Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-01 Modbus RTU

& FS-8700-08 Modbus ASCII

There are several similarities between these two drivers and

we have incorporated them into the same manual to ensure

that our information stays current. Although both drivers are referenced in this manual, they are different drivers and

need to be ordered separately."

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Instruction Manual Part NumberT28700-01

Rev. A.

Applicability and Effectivity

Page 2 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 · click to enlarge
Page 3
1. Modbus RTU/ Modbus ASCII Description
  • The Modbus RTU and Modbus ASCII drivers allow the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Modbus RTU or Modbus ASCII protocol respectively. The driver was developed for Modbus Application Protocol Specification V1.1a" from Modbus-IDA. The specification can be found at <a href="http://www.modbus.org" rel="nofollow noopener" target="_blank">www.modbus.org</a> . The FieldServer can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer. There are various register mapping models being followed by various vendors To cover all these models FieldServer uses the following three Models
  • Modicon_5digit – Use this format where addresses are defined in 0xxxx, 1xxxx, 3xxxx or 4xxxx format. A maximum of 9999 registers can be mapped of each type. This is FieldServer driver’s default format.
  • ADU –Application Data Unit address. Use this format where addresses of each type are defined in the range 1-65536
  • PDU –Protocol Data unit address. Use this format where addresses of each type are defined in the range 0-65535. The key difference between ADU and PDU is for example if Address_Type is ADU and address is 1, the driver will poll for register 0. If Address_Type is PDU, the driver will poll for address 1. Note 1: If vendor document shows addresses in extended Modicon (i.e. 6 digit) format like 4xxxxx then consider these addresses as xxxxx (omit the first digit) and use either ADU or PDU Note 2: The purpose of providing 3 different ways of addressing the Modbus registers is to allow the user to choose the addressing system most compatible with the address list being used. At the protocol level, the same protocol specification is used for all three with the exception of the limited address range for Modicon_5digit.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 4 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 4 · click to enlarge
Page 4
2. Driver Scope of Supply

2.1. Supplied by FieldServer Technologies for this driver

FIELDSERVER TECHNOLOGIES PART # DESCRIPTION FS-8915-10 UTP cable (7 foot) for RS-232 use FS-8917-02 RJ45 to DB9F connector adapter FS-8917-01 RJ45 to DB25M connection adapter FS-8917-21 RS-485 connection adapter FS-8700-01 (T28700-01) Driver Manual

2.2. Provided by Supplier of 3rd Party Equipment

PART # DESCRIPTION Modbus RTU or Modbus ASCII device

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 5 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 5 · click to enlarge
Page 5
3. Hardware Connections

It is possible to connect a Modbus RTU or Modbus ASCII device to any of the existing serial ports on the FieldServer1. These ports simply need to be configured for the appropriate driver in the configuration file. Configure the Modbus RTU or Modbus ASCII device according to manufacturer’s instructions.

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 5)
Fig. 2 · Driver Manual (Supplement to the FieldServer Instruc…

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 6 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 6 · click to enlarge
Page 6
4. Configuring the FieldServer as a Modbus RTU or Modbus ASCII Client.

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Modbus RTU or Modbus ASCII Server.

4.1. Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Modbus RTU or Modbus ASCII communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 6)
Fig. 3 · Driver Manual (Supplement to the FieldServer Instruc…

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters

Provide data format. Each Data Array can only take on one format.

Number of Data Objects. Must be larger than the data storage area required by the map descriptors for the data being placed in this array.

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 6)
Fig. 4 · Driver Manual (Supplement to the FieldServer Instruc…

// Data Arrays Data_Arrays Data_Array_Name, Data_Array_Format, Data_Array_Length DA_AI_01, UInt16, 200 DA_AO_01, UInt16, 200 DA_DI_01, Bit, 200 DA_DO_01, Bit, 200

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Example

Page 7 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 7 · click to enlarge
Page 7

4.2. Client Side Connection Descriptors

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 7)
Fig. 5 · Driver Manual (Supplement to the FieldServer Instruc…

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R22

Baud* Specify baud rate 110 – 115200, standard baud rates only. 9600 Parity* Specify parity Even, Odd, None Data_Bits* Specify data bits 7, 8 Stop_Bits* Specify stop bits 1 (Vendor limitation) Modbus RTU Modbus _RTU Modbus ASCII Protocol Specify protocol used

