FieldServer FS-8700-97

24 pages·205 KB·Computer Drive·PDF·ENDEFRITNLJA
FieldServer FS-8700-97
Table of Contents 40 sections Driver Manual (Supplement to the FieldServer Instruction Manual) · FS-8700-97 Lutron Machine · APPLICABILITY & EFFECTIVITY · Effective for all systems manufactured after May 1, 2001 · … ShowHide
Driver Manual (Supplement to the FieldServer Instruction Manual)p.1FS-8700-97 Lutron Machinep.1APPLICABILITY & EFFECTIVITYp.1Effective for all systems manufactured after May 1, 2001p.11. Lutron Machine Descriptionp.3FieldServer Mode Nodes Commentsp.32. Driver Scope of Supplyp.42.1. Supplied by FieldServer Technologies for this driverp.42.2. Provided by the Supplier of 3 rd Party Equipmentp.42.2.1. Hardwarep.42.2.2. Required 3 rd Party Softwarep.42.2.3. Required 3 rd Party Configurationp.43. Hardware Connectionsp.5FS-B2010p.6LUTRON ELUMEN RS-485p.6CONNECTION DIAGRAMp.6BASE NAME: FILE NAME: FS-T28700-84 .VSDp.6DATE: 11/12/04 BY: MCp.64. Configuring the FieldServer as a Lutron Machine Clientp.74.1. Data Arrays/Descriptorsp.7Column Title Function Legal Valuesp.74.2. Client Side Connection Descriptionsp.8Examplep.84.3. Client Side Node Descriptorsp.94.4.1. FieldServer Related Map Descriptor Parametersp.94.4.2. Driver Related Map Descriptor Parametersp.94.4.3. Timing Parametersp.104.4.4. Map Descriptor Example 1 - Binary Output (Zone and Area Machine)p.114.4.5. Map Descriptor Example 2 - Binary Input (Zone Machine)p.124.4.6. Map Descriptor Example 3 - Binary Input (Area Machine)p.134.4.7. Map Descriptor Example 4 - Analog Output 1 (Area Machine)p.144.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine)p.154.4.10. Map Descriptor Example 7 - Analog Input (Area Machine)p.184.4.11. Map Descriptor Example 8 - Analog Input (Zone Machine)p.194.4.12. Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)p.204.4.13. Map Descriptor Example 10 - Binary Value (Zone and Area Machine)p.224.4.14. Map Descriptor Example 11 - Analog Value (Zone and Area Machine)p.23Appendix A. Revision Historyp.24Date Resp Format Driverp.24Doc. Rev. Commentp.24
Page 1 of the FieldServer FS-8700-97 user manual — APPLICABILITY & EFFECTIVITY
Page 1 · click to enlarge
Page 1
FieldServer FS-8700-97 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 1)
Fig. 1 · Driver Manual (Supplement to the FieldServer Instruc…

A Sierra Monitor Company

Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-97 Lutron Machine

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Page 2 of the FieldServer FS-8700-97 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer FS-8700-97 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 of the FieldServer FS-8700-97 user manual — FieldServer Mode Nodes Comments
Page 3 · click to enlarge
Page 3

1. Lutron Machine Description

The Lutron Machine driver allows the FieldServer to transfer data to and from devices over RS- 232 using Lutron eLumen protocol. The FieldServer can emulate either a Server or Client, although the Lutron Machine driver is only available in Client configuration. Any Server drivers are for FieldServer testing purposes only. Max Nodes Supported

FieldServer Mode Nodes Comments

Client 1 Only one Lutron Machine driver Client node is able to be connected to a Lutron eLumen panel.

