INSTALLATION INSTRUCTIONS ML180UHEp.1THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCEp.1AIR FLOWp.1UPFLOWp.1HORIZONTAL RIGHT HORIZONTAL LEFTp.1506810−01 p.1Unit Dimensions − inches (mm)p.2FLUE OUTLETp.2TOP VIEWp.2FRONT VIEW SIDE VIEWp.2ML180UHE Gas Furnacep.4CAUTIONp.4Shipping and Packing Listp.4Safety Informationp.4DANGERp.4WARNINGp.4Use of Furnace as Construction Heaterp.5Generalp.5Combustion, Dilution & Ventilation Airp.6FURNACEp.10FRONTp.10IF BASE IS USED WITHOUT IAQ CABINET,p.10INDOOR AIRp.10A SINGLE RETURN AIRp.10PLENUMp.10MUST COVER BOTHp.10UNIT ANDp.10RETURN AIR BASE OPENINGSp.10SIDE RETURN AIR OPENINGSp.10OPTIONAL RETURNp.10AIR BASEp.10SIDE VIEWp.10TABLE 1p.12Filtersp.12Ventingp.13HORIZONTAL LEFT POSITIONp.14AIRp.14FLOWp.14TABLE 2p.17Gas Pipingp.23Electricalp.25ELECTROSTATIC DISCHARGE (ESD)p.25*CONDENSING UNIT p.26POWERp.26HEATp.26W1p.26CONDENSINGp.26COOLINGp.26UNIT p.26INDOOR BLOWERp.26CONDENSING UNIT COMMONp.26COMMONp.26*NOTE − R" REQUIRED ON SOME OUTDOOR UNITSp.26ML180UHE Schematic Wiring Diagram and Sequence of Operationp.27TABLE 10p.28Unit Start−Upp.29FOR YOUR SAFETY READ BEFORE LIGHTINGp.29Proper Combustionp.30Gas Pressure Adjustmentp.30TABLE 11 GAS METER CLOCKING CHARTp.30TABLE 12p.30Other Unit Adjustmentsp.31BLOWER DATAp.33Servicep.35ELECTRICAL SHOCK, FIRE,p.35Planned Servicep.37Repair Parts Listp.37Integrated Control Diagnostic Codesp.38HEATING SEQUENCE OF OPERATIONp.39NORMAL HEATING MODE ABNORMAL HEATING MODEp.39POWER ONp.39NOp.39CONTROL SELF−CHECK OKAY?p.39YESp.39IS POLARITY CORRECT?p.39IS THERE A PROPER GROUND?p.39IS VOLTAGE ABOVE 70 VOLTS?p.39ROLLOUT SWITCH CLOSED?p.39AND POWER IS RESET OR T’STAT IS INTERRUPTEDp.39LED FLASHES CODE 12 − FLAME SENSEDp.39
Page 1 of the Lenox Merit Series Furnace (ML180UHE) user manual — 506810−01
Page 1 · click to enlarge
Page 1

INSTALLATION INSTRUCTIONS ML180UHE

2011 Lennox Industries Inc.

Lenox Merit Series Furnace (ML180UHE) — INSTALLATION INSTRUCTIONS ML180UHE diagram (page 1)
Fig. 1

MERIT® SERIES GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE

506810−01 06/2011 Supersedes 506732−01

Litho U.S.A.

THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE

This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

Lenox Merit Series Furnace (ML180UHE) — THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE diagram (page 1)
Fig. 2

Improper installation, adjustment, alteration, service or maintenance can cause property damage, person- al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.

AIR FLOW

UPFLOW

Lenox Merit Series Furnace (ML180UHE) — AIR FLOW diagram (page 1)
Fig. 3

AIR FLOW

AIR FLOW

As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.

HORIZONTAL RIGHT HORIZONTAL LEFT

Table of Contents Unit Dimensions 2 Parts Arrangement 3 ML180UHE Gas Furnace 4 Shipping and Packing List 4 Safety Information 4 Use of Furnace as a Construction Heater 5 General 5 Combustion, Dilution & Ventilation Air 6 Setting Equipment 9 Filters 12 Duct System 12 Venting 13

Gas Piping 23 Electrical 25 Integrated Control 28 Unit Start−Up 29 Gas Pressure Adjustment 30 High Altitude 30 Proper Combustion 30 Other Unit Adjustments 31 Blower Performance Data 33 Service 35 Planned Service 37 Repair Parts List 37 Integrated Control Diagnostic Codes 38 Troubleshooting 39

506810−01

Dallas, Texas, USA

Page 2 of the Lenox Merit Series Furnace (ML180UHE) user manual — FRONT VIEW SIDE VIEW
Page 2 · click to enlarge
Page 2

Unit Dimensions − inches (mm)

Lenox Merit Series Furnace (ML180UHE) — Unit Dimensions − inches (mm) diagram (page 2)
Fig. 4 · Unit Dimensions − inches (mm)

1NOTE − 60C and 60D units that require air volumes over 1800 cfm (850 L/s) must have one of the following: 1. Single side return air with transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.) 2. Single side return with optional return air base. 3. Bottom return air. 4. Return air from both sides. 5. Bottom and one side return air. See Blower Performance Tables for additional information.

Lenox Merit Series Furnace (ML180UHE) — Unit Dimensions − inches (mm) diagram (page 2)
Fig. 5 · Unit Dimensions − inches (mm)

FLUE OUTLET

2Flue outlet may be horizontal but furnace must be vented vertically 3Optional external side return air filter kit cannot be used with the optional RAB Return Air Base.

TOP VIEW

/4(19) nt Panel 76) Right 4 (171) Lef27−3/4 (705) 3−1/4 (83) 19−7/16 t (494) 232) Right (219) Left2FLUE OUTLET (Either Side) ELECTRICAL INLET (Either Side) GAS PIPING INLET (Either Side) 23 (584) 1Side Return 14 Air Opening (356) (Either Side) 1−15/16 (49) 23−1/2 (597) 37) Right (40) Left CAL ther Side) er Side) 3−1/4 (83)
Lenox Merit Series Furnace (ML180UHE) — TOP VIEW diagram (page 2)
Fig. 6
4 9)A B9/16 (14) 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT (Either Side) 33 (83 14−3/4 (375) 16 (406) C5/8 3/4 (16) (19) 9)
Lenox Merit Series Furnace (ML180UHE) — TOP VIEW diagram (page 2)
Fig. 7

1Bottom Return Air Opening

FRONT VIEW SIDE VIEW

Lenox Merit Series Furnace (ML180UHE) — FRONT VIEW SIDE VIEW diagram (page 2)
Fig. 8
ML180UHE Model No.ABCD in.mmin.mmin.mmin.mm 045(X)E36A14−1/236813−3/8340133304−3/4121 070(X)E36B 090(X)E48B17−1/244616−3/8416164066−1/4159 090E60C 110(X)E60C2153319−7/850419−1/24958203 135E60D24−1/262223−3/8546235849−3/4248

(Top) · (Either Side) · 1−1/2 (38)

Page 3 of the Lenox Merit Series Furnace (ML180UHE) user manual — Unit Dimensions − inches (mm)
Page 3 · click to enlarge
Page 3
Lenox Merit Series Furnace (ML180UHE) — Unit Dimensions − inches (mm) diagram (page 3)
Fig. 9 · Unit Dimensions − inches (mm)

Control Box (includes integrated control, interlock switch and transformer)

Page 4 of the Lenox Merit Series Furnace (ML180UHE) user manual — WARNING
Page 4 · click to enlarge
Page 4

ML180UHE Gas Furnace

CAUTION

The ML180UHE unit is shipped ready for installation in the upflow or horizontal right position (for horizontal left posi- tion the combustion air pressure switch must be moved) fueled by natural gas. A conversion kit (ordered separate- ly) is required for use in LP/Propane gas applications. The furnace is shipped with the bottom panel in place. The bot- tom panel must be removed if the unit is to be installed in a horizontal application. The panel may also be removed in upflow applications.

As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.

Certifications ML180UHE units are CSA International certified to ANSI Z21.47. In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address:

Shipping and Packing List

Package 1 of 1 contains 1 −Assembled ML180UHE unit 1 −Bag assembly containing the following: 2 −Screws 1 −Snap bushing 1 −Snap plug 1 − Wire tie 1 −Vent warning label 1 −Owner’s manual and warranty card

American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036 Clearances Adequate clearance must be made around the air open- ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code. Vent installations must be consistent with the National Fuel Gas Code venting tables (in this instruction) and applicable provisions of local building codes. This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 8 and 12. Accessibility and service clearances must take precedence over fire protection clearances. NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring. Installed Locations For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz- ardous atmosphere, the furnace must be installed accord- ing to recommended good practice requirements and cur- rent National Fuel Gas Code. Temperature Rise NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation and may result in premature heat exchanger failure. This ML180UHE furnace must be installed so that its elec- trical components are protected from water.

The following items may be ordered separately: 1 −Thermostat 1 −Suspension kit (for horizontal installations) 1 −LP/Propane changeover kit 1 −Return air base 1 − High altitude kit 1 −Side filter kit

Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.

Safety Information

DANGER

There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, person- al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.

Page 5 of the Lenox Merit Series Furnace (ML180UHE) user manual — General
Page 5 · click to enlarge
Page 5

Installed in Combination with a Cooling Coil

This furnace design has not been CSA International certified for installation in mobile homes, recreational vehicles, or outdoors.

When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. See figure 2. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately pre- vent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. See figure 2.

Use of Furnace as Construction Heater

Lennox does not recommend the use of ML180UHE units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op- eration of the unit with clogged or misplaced filters will dam- age the unit.

ML180UHE units may be used for heating of buildings or structures under construction, if the following conditions are met:

Heating Unit Installed Parallel to Cooling Coil

The vent system must be permanently installed per

Dampers (open during heating operation only)

these installation instructions.

