A Sierra Monitor Company
FS-8700-97 Lutron Machine
Effective for all systems manufactured after May 1, 2001



The Lutron Machine driver allows the FieldServer to transfer data to and from devices over RS- 232 using Lutron eLumen protocol. The FieldServer can emulate either a Server or Client, although the Lutron Machine driver is only available in Client configuration. Any Server drivers are for FieldServer testing purposes only. Max Nodes Supported
Client 1 Only one Lutron Machine driver Client node is able to be connected to a Lutron eLumen panel.
Server 1 One BACNet IP node provides an upstream interface to the Lutron eLumen panel. The Lutron Grafik Machine Zone/Area Machine driver, hereafter simply referred to as the Lutron Machine driver, provides a BACNet IP interface to a Lutron eLumen panel. The driver can be configured to represent zones or areas as used in the Lutron eLumen panel. The FieldServer acts as both Client and Server to provide BACNet objects to an external BACNet Client. In Server mode, the FieldServer collects data from the eLumen panel and holds the data ready for reads from an external BACNet Client. In Client mode, the FieldServer executes pre-defined commands on the eLumen panel, for example, running scripts.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

2.1. Supplied by FieldServer Technologies for this driver
2.2.1. Hardware
Part # Description Lutron eLumen Panel
An external BACnet IP Client to interface to the Lutron Machine on the FieldServer.
BACnet IP Client must be set up to access FieldServer over the network.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

The FieldServer is connected to the Lutron eLumen panel as shown in the connection drawing below:
Configure the eLumen panel according to manufacturer’s instructions.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

120V 15A Dedicated Control Feed
Rx Tx Rx Tx
Ethernet EIA232 USB EIA485
LUTRON ELUMEN RS-485
CONNECTION DIAGRAM
BASE NAME: FILE NAME: FS-T28700-84 .VSD
DATE: 11/12/04 BY: MC
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Lutron eLumen panel.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Lutron Machine communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.
Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters
Float, Bit, UInt16, SInt16, Packed_Bit, Byte, Packed_Byte, Swapped_Byte
Data_Array_Format Provide data format. Each Data Array can only take on one format.
Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.
Example // Data Arrays Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length Binary_Output, Bit, 512 Binary_Input, Bit, 512 Analog_Output, Uint16, 512 Analog_Input, Uint16, 512
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Section Title Data_Arrays · Data_Array_Length · 1-10,000


Specify which port the device is connected to the FieldServer
Protocol Specify protocol used eLumen Baud* Specify baud rate 9600 Parity* Specify parity None Data_Bits* Specify data bits 8 Stop_Bits* Specify stop bits 1
Poll _Delay* Time between internal polls 0-32000 seconds, 1 second
// Client Side Connections Connections Port, Protocol, Baud, Parity, Handshaking, Poll_Delay P1, eLumen, 9600, None, None, 0.100s

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com


Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters
The eLumen processor address. Only decimal values are allowed: e.g. 11 hex must be entered as 17.
Connection Specify which port the device is connected to the FieldServer P1-P8, R1-R21
Node_type Specifies the eLumen command and data format Hex, decimal

// Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Port, Node_Type LUT_GRF6_0, 17, eLumen, P1, Hex


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Column Title Function Legal Values area_status sys_var_val_bin sys_var_val Zone Machine: run_script_AB zone_intensity fade_zone run_script_multi zone_intensity sys_var_val_bin sys_var_val
Name of Data Array that contains a list of parameters needed to execute the command.
A Data Array name.
The offset into the DA_Lut_List Data Array from where the list data is to be used.
0 to the maximum offset into the DA_Lut_List Data Array.
Name of Data Array that contains parameters needed to execute the command.
A Data Array name.
0 to the maximum offset into the DA_Lut_Parms Data Array. Area GRAFIK system area number 0 – 511 Sys_var GRAFIK system variable number 0 – 65535 Zone GRAFIK system zone number 0 – 511
The offset into the DA_Lut_Parms Data Array where the driver will retrieve the parameters.
Length of Map Descriptor. The length is an indication of the number of data elements this Map Descriptor is responsible for updating. It is used in the overall points calculation of the FieldServer.
See example Map Descriptors for individual lengths per Map Descriptor.
The length of the Data Array specified under DA_Lut_List when used with Grafik command: run_script_multi
Column Title Function Legal Values
Scan_Interval Rate at which data is polled ≥0.001s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

