WARNING
SM1 / SM1VR (1-Tank Monitoring Systems)
14 in. (355 mm)
14 in. (355 mm)
Disconnect all electrical power to the machine.
Make sure the machine cannot operate during installation.
1-1/2 in. (38 mm)
Follow all safety warnings of the machine manufacturer.
1/4 in. (6 mm) dia.
Read and follow all installation instructions.
3 in. (76 mm)
1-1/2 in. (38 mm)
The SM Series System can monitor above or below ground, single or multi-tank systems (4 tanks maximum). The SM Series includes BGT1 gage (s) in a wall mounting panel. The SMVR series includes a vapor recovery option that compensates for gas blankets or head pressure caused by vapor recovery storage systems. The SM includes a push-button actuated electrical pump assembly, that supplies the air to clear sensing lines for current readings. Pump oper- ating voltages available are 120 or 230 VAC (see below).
25-3/8 in. (645 mm)
14 in. (355 mm)
2-1/2 in. (63 mm)
1/4 in. (6 mm) dia.
3 in. (76 mm) 1-3/16 in. (30 mm)
SM1: 27 lb. (12.25 kg) approximately. SM2: 44 lb. (20 kg) approx. SM3: 54 lb. (24.5 kg) approx. SM4: 65 lb. (29.5 kg) approx. Shipping Dimensions for All Models (P100 Pump included):
36 in. (914 mm)
40 x 9 x 15-3/4 in. (1016 x 229 x 400 mm).
14 in. (355 mm)
Operating Voltage: 120 VAC (SMPA); 230 VAC (SMPA230). Power Cable: Insulated, 16 AWG (1.5 mm2) x 8 ft. (2.4 m). Case: Weatherproof enclosure; painted. Shipping Weight: 10 lbs. (4.53 kg). Shipping Dimensions: 12 x 12 x 10 in. (305 x 305 x 254 mm).
2-1/2 in. (63 mm)
1/4 in. (6 mm) dia. 4-places–Mounting Holes
3 in. (76 mm) 1-3/16 in. (30 mm)
39-1/2 in. (1 m)
1-1/4 in. (32 mm)
14 in. (355 mm)
12-1/4 in. (311 mm)
9/32 in. (7 mm) dia.
6-places 10 in. (254 mm)
2-1/2 in. (63 mm)
1/4 in. (6 mm) dia. 4-places–Mounting Holes
3 in. (76 mm) 1-3/16 in. (30 mm)
4-1/8 in. (105 mm) 3 in. (76 mm)
3 in. (76 mm)
5/8 in. (16 mm)
* Mounting dimensions also apply for vertical mounting configurations.
4-places Mounting Holes · 4-places Mounting Holes

Installing a Tank Plug Kit (all models) The tank plug kit includes 12 ft. (3.6 m) x 1/4 in. (6 mm) dia. stainless steel tube and fittings. Tank plug is available in 2 NPT or 4 NPT. 1. Locate tank(s) service cover and install a UTKN tank plug kit for each tank. Necessary hardware is available from Murphy, refer to “Service Parts and Accessories” section, on page 4.
SM1 Model
A. Manwell B. Driveway Surface C. UTKN Tank Plug D. Coupling E. Stand-Pipe F. Tank Plug Opening G. 1/4 in. (6 mm) dia. Steel Tube
Vapor Recovery connection (plugged)
MURPHY LEVELGAGE
1/4 x 12 ft. (3.6 m) Steel Tubing
D
E F
Below ground tank (vented)
1/4 in. (6 mm) dia. 304 Stainless Steel tubing (probe); 12 ft. (3.6 m) long Compression
Steel Tube Located 3 in. (76 mm) Off Bottom (typical)
A. First, loosen ferrule and ferrule
Hole Plug Sensor Fitting
fitting nut.
B. Insert the tubing through the
ferrule nut and fitting.
C. Mark tubing at top of fitting–raise tub-
ing exactly 3 in. (76 mm) off bottom and finger tighten ferrule and compression nut.
A. Manwell B. Driveway Surface C. UTKN Tank Plug D. Coupling E. Stand-Pipe F. Tank Plug Opening G. 1/4 in. (6 mm) dia. Steel Tube H. Vapor Recovery Line
D. Cut excess stainless steel tubing allowing 1/2 in. (13 mm) extension
above the compression nut.
Detail B
MURPHY LEVELGAGE
Tubing Fitting (2 included)
6. For SMVR models, connect a second line from the tank top (if using UTKN kit, remove Hole Plug and install second sensor fit- ting and line) to the SMVR gage 1/8 NPTF fitting line. Second sensing line is to be installed through the tank top and into the tank, but keep the tip of the line above product level (refer to Fig. 2, at right and Fig. 3, next page). 7. Securely tighten all fittings; all connections must be air tight.
1/2 in. (13 mm)
Below ground tank (vented) Keep tip of line above product level
UTKN Tank Plug or tank top
Steel Tube Located 3 in. (76 mm) Off Bottom (typical)

