Omega Engineering DP41-E

2 pages·353 KB·Sensor·PDF·ENDEFRITNLJA
Omega Engineering DP41-E
Table of Contents 80 sections High Performance Process Indicator · For immediate technical or application assistance: · TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA · [email protected] · … ShowHide
High Performance Process Indicatorp.1For immediate technical or application assistance:p.1TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGAp.1[email protected]p.1NN TEL: (203) 359-1660NN FAX: (203) 359-7700p.1NN TEL: (514) 856-6928NN FAX: (514) 856-6886p.1www.omega.com Internet e-mailp.1Servicing North America:p.1Servicing Europe:p.1OMEGAnet ® On-Line Servicep.1DP41-Ep.1AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICEp.1RETURN REQUESTS / INQUIRIESp.1WARRANTY/DISCLAIMERp.17. Press MENU. The meter stores this change, then displays “CNT BY”p.1READ 1p.1SETPTS /MAX /MIN MENU RESETp.1INPUT2p.1READ 2p.1Dec ptp.1REset2p.15. Press MENU. The meter stores changes and displays:p.1CNTBYp.1digits and /MAX to change the digit’s value.)p.1value recorded in step 1 of the Measurep.1recorded in step 2 of the Measure Inputp.1“001000”. (Use /MIN to scroll throughp.1displays “000000”. Enter the INPUT 1p.1through digits and /MAX to changep.1number. Change the meter to readp.1Press /MIN. The meter displaysp.1“000000”. Enter the INPUT 2 valuep.1mode. The meter is now scaled top.11. Press /MIN to display “INPUT 1”:p.1Press /MIN to display a six-digitp.13. Press MENU. The meter displays “INPUT 2”:p.1Press /MIN to display a six digitp.1Press /MIN again. The meterp.12. Press MENU. The meter displays “READ 1”:p.1“000000”. (Use /MIN to scrollp.14. Press MENU. The meter displays “READ 2”:p.1storedp.1Scale Input Valuesp.1the digit’s value.)p.1INPUT1p.1IN CNFp.1INp6=0p.1 SETPTS /MAX /MIN MENU RESETp.1IN.SC.OFp.1Measure and Record Input Valuesp.13. Press MENU until the meter displays:p.14. Press MENU until the meter displays:p.1necessary, to read “FFFFFF.” (Usep.1 /MAX to change the decimal pointp.1Change the meter to read “INP.6=1”p.1(Use /MIN to scroll through digitsp.11. Press MENU. The meter displays:p.1Press /MIN to display “INP6=0”p.1INPUT 1 = _________________p.1INPUT 2 = _________________p.1Set Default Decimal Pointp.12. Press MENU. The meter stores changes (if applicable) then displays “RDG.OF”:p.2 /MAX to select 0 as the value). Settingp.22 3 4 START HEREp.2is important to perform all tasks in the order outlined in thep.2CURRNTp.23. Press MENU. The meter stores changes (if applicable), then displays “RDG.CNF”:p.2rdg.CNFp.2RDG.1=0p.2RDG.2=1p.2rdg scp.2INPUTp.21. Press MENU until the meter displays:p.2Press /MAX until the meter displaysp.2Press /MIN to display a flashingp.2Set Up Reading Configurationp.2“RDG.1=0”. Selecting “RDG.1=0”p.2“RDG.2=1”. Selecting “RDG.2=1”p.2Select Input Rangep.2Quick Start Setupp.2
Page 1 of the Omega Engineering DP41-E user manual — SETPTS /MAX   /MIN MENU RESET
Page 1 · click to enlarge
Page 1
Mexico and N TEL(001)800-TC-OMEGA ® N FAX: (001) 203-359-7807
Omega Engineering DP41-E — High Performance Process Indicator diagram (page 1)
Fig. 1 · High Performance Process Indicator

High Performance Process Indicator

For immediate technical or application assistance:

NN Engineering Service1-800-872-9436 / 1-800-USA-WHEN ®

TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA

NN TEL+31 20 3472121NN FAX: +31 20 6434643

NN Northbank, Irlam Manchester M44 5BD United Kingdom

[email protected]

NN TEL: (203) 359-1660NN FAX: (203) 359-7700

NN TEL: (514) 856-6928NN FAX: (514) 856-6886

NN Customer Service1-800-622-2378 / 1-800-622-BEST ®

www.omega.com Internet e-mail

USA and CanadaN Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA ®
BeneluxNN Postbus 8034, 1180 LA Amstelveen, The Netherlands
Germany/AustriaN Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
NN TEL+49 7056 9398-0N FAX: +49 7056 9398-29
NN TEL+44 161 777 6611N FAX: +44 161 777 6622
NN TEL+420 69 6311899N FAX: +420 69 6311114
NN TEL+33 130 621 400N FAX: +33 130 699 120