MB_ASCII Handshaking* Handshaking is not supported None Poll Delay* Time between internal polls 0-32000s, 0.05s Example Change protocol to MB_ASCII to use Modbus ASCII protocol

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 7)
Fig. 6 · Driver Manual (Supplement to the FieldServer Instruc…

// Client Side Connections Connections Port, Baud, Parity, Data_Bits, Stop_Bits, Protocol, Handshaking, Poll_Delay P8, 9600, None, 8, 1, Modbus _RTU, None, 0.100s

2 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 8 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 8 · click to enlarge
Page 8

4.3. Client Side Node Descriptors

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 8)
Fig. 7 · Driver Manual (Supplement to the FieldServer Instruc…

Node_Name Provide name for Node Up to 32 alphanumeric characters

Node_ID Modbus station address of physical Server Node 1-255

Modbus RTU Modbus_RTU Modbus ASCII Protocol Specify protocol used

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R22

Set to Block_Mode if Remote Server Node (RSN) only supports Write Multiple – FC16 & FC15, and does not support FC05 or FC06

Address_Type4 Specify Register Mapping Model ADU,PDU, -, Modicon_5digit Example: Change protocol to MB_ASCII to use Modbus ASCII protocol

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 8)
Fig. 8 · Driver Manual (Supplement to the FieldServer Instruc…

// Client Side Nodes // For devices where 65536 addresses are available in each memory area. Nodes Node_Name, Node_ID, Protocol, Port Address_Type Modbus device 1, 1, Modbus_RTU, P8 ADU Modbus device 2, 2, Modbus_RTU, P8 PDU // For devices where only 9999 registers are available in each memory area. Nodes Node_Name, Node_ID, Protocol, Port Modbus device 3, 3, Modbus_RTU, P8

3 If this parameter is not specified the default function codes will be FC 05 (Single_Coil) and FC 06 (Single_Register). Refer to Appendix A.3 for more information. 4 Optional for Modicon 5 digit devices

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 9 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 9 · click to enlarge
Page 9

4.4. Client Side Map Descriptors

4.4.1. FieldServer Related Map Descriptor Parameters

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 9)
Fig. 9 · Driver Manual (Supplement to the FieldServer Instruc…
Column TitleFunctionLegal Values Map Descriptor Name _ _Name of this Map DescriptorUp to 32 alphanumeric characters Data Array Name _ _Name of Data Array where data is to be stored in the FieldServerOne of the Data Array names from “Data Array” section above Data Array Offset _ _Starting location in Data Array0 to maximum specified in “Data Array” section above FunctionFunction of Client Map DescriptorRDBC, WRBC, WRBX

4.4.2. Driver Related Map Descriptor Parameters

Column Title Function Legal Values

Node_Name Name of Node to fetch data from

One of the Node names specified in “Client Node Descriptor” above Address_Type = ADU Coil, Discrete_Input, Input_Register, Holding_Register, Single_Coil, Single_Register Address_Type = PDU FC01, FC02, FC03, FC04, FC05, FC06, FC15, FC16 Address_Type = Modicon_5digit

Data_Type5 Specify memory area

- (Dash), Single_Register, Single_Coil Address_Type = ADU 1-65536 Address_Type = PDU 0-65535 Address_Type = Modicon_5digit

Address Starting address of read block

Length Length of Map Descriptor

1-125 (For Analog polls), 1-800 (For Binary polls).

Data_Array_Low_Scale* Scaling zero in Data Array

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 0

Data_Array_High_Scale* Scaling max in Data Array

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 100

Node_Low_Scale* Scaling zero in Connected Node

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 0

Node_High_Scale* Scaling max in Connected Node

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 100

4.4.3. Timing Parameters

Column TitleFunctionLegal Values Scan Interval*Rate at which data is polled0-32000, 1

5 Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

40001, 30001, etc

Page 10 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 10 · click to enlarge
Page 10

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Data_Type, Address, Length, Scan_Interval

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Data_Type, Address, Length, Scan_Interval

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Address, Length, Scan_Interval

CMD_AI_01, DA_AI_01, 0, RDBC, MODBUS DEVICE1, Input_Register, 1, 20, 1.000s CMD_AO_01, DA_AO_01, 0, RDBC, MODBUS DEVICE1, Holding_Register, 1, 20, 1.000s CMD_DI_01, DA_DI_01, 0, RDBC, MODBUS DEVICE1, Discrete_Input, 1, 20, 1.000s CMD_DO_01, DA_DO_01, 0, RDBC, MODBUS DEVICE1, Coil, 1, 20, 1.000s