A room thermostat must control the furnace. The use of

fixed jumpers that will provide continuous heating is not allowed.

The return air duct must be provided and sealed to the

furnace.

Return air temperature range between 60°F (16°C) and

80°F (27°C) must be maintained.

Dampers (open during cooling operation only)

Air filters must be installed in the system and must be

maintained during construction.

Air filters must be replaced upon construction comple-

tion.

Heating Unit Installed Upstream of Cooling Coil

The input rate and temperature rise must be set per the

furnace rating plate.

One hundred percent (100%) outdoor air must be pro-

vided for combustion air requirements during construc- tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.

When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec- tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad- dress:

The furnace heat exchanger, components, duct system,

air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.

All furnace operating conditions (including ignition, in-

put rate, temperature rise and venting) must be verified according to these installation instructions.

National Fire Protection Association 1 Battery March Park Quincy, MA 02269

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.

In addition to the requirements outlined previously, the fol- lowing general recommendations must be considered when installing a ML180UHE furnace:

The ML180UHE furnace may be installed in alcoves, clos- ets, attics, basements, garages, crawl spaces and utility rooms in the upflow or horizontal position.

Place the furnace as close to the center of the air dis-

tribution system as possible. The furnace should also be located close to the chimney or vent termination point.

Show 4 more labels / short text on this page
Gas Unit · Cooling Coil · Gas Unit · Cooling Coil
Page 6 of the Lenox Merit Series Furnace (ML180UHE) user manual — Combustion, Dilution & Ventilation Air
Page 6 · click to enlarge
Page 6

Do not install the furnace where drafts might blow direct-

information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted ma- terial is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.

ly into it. This could cause improper combustion and un- safe operation.

Do not block the furnace combustion air openings with

clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.

When the furnace is installed in an attic or other insu-

CAUTION

lated space, keep insulation away from the furnace. NOTE − The Commonwealth of Massachusetts stipu- lates these additional requirements:

Do not install the furnace in a corrosive or contami- nated atmosphere. Meet all combustion and ventila- tion air requirements, as well as all local codes.

Gas furnaces shall be installed by a licensed plumb-

er or fitter only.

The gas cock must be T handle" type.

CAUTION

When a furnace is installed in an attic, the passage-

way to and service area surrounding the equipment shall be floored.

Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust- ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combus- tion air supply:

WARNING

Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal- ifornia to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.

Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials

Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900

All gas-fired appliances require air for the combustion pro- cess. If sufficient combustion air is not available, the fur- nace or other appliances will operate inefficiently and un- safely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex- haust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufficient out- door air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combus- tion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the liv- ing space creating a potentially dangerous situation. In the absence of local codes concerning air for combus- tion and ventilation, use the guidelines and procedures in this section to install ML180UHE furnaces to ensure effi- cient and safe operation. You must consider combustion air needs and requirements for exhaust vents. A portion of this

In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contami- nants may include bleaches, adhesives, detergents, sol- vents and other contaminants which can corrode furnace components.

The requirements for providing air for combustion and ven- tilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Page 7 of the Lenox Merit Series Furnace (ML180UHE) user manual — Combustion, Dilution & Ventilation Air
Page 7 · click to enlarge
Page 7

Unconfined Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com- bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un- confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section. Confined Space A confined space is an area with a volume less than 50 cu- bic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms. When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain- ing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.

Air from Outside If air from outside is brought in for combustion and ventila- tion, the confined space must have two permanent open- ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate di- rectly or by ducts with the outdoors or spaces (crawl or at- tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the en- closure. See figures 4 and 5. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 6.

When ducts are used, they shall be of the same cross−sec- tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cov- ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per- cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 7)
Fig. 10 · Combustion, Dilution & Ventilation Air
Page 8 of the Lenox Merit Series Furnace (ML180UHE) user manual — Combustion, Dilution & Ventilation Air
Page 8 · click to enlarge
Page 8
Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 8)
Fig. 11 · Combustion, Dilution & Ventilation Air

ALL AIR FROM OUTSIDE (Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)

Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 8)
Fig. 12 · Combustion, Dilution & Ventilation Air
Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 8)
Fig. 13 · Combustion, Dilution & Ventilation Air

ALL AIR FROM OUTSIDE (All Air Through Ventilated Attic)

NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi- cate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.

Page 9 of the Lenox Merit Series Furnace (ML180UHE) user manual — Combustion, Dilution & Ventilation Air
Page 9 · click to enlarge
Page 9
Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 9)
Fig. 14 · Combustion, Dilution & Ventilation Air

Upflow Applications Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al- cove installations are shown in figure 8.

Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur- nace. Doing so will adversely affect the operation of the safety control devices, which could result in per- sonal injury or death. The ML180UHE gas furnace can be installed as shipped in either the upflow position or the horizontal position. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level. NOTE − Units with 1/2 or 3/4 hp blower motors are equipped with three flexible legs and one rigid leg. See figure 7. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be removed before the furnace is placed into op- eration. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.

Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 9)
Fig. 15 · Combustion, Dilution & Ventilation Air
Upflow Application Installation Clearances Top Left Side Right Side Bottom Type of Vent ConnectorType CType B1 Top1 in. (25 mm)1 in. (25 mm) *Front2−1/4 in. (57 mm)**2−1/4 in. (57 mm) Back00 Sides0†0 Vent6 in. (152 mm)1 in. (25 mm) Floor0‡0‡ *Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4−1/2" if single wall vent pipe is used. ‡For installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring. †Left side requires 3 inches if a single wall vent is used on 14−1/2 inch cabinets, or 2 inches if a single wall vent pipe is used on 17−1/2 inch cabinets.
Lenox Merit Series Furnace (ML180UHE) — Combustion, Dilution & Ventilation Air diagram (page 9)
Fig. 16 · Combustion, Dilution & Ventilation Air
Page 10 of the Lenox Merit Series Furnace (ML180UHE) user manual — AIR BASE
Page 10 · click to enlarge
Page 10

Return Air −− Upflow Applications

Lenox Merit Series Furnace (ML180UHE) — FURNACE diagram (page 10)
Fig. 17

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

20” X 25” X 1” (508mm X 635mm X 25mm)

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

1 −Single side return air with transition to accommodate 20

x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Re- quired to maintain proper air velocity.) See figure 9.

2 −Single side return air with optional return airbase. See fig-

ure 10.

3 −Bottom return air.

4 −Return air from both sides.

5 −Bottom and one side return air.

Refer to Engineering Handbook for additional information.

Optional Return Air Base (Upflow Applications Only −− For use with A, B, C and D cabinets)

FURNACE

FRONT

IF BASE IS USED WITHOUT IAQ CABINET,

1 23 (584) Overall (Maximum)

1 Minimum 11 (279) 2 Maximum 14 (356)

INDOOR AIR

QUALITY CABINET (PCO, Filter Cabinet, etc.)

A SINGLE RETURN AIR

1 22−7/16 (570) Overall (Maximum)

1 Unit side return air Opening

PLENUM

AIR FLOW

MUST COVER BOTH

UNIT AND

RETURN AIR BASE OPENINGS

SIDE RETURN AIR OPENINGS

OPTIONAL RETURN

14−1/2 (368) A Width (65W75) 17−1/2 (446) B Width (50W98) 21 (533) C Width (50W99) 24−1/2 (622) D Width (51W00)

AIR BASE

SIDE VIEW

NOTE− Optional Side Return Air Filter Kits are not for use with Optional Return Air Base. 1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet. 2 To minimize pressure drop, the largest opening height possible (up to 14 inches 356 mm) is preferred.

Show 7 more labels / short text on this page
3−1/4 (83) · 7−1/4 (184) · 5−5/8 (143) · (Either Side) · 23 3/4 (19) · (584) · (683) 26−7/8
Page 11 of the Lenox Merit Series Furnace (ML180UHE) user manual — FURNACE
Page 11 · click to enlarge
Page 11

Removing the Bottom Panel Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 11.

The ML180UHE furnace can be installed in horizontal ap- plications. Order horizontal suspension kit (51W10) from Lennox, or use equivalent suspension method. Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al- cove installations are shown in figure 12. This furnace may be installed in either an attic or a crawl- space. Either suspend the furnace from roof rafters or floor joists, as shown in figure 13, or install the furnace on a platform, as shown in figure 14.

Lenox Merit Series Furnace (ML180UHE) — FURNACE diagram (page 11)
Fig. 18
Lenox Merit Series Furnace (ML180UHE) — FURNACE diagram (page 11)
Fig. 19

Typical Horizontal Application Unit Suspended in Attic or Crawlspace

Lenox Merit Series Furnace (ML180UHE) — FURNACE diagram (page 11)
Fig. 20
Horizontal Application Installation Clearances Top FLOW Left Right AIR End End Bottom Vent Connector TypeType CType B1 Top00 *Front2−1/4 in. (57 mm)**2−1/4 in. (57 mm) Back00 Ends2 in. (51 mm)2 in. (51 mm) Vent6 in. (152 mm)1 in. (25 mm) Floor0‡0‡ *Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4−1/2 in. if single wall vent pipe is used. ‡For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

NOTE − Heavy−gauge perforated sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust pip- ing installation. Cooling coils and supply and return air plenums must be supported separately. NOTE − When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain.

Return Air −− Horizontal Applications

Return air must be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 11.

