 4 Dimensions diagram (page 11)
Fig. 13 · 4 Dimensions
Page 12 of the Panasonic CS-E18CKE user manual — 5 Refrigeration Cycle Diagram
Page 12 · click to enlarge
Page 12

5 Refrigeration Cycle Diagram

Panasonic CS-E18CKE — 5 Refrigeration Cycle Diagram diagram (page 12)
Fig. 14 · 5 Refrigeration Cycle Diagram
Page 13 of the Panasonic CS-E18CKE user manual — 6 Block Diagram
Page 13 · click to enlarge
Page 13

6 Block Diagram

Panasonic CS-E18CKE — 6 Block Diagram diagram (page 13)
Fig. 15 · 6 Block Diagram
Page 14 of the Panasonic CS-E18CKE user manual — 7 Wiring Diagram
Page 14 · click to enlarge
Page 14

7 Wiring Diagram

Panasonic CS-E18CKE — 7 Wiring Diagram diagram (page 14)
Fig. 16 · 7 Wiring Diagram
Page 15 of the Panasonic CS-E18CKE user manual — 8.1.1. Internal Setting Temperature
Page 15 · click to enlarge
Page 15

8 Operation Details

8.1. BASIC FUNCTION

Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air temperature.

8.1.1. Internal Setting Temperature

Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes. These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.

Panasonic CS-E18CKE — 8.1.1. Internal Setting Temperature diagram (page 15)
Fig. 17 · 8.1.1. Internal Setting Temperature
Table (a)Auto Operation Mode Setting
Mode ShiftTemperature Shift (°C) Cooling/Soft Dry → Heating -2.0 Heating → Cooling/Soft Dry +2.0
Page 16 of the Panasonic CS-E18CKE user manual — 8 Operation Details
Page 16 · click to enlarge
Page 16
Panasonic CS-E18CKE — 8 Operation Details diagram (page 16)
Fig. 18 · 8 Operation Details
ModeOutdoor Temperature, X (°C): Temperature Shift (°C) Manual Operation Auto Operation Cooling/Soft Dry 38
ModePeriod, X (min): Temperature Shift (°C) Cooling X
ModePeriod, X (min): Temperature Shift (°C) Cooling, Soft Dry 20 min

Mode: Fan Speed: Temperature Shift (°C) Cooling Lo -0.25 Me-, Me, Me+, Auto 0.00 Hi +0.25 Soft Dry All +0.25 Heating Lo +1.50 Me-, Me, Me+, Auto +0.75 Hi +0.75

Mode within 60 Minutes from Start-up: Temperature Shift (°C) Cooling/Soft Dry -1.0 Heating +2.0

Page 17 of the Panasonic CS-E18CKE user manual — 8.1.3. Cooling Operation
Page 17 · click to enlarge
Page 17

8.1.2. Compressor Operation Frequency

Intake Air Temperature - Internal Setting Temperature (°C) Freq. H Zone Cooling & Soft Dry Heating Cooling Soft Dry Heating Remark 1 -2.0 1.5 1 1 1 2 -1.5 1.0 1 1 1 3 -1.0 0.5 14 8 11 4 -0.5 0.0 20 8 15 5 0.0 -0.5 27 8 22 6 0.5 -1.0 35 11 27 7 1.0 -1.5 43 11 36 8 1.5 -2.0 46 11 39 Fc, Fh 9 2.0 -2.5 46 11 39 Fc, Fh 10 2.5 -3.0 46 11 39 Fc, Fh 11 Nil -3.5 Nil Nil 39 Fh 12 Nil -4.0 Nil Nil 39 Fh

Operating Frequency Calculation Formula:

CompHz = Freq. A × Freq. H + Freq. C

Cooling & Soft Dry E18CK E21CK Freq. A Freq. C Freq. A Freq. C Low Load (Freq. H

9. 1.2 5.0 1.7 7.0 High Load (Freq. H > 10) 1.53 2.5 2.0 4.0

Example Calculation:

Heating E18CK E21CK Freq. A Freq. C Freq. A Freq. C Low Load (Freq. H

Model No.: E18CK

Operation ModeCooling
11. 1.6 8.0 1.9 7.0 High Load (Freq. H > 12) 2.2 1.0 2.35 1.0

When Intake Air Temperature - Internal setting Temperature: 1.5°C

Freq. Range E18CK E21CK Cooling Fc 72 96 Operation Range 12 ~ 86 12 ~ 102 Heating Fh 86 92 Operation Range 14 ~ 128 14 ~ 128

CompHz = Freq. A × Freq. H + Freq. C = 1.53 × 46 + 2.5 = 72 Hz (It cuts down less than a decimal point)

Remarks:

When Freq. H is equal to 46 (Cooling), 39 (Heating) or above, the Comp. may run at the freq. higher than Fc or Fh up to max. freq. operation.

Every 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc (46), Fh (39).

8.1.3. Cooling Operation

8.1.3.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point +0.5°C.

Panasonic CS-E18CKE — 8.1.3. Cooling Operation diagram (page 17)
Fig. 19 · 8.1.3. Cooling Operation

Best Amenity Control

Page 18 of the Panasonic CS-E18CKE user manual — 8.1.6. Automatic Operation
Page 18 · click to enlarge
Page 18

8.1.4. Soft Dry Operation

8.1.4.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point.

Panasonic CS-E18CKE — 8.1.4. Soft Dry Operation diagram (page 18)
Fig. 20 · 8.1.4. Soft Dry Operation

8.1.5. Heating Operation

8.1.5.1. Thermostat control

  • Compressor is OFF when Intake Air Temperature - Internal Setting > +1.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF

point -0.5°C.

Panasonic CS-E18CKE — 8.1.5. Heating Operation diagram (page 18)
Fig. 21 · 8.1.5. Heating Operation

8.1.6. Automatic Operation

This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air temperature and outdoor air temperature.

During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.

Panasonic CS-E18CKE — 8.1.6. Automatic Operation diagram (page 18)
Fig. 22 · 8.1.6. Automatic Operation
Page 19 of the Panasonic CS-E18CKE user manual — 8.1.7. Indoor Fan Motor Operation
Page 19 · click to enlarge
Page 19

Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the above operation mode chart, every 30 minutes.

Remote Control Setting Temperature (°C) T1 T2 T3 16 ~ 18 +10 +8 -5 19 ~ 22 +8 +7 -7 23 ~ 26 +7 +6 -7 27 ~ 30 +6 +5 -8

There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice verse.

Operation Mode change from Temperature shifts (°C) Cooling/Soft Dry →Heating -2 Heating →Cooling/Soft Dry +2

Example of operation mode chart adjustment:

From the above table, if remote control setting temperature = 25,

T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18

The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made.

Panasonic CS-E18CKE — 8.1.7. Indoor Fan Motor Operation diagram (page 19)
Fig. 23 · 8.1.7. Indoor Fan Motor Operation

8.1.7. Indoor Fan Motor Operation

A. Basic Rotation Speed (rpm)

  • Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)

Remote Control — O — — — Tab (rpm) SHI Hi Me+ Me Me- Lo Lo- SLo SSLo E18CK 1530 1440 1360 1290 1220 1150 850 760 630 E21CK 1610 1520 1420 1330 1240 1150 890 800 630

Remote Control — O — — — Tab (rpm) SSHI SHi Me+ Me Me- Lo Lo- SLo SSLo E18CK 1590 1560 1480 1410 1340 1270 850 400 300 E21CK 1640 1610 1520 1440 1350 1270 890 400 300

[Cooling, Dry, Fan] · [Heating]

Page 20 of the Panasonic CS-E18CKE user manual — 8.1.7. Indoor Fan Motor Operation
Page 20 · click to enlarge
Page 20

B. Indoor Fan Control

i. Indoor fan control operation outline

1. Cooling / Dry
Panasonic CS-E18CKE — 8.1.7. Indoor Fan Motor Operation diagram (page 20)
Fig. 24 · 8.1.7. Indoor Fan Motor Operation
2. Heating
Panasonic CS-E18CKE — 8.1.7. Indoor Fan Motor Operation diagram (page 20)
Fig. 25 · 8.1.7. Indoor Fan Motor Operation
Page 21 of the Panasonic CS-E18CKE user manual — 8.1.7. Indoor Fan Motor Operation
Page 21 · click to enlarge
Page 21

ii. Auto Fan Speed

1. Cooling
Panasonic CS-E18CKE — 8.1.7. Indoor Fan Motor Operation diagram (page 21)
Fig. 26 · 8.1.7. Indoor Fan Motor Operation
2. Heating
Panasonic CS-E18CKE — 8.1.7. Indoor Fan Motor Operation diagram (page 21)
Fig. 27 · 8.1.7. Indoor Fan Motor Operation

a. UP:

  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).

b. DOWN:

  • The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.

c. Current Output Fixed:

  • Maintain at present fan speed.

d. Instantaneous Maximum:

  • Fan speed will be increased to maximum auto fan speed.

e. Temperature in ( ) is for Powerful Mode operation.

Page 22 of the Panasonic CS-E18CKE user manual — 8.1.7. Indoor Fan Motor Operation
Page 22 · click to enlarge
Page 22

iii. Max Capacity Condition

a) During Cooling operation, if all to the following condition is fulfilled, the indoor fan speed is set to Shi.

1. Indoor intake temperature

24°C.

2. Operation frequency 72 Hz (E18CK), 95 Hz (E21CK) & above.
3. Remote Control setting temperature 16°C.
4. Remote Control setting fan speed Hi.
5. Outdoor temperature

30°C.

6. Operation start

within 30 minutes.

* If any of above conditions is not valid, the condition is ended.

b) During Heating operation, if all to the following condition is fulfilled, the indoor fan speed is set to SSHi.

1. Indoor intake temperature is 17°C or above and less than 23°C.
2. Operation frequency 86 Hz (E18CK), 93 Hz (E21CK) & above.
3. Remote Control setting temperature 30°C.
4. Remote Control setting fan speed Hi.
5. Outdoor temperature < 4°C.
6. Operation start

2 hours.

* If any of above conditions is not valid, the condition is ended.

C. Fan Motor Control

i. Motor specification

High voltage PWM Motor

ii. Feedback Control

1. Rotation speed feedback

Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed.

iii. Abnormal Detection

1. Condition * * Step out signal input Feedback rotation speed is more than 2550 rpm or below 50 rpm. However, 10s after fan start, rotation abnormality is not detected.
2. Control * Fan stop
3. Return * Restart after 5s However, in case the fan is stopped by the above conditions within 25s after fan has started, and happened continuously for 7 times, restart will not be performed. → Indoor fan motor lock abnormal (H19)

iv. Restart Prohibition Control

Prohibit to restart within 5s after fan stop. (except when power is ON)

Page 23 of the Panasonic CS-E18CKE user manual — 8.1.8. Outdoor Fan Motor Operation
Page 23 · click to enlarge
Page 23

D. Deodorizing Control

i. Control condition

Control at cooling/dry operation and auto fan speed.

No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.

ii. Operation

The odor status is arranged as below and it is shifted as follow.

* When COMP is ON 1 →2 →3 (Shift to 4 when COMP is OFF) * When COMP is OFF 4 →5 →4 ←→5 (Shift to 1 when COMP is ON) * Start from 4 if the Thermostat is OFF during the start operation.

Odor Status 1 2 3 4 5 4 5 4.5.4... 1 Status Shift according to COMP

ON OFF ON

zone 40 50 — 20 90 20 90 to time (s) Dry zone ON

OFF

OFF

SLo OFF Dry zone OFF SLo OFF

Panasonic CS-E18CKE — OFF diagram (page 23)
Fig. 28

8.1.8. Outdoor Fan Motor Operation

Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.

Panasonic CS-E18CKE — 8.1.8. Outdoor Fan Motor Operation diagram (page 23)
Fig. 29 · 8.1.8. Outdoor Fan Motor Operation
Show 9 more labels / short text on this page
Status Shift · Cooling · according · Cooling · Auto Fan Speed · Fan Speed · zone · SLo · SLo
Page 24 of the Panasonic CS-E18CKE user manual — 8.1.9. Airflow Direction
Page 24 · click to enlarge
Page 24
Panasonic CS-E18CKE — 8.1.9. Airflow Direction diagram (page 24)
Fig. 30 · 8.1.9. Airflow Direction

8.1.9. Airflow Direction

1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature

and intake air temperature) and manual (angles of direction can be adjusted using remote control).