CMD_AI_02, DA_AI_02, 0, RDBC, MODBUS DEVICE2, FC04, 0, 20, 1.000s CMD_AO_02, DA_AO_02, 0, RDBC, MODBUS DEVICE2, FC03, 0, 20, 1.000s CMD_DI_02, DA_DI_02, 0, RDBC, MODBUS DEVICE2, FC02, 0, 20, 1.000s CMD_DO_02, DA_DO_02, 0, RDBC, MODBUS DEVICE2, FC01, 0 20, 1.000s

CMD_AI_03, DA_AI_03, 0, RDBC, MODBUS DEVICE3, 30001, 20, 1.000s CMD_AO_03, DA_AO_03, 0, RDBC, MODBUS DEVICE3, 40001, 20, 1.000s CMD_DI_03, DA_DI_03, 0, RDBC, MODBUS DEVICE3, 10001, 20, 1.000s CMD_DO_03, DA_DO_03, 0, RDBC, MODBUS DEVICE3, 00001, 20, 1.000s

// For Nodes where Address_Type is ADU

// For Nodes where Address_Type is PDU

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

// Note: All three examples below are addressing the same Modbus registers.

4.4.4. Map Descriptor Examples.

// For Nodes where Address_Type is Modicon_5digit.

// Client Side Map Descriptors

Map_Descriptors · Map_Descriptors · Map_Descriptors

Page 11 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 11 · click to enlarge
Page 11
5. Configuring the FieldServer as a Modbus RTU or Modbus ASCII Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Modbus RTU or Modbus ASCII Client. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Modbus RTU or Modbus ASCII communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1. Server Side Connection Descriptors

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 11)
Fig. 10 · Driver Manual (Supplement to the FieldServer Instruc…

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R26

Baud* Specify baud rate 110 – 115200, standard baud rates only Parity* Specify parity Even, Odd, None Data_Bits* Specify data bits 7, 8 Stop_Bits* Specify stop bits 1 (Vendor limitation) Modbus RTU Modbus_RTU Modbus ASCII Protocol Specify protocol used

Example Change protocol to MB_ASCII to use Modbus ASCII protocol // Server Side Connections Connections Port, Baud, Parity, Data_Bits, Stop_Bits, Protocol, Handshaking P1, 9600, None, 8, 1, Modbus_RTU, None

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 11)
Fig. 11 · Driver Manual (Supplement to the FieldServer Instruc…

6 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 12 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 12 · click to enlarge
Page 12

5.2. Server Side Node Descriptors

Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Node ID of physical Server Node 1 – 255 Protocol Specify protocol used Modbus RTU Address_Type7 Specify Register Mapping Model ADU,PDU, -, Modicon_5digit

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 12)
Fig. 12 · Driver Manual (Supplement to the FieldServer Instruc…

Example Change protocol to MB_ASCII to use Modbus ASCII protocol

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 12)
Fig. 13 · Driver Manual (Supplement to the FieldServer Instruc…

// Server Side Nodes // For devices where 65536 addresses are available in each memory area. Nodes Node_Name, Node_ID, Protocol Address_Type MB_Srv_11, 11, Modbus_RTU ADU MB_Srv_12, 12, Modbus_RTU PDU // For devices where only 9999 registers are available in each memory area. Nodes MB_Srv_13, 13, Modbus_RTU Modicon_5digit MB_Srv_14, 14, Modbus_RTU -

7 Optional for Modicon 5 digit devices

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 13 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 13 · click to enlarge
Page 13

5.3. Server Side Map Descriptors

5.3.1. FieldServer Specific Map Descriptor Parameters

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 13)
Fig. 14 · Driver Manual (Supplement to the FieldServer Instruc…

Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters

Data_Array_Name Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above

5.3.2. Driver Specific Map Descriptor Parameters

Column Title Function Legal Values

Node_Name Name of Node to fetch data from

One of the Node names specified in “Client Node Descriptor” above Address_Type = ADU Coil, Discrete_Input, Input_Register, Holding_Register, Single_Coil, Single_Register Address_Type = PDU FC01, FC02, FC03, FC04, FC05, FC06, FC15, FC16 Address_Type = Modicon_5digit

Data_Type8 Specify memory area

- (Dash), Single_Register, Single_Coil

Length Length of Map Descriptor 1-10000.