Server 1 One BACNet IP node provides an upstream interface to the Lutron eLumen panel. The Lutron Grafik Machine Zone/Area Machine driver, hereafter simply referred to as the Lutron Machine driver, provides a BACNet IP interface to a Lutron eLumen panel. The driver can be configured to represent zones or areas as used in the Lutron eLumen panel. The FieldServer acts as both Client and Server to provide BACNet objects to an external BACNet Client. In Server mode, the FieldServer collects data from the eLumen panel and holds the data ready for reads from an external BACNet Client. In Client mode, the FieldServer executes pre-defined commands on the eLumen panel, for example, running scripts.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 4 of the FieldServer FS-8700-97 user manual — 2.2.3. Required 3 rd Party Configuration
Page 4 · click to enlarge
Page 4

2. Driver Scope of Supply

2.1. Supplied by FieldServer Technologies for this driver

FieldServer TechnologiesDescription PART # FS-8915-10UTP cable (7 foot) for RS-232 use FS-8917-02RJ45 to DB9F connector adapter FS-8700-97Driver Manual.

2.2. Provided by the Supplier of 3 rd Party Equipment

2.2.1. Hardware

Part # Description Lutron eLumen Panel

2.2.2. Required 3 rd Party Software

An external BACnet IP Client to interface to the Lutron Machine on the FieldServer.

2.2.3. Required 3 rd Party Configuration

BACnet IP Client must be set up to access FieldServer over the network.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 5 of the FieldServer FS-8700-97 user manual — 3. Hardware Connections
Page 5 · click to enlarge
Page 5

3. Hardware Connections

The FieldServer is connected to the Lutron eLumen panel as shown in the connection drawing below:

Configure the eLumen panel according to manufacturer’s instructions.

FieldServer FS-8700-97 — 3. Hardware Connections diagram (page 5)
Fig. 2 · 3. Hardware Connections
FUNCTIONFROMTOCOLOUR RXRJ45-01DB9M-02WHITE CTSRJ45-02DB9M-08BROWN DSRRJ45-03DB9M-06YELLOW GNDRJ45-04DB9M-05GREEN GNDRJ45-05RED DTRRJ45-06DB9M-04BLACK RTSRJ45-07DB9M-07ORANGE TXRJ45-08DB9M-03BLUE

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 6 of the FieldServer FS-8700-97 user manual — FS-B2010
Page 6 · click to enlarge
Page 6

120V 15A Dedicated Control Feed

Rx Tx Rx Tx

Ethernet EIA232 USB EIA485

FS-B2010

LUTRON ELUMEN RS-485

CONNECTION DIAGRAM

BASE NAME: FILE NAME: FS-T28700-84 .VSD

DATE: 11/12/04 BY: MC

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 11 more labels / short text on this page
Wallstation link · To control stations · Aux Link (RS-485) · eLumen Processor · User Interface link · Dimmer panel link · To dimmer panels · Inter-processor link · Power OK Serial · + - · (408)-262-2299
Page 7 of the FieldServer FS-8700-97 user manual — Column Title Function Legal Values
Page 7 · click to enlarge
Page 7

4. Configuring the FieldServer as a Lutron Machine Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Lutron eLumen panel.

4.1. Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Lutron Machine communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Column Title Function Legal Values

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters

Float, Bit, UInt16, SInt16, Packed_Bit, Byte, Packed_Byte, Swapped_Byte

Data_Array_Format Provide data format. Each Data Array can only take on one format.

Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.

Example // Data Arrays Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length Binary_Output, Bit, 512 Binary_Input, Bit, 512 Analog_Output, Uint16, 512 Analog_Input, Uint16, 512

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Section Title Data_Arrays · Data_Array_Length · 1-10,000

Page 8 of the FieldServer FS-8700-97 user manual — Example
Page 8 · click to enlarge
Page 8

4.2. Client Side Connection Descriptions

FieldServer FS-8700-97 — 4.2. Client Side Connection Descriptions diagram (page 8)
Fig. 3 · 4.2. Client Side Connection Descriptions

Specify which port the device is connected to the FieldServer

Protocol Specify protocol used eLumen Baud* Specify baud rate 9600 Parity* Specify parity None Data_Bits* Specify data bits 8 Stop_Bits* Specify stop bits 1

Poll _Delay* Time between internal polls 0-32000 seconds, 1 second

Example

// Client Side Connections Connections Port, Protocol, Baud, Parity, Handshaking, Poll_Delay P1, eLumen, 9600, None, None, 0.100s

FieldServer FS-8700-97 — Example diagram (page 8)
Fig. 4 · Example

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 9 of the FieldServer FS-8700-97 user manual — 4.4.2. Driver Related Map Descriptor Parameters
Page 9 · click to enlarge
Page 9

4.3. Client Side Node Descriptors

FieldServer FS-8700-97 — 4.3. Client Side Node Descriptors diagram (page 9)
Fig. 5 · 4.3. Client Side Node Descriptors

Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters

The eLumen processor address. Only decimal values are allowed: e.g. 11 hex must be entered as 17.

