
Series 165 Automatic Transfer Switches rated 100, 200, & 230 amps, single phase, 240 V ac Owner’s
ASCO Series 165 Automatic Transfer Switches are Listed under the Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby systems in accordance with the National Electrical Code, NEC/NFPA 70, Article 702. This ATS is for use with 2–wire automatic start generators only.
from high voltages capable of causing shock, burns, or death.
Refer to Application Information 381339–219 to confirm that you have selected the appropriate product for the intended installation.
personal injury.
Each Automatic Transfer Switch (ATS) has rating labels to define the loads and fault current withstand/ closing ratings. Refer to those label on the Transfer Switch for specific values.
of possible equipment damage.
Installation should be performed by a licensed electrician and in accordance with the National Electrical Code (NEC) and all local electrical code requirements. Read and understand all instructions before installing, servicing, or operating. Failure to do so could result in serious personal injuries or property damage.
INJURY or SWITCH DAMAGE Do not exceed the rating label values; it can cause personal in-
jury or serious switch damage.

The Transfer Switch nameplate includes data for each specific ASCO Series 165 ATS. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is also shown below with its elements explained:
Automatic Transfer Switch for use on Standby Systems Cat No 165A2200F3C Ser No 123456 200 A BOM 999999 240 V 60 Hz
enclosure C = Type 1 F = Type 3R
A = solid neutral
poles 2 = 2 lines
ampere rating 100, 200, or 230 amps voltage code F = 240 V AC
381333–163 C 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA 1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca


CONTROLLER
Voltage (nominal) 220–240 V ac Pickup (source acceptable) 204 V ac Dropout (source unacceptable) 180 V ac
Type 1 24” H x 14¼” W x 8” D
(610 mm H x 362 mm W x 203 mm D) Type 3R 25” H x 14¾” W x 8½” D
(635 mm H x 375 mm W x 216 mm D)
Frequency (nominal) alternate (generator) source 60 Hz . Pickup (source acceptable) 57 Hz Dropout (source unacceptable) 54 Hz
Weight Type 1 enclosure 67 lb Type 3R enclosure 82 lb
Operating –4˚ F to +122˚ F(–20˚ C to +50˚ C) . . . Storage –67˚ F to +149˚ F(–55˚ C to +65˚ C)
Start / Stop spdt 5 A max / 300 mA min at 30 V dc max.
terminals accept #22 to #14 AWG
stranded copper wire per terminal
Poles 2 Voltage (nominal) 220–240 V ac single phase
Ignore preferred (utility) source outages 3 sec Ignore alternate (generator) source outages 15 sec Load transfer to alternate (generator) source 15 sec Load retransfer to preferred (utility) source 5 min Generator cooldown period (after load retransfer) 1 min.
Frequency (nominal) 60 Hz Current (depending upon the unit) 100, 200, or 230 amps
Withstand / Close–On Current 10,000 amps RMS Symmetrical amps 240 V ac max. for any circuit breaker, manufacturer, or Type
Repeat time every 14 days Duration 20 minutes
per National Electrical Code, NEC/NFPA 70 100 amp. Transfer Switch power terminals accept wire sizes one #14 to 4/0 AWG AL or CU 200 amp. Transfer Switch power terminals accept wire sizes one #14 to 4/0 AWG CU (copper only) 230 amp. Transfer Switch power terminals accept wire sizes one #14 to 4/0 AWG CU (copper only)
This product is not intended for emergency or life–support systems. If you have more stringent application requirements contact ASCO for other products suitable for critical applications.
ASCO Series 165 Automatic Transfer Switches are Listed under the Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby systems in accordance with theNational Electrical Code, NEC/NFPA 70, Article 702.
The automatic transfer switch helps provide safe connection of the alternate source (generator) to the electrical load after disconnecting the preferred source (utility). It contains a double–throw, electromechanical switching device for inherent isolation of the preferred and alternate sources. This isolation prevents the danger of connecting the utility to the generator which could cause damage or personal injury. The automatic transfer switch’s digital controller provides continuous monitoring of both power sources and a start/stop signal to the generator.
This automatic transfer switch is intended for standby power applications in residential or light commercial use only.
The Series 165 Automatic Transfer
Switch is not for emergency or
life–support systems.