Address_Type = ADU 1-65536 Address_Type = PDU 0-65535 Address_Type = Modicon_5digit

Address Starting address of read block

Data_Array_Low_Scale* Scaling zero in Data Array

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 0

Data_Array_High_Scale* Scaling max in Data Array

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 100

Node_Low_Scale* Scaling zero in Connected Node

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 0

Node_High_Scale* Scaling max in Connected Node

Any signed 32 bit integer in the range: -2,147,483,648 to 2,147,483,647. 100

Set the FieldServer response to the Modbus RTU Client when the Server Node supplying the data has gone offline

No_Response, Old_Data, Zero_Data, FFFF_Data, Refer to Appendix A.6 for further information.

8 Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

40001, 30001, etc · Node_Offline_Response

Page 14 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 14 · click to enlarge
Page 14

Map_Descriptor_Name Data_Array_Name Data_Array_Offset, Function Node_name, Data_type Address, Length, Data_Array_Low_Scale, Data_Array_High_Scale Node_Low_Scale Node_High_Scale

Map_Descriptor_Name Data_Array_Name Data_Array_Offset, Function Node_name, Data_type Address, Length, Data_Array_Low_Scale, Data_Array_High_Scale Node_Low_Scale Node_High_Scale

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Address, Length, Data_Array_Low_Scale, Data_Array_High_Scale Node_Low_Scale Node_High_Scale

SMD_AI_01, DA_AI_01, 0, Server, MB_Srv_11 Input_Register 1, 200, 0, 100, 0, 10000 SMD_AO_01, DA_AO_01, 0, Server, MB_srv_11 Holding_Register 1, 200, 0, 100, 0, 10000

SMD_AI_02, DA_AI_02, 0, Server, MB_Srv_12 FC04 0, 200, 0, 100, 0, 10000 SMD_AO_02, DA_AO_02, 0, Server, MB_srv_12 FC03 0, 200, 0, 100, 0, 10000

SMD_AI_01, DA_AI_01, 0, Server, MBP_Srv_13, 30001, 200, 0, 100, 0, 10000 SMD_AO_01, DA_AO_01, 0, Server, MBP_Srv_13, 40001, 200, 0, 100, 0, 10000

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

5.3.3. Map Descriptor Examples

// Note: All three examples below are addressing the same Modbus registers.

// Server Side Map Descriptors where Node Address_Type is ADU

// Server Side Map Descriptors where Node Address_Type is PDU

// For Nodes where Address_Type is Modicon_5digit.

// For Nodes where Address_Type is ADU

Map_Descriptors · Map_Descriptors · Map_Descriptors

Page 15 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 15 · click to enlarge
Page 15

Appendix A. Advanced Topics – Modbus RTU

Appendix A.1. Data Types

If Node parameter Address_Type is set as ADU or PDU, then Data_Type must be specified as follows For Address_Type ADU :

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 15 · Driver Manual (Supplement to the FieldServer Instruc…

Address range Data_Type Function Code (Write) Function Code (Read) 1 - 65536 Coil 15 1 1 – 65536 Discrete_Input n/a. 2 1 – 65536 Input_Register n/a. 4 1 - 65536 Holding_Register 16 3 For Address_Type PDU :

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 16 · Driver Manual (Supplement to the FieldServer Instruc…

Address range Data_Type Function Code (Write) Function Code (Read) 0 - 65535 FC01 15 1 0 – 65535 FC02 n/a. 2 0 – 65535 FC04 n/a. 4 0 – 65535 FC03 16 3 For Address_Type Modicon_5digit When a Modbus address range is specified, a particular Data Type is implied. The defaults are as follows:

Address range Data_Type Function Code (Write) Function Code (Read) 40001 - 49999 Register 16 3 30001 - 39999 Analog _Input n/a. 4 10001 - 19999 Digital_Input n/a. 2 00001 - 09999 Coil 15 1

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 17 · Driver Manual (Supplement to the FieldServer Instruc…

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 16 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 16 · click to enlarge
Page 16

Appendix A.2. Single Writes

For pure write operations where the function = WRBC or WRBX, the driver defaults to using Function Codes 15 and 16 (Multiple writes). It is possible to force the driver to use Function Codes 5 and 6 (Single Writes) by manipulating the Data_Type parameter as follows:

For Address_Type ADU: Address range Data_Type Function Code (Write) 1 - 65536 Single_Coil 5 1 - 65536 Single_Register l 6 For Address_Type PDU: Address range Data_Type Function Code (Write) 0 - 65535 FC05 5 0 - 65535 FC06 6 For Address_Type Modicon_5digit

Address range Data_Type Function Code (Write) 40001 - 49999 Single_Register 6 30001 - 39999 Single_Coil 5. Example: FC 6 = Write Single Register Add a parameter to the Modbus client side Map Descriptor called Data_Type. If you specify the Data_Type as Single_Register and the Function as WRBC or WRBX, then a Modbus poll with FC 6 will be generated. Logically Single Register implies a length of one, and even if you try to set the length longer in the csv file, the length is limited to 1 in the driver.

