Example: DCDF165-Y C
D D 165 - Y *
F
F = Fan Speed Control L = Main Control / Lee-Temp C = No Control / Chiller
Lee-Temp T = Ambient Fan Cycle/
Lee-Temp V = Variable Frequency
Drive (VFD) Control (available only for dual refrigerant circuit condensers
D = Disconnect Switch
S = Single Refrigerant Circuit D = Dual Refrigerant Circuit
P = 208/230V-1ph-60Hz Z = 460V-1ph-60Hz V = 575V-1ph-60Hz W = 200/230V-1ph-50Hz Y = 208/230V-3ph-60Hz A = 460V-3ph-60Hz B = 575V-3ph-60Hz N = 200/230V-3ph-50Hz M = 380/415V-3ph-50Hz
(optional on Fan Speed Control, Chiller & Standard Lee-Temp Condensers; standard on Quiet-Line and VFD Control condensers T = TVSS & Disconnect
Switch; available only on the VFD Control condensers
* Single-phase voltage is only voltage available as standard on Fan Speed Control 1-fan condensers * Three-phase voltage is only voltage available as standard on condensers with VFD Control, Lee-temp receivers, and Fan Speed Control (2-8 fan models only). * VFD Control Condensers are not available in 575-3-60.
NOT ALL POSSIBLE COMBINATIONS OF MODELS, CONTROLS AND VOLTAGES ARE AVAILABLE.
Reserved · Condenser · Model Size



The Liebert condenser is low-profile direct-drive propeller fan-type air cooled unit suitable for mount- ing outdoors. It provides for the heat rejection of either one or two separate refrigeration circuits, matching heat rejection capacity varying with the outdoor ambient temperatures with each corre- sponding compressors heat rejection requirements. Constructed with an aluminum cabinet and a cop- per-tube aluminum fin coil, the unit is quiet and corrosion resistant. The condenser is quickly and easily installed, because all internal wiring is completed at the factory with only electrical connec- tions to be made at the job site. All electrical connections and controls are enclosed in an integral weatherproof section of the condenser.

Fan speed control utilizes a wave-chopper control to vary the air volume over the condenser coil, based on refrigerant head pressure. The fan motor next to the electrical panel (two fans on 6-fan and 8-fan models) is a single-phase, permanent split capacitor motor with motor speed adjusted in response to refrigerant pressure. The balance of fans on multi-fan units cycle on ambient thermostats. The control system provides refrigerant head pressure control for outdoor ambients as low as -20°F (-28.9 °C).
VFD Condenser control system utilizes a variable frequency drive, inverter duty fan motor operating from 0% to 100% motor RPM based on head pressure, sensed by refrigerant pressure transducers. VFD, ambient-temperature thermostat(s), motor overload protection and electrical control circuit are factory-wired in the integral control panel. VFD controls the fan adjacent to the connection end of the condenser and remains energized with active compressor operation. The balance of fans on multi-fan units cycle on ambient thermostats. This system provides refrigerant head pressure control for out- door ambients as low as -20°F (-28.9°C).
Introduction

The Liebert Lee-Temp head pressure control system is designed to maintain proper operating head pressures in outdoor temperatures down to -30°F (-34.4°C). The condensers utilize head pressure con- trol valves, extra refrigerant and insulated refrigerant receivers with heater pads. It works by flood- ing the condenser coil with liquid refrigerant to a level that balances the system condensing requirements with the condenser coil surface available to reject the system heat. During the summer, the system requires the entire condenser coil surface for heat rejection and most of the refrigerant is stored in a receiver. In the winter, the same amount of heat can be rejected by only a fraction of the coil surface. As head pressure begins to fall, the control valve restricts the flow of liquid refrigerant exiting from the condenser. This extra liquid refrigerant reduces the effective condenser surface area available for heat transfer. The head pressure control valve also bypasses hot gas into the receiver to warm the liquid and maintain liquid pressure for proper operation of the expansion valve. Condenser fan controls are either fan cycling on ambient temperature or constant on. Lee-Temp control is required for Quiet-Line Condensers.
All Fan Speed and VFD Condensers are standard condensers with moderate operating sound levels. Lee-Temp Condensers with standard-size coils matching Fan Speed and VFD coil sizes are standard sound level condensers.
Quiet-Line condensers can help your facility meet the strictest noise codes and do so at less cost than traditional condensers with acoustical shielding. The Quiet-Line condensers utilize the same reliable construction features of the standard condensers and have oversized coils and slower speed fan motors which yield the required heat rejection needed at significantly lower sound levels. Lee-Temp control is required for Quiet-Line Condensers.
Transient Voltage Surge Suppression (TVSS) panel is standard in the VFD Condenser models only. Surge protection is necessary because rooftop voltage supply often is not conditioned the same as the voltage supply inside the data center. The TVSS is designed to protect sensitive electronic condenser components from high voltage transients, up to 25kVA/phase.
An illuminated green LED indicates power supply is On and panel status is OK. An illuminated red LED indicates conditions require service and the TVSS may require replacement to restore surge pro- tection to the condenser.
Figure 2 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the outdoor condenser (VFD, Fan Speed Control or Lee-Temp) and field supplied interconnection piping.
Introduction