Servicing North America:

Czech RepublicN Rudé armády 1868, 733 01 Karviná 8
NN Toll Free in Germany0800 639 7678
USANN One Omega Drive, P.O. Box 4047
NN Toll Free in Benelux0800 0993344N
FranceNN 9, rue Denis Papin, 78190 Trappes
NN Toll Free in England0800 488 488
Latin AmericanEn Espa ñ ol: (001) 203-359-7803 N

Servicing Europe:

NN Toll Free in France0800406342
NN e-mailinfo@ omega.com .mx
NN e-mailgermany@ omega.com

ISO 9002 CertifiedN River Bend Technology Centre

NN e-mailczech@ omega.com
NN e-mailfrance@ omega.com
NN e-mailsales@ omega.co .uk

ISO 9001 CertifiedN Stamford CT 06907-0047

NN e-mailinfo@ omega.com

NN Laval (Quebec) H7L 5A1

NN e-mailnl@ omega.com

OMEGAnet ® On-Line Service

United KingdomN One Omega Drive
CanadaNN 976 Bergar

DP41-E

stored PTS/MAX/MIN MENU RESET

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.

OMEGA is constantly pursuing certification of its products to the European New Approach

The information contained in this document is believed to be correct, but OMEGA Engineering,

Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications

TRADEMARK NOTICE® , omega.com ® , are trademarks of OMEGA

12450ML-99 Rev.F MQS1297/0202

This device is marked with the international caution symbol. It is important to read the

Setup Guide before installing or commissioning this device as it contains important

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and

workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an

additional one (1) month grace period to the normal one (1) year product warranty to cover

handling and shipping time. This ensures that OMEGA’s customers receive maximum

If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s

Customer Service Department will issue an Authorized Return (AR) number immediately upon

phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will

be repaired or replaced at no charge. OMEGA'S WARRANTY does not apply to defects resulting

from any action of the purchaser, including but not limited to mishandling, improper interfacing,

operation outside of design limits, improper repair, or unauthorized modification. This

WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence

of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration;

improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s

control. Components which wear are not warranted, including but not limited to contact points,

OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA

neither assumes responsibility for any omissions or errors nor assumes liability for any damages

that result from the use if its products in accordance with information provided by OMEGA, either

verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and

free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY

KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED

WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A

additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or

Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.

BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN

AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE

DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number

The purchaser is responsible for shipping charges, freight, insurance and proper packaging to

OMEGA for current repair charges. Have the

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is

This document may not be copied, photocopied, reproduced, translated, or reduced to any

electronic medium or machine-readable form, in whole or in part, without prior written consent

PATENT NOTICE: This product is covered by one or more of the following patents: U.S.

Pat. No. Des. 336,895; 5,274,577 / CANADA 2052599; 2052600 / ITALY 1249456;

1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Case Bezel

Design” is a trademark of NEWPORT Electronics, Inc., registered in the U.S. USED

FOR NON-WARRANTY REPAIRS, consult

2. Model and serial number of product, and 3. Repair instructions and/or specific problems relative to the product.

should then be marked on the outside of the return package and on any correspondence.

following information available BEFORE

1. P.O. number to cover the COST of the repair,

Directives. OMEGA will add the CE mark to every appropriate device upon certification.

possible. This affords our customers the latest in technology and engineering.

damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS / INQUIRIES

UNDER LICENSE. OTHER INTERNATIONAL PATENTS PENDING.

WARRANTY/DISCLAIMER

OMEGA is a registered trademark of OMEGA ENGINEERING, INC.

© Copyright 2002 OMEGA ENGINEERING, INC. All rights reserved.

contacting OMEGA:

information relating to safety and EMC.

stored SETPTS/MAX/MINMENU RESET

FOR WARRANTY RETURNS, please have

the following information available BEFORE

2. Model and serial number of the product under warranty, and
1. P.O. number under which the product was PURCHASED,
3. Repair instructions and/or specific problems relative to the product.

of OMEGA ENGINEERING, INC.

coverage on each product.

prevent breakage in transit.

connected applications.

contacting OMEGA:

fuses, and triacs.