Installing the CKBO Check Valve The optional CKBO check valve is designed to prevent product from backing up into the gage(s). We recommend installing the CKBO valve at top of the tank plug as follows (refer to Detail C): 1. Determine a location for the valve. Use of sealant on all fitting threads is strongly suggested. 2. Attach CKBO to the tank plug using wrench on valve flats. See markings on the valve body for positioning. 3. Attach tubing to CKBO as shown. Securely tighten all fittings. All connections must be air tight.
Detail C
FEET
FEET
T A N K
MURPHY LEVELGAGE
MURPHY LEVELGAGE
1/2 NPTM to 1/4 NPTF Reducer
1/4 NPTM straight fitting
UTKN Tank Plug or tank top Hole Plug
Installing the SMPA/SMPA230 Pump Assembly The pump assembly should be installed near the SM or SMVR panel. Connect the pump as follows (refer to Fig. 3 and 4 also see Detail D): 1. Before connecting the tubing from the SM or SMVR panel to the pump assembly, make sure the tubing reaches the pump assembly sensor fitting. 2. Connect the end of the tubing to the sen- sor fitting as shown at right (Detail D). Tubing should be continuous length without splices. 3. The pump assembly includes a power cable, 16 AWG (1.5 mm2), 8 ft. (2.4 m) long. Connect the cable to 120 VAC or 230 VAC power source.
To Tank 2 Plug
To Tank 1 Plug
To Tank 1 Plug Vapor Recovery
To Tank 2 Plug Vapor Recovery
Fig. 4 Pump Assembly
Y
S
W
H
G
M
U
R
P
PSI
A
G
E
The pump assembly has a pressure SWICHGAGE®
with low and high pressure set points. When the gage pointer reaches the low pressure set point, the pump starts to built up purge pressure. When the pointer reaches the high set point, sufficient volume is reached stopping the pump. The set points are factory pre-set for your convenience.
Resetting the Pointer
120 VAC or 230 VAC
Tubing to SM Panel
After the SM/SMVR complete system has been connected, reset the pointer for proper level indication, proceed as follows (see Fig. 5 and Detail E): 1. Determine actual product level by any reliable means and record this value. 2. Very carefully remove the retaining ring guarding against its spring-action, it can cause injuries. Remove the lens also. 3. Carefully hold the pointer, as shown at right, making sure not to bend it. 4. With a small screwdriver, turn the setting screw to corresponding stick reading value recorded in step 1. Clockwise to raise the pointer — counter clockwise to lower the pointer. 5. Replace the lens and snap ring.
Turn to Raise the Pointer
FEET
Turn to Lower the Pointer
MURPHY LEVELGAGE
UNLEADED UNLEADED

SM Panel (SM2 Model Shown)
1. Make sure that the pump assembly is connected to a power source, either 120 VAC or 230 VAC according to the pump model used. 2. Depress the read button, located next to the gage(s) and hold until the gage pointer stops traveling across the scale. See Fig. 6, at right. 3. When pointer stops release the read button to allow pointer to settle. 4. The value observed in the dial of the gage, is the level of the tank. 5. Perform this operation as necessary for each tank to be checked.
FEET
MURPHY LEVELGAGE
MURPHY LEVELGAGE
UNLEADED UNLEADED
Service Parts and Accessories
UTKN2: 2 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings). UTKN2LT: 2 NPTM tank plug less tubing (includes fittings). UTKN4: 4 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings). UTKN4LT: 4 NPTM tank plug less tubing (includes fittings). UTKN4VR: 4 NPTM tank kit for vapor recovery (tubing and fittings included). UTKN4VRLT: 4 NPTM tank plug for vapor recovery– less tubing (includes fittings). SMPA: Pump assembly for 120 VAC. SMPA230: Pump assembly for 230 VAC. 05090051: Pressure SWICHGAGE® instrument with low and high pressure limit contacts, 15 psi scale. CKBO: Check Valve assembly–prevents product from backing up into gage. 85-01-0405: 1/2 NPTM x 1/4 NPTF reducing bushing–for CKBO valve mounting. 85-01-0402: 1/4 in. (6 mm) dia. 316 stainless steel tubing/ft. (probe). 85-01-0403: 1/4 in. (6 mm) dia. poly tubing/ft. (sensing line). 86-03-0405: 1/4 x 1/4 male hex nipple kit–for connecting tubing line to tank top. 85-03-0407: 1/4 x 1/4 male hex fitting kit–for connecting tubing or probe line to the tank top.
Warranty A two year limited warranty on materials and workmanship is provided with this Murphy product.
Details are available on request and are packed with each unit.
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
® FRANK W.
I Frank W. Murphy, Ltd. Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. tel. +44 1722 410055 fax +44 1722 410088 tlx 477088 e-mail sales@fwmurphy.co.uk I Frank W. Murphy Pte., Ltd. 26 Siglap Drive; Republic of Singapore 456153 tel. +65 241-3166 fax +65 241-8382 e-mail fwmsales@fwmurphy.com.sg I Murphek Pty., Ltd. 1620 Hume Highway; Campbellfield, Vic 3061; Australia tel. +61 3 9358-5555 fax +61 3 9358-5558
I Murphy de México, S.A. de C.V. Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 tel. +52-48-206264 fax +52-48-206336 e-mail murmexsl@sanluis.podernet.com.mx I Murphy Switch of California P.O. Box 900788; Palmdale, California 93590; USA tel. (805) 272-4700 fax (805) 947-7570 e-mail sales@murphyswitch.com I Frank W. Murphy France tel. +33 1 30 762626 fax +33 1 30 763989
MFR.
I Frank W. Murphy Manufacturer P.O. Box 470248; Tulsa, Oklahoma 74147; USA tel. (918) 627-3550 fax (918) 664-6146 e-mail fwmurphy@ionet.net
I Frank W. Murphy Southern Division P.O. Box 1819; Rosenberg, Texas 77471; USA tel. (281) 342-0297 fax (281) 341-6006 e-mail murphysd@intertex.net
Printed in U.S.A.