Operation Mode Airflow Direction Vane Angle (°) 1 2 3 4 5 Heating Auto with Heat Exchanger 17 Temperature 58 7 Manual 7 17 33 49 67 Cooling, Soft Dry and Fan, Ion Auto 7 ~ 37 Manual 7 17 25 33 41 Mode Judgment in Auto Auto 7 Manual 7 17 25 33 41

Basic Rotation Speed · Vertical Airflow

Page 25 of the Panasonic CS-E18CKE user manual — 8.1.9. Airflow Direction
Page 25 · click to enlarge
Page 25
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated

above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the

positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

Panasonic CS-E18CKE — 8.1.9. Airflow Direction diagram (page 25)
Fig. 31 · 8.1.9. Airflow Direction
1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as

stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.

Operation Mode Vane Angle (°) Heating, with heat exchanger temperature A 55 ~ 125 B 90 Cooling, Soft Dry and Fan, Ion 55 ~ 125

Panasonic CS-E18CKE — 8.1.9. Airflow Direction diagram (page 25)
Fig. 32 · 8.1.9. Airflow Direction
2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the

positions of the vane are as Figure 2 above.

Pattern 1 2 3 4 5 Airflow Direction Patterns at Remote Control

Vane Angle (°) 90 55 70 110 125

Horizontal Airflow

Page 26 of the Panasonic CS-E18CKE user manual — 8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Page 26 · click to enlarge
Page 26

8.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)

A. Purpose

To provide quiet cooling operation compare to normal operation.

B. Control condition

a. Quiet operation start condition

  • When “quiet” button at remote control is pressed.

Quiet LED illuminates.

b. Quiet operation stop condition

1. When one of the following conditions is satisfied, quiet operation stops:

a. Powerful button is pressed.

b. Stop by OFF/ON switch.

c. Timer “off” activates.

d. When change mode to fan only mode.

e. Quiet button is pressed again.

2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.

D. Control contents

1. Fan speed is changed from normal setting to quiet setting of respective fan speed.

This is to reduce sound of Hi, Me, Lo for 3dB.

2. Fan speed for quiet operation is -100 rpm from setting fan speed. (Cool and fan mode)

8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)

Automatic Fan Speed (Dry operation)

Panasonic CS-E18CKE — 8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode) diagram (page 26)
Fig. 33 · 8.1.10.1. Quiet operation under Soft Dry operation (…

Manual Fan Speed (Dry operation)

Panasonic CS-E18CKE — 8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode) diagram (page 26)
Fig. 34 · 8.1.10.1. Quiet operation under Soft Dry operation (…
Page 27 of the Panasonic CS-E18CKE user manual — 8.1.10.2. Quiet operation (Heating)
Page 27 · click to enlarge
Page 27

8.1.10.2. Quiet operation (Heating)

A. Purpose

To provide quiet heating operation compare to normal operation.

B. Control condition

a. Quiet operation start condition

  • When “quiet” button at remote control is pressed.

Quiet LED illuminates.

b. Quiet operation stop condition

1. When one of the following conditions is satisfied, quiet operation stops:

a. Powerful button is pressed.

b. Stop by OFF/ON switch.

c. Timer “off” activates.

d. When change mode to fan only mode.

e. Quiet button is pressed again.

2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.

C. Control contents

a. Fan Speed manual

1. Fan speed is changed from normal setting to quiet setting of respective fan speed.

This is to reduce sound of Hi, Me, Lo for 3dB.

2. Fan speed for quiet operation is -100 rpm from setting fan speed.
3. Fan Speed Auto
  • If FM

-100 rpm reduce from normal Heating Auto Fan Speed

  • If FM

Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.

Lo · Lo · maintain RPM

Page 28 of the Panasonic CS-E18CKE user manual — 8.1.13. Delay OFF Timer Control
Page 28 · click to enlarge
Page 28

8.1.11. Powerful Mode Operation

When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.

Panasonic CS-E18CKE — 8.1.11. Powerful Mode Operation diagram (page 28)
Fig. 35 · 8.1.11. Powerful Mode Operation

(b) Soft Dry Operation

Panasonic CS-E18CKE — 8.1.11. Powerful Mode Operation diagram (page 28)
Fig. 36 · 8.1.11. Powerful Mode Operation
Panasonic CS-E18CKE — 8.1.11. Powerful Mode Operation diagram (page 28)
Fig. 37 · 8.1.11. Powerful Mode Operation

8.1.12. Delay ON Timer Control

Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time.

Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.

From the above judgment, the decided operation will start operate earlier than the set time as shown below.

Panasonic CS-E18CKE — 8.1.12. Delay ON Timer Control diagram (page 28)
Fig. 38 · 8.1.12. Delay ON Timer Control

8.1.13. Delay OFF Timer Control

Delay OFF timer can be set using remote control, the unit with timer set will stop operate at set time.

(a) Cooling Operation · (c) Heating Operation

Page 29 of the Panasonic CS-E18CKE user manual — 8.1.16. Auto Operation Switch
Page 29 · click to enlarge
Page 29

8.1.14. Auto Restart Control

1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four

minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.

2. This type of control is not applicable during ON/OFF Timer setting.

8.1.15. Indication Panel

Panasonic CS-E18CKE — 8.1.15. Indication Panel diagram (page 29)
Fig. 39 · 8.1.15. Indication Panel

LED POWER MONITOR POWER QUIET TIMER POWERFUL ION Color Green Green Orange Orange Orange Green Light ON Compressor ON Operation ON Quiet Mode ON Timer Setting ON Powerful Mode ON Ion Mode ON Light OFF Compressor OFF Operation OFF Quiet Mode OFF Timer Setting OFF Powerful Mode OFF Ion Mode OFF

  • If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode

judgment, or delay ON timer sampling.

  • If Timer LED is blinking, there is an abnormality operation occurs.
  • If Ionizer, LED is blinking, there is an abnormality of Ionizer occurs.

Power Monitor LED Control Frequency

Lighting of 3 LED base on instructed running frequency from indoor unit to compressor at cool, dry & heating operation.

Cool, Dry Instructed Hz No

Heat Instructed Hz No

8.1.16. Auto Operation Switch

Panasonic CS-E18CKE — 8.1.16. Auto Operation Switch diagram (page 29)
Fig. 40 · 8.1.16. Auto Operation Switch
1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
3. When the switch is pressed between 8 to 11 seconds, the unit is forced to operate in Heating Mode.
4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control, the unit can be

changed to different controlling setting (4 type of transmission codes).

5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control signal

receiving sound can be cancelled or turned on.

Show 7 more labels / short text on this page
Position of LED · Hz · Hz · 59 Hz · Hz · Hz · 63 Hz
Page 30 of the Panasonic CS-E18CKE user manual — 8.1.18. Ionizer Operation
Page 30 · click to enlarge
Page 30

8.1.17. Indoor Power Relay Control

Power relay will turn on during operation or in progress of stopping operation. Although operation stops, the power relay continues on for three minutes.

However, during instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 2 minutes after power recover and the unit will operate as previous operation condition.

8.1.18. Ionizer Operation

To provide fresh air effect to users by discharging minus ion to air.

Panasonic CS-E18CKE — 8.1.18. Ionizer Operation diagram (page 30)
Fig. 41 · 8.1.18. Ionizer Operation

a. Ionizer Only Operation.

1. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed.

Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1 →2)

However, fan speed can be adjusted later by customer during this operation.

Panasonic CS-E18CKE — 8.1.18. Ionizer Operation diagram (page 30)
Fig. 42 · 8.1.18. Ionizer Operation

Airflow direction (Horizontal Vane) control:

Follow vane direction control at cooling mode.

Horizontal vane can be changed by customer during ion only operation.

b. Operation Mode + Ionizer Operation.

1. Ionising Operation Start Condition

When air conditioner unit is in “ON” condition (Heat, Cool, Dry, Fan, Auto mode) and ION operation button at remote control is pressed. Ionizer on & ION LED illuminates. (3 →4)

Power LED also illuminates.

2. Ionising Operation Stop Condition

When one of the following condition is satisfied, ION operation stops.

a. Stopped by ON/OFF switch.

b. Timer OFF activates.

c. ION operation button is pressed again.

d. ION feedback signal shows error.

Purpose · Control Condition

Page 31 of the Panasonic CS-E18CKE user manual — 8.1.18.2. Ionizer Operation case study
Page 31 · click to enlarge
Page 31
3. Ionizer operation status is not memorised by micon. After OFF, when operation is “ON” again, air conditioner operates

without ionizer operation.

c. Timer during ionizer operation

Refer to case study in next page for detail.

8.1.18.1. Ionizer Problem Detection Control

i. Purpose

To inform user of ionizer problems and detection.

ii. Two types of problem detection control:

Control Detection Method Protection Recovery

ERROR PROTECTION

(i) Actual ionON (i) Actual ion ON for 10s & OFF for

(i) Actual ion is permanently OFF & ion

(i) Press ON/OFF button

30 min. continuously for 24 times (approx. 11 hr. 30 min.)

LED is blinking.

(ii) ion feedback signal:

0V (ii) Within 24 counts, if anytime

(ii) Press remote control ion button for

CONDITION becomes false then count is cleared.

a) ON: Ion LED blink & buzzer = beep b) OFF: Ion LED OFF & buzzer = beep

Off by force operation

BREAKDOWN PROTECTION

Case 1: During Air-Con. ON. Air-Cond OFF with abnormal no. H26 is activated with timer LED is blinking permanently.

Actual ionOFF

(i) Actual ion OFF

CONDITION becomes false.

ion feedback signal5V

Case 2: During Air-Con. OFF. Abnormal no. H26 is activated with timer LED is blinking permanently for both cases 1 & 2.

(ii) Once recovered, ion &

Timer LED stops blinking permanently. (ii) Press remote control ion button for

a) ONIon LED blink b) OFF: Ion LED OFF

(iii) Main power reset.

(iii) Press any remote control button to

a) ONBuzzer = beep beep beep beep b) OFF: Buzzer = beep beep beep beep

8.1.18.2. Ionizer Operation case study

Panasonic CS-E18CKE — 8.1.18.2. Ionizer Operation case study diagram (page 31)
Fig. 43 · 8.1.18.2. Ionizer Operation case study
Show 10 more labels / short text on this page
to OFF · (ii) · Reset power · (iii) · (i) · 2s (i) · (i) When anytime · (ii) · (i) · Case 1
Page 32 of the Panasonic CS-E18CKE user manual — 8.2.1.3. Total Running Current Control
Page 32 · click to enlarge
Page 32

8.2. Protection Control Features

8.2.1. Protection Control For All Operations

8.2.1.1. Time Delay Safety Control

1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.

8.2.1.2. 30 Seconds Forced Operation

1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.

8.2.1.3. Total Running Current Control

1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be

decreased.

2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.

E21CK E18CK Operation Mode X (A) Y (A) X (A) Y (A) Cooling/Soft Dry (A) 11.0 15.0 8.8 15.0 Cooling/Soft Dry (B) 9.6 15.0 7.7 15.0 Heating 11.5 17.0 10.8 17.0

4. The first 30 minutes of cooling operation, (A) will be applied.
Panasonic CS-E18CKE — 8.2.1.3. Total Running Current Control diagram (page 32)
Fig. 44 · 8.2.1.3. Total Running Current Control
Page 33 of the Panasonic CS-E18CKE user manual — 8.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)
Page 33 · click to enlarge
Page 33

8.2.1.4. IPM (Power transistor) Prevention Control

A. Overheating Prevention Control

1. When the IPM temperature rises to 110°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95°C.

B. DC Peak Current Control

1. When electric current to IPM exceeds set value of 25.0 ± 4.0 A, the compressor will stop operate. Then, operation will restart

after three minutes.

2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two

minute.

3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.

If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.

8.2.1.5. Compressor Overheating Prevention Control

Instructed frequency for compressor operation will be regulated by compressor top temperature. The changes of frequency are as below figure.

Panasonic CS-E18CKE — 8.2.1.5. Compressor Overheating Prevention Control diagram (page 33)
Fig. 45 · 8.2.1.5. Compressor Overheating Prevention Control

8.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)

1. When the conditions listed in below table occur, the compressor stops and restarts after three minutes.
2. If this phenomenon is continuously occurring for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.