A write to the Binary Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of two scripts on the
eLumen panel. The script numbers corresponding to binary inactive (0) and active (1) are specified in the Data Array specified by

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length
Run_Script_0, Binary_Output, 0, AWT, LUT_GRF6_0, run_script_AB, Script_list_BO, 0, 512
SMD00_BO, Binary_Output, 0, Server, Virtual_BCU_11, BO, 1, 512, 0
Script_list_BO , Uint16 , 1 , 0 Script_list_BO , Uint16 , 2 , 1
Script_list_BO , Uint16 , 3 , 2 Script_list_BO , Uint16 , 4 , 3
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
The Data Array specified under “DA_Lut_List” must be preloaded with script numbers as shown below:
“DA_Lut_List” from offset specified by “DA_Lut_List_Offset”. Script numbers range from 0 to 65535.
// ScriptA in even locations, ScriptB in uneven locations, values in Preload_Data_Value
// ScriptB will be run when writing non-zero into the object ID
// ScriptA will be run when writing zero into the Object ID
// All values are in decimal (0 - 65535)
// Binary Output Scripts Setup
// Binary Output Object ID 1
// Binary Output Object ID 2
//================================================================================ · Preloads · //

A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the relay state for the given zone.
BACNet object presenting Binary Output is inactive if the intensity is zero and active if the intensity is non-zero. Zone numbers range
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The
start zone number is specified under the “Zone” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two
series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as
The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the value of zone intensity. The value of each

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Zone_int_0, Binary_Input, 0, ARCO, LUT_GRF6_0, zone_intensity, 0, 512
SMD00_BI, Binary_Input, 0, Server, Virtual_BCU_11, BI, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
RDBC Map Descriptors with the same length.
from 0 to 511

A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the scene-on state for the given
area. The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the scene-on state for the given area. The
value returned by the BACNet object is inactive (0) if the off scene is selected and active (1) if any other scene is selected. The off
The ARCO function is the same as RDBC except that the Map Descriptor length is taken as the number of areas to poll. The start
area number is specified under the “Area” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two series
of area numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as RDBC Map

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, Area, DA_Lut_List, DA_Lut_List_Offset, Length

Area_sts_0, Binary_Input, 0, ARCO, LUT_GRF6_0, area_sts_offscene, 0, off_scene, 0, 512
SMD00_BI, Binary_Input, 0, Server, Virtual_BCU_11, BI, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
scene numbers range from 0 to 65535 and are preloaded in the Data Array specified under “DA_Lut_List”.
The Data Array specified under “DA_Lut_List” must be preloaded with scene numbers as shown below:
// Insert the off-scene number in the preload_data_value field
// All values are in decimal ( 0 - 65535 )
Descriptors with the same length.
// Binary Input Scenes Setup
// Binary Input Object ID 1
// Binary Input Object ID 2
//================================================================================ · Preloads · //

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on
The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array.
SMD000_AO, Analog_Output, 0, Server, Virtual_BCU_11, AO, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command a zone on the Lutron eLumen
The zone field must be used to indicate the start zone number that will be associated with the first element of the Data Array
specified under Data_Array_Name . Zone numbers increase with the Length field in association with increasing offset into the Data

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, zone, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Fade_to_lvl_0, Analog_Output, 0, AWT, LUT_GRF6_0, fade_zone, 0, Zone_pars_AO1, 0, 512
SMD000_AO, Analog_Output, 0, Server, Virtual_BCU_11, AO, 1, 512, 0
Zone_pars_AO1 , Uint16 , 0 , 0 Zone_pars_AO1 , Uint16 , 1 , 1
Zone_pars_AO1 , Uint16 , 2 , 2 Zone_pars_AO1 , Uint16 , 3 , 3
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Fade and Delay times per zone must be preloaded into the Data Array specified under “DA_Lut_Parms”:
panel to the written intensity. Intensities are written as a percentage value (0 to 100%).
// Fade time in even locations, Delay time in uneven locations
// Fill in time values under Preload_Data_Value
// All values are in decimal ( 0 - 65535 )
// Analog Output1 Settings Setup
// Analog Output1 Object ID 1
// Analog Output1 Object ID 2
Array.
//================================================================================ · Preloads · //

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts on the
Lutron eLumen panel. The value written into the Analog Output Data Array is used as an offset into the Data Array defined under
The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length, Multi_Scripts_Length
Run_script_512, Analog_Output, 512, AWT, LUT_GRF6_0, run_script_multi, Scr_lst_AO2_512, 0, 1, 10
SMD512_AO, Analog_Output, 512, Server, Virtual_BCU_11, AO, 513, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
4.4.9. Map Descriptor Example 6 - Analog Output 2 (Zone and Area Machine)
Descriptor per object must be defined with a Multi_Scripts_Length value of 1 or greater.
“DA_Lut_List” to retrieve a script number. Script numbers range from 0 to 65535.