Connection Specify which port the device is connected to the FieldServer P1-P8, R1-R21

Node_type Specifies the eLumen command and data format Hex, decimal

Example

FieldServer FS-8700-97 — Example diagram (page 9)
Fig. 6 · Example

// Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Port, Node_Type LUT_GRF6_0, 17, eLumen, P1, Hex

4.4.1. FieldServer Related Map Descriptor Parameters

Column TitleFunctionLegal Values Map Descriptor Name _ _Name of this Map DescriptorUp to 32 alphanumeric characters Data Array Name _ _Name of Data Array where data is to be stored in the FieldServerOne of the Data Array names from “Data Array” section above Data Array Offset _ _Starting location in Data Array0 to maximum specified in “Data Array” section above FunctionFunction of Client Map DescriptorARCO, AWT, RDBC, Passive Client
FieldServer FS-8700-97 — 4.4.1. FieldServer Related Map Descriptor Parameters diagram (page 9)
Fig. 7 · 4.4.1. FieldServer Related Map Descriptor Parameters

4.4.2. Driver Related Map Descriptor Parameters

Column TitleFunctionLegal Values Node Name _Name of Node to fetch data fromOne of the node names specified in “Client Node Descriptor” above Grafik Command _Specifies the command that will be sent to the eLumen.Area Machine: run script AB _ _ area sts offscene _ _ sel scene in area _ _ _ run script multi
FieldServer FS-8700-97 — 4.4.2. Driver Related Map Descriptor Parameters diagram (page 9)
Fig. 8 · 4.4.2. Driver Related Map Descriptor Parameters

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 10 of the FieldServer FS-8700-97 user manual — 4.4.3. Timing Parameters
Page 10 · click to enlarge
Page 10

Column Title Function Legal Values area_status sys_var_val_bin sys_var_val Zone Machine: run_script_AB zone_intensity fade_zone run_script_multi zone_intensity sys_var_val_bin sys_var_val

Name of Data Array that contains a list of parameters needed to execute the command.

A Data Array name.

The offset into the DA_Lut_List Data Array from where the list data is to be used.

0 to the maximum offset into the DA_Lut_List Data Array.

Name of Data Array that contains parameters needed to execute the command.

A Data Array name.

0 to the maximum offset into the DA_Lut_Parms Data Array. Area GRAFIK system area number 0 – 511 Sys_var GRAFIK system variable number 0 – 65535 Zone GRAFIK system zone number 0 – 511

The offset into the DA_Lut_Parms Data Array where the driver will retrieve the parameters.

Length of Map Descriptor. The length is an indication of the number of data elements this Map Descriptor is responsible for updating. It is used in the overall points calculation of the FieldServer.

See example Map Descriptors for individual lengths per Map Descriptor.

The length of the Data Array specified under DA_Lut_List when used with Grafik command: run_script_multi

1. 10,000

4.4.3. Timing Parameters

Column Title Function Legal Values

Scan_Interval Rate at which data is polled ≥0.001s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 6 more labels / short text on this page
DA_Lut_List · DA_Lut_List_Offset · DA_Lut_Parms · DA_Lut_Parms_Offset · Length · Multi_Scripts_Length
Page 11 of the FieldServer FS-8700-97 user manual — 4.4.4. Map Descriptor Example 1 - Binary Output (Zone and Area Machine)
Page 11 · click to enlarge
Page 11

A write to the Binary Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of two scripts on the

eLumen panel. The script numbers corresponding to binary inactive (0) and active (1) are specified in the Data Array specified by