Conditions E18CK E21CK Cooling/Soft Dry Heating Cooling/Soft Dry Heating 1. Compressor frequency (Hz)

93 2. Outdoor total running current (A)

1.5 3. Indoor heat exchanger temperature (°C)

Page 34 of the Panasonic CS-E18CKE user manual — 38 T
Page 34 · click to enlarge
Page 34

8.2.1.7. CT Disconnection Detection

1. Control Starting Condition

a. Total Current is below 0.74 ~ 0.94 Amp.

b. Operating Frequency is 72 Hz (E18CK), 95 Hz (E21CK) +1 and above.

c. Continuously for 20s.

2. Control Contents

a. Abnormal signal transmitted to indoor unit after 3 minutes outdoor power is supplied. (Indoor unit stop)

3. Control Cancellation Condition

Starting condition, (1) is not fulfilled.

8.2.1.8. Low Frequency Protection Control 1

When the compressor operate at frequency lower than 22 Hz for 240 minutes, the operation frequency will be increased to 22 Hz for two minutes.

8.2.1.9. Low Frequency Protection Control 2

When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz.

Temperature, T, forCooling/Soft Dry Heating Indoor intake air (°C) T

28 Outdoor air (°C) T

30 T

24 Indoor heat exchanger (°C) T

38 T

30 T

8.2.1.10. Minimum Frequency Protection Control

  • During cooling operation (Anti Freezing control, soft dry) carry out the following operation.
1. During remote control setting is less than 28 deg

Indoor Fan Speed Above Hi minHz = 21 Above Me- minHz = 21 Less than Me- minHz = 18 Auto minHz = 16

2. During Powerful ON

However, when less than thermo OFF for 120 sec. continuously, the above control will be cancel.

  • During heating operation, operate the followings control.
1. During Remote Control setting is less than 18 deg

Indoor Fan Speed Above Hi minHz = 30 Above Lo minHz = 25 Less than Lo minHz = 15

2. During Powerful ON

However, when less than thermo OFF for 100 sec. continuously, the above control will be cancel.

Show 6 more labels / short text on this page
15 or T · 14 or T · 13 or T · 4 or T · minHz = 22 · minHz = 35
Page 35 of the Panasonic CS-E18CKE user manual — 8.2.2.2. Cooling Overload Control
Page 35 · click to enlarge
Page 35

8.2.2. Protection Control For Cooling & Soft Dry Operation

8.2.2.1. Outdoor Air Temperature Control

The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.

Panasonic CS-E18CKE — 8.2.2. Protection Control For Cooling & Soft Dry Operation diagram (page 35)
Fig. 46 · 8.2.2. Protection Control For Cooling & Soft Dry Ope…

8.2.2.2. Cooling Overload Control

i. Pipe temperature limitation/restriction

  • Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)
  • The compressor stop if outdoor pipe temperature exceeds 63°C
  • If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)
Panasonic CS-E18CKE — 8.2.2.2. Cooling Overload Control diagram (page 35)
Fig. 47 · 8.2.2.2. Cooling Overload Control

ii. Electrical part temperature rise protection control

  • To prevent electrical component temperature rise during cooling overload.
  • Judgement condition is by outdoor temperature (sampled every 10s).
  • Control contents:

Outdoor fan speed (switch to zone A and B minimum fan speed).

Outdoor total current (zone C) higher than the specified.

  • Cancellation condition: When one of above is not satisfied.
Page 36 of the Panasonic CS-E18CKE user manual — 8.2.2.4. Anti-Dew Formation Control
Page 36 · click to enlarge
Page 36
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 36)
Fig. 48 · 8.2. Protection Control Features

8.2.2.3. Anti-Freezing Control

1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
Panasonic CS-E18CKE — 8.2.2.3. Anti-Freezing Control diagram (page 36)
Fig. 49 · 8.2.2.3. Anti-Freezing Control

8.2.2.4. Anti-Dew Formation Control

  • During anti-dew formation control, compressor operates at frequency shift as shown below when indoor fan speed is less

than Me.

Panasonic CS-E18CKE — 8.2.2.4. Anti-Dew Formation Control diagram (page 36)
Fig. 50 · 8.2.2.4. Anti-Dew Formation Control
  • This control is cancelled after started for 420 minutes, or remote control setting temperature or fan speed setting is changed.
  • When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled and air vane change

Horizontal vane shift to 2nd position and Vertical vane shift to center position.

1. Indoor intake air temperature is 25°C or above and less than 29°C.
2. Outdoor air temperature is less than 30°C.
3. Air vane control: Manual Horizontal Airflow and Manual Vertical Airflow.
4. Fan speed is quiet Lo.

a) Control 1 · b) Control 2

Page 37 of the Panasonic CS-E18CKE user manual — 8.2.3. Protection Control For Heating Operation
Page 37 · click to enlarge
Page 37

8.2.3. Protection Control For Heating Operation

8.2.3.1. Anti Cold Draft Control

Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown below.

1. Manual Fan Speed
Panasonic CS-E18CKE — 8.2.3. Protection Control For Heating Operation diagram (page 37)
Fig. 51 · 8.2.3. Protection Control For Heating Operation
2. Auto Fan Speed
Panasonic CS-E18CKE — 8.2.3. Protection Control For Heating Operation diagram (page 37)
Fig. 52 · 8.2.3. Protection Control For Heating Operation
Page 38 of the Panasonic CS-E18CKE user manual — 8.2.3.3. Outdoor Air Temperature Control
Page 38 · click to enlarge
Page 38

a. UP:

  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E21CK), 1480 rpm (E18CK).

b. DOWN:

  • The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.

c. Current Output Fixed:

  • Maintain at present fan speed.

d. Instantaneous Maximum:

  • Fan speed will be increased to maximum auto fan speed.

e. Temperature in ( ) is for Powerful Mode operation.

8.2.3.2. Intake Air Temperature Control

Compressor will operate at maximum of 128 Hz respectively if either one of the below conditions occur:

1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
2. When the indoor intake air temperature is 30°C or above.

8.2.3.3. Outdoor Air Temperature Control

The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This control will begin one minute after the compressor starts.

Panasonic CS-E18CKE — 8.2.3.3. Outdoor Air Temperature Control diagram (page 38)
Fig. 53 · 8.2.3.3. Outdoor Air Temperature Control
Page 39 of the Panasonic CS-E18CKE user manual — 8.2.3.5. Outdoor Temperature Control
Page 39 · click to enlarge
Page 39

8.2.3.4. Overload Protection Control

The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.

Panasonic CS-E18CKE — 8.2.3.4. Overload Protection Control diagram (page 39)
Fig. 54 · 8.2.3.4. Overload Protection Control

8.2.3.5. Outdoor Temperature Control

  • Outdoor temperature is detected and the following control is perform.
  • Control operates after more than 1 minute the compressor has started.
Panasonic CS-E18CKE — 8.2.3.5. Outdoor Temperature Control diagram (page 39)
Fig. 55 · 8.2.3.5. Outdoor Temperature Control
Page 40 of the Panasonic CS-E18CKE user manual — 8.2.3.6. Deice Control
Page 40 · click to enlarge
Page 40

8.2.3.6. Deice Control

A. Deice operation (Normal Deice Operation)

1. Detection methods

Outdoor heat exchanger temperature sensor, timer.

2. Deice operation time chart
Panasonic CS-E18CKE — 8.2.3.6. Deice Control diagram (page 40)
Fig. 56 · 8.2.3.6. Deice Control

a. During deice operation, the relationship between outdoor pipe temperature and time T1 is such operation will

proceed to next stage.

b. The deice will be performed only after 1 hour from when the operation has started.

c. When Comp. OFF by the sequence No. 1, 6, 7 compressor can restart back without 3 minutes waits (immediate

restart).

Panasonic CS-E18CKE — 8.2.3.6. Deice Control diagram (page 40)
Fig. 57 · 8.2.3.6. Deice Control

Outdoor heat exchanger temperature

a 15°C b 18°C c 25°C

Page 41 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 41 · click to enlarge
Page 41
3. Explanation of operation
1. Before the deice is started, compressor frequency is set to the specified value for T0-timer.
2. After deice is started, the 4-way valve, OD Fan and ID fan are OFF.
3. After 4-way valve is OFF for 30 s, compressor frequency is set to the specified value.
4. Before deice is ended, if the outdoor heat exchanger temperature exceeds a°C, set compressor frequency and expansion valve to the specified values.
5. When outdoor heat exchanger temperature exceeds b°C, or 10.5 minutes has passed since the 4-way valve is OFF, operation at timer T5 will be started.
6. After the above 5) operation, if the specified time has passed, the deice operation ending signal will be produced. The comp. Hz is set to the specified value and at the same time outdoor fan motor ON signal is produced.
7. After T6 the deice ending signal is produced, 4-way valve is set to ON, indoor fan is ON, Compressor frequency is FREE, and return to normal heating operation.
4. Deice operation judgement condition

When any of below a, b, c, d condition is satisfied, deice signal is produced.

a. Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature

-5°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.

b. Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature < -

6°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.

c. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -

7°C and outdoor air temperature

-3°C for 3 minutes and Comp. is ON.

d. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -

8°C for 3 minutes and outdoor air temperature < -3°C and Comp. is ON.

However, the first deice will start only after minimum of 60 minutes in operation.

(2nd deice and onward shall follow above conditions)

B. Auto clean deice

1. Purpose

To improve heating start-up operation by detecting the residual ice on OD heat exchanger and perform deice operation automatically before operation is started by ON Timer.

2. Control Content:

1). Auto deice is performed 15 min. before standby operation (pre-deice operation in 15 min.).

2). When below deice conditions are fulfilled, auto clean deice operation will start.

3). After auto clean deice is completed, standby operation is performed as per load.

4). When deice conditions are not fulfilled, auto clean deice will not happen and will continue with standby operation.

Page 42 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 42 · click to enlarge
Page 42
3. Deice condition:

OD air temp. t

0°C.

OD heat exchanger temp.

0°C for 14 min.

OD heat exchanger temp.

-8°C for 10 min.

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 42)
Fig. 58 · 8.2. Protection Control Features
4. Auto clean deice time chart

Similar to deice operation 2 except for frequency values.

a. Detection methods

Outdoor heat exchanger temp. sensor, timer, indoor air temp. sensor.

b. Deice operation control time chart.

Page 43 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 43 · click to enlarge
Page 43
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 43)
Fig. 59 · 8.2. Protection Control Features
1. During deice operation, the relationship between outdoor pipe temperature and time T1 is such proceed to next

operation.

2. The deice will be performed only after 1 hour from when the operation has started.
3. When Comp. OFF by the sequence No. 1, 6, 7 compressor can restart back without 3 minutes waits (immediate restart).
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 43)
Fig. 60 · 8.2. Protection Control Features

Outdoor heat exchanger pipe temperature

a 15°C b 18°C c 25°C

Page 44 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 44 · click to enlarge
Page 44
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 44)
Fig. 61 · 8.2. Protection Control Features
Page 45 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 45 · click to enlarge
Page 45
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 45)
Fig. 62 · 8.2. Protection Control Features
Page 46 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 46 · click to enlarge
Page 46
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 46)
Fig. 63 · 8.2. Protection Control Features

or Set time Confirm OFF or Set time Confirm ON & OFF Timer Timer Timer

Page 47 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 47 · click to enlarge
Page 47
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 47)
Fig. 64 · 8.2. Protection Control Features
Page 48 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 48 · click to enlarge
Page 48
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 48)
Fig. 65 · 8.2. Protection Control Features
Page 49 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 49 · click to enlarge
Page 49
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 49)
Fig. 66 · 8.2. Protection Control Features
Page 50 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 50 · click to enlarge
Page 50
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 50)
Fig. 67 · 8.2. Protection Control Features

Do NOT pull out the plug by the cable

Do NOT insert finger or other objects into the unit! —> especially dangerous for children!

Page 51 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 51 · click to enlarge
Page 51
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 51)
Fig. 68 · 8.2. Protection Control Features
Page 52 of the Panasonic CS-E18CKE user manual — 10.1.1. About R410A Refrigerant
Page 52 · click to enlarge
Page 52

10 Installation And Servicing Air Conditioner Using R410A

10.1. OUTLINE

10.1.1. About R410A Refrigerant

1. Converting air conditioners to R410A

Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction. The R22 refrigerant which has conventionally been used in ACs is an HCFC refrigerant and, therefore, possesses this ozone- destroying potential. International regulations (the Montreal Protocol Ozone-Damaging Substances) and the domestic laws of various countries call for the early substitution of R22 by a refrigerant which will not harm the ozone layer.