Relief Valve Service Valve
Inverted trap on discharge & liquid lines to extend above base of coil by a minimum of 7-1/2” (190mm).
Lee-Temp
Fan Speed and VFD
Liquid
* Traps every 25ft (7.6m) of rise
28-42kW Digital Solenoid Valve
53-70kW Digital Solenoid Valve
Field-installed relief valve(s) required for 50 Hz EU CE units rated maximum 480 PSIG (33 Bar).
Service Valve External Equalizer
Pitch horizontal hot gas piping 1/2" per 10 ft. (42mm per 10m) in direction of refrigerant/oil flow.
Liquid Return Filter Dryer Sight Glass Solenoid Valve Expansion Valve
Components are not supplied by Liebert, but are recommended for proper circuit operation and maintenance.
Field Refrigerant Piping Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connection With Valve Core
DPN000798 Rev. 2
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .

The condensers should be installed in a location offering maximum security and access for mainte- nance.
Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumula- tions. Utilize Piggyback condensers whenever interior building locations must be used. To ensure ade- quate air supply, Liebert recommends that condensers be installed in an area with clean air, away from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
The condenser must not be installed in a pit.
The condenser must be installed on a level surface to ensure proper refrigerant flow.
For roof installation, mount the condenser on suitable curbs or other supports in accordance with local codes.
Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering Department for assistance.
Site Preparation


Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Site Preparation


Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.

Site Preparation


Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Overalll height to the top of the fan guard is 43-1/8” (1095mm).
Site Preparation


Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers

Traps to extend above coil base by a minimum of 7-1/2" (190mm) Inverted Traps (field-supplied)
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately to avoid coil damage and loss of charge.
Site Preparation

Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers

Inverted Traps (field-supplied) to extend 8" (203mm) above coil base
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-provided). Support field piping separately to avoid coil damage and loss of charge.

Inlet Connection Upper Headers (Typ.) Entering Hot Gas Line Leaving Liquid Line Condenser Connections, Typical
Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
Site Preparation


Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
Site Preparation

Connection Size, OD, In. Net Weight
lb (kg) Hot Gas Liquid
CD*104 1 2 7/8 1/2 315 (143)
CS*104 1 1 1-1/8 5/8 315 (143)
CD*165 2 2 7/8 5/8 425 (193)
CS*165 2 1 1-1/8 7/8 425 (193)
CD*205 2 2 1-1/8 7/8 495 (225)
CS*205 2 1 1-1/8 7/8 495 (225)
CD*251 3 2 1-1/8 7/8 500 (227)
CS*251 3 1 1-3/8 1-1/8 500 (227)
CD* 308 3 2 1-3/8 1-1/8 670 (304)
CS*308 3 1 1-5/8 1-1/8 670 (304)
CD* 415 4 2 1-3/8 1-1/8 840 (381)
CS*415 4 1 1-5/8 1-1/8 840 (381)
CD*510 4 2 1-5/8 1-1/8 1188 (539)
CD*616 6 2 1-5/8 1-1/8 1380 (626)
CS*616 1 6 1 (2)1-5/8 (2)1-1/8 1380 (626)
CD*830 8 2 1-5/8 1-1/8 1750 (794)
CD*1010 8 2 2-1/8 1-5/8 2640 (1197)
DCS*063 1 1 1-1/8 5/8 315 (143)
DCD*063 1 2 7/8 1/2 315 (143)
DCS*119 2 1 1-1/8 7/8 425 (193)
DCD*119 2 1 1-1/8 7/8 425 (193)
DCS*127 2 1 1-1/8 7/8 495 (225)
DCD*127 2 2 1-1/8 7/8 495 (225)
DCS*143 2 1 1-1/8 7/8 515 (234)
DCD*143 2 2 1-1/8 7/8 515 (234)
DCS*214 3 1 1-5/8 1-1/8 840 (381)
DCD*214 3 2 1-1/8 7/8 840 (381)
DCS*286 4 1 2-1/8 1-1/8 1105 (501)
DCD*286 4 2 1-1/8 7/8 1105 (501)
DCD*409 6 2 1-5/8 1-1/8 1380 (626)
DCD*572 8 2 2-1/8 1-1/8 2430 (1102)

