SM Series TANKTENDTM Systems Installation and Operation Instructions Models: SM1, SM1VR, SM2, SM2VR, SM3, SM3VR, SM4, SM4VRTSM-95129N Revised 01-97 Section 15 (00-02-2019) FRANK W. ® MFR. Please read the following information before installing. A visual inspection of this product for damage during shipping is recommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.

GENERAL INFORMATION

Mounting Dimensions

WARNING

SM1 / SM1VR (1-Tank Monitoring Systems)

14 in. (355 mm)

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

14 in. (355 mm)

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

1-1/2 in. (38 mm)

Follow all safety warnings of the machine manufacturer.

1/4 in. (6 mm) dia.

Read and follow all installation instructions.

3 in. (76 mm)

1-1/2 in. (38 mm)

The SM Series System can monitor above or below ground, single or multi-tank systems (4 tanks maximum). The SM Series includes BGT1 gage (s) in a wall mounting panel. The SMVR series includes a vapor recovery option that compensates for gas blankets or head pressure caused by vapor recovery storage systems. The SM includes a push-button actuated electrical pump assembly, that supplies the air to clear sensing lines for current readings. Pump oper- ating voltages available are 120 or 230 VAC (see below).

SM2 / SM2VR (2-Tank Monitoring Systems) *

25-3/8 in. (645 mm)

14 in. (355 mm)

2-1/2 in. (63 mm)

1/4 in. (6 mm) dia.

SM Series Specifications PanelHollow wall mount, cold rolled steel, painted. Shipping Weight (P100 Pump included):

3 in. (76 mm) 1-3/16 in. (30 mm)

SM1: 27 lb. (12.25 kg) approximately. SM2: 44 lb. (20 kg) approx. SM3: 54 lb. (24.5 kg) approx. SM4: 65 lb. (29.5 kg) approx. Shipping Dimensions for All Models (P100 Pump included):

SM3 / SM3VR (3-Tank Monitoring Systems) *

36 in. (914 mm)

40 x 9 x 15-3/4 in. (1016 x 229 x 400 mm).

14 in. (355 mm)

SMPA and SMPA230 Pump Assemblies

Operating Voltage: 120 VAC (SMPA); 230 VAC (SMPA230). Power Cable: Insulated, 16 AWG (1.5 mm2) x 8 ft. (2.4 m). Case: Weatherproof enclosure; painted. Shipping Weight: 10 lbs. (4.53 kg). Shipping Dimensions: 12 x 12 x 10 in. (305 x 305 x 254 mm).

2-1/2 in. (63 mm)

1/4 in. (6 mm) dia. 4-places–Mounting Holes

3 in. (76 mm) 1-3/16 in. (30 mm)

SM4 / SM4VR (4-Tank Monitoring Systems) * SMPA and SMPA230 Mounting Dimensions

39-1/2 in. (1 m)

1-1/4 in. (32 mm)

14 in. (355 mm)

12-1/4 in. (311 mm)

9/32 in. (7 mm) dia.

6-places 10 in. (254 mm)

2-1/2 in. (63 mm)

1/4 in. (6 mm) dia. 4-places–Mounting Holes

3 in. (76 mm) 1-3/16 in. (30 mm)

4-1/8 in. (105 mm) 3 in. (76 mm)

3 in. (76 mm)

5/8 in. (16 mm)

* Mounting dimensions also apply for vertical mounting configurations.

4-places Mounting Holes · 4-places Mounting Holes

Page 2 of the Murphy SM4VR user manual — G
Page 2 · click to enlarge
Page 2

INSTALLATION

Installing a Tank Plug Kit (all models) The tank plug kit includes 12 ft. (3.6 m) x 1/4 in. (6 mm) dia. stainless steel tube and fittings. Tank plug is available in 2 NPT or 4 NPT. 1. Locate tank(s) service cover and install a UTKN tank plug kit for each tank. Necessary hardware is available from Murphy, refer to “Service Parts and Accessories” section, on page 4.

Fig. 1 SM Series Typical Installation

Tank Plug

SM1 Model

A. Manwell B. Driveway Surface C. UTKN Tank Plug D. Coupling E. Stand-Pipe F. Tank Plug Opening G. 1/4 in. (6 mm) dia. Steel Tube

Vapor Recovery connection (plugged)

FEET

MURPHY LEVELGAGE

2. Route a tubing line (1/4 in. [6 mm] outside dimension) from the tank top to the panel location. If applicable, cut a channel in the driveway surface to route the tubing. The use of rigid conduit is recommended especially when routing the tubing line under a driveway surface. Refer to Fig. 1 , at right.