  • In ACs, the HFC refrigerant which has become the mainstream alternative called <a href="http://R410A.Com" rel="nofollow noopener" target="_blank">R410A.Com</a>pared with R22, the pressure

of R410A is approximately 1.6 times as high at the same refrigerant temperature, but the energy efficiency is about the same. Consisting of hydrogen (H), fluorine (F) and carbon (C), R410A is an HFC refrigerant. Another typical HFC refrigerant is R407C. While the energy efficiency of R407C is some what inferior to that of R410A, it offers the advantage of having pressure characteristics which are about the same as those of R22, and is used mainly in packaged ACs.

2. The characteristics of HFC (R410A) refrigerants

a. Chemical characteristics

The chemical characteristics of R410A are similar to those of R22 in that both are chemically stable, non-flammable refrigerants with low toxicity. However, just like R22, the specific gravity of R410A gas is heavier than that of air. Because of this, it can cause an oxygen deficiency if it leaks into a closed room since it collects in the lower area of the room. It also generates toxic gas when it is directly exposed to a flame, so it must be used in a well ventilated environment where it will not collect.

Table 1 Physical comparison of R410A and R22

R410A R22 Composition (wt%) R32/R125 (50/50) R22 (100) Boiling point (°C) -51.4 -40.8 Vaporizing pressure (25°C) 1.56 Mpa (15.9 kgf/cm2) 0.94 Mpa (9.6 kgf/cm2) Saturated vapor density 64.0 kg/m3 44.4 kg/m3

Flammability Non-flammable Non-flammable Ozone-destroying point (ODP) 0 0.005 Global-warming point (GWP) 1730 1700

b. Compositional change (pseudo-azeotropic characteristics)

R410A is a pseudo-azeotropic mixture comprising the two components R32 and R125. Multi-component refrigerants with these chemical characteristics exhibit little compositional change even from phase changes due to vaporization 9or condensation), which means that there is little change in the circulating refrigerant composition even when the refrigerant leaks from the gaseous section of the piping. Accordingly, R410A can be handled in almost the same manner as the single-component refrigerant R22. However, when charging, because there is a slight change in composition between the gas phase and the liquid phase inside a cylinder or other container, charging should basically begin with the liquid side.

c. Pressure characteristics

As seen in Table 2, the gas pressure of R410A is approximately 1.6 times as high as that of R22 at the same refrigerant temperature, which means that special R410A tools and materials with high-pressure specifications must be used for all refrigerant piping work and servicing.

Table 2 Comparison of R410A and R22 saturated vapor density

Unit: MPa Refrigerant Temperature (°C) R410A R22 -20 0.30 0.14 0 0.70 0.40 20 1.35 0.81 40 2.32 1.43 60 3.73 2.33 65 4.15 2.60

Page 53 of the Panasonic CS-E18CKE user manual — 10.2.1. Necessary Tools
Page 53 · click to enlarge
Page 53

d. R410A refrigerating machine oil

Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have a high compatibility with R410A are used as refrigerating machine oil. Because of the high hygroscopic property of synthetic oil, more care must be taken in its handling than was necessary with conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene, causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.

10.1.2. Safety Measure When Installing / Receiving Refrigerant Piping

Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake in installation or servicing could result in a major accident. It is essential that you use R410a tools and materials, and that you observe the following precautions to ensure safety.

1. Do not use any refrigerant other than R410A in ACs that have been used with R410A.
2. If any refrigerant gas leaks while you are working, ventilate the room. Toxic gas may be generated if refrigerant gas is exposed

to a direct flame.

3. When installing or transferring an AC, do not allow any air or substance other than R410A to mix into the refrigeration cycle. If

it does, the pressure in the refrigeration cycle can become abnormally high, possibly causing an explosion and/or injury.

4. After finishing the installation, check to make sure there is no refrigerant gas leaking.
5. When installing or transferring an AC, follow the instructions in the installation instructions carefully. Incorrect installation can

result in an abnormal refrigeration cycle or water leakage, electric shock, fire, etc.

6. Do not perform any alterations on the AC unit under any circumstances. Have all repair work done by a specialist. Incorrect

repairs can result in an water leakage, electric shock, fire, etc.

10.2. TOOL FOR INSTALLING / SERVICING REFRIGERANT PIPING

10.2.1. Necessary Tools

In order to prevent an R410A AC from mistakenly being charged with any other refrigerant, the diameter of the 3-way valve service port on the outdoor unit has been changed. Also, to increase its ability to withstand pressure, the opposing dimensions have been changed for the refrigerant pipe flaring size and flare nut. Accordingly, when installing or servicing refrigerant piping, you must have both the R410A and ordinary tools listed below.

Table 3 Tools for installation, transferring or replacement Type of work Ordinary tools R410A tools Flaring Flaring tool (clutch type), pipe cutter, reamer

Copper pipe gauge for clearance Adjustment, flaring tool (clutch type)*1) Bending, connecting pipes Torque wrench (nominal diameter 1/4, 3/8,1/2) Fixed spanner (opposing sides 12 mm, 17 mm, 19 mm)Adjustable wrench, Spring bender Air purging Vacuum pump Hexagonal wrench (opposing sides 4 mm)

Manifold gauge, charging hose, vacuum pump adaptor Gas leak inspection Gas leak inspection fluid or soapy water Electric gas leak detector for HFC refrigerant*2)

*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.

*2) Use when it is necessary to detect small gas leaks.

For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.

Table 4 Tools for serving Type of work Ordinary tools R410A tools Refrigerant charging Electronic scale for refrigerant charging Refrigerant cylinder Charging orifice and packing for refrigerant cylinder Brazing (Replacing refrigerating cycle part*1)

Nitrogen blow set (be sure to use nitrogen blowing for all brazing), and brazing), and brazing machine

*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming operation within 2 hours.

Page 54 of the Panasonic CS-E18CKE user manual — 10.2.2. R410A Tools
Page 54 · click to enlarge
Page 54

10.2.2. R410A Tools

Panasonic CS-E18CKE — 10.2.2. R410A Tools diagram (page 54)
Fig. 69 · 10.2.2. R410A Tools
1. Cooper tube gauge for clearance adjustment

(used when flaring with the conventional flaring tool (clutch type))

  • This gauge makes it easy to set the clearance for the

copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.

Fig. 1 Copper tube gauge for clearance adjustment

Panasonic CS-E18CKE — 10.2.2. R410A Tools diagram (page 54)
Fig. 70 · 10.2.2. R410A Tools
2. Flaring tool (clutch type)
  • In the R410A flaring tool, the receiving hole for the

clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the pipe- expanding torque. This flaring tools can also be used with R22 piping, so we recommend that you select it if you are buying a new flaring tool.

Fig. 2 Flaring tool (clutch type)

Panasonic CS-E18CKE — 10.2.2. R410A Tools diagram (page 54)
Fig. 71 · 10.2.2. R410A Tools
3. Torque wrenches

Fig. 3 Torque wrenches

Table 5 Conventional wrenches R410A wrenches For 1/4 (opposite side x torque) 17 mm x 18 N.m (180 kgf.cm) 17 mm x 18 N.m (180 kgf.cm) For 3/3 (opposite side x torque) 22 mm x 42 N.m (180 kgf.cm) 22 mm x 42 N.m (180 kgf.cm) For 1/2 (opposite side x torque) 24 mm x 55 N.m (180 kgf.cm) 26 mm x 55 N.m (180 kgf.cm)

4. Manifold gauge
  • Because the pressure is higher for the R410A type, the conventional type cannot be used.

Table 6 Difference between R410A and conventional high / low-pressure gauges

Conventional wrenches R410A wrenches High-pressure gauge (red) -76 cmHg - 35 kgf/cm3 -0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm3

High-pressure gauge (blue) -76 cmHg - 17 kgf/cm3 -0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm3

  • The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of

refrigerant.

Table 7 Difference between R410A and conventional manifold port size

Conventional gauges R410A gauges Port size 7/6 UNF 20 threads 1/2 UNF 20 threads

Page 55 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 55 · click to enlarge
Page 55
5. Charging hose
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 55)
Fig. 72 · 8.2. Protection Control Features
  • The pressure resistance of the charging hose has been

raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.

Fig. 4 Manifold gauge charging hose

Table 8 Difference between R410A and conventional charging hoses

Conventional hoses R410A hoses Pressure resistance

Working pressure 3.4 MPa (35 kgf/cm3) 5.1 MPa (52 kgf/cm3) Bursting pressure 17.2 MPa (175 kgf/cm3) 27.4 MPa (280 kgf/cm3) Material NBR rubber HNBR rubber Nylon coating inside

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 55)
Fig. 73 · 8.2. Protection Control Features
6. Vacuum pump adaptor
  • When using a vacuum pump for R410A, it is necessary

to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the vacuum pump oil (mineral oil) becomes mixed with R410A, it will damage the unit.

Fig. 5 Vacuum pump adaptor

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 55)
Fig. 74 · 8.2. Protection Control Features
7. Electric gas leak detector for HFC refrigerant
  • The leak detector and halide torch that were used with

CFC and HCFC cannot be used with R410A (because there is no chlorine in the refrigerant).

  • The present R134a leak detector can be used, but the

detection sensitivity will be lower (setting the sensitivity for R134a at 1, the level for R410A will drop to 0.6).

  • For detecting small amounts of gas leakage, use the

electric gas leak detector for HFC refrigerant. (Detection sensitivity with R410A is about 23 g/year).

Fig. 6 Electric gas leak detector for HFC refrigerant

Page 56 of the Panasonic CS-E18CKE user manual — 10.2.3. R410A Tools Which Are Usable for R22 Models
Page 56 · click to enlarge
Page 56
8. Electronic scale for refrigerant charging
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 56)
Fig. 75 · 8.2. Protection Control Features
  • Because of the high pressure and fast vaporizing speed

of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinder cannot be used because of the differences in the pressure resistance, scale gradation, connecting port size, etc.)

  • The electronic scale has been strengthened by using a

structure in which the weight detector for the refrigerant cylinder is held by four supports. It is also equipped with two connection ports, one for R22 *7/16 UNF, 20 threads) and one for R410A (1/2 UNF, 20 threads), so it can also be used for conventional refrigerant charging.

Fig. 7 Electronic scale for refrigerant charging

  • There are two types of electronic scales, one for 10-kg

cylinders and one for 20-kg cylinders. (The 10-kg cylinder is recommended.)

Refrigerant charging is done manually by opening and closing the valve.

9. Refrigerant cylinders
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 56)
Fig. 76 · 8.2. Protection Control Features
  • The R410A cylinders are labeled with the refrigerant

name, and the coating color of the cylinder protector is pink, which is the color stipulated by ARI of the U.S.

  • Cylinder equipped with a siphon tube are available to

allow the cylinder to stand upright for liquid refrigerant charging.

Fig. 8 Refrigerant cylinders

10. Charging orifice and packing for refrigerant cylinders
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 56)
Fig. 77 · 8.2. Protection Control Features
  • The charging orifice must match the size of the charging

hose fitting (1/2 UNF, 20 threads).

  • The packing must also be made of an HFC-resistant

material.

Fig. 9 Charging orifice and packing

10.2.3. R410A Tools Which Are Usable for R22 Models

Table 9 R410A tools which are usable for R22 models

R410A tools Usable for R22 models (1) Copper tube gauge for clearance adjustment OK (2) Flaring tool (clutch type) OK (3) Manifold gauge NG (4) Charging hose NG (5) Vacuum pump adaptor OK (6) Electric gas leak detector for HFC refrigerant NG (7) Electronic scale for refrigerant charging OK (8) Refrigerant cylinder NG (9) Charging orifice and packing for refrigerant cylinder NG

Page 57 of the Panasonic CS-E18CKE user manual — 10.3.2. Processing and Connecting Piping Materials
Page 57 · click to enlarge
Page 57

10.3. REFRIGERANT PIPING WORK

10.3.1. Piping Materials

It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not used pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries. Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materials that are appropriate for these standards. The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing with a thickness of only 0.7 mm is also available on the market, but this should never be used.

Table 10 Difference between R410A and conventional copper tube Soft pipe Thickness (mm) Nominal diameter Outside diameter (mm) R410A (Reference) R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.7 0.80 0.80

10.3.2. Processing and Connecting Piping Materials

When working with refrigerant piping, the following points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks.