FieldServer FS-8700-97 — 4.4.4. Map Descriptor Example 1 - Binary Output (Zone and Area Machine) diagram (page 11)
Fig. 9 · 4.4.4. Map Descriptor Example 1 - Binary Output (Zon…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.4. Map Descriptor Example 1 - Binary Output (Zone and Area Machine) diagram (page 11)
Fig. 10 · 4.4.4. Map Descriptor Example 1 - Binary Output (Zon…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length

Run_Script_0, Binary_Output, 0, AWT, LUT_GRF6_0, run_script_AB, Script_list_BO, 0, 512

SMD00_BO, Binary_Output, 0, Server, Virtual_BCU_11, BO, 1, 512, 0

Script_list_BO , Uint16 , 1 , 0 Script_list_BO , Uint16 , 2 , 1

Script_list_BO , Uint16 , 3 , 2 Script_list_BO , Uint16 , 4 , 3

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

The Data Array specified under “DA_Lut_List” must be preloaded with script numbers as shown below:

4.4.4. Map Descriptor Example 1 - Binary Output (Zone and Area Machine)

“DA_Lut_List” from offset specified by “DA_Lut_List_Offset”. Script numbers range from 0 to 65535.

// ScriptA in even locations, ScriptB in uneven locations, values in Preload_Data_Value

// ScriptB will be run when writing non-zero into the object ID

// ScriptA will be run when writing zero into the Object ID

// All values are in decimal (0 - 65535)

// Binary Output Scripts Setup

// Binary Output Object ID 1

// Binary Output Object ID 2

//================================================================================ · Preloads · //

Page 12 of the FieldServer FS-8700-97 user manual — 4.4.5. Map Descriptor Example 2 - Binary Input (Zone Machine)
Page 12 · click to enlarge
Page 12

A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the relay state for the given zone.

BACNet object presenting Binary Output is inactive if the intensity is zero and active if the intensity is non-zero. Zone numbers range

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The

start zone number is specified under the “Zone” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two

series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as

The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the value of zone intensity. The value of each

FieldServer FS-8700-97 — 4.4.5. Map Descriptor Example 2 - Binary Input (Zone Machine) diagram (page 12)
Fig. 11 · 4.4.5. Map Descriptor Example 2 - Binary Input (Zone…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.5. Map Descriptor Example 2 - Binary Input (Zone Machine) diagram (page 12)
Fig. 12 · 4.4.5. Map Descriptor Example 2 - Binary Input (Zone…

Zone_int_0, Binary_Input, 0, ARCO, LUT_GRF6_0, zone_intensity, 0, 512

SMD00_BI, Binary_Input, 0, Server, Virtual_BCU_11, BI, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.5. Map Descriptor Example 2 - Binary Input (Zone Machine)

RDBC Map Descriptors with the same length.

from 0 to 511

Page 13 of the FieldServer FS-8700-97 user manual — 4.4.6. Map Descriptor Example 3 - Binary Input (Area Machine)
Page 13 · click to enlarge
Page 13

A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the scene-on state for the given

area. The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the scene-on state for the given area. The

value returned by the BACNet object is inactive (0) if the off scene is selected and active (1) if any other scene is selected. The off

The ARCO function is the same as RDBC except that the Map Descriptor length is taken as the number of areas to poll. The start

area number is specified under the “Area” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two series

of area numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as RDBC Map

FieldServer FS-8700-97 — 4.4.6. Map Descriptor Example 3 - Binary Input (Area Machine) diagram (page 13)
Fig. 13 · 4.4.6. Map Descriptor Example 3 - Binary Input (Area…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, Area, DA_Lut_List, DA_Lut_List_Offset, Length

FieldServer FS-8700-97 — 4.4.6. Map Descriptor Example 3 - Binary Input (Area Machine) diagram (page 13)
Fig. 14 · 4.4.6. Map Descriptor Example 3 - Binary Input (Area…

Area_sts_0, Binary_Input, 0, ARCO, LUT_GRF6_0, area_sts_offscene, 0, off_scene, 0, 512

SMD00_BI, Binary_Input, 0, Server, Virtual_BCU_11, BI, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

scene numbers range from 0 to 65535 and are preloaded in the Data Array specified under “DA_Lut_List”.