Planning for the refrigerant requirements of the completed system is the addition of the charges from Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping. Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting piping. Consult indoor unit manuals for indoor unit charge requirements.
These values can be used for obtaining adequate refrigerant for the system, but should not be used for final charging. Consult indoor unit manual for charging procedures.
Approximate R-22 Refrigerant Needed Approximate R-407C Refrigerant Needed
Dual Circuit lb/circuit (kg/circuit)
Dual Circuit lb/circuit (kg/circuit)
VFD
VFD
VFD
83 5 (2.3) 27 (12.3) 3 (1.4) 15 (6.8) 5 (2.3) 26 (11.8) 3 (1.4) 15 (6.8)
104 8 (3.6) 39 (17.7) 7 (3.2) 21 (9.5) 8 (3.6) 37 (16.8) 7 (3.2) 20 (9.0)
165 15 (6.8) 53 (24.0) 5 (2.3) 27 (12.3) 15 (6.8) 50 (22.7) 5 (2.3) 26 (11.8)
205 20 (9.1) 76 (34.5) 7 (3.2) 38 (17.2) 19 (8.6) 72 (32.7) 7 (3.2) 36 (16.3)
251 19 (8.6) 75 (34.0) 10 (4.6) 38 (17.2) 18 (8.2) 71 (32.23) 10 (4.6) 36 (16.3)
308 29 (13.2) 113 (51.3) 11 (5.0) 58 (26.3) 28 (12.7) 107 (48.5) 11 (5.0) 55 (24.9)
415 54 (24.5) 182 (82.6) 15 (6.8) 75 (34.0) 51 (23.1) 173 (78.4) 15 (6.8) 71 (32.2)
510 72 (32.7) N/A 30 (13.6) 149 (67.6) 68 (30.8) N/A 29 (13.2) 142 (64.4)
616 N/A 267 (121.3) 27 (12.3) 113 (51.3) N/A 254 (115.2) 26 (11.8) 108 (49.0)
830 N/A N/A 30 (13.6) 149 (67.6) N/A N/A 29 (13.2) 142 (64.4)
1010 N/A N/A 60 (27.2) 154 (69.9) N/A N/A 57 (25.9) 147 (66.7)
63 N/A 39 (17.7) N/A 21 (9.5) N/A 37 (16.8) N/A 20 (9.1)
119 N/A 50 (22.7) N/A 27 (12.3) N/A 48 (21.8) N/A 26 (11.8)
127 N/A 76 (34.5) N/A 38 (17.2) N/A 72 (32.6) N/A 36 (16.3)
143 N/A 126 (57.2) N/A 64 (29.0) N/A 120 (54.5) N/A 61 (27.7)
214 N/A 161 (73.0) N/A 81 (36.7) N/A 153 (69.4) N/A 77 (34.9)
286 N/A 196 (88.9) N/A 125 (56.7) N/A 186 (84.4) N/A 119 (54.0)
409 N/A N/A N/A 129 (58.5) N/A N/A N/A 125 (55.8)
572 N/A N/A N/A 196 (88.9) N/A N/A N/A 186 (84.4)
R-22, lb/100 ft. (kg/30m) R-407C, lb/100 ft. (kg/30m)
O.D., in.
Liquid Line Hot Gas Line Liquid Line Hot Gas Line
3/8 3.8 (1.7) — 3.7 (1.7) —
1/2 7.3 (3.3) — 6.9 (3.1) —
5/8 11.7 (5.3) 2.1 (1.0) 11.0 (5.0 2.2 (1.0)
3/4 16.6 (7.5) 3.0 (1.4) 15.7 (7.1) 3.1 (1.3)
7/8 24.4 (11.1) 4.4 (2.0) 23.0 (10.4) 4.5 (1.9)
1-1/8 41.4 (18.9) 7.8 (3.5) 39.3 (17.8) 7.8 (3.5)
1-3/8 63.3 (28.7) 11.8 (5.4) 59.8 (27.1 11.8 (5.4)
1-5/8 — 16.7 (7.6) — 16.7 (7.6)

Before unpacking the condenser, verify that the labeled equipment matches the bill of lading. Care- fully inspect all items for damage, either visible or concealed. Report any damage immediately to the carrier and your local Liebert representative. File a damage claim with the carrier and send a copy to your local Liebert representative.
All material used to package this unit is recyclable. Please save it for future use or dispose of the material appropriately. SAFETY INFORMATION
! WARNING Risk of top-heavy unit falling over. Can cause equipment damage, injury or death.
Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
! WARNING Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes, glasses and protective clothing should attempt to move, lift, remove packaging from or prepare unit for installation.
Risk of overhead interference. Can cause unit and/or structure damage. Refer to the installation plans prior to moving the unit to verify clearances. NOTICE
Risk of damage from forklift. Improper handling with the forklift. Can cause exterior and/or underside damage. Keep tines of the forklift level and at a height suitable to fit below the skid. NOTICE
Risk of unit damage if improperly stored. Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.




Transport the unit using a fork lift or a crane with sling and spreader bars.
Remove outer packaging when ready to install the unit. Be sure to locate, and set aside, the bag of mounting hardware that is to be used for mounting the support legs on the unit.




Three-fan unit shown for illustration. Methods for other sizes of condensers are the same.