1/4 x 12 ft. (3.6 m) Steel Tubing

A B

D

E F

3. Before inserting the 1/4 in. (6 mm) dia. stainless steel tubing (probe) through tank plug fitting, make sure tubing can reach bottom and also will allow extra tubing for adjustments. Now lower the tubing until it touches the bottom of the tank, do this as follows (refer to Detail A, at right ):

Detail A

Below ground tank (vented)

G

1/4 in. (6 mm) dia. 304 Stainless Steel tubing (probe); 12 ft. (3.6 m) long Compression

Steel Tube Located 3 in. (76 mm) Off Bottom (typical)

A. First, loosen ferrule and ferrule

Hole Plug Sensor Fitting

fitting nut.

B. Insert the tubing through the

ferrule nut and fitting.

C. Mark tubing at top of fitting–raise tub-

ing exactly 3 in. (76 mm) off bottom and finger tighten ferrule and compression nut.

Fig. 2 SMVR Series (Vapor Recovery Systems)

A. Manwell B. Driveway Surface C. UTKN Tank Plug D. Coupling E. Stand-Pipe F. Tank Plug Opening G. 1/4 in. (6 mm) dia. Steel Tube H. Vapor Recovery Line

SM1 Model

D. Cut excess stainless steel tubing allowing 1/2 in. (13 mm) extension

above the compression nut.

FEET

Detail B

MURPHY LEVELGAGE

4. Connect tubing line to tank probe as shown (refer to Detail B , at right).

A B

5. Now connect other end of tubing line to the SM/SMVR gage panel fitting. Tubing should be continuous length without splices.

Tubing Fitting (2 included)

D

6. For SMVR models, connect a second line from the tank top (if using UTKN kit, remove Hole Plug and install second sensor fit- ting and line) to the SMVR gage 1/8 NPTF fitting line. Second sensing line is to be installed through the tank top and into the tank, but keep the tip of the line above product level (refer to Fig. 2, at right and Fig. 3, next page). 7. Securely tighten all fittings; all connections must be air tight.

E F

1/2 in. (13 mm)

Below ground tank (vented) Keep tip of line above product level

H

UTKN Tank Plug or tank top

G

Steel Tube Located 3 in. (76 mm) Off Bottom (typical)

Show 17 more labels / short text on this page
Tubing Connection · To Pump Assembly · Tubing · Nut · Ferrule · Product · UTKN Tank Plug · typical Installation · To Pump Assembly · Tubing · Tubing · Vapor Recovery Tubing · Ferrule · Compression · Nut · Hole Plug · Product
Page 3 of the Murphy SM4VR user manual — MURPHY LEVELGAGE
Page 3 · click to enlarge
Page 3

INSTALLATION Continued

Installing the CKBO Check Valve The optional CKBO check valve is designed to prevent product from backing up into the gage(s). We recommend installing the CKBO valve at top of the tank plug as follows (refer to Detail C): 1. Determine a location for the valve. Use of sealant on all fitting threads is strongly suggested. 2. Attach CKBO to the tank plug using wrench on valve flats. See markings on the valve body for positioning. 3. Attach tubing to CKBO as shown. Securely tighten all fittings. All connections must be air tight.

Fig. 3 SM Panel Tubing Configuration

SM Panel (SM2 Model Shown)

Detail C

FEET

FEET

T A N K

MURPHY LEVELGAGE

MURPHY LEVELGAGE

1/2 NPTM to 1/4 NPTF Reducer

1/4 NPTM straight fitting

UTKN Tank Plug or tank top Hole Plug

Installing the SMPA/SMPA230 Pump Assembly The pump assembly should be installed near the SM or SMVR panel. Connect the pump as follows (refer to Fig. 3 and 4 also see Detail D): 1. Before connecting the tubing from the SM or SMVR panel to the pump assembly, make sure the tubing reaches the pump assembly sensor fitting. 2. Connect the end of the tubing to the sen- sor fitting as shown at right (Detail D). Tubing should be continuous length without splices. 3. The pump assembly includes a power cable, 16 AWG (1.5 mm2), 8 ft. (2.4 m) long. Connect the cable to 120 VAC or 230 VAC power source.

To Tank 2 Plug

To Tank 1 Plug

To Tank 1 Plug Vapor Recovery

To Tank 2 Plug Vapor Recovery

Detail D

Fig. 4 Pump Assembly

H

Y

S

W

H

G

M

U

R

P

PSI

A

G

E

The pump assembly has a pressure SWICHGAGE®

with low and high pressure set points. When the gage pointer reaches the low pressure set point, the pump starts to built up purge pressure. When the pointer reaches the high set point, sufficient volume is reached stopping the pump. The set points are factory pre-set for your convenience.