The Data Array specified under “DA_Lut_List” must be preloaded with scene numbers as shown below:

4.4.6. Map Descriptor Example 3 - Binary Input (Area Machine)

// Insert the off-scene number in the preload_data_value field

// All values are in decimal ( 0 - 65535 )

Descriptors with the same length.

// Binary Input Scenes Setup

// Binary Input Object ID 1

// Binary Input Object ID 2

//================================================================================ · Preloads · //

Page 14 of the FieldServer FS-8700-97 user manual — 4.4.7. Map Descriptor Example 4 - Analog Output 1 (Area Machine)
Page 14 · click to enlarge
Page 14

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on

The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified

FieldServer FS-8700-97 — 4.4.7. Map Descriptor Example 4 - Analog Output 1 (Area Machine) diagram (page 14)
Fig. 15 · 4.4.7. Map Descriptor Example 4 - Analog Output 1 (A…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.7. Map Descriptor Example 4 - Analog Output 1 (Area Machine) diagram (page 14)
Fig. 16 · 4.4.7. Map Descriptor Example 4 - Analog Output 1 (A…

under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array.

SMD000_AO, Analog_Output, 0, Server, Virtual_BCU_11, AO, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511

4.4.7. Map Descriptor Example 4 - Analog Output 1 (Area Machine)

Page 15 of the FieldServer FS-8700-97 user manual — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine)
Page 15 · click to enlarge
Page 15

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command a zone on the Lutron eLumen

The zone field must be used to indicate the start zone number that will be associated with the first element of the Data Array

specified under Data_Array_Name . Zone numbers increase with the Length field in association with increasing offset into the Data

FieldServer FS-8700-97 — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine) diagram (page 15)
Fig. 17 · 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Z…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine) diagram (page 15)
Fig. 18 · 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Z…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, zone, DA_Lut_Parms, DA_Lut_Parms_Offset, Length

Fade_to_lvl_0, Analog_Output, 0, AWT, LUT_GRF6_0, fade_zone, 0, Zone_pars_AO1, 0, 512

SMD000_AO, Analog_Output, 0, Server, Virtual_BCU_11, AO, 1, 512, 0

Zone_pars_AO1 , Uint16 , 0 , 0 Zone_pars_AO1 , Uint16 , 1 , 1

Zone_pars_AO1 , Uint16 , 2 , 2 Zone_pars_AO1 , Uint16 , 3 , 3

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Fade and Delay times per zone must be preloaded into the Data Array specified under “DA_Lut_Parms”:

4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine)

panel to the written intensity. Intensities are written as a percentage value (0 to 100%).

// Fade time in even locations, Delay time in uneven locations

// Fill in time values under Preload_Data_Value

// All values are in decimal ( 0 - 65535 )

// Analog Output1 Settings Setup

// Analog Output1 Object ID 1

// Analog Output1 Object ID 2

Array.

//================================================================================ · Preloads · //

Page 16 of the FieldServer FS-8700-97 user manual — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine)
Page 16 · click to enlarge
Page 16

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts on the

Lutron eLumen panel. The value written into the Analog Output Data Array is used as an offset into the Data Array defined under

The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map

FieldServer FS-8700-97 — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine) diagram (page 16)
Fig. 19 · 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Z…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length, Multi_Scripts_Length

Run_script_512, Analog_Output, 512, AWT, LUT_GRF6_0, run_script_multi, Scr_lst_AO2_512, 0, 1, 10

SMD512_AO, Analog_Output, 512, Server, Virtual_BCU_11, AO, 513, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.9. Map Descriptor Example 6 - Analog Output 2 (Zone and Area Machine)

Descriptor per object must be defined with a Multi_Scripts_Length value of 1 or greater.

“DA_Lut_List” to retrieve a script number. Script numbers range from 0 to 65535.