3.4.1 Removing the Skid and Attaching Slings 1. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by Liebert. Liebert recommends using a 5/8" socket and ratchet. 2. Place slings or equivalent items through holes in the legs on 1, 2- and 3-fan condensers (see Step 2 and Step 3 in Figure 13). Use eyebolts for attaching a sling or similar equipment to 4-fan units. 3. Using spreader bars and a crane, or similar lifting equipment, lift the condenser off the skid to allow safely turning the condenser upright. 4. Lift the condenser and move it to the installation location.
Figure 13 Attaching legs and sling to a 1-, 2-, 3- or 4-fan condenser for moving



Three-fan unit shown for illustration. Method for 1-fan and 2--fan condensers is the same. Attach sling to 4-fan condensers with eyebolts.
Step 1 · Step 2 · Step 3

3.5.1 Removing the Skid and Attaching Slings The following procedure is one recommended process for removing a Liebert condenser from its ship- ping skid. Other methods may be used, provided that the methods are safe for personnel, the con- denser and equipment. 1. Place a sling through to rigging attachment points as shown in Step 1 in Figure 14. 2. Raise the condenser high enough that the skid can be safely removed. 3. Place protective material under the unit to protect it from scrapes and gouges. Lower the condenser onto the material. 4. Lower the condenser to an angle and distance that will allow attaching the legs to one side of the condenser. The number of legs varies according to the condenser model. 5. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by Liebert. Liebert recommends using a 5/8" socket and ratchet. 6. Turn the condenser so that the legs just installed support one side of the unit as shown in Step 3 in Figure 14. 7. Remove the sling and it attach it to the opposite side of the condenser as shown in Step 4 in Figure 15. 8. Raise the condenser to an angle to safely install legs on the opposite side of the condenser. 9. Lower the condenser so all legs support it. 10. Place slings on both sides of the condenser to lift and move it to the installation location.

Six-fan unit shown for illustration. Method for eight-fan condenser is the same.

Six-fan unit shown for illustration. Method for 8-fan condenser is the same.
The condenser must be installed so that it is level within 1/2" (13mm) to ensure proper refrigerant flow. For roof installation, mount the condenser on suitable curbs or other supports; follow all local and national codes. Secure the legs to the mounting surface using a field-supplied 1/2" (13mm) diame- ter bolt in each of the two 5/8" (16mm) holes in each leg. See Figures 3, 4 and 5 for anchor dimen- sions.
Step 4 · Step 5

Line voltage electrical service is required for all models. Refer to equipment nameplate regarding wire size and circuit protection requirements. Electrical service must conform to national and local electrical codes. Refer to Figures 19, 20 and 21 for electrical service entrances into unit. Refer to electrical schematic when making connections.
Each unit is shipped from the factory with all internal unit wiring completed.
! WARNING Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electrical power supplies before working within the electrical enclosure.
The line side of the disconnect remains energized when the disconnect is Off.
Use a voltmeter to verify that the electrical power is Off before performing any electrical and/or mechanical service and/or maintenance operations.
! WARNING Risk of high speed moving parts. Can cause injury or death.
The fan(s) blades can start to rotate unexpectedly when the power is On. Disconnect all local and remote electrical power supplies before working within the fan compartment.
Use a voltmeter to verify that the electrical power is Off before performing any electrical and/or mechanical service and/or maintenance operations.
Each unit is shipped from the factory with all internal unit wiring completed. Refer to the electrical schematic supplied with the condenser when making line voltage supply, low voltage indoor unit interlock and any low voltage alarm connections. All wiring must be done in accordance with all appli- cable local, state and national electrical codes.
! WARNING Risk electrical fire and short circuit. Can cause property damage, injury or death.
Select and install the electrical supply wire and overcurrent protection device(s) according to the specifications on the unit nameplate(s), per the instructions in this manual and according to the applicable national, state and local code requirements. Use copper conductors only. Make sure all electrical connections are tight. Unit-specific wiring diagrams are provided on each unit.
Condenser-rated voltage should be verified with available power supply before installation. Refer to the unit’s electrical schematic and serial tag for specific electrical requirements.
Line voltage electrical service is required for all condensers at the location of the condenser. The power supply does not necessarily have to be the same voltage supply as required by the indoor unit connected to the condenser. See the unit’s serial tag for specific condenser electrical requirements. A unit disconnect is standard on VFD and Quiet-Line Condensers and is optional on Fan Speed Control and standard Lee-Temp condensers. However, a site disconnect may be required per local code to iso- late the unit for maintenance. Route the supply power to the site disconnect switch and then to the unit. Route the conduit through the hole provided in the cabinet. Connect earth ground to lug pro- vided near terminal board.