Engineering, Inc.

without notice.

stored SETPTS/MAX/MINMENU RESET

7. Press MENU. The meter stores this change, then displays “CNT BY”

READ 1

SETPTS /MAX /MIN MENU RESET

INPUT2

SETPTS /MAX /MIN MENU RESET

READ 2

SETPTS /MAX /MIN MENU RESET

Dec pt

SETPTS /MAX /MIN MENU RESET

6. Press /MIN to display the current decimal point. Press /MAX to change the decimal point location to “FFFFF.F”.

SETPTS /MAX /MIN MENU RESET

REset2

SETPTS /MAX /MIN MENU RESET

5. Press MENU. The meter stores changes and displays:

CNTBY

stored SETPTS/MAX/MIN MENU RESET

digits and /MAX to change the digit’s value.)

8. Press RESET twice. The meter displays: “RESET 2”, then returns to the run

value recorded in step 1 of the Measure

Input Values section of this quick start.

recorded in step 2 of the Measure Input

“001000”. (Use /MIN to scroll through

displays “000000”. Enter the INPUT 1

through digits and /MAX to change

number. Change the meter to read

Press /MIN. The meter displays

“000000”. Enter the INPUT 2 value

number. Change the meter to read

mode. The meter is now scaled to

read 0 to 100.0 for a 4-20 mA input.

1. Press /MIN to display “INPUT 1”:

Press /MIN to display a six-digit

3. Press MENU. The meter displays “INPUT 2”:

Press /MIN to display a six digit

Press /MIN again. The meter

2. Press MENU. The meter displays “READ 1”:

“000000”. (Use /MIN to scroll

Values section of this quick start.

4. Press MENU. The meter displays “READ 2”:

stored

SETPTS /MAX /MIN MENU RESET

stored

SETPTS /MAX /MIN MENU RESET

Scale Input Values

the digit’s value.)

Dec pt

SETPTS /MAX /MIN MENU RESET

FFFFFF.

SETPTS /MAX /MIN MENU RESET

3. Press MENU. The meter stores changes (if applicable), then displays “CNT BY”.

SETPTS /MAX /MIN MENU RESET

INPUT1

SETPTS /MAX /MIN MENU RESET

INPUT2

SETPTS /MAX /MIN MENU RESET

IN CNF

SETPTS /MAX /MIN MENU RESET

INp6=0

SETPTS /MAX /MIN MENU RESET

CNTBY

4. Press RESET twice. The meter momentarily displays “RESET 2” then returns to the run mode. The meter

5. Press MENU. The meter stores changes and displays:

will now read the input signal (4mA = ≈ 000000.

IN.SC.OF

SETPTS /MAX /MIN MENU RESET

and /MAX to change the digit’s value).

2. Apply 20mA to the input and record the display reading.
2. Press /MIN to display the current decimal point. Change the display, if

Measure and Record Input Values

1. Apply 4mA to the input and record the display reading.

3. Press MENU until the meter displays:

4. Press MENU until the meter displays:

necessary, to read “FFFFFF.” (Use

/MAX to change the decimal point

Change the meter to read “INP.6=1”

(Use /MIN to scroll through digits

1. Press MENU. The meter displays:

Press /MIN to display “INP6=0”

INPUT 1 = _________________

INPUT 2 = _________________

Set Default Decimal Point

stored

SETPTS /MAX /MIN MENU RESET

Refer to this as Input One.

Refer to this as Input Two.

and 20mA = ≈ 020000.).

stored

SETPTS /MAX /MIN MENU RESET

position).

® · ® · ®

Page 2 of the Omega Engineering DP41-E user manual — ~ AC Line
Page 2 · click to enlarge
Page 2
Omega Engineering DP41-E — 2. Press MENU. The meter stores changes (if applicable) then displays “RDG.OF”: diagram (page 2)
Fig. 2 · 2. Press MENU. The meter stores changes (if applicab…

2. Press MENU. The meter stores changes (if applicable) then displays “RDG.OF”:

2. Press MENU. The meter stores changes, if applicable, then displays “IN.SC.OF”.
1.00000 PTS/MAX /MIN MENURESET
1. Press /MIN to display the scale factor value. Change the value, if necessary,
3. Press /MIN to display the offset value. Change the value, if necessary, to read
4. Press MENU. The meter stores change, if applicable, then displays “IN CNF”.