Page 17 of the FieldServer FS-8700-97 user manual — 4.4.8. Map Descriptor Example 5 - Analog Output 1 (Zone Machine)
Page 17 · click to enlarge
Page 17

Data_Array_Name , Preload_Data_Format , Preload_Data_Value , Location

The script numbers per BACNet object element need to be preloaded into the Data Arrays defined under “DA_Lut_List”.

Scr_lst_AO2_512 , Uint16 , 100 , 0 Scr_lst_AO2_512 , Uint16 , 200 , 1 Scr_lst_AO2_512 , Uint16 , 300 , 2 Scr_lst_AO2_512 , Uint16 , 400 , 3 Scr_lst_AO2_512 , Uint16 , 500 , 4 Scr_lst_AO2_512 , Uint16 , 600 , 5 Scr_lst_AO2_512 , Uint16 , 700 , 6 Scr_lst_AO2_512 , Uint16 , 800 , 7 Scr_lst_AO2_512 , Uint16 , 900 , 8 Scr_lst_AO2_512 , Uint16 , 65000 , 9

Scr_lst_AO2_513 , Uint16 , 101 , 0 Scr_lst_AO2_513 , Uint16 , 201 , 1 Scr_lst_AO2_513 , Uint16 , 301 , 2 Scr_lst_AO2_513 , Uint16 , 401 , 3 Scr_lst_AO2_513 , Uint16 , 501 , 4 Scr_lst_AO2_513 , Uint16 , 601 , 5 Scr_lst_AO2_513 , Uint16 , 701 , 6 Scr_lst_AO2_513 , Uint16 , 801 , 7 Scr_lst_AO2_513 , Uint16 , 901 , 8 Scr_lst_AO2_513 , Uint16 , 65001 , 9

// Analog Output2 Object ID 514

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

// Specify up to 10 scripts for each Object ID by editing Preload_Data_Value

// All values are in decimal ( 0 - 65535 )

// Analog Output2 Settings Setup

// Analog Output2 Object ID 513

Preloads · //==================================================================== · //

Page 18 of the FieldServer FS-8700-97 user manual — 4.4.10. Map Descriptor Example 7 - Analog Input (Area Machine)
Page 18 · click to enlarge
Page 18

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the last scene selected in a

given area on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of areas to poll. The

start area number is specified under the “Area” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two

series of area numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC

FieldServer FS-8700-97 — 4.4.10. Map Descriptor Example 7 - Analog Input (Area Machine) diagram (page 18)
Fig. 20 · 4.4.10. Map Descriptor Example 7 - Analog Input (Are…
FieldServer FS-8700-97 — 4.4.10. Map Descriptor Example 7 - Analog Input (Area Machine) diagram (page 18)
Fig. 21 · 4.4.10. Map Descriptor Example 7 - Analog Input (Are…

SMD00_AI, Analog_Input, 0, Server, Virtual_BCU_11, AI, 1, 1, 0, 0, 100, 0, 100

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

// Insert a first available scene number under the Data_Array_High_Scale field for each Object ID or

4.4.10. Map Descriptor Example 7 - Analog Input (Area Machine)

// use the scale fields as desired to scale scene numbers.

// All values are in decimal ( 0 - 65535 )

Map Descriptors with the same length.

The last scene value may be scaled:

// Analog Input Settings Setup

// Object IDs are contiguous

scene numbers.

Show 4 more labels / short text on this page
//================================================================================ · Name, Data_Array_ · Name, Data_Array_ · //
Page 19 of the FieldServer FS-8700-97 user manual — 4.4.11. Map Descriptor Example 8 - Analog Input (Zone Machine)
Page 19 · click to enlarge
Page 19

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given

zone is set on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The

start zone number is specified under the “zone” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two

series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC

FieldServer FS-8700-97 — 4.4.11. Map Descriptor Example 8 - Analog Input (Zone Machine) diagram (page 19)
Fig. 22 · 4.4.11. Map Descriptor Example 8 - Analog Input (Zon…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.11. Map Descriptor Example 8 - Analog Input (Zone Machine) diagram (page 19)
Fig. 23 · 4.4.11. Map Descriptor Example 8 - Analog Input (Zon…

zone intensities. The intensity value returned is scaled to a percentage value (0 to 100%). Zone numbers range from 0 to 511.