Model # 83, 104 165, 205 251, 308 415, 510 616 830, 1010
# of Fans 1 2 3 4 6 8
Input Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
4.8 6.0 15 —
460 2.5 3.1 15 —
575 1.9 2.4 15 —
— — — 8.3 9.5 15 11.8 13.0 15 15.3 16.5 20 23.6 24.8 25 30.6 31.8 35
460 — — — 4.2 4.8 15 5.9 6.5 15 7.6 8.2 15 11.8 12.4 15 15.2 15.8 20
575 — — — 3.3 3.8 15 4.7 5.2 15 6.1 6.6 15 9.4 9.9 15 12.2 12.7 15
208/230 3 3.7 4.6 15 7.2 8.1 15 10.7 11.6 15 14.2 15.1 20 N/A
460 1.8 2.3 15 3.5 4.0 15 5.2 5.7 15 6.9 7.4 15 N/A
3.5 4.4 15 7.0 7.9 15 10.5 11.4 15 14.0 14.9 15 21.0 21.9 25 28.0 28.9 30
460 1.7 2.1 15 3.4 3.8 15 5.1 5.5 15 6.8 7.2 15 10.2 10.6 15 13.6 14.0 15
575 1.4 1.8 15 2.8 3.2 15 4.2 4.6 15 5.6 6.0 15 8.4 8.8 15 11.2 11.6 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

Model # ph 63 119, 127, 143 214 286 409 572
# of Fans 1 2 3 4 6 8
Input Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
1.8 2.3 15 3.6 4.1 15 5.4 5.9 15 7.2 7.7 15 10.8 11.3 15 14.4 14.9 15
460 0.9 1.1 15 1.8 2.0 15 2.7 2.9 15 3.6 3.8 15 5.4 5.6 15 7.2 7.4 15
575 0.7 0.9 15 1.4 1.6 15 2.1 2.3 15 2.8 3.0 15 4.2 4.4 15 5.6 5.8 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

83, 104 1 4.0 - 3.7 1.8 3.5 1.7 63 1.8 0.9
165, 205 2 — 3.7 7.2 3.5 7.0 3.4 119, 127, 143 3.6 1.8
251, 308 3 — 5.4 10.7 5.2 10.5 5.1 214 5.4 2.7
415, 510 4 — 7.1 14.2 6.9 14.0 6.8 286 7.2 3.6
616 6 — 10.8 — — 21.0 10.2 409 10.8 5.4
830, 1010 8 — 14.2 — — 28.0 13.6 572 14.4 7.2

Rated Voltage - Single Phase 120 200/208/230
Watts/Receiver 150 300 450 150 300 450
Full Load Amps 1.4 2.8 4.2 0.7 1.4 2.1
Wire Size Amps 1.8 3.5 5.3 0.9 1.8 2.7
Maximum Overcurrent Protection Device, Amps 15
NOTICE
Risk of control malfunction. Can cause improper unit operation. Make sure that all low voltage electrical wiring has been performed per the schematic diagram provided and that all low voltage wiring connections are tight.
A control interlock between the condenser and the indoor cooling units is required. Field-supplied cop- per wire (Class 1 for TCDV models and Class 2 for all other condenser models) is required for connec- tion between like-numbered terminals 70 & 71 on both units. Wiring must be sized so that the voltage drop in the circuit does not exceed 1 volt. See Figures 19, 20 and 21 and indoor unit manual for loca- tion of terminals on condensers and indoor units.
Condensers with monitoring terminals may be wired with Class 1 copper wire to the indoor cooling unit or other monitoring panel. Wiring must be sized so that the voltage drop in the circuit does not exceed 1 volt. Dry contacts close when a monitored event occurs. Consult condenser electrical sche- matic, supplied with the unit, for details.
Contact closure on VFD Drive monitoring terminals indicates a permanent VFD fault. A factory-pro- grammed VFD must be used as the replacement.
Contact closure on TVSS monitoring terminals may indicate unit trouble ranging from electrical sup- ply issues to TVSS replacement required. A properly trained and qualified electrician is required.
Electrical service is required for all models. Electrical service shall conform to national and local elec- trical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections. Refer to Figures 19, 20 and 21 for electrical service entrances into unit.
A manual electrical disconnect switch should be installed in accordance with local codes. Consult local codes for external disconnect requirements.
! WARNING Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Unit contains lethal voltage in some circuits. Use voltmeter to make sure power is turned Off before making any electrical connections.
Installation and service of this equipment should be done only by properly trained and qualified personnel who have been specially trained in the installation of air conditioning equipment. NOTICE
Use copper wiring only. Make sure that all conections are tight.

The installer/startup technician must determine the type of 3-phase supply power being used for the VFD Control Condenser: Wye-connected power or Delta- connected power.
Wye-connected power has two different voltages that can be measured: Phase-to-Phase voltage (this is equal to the nominal input voltage) and Phase-to-Neutral voltage (typically used for small single phase loads (120 VAC or 277 VAC). See Figure 16.
Delta-connected power only has one voltage level that can be measured: Phase-to-Phase. See Figure 17.
No control changes are required if the Liebert VFD Control Condenser will be operated with Wye-con- nected power.
B
A
3.7.3 Delta-Connected Power Supply
Figure 17 Delta-connected power diagram
C-A

Installer/startup technician needs to disconnect the EMC filter on the VFD to ensure proper operation if the Liebert VFD Control Condenser will be operated with Delta-connected power.
A
Internal EMC filter · Internal EMC filter

