Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-40 SBT-FSI

(Siemens Building Technologies – Foreign Systems Interface)

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after September 2008

Driver Version1.08 Document Revision: 3
Page 3 of the FieldServer FS-8700-40 user manual — 1 SBT-FSI DESCRIPTION
Page 3 · click to enlarge
Page 3

1 SBT-FSI DESCRIPTION

The SBT-FSI (Siemens Building Technologies – Foreign Systems Interface) driver allows the FieldServer to transfer data to and from Siemens MXL/XLS devices (NIM-1R1 or NIM-1W or RPM2) over either RS-232 or RS-485 using MXL/XLS to foreign system protocol. The FieldServer can emulate either a Server or a Client.

FieldServer FS-8700-40 — 1 SBT-FSI DESCRIPTION diagram (page 3)
Fig. 2

1-10 (one Client per physical FieldServer serial port). Depends on FieldServer model and configuration.

Server 99 Panel numbers from 1 to 99 may be emulated

FieldServer FS-8700-40 — 1 SBT-FSI DESCRIPTION diagram (page 3)
Fig. 3

FieldServer Technologies PART # Description FS-8917-03 RJ45 to DB9F connector adapter FS-8700-40 SBT FSI Driver Manual

2.2 Provided by the Supplier of 3rd Party Equipment

FieldServer FS-8700-40 — 1 SBT-FSI DESCRIPTION diagram (page 3)
Fig. 4

Part # Description Siemens MXL/XLS System Siemens NIM-1R Network Interface Module ( for MXL usage ) Siemens RPM Network Interface Module ( for XLS usage ) 500-699103 Siemens NIM-1W Network Interface Module ( for MXL usage ) Siemens Cable P/N 555-193085 (For RS-232 connection)

  • The SBT-FSI System must be set up for remote monitoring with the MXL or XLS to foreign systems protocol.
  • The ports on the RPM must be configured by the XLS panel. The RPM can be configured for RS-232 or RS485, but not both together. Connection to the RS-485 port has not been tested and is not supported.

1 Note that NIM-1R is no longer supported by Siemens and is therefore considered to be legacy while NIM-1W is common. 2 The ports on the RPM need to be configured by the XLS panel. Configuration can be set up for either RS-232 or RS-485, but not both together. Connection to the RS-485 port of the RPM has not been tested and is not supported.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Max Nodes Supported

Page 4 of the FieldServer FS-8700-40 user manual — 3 HARDWARE CONNECTIONS
Page 4 · click to enlarge
Page 4

3 HARDWARE CONNECTIONS

Configure the MXL/XLS device according to manufacturer’s instructions.

It is possible to connect a MXL/XLS device to any RS-232 or RS-485 port. The appropriate ports must be configured for MXL/XLS in the configuration file.

3.1 Using the NIM-1R or NIM-1W for MXL

  • Configure the NIM-1R 3

or NIM-1W for Foreign System Interface (FSI) by setting all of the switches in SW2 to open (or OFF). See connection diagram below:

  • The ports on the RPM need to be configured by the XLS panel. Configuration can be set up for either RS232 or RS-485, but not both together. Connection to the RS-485 port of the RPM has not been tested and is not supported.
FieldServer FS-8700-40 — 3 HARDWARE CONNECTIONS diagram (page 4)
Fig. 5
COLORDB9P3 RED GREEN BLACK BROWN WHITE2 Rx 3 Tx 5 GND 7 RTS 8 CTS14 13 16 12 15

3 Note that NIM-1R is no longer supported by Siemens and is therefore considered to be legacy while NIM-1W is common.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

FieldServer

Page 5 of the FieldServer FS-8700-40 user manual — P2
Page 5 · click to enlarge
Page 5

3.2 FSI Connection Notes

  • One FSI panel may be connected per FieldServer port, but multiple panels may be connected per FSI. The following diagram illustrates two possible connection configurations.

FSI

P1

Configuration 2 – One FSI Panel per FieldServer port, 3 panels connected in series to the FSI

FSI FSI

1 8 1 8

P2

P1

Configuration 1 – One FSI Panel per FieldServer per port, one Panel per FSI

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Show 4 more labels / short text on this page
Panel Panel Panel · FieldServer · Panel Panel · FieldServer
Page 6 of the FieldServer FS-8700-40 user manual — 4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT
Page 6 · click to enlarge
Page 6

4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a SBT-FSI Server.

In FSI mode, the NIM-1R or NIM-1W or RPM allows the FieldServer to gather data from up to 63 MXL/XLS Panels connected via an MXL/XLS network. The default configuration shipped with the FieldServer will monitor two panels (1 and 2) with 8 modules (1 to 8) each.

When the FieldServer is configured as a Client, two sets of data are collected by a “poller” Map Descriptor.