Zone_inta_0, Analog_Input, 0, ARCO, LUT_GRF6_0, zone_intensity, 0, 512

SMD00_AI, Analog_Input, 0, Server, Virtual_BCU_11, AI, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.11. Map Descriptor Example 8 - Analog Input (Zone Machine)

Map Descriptors with the same length.

Page 20 of the FieldServer FS-8700-97 user manual — 4.4.12. Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)
Page 20 · click to enlarge
Page 20

A write to the Multistate Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts. The

multiple scripts are specified in the Data Array defined under “DA_Lut_List”. The value written into the Multistate Output Data Array

is used as the offset into the Data Array defined under “DA_Lut_List” to retrieve a script number from the Data Array. Script numbers

The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map

FieldServer FS-8700-97 — 4.4.12. Map Descriptor Example 9 - Multistate Output (Zone and Area Machine) diagram (page 20)
Fig. 24 · 4.4.12. Map Descriptor Example 9 - Multistate Output…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default,

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Grafik_Command, DA_Lut_List, DA_Lut_List_Offset, Length, Multi_Scripts_Length

Run_scriptms_0, MultiSt_Output, 0, AWT, LUT_GRF6_0, run_script_multi, Scr_lst_MSO_0, 0, 1, 10

SMD00_MO, MultiSt_Output, 0, Server, Virtual_BCU_11, MO, 1, 512, 0,

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.12. Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)

Descriptor per object must be defined with a Multi_Scripts_Length value of one or greater.

range from 0 to 65535.

Page 21 of the FieldServer FS-8700-97 user manual — 4.4.12. Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)
Page 21 · click to enlarge
Page 21

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Data_Array_Name Preload_Data_Format Preload_Data_Value Location

Scr_lst_MSO_0 , Uint16 , 110 , 0 Scr_lst_MSO_0 , Uint16 , 210 , 1 Scr_lst_MSO_0 , Uint16 , 310 , 2 Scr_lst_MSO_0 , Uint16 , 410 , 3 Scr_lst_MSO_0 , Uint16 , 510 , 4 Scr_lst_MSO_0 , Uint16 , 610 , 5 Scr_lst_MSO_0 , Uint16 , 710 , 6 Scr_lst_MSO_0 , Uint16 , 810 , 7 Scr_lst_MSO_0 , Uint16 , 910 , 8 Scr_lst_MSO_0 , Uint16 , 65010 , 9

Scr_lst_MSO_1 , Uint16 , 120 , 0 Scr_lst_MSO_1 , Uint16 , 220 , 1 Scr_lst_MSO_1 , Uint16 , 320 , 2 Scr_lst_MSO_1 , Uint16 , 420 , 3 Scr_lst_MSO_1 , Uint16 , 520 , 4 Scr_lst_MSO_1 , Uint16 , 620 , 5 Scr_lst_MSO_1 , Uint16 , 720 , 6 Scr_lst_MSO_1 , Uint16 , 820 , 7 Scr_lst_MSO_1 , Uint16 , 920 , 8 Scr_lst_MSO_1 , Uint16 , 65020 , 9

// Multistate Output Object ID 1

// Multistate Output Object ID 2

The scripts per object element must be preloaded into the Data Array defined under “DA_Lut_List”:

// Specify up to 10 scripts for each Object ID by editing Preload_Data_Value

// All values are in decimal ( 0 - 65535 )

// Multistate Output Scripts Setup

Preloads · //===================================================================== · //

Page 22 of the FieldServer FS-8700-97 user manual — 4.4.13. Map Descriptor Example 10 - Binary Value (Zone and Area Machine)
Page 22 · click to enlarge
Page 22

A read from the Binary Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a

system variable in the Lutron eLumen panel. The value returned is inactive (0) if the system variable is zero and active (1) if

non-zero. The Lutron Machine Map Descriptor regularly polls the Lutron panel to retrieve the system variable values. A write

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of system variables to

poll. The start system variable number is specified under the “Sys_Var” Map Descriptor field. More than one ARCO Map Descriptor

may be used to poll two series of system variable numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1