Appendix A.3. Read/write Operation

When using the driver as a Modbus master, the function RDBC allows read/write capability with Register and Coil data types. If defaults are used, then Function codes 5 and 6 (Single Writes) are used to write data back to the registers being read, regardless of data length being read. If multiple writes (FC 15 and 16) are needed for Read/write operation, the user needs to specify the Node_Type parameter in the Client Side Nodes Section and set it to Block_Mode. Note that block writes of length 1 are currently all that is supported.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 17 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 17 · click to enlarge
Page 17

Modbus as a standard does not support floating point formats. Many vendors have written higher level communications software to

use two 16 bit registers to represent floating point or 32 bit integers. This requires conversion software on both ends of the

The following example shows how scaling can be achieved on the Server side of the configuration. Note that scaling can also be

done on the Client side to scale down a value that was scaled up by a Modbus vendor. Further information regarding scaling can be

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Address, Length, Data_Array_Low_Scale, Data_Array_High_Scale, Node_Low_Scale, Node_High_Scale,

This example multiplies the values in the data array by 100 (10000 on Node_High_Scale is 100X larger than 100 on

Data_Array_High_Scale). This is most commonly used when the user wants to introduce values after the decimal point. For

SMD_AI1, DA_AI_01, 0, Server, MBP_Srv_11, 30001, 200, 0, 100, 0, 10000 SMD_AO1, DA_AO_01, 0, Server, MBP_Srv_11, 40001, 200, 0, 100, 0, 10000

communication channel. The FieldServer supports this function and also provides other options to resolve this issue.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

  • Use the scaling function on the FieldServer, which will allow you to set up any range, with 16 bit resolution.
  • Declare data arrays as type Uint16 (Unsigned integer). This will give you a range from 0 to 65535.

example, a value of 75.6 will be sent as 7560, which can then be rescaled by the Modbus master.

It is possible to represent values higher than 32767 using one register in one of two ways:

Appendix A.4. Managing Floating points with Modbus

Transferring non-integer values with one register

found in the FieldServer Configuration manual.

Example :

Map_Descriptors

Page 18 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 18 · click to enlarge
Page 18

Transferring 32 bit values with two registers If a Modbus Server sends two consecutive registers to the FieldServer representing either a floating point value or a 32 bit integer value, the FieldServer can combine and decode these registers back into their original format. To do this, the user must read the registers into an integer data array, and then use the Moves function to move the data to a floating point or 32 bit integer data array. The “function” field in the move must be populated with the correct move function required. Details of the available function fields are listed in the FieldServer configuration manual along with a more detailed explanation of moves. Note that functions also exist to split a floating point value into two integers using the reverse operation. A diagrammatic representation of this process is depicted below:

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 18)
Fig. 18 · Driver Manual (Supplement to the FieldServer Instruc…

Float Data Array Offset 40: Float value Modbus

Source Data Array Offset 0: 40001 Offset 1: 40002

Modbus Device Two 16 bit integers polled: e.g: 40001, length 2 Together, they combine to form a 32 bit IEEE Floating point number.

The example below shows how a floating point value is retrieved from two Modbus registers that were placed in an integer data array.

Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length DA1, int16, 20 DA2, float, 10 Moves Function, Source_Data_Array, Source_Offset, Target_Data_Array, Target_Offset 2.i16-1.float-sw, DA1, 0, DA2, 6

FieldServer Protocol Gateway (FS-8700-01) — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 18)
Fig. 19 · Driver Manual (Supplement to the FieldServer Instruc…

This Move will cause two integers at offsets 0 and 1 in the integer Data Array DA1 to be copied to offset 6 in the float Data Array DA2. In the process of copying the values, the integers will be combined and treated as an IEEE 32 bit floating point number.