Horizontal Applications

Page 12 of the Lenox Merit Series Furnace (ML180UHE) user manual — Filters
Page 12 · click to enlarge
Page 12
Lenox Merit Series Furnace (ML180UHE) — TABLE 1 diagram (page 12)
Fig. 21

TABLE 1

Lenox Merit Series Furnace (ML180UHE) — TABLE 1 diagram (page 12)
Fig. 22
Furnace Cabinet WidthFilter Size Side ReturnBottom Return A − 14−1/2"16 X 25 X 1 (1)14 X 25 X 1 (1) B − 17−1/2"16 X 25 X 1 (1)16 X 25 X 1 (1) C − 21"16 X 25 X 1 (1)20 X 25 X 1 (1) D − 24−1/2"16 X 25 X 1 (2)24 X 25 X 1 (1)

Use industry-approved standards (such as those pub- lished by Air Conditioning Contractors of America or Ameri- can Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution. NOTE − Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.5 inches w.c. Higher external static pressures may cause erratic lim- it operation. Supply Air Plenum

WARNING

If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operat- ing and it must not allow leaks into the supply air duct sys- tem.

Improper installation of the furnace can result in per- sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace. In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple- num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al- low absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper- ty damage could result.

Return Air Plenum NOTE − Return air must not be drawn from a room- where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide producing de- vice (i.e., wood fireplace) is installed.

When return air is drawn from a room, a negative pres- sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com- bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju- ry or death.

In upflow applications, the return air can be brought in through the bottom or either side of the furnace. If a fur- nace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equiva- lent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.

Filters

This unit is not equipped with a filter or rack. A field−pro- vided high−velocity filter is required for the unit to operate properly. Table 1 lists recommended filter sizes. A filter must be in place any time the unit is operating.

Page 13 of the Lenox Merit Series Furnace (ML180UHE) user manual — Venting
Page 13 · click to enlarge
Page 13

Venting

1 −Remove the four mounting screws (figure 15) which

secure the combustion air inducer / pressure switch assembly to the orifice plate. Lift the assembly and ro- tate it 90 degrees clockwise or counterclockwise to ei- ther the 3 o’clock position or to 9 o’clock position. Re− secure with four screws. Gasket should be left in place. 2 −Use tin snips to cut preferred opening on the cabinet

A 4−inch diameter flue transition is factory-installed on the combustion air inducer outlet of all models. Figure 16 shows the combustion air inducer as shipped from the factory.

Lenox Merit Series Furnace (ML180UHE) — Venting diagram (page 13)
Fig. 23 · Venting

for repositioning the flue outlet. Use the cut−out piece as a cover plate to patch unused opening on cabinet.

Lenox Merit Series Furnace (ML180UHE) — Venting diagram (page 13)
Fig. 24 · Venting

Gas supply piping must be brought into the unit from the right

side in order to accommodate the flue pipe. Cut Combustion air inducer tubing from 9" to 8" to avoid inter-

ference with inducer motor Remove make−up box assembly (2 screws) and cut wire tie to

free make−up box wires. Re−install make−up box on other side of cabinet. Re−secure make−up box wires: Either pull excess wires

through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.

Lenox Merit Series Furnace (ML180UHE) — Venting diagram (page 13)
Fig. 25 · Venting
Lenox Merit Series Furnace (ML180UHE) — Venting diagram (page 13)
Fig. 26 · Venting

The unit will not vent properly with the flue transition pointed down in the 6 o’clock position. The combustion air inducer may be rotated clock- wise or counterclockwise by 90° to allow for top or side vent discharge in all applications. When the unit is installed, the flue transition must be in the 9 o’clock, 12 o’clock or 3 o’clock position.

Cut combustion air inducer tubing from 9" to 5" to avoid

If necessary, reposition the combustion air inducer, pres- sure switch and/or make−up box as needed per the follow- ing steps. See figures 17 through 21.

Page 14 of the Lenox Merit Series Furnace (ML180UHE) user manual — AIR
Page 14 · click to enlarge
Page 14
Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 14)
Fig. 27

HORIZONTAL LEFT POSITION

AIR

FLOW

Make−Up Box Collector Box

Disconnect pressure switch hose from barbed fitting on the

Gas supply piping must be brought into the unit from the bot-

pressure switch assembly. Remove pressure switch assembly (1 screw) and cut wire tie to free pressure switch wires. Re− install pressure switch on the other side of orifice plate and re− connect pressure switch hose. Re−secure pressure switch wires: Either pull excess wires

tom in order to accommodate the flue pipe. Cut combustion air inducer tubing from 9" to 8" to avoid inter-

Remove make−up box assembly (2 screws) and cut wire tie to

through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.

free make−up box wires. Re−install make−up box on other side of cabinet. Re−secure make−up box wires: Either pull excess wires through

the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.

HORIZONTAL LEFT POSITION

Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 14)
Fig. 28

HORIZONTAL RIGHT POSITION Side Vent Discharge − no modifications necessary

AIR

FLOW

Make−Up Box Collector Box

Cut combustion air inducer tubing from 9" to 7" to avoid inter-

ference with inducer motor

Disconnect pressure switch hose from barbed fitting on the

pressure switch assembly. Remove pressure switch assembly (1 screw) and cut wire tie to free pressure switch wires. Re− install pressure switch on the other side of orifice plate and re− connect pressure switch hose. Re−secure pressure switch wires: Either pull excess wires

through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.

Show 9 more labels / short text on this page
Vent Pipe · Top Vent Discharge · Pressure · Switch · Flue Transition · Cover Plate · Side Vent Discharge · Pressure Switch · Vent Pipe
Page 15 of the Lenox Merit Series Furnace (ML180UHE) user manual — HORIZONTAL LEFT POSITION
Page 15 · click to enlarge
Page 15

The ML180UHE series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the USA. A fan−assisted Category I fur- nace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger. The ML180UHE is not approved for use with horizontal venting.

lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 24 and 25 for com- mon venting. A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney. An exterior masonry chimney that is not tile−lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile−lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent. If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting meth- od must be found. Insulation for the flexible vent pipe must be an encapsu- lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 24. Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.

The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper ap- plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab- sence of local codes, the NFGC serves as the defining doc- ument. Use self−drilling sheet metal screws or a mechanical fas- tener to firmly secure the vent pipe to the round collar of the flue transition. If self−drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self−drilling screw through the front and one through each side of the vent pipe and collar. See figure 23.

Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 15)
Fig. 29

Once the venting system is installed, attach the Dis- connected Vent" warning sticker to a visible area of the plenum near the vent pipe. See figure 23. The warning sticker is provided in the bag assembly. Or- der kit 66W04 for additional stickers.

Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet. See figure 23.

Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 15)
Fig. 30

The following additional requirements apply when a lined masonry chimney is used to vent this furnace.

Asphyxiation hazard. The exhaust vent for this fur- nace must be securely connected to the furnace flue transition at all times.

Masonry chimneys used to vent Category I central fur- naces must be either tile-lined or lined with a listed metal

Page 16 of the Lenox Merit Series Furnace (ML180UHE) user manual — HORIZONTAL LEFT POSITION
Page 16 · click to enlarge
Page 16
Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 16)
Fig. 31

When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting ML180UHE series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions. Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney. Never connect a Category I appliance to a chimney that is servicing a solid−fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed. A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors. General Venting Requirements Vent all ML180UHE furnaces according to these instruc- tions: 1 −Vent diameter recommendations and maximum allow-

able piping runs are found in the provided venting tables. 2 −In no case should the vent or vent connector diameter

DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran- ular insulating material.

be less than the diameter specified in the provided venting tables. 3 −The minimum vent capacity determined by the sizing

Lenox Merit Series Furnace (ML180UHE) — HORIZONTAL LEFT POSITION diagram (page 16)
Fig. 32

tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating. 4 −Single appliance vents − If the vertical vent or tile-lined

SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac- cording to the provided venting tables and the vent pipe manufacturer’s instructions.

chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de- termine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, however, shall not exceed 7 times the flow area of the listed ap- pliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods. 5 −Multiple appliance vents − The flow area of the largest

A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:

The chimney is currently serving at least one drafthood−

equipped appliance; The vent connectors and chimney are sized according

to the provided venting tables. If type B1 double-wall vent is used inside a chimney, no oth- er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as- sembly according to the terms of their respective listings and the vent manufacturer’s instructions.

section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless de- signed according to approved engineering methods.

Page 17 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 2
Page 17 · click to enlarge
Page 17
Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 17)
Fig. 33

Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector

MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT

6 −The entire length of single wall metal vent connector

1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.

shall be readily accessible for inspection, cleaning, and replacement. 7 −Single appliance venting configurations with zero lat-

10 −The vent pipe should be as short as possible with the least number of elbows and angles required to com- plete the job. Route the vent connector to the vent us- ing the shortest possible route. 11 −A vent connector shall be supported without any dips or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance. 12 −Vent connectors shall be firmly attached to the furnace flue collar by self−drilling screws or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means. 13 −When the vent connector used for Category I ap- pliances must be located in or pass through a crawl- space, attic or other areas which may be cold, that por- tion of the vent connector shall be constructed of listed double-wall type B vent material or material having equivalent insulation qualities. 14 −All venting pipe passing through floors, walls, and ceil- ings must be installed with the listed clearance to com- bustible materials and be fire stopped according to lo- cal codes. In absence of local codes, refer to NFGC (Z223.1). 15 −No portion of the venting system can extend into, or pass through any circulation air duct or plenum.

eral lengths (tables 3 and 4) are assumed to have no elbows in the vent system. For all other vent configura- tions, the vent system is assumed to have two 90° el- bows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed ca- pacity). 8 −The common venting tables (5, 6, 7, and 8) were gen-

erated using a maximum horizontal vent connector length of 1−1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:

TABLE 2

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 17)
Fig. 34

9 −If the common vertical vent is offset, the maximum

common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed

Page 18 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 2
Page 18 · click to enlarge
Page 18

16 −Vent connectors serving Category I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.

two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet. 20 −Do not install a manual damper, barometric draft regu- lator or flue restrictor between the furnace and the chimney. 21 −When connecting this appliance to an existing dedi- cated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables. If the existing venting system does not meet these re- quirements, it must be resized. TABLE 3 Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors

17 −If vent connectors are combined prior to entering the common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maximum common vent capacity).