FieldServer FS-8700-97 — 4.4.13. Map Descriptor Example 10 - Binary Value (Zone and Area Machine) diagram (page 22)
Fig. 25 · 4.4.13. Map Descriptor Example 10 - Binary Value (Zo…
FieldServer FS-8700-97 — 4.4.13. Map Descriptor Example 10 - Binary Value (Zone and Area Machine) diagram (page 22)
Fig. 26 · 4.4.13. Map Descriptor Example 10 - Binary Value (Zo…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

Zone_var_0, Binary_Value, 0, ARCO, LUT_GRF6_0, sys_var_val_bin, 0, 512

to the Binary Value Data Array will set the system variable to 255 on active (1) write or to zero on inactive (0) write.

SMD00_BV, Binary_Value, 0, Server, Virtual_BCU_11, BV, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.13. Map Descriptor Example 10 - Binary Value (Zone and Area Machine)

fullfil the same function as RDBC Map Descriptors with the same length.

Page 23 of the FieldServer FS-8700-97 user manual — 4.4.14. Map Descriptor Example 11 - Analog Value (Zone and Area Machine)
Page 23 · click to enlarge
Page 23

A read from the Analog Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system

variable in the Lutron eLumen panel. The variable values range from 0 to 255. The Lutron Machine Map Descriptors are regularly

updated with system variable values from the active Binary Value Map Descriptors. A write to the Analog Value Data Array will set

The Passive_Client function is used to prevent double-polling the Lutron eLumen panel for system variables. The Analog Value Map

Descriptors should be set up identical to the Binary Value Map Descriptors in terms of the Sys_Var and Length fields to ensure

FieldServer FS-8700-97 — 4.4.14. Map Descriptor Example 11 - Analog Value (Zone and Area Machine) diagram (page 23)
Fig. 27 · 4.4.14. Map Descriptor Example 11 - Analog Value (Zo…

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Object_ID, Length, Relinquish_Default

FieldServer FS-8700-97 — 4.4.14. Map Descriptor Example 11 - Analog Value (Zone and Area Machine) diagram (page 23)
Fig. 28 · 4.4.14. Map Descriptor Example 11 - Analog Value (Zo…

Zone_vara_0, Analog_Value, 0, Passive_Client, LUT_GRF6_0, sys_var_val, 0, 512

SMD00_AV, Analog_Value, 0, Server, Virtual_BCU_11, AV, 1, 512, 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

4.4.14. Map Descriptor Example 11 - Analog Value (Zone and Area Machine)

system variable values will be stored correctly.

the system variable to the written value.

Page 24 of the FieldServer FS-8700-97 user manual — Appendix A. Revision History
Page 24 · click to enlarge
Page 24

Appendix A. Revision History

Date Resp Format Driver

Doc. Rev. Comment

Ver.

07/04/03 DR 1.00 0 Created 07/08/03 DR 1.01 1 Updated driver version, SPR2912 09/05/03 DR 1.02 1 Updated with ARCO Map Descriptor usage 09/09/03 DR 1.02 2 Updated with passive Client mapdescs

10/15/03 MF 1.02 3 Updated according to DUR0215. Updated formatting 1/21/04 JD 1.02 4 Releasing 3/22/04 DR 1.02 5 Updated for release

3/24/04 MC MC 1.02 6 Updated formatting. Added new revision table. Changed page setup to letter. 6/10/04 JD 1.02 7 Releasing

11/3/04 Meg Meg 1.03 0 Changed references to Grafik to eLumen – DUR0484.

Connection diagrams added for RS-232 and RS-485. Modifications to scope of supply table. Table formatting. Map Descriptor example titles added. Added RS-485 compatibility. 4/12/05 JD JD 1.03 1 Releasing 4/27/05 JD JD 1.03 2 Corrected page numbering. Releasing.

12/30/04 Meg Meg 1.03 1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-97

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-97

Be the first to ask — other owners or our team will answer.

Original document

FieldServer FS-8700-97 manual PDF

24 pages·205 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…