FieldPoint™, Nat ional Instruments™, and ni. com™ are trademarks of National Instrument s Corporation. Product and company names mentione d herein are trademarks or trade names of their respective companies. 322633B-01 © Copyright 20 00 National Inst ruments Corp.
FP-QUAD-510 2 www.ni.com When defin ing a FieldPoint system that uses an FP-QU AD-510 module, you must calculate the power consu mption. First refer to the specifications section in the user man ual for your network module. The maximum number of terminal bases per bank multiplied by 1 watt is the total po wer the network module can supply .
© National Instruments Corp. 3 FP-QUAD-510 Figure 1. Install Y our Module Field Wiring The terminal base provides connections for each axis and for an external supply to po wer the FP-QU AD-510 input channels and field de vices. The FP-QU AD-510 accepts two types of encoder signal inputs: single-ended (TTL) or differential line dri ver .
FP-QUAD-510 4 www.ni.com Figure 3. Basic Field Connections to Single-Ended Encoders The FP-QU AD-510 supports differential inputs for Phase A, Phase B, and Index signals. Y ou can easily accommodate encoders with various phase relationships b y sw apping the signals and/or connecting them to the in verting inputs as specific applications require.
© National Instruments Corp. 5 FP-QUAD-510 T erminal assignments and wiring diagrams are also listed under the slide-in card on the front of the FP-QU AD-510 module. Status Indicators Figure 5 show s the module label and status indicators. Remov e the slide-in card to see wiring diagrams for the input signals.
FP-QUAD-510 6 www.ni.com Position Counter Operation Each position counter has a 32-bit binary counter th at represents the current position of the shaft connected to the axis. Channels 0 through 3 contain the lo west 16 bits of these counters f or axes 0 through 3 respecti ve ly .
© National Instruments Corp. 7 FP-QUAD-510 Reset on Index Capability Y ou can configure each position counter to reset each time the index condition is met. An index-initiated reset resets both the upper and lo wer 16-bit reg ister s associated with that axis.
FP-QUAD-510 8 www.ni.com The vel oci ty range is the ma ximum v elocity that can be measured for a gi ven timebase. The velocity re gister uses a 15-bit counter , which giv es a maximum number of counts of 2 15 , or 32,768.
© National Instruments Corp. 9 FP-QUAD-510 Note If the axis is stopped with the index condition true, then reading the status bit causes the bit to reset to 0. Howe ver , since the index condition is still true, the bit is immediately latched back to 1.
FP-QUAD-510 10 www.ni.com • As with any hazardous voltage wiring, mak e sure that all wiring and connection s meet applicable electrical codes and common sense practices. Mount terminal bases in an area, position, or cabinet that pre vents accidental or unauthorized access to wiring that carries hazar dous voltages.
© National Instruments Corp. 11 FP-QUAD-510 Specifications The following specif ications are typical for a range of –40 to +70 °C, unless otherwise noted. Encoder Input Number of channels ............ ............. . 4 Input type Single-ended ....
CE Mark Compliance This product meets applicable EU directi ve(s), as follo ws: Safety isolation ................................ EN 61010 (double insulation for 250 Vrms working isolation, installation category I I) EMC directi ve Immunity ..........
An important point after buying a device National Instruments Quadrature Input Module FP-QUAD-510 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought National Instruments Quadrature Input Module FP-QUAD-510 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data National Instruments Quadrature Input Module FP-QUAD-510 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, National Instruments Quadrature Input Module FP-QUAD-510 you will learn all the available features of the product, as well as information on its operation. The information that you get National Instruments Quadrature Input Module FP-QUAD-510 will certainly help you make a decision on the purchase.
If you already are a holder of National Instruments Quadrature Input Module FP-QUAD-510, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime National Instruments Quadrature Input Module FP-QUAD-510.
However, one of the most important roles played by the user manual is to help in solving problems with National Instruments Quadrature Input Module FP-QUAD-510. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device National Instruments Quadrature Input Module FP-QUAD-510 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center