/MAX to select 0 as the value). Setting

1. Press /MIN until the meter flashes. Change the value, if necessary, to read

2 3 4 START HERE

rdg.of SETPTS/MAX /MIN MENURESET
000000 SETPTS/MAX /MIN MENURESET

Quick Start Setup scales your meter to read 0 to 100.0 for a

4. 20mA input. This setup procedure is actually a series of short tasks. To complete Quick Start Setup successfully, it

is important to perform all tasks in the order outlined in the

SETPTS /MAX /MIN MENU RESET

CURRNT

SETPTS /MAX /MIN MENU RESET

3. Press MENU. The meter stores changes (if applicable), then displays “RDG.CNF”:

rdg.CNF

SETPTS /MAX /MIN MENU RESET

RDG.1=0

SETPTS /MAX /MIN MENU RESET

RDG.2=1

SETPTS /MAX /MIN MENU RESET

3. Press MENU. The meter stores changes (if applicable), then displays “RDG SC”:

rdg sc

SETPTS /MAX /MIN MENU RESET

INPUT

CNTBY SETPTS/MAX /MIN MENURESET
2. Press /MIN to display “RDG.2”. Press /MAX until the meter displays

1. Press MENU until the meter displays:

2. Press /MIN until the meter flashes: Press MENU and “CURRNT” stops

Press /MAX until the meter displays

1. Press /MIN to display “RDG.1”. Press /MAX until the meter displays

Press /MIN to display a flashing

input range of 4-20mA or 0-20 mA.

Set Up Reading Configuration

“RDG.1=0”. Selecting “RDG.1=0”

“RDG.2=1”. Selecting “RDG.2=1”

enables an active decimal point.

stored

SETPTS /MAX /MIN MENU RESET

stored

SETPTS /MAX /MIN MENU RESET

enables direct formatting.

Select Input Range

Quick Start Setup

INp.6=0 TPTS/MAX /MIN MENURESET

Quick Start Setup.

“4-20mA.”

flashing.

1. Locate connectors P3&P9 on the right-side-rear of the unit.
3. Apply ac power. The front panel of the unit flashes RESET2.
/MAXchange the value of a submenu. RESETmove backward one menu (press once) or exit the configuration menus (press twice).
IN.SC.OF SETPTS/MAX /MIN MENU RESETIN.SC.OF ETPTS/MAX /MIN MENURESET

Wiring Example: Current Input with Sensor Excitation

b. Verify the P1 power and P3 and P9 input connections.

enter and scroll through a submenu.

2. Attach the wires and tighten the retaining screws. Tug gently on the wires to verify the connection.

change the value of a submenu.

move backward one menu (press

stored SETPTS/MAX/MIN MENU RESET

Follow these steps to wire a current input sensor with

once) or exit the configuration

menus (press twice).

P9

P3 N/C

setpoint values.

Wiring a Current Transmitter

of each button is described below:

+E

+S

–S

–E

RTN

to the next.

c. Check your power source.

d. Check your signal source.

N/C

5. Apply ac power once again.

Press This Button To:

a. Remove ac power.

Configure the Meter

JUMPER

PROVIDED

(-) (4-20mA)

USER

sensor excitation.

If it does not:

SETPTS

MENU

/MIN

/MAX

RESET

screw.

  • connect ac power
  • wire the sensor
  • configure the meter, using the front panel buttons and the configuration menus

uses the C2 (4 - 20mA) range. If your meter is setup for a

Use this Quick Start Manual to get your High Performance

DC1 - DC10 are voltage ranges. This quick start manual

  • ac Power Connector (orange -P1), Input Connectors (2) (grey -P3 and P9), and rear protective cover (mounted).

Process Indicator up and running. These instructions use

Check the serial label on the top of the meter case. The

model number’s last 3 digits indicate if the meter is set up

Contact the nearest Customer Service Department using

the numbers listed on the front of this quickstart manual if

any of these parts are missing, or if you have questions .

In addition to the unit and related parts, you will need the

2. Locate connector P1 on the bottom-left-rear of the unit. The connector has three screw-down terminals.
3. Insert the correct wire in each terminal and tighten the lockdown screw. Tug gently on each wire to verify the

for voltage or current. C1 - C2 are current ranges and

the factory default settings of current input and 24 Vdc

range other than C2, consult the reference manual.

1. Remove the rear protective cover and set it aside. The cover is secured with a Phillips-head screw.

GASKET

  • ac power, as listed on meter’s Product/ID
  • 4-20mA input (eg: load cell, calibrator)
  • 1/8” Phillips head screwdriver
  • 1/8” flat blade screwdriver

Your unit should have the following parts:

sensor excitation. To start your unit you:

P1 Connector

P1

N L

Using This Quick Start Manual

following items to set up your unit:

  • Front panel button cover
  • Panel mounting gaskets

Before You Begin

Connect ac Power

EARTH GROUND

~ AC Neutral

connection.

~ AC Line

  • Meter

(+)

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Omega Engineering DP41-E

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Omega Engineering DP41-E

Be the first to ask — other owners or our team will answer.

Original document

Omega Engineering DP41-E manual PDF

2 pages·353 KB·Sensor·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…