18 −The common vent diameter must always be at least as large as the largest vent connector diameter.

19 −In no case, shall the vent connector be sized more than

Serving a Single Category I Appliance

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 18)
Fig. 35

Appliance Input Rating in Thousands of Btu Per Hour

0 0 78 0 152 0 251 0 375

2 13 51 18 97 27 157 32 232

4 21 49 30 94 39 153 50 227

6 25 46 36 91 47 149 59 223

0 0 84 0 165 0 276 0 415

2 12 57 16 109 25 178 28 263

5 23 53 32 103 42 171 53 255

8 28 49 39 98 51 164 64 247

0 0 88 0 175 0 295 0 447

2 12 61 17 118 23 194 26 289

5 23 57 32 113 41 187 52 280

10 30 51 41 104 54 176 67 267

0 0 94 0 191 0 327 0 502

2 11 69 15 136 20 226 22 339

5 22 65 30 130 39 219 49 330

10 29 59 40 121 51 206 64 315

15 35 53 48 112 61 195 76 301

0 0 97 0 202 0 349 0 540

2 10 75 14 149 18 250 20 377

5 21 71 29 143 38 242 47 367

10 28 64 38 133 50 229 62 351

15 34 58 46 124 59 217 73 337

20 48 52 55 116 69 206 84 322

0 0 100 0 213 0 374 0 587

2 9 81 13 166 14 283 18 432

5 21 77 28 160 36 275 45 421

10 27 70 37 150 48 262 59 405

15 33 64 44 141 57 249 70 389

20 56 58 53 132 66 237 80 374

30 NA NA 73 113 88 214 104 346 NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi- mum listed capacity).

Page 19 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 2
Page 19 · click to enlarge
Page 19

TABLE 4 Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving a Single Category I Appliance

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 19)
Fig. 36

Appliance Input Rating in Thousands of Btu Per Hour

0 38 77 59 151 85 249 126 373

2 39 51 60 96 85 156 123 231

4 NA NA 74 92 102 152 146 225

6 NA NA 83 89 114 147 163 220

0 37 83 58 164 83 273 123 412

2 39 56 59 108 83 176 121 261

5 NA NA 77 102 107 168 151 252

8 NA NA 90 95 122 161 175 243

0 37 87 57 174 82 293 120 444

2 39 61 59 117 82 193 119 287

5 52 56 76 111 105 185 148 277

10 NA NA 97 100 132 171 188 261

0 36 93 56 190 80 325 116 499

2 38 69 57 136 80 225 115 337

5 51 63 75 128 102 216 144 326

10 NA NA 95 116 128 201 182 308

15 NA 158 186 220 290

0 35 96 54 200 78 346 114 537

2 37 74 56 148 78 248 113 375

5 50 68 73 140 100 239 141 363

10 NA NA 93 129 125 223 177 344

15 NA 155 208 216 325

20 NA 186 192 254 306

0 34 99 53 211 76 372 110 584

2 37 80 55 164 76 281 109 429

5 49 74 72 157 98 271 136 417

10 NA NA 91 144 122 255 171 397

15 NA NA 115 131 151 239 208 377

20 NA 181 223 246 357

30 NA NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi- mum listed capacity).

Page 20 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 2
Page 20 · click to enlarge
Page 20

TABLE 5 Vent Connector Capacity Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 20)
Fig. 37

Appliance Input Rating in Thousands of Btu Per Hour

1 22 37 35 66 46 106 58 164

2 23 41 37 75 48 121 60 183

3 24 44 38 81 49 132 62 199

1 22 40 35 72 49 114 64 176

2 23 44 36 80 51 128 66 195

3 24 47 37 87 53 139 67 210

1 22 43 34 78 49 123 65 189

2 23 47 36 86 51 136 67 206

3 24 50 37 92 52 146 69 220

1 21 50 33 89 47 142 64 220

2 22 53 35 96 49 153 66 235

3 24 55 36 102 51 163 68 248

1 21 54 33 99 46 157 62 246

2 22 57 34 105 48 167 64 259

3 23 60 35 110 50 176 66 271

1 20 62 31 113 45 181 60 288

2 21 64 33 118 47 190 62 299

3 22 66 34 123 48 198 64 309

TABLE 6 Common Vent Capacity Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 20)
Fig. 38

Appliance Input Rating in Thousands of Btu Per Hour

FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT

6 92 81 140 116 204 161 309 248

8 101 90 155 129 224 178 339 275

10 110 97 169 141 243 194 367 299

15 125 112 195 164 283 228 427 352

20 136 123 215 183 314 255 475 394

30 152 138 244 210 361 297 547 459

Page 21 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 2
Page 21 · click to enlarge
Page 21

TABLE 7 Vent Connector Capacity Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving Two or More Category I Appliances

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 21)
Fig. 39

Appliance Input Rating in Thousands of Btu Per Hour

1 NA

2 NA 168 182

3 NA 121 131 175 198

1 NA

2 NA 125 126 184 193

3 NA 130 138 191 208

1 NA 119 121 182 186

2 NA NA 84 85 124 134 189 203

3 NA NA 89 91 129 144 197 217

1 NA NA 79 87 116 138 177 214

2 NA NA 83 94 121 150 185 230

3 NA NA 87 100 127 160 193 243

1 49 56 78 97 115 152 175 238

2 52 59 82 103 120 163 182 252

3 55 62 87 107 125 172 190 264

1 47 60 77 110 112 175 169 278

2 51 62 81 115 117 185 177 290

3 54 64 85 119 122 193 185 300 NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi- mum listed capacity).

TABLE 8 Common Vent Capacity Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving Two or More Category I Appliances

Lenox Merit Series Furnace (ML180UHE) — TABLE 2 diagram (page 21)
Fig. 40

Appliance Input Rating in Thousands of Btu Per Hour

FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT

6 NA 78 NA 113 200 158 304 244

8 NA 87 NA 126 218 173 331 269

10 NA 94 163 137 237 189 357 292

15 121 108 189 159 275 221 416 343

20 131 118 208 177 305 247 463 383

30 145 132 236 202 350 286 533 446

Page 22 of the Lenox Merit Series Furnace (ML180UHE) user manual — WARNING
Page 22 · click to enlarge
Page 22

Removal of the Furnace from Common Vent In the event that an existing furnace is removed from a venting system commonly run with separate gas ap- pliances, the venting system is likely to be too large to properly vent the remaining attached appliances. Conduct the following test while each appliance is operat- ing and the other appliances (which are not operating) re- main connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re- quirements section.

3 −Close all building doors and windows and all doors be-

tween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dry- ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper- ate at maximum speed. Do not operate a summer ex- haust fan. Close fireplace dampers. 4 −Follow the lighting instructions. Turn on the appliance

that is being inspected. Adjust the thermostat so that the appliance operates continuously. 5 −After the burner have operated for 5 minutes, test for

WARNING

leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle. 6 −After determining that each appliance connected to the

CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon mon- oxide poisoning or death. The following steps shall be followed for each ap- pliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp- ers, and any other gas−burning appliances to their pre- vious mode of operation. 7 −If a venting problem is found during any of the preced-

ing tests, the common venting system must be modi- fied to correct the problem.

1 −Seal any unused openings in the common venting sys-

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan- dards of the National Fuel Gas Code ANSI Z223.1.

tem. 2 −Inspect the venting system for proper size and horizontal

pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

Page 23 of the Lenox Merit Series Furnace (ML180UHE) user manual — Gas Piping
Page 23 · click to enlarge
Page 23

Gas Piping

4 −The piping should be sloped 1/4 inch (6.4 mm) per 15

feet (4.57 m) upward toward the meter from the fur- nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang- ers or straps. Install a drip leg in vertical pipe runs to the unit.

Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.

Lenox Merit Series Furnace (ML180UHE) — Gas Piping diagram (page 23)
Fig. 41 · Gas Piping

5 −A 1/8" N.P.T. plugged tap or pressure post is located

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

on the gas valve to facilitate test gauge connection. See figure 35.

6 −In some localities, codes may require the installation of

a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.

Gas Supply 1 −This unit is shipped standard for left or right side instal-

Lenox Merit Series Furnace (ML180UHE) — Gas Piping diagram (page 23)
Fig. 42 · Gas Piping

lation of gas piping (or top entry in horizontal applica- tions). Connect the gas supply to the piping assembly. 2 −When connecting the gas supply piping, consider fac-

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro- leum gases.

tors such as length of run, number of fittings, and fur- nace rating to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical applications. 3 −The gas piping must not run in or through air ducts,

clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.

TABLE 9 Gas Pipe Capacity − ft3/hr (m3/hr)

Lenox Merit Series Furnace (ML180UHE) — Gas Piping diagram (page 23)
Fig. 43 · Gas Piping
Page 24 of the Lenox Merit Series Furnace (ML180UHE) user manual — Gas Piping
Page 24 · click to enlarge
Page 24
Lenox Merit Series Furnace (ML180UHE) — Gas Piping diagram (page 24)
Fig. 44 · Gas Piping
Lenox Merit Series Furnace (ML180UHE) — Gas Piping diagram (page 24)
Fig. 45 · Gas Piping

Horizontal Application Right−Side Air Discharge NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET

Page 25 of the Lenox Merit Series Furnace (ML180UHE) user manual — ELECTROSTATIC DISCHARGE (ESD)
Page 25 · click to enlarge
Page 25

The unit is equipped with a field make−up box on the left hand side of the cabinet. The make−up box may be moved to the right side of the furnace to facilitate installation. If the make−up box is moved to the right side, clip the wire ties that bundle the wires together. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage.

After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means. NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these devices.

Lenox Merit Series Furnace (ML180UHE) — Electrical diagram (page 25)
Fig. 46 · Electrical
Lenox Merit Series Furnace (ML180UHE) — Electrical diagram (page 25)
Fig. 47 · Electrical

Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af- ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.