Panasonic CS-E18CKE — 10.3.2. Processing and Connecting Piping Materials diagram (page 57)
Fig. 78 · 10.3.2. Processing and Connecting Piping Materials
1. Procedure and precautions for flaring work

a. Cut the pipe

Use a pipe cutter, and cut slowly so the pipe will not be deformed.

b. Remove burrs and clean shavings from the cut surface

If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may lead to refrigerant leaks. To prevent this, turn the cut surface downward and remove burrs, then clean the surface, carefully.

Fig. 10 Flaring dimensions

c. Insert the flare nut (be sure to used the same nut that is

used on the AC unit)

d. Flaring

Check the clamp bar and the cleanliness of the copper pipe. Be sure to sued the clamp bar to do the flaring with accuracy. Use either an R410A flaring tool, or a conventional flaring tool. flaring tools come in different sizes, so be sure to check the size before using. When using a conventional flaring tool, use the copper pipe gauge for clearance adjustment, etc., to ensure the correct A dimension (see Fig. 10)

Panasonic CS-E18CKE — 10.3.2. Processing and Connecting Piping Materials diagram (page 57)
Fig. 79 · 10.3.2. Processing and Connecting Piping Materials

Fig. 11 Relation between the flare nut structure and flaring tool end

Page 58 of the Panasonic CS-E18CKE user manual — 10.3.3. Storing and managing Piping Materials
Page 58 · click to enlarge
Page 58

Table 11 R410A flaring dimensions Nominal diameter

A (mm) R410A flaring tool, clutch type

Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 3/8 9.52 0.8 0 - 0.5 1.0 - 1.5 1.5 - 2.0 1/2 12.70 0.8 0 - 0.5 1.0 - 1.5 2.0 - 2.5

Table 12 R410A flaring dimensions Nominal diameter

A (mm) R410A flaring tool, clutch type

Conventional flaring tool Clutch type Wing-nut type 1/4 6.35 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 3/8 9.52 0.8 0 - 0.5 0.5 - 1.0 1.0 - 1.5 1/2 12.70 0.8 0 - 0.5 0.5 - 1.0 1.5 - 2.0

Table 13 R410A flaring and flare nut dimensions Unit: mm Nominal diameter

A +0, -0.4 B dimension

width 1/4 6.35 0.8 9.1 9.2 6.5 13 17 3/8 9.52 0.8 13.2 13.5 9.7 20 22 1/2 12.70 0.8 16.6 16.0 12.9 23 26

Table 14 R410A flaring and flare nut dimensions Unit: mm Nominal diameter

A +0, -0.4 B dimension

width 1/4 6.35 0.8 9.0 9.2 6.5 13 17 3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24

2. Procedure and precautions for flare connection

a. Check to make sure there are no scratches, dust, etc., on the flare and union.

b. Align the flared surface with the axial center of the union.

c. Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional

torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split the flare nut or make it impossible to remove the flare nut.

Table 15 R410A tightening torque Nominal diameter

Torque wrench tightening torque

N.m (kgf.cm) 1/4 6.35 14 - 18 (140 - 180) 18 (180) 3/8 9.52 33 - 42 (330 -420) 42 (420) 1/2 12.70 55 (550) 55 (550)

N.m (kgf.cm)

10.3.3. Storing and managing Piping Materials

1. Types of piping and their storage

The following is a general classification of the refrigerant pipe materials used for ACs.

Panasonic CS-E18CKE — 10.3.3. Storing and managing Piping Materials diagram (page 58)
Fig. 80 · 10.3.3. Storing and managing Piping Materials

Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.

2. Makings and management

a. Sheathed copper pipes and copper-element pipes

When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit.

Show 22 more labels / short text on this page
Outside diameter · Wall thickness · (mm) · (mm) · Outside diameter · Wall thickness · (mm) · (mm) · Outside diameter (mm) · Wall thickness · C dimension · D dimension · Flare nut · (mm) · Outside diameter (mm) · Wall thickness · C dimension · D dimension · Flare nut · (mm) · Outside diameter (mm) · Tightening torque
Page 59 of the Panasonic CS-E18CKE user manual — 10.4. INSTALLATION, TRANSFERRING, SERVICING
Page 59 · click to enlarge
Page 59

b. Copper pipes

Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.

3. Precautions during refrigerant piping work

Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and dust is even more important that in conventional piping).

a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.

b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil,

and lead to malfunctions in the equipment.

c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing

the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.

10.4. INSTALLATION, TRANSFERRING, SERVICING

10.4.1. Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New Refrigerant Piping)

1. From the viewpoint of protecting the global environment, please do not release refrigerant into the atmosphere.

a. Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way

valve. (1)

b. Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge

instantly reaches vacuum, re-check step a).)

c. Continue the vacuum process for at least 15 minutes, then check to make sure the low-pressure gauge has reached -0.1

MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)

d. Turn the valve stem of the 2-way valve 90 counter-clockwise to open it, then, after 10 seconds, close it and inspect for a gas

e. Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn

the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).

f. Tighten the service port cap with a torque wrench (18 N.m (1.8 kgf.m)). (5) Then tighten the 2-way valve and 3-way valve

caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)).

g. After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)

Panasonic CS-E18CKE — 10.4. INSTALLATION, TRANSFERRING, SERVICING diagram (page 59)
Fig. 81
  • Be sure to read the instructions for the vacuum pump,

vacuum pump adaptor and manifold gauge prior to use, and follow the instructions carefully.

  • Make sure that the vacuum pump is filled with oil up to

the designated line on the oil gauge.

  • The gas pressure back flow prevention valve on the

charging hose is generally open during use. When you are removing the charging hose from the service port, it will come off more easily if you close this valve.

Fig. 12 Vacuum pump air purging configuration

leak (4) · Precautions

Page 60 of the Panasonic CS-E18CKE user manual — 10.4.5. Recharging Refrigerant During Servicing
Page 60 · click to enlarge
Page 60

10.4.2. Transferring (Using New Refrigerant Piping)

1. Removing the unit

a. Collecting the refrigerant into the outdoor unit by pumping down

The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.

  • Check to make sure that the valve stems of the 2-way valve and 3-way valve have been opened by turning them counter-

clockwise. (Remove the valve stem caps and check to see that the valve stems are fully opened position. Always use a hex wrench (with 4-mm opposing sides) to operate the valve stems.)

  • Press the TEST RUN button on the indoor unit, and allow preliminary for 5-6 minutes. (TEST RUN mode)
  • After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in

the clockwise direction.

  • Press the TEST RUN button on the indoor unit again, and after 2-3 minutes of operation, turn the valve stem of the 3-

way valve quickly in the clockwise direction to close it, then stop the operation.

  • Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.
  • Remove the connection pipes (liquid side and gas side).
2. Installing the unit

Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor and outdoor units, and the pipes of the indoor unit, and check for gas leaks.

10.4.3. AC Units Replacement (Using Existing Refrigerant Piping)

When replacing and R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil is different. When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section 10.1.1.(2)). In this case, you should use new refrigerant piping rather than the existing piping.

1. Piping check

Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times different. the wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections of the piping also cannot be checked.

2. Pipe cleaning

A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is difficult with the present technology.

10.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)

Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.

10.4.5. Recharging Refrigerant During Servicing

When recharging is necessary, insert the specified amount of new refrigerant in accordance with the following procedure.

1. Connect the charging hose to the service port of the outdoor unit.
2. Connect the charging hose to the vacuum pump adaptor. At this time, fully open the 2-way valve and 3-way valve.
3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuum process for

at least one hour.

4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo, and turn off the

vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge has not returned. See Fig. 13 for the remaining steps of this procedure.

Page 61 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 61 · click to enlarge
Page 61
5. Set the refrigerant cylinder onto the electronic scale, then correct the hose the cylinder and to the connection port for the

electronic scale. (1)(2)

Precaution:

Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid without having to turn the cylinder around

6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the

electronic scale. (2)(3)

7. Open the valve of the refrigerant cylinder, then open the charging valve slightly and close it. Next, press the check valve of the

manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.)

8. After adjusting the electronic scale to zero, open the charging valve, then open the valve Lo of the manifold gauge and charge

with the liquid refrigerant. (2)(5) (Be sure to read the operating instructions for the electronic scale.)

9. If you cannot charge the stipulated amount, operate the unit in the cooling mode while charging a little of the liquid at a time

(about 150 g/time as a guideline). If the charging amount is insufficient from one operation, wait about one minute, then use the same procedure to do the liquid charging again.

Precaution:

Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit.

10. Close the charging valve, and after charging the liquid refrigerant inside the charging hose, fully close the valve Lo of the

manifold gauge, and stop the operation of the unit. (2)(5)

11. Quickly remove the charging hose from the service port. (6) If you stop midway through, the refrigerant that is in the cycle will

be discharged.

12. After putting on the caps for the service port and operating valve, inspect around the caps for a gas leak. (6)(7)
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 61)
Fig. 82 · 8.2. Protection Control Features

Fig. 13 Re-charging refrigerant

Page 62 of the Panasonic CS-E18CKE user manual — 10.4.7. Servicing Tips
Page 62 · click to enlarge
Page 62

10.4.6. Brazing

As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N2) flow.

<Brazing Method for Preventing Oxidation>

1. Attach a reducing valve to the nitrogen gas cylinder.
2. Attach a reducing valve to the nitrogen gas cylinder.
3. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas

from flowing backward.

4. When the nitrogen gas is flowing, be sure to keep the piping end open.
5. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m 3 /h, or 0.02 MPa (0.2 kgf/cm 2 ) by means of the reducing valve.
6. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at

which pipes are touchable with finger).

7. Completely remove the flux after brazing.
Panasonic CS-E18CKE — 10.4.6. Brazing diagram (page 62)
Fig. 83 · 10.4.6. Brazing
1. General Cautions

a. The brazing strength should be high as required.

b. After operation, airtightness should be kept under pressurized condition.

c. During brazing do not allow component materials to become damaged due to overheating.

d. The refrigerant pipe work should not become blocked with scale or flux.

e. The brazed part should not restrict the flow in the refrigerant circuit.

f. No corrosion should occur from the brazed part.

2. Preventing of Overheating

Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So, make brazing at adequate brazing temperature and with minimum of heating area.

3. Overheating Protection

In order to prevent components near the brazed part from overheating damaged or quality deterioration due to flame or heat, take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means of heat absorbent.

4. Movement during Brazing

Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.

5. Oxidation Preventative

In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.

10.4.7. Servicing Tips

The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has leaked completely. (Applicable for drier models only)

Page 63 of the Panasonic CS-E18CKE user manual — 11.1. Safety Precautions
Page 63 · click to enlarge
Page 63

11 Installation Instructions

Required tools for Installation Works 1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter 2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench 18 NGm (1.8 kgfGm) 55 NGm (5.5 kgfGm) 65 NGm (6.5 kgfGm) 3. Electric drill, hole core drill (ø70 mm)

7. Reamer 11. Thermometer 15. Vacuum pump
4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold

11.1. Safety Precautions

  • Read the following “SAFETY PRECAUTIONS” carefully before installation.
  • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit

for the model to be installed.

  • The caution items stated here must be followed because these important contents are related to safety. The meaning of each

indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

This indication shows the possibility of causing death or serious injury.

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

  • Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and

maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire. 2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock. 4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. 5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 6. Use the specified cable (2.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. 8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

9. When connecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and injury.
10. • When connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials.
  • Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8

mm.

  • It is desirable that the amount of residual oil is less than 40 mg/10 m.
11. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
Page 64 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 64 · click to enlarge
Page 64
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

1. Selection of the installation location. Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance. 2. Power supply connection to the room air conditioner. Connect the power supply cord of the room air conditioner to the mains using one of the following method. Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the receptacle using a power plug.

Use an approved 16A power plug with earth pin for 2.0HP (E18CK, E21CK) for the connection to the socket.

2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for 2.0HP (E18CK,

E21CK) for the permanent connection. It must be a double pole switch with a minimum 3 mm contact gap. 3. Do not release refrigerant. Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite. 4. Installation work. It may need two people to carry out the installation work. 5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

Page 65 of the Panasonic CS-E18CKE user manual — OUTDOOR UNIT
Page 65 · click to enlarge
Page 65
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 65)
Fig. 84 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 65)
Fig. 85 · 8.2. Protection Control Features

Indoor/Outdoor Unit Installation Diagram

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 65)
Fig. 86 · 8.2. Protection Control Features

CZ-4F5, 7, 10AN (E18CK, E21CK)

SELECT THE BEST LOCATION

INDOOR UNIT

  • There should not be any heat source or steam near the

unit.

