A Sierra Monitor Company
FS-8700-87 SDD16
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001



The SDD16 driver allows the FieldServer to transfer data to and from devices over RS-485 using SDD16 protocol. The FieldServer can only emulate a Client. The SDD16 driver is used to communicate with a digital I/O module model 485SDD16. The current driver only supports reading the status of all sixteen digital input lines. The SDD16 driver in conjunction with the 485SDD16 module allows the FieldServer to sense external On/Off conditions and to control a variety of devices. The SDD16 driver makes use of the data complement mode feature of the 485SDD16 module. In data complement mode the driver and module communicates with double the amount of data bytes to enable better error detection in noisy electrical environments.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

2.1. Supplied by FieldServer Technologies for this driver
FieldServer Technologies PART # Description FS-8700-87 Driver Manual.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

The FieldServer is connected to the RS-485 SDD16 module as shown below. Configure the RS-485 SDD16 module according to manufacturer’s instructions. Note that the module auto-detects valid baud rates as defined in the client side connections.
!"## $% "#
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

For a detailed discussion on FieldServer configuration, please refer to the configuration manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a SDD16 Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for SDD16 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters
Data_Format Provide data format. Each data array can only take on one format.
Number of Data Objects. Must be larger than the data storage area required for the data being placed in this array.

//Data Arrays // Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length Digitals_01, Bit, 16
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Example


R1-R2 FSx40 Servers FSx20 Servers Baud Specify baud rate 1200, 2400, 4800, 9600 Parity* Specify parity None Data_Bits* Specify data bits 8 Stop_Bits* Specify stop bits 1 Protocol Specify protocol used SDD16 Handshaking* Specify hardware handshaking None Line_Drive_On Time to wait before driving line 0.001s
Port Specify which port the device is connected to the FieldServer
Poll _Delay* Time between internal polls 0-32000 seconds,1 second
// Client Side Connections Connections Port, Baud, Parity, Protocol, Handshaking, Poll_Delay, Line_Drive_On, Line_Drive_Off R1, 9600, None, SDD16, None, 0.100s, 0.001s, 0s


Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID Module address 0-255 (48 is default address on module) Protocol Specify protocol used SDD16
Specify which port the device is connected to the FieldServer

// Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Port Module_1, 48, SDD16, R1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Example · Example

4.4.1. FieldServer Related Map Descriptor Parameters

Name of Data Array where data is to be stored in the FieldServer
One of the Data Array names from “Data Array” section above
0 to maximum specified in “Data Array” section above

One of the node names specified in “Client Node Descriptor” above Data_Type* Data type Flag Length Length of Map Descriptor 1-16 Address Starting digital line number 0 – 15
Column Title Function Legal Values Scan_Interval Rate at which data is polled >0.1s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_name, Address, Length
Digital_inputs, 1s, Digitals_0, 0, rdbc, Module_0, 0, 16
be stored.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
number.
from.
will be stored. Offset into
be stored.
4.4.4. Map Descriptor Example.
// Client Side Map Descriptors
Descriptor.
Descriptor.