Data_Array_Name , Preload_Data_Format , Preload_Data_Value , Location
The script numbers per BACNet object element need to be preloaded into the Data Arrays defined under “DA_Lut_List”.
Scr_lst_AO2_512 , Uint16 , 100 , 0 Scr_lst_AO2_512 , Uint16 , 200 , 1 Scr_lst_AO2_512 , Uint16 , 300 , 2 Scr_lst_AO2_512 , Uint16 , 400 , 3 Scr_lst_AO2_512 , Uint16 , 500 , 4 Scr_lst_AO2_512 , Uint16 , 600 , 5 Scr_lst_AO2_512 , Uint16 , 700 , 6 Scr_lst_AO2_512 , Uint16 , 800 , 7 Scr_lst_AO2_512 , Uint16 , 900 , 8 Scr_lst_AO2_512 , Uint16 , 65000 , 9
Scr_lst_AO2_513 , Uint16 , 101 , 0 Scr_lst_AO2_513 , Uint16 , 201 , 1 Scr_lst_AO2_513 , Uint16 , 301 , 2 Scr_lst_AO2_513 , Uint16 , 401 , 3 Scr_lst_AO2_513 , Uint16 , 501 , 4 Scr_lst_AO2_513 , Uint16 , 601 , 5 Scr_lst_AO2_513 , Uint16 , 701 , 6 Scr_lst_AO2_513 , Uint16 , 801 , 7 Scr_lst_AO2_513 , Uint16 , 901 , 8 Scr_lst_AO2_513 , Uint16 , 65001 , 9
// Analog Output2 Object ID 514
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
// Specify up to 10 scripts for each Object ID by editing Preload_Data_Value
// All values are in decimal ( 0 - 65535 )
// Analog Output2 Settings Setup
// Analog Output2 Object ID 513
Preloads · //==================================================================== · //

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the last scene selected in a
given area on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of areas to poll. The
start area number is specified under the “Area” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two
series of area numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC


SMD00_AI, Analog_Input, 0, Server, Virtual_BCU_11, AI, 1, 1, 0, 0, 100, 0, 100
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
// Insert a first available scene number under the Data_Array_High_Scale field for each Object ID or
// use the scale fields as desired to scale scene numbers.
// All values are in decimal ( 0 - 65535 )
Map Descriptors with the same length.
The last scene value may be scaled:
// Analog Input Settings Setup
// Object IDs are contiguous
scene numbers.

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given
zone is set on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The
start zone number is specified under the “zone” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two
series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

zone intensities. The intensity value returned is scaled to a percentage value (0 to 100%). Zone numbers range from 0 to 511.
Zone_inta_0, Analog_Input, 0, ARCO, LUT_GRF6_0, zone_intensity, 0, 512
SMD00_AI, Analog_Input, 0, Server, Virtual_BCU_11, AI, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Map Descriptors with the same length.

