R M011101 Issue 6, revised 06/99

Autostart’s operating mode is selected by use of its 3 position front facia switch:– Off/reset. Disables the engine and resets a latched fault condition.
Automatic start-up, load transfer and return to standby in response to a mains fail or remote start condition, with full fault protection. Manual start and stop of the generator, either immediately on selecting manual mode or by use of remote push button switches. Green and amber LEDs around the switch indicate the selection of Auto and Manual modes. On keyswitch versions, the key is common to all units and may be removed in the Off and Auto positions only. Control Outputs
In Auto or Manual modes, Autostart will shut down and latch out the generator on detection of low oil pressure, high engine temperature, overspeed, start fail or emergency stop faults. The Autostart may also be set up to shut down the generator on low generator frequency or speed.
3 additional inputs may be used with remote fault switches (giving a ‘shutdown’ or ‘warning’ response), or as control inputs with remote contacts or panel switches (see overleaf).
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our
Non-latching, 'warning only' alarms are fitted for high and low battery volts, charge fail and mag. pickup fail conditions.
specifications and designs at any time.
Catalogue section 75 · Operation


The Autostart 705 has over 40 programmable functions:- Timers:-
Start delay; preheat, crank and crank cool (dwell) times; fault override time; warm-up delay, mains restore delay; engine cool (run on, off load) time, speed signal delay. Inputs:-
Inputs 1 and 2 are dedicated for use with low oil pressure and high engine temperature switch sensors. Inputs 3, 4 and 5 may be programmed for a range of uses, including shutdown or warning faults, lamp test, manual restore (of mains), test off load, alarm mute, etc. The inputs may be set up to work with remote contacts which either open or close when active, with wiring to either +ve or –ve DC. Outputs:-
6 programmable outputs, each of which may be set to give one of over 30 signalling or control ‘actions’, including: Preheat (4 types), Energised to Stop Fuel, Louvre Control, Generator Available, Common Alarm, Alarm (muteable), Shutdown Fault, Warning Fault, Overspeed, Start Fail, individual input faults (1 - 5), etc. LED indicators:-

5 programmable LED indicators, each of which may be set to display extra status information (e.g. ‘generator on load’, ‘fuel on’) or specific faults which are not indicated by the dedicated LEDs (e.g. low/high/faulty battery voltage, low generator volts, magnetic pickup failure, etc.). Next to the 5 LEDs is a windowed 'pocket' in the front label, into which a custom message label may be inserted. A sheet of typical fault and status messages is supplied with each unit. Other System parameters:-
Crank release (by engine RPM, generator Hz. or charge alternator WL voltage), underspeed and overspeed trip levels (Hz. or RPM); maximum number of start attempts; high and low battery voltage warning levels; enable or disable loading of generator in manual mode. Each Autostart is programmed by use of Murphy-Modex communication software running on an IBM compatible PC or lap-top. The computer is connected to the Autostart through a small interface unit and serial lead. Autostart program ‘profiles’ may be created, edited or saved on the computer’s hard disk, up-loaded from or down-loaded to any number of Autostarts, quickly and error-free. The software also has a real-time monitoring feature, allowing the PC to display data such as operating mode, engine running status, speed/ frequency, hours run, fault conditions, battery voltage, input/output status, etc.
For a typical connection circuit, please see Autostart 710 data sheet (the Autostart 705 and 710 are pin compatible).
When ordering, please specify:-
Accessories:- AS7CA 9 way (interface) to 9 way (PC) comms lead AS7CB 9 way (interface) to 25 way (PC) comms lead AS7CC interface for local RS232 communications AS7CK AS7xx communication and programming software
K = keyswitch R = rotary (knob) switch
D = 230 VAC C = 110 VAC
AS705S
Frank W. Murphy Ltd. Incorporating Modex Automation Church Road, Laverstock, Salisbury U.K. Tel: + 44 1722 410055 Fax + 44 1722 410088 Pour service en Français, tél: + 44 1722 410697 email: sales@fwmurphy.co.uk web: http://www.fwmurphy.co.uk
Frank W. Murphy Ltd. en France Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 Direct usine Tel: + 44 1722 410697 email: sales@fwmurphy.co.uk
Frank W. Murphy Southern Division PO Box 1819, Rosenberg, Texas 77471, USA Tel: + 1 281 342 0297 Fax: + 1 281 341 6006 email: sales@fwmurphy.com
Macquarrie Corporation 1620 Hume Highway, Campbellfield, Vic. 3061 Australia Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558 email: murphy@macquarrie.com.au Murphy Switch of California 41343 12th Street West, Palmdale, CA 93551, USA Tel: + 1 661 272 4700 Fax: + 1 661 947 7570 email: sales@murphyswitch.com web: http://www.murphyswitch.com
Frank W. Murphy Manufacturer PO Box 470248, Tulsa, Oklahoma 74147, USA Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 email: sales@fwmurphy.com web: http://www.fwmurphy.com
Frank W. Murphy Pte, Ltd. No. 2 Tuas South Street 2, Sprintecs Building 02-01/02, Singapore 637895 Tel: + 65 863 1398 Fax: + 65 863 0208 email: fwmsales@fwmurphy.com.sg
Murphy de Mexico S.A. de C.V. Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P. México 78384 Tel: + 52 48 206264 Fax: + 52 48 206336 email: murmexsl@sanluis.podernet.com.mx
Programmable functions · Since 1939
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.