  • There should not be any obstacles blocking the air

circulation.

  • A place where air circulation in the room is good.
  • A place where drainage can be easily done.
  • A place where noise prevention is taken into consideration.
  • Do not install the unit near the door way.
  • Ensure the spaces indicated by arrows from the wall,

ceiling, fence or other obstacles.

  • Recommended installation height for indoor unit shall be

at least 2.3 m.

OUTDOOR UNIT

  • If an awning is built over the unit to prevent direct

sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

  • There should not be any animal or plant which could be

affected by hot air discharged.

  • Keep the spaces indicated by arrows from wall, ceiling,

fence or other obstacles.

  • Do not place any obstacles which may cause a short

circuit of the discharged air.

  • This illustration is for explanation purposes only.
  • If piping length is over 10m, additional refrigerant should

The indoor unit will actually face a different way.

be added as shown in the table.

Attached accessories · Applicable piping kit

Page 66 of the Panasonic CS-E18CKE user manual — 11.2.4. INDOOR UNIT INSTALLATION
Page 66 · click to enlarge
Page 66

11.2. INDOOR UNIT

11.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section)

11.2.3. TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING

11.2.2. HOW TO FIX INSTALLATION PLATE

1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the wall.

The mounting wall is strong and solid enough to prevent it from the vibration.

When the wall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable.

Panasonic CS-E18CKE — 11.2.2. HOW TO FIX INSTALLATION PLATE diagram (page 66)
Fig. 87
4. Finish by sealing the sleeve with putty or caulking compound at the final stage.
Panasonic CS-E18CKE — 11.2.2. HOW TO FIX INSTALLATION PLATE diagram (page 66)
Fig. 88

The centre of installation plate should be at more than 550 mm at right and left of the wall.

The distance from installation plate edge to ceiling should more than 67 mm.

From installation plate left edge to unit’s left side is 47 mm.

From installation plate right edge to unit’s right is 73 mm.

:

For left side piping, piping connection for liquid should be about 126 mm from this line. For left side piping, piping connection for gas should be about 174 mm from this line. For left side piping, piping connecting cable should be about 984 mm from this line.

:

11.2.4. INDOOR UNIT INSTALLATION

:

1. For the right rear piping
Panasonic CS-E18CKE — 11.2.4. INDOOR UNIT INSTALLATION diagram (page 66)
Fig. 89
1. Mount the installation plate on the wall with 5 screws or

more. (If mounting the unit on the concrete wall consider using anchor bolts.)

  • Always mount the installation plate horizontally by

aligning the marking-off line with the thread and using a level gauge.

2. Drill the piping plate hole with ø70 mm hole-core drill.
2. For the right and right bottom piping
  • Line according to the arrows marked on the lower left

and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively.

Panasonic CS-E18CKE — 11.2.4. INDOOR UNIT INSTALLATION diagram (page 66)
Fig. 90
  • Drill the piping hole at either the right or the left and the

hole should be slightly slanted to the outdoor side.

Page 67 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 67 · click to enlarge
Page 67
3. For the embedded piping
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 91 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 92 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 93 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 94 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 95 · 8.2. Protection Control Features

(This can be used for left rear piping & left bottom piping also.)

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 96 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 97 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 98 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 67)
Fig. 99 · 8.2. Protection Control Features
Page 68 of the Panasonic CS-E18CKE user manual — HOW TO TAKE OUT FRONT GRILLE
Page 68 · click to enlarge
Page 68
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 68)
Fig. 100 · 8.2. Protection Control Features
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 68)
Fig. 101 · 8.2. Protection Control Features

11.2.5. CONNECT THE CABLE TO THE INDOOR UNIT

1. The inside and outside connecting cable can be connected
Panasonic CS-E18CKE — 11.2.5. CONNECT THE CABLE TO THE INDOOR UNIT diagram (page 68)
Fig. 102

without removing the front grille.

2. Connecting cable between indoor unit and outdoor unit

shall be approved polychloroprene sheathed 4 × 2.5 mm2

(E18CK, E21CK) flexible cord, type designation 245 IEC 57 or heavier cord.

Panasonic CS-E18CKE — 11.2.5. CONNECT THE CABLE TO THE INDOOR UNIT diagram (page 68)
Fig. 103
  • Ensure the color of wires of outdoor unit and the

terminal Nos. are the same to the indoor’s respectively.

  • Earth lead wire shall be longer than the other lead wires

as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage.

  • Secure the cable onto the control board with the holder

(clamper).

HOW TO TAKE OUT FRONT GRILLE

INSTALLATION OF AIR PURIFYING FILTERS

Please follow the steps below to take out front grille if necessary such as when servicing.

a. Open the front panel.

b. Remove the air filters.

a. Open the intake grille and remove the screw at the front

c. Put air purifying filters (left) and triple deodorizing filter

of the front grille.

(right) into place as shown in illustration below.

b. Set the vertical airflow direction louver to the horizontal

Panasonic CS-E18CKE — HOW TO TAKE OUT FRONT GRILLE diagram (page 68)
Fig. 104

position.

c. Slide down the 3 caps on the front grille as shown in the

illustration below, and then remove the 3 mounting screws.

d. Pull the lower section of the front grille towards you to

remove the front grille.

When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.

Panasonic CS-E18CKE — HOW TO TAKE OUT FRONT GRILLE diagram (page 68)
Fig. 105
Page 69 of the Panasonic CS-E18CKE user manual — 11.3.3. CONNECTING THE PIPING
Page 69 · click to enlarge
Page 69

AUTO SWITCH OPERATION

The below operations will be performed by pressing the “AUTO” switch.

1. AUTO OPERATION MODE

The Auto operation will be activated immediately once the Auto Switch is pressed.

2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)

The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 8 sec. A “beep” sound will occur at the fifth sec., in order to identify the starting of Test Run operation

3. HEATING TRIAL OPERATION

Press the AUTO Switch continuously for more than 8 sec. to below 11 sec. and release when a “beep beep” sound is occurred at eighth sec. (However, a “beep” sound is occurred at fifth sec.)

4. REMOTE CONTROL RECEIVING SOUND ON/OFF

The ON/OFF of Remote Control receiving sound can be changed over by following steps:

a. Press “AUTO” switch continuously for more than 16 sec. to below 21 sec. A “beep” sound will occur

at sixteenth sec.

b. Press the “Check” button once at Remote Control. A “beep” sound will occur.

c. Press the “AUTO” switch once to select Remote Control receiving sound ON/OFF. A “beep” sound indicates receiving sound

ON, and a “beep” sound indicates receiving sound OFF.

Panasonic CS-E18CKE — 4. REMOTE CONTROL RECEIVING SOUND ON/OFF diagram (page 69)
Fig. 106

11.3. OUTDOOR UNIT

11.3.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section)

11.3.2. INSTALL THE OUTDOOR UNIT

  • After selecting the best location, start installation according
Panasonic CS-E18CKE — 11.3.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) diagram (page 69)
Fig. 107 · 11.3.1. SELECT THE BEST LOCATION (Refer to “Select t…

to Indoor/Outdoor Unit Installation Diagram.

1. Fix the unit on concrete or rigid frame firmly and horizontally

by bolt nut. (ø10 mm).

2. When installing at roof, please consider strong wind and

earthquake. Please fasten the installation stand firmly with bolt or nails.

11.3.3. CONNECTING THE PIPING

Connecting The Piping To Indoor Unit

Panasonic CS-E18CKE — 11.3.3. CONNECTING THE PIPING diagram (page 69)
Fig. 108

Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)

  • Align the center of piping and sufficiently tighten the flare

nut with fingers.

MODEL Piping size (Torque) Gas Liquid E18CK, E21CK 1/2” (55 N.m) 1/4” (18 N.m)

  • Further tighten the flare nut with torque wrench in specified

torque as stated in the table.

Connecting The Piping to Outdoor Unit

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located at valve) onto the copper pipe.

Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.

Connect the piping

Page 70 of the Panasonic CS-E18CKE user manual — CAUTION
Page 70 · click to enlarge
Page 70

CUTTING AND FLARING THE PIPING

Panasonic CS-E18CKE — CUTTING AND FLARING THE PIPING diagram (page 70)
Fig. 109
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not

removed, gas leakage may be caused.

Turn the piping end down to avoid the metal powder entering the pipe.

3. Please make flare after inserting the flare nut onto the

copper pipes.

11.3.4. EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.

Panasonic CS-E18CKE — 11.3.4. EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION) diagram (page 70)
Fig. 110
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
  • Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to

-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.

4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not

move after approximately five minutes.

5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal

wrench (4 mm).

8. Mount valve caps onto the 2-way valve and the 3-way valve.
  • Be sure to check for gas leakage.

CAUTION

  • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
  • If the leak stops when the piping connections are tightened further, continue working from step 3.
  • If the leak does not stop when the connections are retightened, repair the location of leak.
  • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause

frostbite.

Page 71 of the Panasonic CS-E18CKE user manual — CHECK THE DRAINAGE
Page 71 · click to enlarge
Page 71

11.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT

1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 2.5 mm 2 (E18CK,

E21CK) flexible cord, type designation 245 IEC 57 or heavier cord.

Panasonic CS-E18CKE — 11.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT diagram (page 71)
Fig. 111
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover back to the original position with the screw.

11.3.6. PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap

the insulated piping end to prevent water from going inside the piping.

2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM

with thickness 6 mm or above.

DISPOSAL OF OUTDOOR UNIT DRAIN WATER

EVALUATION OF THE PERFORMANCE

  • If a drain elbow is used, the unit should be placed on a
  • Operate the unit at cooling operation mode for fifteen

stand which is taller than 3 cm.

minutes or more.

  • If the unit is used in an area where temperature falls below
  • Measure the temperature of the intake and discharge air.

0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.

  • Ensure the difference between the intake temperature and

the discharge is more than 8°C.

Panasonic CS-E18CKE — DISPOSAL OF OUTDOOR UNIT DRAIN WATER diagram (page 71)
Fig. 112
Panasonic CS-E18CKE — DISPOSAL OF OUTDOOR UNIT DRAIN WATER diagram (page 71)
Fig. 113

CHECK ITEMS

Is there any gas leakage at flare nut connections?

CHECK THE DRAINAGE

Has the heat insulation been carried out at flare nut connection?

  • Open front panel and remove air filters.

Is the connecting cable being fixed to terminal board firmly?

(Drainage checking can be carried out without removing the front grille.)

Is the connecting cable being clamped firmly?

  • Pour a glass of water into the drain tray-styrofoam.
  • Ensure that water flows out from drain hose of the indoor

Is the drainage OK? (Refer to “Check the drainage” section)

unit.

Panasonic CS-E18CKE — CHECK THE DRAINAGE diagram (page 71)
Fig. 114

Is the earth wire connection properly done?

Is the indoor unit properly hooked to the installation plate?

Is the power supply voltage complied with rated value?

Is there any abnormal sound?

Is the cooling operation normal?

Is the thermostat operation normal?

Is the remote control’s LCD operation normal?

Is the air purifying filter installed?

Page 72 of the Panasonic CS-E18CKE user manual — 12.1. Troubleshooting
Page 72 · click to enlarge
Page 72

12 Servicing Information

  • Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use

a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).

  • Pb free solder will tend to splash when heated too high (about 1100° F/600°C).

12.1. Troubleshooting

1. Rated Frequency Operation

During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the specification and technical data. Below are the methods used to obtain rated compressor operating specification.

(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.

(“beep” will be heard at the 5th second.)

Panasonic CS-E18CKE — 12.1. Troubleshooting diagram (page 72)
Fig. 115 · 12.1. Troubleshooting

(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.

Panasonic CS-E18CKE — 12.1. Troubleshooting diagram (page 72)
Fig. 116 · 12.1. Troubleshooting

Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated frequency. (“beep” “beep” will be heard at the 8th second.)

(a) Cooling · (b) Heating

Page 73 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 73 · click to enlarge
Page 73
2. Troubleshooting Air Conditioner
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 73)
Fig. 117 · 8.2. Protection Control Features

In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.