Installation of the ASCO Series 165 automatic transfer switch must be performed by a licensed electrician. It must be installed according to the National Electrical Code and all local electrical code requirements. Refer to the installation drawing and wiring diagram.
CABLE LOOSENING DUE TO SHORT–CIRCUIT. Install
3 cable spacers 1½ in. from terminal lugs to prevent cables from loosening in a short–circuit condition.
CABLE CONNECTIONS (see wiring diagram)
MALFUNCTION or SHORTENED LIFE Protect the unit from construction grit and metal
Prepare the wires for connection as follows: strip the insulation; avoid nicking or ringing the conductors when stripping the cable. Remove surface oxides from conductors by cleaning with a wire brush. Apply electrical joint compound and wipe away excess. Insert prepared cable into lug and tighten the lug to the torque specified on the rating label on the transfer switch.
chips to prevent malfunction or shortened life.
Remove the enclosure cover and inspect the unit for ship– ping damage. If damage is evident do not install the unit. Type 1 enclosure is for indoor use only (refer to local codes for Type 4 use). Mount the automatic transfer switch vertically to a rigid supporting structure. Level all mounting points with flat washers behind the holes to avoid distortion of enclosure.
Connect the preferred source (utility) line 1 and 2 wires to the terminal lugs marked L1 and L5 at the bottom. Connect the alternate source (generator) line 1 and 2 wires to the terminal lugs marked L2 and L6 at the upper middle. Connect the load line 1 and 2 wires to the terminal lugs marked L3 and L7 at the top of the transfer switch. Neutral and ground terminals are provided.
Installation wiring must be performed by a licensed electrician in accordance with the National Electrical Code (NEC) and all local electrical code requirements.
The automatic transfer switch must be protected by suitably sized circuit breakers feeding the preferred and alternate source terminals. The ratings of the circuit breakers must be based on the requirements of the National Electrical Code for its nameplate ampere and short circuit withstandratings. See the wiring diagram provided with the unit.
Before wiring the generator starting contacts refer to the generator manufacturer’s installation manual for require- ments. Make all connections to the controller with the gen- erator battery disconnected. Verify that the ignition switch is in the OFF position. Connect the generator starting con- tacts to the appropriate terminals on terminal block TB7 on the Controller (CP). See the wiring diagram provided with the unit. For wiring convenience terminal block TB7 has a removable plug. Reconnect the plug with terminal screws facing inward.
ELECTROCUTION HAZARD Turn off utility power and turn off the
generator to prevent electrocution
when wiring the transfer switch.
CABLE SPACERS (200 and 230 amp. units)
CONTROLLER DAMAGE. Observe polarity when connecting the generator battery to the controller.
Three cable spacers are included with 200 and 230 ampere size transfer switches. Run the power cables through the cable spacers as shown here and position the cable spacers approximately 1½ inches from the terminal lugs. Use copper cables for 200 and 230 amp. transfer switches.
Refer to wiring diagram. Be sure to reinstall the
TB7 block with terminal screws facing inward.


1 ½ inch approximate from terminal lugs
200 & 230 amp. transfer switches require cable spacers and copper cables
facing inward.

After installing the Series 165 automatic transfer switch perform the following three–part functional test.

ELECTROCUTION – FLASH HAZARD Do not manually operate the transfer
switch until utility and generator are disconnected; open circuit breakers.
transfer switch on utility (preferred source) light
transfer switch on generator

With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers.
weight marked P (preferred) and A (alternate)
This light indicates that the generator is running and that its output voltage and frequency are acceptable. Under typical conditions, the light should come on after about 5 to 10 seconds. If the generator is running and fails to produce the proper voltage and frequency after 60 seconds then a malfunction has occurred (consult the Troubleshooting section).
The Series 165 automatic transfer switch is rated for nominal 240 V ac at 60 Hz (as stated on the nameplate). Verify that both your preferred and alternate sources are also 240 V ac nominal, 60 Hz. See the wiring diagram.
This procedure checks the electrical operation of the automatic transfer switch. If the actual operation does not follow this procedure, consult the Troubleshooting section.
PERSONAL INJURY HAZARD Install front cover before operation.
An electrical system fault could
cause a flash and cause injury.
This completes the Functional Test. Proceed to next page.