Electric service connection terminals when factory disconnect is NOT supplied.
Electric service connection and fuse block.
Factory wired to 24V Class 2 control circuit.
Electric service connection terminals when factory disconnect is supplied.
Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
Factory installed disconnect switch (optional).
Electric service entrance. A 7/8 in. (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box.
Factory-wired to components on electric panel.
Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire.
Electric service, not by Liebert. Single-phase for condenser models CSF, CDF with single fan motor. Three-phase for all other condenser models.
Earth ground connection (60Hz). Connection terminals for field supplied earth grounding wire when factory disconnect is NOT supplied.
Earth ground connection (60Hz). Connection terminal for field- supplied earth grounding wire when factory disconnect is supplied.
DPN000666 Rev. 0

Factory-installed fuse block on 60Hz units. Circuit breaker supplied in lieu of fuse block on 50Hz units.
Factory-wired to 24V control circuit.
Control interlock (70, 71) Field-supplied Class 1 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
Electric service connection terminals with factory- supplied disconnect.
Factory-installed disconnect switch.
Alarm Connections Field-supplied 24V Class 1 wiring to remote alarm circuits Variable Frequency Drive (VFD) alarm contact connections (13, 14) Transient Voltage Surge Suppressor (TVSS) alarm contact connections (11, 12).
Electric service entrance. A 7/8" (22.2mm) diameter hole in a 1-1/8 in (28.6mm) knockout provided in bottom of electric box.
Factory-wired to components on electric panel. Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is supplied. Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire.
Electric service, not by Liebert
DPN001051 Rev. 0 NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

Lee-Temp receiver tank (1 per circuit). NOTE: Standard heater pads are 150 watts each. (Optional 300 watt heater pads are available.) Standard heater pad voltage is 230V. (120V heater pad voltage is optional.)
Electrical connection box with cover.
Electrical service connection. Pigtails in electric handy box are factory wired to Lee- Temp heater pads for field connection of separate continuous electric source, wiring not by Liebert.
Electric service connection and fuse block.
Electric service connection terminals when factory disconnect is NOT supplied.
Factory wired to 24V Class 2 control circuit.
Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
Electric service connection terminals when factory disconnect is supplied.
Factory-installed disconnect switch (optional).
Factory-wired to components on electric panel.
Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high-voltage component for field-supplied earth grounding wire.
Electric service entrance. A 7/8 in (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box.
Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is NOT supplied.
Electric service. Three-phase for all models. Wiring not by Liebert.
Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is supplied.
DPN000683 Rev. 0

! WARNING Risk of explosive discharge from high-pressure refrigerant. Can cause equipment damage, injury or death. Relieve pressure before working with piping. ! WARNING Risk of refrigerant system rupture or explosion from overpressurization. Can cause equipment damage, injury or death. If a pressure relief device is not provided with the condenser unit, the system installer must provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and the field installed relief valve. One or more additional pressure relief valves are required downstream of any and all field installed isolation valves as shown in Figures 2 and 24. Do not isolate any refrigerant circuits from overpressurization protection.
NOTE POE (polyol ester) oil, required with R407C and used with some R22 systems, is much more hygroscopic than mineral oils. This means that POE oil absorbs water at a much faster rate when exposed to air than previously used mineral oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
Indoor units and condensers both ship with nitrogen holding charges. Do not vent the condenser until all refrigerant piping is in place, ready for connection to indoor unit and condenser.
NOTE Failure to use compressor oils recommended by compressor manufacturer will void compressor warranty. Consult Liebert or compressor manufacturer for further recommendations or if you have questions about compressor oils. Refer to ASHRAE Refrigeration Handbook for general good practices for refrigeration piping. A pressure relief valve is provided with Liebert Lee-Temp condensers. A fusible plug is provided on Liebert Fan Speed Control and VFD condensers. The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side refrigerant circuit.

One discharge line and one liquid line must be field-installed for each circuit of the indoor unit and the outdoor condenser(s). Dual circuit condensers are available for most dual circuit indoor unit appli- cations. Refer to Figures 22, 23 and 24 below for additional field-installed piping needed at the con- denser. This piping is needed for proper system performance and for installation/interconnecting receivers and head pressure control valves for Lee-Temp systems.
When all the field interconnecting piping is in place, vent the condenser’s dry nitrogen charge and connect to the field piping. Finally, vent the evaporator unit’s dry nitrogen charge and make its piping connections last.
Follow all proper brazing practices, including a dry nitrogen purge to maintain system cleanliness.

Traps to Extend Above Base of Coil by a Minimum of 7-1/2" (190mm)
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators ( field-supplied). Support field piping separately to avoid coil damage and loss of charge.