The first is a collection of 19 counters per panel. Each 16-bit counter is incremented by the poller Map Descriptor whenever the corresponding event occurs. An external Client can read these counters to quickly determine whether a new event has been reported to the Server. The counters are mapped into the Data Array specified for the poller Map Descriptor. Counter offsets into the Data Array per event type are indicated below:

FieldServer FS-8700-40 — 4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT diagram (page 6)
Fig. 6

Event Counter Offset Fire Alarm In 0 Fire Alarm Out 1 Fire Alarm Acknowledge 2 Trouble In 3 Trouble Out 4 Trouble Acknowledge 5 Supervisory In 6 Supervisory Out 7 Supervisory Acknowledge 8 Security Alarm In 9

FieldServer FS-8700-40 — 4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT diagram (page 6)
Fig. 7

Event Counter Offset Security Alarm Out 10 Security Alarm Acknowledge 11 Status In 12 Status Out 13 Test In 14 Test Out 15 Audible Silenced 16 Audible Unsilenced 17 System Reset 18

The second set of data is a collection of bit maps that can be queried to identify the device that has reported the event. When an alarm event arrives from a device, the corresponding bit is set in two separate arrays. The bit in one array indicates the alarm has occurred, and the bit in the other array indicates that the alarm has not yet been acknowledged. When an “alarm clear” event arrives, the bit in the alarm array is cleared. If an “alarm acknowledge” event arrives, the bit in the un-acknowledged array is cleared. All event arrays in a Client driver configuration are optional. To enable an event array, a Map Descriptor must be defined in the configuration using a Map Descriptor message type that corresponds to the array as shown in the following table:

Array Msg_Type Security Alarm Secur Security Alarm Un-Acknowledged Secur_Ack Status Status Test Test Audible (Un)Silenced Audible System Reset Reset

FieldServer FS-8700-40 — 4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT diagram (page 6)
Fig. 8

Array Msg_Type Fire Alarm Fire Fire Alarm Un-Acknowledged Fire_Ack Trouble Alarm Trouble Trouble Un-Acknowledged Trouble_Ack Supervisory Alarm Super Supervisory Un-Acknowledge Super_Ack

FieldServer FS-8700-40 — 4 CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT diagram (page 6)
Fig. 9

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 7 of the FieldServer FS-8700-40 user manual — Configuring the FieldServer as a SBT-FSI Client
Page 7 · click to enlarge
Page 7

1 Map Descriptors are used to determine which bit to set in the Data Array. When an event arrives from a panel, the FieldServer will scan for a Map Descriptor with a Node_ID matching the panel number reported in the event. This Map Descriptor will point to the Data Array to be modified. The location can be further refined if a starting module within the panel is specified in the Block_Number field. Each module represents 256 bits that can be set or reset by an event. A Map Descriptor that is 512 bits long with a starting module (Block_Number) of 3 represents the events for Modules 3 and 4. A Map Descriptor that is 10 bits long will only map the first 10 devices for that module. The combination of Block_Number and Data_Array_Location can be used to map multiple panels with various numbers of modules into a packed array to be read by the Server side of the FieldServer.

2 When the customer receives a Communication FieldServer with the default driver installed, the configuration is set to poll 2 MXL/XLS devices once per second.

3 In addition to the two sets of event counters, alarm bit arrays are set up for 8 modules (1 to 8) per device. If the required configuration falls within this size, only the Server side of the FieldServer needs to be configured. To connect to a device using Modbus RTU protocol, configure the interface as if the FieldServer were another Modbus PLC and create a Map Descriptor to assign a Modbus address (such as 40001) to the Counts Data Array so that it can be read by the Modbus bus master.

4 If the customer has different panel numbers, the Nodes section of the configuration file will need to be changed. To add more panels, add Node entries and Map Descriptors by copying the original ones and modifying the Panel number entries and Data Array offsets. To access panels with more modules, first increase the Data Array lengths. If the extra modules are contiguous, the Map Descriptors for that panel can have their lengths increased also. If there are large gaps in the numbering of the module, it will be more efficient to add additional Map Descriptors by copying the ones that are given and modifying the Block_Number to start at the next existing module number.

5 While the creation of passive Client-side Map Descriptors is optional, error messages will appear when events arrive for which Map Descriptors cannot be found. It is therefore recommended that Map Descriptors (especially ack mapdescs) be allocated even if only as dummies to prevent nuisance error messages.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 8 of the FieldServer FS-8700-40 user manual — Data Arrays
Page 8 · click to enlarge
Page 8

4.1 Data Arrays

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for SBT-FSI communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

FieldServer FS-8700-40 — Data Arrays diagram (page 8)
Fig. 10 · Data Arrays

Data_Array_Format Provide data format. Each Data Array can only take on one format.4 Int16, Uint16, Bit

Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.