A write to the Multistate Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts. The
multiple scripts are specified in the Data Array defined under “DA_Lut_List”. The value written into the Multistate Output Data Array
is used as the offset into the Data Array defined under “DA_Lut_List” to retrieve a script number from the Data Array. Script numbers
The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default,
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length, Multi_Scripts_Length
Run_scriptms_0, MultiSt_Output, 0, AWT, LUT_GRF6_0, run_script_multi, Scr_lst_MSO_0, 0, 1, 10
SMD00_MO, MultiSt_Output, 0, Server, Virtual_BCU_11, MO, 1, 512, 0,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Descriptor per object must be defined with a Multi_Scripts_Length value of one or greater.
range from 0 to 65535.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Data_Array_Name Preload_Data_Format Preload_Data_Value Location
Scr_lst_MSO_0 , Uint16 , 110 , 0 Scr_lst_MSO_0 , Uint16 , 210 , 1 Scr_lst_MSO_0 , Uint16 , 310 , 2 Scr_lst_MSO_0 , Uint16 , 410 , 3 Scr_lst_MSO_0 , Uint16 , 510 , 4 Scr_lst_MSO_0 , Uint16 , 610 , 5 Scr_lst_MSO_0 , Uint16 , 710 , 6 Scr_lst_MSO_0 , Uint16 , 810 , 7 Scr_lst_MSO_0 , Uint16 , 910 , 8 Scr_lst_MSO_0 , Uint16 , 65010 , 9
Scr_lst_MSO_1 , Uint16 , 120 , 0 Scr_lst_MSO_1 , Uint16 , 220 , 1 Scr_lst_MSO_1 , Uint16 , 320 , 2 Scr_lst_MSO_1 , Uint16 , 420 , 3 Scr_lst_MSO_1 , Uint16 , 520 , 4 Scr_lst_MSO_1 , Uint16 , 620 , 5 Scr_lst_MSO_1 , Uint16 , 720 , 6 Scr_lst_MSO_1 , Uint16 , 820 , 7 Scr_lst_MSO_1 , Uint16 , 920 , 8 Scr_lst_MSO_1 , Uint16 , 65020 , 9
// Multistate Output Object ID 1
// Multistate Output Object ID 2
The scripts per object element must be preloaded into the Data Array defined under “DA_Lut_List”:
// Specify up to 10 scripts for each Object ID by editing Preload_Data_Value
// All values are in decimal ( 0 - 65535 )
// Multistate Output Scripts Setup
Preloads · //===================================================================== · //

A read from the Binary Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a
system variable in the Lutron eLumen panel. The value returned is inactive (0) if the system variable is zero and active (1) if
non-zero. The Lutron Machine Map Descriptor regularly polls the Lutron panel to retrieve the system variable values. A write
The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of system variables to
poll. The start system variable number is specified under the “Sys_Var” Map Descriptor field. More than one ARCO Map Descriptor
may be used to poll two series of system variable numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1


Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default
Zone_var_0, Binary_Value, 0, ARCO, LUT_GRF6_0, sys_var_val_bin, 0, 512
to the Binary Value Data Array will set the system variable to 255 on active (1) write or to zero on inactive (0) write.
SMD00_BV, Binary_Value, 0, Server, Virtual_BCU_11, BV, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
fullfil the same function as RDBC Map Descriptors with the same length.

A read from the Analog Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system
variable in the Lutron eLumen panel. The variable values range from 0 to 255. The Lutron Machine Map Descriptors are regularly
updated with system variable values from the active Binary Value Map Descriptors. A write to the Analog Value Data Array will set
The Passive_Client function is used to prevent double-polling the Lutron eLumen panel for system variables. The Analog Value Map
Descriptors should be set up identical to the Binary Value Map Descriptors in terms of the Sys_Var and Length fields to ensure

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Zone_vara_0, Analog_Value, 0, Passive_Client, LUT_GRF6_0, sys_var_val, 0, 512
SMD00_AV, Analog_Value, 0, Server, Virtual_BCU_11, AV, 1, 512, 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
system variable values will be stored correctly.
the system variable to the written value.

Date Resp Format Driver
Doc. Rev. Comment
Ver.
07/04/03 DR 1.00 0 Created 07/08/03 DR 1.01 1 Updated driver version, SPR2912 09/05/03 DR 1.02 1 Updated with ARCO Map Descriptor usage 09/09/03 DR 1.02 2 Updated with passive Client mapdescs
10/15/03 MF 1.02 3 Updated according to DUR0215. Updated formatting 1/21/04 JD 1.02 4 Releasing 3/22/04 DR 1.02 5 Updated for release
3/24/04 MC MC 1.02 6 Updated formatting. Added new revision table. Changed page setup to letter. 6/10/04 JD 1.02 7 Releasing
11/3/04 Meg Meg 1.03 0 Changed references to Grafik to eLumen – DUR0484.
Connection diagrams added for RS-232 and RS-485. Modifications to scope of supply table. Table formatting. Map Descriptor example titles added. Added RS-485 compatibility. 4/12/05 JD JD 1.03 1 Releasing 4/27/05 JD JD 1.03 2 Corrected page numbering. Releasing.