Hot Gas Line
Inverted Traps (field-supplied) to extend 8" (203mm) above coil base
Liquid Line
Entering Hot Gas Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately to avoid coil damage and loss of charge.
Position elbow to direct relief valve downward
See Detail A-A
DPN000669 Rev. 2
Metal Clamp · Isolator · Detail A-A

Condenser Coil
Inverted Trap * on discharge line to extend 7-1/2" (190mm) above coil base
Rotalock Valve **
Check Valve Head Pressure Control with Integral Check Valve
1/4" (6.4mm) Pressure Relief Valve**
Lee-temp
Receiver
Sight Glass
* Traps every 25 ft (7.6m) of rise on hot gas line only
Liquid Return from Condenser
Solenoid Valves
Shutoff * (Isolation) Valve
Sensing Bulb
Sight Glass
Filter Dryer
External Equalizers Liquid Return
Service Valves Check Valve
Hot Gas Bypass (optional)
Compressor***
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance. ** Components supplied by Liebert and must be field-installed. *** Various compressor types may be available.
Single Circuit Shown
Factory Piping
Optional Piping
DPN000681 Rev. 0
Field Piping

Procedures for leak check and evacuation of the entire refrigeration system are contained in the installation manual of the indoor unit. Use the proper manual section corresponding to the winter control system used on the condenser (VFD/Fan Speed Control or Lee-Temp Control) and the refriger- ant to be charged into the system.

Checklist for Completed Installation
___ 1. Unpack and check received material
___ 2. Proper clearance for service access has been maintained around the equipment
___ 3. Equipment is level and mounting fasteners are tight
___ 1. Line voltage connected and matches equipment nameplate
___ 2. Power line circuit breakers or fuses have proper ratings for equipment installed
___ 3. Control wiring connections completed between indoor cooling unit and condenser
___ 4. All internal and external high and low voltage wiring connections are tight
___ 5. TCDV condensers only—Check for Delta-Connected Power Supply and make any needed adjustments per 3.7.1 - VFD Control Condensers (TCDV) only
___ 6. Monitoring wiring connections completed, when equipped, to indoor cooling unit or external monitoring panel
___ 7. Confirm that unit is properly grounded to an earth ground
___ 8. Control transformer setting matches incoming power
___ 9. Electrical service conforms to national and local codes
___ 10. Check fans for proper phase rotation. Blades should rotate clockwise when viewing the unit
from the fan guard side.
___ 1. Piping is completed to corresponding indoor cooling unit refrigeration circuit.
___ 2. Piping leak-checked, evacuated and charged.
___ 3. Piping is properly sized, sloped and trapped for proper oil return.
___ 4. Piping is routed to reduce potential of rub-through or chaffing.
___ 1. Fans rotate freely and in proper direction
___ 2. Adjust ambient thermostat setpoints to match setpoints on the electrical schematic supplied with the condenser.
___ 3. Foreign material removed from in and around all equipment installed (construction materials, construction debris, etc.).
___ 4. Installation materials and tools have been removed from in and around all equipment (literature, shipping materials, tools, etc.).
___ 5. Blank start-up sheet located, ready for completion by installer or start-up technician.

! WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within. Unit contains potentially lethal electrical voltage.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning operations.
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.
Refer to 4.0 - Checklist for Completed Installation and verify that all installation items have been completed before beginning to start the condenser.
Operation

! WARNING Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Use voltmeter to make sure power is turned Off before making any electrical connections.
Unit contains lethal voltage in some circuits.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning operations. The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.
Periodic attention is necessary for continued satisfactory operation of your unit. Restricted air flow through the condenser coil, reduced airflow from non-functioning fans and low refrigerant system charge levels will reduce the operating efficiency of the unit and can result in high condensing tem- peratures and loss of cooling. In winter, do not permit snow to accumulate around the sides or under- neath the condenser coil.
Monthly and semi-annual inspections and maintenance are recommended for proper system opera- tion. Use copies of 6.2.2 - Maintenance Inspection Checklist for each of these inspections.
If performance or operation problems are detected at anytime, refer to Table 9 - Troubleshooting for required action.
System Maintenance

Keeping the outdoor condenser coils clean is an important factor in maintaining peak efficiency, reli- ability and long life of the equipment. It is much easier to keep up on frequent cleanings rather than wait until heavy build up has occurred which may create head pressure problems with the evaporator units.
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard monthly preventive maintenance schedule, a visual inspection of the coil is recommended to monitor conditions.
The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy build up on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins could result. If a cleaner is required, we recommend a non-acidic type cleaner be used. Acid-type cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow the use of acidic cleaners for environmental reasons.
The absolute best way to clean coils is from the inside out. This requires disconnecting the power sup- ply from the condenser before working on the unit. The fan guards and fan blades must be removed to gain access to the coil surface. The sprayer can then be worked across the coil using the water/clean- ing solution, pushing the dirt and debris out the bottom of the coil. Although this does extend the time involved, the results are well worth it. This method should be used at least once a year. Spraying the coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins and con- tinue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for an extended time. A pre-scheduled shutdown with the operator may be in order. If you are using a cleaner along with the spraying process, follow recommended manufacturer instructions and be sure to rinse the coil thoroughly. Any residue left on the coil can act as a magnet to dirt.
Reinstall and secure the fan blades and fan guards after the cleaning is finished. Last, reconnect the power supply to the condenser.
System Maintenance