The furnace must be isolated by closing its individual manual shut-off valve and disconnecting from from the gas supply system during any pressure testing of the gas sup- ply system at pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).

Lenox Merit Series Furnace (ML180UHE) — Electrical diagram (page 25)
Fig. 48 · Electrical

When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 28. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).

Lenox Merit Series Furnace (ML180UHE) — Electrical diagram (page 25)
Fig. 49 · Electrical

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Refer to figure 32 for schematic wiring diagram and trou- bleshooting and figure 33 for field wiring.

Lenox Merit Series Furnace (ML180UHE) — ELECTROSTATIC DISCHARGE (ESD) diagram (page 25)
Fig. 50

The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.

Electrostatic discharge can affect electronic com- ponents. Take precautions during furnace installa- tion and service to protect the furnace’s electronic controls. Precautions will help to avoid control ex- posure to electrostatic discharge by putting the fur- nace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an un- painted unit surface, such as the gas valve or blower deck, before performing any service procedure.

Holes are on both sides of the furnace cabinet to facilitate wiring.

Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

Leak Check · Precautions and Procedures

Page 26 of the Lenox Merit Series Furnace (ML180UHE) user manual — HEAT
Page 26 · click to enlarge
Page 26

Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.

Generator Use − Voltage Requirements

The following requirements must be kept in mind when specifying a generator for use with this equipment: The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts). The furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz). The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power. Generator should have a wave form distortion of less than 5% total harmonic distortion. Thermostat

Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring diagram shown in figure 33. Use 18−gauge wire or larger that is suit- able for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Na- tional Electric Code (ANSI/NFPA No. 70). A green ground wire is provided in the field make−up box. NOTE − The ML180UHE furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

Install the room thermostat according to the instructions provided with the thermostat. See figure 31 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropri- ate dual fuel thermostat instructions.

One line voltage EAC" 1/4" spade terminal is provided on the furnace integrated control. See figure 34 for integrated control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an exter- nal relay.

ML180UHE and CONDENSING UNIT

THERMOSTAT DESIGNATIONS (Refer to specific thermostat and outdoor unit.)

*CONDENSING UNIT

POWER

R

R

One line voltage HUM" 1/4" spade terminal is provided on the furnace integrated control. See figure 34 for integrated control configuration. This terminal is energized in the heating mode when the combustion air inducer is operat- ing. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con- nected to one of the provided neutral terminals. If a humidi- fier rated at greater than one amp is connected to this termi- nal, it is necessary to use an external relay relay.

HEAT

W1

W

CONDENSING

Y

COOLING

Y

UNIT

INDOOR BLOWER

G

G

CONDENSING UNIT COMMON

COMMON

*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS

One 24V "H" 1/4" spade terminal is provided on the furnace integrated control. See figure 34 for integrated control con- figuration. The terminal is energized in the heating mode when the combustion air inducer is operating and the pres- sure switch is closed. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the "C" terminal.

1 −When the thermostat is set to FAN ON," the indoor

blower will run continuously on the fan speed when there is no cooling or heating demand. 2 −When the ML180UHE is running in the heating mode,

the indoor blower will run on the heating speed. 3 −When there is a cooling demand, the indoor blower will

run on the cooling speed.

Show 4 more labels / short text on this page
Accessory Terminals · Thermostat Furnace Condensing · Unit · Indoor Blower Speeds
Page 27 of the Lenox Merit Series Furnace (ML180UHE) user manual — ML180UHE Schematic Wiring Diagram and Sequence of Operation
Page 27 · click to enlarge
Page 27

ML180UHE Schematic Wiring Diagram and Sequence of Operation

1 − Line voltage is applied to L1 and N. the T1 low voltage transformer is energized, and line voltage is applied to B3 indoor blower.

2 − S47 rollout switch(es) must be closed in order for 24V from transformer to be output on integrated control "R" to power thermostat.

3 − When there is a call for heat, W1 of the thermostat energizes W of the furnace control with 24VAC.

4 − A92 integrated control runs a self−check. S10 primary limit and S21 secondary limit contacts are found to be closed. Call for heat can continue. 5 − A92 integrated control energizes B6 combustion air inducer. S18 combustion air pressure switch closes . Once S18 closes, a 15−second pre−purge follows. 6 − A92 integrated control energizes R33 ignitor. A 20−second warm−up period begins.

7 − GV1 gas valve opens for a 4−second trial for ignition

8 − Flame is sensed, gas valve remains open for the heat call.

9 − After 30−second delay (from flame sensed), A92 integrated control applies 24vVAC to Heat speed of B3 indoor blower.

10 − When heat demand is satisfied, W1 of the indoor thermostat de−energizes W of A92ignition control which de−energizes GV1 gas valve. B6 combustion air inducer continues a 5−second post−purge period, and B3 indoor blower completes a selected OFF time delay.

Page 28 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 10
Page 28 · click to enlarge
Page 28
Lenox Merit Series Furnace (ML180UHE) — TABLE 10 diagram (page 28)
Fig. 51
Lenox Merit Series Furnace (ML180UHE) — TABLE 10 diagram (page 28)
Fig. 52

TABLE 10

Lenox Merit Series Furnace (ML180UHE) — TABLE 10 diagram (page 28)
Fig. 53
Page 29 of the Lenox Merit Series Furnace (ML180UHE) user manual — FOR YOUR SAFETY READ BEFORE LIGHTING
Page 29 · click to enlarge
Page 29

Unit Start−Up

4 −This furnace is equipped with an ignition device which

automatically lights the burners. Do not try to light the burners by hand. 5 −Remove the upper access panel. 6 −Move switch on gas valve to OFF. Do not force. See

FOR YOUR SAFETY READ BEFORE LIGHTING

Lenox Merit Series Furnace (ML180UHE) — FOR YOUR SAFETY READ BEFORE LIGHTING diagram (page 29)
Fig. 54

figure 35. 7 −Wait five minutes to clear out any gas. If you then smell

Do not use this furnace if any part has been under- water. A flood−damaged furnace is extremely dan- gerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified ser- vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.

gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instruc- tions. If you do not smell gas go to next step.

Lenox Merit Series Furnace (ML180UHE) — FOR YOUR SAFETY READ BEFORE LIGHTING diagram (page 29)
Fig. 55

If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.

Lenox Merit Series Furnace (ML180UHE) — FOR YOUR SAFETY READ BEFORE LIGHTING diagram (page 29)
Fig. 56

8 −Move switch on gas valve to ON. Do not force. See fig-

ure 35. 9 −Replace the upper access panel. 10−Turn on all electrical power to to the unit. 11−Set the thermostat to desired setting. NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line. 12−If the appliance will not operate, follow the instructions Turning Off Gas to Unit" and call your service techni- cian or gas supplier. Turning Off Gas to Unit 1 −Set the thermostat to the lowest setting. 2 −Turn off all electrical power to the unit if service is to be

Before attempting to perform any service or mainte- nance, turn the electrical power to unit OFF at dis- connect switch.

BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

The gas valve on the ML180UHE unit is equipped with a gas control switch. Use only your hand to move the switch. Never use tools. If the switch will not turn or if the control switch will not move by hand, do not try to repair it.

Placing the furnace into operation:

performed. 3 −Remove the upper access panel. 4 −Move switch on gas valve to OFF. Do not force. 5 −Replace the upper access panel.

ML180UHE units are equipped with an automatic ignition system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with an automatic ignition system.

Failure To Operate If the unit fails to operate, check the following: 1 −Is the thermostat calling for heat? 2 −Are access panels securely in place? 3 −Is the main disconnect switch closed? 4 −Is there a blown fuse or tripped circuit breaker? 5 −Is the filter dirty or plugged? Dirty or plugged filters will

Lenox Merit Series Furnace (ML180UHE) — FOR YOUR SAFETY READ BEFORE LIGHTING diagram (page 29)
Fig. 57

If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.

cause the limit control to shut the unit off. 6 −Is gas turned on at the meter? 7 −Is the manual main shut-off valve open? 8 −Is the internal manual shut-off valve open? 9 −Is the unit ignition system in lock out? If the unit locks out

Gas Valve Operation (Figure 35)

1 −STOP! Read the safety information at the beginning of

again, call the service technician to inspect the unit for blockages. 10 −Is pressure switch closed? Obstructed flue will cause unit to shut off at pressure switch. Check flue and outlet for blockages.

this section.

2 −Set the thermostat to the lowest setting.

3 −Turn off all electrical power to the unit.

Page 30 of the Lenox Merit Series Furnace (ML180UHE) user manual — TABLE 12
Page 30 · click to enlarge
Page 30

11 −Are flame rollout switches tripped? If flame rollout switches are tripped, call the service technician for in- spection.

Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. See table 13 for proper line pressure. Replace the threaded plug after mea- surements have been taken. Manifold Pressure Measurement 1 −Remove the threaded plug from the outlet side of the

Heating Sequence Of Operation (follow steps below or see Figure 32 for more detail)

1 −When thermostat calls for heat, combustion air blower

starts. 2 −Combustion air pressure switch proves blower opera-

tion. Switch is factory−set and requires no adjustment. 3 −After a 15−second prepurge, the hot surface ignitor en-

gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pres- sure. 2 −Start unit and allow 5 minutes for unit to reach steady

ergizes. 4 −After a 20−second ignitor warm−up period, the gas

valve solenoid opens. A 4−second trial for ignition peri- od begins. 5 −Gas is ignited, flame sensor proves the flame, and the

state. 3 −While waiting for the unit to stabilize, observe the

flame. Flame should be stable and should not lift from burner. Natural gas should burn blue. 4 −After allowing unit to stabilize for 5 minutes, record

combustion process continues. 6 −If flame is not detected after first ignition trial, the igni-

tion control will repeat steps 3 and 4 four more times before locking out the gas valve (WATCHGUARD" flame failure mode). The ignition control will then auto- matically repeat steps 1 through 6 after 60 minutes. 7 −To interrupt the 60−minute WATCHGUARD" period,

manifold pressure and compare to value given in table 13. NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

move thermostat from Heat" to OFF" then back to Heat." Heating sequence then restarts at step 1.