The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 73)
Fig. 118 · 8.2. Protection Control Features

Refrigeration cycle system

Page 74 of the Panasonic CS-E18CKE user manual — 12.2. Breakdown Self Diagnosis Function
Page 74 · click to enlarge
Page 74
1. Relationship between the condition of the air conditioner and pressure and electric current

Cooling Mode Heating Mode Condition of the air

conditoner Low Pressure High Pressure Electric current during operation

Low Pressure High Pressure Electric current during operation

Insufficient refrigerant (gas leakage)

Clogged capillary tube or Strainer

Short circuit in the indoor unit

Heat radiation deficiency of the outdoor unit

  • Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

12.2. Breakdown Self Diagnosis Function

Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below breakdown diagnosis method:

  • Press “CHECK” button at remote control continuously for more than five seconds to turn on the diagnosis mode, “H11” will be

displayed at remote control.

  • By pressing the TMER “

” button once, next error code will be displayed; press “V” button once, previous error code will be displayed.

  • If error code displayed matches the error code saved in unit memory (abnormality detected), four “beep” sounds will be heard

and Power LED will light on. Otherwise, one “beep” sound is heard.

If “CHECK” button is press again during Cooling operation using test run operation mode for 30 seconds, the diagnosis mode will turn off.

Inefficient compression

Page 75 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 75 · click to enlarge
Page 75

Abnormality / Protection control Abnormality

Primary location to verify

H11 Indoor / outdoor abnormal communication

> 1 min after starting operation

  • Internal / external cable connections
  • Indoor / Outdoor PCB H14 Indoor intake air temperature sensor abnormality

Continue for 5 sec. — • Intake air temperature sensor

(defective or disconnected) H15 Outdoor compressor temperature sensor abnormality

Continue for 5 sec. — • Compressor temperature sensor

(defective or disconnected) H16 Outdoor Current Transformer open circuit

— — • Outdoor PCB

  • IPM (Power transistor) module H19 Indoor fan motor merchanism lock — —
  • Indoor PCB
  • Fan motor H23 Indoor heat exchanger temperature sensor abnormality

Continue for 5 sec. O (Cooling only)

  • Heat exchanger temperature sensor

(defective or disconnected) H26 Ion abnormality — — • Indoor PCB

  • Ionizer H27 Outdoor air temperature sensor abnormality

Continue for 5 sec. O • Outdoor temperature sensor

(defective or disconnected) H28 Outdoor heat exchanger temperature sensor abnormality

Continue for 5 sec. O • Outdoor heat exchanger

temperature sensor (defective or disconnected) H30 Discharge temperature sensor abnormality

Continue for 5 sec. — • Discharge temperature sensor

  • H33 Indoor/Outdoor wrong connection — —
  • Indoor/Outdoor supply voltage H97 Outdoor Fan Motor lock abnormality — —
  • Outdoor PCB
  • Outdoor Fan Motor H98 Indoor high pressure protection — —
  • Air filter dirty
  • Air circulation short circuit H99 Indoor heat exchanger anti-freezing protection

— — • Insufficient refrigerant

  • Air filter dirty F11 Cooling / Heating cycle changeover abnormality

4 times occurance within 30 minutes

— • 4-way valve

  • V-coil F90 PFC control 4 times occurance within 10 minutes

— • Voltage at PFC

F91 Refrigeration cycle abnormality 7 times occurance continuously

— • No refrigerant

(3-way valve is closed) F93 Outdoor compressor abnormal revolution 4 times occurance within 20 minutes

— • Outdoor compressor

F95 Cool high pressure protection 4 times occurance within 20 minutes

— • Outdoor refrigerant circuit

F96 IPM (power transistor) overheating protection

— — • Excess refrigerant

  • Improper heat radiation
  • IPM (Power transistor) F97 Outdoor compressor overheating protection

4 times occurance within 20 minutes

— • Insufficient refrigerant

  • Compressor F98 Total running current protection 3 times occurance within 20 minutes

— • Excess refrigerant

  • Improper heat radiation F99 Outdoor Direct Current (DC) peak detection

7 times occurance continuously

— • Outdoor PCB

  • IPM (Power transistor)
  • Compressor

“O” - Frequency measured and fan speed fixed.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “RESET” button at Remote Control.

Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is changed from one “beep” to four “beep” sounds.

Show 8 more labels / short text on this page
Error Codes Table · Diagnosis · Emergency · display · Judgement · operation · Indoor fan operation · only
Page 76 of the Panasonic CS-E18CKE user manual — 12.3. Remote Control
Page 76 · click to enlarge
Page 76

12.3. Remote Control

  • Remote Control Reset
Panasonic CS-E18CKE — 12.3. Remote Control diagram (page 76)
Fig. 119 · 12.3. Remote Control

When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work.

If this happen, remove the cover of the remote control and push the reset point once to clear the memory data.

  • Changing the wireless remote control transmission
Panasonic CS-E18CKE — 12.3. Remote Control diagram (page 76)
Fig. 120 · 12.3. Remote Control

When there are more than one indoor units installed in the same room, it is possible to set different remote control receiving signal by modifying the jumpers inside Remote Control.

Panasonic CS-E18CKE — 12.3. Remote Control diagram (page 76)
Fig. 121 · 12.3. Remote Control

code

Page 77 of the Panasonic CS-E18CKE user manual — 12.4. Indoor Electronic Controllers Removal Procedures
Page 77 · click to enlarge
Page 77

12.4. Indoor Electronic Controllers Removal Procedures

Panasonic CS-E18CKE — 12.4. Indoor Electronic Controllers Removal Procedures diagram (page 77)
Fig. 122 · 12.4. Indoor Electronic Controllers Removal Procedur…
1. The Electronic Controller, a Signal Receiver and an Indicator (Fig. 3) can be seen by the below steps:
  • Open the Intake Grille and remove the screw at the front

of the Front Grille. (Fig. 1).

  • Remove the 3 caps and 3 screws at the bottom of the

Front Grille. (Fig. 1)

  • Remove the Front Grille by releasing the 3 hooks at the

top of the Front Grille. (Fig. 1)

Panasonic CS-E18CKE — 12.4. Indoor Electronic Controllers Removal Procedures diagram (page 77)
Fig. 123 · 12.4. Indoor Electronic Controllers Removal Procedur…
  • Unhook the tabs at the Control Board to remove the

Control Board Cover. (Fig. 2)

Panasonic CS-E18CKE — 12.4. Indoor Electronic Controllers Removal Procedures diagram (page 77)
Fig. 124 · 12.4. Indoor Electronic Controllers Removal Procedur…
2. To remove the Main Electronic Controller:
  • Release the 2 Particular Piece. (Fig. 3)
  • Release the CN-REC/DISP connectors. (Fig. 4)
  • Release the CN-TH connector. (Fig. 4)
  • Release the CN-MAIN connector. (Fig. 4)
  • Release the CN-STM1 connector. (Fig. 4)
  • Release the CN-STM2 connector. (Fig. 4)
  • Release the hooks that hold the Electronic Controller.

(Fig. 3)

3. To remove the Power Electronic Controller:
Panasonic CS-E18CKE — 12.4. Indoor Electronic Controllers Removal Procedures diagram (page 77)
Fig. 125 · 12.4. Indoor Electronic Controllers Removal Procedur…
  • Release the CN-001 connector. (Fig. 4)
  • Release the CN-002 connector. (Fig. 4)
Page 78 of the Panasonic CS-E18CKE user manual — 12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures
Page 78 · click to enlarge
Page 78

12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures

Panasonic CS-E18CKE — 12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures diagram (page 78)
Fig. 126 · 12.5. Cross Flow Fan and Indoor Fan Motor Removal Pr…
1. In order to remove the Cross Flow Fan and Indoor Fan

Motor, Control Board need to be taken out by releasing all the connectors as indicated below.

a. Release the Earth Wire screw. (Fig. 5)

b. Release the Intake Air Sensor. (Fig. 5)

c. Release the Piping Sensor. (Fig. 5)

d. Release the CN-REC connectors. (Fig. 5)

e. Release the CN-STM1. (Fig. 5)

f. Release the CN-STM2. (Fig. 5)

g. Release connectors generator Ionizer. (Fig. 5)

Panasonic CS-E18CKE — 12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures diagram (page 78)
Fig. 127 · 12.5. Cross Flow Fan and Indoor Fan Motor Removal Pr…
2. Pull out the Drain Hose from outlet to remove the Discharge

Grille. (Fig. 6)

Panasonic CS-E18CKE — 12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures diagram (page 78)
Fig. 128 · 12.5. Cross Flow Fan and Indoor Fan Motor Removal Pr…
3. Removing the right and left screws. (Fig. 7)
4. By pressing down the hook at the left and pushing up the

hook at the right, you will be able to remove the Control Board. (Fig. 7)

Panasonic CS-E18CKE — 12.5. Cross Flow Fan and Indoor Fan Motor Removal Procedures diagram (page 78)
Fig. 129 · 12.5. Cross Flow Fan and Indoor Fan Motor Removal Pr…
5. Remove the screw at the Cross Flow Fan. (Fig. 8)
Page 79 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 79 · click to enlarge
Page 79
6. Remove the Bearing. (Fig. 9)
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 79)
Fig. 130 · 8.2. Protection Control Features
7. Remove the screws at the left of the Evaporator. (Fig. 9)
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 79)
Fig. 131 · 8.2. Protection Control Features
8. Push up the Evaporator and pull out the Cross Flow Fan

from shaft. By then, Fan Motor can be taken out. (Fig. 10).

REMINDER - To reinstall the Fan Motor, put it back in place, adjust the position of the Fan Motor’s leadwire appropriately as shown in the Fig. 8 before installing the Cross Flow Fan.

Page 80 of the Panasonic CS-E18CKE user manual — 12.6. Outdoor Electronic Controller Removal Procedure
Page 80 · click to enlarge
Page 80

12.6. Outdoor Electronic Controller Removal Procedure

1. Remove the top panel and front panel
Panasonic CS-E18CKE — 12.6. Outdoor Electronic Controller Removal Procedure diagram (page 80)
Fig. 132 · 12.6. Outdoor Electronic Controller Removal Procedur…
  • Be save to return the wiring to its original position
  • There are many high voltage components within the heat

sink cover so never touch the interior during operation. Wait at least two minutes after power has been turned off.

2. Remove the Outdoor Electronic Controller
Panasonic CS-E18CKE — 12.6. Outdoor Electronic Controller Removal Procedure diagram (page 80)
Fig. 133 · 12.6. Outdoor Electronic Controller Removal Procedur…
Panasonic CS-E18CKE — 12.6. Outdoor Electronic Controller Removal Procedure diagram (page 80)
Fig. 134 · 12.6. Outdoor Electronic Controller Removal Procedur…
Panasonic CS-E18CKE — 12.6. Outdoor Electronic Controller Removal Procedure diagram (page 80)
Fig. 135 · 12.6. Outdoor Electronic Controller Removal Procedur…
Page 81 of the Panasonic CS-E18CKE user manual — 13 Technical Data
Page 81 · click to enlarge
Page 81

13 Technical Data

Panasonic CS-E18CKE — 13 Technical Data diagram (page 81)
Fig. 136 · 13 Technical Data
Page 82 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 82 · click to enlarge
Page 82
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 82)
Fig. 137 · 8.2. Protection Control Features
Page 83 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 83 · click to enlarge
Page 83
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 83)
Fig. 138 · 8.2. Protection Control Features

Outdoor Temp. (°C) Indoor wet bulb temp.

30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 5.26 3.99 1.51 4.91 3.82 1.63 4.57 3.67 1.74 4.16 3.49 1.88 19.0°C 5.30 1.65 19.5°C 5.77 4.17 1.54 5.40 4.01 1.66 5.02 3.86 1.77 4.56 3.67 1.91 22.0°C 6.29 4.33 1.57 5.88 4.16 1.69 5.47 4.01 1.80 4.97 3.83 1.95

Outdoor Temp. (°C) Indoor wet bulb temp.

30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 6.25 4.74 2.02 5.84 4.54 2.18 5.43 4.37 2.33 4.94 4.15 2.51 19.0°C 6.30 2.21 19.5°C 6.86 4.96 2.06 6.41 4.77 2.22 5.97 4.59 2.37 5.42 4.37 2.56 22.0°C 7.48 5.14 2.10 6.99 4.95 2.26 6.50 4.77 2.42 5.91 4.55 2.61

TC - Total Cooling Capacity (kW) Indoor 27°C/19°C SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C IP - Input Power (kW)

Page 84 of the Panasonic CS-E18CKE user manual — 14 Exploded View
Page 84 · click to enlarge
Page 84

14 Exploded View

Panasonic CS-E18CKE — 14 Exploded View diagram (page 84)
Fig. 139 · 14 Exploded View

The above exploded view is for the purpose of parts disassembly and replacement.