utility (preferred source) acceptable light
On the front control display are two push buttons that control the operation of the generator and the automatic transfer switch.
(alternate source) light transfer switch on utility
transfer switch on generator
The load is normally connected to the preferred source (utility) if that source is acceptable. If the preferred source (utility) fails, the following sequence occurs: 1. The UTILITY source acceptable light goes off.
On the front control display are five lights that indicate the status of the sources and the automatic transfer switch.
❍Utility (preferred source) acceptable
(light at the top left of the display)
❍Generator (alternate source) acceptable
(light at the top right of the display)
❍Transfer Switch on utility (preferred source)
(light at the center left of display)
❍Transfer Switch on generator (alt. source)
(light at the center right of display)
❍Automatic Generator Exerciser
(light above button at the right of display)

automatic generator exerciser light
The automatic generator exerciser automatically exercises the generator for 20 minutes once every 14 days. TO SET EXERCISER Press and release the Automatic Generator Exerciser but- ton. After about 8 seconds the exerciser light flashes 14 times to indicate that the exerciser has been set. The number of flashes indicates the number of days until thenext exercisepe- riod (at approximately the same time the button was pressed).
TO DISABLE EXERCISER Press and hold the Automatic Generator Exerciser button until the light above the button goes off (light flashes then goes off). The exerciser is now disabled and the light is off.
TO ENABLE EXERCISER Press and hold the Automatic Generator Exerciser button until the light goes off (light flashes then goes off). Exerciser is now enabled. After about 8 seconds exerciser light flashes 14 times to indicate that the exerciser has been re–enabled.
GENERATOR TEST WITHOUT LOAD TRANSFER
During this test a utility failure is simulated. The generator starts and the load transfers to the generator. Then the load retransfers back to the utility and generator stops.
During the test the generator cranks and starts and the GENERATOR light comes on (if it is acceptable). After running for 20 minutes it stops. Throughout the test the load remains connected to the utility (the automatic transfer switch does not transfer the load to the generator).
cancel the test, press and release the Push to Test button again.
the GENERATOR accept- able light goes off.
(alternate source) light transfer switch on utility
transfer switch on generator
(preferred source) light 7

This troubleshooting guide describes some of the simple causes of problems with the installation of the automatic transfer switch. Troubleshooting beyond the scope of this guide should not be attempted by the installer. A licensed electrician must perform all internal troubleshooting. ASCO can be contacted at 800–937–ASCO or www.asco.com
The automatic transfer switch does not transfer the load to the generator (TRANSFER SWITCH on generator light does not come on).
Do not work on the transfer switch until both the utility and generator are
off. Turn OFF both circuit breakers.
The automatic transfer switch does not transfer the load back to the utility (TRANSFER SWITCH on utility light does not come on). ●Verify that the UTILITY source acceptable light is on. The transfer switch will not retransfer the load to the utility until the utility source is acceptable and the light is on. If light is off, verify that the circuit breaker from the utility feed isON.
Problem 7
Power is connected (UTILITY acceptable light and/or GENERATOR acceptable lights are on) but both TRANSFER SWITCH position lights are off.
The GENERATOR source acceptable light does not go off after the automatic transfer switch retransfers the load back to the utility.
Generator does not crank when the utility source fails or when the Push to Test button is pressed.
Both TRANSFER SWITCH position lights are flashing (this indicates an error condition). * ●Count the number of times the Automatic Generator Exerciser light flashes (repeats after pause). This number is the error code.
to the generator. Service required. 6 Transfer Switch did not transfer the load
Generator cranks but does not start when the utility source fails or when the Push to Test button is pressed.
to the utility. Service required. 7 Controller error. Service required. ●To clear error code, press and release Push to Test button.
* NOTE: These lights will flash only when controller power is available from either of the two power sources.
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.