Proper Combustion

Gas Pressure Adjustment

Furnace should operate a minimum 15 minutes with cor- rect manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue out- let and compare to the tables below. The maximum car- bon monoxide reading should not exceed 50 ppm.

TABLE 11 GAS METER CLOCKING CHART

Lenox Merit Series Furnace (ML180UHE) — TABLE 11 GAS METER CLOCKING CHART diagram (page 30)
Fig. 58

TABLE 12

Lenox Merit Series Furnace (ML180UHE) — TABLE 12 diagram (page 30)
Fig. 59

2 cu ft DIAL −045 80 160 200 400 −070 55 110 136 272 −090 41 82 102 204 −110 33 66 82 164 −135 27 54 68 136 Natural−1000 btu/cu ft LP−2500 btu/cu ft

7.2 − 7.8 7.5 − 9.0 −070 −090 −110 −135

The manifold pressure may require adjustment and com- bustion air pressure switch may need replacing to ensure proper combustion at higher altitudes. Refer to table 13 for manifold pressure and table 14 for pressure switch change and gas conversion kits.

Furnace should operate at least 5 minutes before check- ing gas flow. Determine time in seconds for two revolu- tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 11. If manifold pressure matches table 13 and rate is incorrect, check gas orifices for proper size and restric- tion. Remove temporary gas meter if installed.

Lenox Merit Series Furnace (ML180UHE) — TABLE 12 diagram (page 30)
Fig. 60

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

Gas Flow (Approximate)

Page 31 of the Lenox Merit Series Furnace (ML180UHE) user manual — Other Unit Adjustments
Page 31 · click to enlarge
Page 31

TABLE 13 Manifold Pressure Settings at all Altitudes

Lenox Merit Series Furnace (ML180UHE) — Other Unit Adjustments diagram (page 31)
Fig. 61 · Other Unit Adjustments

Model Input Size Gas 0−2000 ft 2001−4500 ft. 4501−7500 ft 7501 − 10,000 ft Line Pressure in.wg.

TABLE 14 Pressure Switch and Gas Conversion Kits at all Altitudes

Lenox Merit Series Furnace (ML180UHE) — Other Unit Adjustments diagram (page 31)
Fig. 62 · Other Unit Adjustments

0−4500 ft 4501−7500 ft 7501 − 10,000 ft 7501 − 10,000 ft 0 − 7500 ft 7501 − 10,000 ft 0 − 7500 ft

Other Unit Adjustments

air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.

Primary and Secondary Limits

The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo- cated in the blower compartment, attached to the back side of the blower. These auto reset limits are factory−set and re- quire no adjustment.

Fan Control The heat fan−on time of 30 seconds is not adjustable. The heat fan−off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position across the five pins on the integrated control. The unit is shipped with a factory fan−off delay setting of 90 seconds. The fan−off delay affects com- fort and is adjustable to satisfy individual applications. Ad- just the fan−off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de−energized. Longer off delay settings provide lower re- turn air temperatures; shorter settings provide higher re- turn air temperatures. See figure 36.

These manually reset switches are located on the burner box. Pressure Switch The pressure switch is located in the heating compartment adjacent to the combustion air inducer. The switch checks for proper combustion air inducer operation before allow- ing ignition trial. The switch is factory−set and requires no adjustment.

Temperature Rise After the furnace has been started, and supply and return

Flame Rollout Switches

Page 32 of the Lenox Merit Series Furnace (ML180UHE) user manual — Other Unit Adjustments
Page 32 · click to enlarge
Page 32
Lenox Merit Series Furnace (ML180UHE) — Other Unit Adjustments diagram (page 32)
Fig. 63 · Other Unit Adjustments

Input Voltage Requirements The circuit is designed to be operated with AC voltage. A voltage of 12 to 33VAC is required to energize the motor. Expected current draw will be less than 20mA. Blower Speeds Follow the steps below to change the blower speeds.

1 −Turn off electrical power to furnace.

To adjust fan−off timing, reposition jumper across pins to

2 −Remove blower access panel.

3 −Disconnect existing speed tap at integrated control

speed terminal. NOTE − Termination of any unused motor leads must be insulated. 4 −Place unused blower speed tap on integrated control

PARK" terminal or insulate.

5 −Refer to blower speed selection chart on unit wiring dia-

gram for desired heating or cooling speed. See Blower performance data beginning on the next page.

6 −Connect selected speed tap at integrated control

speed terminal.

Thermostat Heat Anticipation Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.

7 −Resecure blower access panel.

8 −Turn on electrical power to furnace.

9 −Recheck temperature rise. Electronic Ignition The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re- set device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will re−set and remake thermostat demand to the furnace and automatically reset the inte- grated control to begin the ignition sequence.

Constant Torque Motor ML180UHE units are equipped with a constant torque ECM motor. It has a DC motor coupled to an electronic control module both contained in the same motor housing. The mo- tor is programmed to provide constant torque at each of the five selectable speeds. The motor has five speed taps. Each tap requires 24 volts to energize.

Page 33 of the Lenox Merit Series Furnace (ML180UHE) user manual — BLOWER DATA
Page 33 · click to enlarge
Page 33

BLOWER DATA

ML180UH045E36A PERFORMANCE (Less Filter)

Lenox Merit Series Furnace (ML180UHE) — BLOWER DATA diagram (page 33)
Fig. 64

cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

0.00 1380 265 1155 165 995 120 975 115 945 105

0.10 1345 270 1120 175 950 120 880 105 865 100

0.20 1320 285 1080 190 900 125 805 105 700 85

0.30 1290 295 1055 200 875 135 750 110 640 90

0.40 1265 310 1010 205 825 145 710 120 595 95

0.50 1230 315 990 215 790 155 660 125 535 100

0.60 1190 330 945 230 750 165 630 135 500 110

0.70 1165 340 915 235 705 170 570 140 435 115

0.80 1130 350 880 245 670 180 535 150 380 120

ML180UH070E36B PERFORMANCE (Less Filter)

Lenox Merit Series Furnace (ML180UHE) — BLOWER DATA diagram (page 33)
Fig. 65

cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

0.00 1415 265 1330 170 1215 135 1175 125 1075 85

0.10 1415 280 1295 170 1145 145 1130 130 955 95

0.20 1355 290 1225 185 1110 150 1080 140 885 100

0.30 1330 300 1190 200 1060 160 1035 155 825 110

0.40 1290 310 1155 205 1015 175 970 160 770 120

0.50 1245 325 1115 215 980 180 930 170 695 125

0.60 1225 335 1045 230 920 190 865 180 625 135

0.70 1190 350 1000 235 855 205 790 190 540 140

0.80 1160 365 925 245 790 205 735 200 445 145

ML180UH090E48B PERFORMANCE (Less Filter)

Lenox Merit Series Furnace (ML180UHE) — BLOWER DATA diagram (page 33)
Fig. 66

cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

0.00 1785 380 1570 270 1440 220 1395 190 1190 120

0.10 1755 395 1535 275 1420 230 1350 205 1140 130

0.20 1730 415 1505 290 1380 245 1310 215 1110 145

0.30 1690 435 1460 305 1345 260 1275 230 1065 155

0.40 1645 440 1435 320 1310 270 1240 240 1010 165

0.50 1615 455 1395 335 1265 285 1180 255 955 180

0.60 1590 470 1350 350 1210 290 1150 265 915 185

0.70 1545 475 1300 360 1175 305 1095 275 860 200

0.80 N/A N/A 1270 370 1140 310 1040 285 820 210

Page 34 of the Lenox Merit Series Furnace (ML180UHE) user manual — BLOWER DATA
Page 34 · click to enlarge
Page 34

BLOWER DATA

ML180UH090E60C PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity. High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

in. w.g.

0.00 2255 640 1940 420 1750 310 1580 230 1485 185 2290 655 1980 425 1775 310 1605 235 1495 195

0.10 2200 655 1910 440 1705 315 1535 240 1385 190 2250 675 1945 445 1730 320 1555 245 1400 190 0.20 2150 675 1865 450 1655 340 1490 260 1340 205 2210 695 1885 465 1680 340 1510 265 1350 205 0.30 2125 695 1835 475 1635 355 1450 275 1285 215 2165 715 1850 475 1645 355 1470 275 1285 215 0.40 2090 715 1800 495 1585 370 1405 285 1235 230 2135 720 1810 490 1595 370 1410 290 1225 230 0.50 2060 735 1760 510 1545 385 1370 305 1200 245 2070 735 1765 515 1545 390 1370 305 1180 245 0.60 2020 750 1725 525 1515 405 1320 320 1145 255 2030 760 1715 530 1495 405 1325 320 1140 255 0.70 1980 765 1680 540 1465 420 1265 330 1105 270 1990 775 1685 540 1450 425 1265 330 1095 270 0.80 1935 785 1635 560 1420 435 1225 350 1055 285 1950 795 1645 560 1415 435 1225 345 1040 285

ML180UH110E60C PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity. High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

in. w.g.