The non-numbered parts are not kept as standard service parts.

Page 85 of the Panasonic CS-E18CKE user manual — 15 Replacement Parts List
Page 85 · click to enlarge
Page 85

15 Replacement Parts List

<ModelCS-E18CKE & CS-E21CKE>

REF. NO. PART NAME & DESCRIPTION QTY. CS-E18CKE CS-E21CKE REMARKS 1 CHASSY COMPLETE 1 CWD50C1293 ← 2 FAN MOTOR 1 CWA981056 ← 0 3 CROSS FLOW FAN COMPLETE 1 CWH02C1010 ← 4 SCREW - CROSS FLOW FAN 1 CWH4580304 ← 5 BEARING ASS’Y 1 CWH64K007 ← 6 EVAPORATOR 1 CWB30C1387 CWB30C1336 7 FLARE NUT 1 CWT25086 (7/16”) ← 8 FLARE NUT 1 CWT25096 (3/4”) ← 9 INTAKE AIR SENSOR HOLDER 1 CWH32142 ← 10 DISCHARGE GRILLE COMPLETE 1 CWE20C2240 ← 11 VERTICAL VANE 15 CWE241088 ← 12 CONNECTING BAR 2 CWE261025 ← 13 AIR SWING MOTOR 1 CWA98260 ← 0 14 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3849 ← 15 AIR SWING MOTOR 1 CWA981041 ← 0 16 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3731 ← 17 HORIZONTAL VANE 1 CWE241136 ← 18 CAP - DRAIN TRAY 1 CWH52C1001 ← 19 PARTICULAR PIECE 1 CWD932162 ← 20 CONTROL BOARD 1 CWH102103 ← 21 TERMINAL BOARD COMPLETE 1 CWA28C2128 ← 0 22 POWER SUPPLY CORD 1 CWA20C2328 ← 23 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1456 CWA73C1457 0 24 ELECTRONIC CONTROLLER - POWER 1 CWA743304 ← 0 25 P.C.B. RECEIVER 1 CWA742724 ← 26 ELECTRONIC CONTROLLER - INDICATOR 1 CWE39C1102 ← 0 28 INDICATOR HOLDER 1 CWD932163 ← 29 SENSOR COMPLETE 1 CWA50C2122 ← 0 30 CONTROL BOARD TOP COVER 1 CWH131091 ← 31 CONTROL BOARD FRONT COVER 1 CWH131090 ← 32 REMOTE CONTROL COMPLETE 1 CWA75C2401 ← 0 33 FRONT GRILLE COMPLETE 1 CWE11C2843 ← 34 INTAKE GRILLE 1 CWE22C1105 ← 35 GRILLE DOOR 1 CWE141033 ← 36 CONTROL PANEL 1 CWE312291 ← 37 DECORATION BASE (R) 1 CWE351067 ← 38 DECORATION BASE (L) 1 CWE351068 ← 39 AIR FILTER 2 CWD001049 ← 40 SCREW - FRONT GRILLE 4 XTT4+16C ← 41 CAP - FRONT GRILLE 3 CWH521062 ← 42 DRAIN HOSE 1 CWH85285 ← 43 AIR PURIFYING FILTER 1 CWMD00C0001 ← 0 44 TRIPLE DEODORIZING FILTER 1 CWMD00C0004 ← 0 45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ← 46 INSTALLATION PLATE 1 CWH36K1007 ← 47 FULCRUM 2 CWH621013 ← 48 ELECTRONIC CONTROLLER - IONIZER 1 CWA743099 ← 0 49 CASING - IONIZER 1 CWD932228 ← 50 ION - GENERATOR 1 CWH94C0001 ←

  • All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
  • “O” marked parts are recommended to be kept in stock.

(Note)

Page 86 of the Panasonic CS-E18CKE user manual — 16 Exploded View
Page 86 · click to enlarge
Page 86

16 Exploded View

Panasonic CS-E18CKE — 16 Exploded View diagram (page 86)
Fig. 140 · 16 Exploded View

The above exploded view is for the purpose of parts disassembly and replacement.

The non-numbered parts are not kept as standard service parts.

Page 87 of the Panasonic CS-E18CKE user manual — 17 Replacement Parts List
Page 87 · click to enlarge
Page 87

17 Replacement Parts List

<ModelCU-E18CKR & CU-E21CKR>

REF NO. DESCRIPTION & NAME QTY. CU-E18CKR CU-E21CKR REMARKS 1 CHASSY ASSY 1 CWD50K2085 ← 2 ANTI-VIBRATION BUSHING 3 CWH50077 ← 3 COMPRESSOR 1 5CS130XAC03 ← O 4 NUT-COMPRESSOR MOUNT 3 CWH56000 ← 5 SOUND PROOF MATERIAL 1 CWG302111 ← 6 FAN MOTOR BRACKET 1 CWD541054 ← 7 FAN MOTOR 1 CWA981110 ← O 8 SCREW - FAN MOTOR BRACKET 2 CWH551060 ← 9 SCREW - FAN MOTOR MOUNT 3 CWH551109 ← 10 PROPELLER FAN ASSY 1 CWH03K1016 ← 11 NUT - PROPELLER FAN 1 CWH56053 ← 12 CONDENSER 1 CWB32C1317R CWB32C1324R 14 TUBE ASS’Y COMPLETE (VALVE/RECEIVER) 1 CWT01C2900 CWT01C2901 O 15 4 WAYS VALVE 1 CWB001027 ← 16 STRAINER 1 CWB11094 ← 18 HOLDER - COUPLING 1 CWH351035 ← 19 3 WAYS VALVE (GAS) 1 CWB011170 ← O 20 2 WAYS VALVE (LIQUID) 1 CWB021135 ← O 21 DRYER 1 CWB101015 ← O 22 SOUND PROOF BOARD 1 CWH151050 ← 23 TERMINAL COVER 1 CWH171001 ← 24 NUT-TERMINAL COVER 1 CWH7080300 ← 25 SENSOR COMPLETE (COMP. TOP) 1 CWA50C2168 ← 26 HOLDER SENSOR 3 CWH321010 ← 27 V-COIL COMPLETE (4-WAYS VALVE) 1 CWA43C2098 ← 28 V-COIL COMPLETE (EXPAND VALVE) 1 CWA43C2058 ← 29 SENSOR COMPLETE (COMP. DISC.) 1 CWA50C2169 ← 30 SENSOR COMPLETE 1 CWA50C2120 ← 31 REACTOR 1 CWA421069 ← 32 CONTROL BOARD (SIDE) 1 CWH102122 ← 33 TERMINAL BOARD ASSY 1 CWA28K1036 ← 34 FUSE HOLDERS 1 - - 35 FUSE 1 - - 36 CONTROL BOARD (TOP) 1 CWH102204 ← 37 CONTROL BOARD (BOTTOM) 1 CWH102205 ← 38 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1464 CWA73C1465 40 CONTROL BOARD COVER (TOP) 1 CWH131167 ← 41 CABINET SIDE PLATE (LEFT) 1 CWE041082A ← 42 HANDLE 1 CWE161010 ← 43 CABINET SIDE PLATE (RIGHT) 1 CWE041083A ← 44 HANDLE 1 - - 45 CABINET FRONT PLATE CO. 1 CWE06K1043 ← 46 WIRE NET 1 CWD041041A ← 47 CABINET TOP PLATE 1 CWE031031A ← 48 CONTROL BOARD COVER (BOTTOM) 1 CWH131168 ← 49 CONTROL BOARD COVER (TOP) 1 CWH131169A ← 50 OPERATING INSTRUCTION 1 CWF563989 ← 51 OPERATING INSTRUCTION 1 CWF563990 ← 52 OPERATING INSTRUCTION 1 CWF563991 ← 53 INSTALLATION INSTRUCTION 1 CWF612433 ← 54 INSTALLATION INSTRUCTION 1 CWF612434 ← 55 INSTALLATION INSTRUCTION 1 CWF612435 ← 56 DRAIN HOSE 1 CWH5850080 ← 57 PACKING 1 CWB81012 ←

  • All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
  • “O” marked parts are recommended to be kept in stock.

(Note)

Page 88 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 88 · click to enlarge
Page 88
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 88)
Fig. 141 · 8.2. Protection Control Features

6 5 4 3 2 1 CN-MAIN 7 10 9 8

C9 0.01µ R20 10kΩ R21 1kΩ

R45 270Ω R46 270Ω R47 270Ω

R49 330Ω R50 330Ω R51 270Ω

R33 10kΩ R34 10kΩ R35 10kΩ R36 10kΩ C20 0.01µ

Page 89 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 89 · click to enlarge
Page 89
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 89)
Fig. 142 · 8.2. Protection Control Features

64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49

32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17

(20k 3950) PIPE TEMP. SENSOR R22 15kΩ 1%

Page 90 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 90 · click to enlarge
Page 90
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 90)
Fig. 143 · 8.2. Protection Control Features

3 4 5 6 7 8 9 10 11

Page 91 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 91 · click to enlarge
Page 91
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 91)
Fig. 144 · 8.2. Protection Control Features
Page 92 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 92 · click to enlarge
Page 92
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 92)
Fig. 145 · 8.2. Protection Control Features
Page 93 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 93 · click to enlarge
Page 93
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 93)
Fig. 146 · 8.2. Protection Control Features

R212 10k R213 10k R214 10k R215 10k R216 10k R217 10k

100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85

41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26

Page 94 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 94 · click to enlarge
Page 94
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 94)
Fig. 147 · 8.2. Protection Control Features
Page 95 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 95 · click to enlarge
Page 95
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 95)
Fig. 148 · 8.2. Protection Control Features
Page 96 of the Panasonic CS-E18CKE user manual — 8.2. Protection Control Features
Page 96 · click to enlarge
Page 96
Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 96)
Fig. 149 · 8.2. Protection Control Features
Page 97 of the Panasonic CS-E18CKE user manual — TIMER TABLE <OUTDOOR>
Page 97 · click to enlarge
Page 97

How to use electronic circuit diagram

Panasonic CS-E18CKE — 8.2. Protection Control Features diagram (page 97)
Fig. 150 · 8.2. Protection Control Features

TIMER TABLE <INDOOR>

Test mode Name Time (When test point

Short-circuited) 4 way valve abnormality 4 min. 24 sec. Outdoor air temp. for Hz No. decision 30 min. 0 sec. Anti-dew formation control 20 min. 0 sec. Anti-freezing control 6 min. 0 sec. Thermo OFF delay 3 min. 0 sec. Low pressure control (gas leakage) compressor OFF time 3 min. 0 sec. Time delay safety control 2 min. 58 sec. 0 sec. 20 sec. Odour timer status shift time 90 sec. 0 sec. 20 sec. 120 sec. Intake air temp. sampling time 2 min. 0 sec. Self diagnosis display time 10 sec. 0 sec. Auto mode judgement sampling time 20 sec. 0 sec. 24 hours Real Timer 1 hour 1 min. Heating SSHi fan speed shift 120 min. 12 sec. Cooling SHi fan speed shift 30 min. 3 sec. Hot start forced completion 4 min. 0.4 sec. Auto mode judgement interval 30 min. 3 sec. After Hot start / Deice 2 min. 12 sec.

TIMER TABLE <OUTDOOR>

Test mode Name Time (When test point

Short-circuited) DC PEAK 30 sec. 3 sec. 120 min. 24 sec. Deice detection 80 min. 16 sec. 40 min. 8 sec. 40 min. 8 sec. Hz lock time 30 sec. 0 sec. Outdoor fan delay operation control 30 sec. 3 sec. 4 way valve delay operation control 3 min. 18 sec.

Page 98 of the Panasonic CS-E18CKE user manual — 18.1. REMOTE CONTROL
Page 98 · click to enlarge
Page 98

18.1. REMOTE CONTROL

Panasonic CS-E18CKE — 18.1. REMOTE CONTROL diagram (page 98)
Fig. 151
Page 99 of the Panasonic CS-E18CKE user manual — 18.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD
Page 99 · click to enlarge
Page 99

18.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD

Panasonic CS-E18CKE — 18.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD diagram (page 99)
Fig. 152
Page 100 of the Panasonic CS-E18CKE user manual — 18.3. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW
Page 100 · click to enlarge
Page 100

18.3. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW

Panasonic CS-E18CKE — 18.3. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW diagram (page 100)
Fig. 153

100 [MAICO] Printed in Malaysia

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Panasonic CS-E18CKE

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.