Appendix A.5. Connection to York Modbus Microgateway

If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and the stop bits are 1. Other Node_ID combinations can be found in the York Modbus Microgateway Installation Manual.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Example

Page 19 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 19 · click to enlarge
Page 19

Appendix A.6. Node_Offline_Response

  • This function is specific to the Modbus RTU driver. In systems where data is being collected from multiple Server Nodes and made available on a FieldServer configured as a Modbus RTU Server, when a Server Node goes offline the default behavior of the FieldServer would be to stop responding to polls for this data. This might not be what the user wants. Various options exist making it possible to signal that the data quality has gone bad without creating error conditions in systems sensitive to the default option. The following options can be configured under the Node parameter, Node_Offline_Response, to set the response of the FieldServer to the Modbus RTU Client when the Server Node supplying the data is offline:
  • No_Response - this is the default option. The FieldServer simply does not respond when the corresponding Server Node is offline.
  • Old_Data - The FieldServer will respond, but with the last known value of the data. This maintains the communication link in an active state, but may hide the fact that the Server Node is offline.
  • Zero_Data - The FieldServer will respond, but with the data values set to zero. If the user normally expects non-zero values, this option will signal the offline condition without disrupting communications.
  • FFFF_Data - The FieldServer will respond, but with the data values set to FFFF (hex). If the user normally expects other values, this option will signal the offline condition without disrupting communications.

Example: Nodes Node_name, Node_ID, Protocol, Node_Offline_Response, port DEV11, 11, Modbus_rtu, No_Response, - DEV12, 12, Modbus_rtu, Old_Data, - DEV15, 15, Modbus_rtu, Zero_Data, - DEV16, 16, Modbus_rtu, FFFF_Data, -

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 20 of the FieldServer Protocol Gateway (FS-8700-01) user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 20 · click to enlarge
Page 20

Appendix B. Modbus ASCII - Examples of FieldServer setup for typical clients

Appendix B.1. FieldServer with GE Cimplicity as client

  • Run the Cimplicity “Workbench” and create a “New Project” with a unique “Project Name” option of “Basic Control” and protocol “Modbus ASCII”.
  • Check the project properties and continue with the “Project Wizard Setup” that appears.
  • Add Modbus port giving it a description.
  • Create and configure the devices, select “new item”.
  • Name the device, select the port, give it a description (e.g. FieldServer), and choose “SYSTEM” resource.
  • Create and configure the points.
  • Select “new item”, name the point and choose the appropriate device.
  • Under the “General” tab, point properties require a description. Note that the elements must have a value greater than 8.
  • Under the “Device” tab, properties need the appropriate address (e.g. 40001 and also require the leading 0’s), change the update criteria to “On Scan”.
  • When the project is configured, run by pressing the “play” button.
  • Expect the Cimplicity driver to connect and poll the FieldServer for a range of valid addresses, and then proceed to poll for just the configured Points.
  • From the start menu choose the “Point Control Panel”, select edit and add the project you want to view. Note, to log on the User name “ADMINISTRATOR” must be supplied
  • Use “Modbus ASCII Diagnostics” to connect to host and then read the register.

Appendix B.2. FieldServer with Intellution FIX as a client

  • Install Intellution FIX, choosing the MB1 Modbus ASCII I/O driver
  • Run from Start menu and choose “Intellution Fix”.
  • Choose “System Configuration Utility”.
  • Modify SCADA, add the MB1 Modbus ASCII I/O driver
  • Configure the Modbus ASCII Driver.
  • Device is D11, select 5-digit address, add the FieldServer virtual Node ID to station address
  • Set up poll record
  • SAVE the configuration.
  • Open “StaRTUp”
  • Open “Mission Control” from the “Apps” menu and confirm Fix is polling.
  • To display the data create a link in Fix draw, add link, data link.
  • Give it a tagname, allow data entry, numeric entry and set enable option.
  • If tag is not in database, select “Add”, choose “AR”. Then set output enable , device MB1, I/O address d11.
  • Save the settings
  • Use “Quickview” from the “View” menu to confirm the reading of data without ??? appearing
  • Change the value and wait a few seconds to ensure the change really occurred.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Page 21 of the FieldServer Protocol Gateway (FS-8700-01) user manual — THIS PAGE INTENTIONALLY LEFT BLANK
Page 21 · click to enlarge
Page 21

THIS PAGE INTENTIONALLY LEFT BLANK

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer Protocol Gateway (FS-8700-01)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer Protocol Gateway (FS-8700-01)

Be the first to ask — other owners or our team will answer.

Original document

FieldServer Protocol Gateway (FS-8700-01) manual PDF

21 pages·287 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…