PRESSURE

Resetting the Pointer

120 VAC or 230 VAC

Tubing to SM Panel

After the SM/SMVR complete system has been connected, reset the pointer for proper level indication, proceed as follows (see Fig. 5 and Detail E): 1. Determine actual product level by any reliable means and record this value. 2. Very carefully remove the retaining ring guarding against its spring-action, it can cause injuries. Remove the lens also. 3. Carefully hold the pointer, as shown at right, making sure not to bend it. 4. With a small screwdriver, turn the setting screw to corresponding stick reading value recorded in step 1. Clockwise to raise the pointer — counter clockwise to lower the pointer. 5. Replace the lens and snap ring.

Detail E

SM Panel (SM2 Model Shown)

Turn to Raise the Pointer

FEET

FEET

Turn to Lower the Pointer

MURPHY LEVELGAGE

MURPHY LEVELGAGE

UNLEADED UNLEADED

Show 30 more labels / short text on this page
(SM2 Model shown) · 1/4 NPTM straight · Tubing · fitting · Valve Flat · Check Valve · Ferrule Ferrule nut · To Pump Assembly · Sensor Fitting · Sensor Fitting · Fitting · Fitting · Pump Panel · Sensor Fitting · Power · Cable · Ferrule · Pressure SWICHGAGE® · Compression · Tubing · Nut · ® · kPa · Low trip point · High trip point · adjustment · adjustment · Snap Ring · Pointer · Read Button
Page 4 of the Murphy SM4VR user manual — FEET
Page 4 · click to enlarge
Page 4

INSTALLATION Continued

Operation Sequence

SM Panel (SM2 Model Shown)

1. Make sure that the pump assembly is connected to a power source, either 120 VAC or 230 VAC according to the pump model used. 2. Depress the read button, located next to the gage(s) and hold until the gage pointer stops traveling across the scale. See Fig. 6, at right. 3. When pointer stops release the read button to allow pointer to settle. 4. The value observed in the dial of the gage, is the level of the tank. 5. Perform this operation as necessary for each tank to be checked.

FEET

FEET

MURPHY LEVELGAGE

MURPHY LEVELGAGE

UNLEADED UNLEADED

Service Parts and Accessories

UTKN2: 2 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings). UTKN2LT: 2 NPTM tank plug less tubing (includes fittings). UTKN4: 4 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings). UTKN4LT: 4 NPTM tank plug less tubing (includes fittings). UTKN4VR: 4 NPTM tank kit for vapor recovery (tubing and fittings included). UTKN4VRLT: 4 NPTM tank plug for vapor recovery– less tubing (includes fittings). SMPA: Pump assembly for 120 VAC. SMPA230: Pump assembly for 230 VAC. 05090051: Pressure SWICHGAGE® instrument with low and high pressure limit contacts, 15 psi scale. CKBO: Check Valve assembly–prevents product from backing up into gage. 85-01-0405: 1/2 NPTM x 1/4 NPTF reducing bushing–for CKBO valve mounting. 85-01-0402: 1/4 in. (6 mm) dia. 316 stainless steel tubing/ft. (probe). 85-01-0403: 1/4 in. (6 mm) dia. poly tubing/ft. (sensing line). 86-03-0405: 1/4 x 1/4 male hex nipple kit–for connecting tubing line to tank top. 85-03-0407: 1/4 x 1/4 male hex fitting kit–for connecting tubing or probe line to the tank top.

Warranty A two year limited warranty on materials and workmanship is provided with this Murphy product.

Details are available on request and are packed with each unit.

In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.

® FRANK W.

I Frank W. Murphy, Ltd. Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. tel. +44 1722 410055 fax +44 1722 410088 tlx 477088 e-mail sales@fwmurphy.co.uk I Frank W. Murphy Pte., Ltd. 26 Siglap Drive; Republic of Singapore 456153 tel. +65 241-3166 fax +65 241-8382 e-mail fwmsales@fwmurphy.com.sg I Murphek Pty., Ltd. 1620 Hume Highway; Campbellfield, Vic 3061; Australia tel. +61 3 9358-5555 fax +61 3 9358-5558

I Murphy de México, S.A. de C.V. Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 tel. +52-48-206264 fax +52-48-206336 e-mail murmexsl@sanluis.podernet.com.mx I Murphy Switch of California P.O. Box 900788; Palmdale, California 93590; USA tel. (805) 272-4700 fax (805) 947-7570 e-mail sales@murphyswitch.com I Frank W. Murphy France tel. +33 1 30 762626 fax +33 1 30 763989

MFR.

I Frank W. Murphy Manufacturer P.O. Box 470248; Tulsa, Oklahoma 74147; USA tel. (918) 627-3550 fax (918) 664-6146 e-mail fwmurphy@ionet.net

I Frank W. Murphy Southern Division P.O. Box 1819; Rosenberg, Texas 77471; USA tel. (281) 342-0297 fax (281) 341-6006 e-mail murphysd@intertex.net

Printed in U.S.A.

Show 4 more labels / short text on this page
Snap Ring · Pointer · Read Button · Since 1939
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Murphy SM4VR

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.