Date: Prepared By:
Model #: Serial Number:
Condenser
___ 1. Coil surfaces free of debris
___ 1. Complete all monthly items
___ 2. Fans free of debris
___ 2. Piping in good condition
___ 3. Fan motors securely mounted
___ 3. Inspect refrigerant lines for signs of oil leaks. Repair leaks as found.
___ 4. Motor bearings in good condition
___ 4. Check refrigerant charge level in each receiver tank (if equipped), based on procedures in the indoor unit’s manual. Continuous system operation required.
___ 5. Check all refrigerant lines and capillaries for vibration isolation. Support as necessary.
___ 5. Wash coil as needed
___ 6. No refrigerant leaks.
___ 6. Repair bent or damaged fins.
Condenser Electric Panel
___ 1. On TCDV models, check TVSS protection status indicator light.
___ 1. Check all electrical connections
___ 2. Check contactors for pitting
___ 3. Operational sequence/setpoints
___ 1. Motor #1 amp draw amps
___ 2. Motor #2 amp draw amps
___ 3. Motor #3 amp draw amps
___ 4. Motor #4 amp draw amps
___ 5. Motor #5 amp draw amps
___ 6. Motor #6 amp draw amps
___ 7. Motor #7 amp draw amps
___ 8. Motor #8 amp draw amps
Make photocopies of this form for your records
System Maintenance

Symptom Possible Cause Check or Remedy
No power to condenser Check voltage at input terminal block
Circuit breaker for low voltage transformer in condenser is tripped
Locate problem in condenser electrical panel and repair
Condenser will not start
No low voltage signal to/from indoor unit Locate open circuit and repair
Insufficient refrigerant in system Check for leaks, repair, and add refrigerant
Low indoor unit suction pressure
Fan-cycling ambient thermostats setpoints too low
Check schematic for recommended setpoints and adjust.
Low discharge pressure Faulty head pressure control valve or condenser FSC/VFD control Replace if defective
Dirty condenser fins Clean coil
Check for low voltage signal from indoor unit
Check fan motors and fuses
Condenser fans not operating
Check for correct ambient thermostat setpoints, as applicable.
High refrigerant charge Check refrigerant charge
VFD Condenser trips out on overvoltage (OU displayed on VFD controller)
Supply voltage is Delta configuration or is ungrounded/high impedance
Shut off AC voltage, locate the VFD, pull out the EMC tab and reconnect power
No voltage or improper phasing exists at condenser Check voltage at input terminal block
TVSS indicator lights are extinguished or red LED is illuminated and monitoring terminals 11/12 are closed
Electrical connections to TVSS are faulty Locate connection problem and repair
Replace TVSS and inspect other components for damage and replace them if necessary
A surge exceeding the rating of the TVSS has occurred
System Maintenance · High discharge pressure

System Maintenance

System Maintenance



Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@emersonnetworkpower.com
800-222-5877 upstech@emersonnetworkpower.com
800-543-2378 powertech@emersonnetworkpower.com
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250
EmersonNetworkPower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity.
Embedded Computing Embedded Power Power Switching & Controls
Services Racks & Integrated Cabinets Outside Plant
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Condenser will not start | No power to condenser | Check voltage at input terminal block | p.40 |
| Condenser will not start | Circuit breaker for low voltage transformer in condenser is tripped | Locate problem in condenser electrical panel and repair | p.40 |
| Condenser will not start | No low voltage signal to/from indoor unit | Locate open circuit and repair | p.40 |
| Low indoor unit suction pressure | Insufficient refrigerant in system | Check for leaks, repair, and add refrigerant | p.40 |
| Low indoor unit suction pressure | Fan-cycling ambient thermostats setpoints too low | Check schematic for recommended setpoints and adjust. | p.40 |
| Low discharge pressure | Faulty head pressure control valve or condenser FSC/VFD control | Replace if defective | p.40 |
| High discharge pressure | Dirty condenser fins | Clean coil | p.40 |
| High discharge pressure | Condenser fans not operating | Check for low voltage signal from indoor unit | p.40 |
| High discharge pressure | Check fan motors and fuses | p.40 | |
| High discharge pressure | Check for correct ambient thermostat setpoints, as applicable. | p.40 | |
| High discharge pressure | High refrigerant charge | Check refrigerant charge | p.40 |
| VFD Condenser trips out on overvoltage (OU displayed on VFD controller) | Supply voltage is Delta configuration or is ungrounded/high impedance | Shut off AC voltage, locate the VFD, pull out the EMC tab and reconnect power | p.40 |
| TVSS indicator lights are extinguished or red LED is illuminated and monitoring terminals 11/12 are closed | No voltage or improper phasing exists at condenser | Check voltage at input terminal block | p.40 |
| TVSS indicator lights are extinguished or red LED is illuminated and monitoring terminals 11/12 are closed | Electrical connections to TVSS are faulty | Locate connection problem and repair | p.40 |
| TVSS indicator lights are extinguished or red LED is illuminated and monitoring terminals 11/12 are closed | A surge exceeding the rating of the TVSS has occurred | Replace TVSS and inspect other components for damage and replace them if necessary | p.40 |