0.00 2230 635 1945 430 1715 295 1555 230 1470 185 2315 645 1990 415 1780 300 1610 230 1510 200

0.10 2180 655 1905 445 1690 305 1510 240 1340 175 2260 655 1945 425 1740 315 1550 240 1400 185 0.20 2135 680 1865 465 1630 330 1470 260 1280 190 2210 680 1895 450 1680 335 1510 255 1350 200 0.30 2090 695 1830 480 1595 345 1440 275 1235 200 2165 700 1850 465 1650 355 1455 275 1285 210 0.40 2050 715 1785 495 1550 360 1385 285 1175 210 2130 715 1830 485 1585 365 1395 285 1230 225 0.50 2025 730 1740 520 1500 375 1340 300 1130 225 2095 730 1770 500 1535 385 1365 300 1175 235 0.60 2010 750 1710 535 1470 390 1305 320 1080 240 2055 755 1725 515 1495 400 1305 315 1135 250 0.70 1965 755 1670 555 1420 410 1255 330 1015 255 2000 765 1675 535 1465 410 1255 325 1080 265 0.80 1905 785 1635 560 1380 425 1215 350 975 270 1965 785 1640 555 1400 425 1210 345 1025 275

ML180UH135E60D PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity. High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

in. w.g.

0.00 2495 755 2295 590 2045 435 1845 315 1650 230 2365 725 2295 575 2005 410 1820 300 1635 235

0.10 2440 780 2220 620 2015 445 1820 330 1615 245 2350 745 2210 595 2000 435 1745 320 1530 230 0.20 2390 790 2175 640 1935 470 1735 350 1550 255 2330 775 2175 625 1945 455 1730 330 1490 250 0.30 2360 805 2140 655 1895 490 1720 370 1485 275 2245 785 2135 645 1895 475 1655 355 1425 265 0.40 2285 835 2125 675 1850 510 1660 380 1455 290 2215 810 2085 660 1840 495 1600 375 1385 285 0.50 2240 860 2060 690 1815 535 1610 400 1415 310 2175 825 2045 680 1815 505 1590 390 1340 290 0.60 2225 865 2015 715 1785 550 1535 420 1330 320 2125 845 1995 700 1765 530 1525 405 1300 310 0.70 2160 895 1955 735 1755 570 1500 440 1265 340 2095 865 1950 710 1700 545 1485 420 1260 325 0.80 2105 905 1925 750 1715 580 1435 450 1215 345 2065 880 1890 725 1680 565 1415 445 1205 345

Show 6 more labels / short text on this page
External · Static Pressure · External · Static Pressure · External · Static Pressure
Page 35 of the Lenox Merit Series Furnace (ML180UHE) user manual — WARNING
Page 35 · click to enlarge
Page 35

Service

3 −Label the wires from gas valve, rollout switches, prima- ry limit switch and make−up box then disconnect them. 4 −Remove the screws that secure the combustion air in- ducer/pressure switch assembly to the collector box. Carefully remove the combustion air inducer to avoid damaging blower gasket. If gasket is damaged, it must be replaced to prevent leakage. 5 −Remove the collector box located behind the combus- tion air inducer. Be careful with the collector box gas- ket. If the gasket is damaged, it must be replaced to prevent leakage. 6 −Disconnect gas supply piping. Remove the four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit. 7 −NOX units only − Remove screw securing NOX insert.

WARNING

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous opera- tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis- connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.

Remove NOX insert. See figure 38. 8 −Remove screws from both sides, top and bottom of

vestibule panel. 9 −Remove heat exchanger. It may be necessary to

spread cabinet side to allow more room. If so, remove five screws from the left side or right side of cabinet. See figure 39.

At the beginning of each heating season, a qualified techni- cian should check the system as follows: Blower

10 −Backwash using steam. Begin from the burner opening on each clam. Steam must not exceed 275°F.

Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.

11 −To clean burners, run a vacuum cleaner with a soft brush attachment over the face of burners. Visually inspect in- side the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. Figure 37 shows burner detail.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju- ry or death.

12 −To clean the combustion air inducer visually inspect and using a wire brush clean where necessary. Use com- pressed air to clean off debris and any rust.

13 −Reinstall heat exchanger in vestibule. (Replace the five screws in the cabinet from step 10 if removed).

Filters All ML180UHE filters are installed external to the unit. Fil- ters should be inspected monthly. Clean or replace the fil- ters when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high veloc- ity airflow. Table 1 lists recommended filter sizes. Flue And Chimney 1 −Check flue pipe, chimney and all connections for tight-

14 −NOx units only − Replace NOx inserts.

15 −Reinstall collector box and combustion air assembly. Reinstall all screws to the collector box and combustion air inducer. Failure to replace all screws may cause leaks. Inspect gaskets for any damage and replace if necessary.

16 −Reinstall burner box and manifold assembly.

ness and to make sure there is no blockage. 2 −Check unit for proper draft.

17 −Reconnect all wires.

18 −Reconnect top cap and vent pipe to combustion air in- ducer outlet.

Electrical 1 −Check all wiring for loose connections. 2 −Check for the correct voltage at the furnace (furnace

19 −Reconnect gas supply piping.

operating). Correct voltage is 120VAC + 10%. 3 −Check amp−draw on the blower motor with blower ac-

20 −Turn on power and gas supply to unit.

21 −Set thermostat and check for proper operation.

cess panel in place. Unit Nameplate Actual Cleaning the Heat Exchanger and Burners NOTE − Use papers or protective covering in front of the fur- nace during cleaning. 1 −Turn off both electrical and gas power supplies to fur- nace. 2 − Remove flue pipe and top cap (some applications top cap can remain) from the unit.

22 −Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means.

23 −If a leak is detected, shut gas and electricity off and repair leak.

24 −Repeat steps 24 and 26 until no leaks are detected.

25 −Replace access panel.

Page 36 of the Lenox Merit Series Furnace (ML180UHE) user manual — Service
Page 36 · click to enlarge
Page 36
Lenox Merit Series Furnace (ML180UHE) — Service diagram (page 36)
Fig. 67 · Service
Lenox Merit Series Furnace (ML180UHE) — Service diagram (page 36)
Fig. 68 · Service
Lenox Merit Series Furnace (ML180UHE) — Service diagram (page 36)
Fig. 69 · Service
Lenox Merit Series Furnace (ML180UHE) — Service diagram (page 36)
Fig. 70 · Service

Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af- ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.

Page 37 of the Lenox Merit Series Furnace (ML180UHE) user manual — Repair Parts List
Page 37 · click to enlarge
Page 37

Planned Service

The following items should be checked during an annual inspection. Power to the unit must be shut off for the service techni- cian’s safety.

Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob- structed to provide combustion air.

Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.

Burners − Must be inspected for rust, dirt, or signs of water.

Combustion gases − Flue products must be analyzed and compared to the unit specifications. See table 12.

Vent pipe − Must be inspected for signs of water, damaged or sagging pipe, or disconnected joints.

Problems detected during the inspection may make it nec- essary to temporarily shut down the furnace until the items can be repaired or replaced.

Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.

Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace in- spections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas.

Blower access panel − Must be properly in place and pro- vide a seal between the return air and the room where the furnace is installed.

Return air duct − Must be properly attached and provide an air seal to the unit.

Repair Parts List

The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate −− Example: ML180UHE045P24A−01. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.

Upper access panel Blower panel Top cap Control Panel Parts

Flame sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Flame rollout switch (s) Secondary limit

Transformer Integrated control Door interlock switch Circuit breaker Blower Parts

Blower wheel Blower housing Motor Motor mounting frame Motor power choke Blower housing cutoff plate

Cabinet Parts · Heating Parts

Page 38 of the Lenox Merit Series Furnace (ML180UHE) user manual — Integrated Control Diagnostic Codes
Page 38 · click to enlarge
Page 38

Integrated Control Diagnostic Codes

RED LED Flash Code Diagnostic Codes / Status of Furnace

Off No power to control or board fault detected

On Board fault detected,

Heartbeat1 Control powered − displayed during all modes of operation if no errors are detected

1 Reverse Line Voltage Polarity

2 Improper Earth Ground

3 Burner failed to light, or lost flame during heat demand

4 Low Flame Signal − check flame sensor

5 Watchguard − burner failed to light, exceeded maximum number of retries or recycles.

7 Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 min- utes

8 Rollout Switch Open

9 Pressure Switch failed to close or opened during heat demand

10 Watchguard − Pressure Switch opened 5 times during one heat demand

11 Pressure Switch stuck closed prior to activation of combustion air inducer

12 Flame Sensed without gas valve energized

13 Low Line Voltage

Last 10 error codes are stored in memory including when power is shut off to the unit. − To recall, press and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

6 Not Used

Page 39 of the Lenox Merit Series Furnace (ML180UHE) user manual — RESET PERIOD COMPLETE?
Page 39 · click to enlarge
Page 39
TroubleshootingHeating Sequence of Operation

HEATING SEQUENCE OF OPERATION

NORMAL HEATING MODE ABNORMAL HEATING MODE

POWER ON

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

NO

INDOOR BLOWER DELAY OFF.

CONTROL SELF−CHECK OKAY?

LED SLOW FLASH (RESET CONTROL BY TURNING MAIN POWER OFF.)

YES

NO

LED FLASHES CODE 1 − POLARITY REVERSED.

IS POLARITY CORRECT?

YES

NO

IS THERE A PROPER GROUND?

LED FLASHES CODE 2 − IMPROPER GROUND.

YES

NO

LED FLASHES CODE 13 − LOW LINE VOLTAGE. CONTROL WILL NOT RESPOND TO A CALL FOR HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.

IS VOLTAGE ABOVE 70 VOLTS?

LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.

YES

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

ROLLOUT SWITCH CLOSED?

INDOOR BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES

YES

AND POWER IS RESET OR T’STAT IS INTERRUPTED

FOR MINIMUM OF 1 SECOND.

LED FLASHES CODE 12 − FLAME SENSED

BURNER OFF? (Flame sensed without gas valve energized)

NO

WITHOUT GAS VALVE ENERGIZED. GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER ON HEATING SPEED.

YES

NO

NORMAL OPERATION:

LED SLOW FLASH

YES

THERMOSTAT CALLS FOR HEAT:

LED FLASHES CODE 7 − PRIMARY LMIT

LED SLOW FLASH

OPEN. COMBUSTION AIR INDUCER

OFF.INDOOR BLOWER ON NO

YES

PRIMARY LIMIT SWITCH. CLOSED?

LED FLASHES CODE 11 − PRESSURE

YES

SWITCH CLOSED. GAS VALVE OFF COMBUSTION AIR

NO

IS COMBUSTION AIR PRESSURE SWITCH OPEN?

INDUCER OFF. INDOOR BLOWER

OFF WITH DELAY. (Sequence holds until pressure switch

YES

opens or thermostat resets control.)

IS COMBUSTION AIR INDUCER

ENERGIZED?

YES LED FLASHES CODE 9 − PRESSURE SWITCH FAILED

YES

HAS COMBUSTION AIR PRESSURE

NO

TO CLOSE OR OPENED DURING HEAT DEMAND. PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS

SWITCH CLOSED IN 2.5 MINUTES?

YES

VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE

RESET PERIOD COMPLETE?

CONTINUED NEXT PAGE

Page 40 of the Lenox Merit Series Furnace (ML180UHE) user manual — WITHIN 2.5 MINUTES?
Page 40 · click to enlarge
Page 40
TroubleshootingHeating Sequence of Operation (Continued)

HEATING SEQUENCE CONTINUED

NORMAL HEATING MODE ABNORMAL HEATING MODE

15-SECOND COMBUSTION AIR INDUCER PREPURGE INITIATED BY CLOSED PRESSURE SWITCH.

YES

LED FLASHES CODE 13 −

NO

LOW LINE VOLTAGE. ONCE VOLTAGE IS ABOVE

NO

IGNITOR WARM-UP −− 20 SECONDS.

IS VOLTAGE ABOVE 70 VOLTS?

75 VOLTS, HEATING SEQUENCE RESTARTS.

YES

YES

4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS. IGNITOR ENERGIZED FOR

FIRST 3 SECONDS OF THE TRIAL.

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER OFF. HAS CONTROL FAILED TO SENSE FLAME FOR

YES

NO

NO

FIVE CONSECUTIVE TRIES DURING A SINGLE

FLAME STABILIZATION PERIOD.

HEAT DEMAND?

4 SECONDS

YES

FLAME RECTIFICATION CURRENT CHECK. CAN FLAME BE PROVEN WITHIN

LED SIGNAL WATCHGUARD FAILURE CODE

WATCHGUARD MODE. GAS VALVE OFF.

4 SECONDS AFTER GAS VALVE OPENS? (0.5 microamps)

COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY IS 60-MINUTE RESET PERIOD COMPLETE?

YES

NO YES

NO

HAS CONTROL RESET IGNITION

FLAME PRESENT?

SEQUENCE FOUR TIMES?

YES

YES

LED FLASHES CODE

NO

7 − PRIMARY LIMIT OPEN. GAS VALVE, COMB. AIR INDUCER AND INDOOR BLOW-

LED FLASHES CODE 4 − LOW FLAME

SIGNAL. (Does not affect operation of control)

FLAME SIGNAL 1.5 MICROAMPS OR GREATER?

YES

ER OFF. LEDs SIG- NAL LIMIT SWITCH OPEN UNTIL MAIN

INDOOR BLOWER ON AFTER 30−SECOND DELAY

LED FLASHES CODE 7 − PRIMARY LIMIT OPEN

POWER IS INTERRUPTED OR T’STAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM. 60−MINUTE

YES

GAS VALVE DE−ENERGIZED. COMBUSTION AIR INDUCER DE−ENERGIZED. INDOOR BLOWER ON UNTIL SWITCH CLOSES.

NO

PRIMARY LIMIT SWITCH CLOSED?

LIMIT SWITCH CLOSED?

YES

WATCHGUARD PE-

YES HAS PRIMARY LIMIT RESET TIME EXCEEDED 3 MINUTES?

RIOD STARTS AT TIME LIMIT CLOSES.

YES

IS 60−MIN. PERIOD

COMPLETE? NO

NO

ROLLOUT SWITCH CLOSED? LED FLASHES CODE 8 − ROLLOT SWITCH OPEN. GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT

YES

SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR

THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.

NO

COMBUSTION AIR PRESSURE

SWITCH CLOSED?

YES

HAS PRESSURE SWITCH OPENED 5 TIMES

LED FLASHES

THERMOSTAT DEMAND SATISFIED.

IN THE SAME HEAT DEMAND?

CODE 10 1 HR PRESSURE SWITCH WATCHGUARD

YES

NO

YES

LED SLOW FLASH.

GAS VALVE DE−ENERGIZED. COMBUSTION AIR

INDUCER ON. INDOOR BLOWER OFF WITH DELAY. HAS CAB PRESSURE SWITCH CLOSED

MODE

YES

COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE AFTER T’STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER COMPLETES SELECTED OFF"

WITHIN 2.5 MINUTES?

YES

NO

5-MINUTE PRESSURE SWITCH WATCHGUARD MODE.

DELAY BEFORE SHUTTING OFF.

Page 41 of the Lenox Merit Series Furnace (ML180UHE) user manual — SYSTEM FAN AND EAC TERM. OFF
Page 41 · click to enlarge
Page 41
TroubleshootingCooling Sequence of Operation

COOLING SEQUENCE OF OPERATION

NORMAL COOLING MODE ABNORMAL COOLING MODE

POWER ON

IGNITION CONTROL MAIN POWER ON.

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

CONTROL SELF DIAGNOSTIC CHECK. IS CONTROL OPERATING NORMALLY?

NO

INDOOR BLOWER OFF WITH NORMAL DELAY.

SIGNAL CIRCUIT BOARD FAILURE AT LED. INTERRUPT MAIN POWER TO RESET CONTROL.

YES

NO LED FLASHES CODE 2 IMPROPER GROUND CONTROL WILL CONTINUE TO CALL FOR COOLING

IS THERE A PROPER GROUND?

IN THIS CONDITION.

YES

NO

LED FLASHES CODE 1 POLARITY REVERSED CONTROL WILL CONTINUE TO CALL FOR COOLING IN

IS POLARITY CORRECT?

THIS CONDITION.

YES

NO

LED FLASHES CODE 13 LOW VOLTAGE. CONTROL

IS VOLTAGE ABOVE 70 VOLTS?

WILL CONTINUE TO CALL FOR COOLING

IN THIS CONDITION. YES

LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH

NO

ROLLOUT SWITCH MONITORED CONTINUOUSLY.

IS ROLLOUT SWITCH CLOSED?

CLOSES AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.

YES

LED: SLOW FLASH RATE REMAINS UNCHANGED

THROUGHOUT COOLING CYCLE.

THERMOSTAT CALLS FOR COOLING.

COMPRESSOR CONTACTOR AND SYSTEM FAN

ENERGIZED WITH 2-SECOND DELAY (COOLING SPEED). EAC TERM. ENERGIZED.

THERMOSTAT OPENS.

COMPRESSOR OFF.

SYSTEM FAN AND EAC TERM. OFF

WITH 45-SECOND DELAY.

Page 42 of the Lenox Merit Series Furnace (ML180UHE) user manual — SWITCHES TO FAN SPEED AFTER BLOWER
Page 42 · click to enlarge
Page 42
TroubleshootingContinuous Fan Sequence of Operation

CONTINUOUS FAN SEQUENCE OF OPERATION

LED: SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT SEQUENCE.

MANUAL FAN SELECTION MADE AT THERMOSTAT.

CONTROL (G) ENERGIZES SYSTEM FAN AT FAN

SPEED. EAC TERMINAL IS ENERGIZED.

THERMOSTAT CALLS FOR HEAT (W).

NO YES

SYSTEM FAN CONTINUES FAN SPEED WITHOUT

THERMOSTAT CALLS FOR COOLING.

YES NO

INTERRUPTION. EAC TERMINAL REMAIN ON. HUM TERMINAL IS ENERGIZED WITH COMBUSTION

SYSTEM FAN SWITCHED TO COOL SPEED.

AIR BLOWER.

EAC TERM. REMAINS ON.

THERMOSTAT OPENS.

SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 SECOND DELAY. EAC AND HUM TERMINAL REMAIN ON.

MANUAL FAN SELECTION MADE AT THERMOSTAT.

CONTROL (G) ENERGIZES SYSTEM FAN AT FAN

THERMOSTAT OPENS.

SPEED. EAC TERM. ENERGIZED.

HUM. TERMINAL OFF AFTER POST PURGE BY COMBUSTION AIR BLOWER. SYTEM FAN

SWITCHES TO FAN SPEED AFTER BLOWER

OFF DELAY. EAC CONTINUES WITHOUT

INTERRUPTION.

Page 43 of the Lenox Merit Series Furnace (ML180UHE) user manual — HEATING SEQUENCE OF OPERATION
Page 43 · click to enlarge
Page 43
Lenox Merit Series Furnace (ML180UHE) — HEATING SEQUENCE OF OPERATION diagram (page 43)
Fig. 71
Page 44 of the Lenox Merit Series Furnace (ML180UHE) user manual — HEATING SEQUENCE OF OPERATION
Page 44 · click to enlarge
Page 44
Lenox Merit Series Furnace (ML180UHE) — HEATING SEQUENCE OF OPERATION diagram (page 44)
Fig. 72

COMBUSTION SAMPLE CO2% CO PPM 2

Return Duct Temperature Supply Duct Temperature

TEMPERATURE RISE 4 Supply Duct Temperature Return Duct Temperature

Supply External Static Return External Static + Total External Static =

Ask about the Lenox Merit Series Furnace (ML180UHE)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Lenox Merit Series Furnace (ML180UHE)

Be the first to ask — other owners or our team will answer.

Original document

Lenox Merit Series Furnace (ML180UHE) manual PDF

44 pages·2.7 MB·Furnace·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…