FieldServer FS-8700-40 — Data Arrays diagram (page 8)
Fig. 11 · Data Arrays

// Data Arrays Data_Arrays Data_Array_Name ,Data_Format ,Data_Array_Length Event_Counts ,Uint16 ,19 Fire ,Bit ,2048 Fire_UnAck ,Bit ,2048

4Format must be Uint16 or Int16 to see trouble codes.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Example

Page 9 of the FieldServer FS-8700-40 user manual — Client Side Connection Descriptions
Page 9 · click to enlarge
Page 9

4.2 Client Side Connection Descriptions

Section Title Connections Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer P1-P8, R1-R25

Protocol Specify protocol used Cerberus, SBT-FSI

Enables legacy or enhanced protocol.. MXL panels do not currently support Enhanced_Protocol, so this parameter must be set to “No” for MXL. The parameter is normally set to “Yes” for XLS, but may be set to “No” if problems are being experienced.

Yes (XLS) No (MXL)

System_Type Specifies Siemens Panel type MXL, XLS Block_Acks6 Specifies if the driver uses block or individual command acks Yes, No

Fire_Alarms_Hold Specifies if the driver should hold fire alarms until the system reset, or clear on fire alarms going out Yes, No

Baud* Specify baud rate

Parity* Specify parity Even (Vendor limitation)

Data_Bits* Specify data bits 7 (Vendor limitation)

Stop_Bits* Specify stop bits 1 (Vendor limitation) Handshaking7 Specify hardware handshaking * None

0-32000 seconds, 1 second Example

Poll _Delay* Time between internal polls

FieldServer FS-8700-40 — Client Side Connection Descriptions diagram (page 9)
Fig. 12 · Client Side Connection Descriptions

// Client Side Connections Connections Port ,Protocol ,Baud ,Parity ,Data_Bits ,Poll_Delay P1 ,SBT-FSI ,19200 ,Even ,7 ,0.100s

5 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. 6 Refer to the Advanced Driver Manual for usage. This function not enabled on standard driver. 7 Handshaking is not supported.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Enhanced_Protocol · 19200 (Vendor limitation)

Page 10 of the FieldServer FS-8700-40 user manual — Client Side Node Descriptors
Page 10 · click to enlarge
Page 10
FieldServer FS-8700-40 — Client Side Node Descriptors diagram (page 10)
Fig. 13 · Client Side Node Descriptors

Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Node_ID Panel number 1-99 Protocol Specify protocol used Cerberus, SBT-FSI

Port Specify on which port the device is connected to the FieldServer P1-P8, R1-R21

FieldServer FS-8700-40 — Client Side Node Descriptors diagram (page 10)
Fig. 14 · Client Side Node Descriptors

// Client Side Nodes Nodes Node_Name ,Node_ID ,Protocol ,Port Panel1 ,1 ,SBT-FSI ,P1

4.4 Client Side Map Descriptors

4.4.1 FieldServer Related Map Descriptor Parameters

Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters

Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above

Rdbc for Msg_Type: Poller, Analog_Volts, Analog_Sense, Analog_Thres Passive for Msg_Type: Fire, Fire_Ack, Trouble, Trouble_Ack, Secur, Secur_Ack, Super, Super_Ack, Status, Test Audible, Reset Awt for Msg_Type: Entity_Arm_Disarm; Entity_Activate_Deact

Function Function of Client Map Descriptor

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Example · Data_Array_Name

Page 11 of the FieldServer FS-8700-40 user manual — Driver Related Map Descriptor Parameters
Page 11 · click to enlarge
Page 11

4.4.2 Driver Related Map Descriptor Parameters

Column Title Function Legal Values

Node_Name Name of Node to fetch or store data from

One of the node names specified in “Client Node Descriptor” above

Starting module number within panel. There are 256 points per module.

1. 256

Sub_Module Sub module number for XLS systems only 0 – 99

Component_Address Component address for XLS systems only 0 – 99

Length of Map Descriptor specifies number of points. There are 256 points per module.

1. 10000

Indicates a “poller” Map Descriptor or identifies the type of event message this Map Descriptor will handle.

Poller; Fire; Fire_Ack; Trouble; Trouble_Ack; Super; Super_Ack; Secur; Secur_Ack; Status; Test; Audible; Reset; Analog_Volts; Analog_Sense; Analog_Thres; Entity_Arm_Disarm8; Entity_Activate_Deact9

0. devices 1-60 1 : devices 61-121 2 : devices 122-182 3 : devices 183-243 4 : devices 244-252

Analog_Device Indicates range of device data to be requested by analogs

This field allows you to set the start address of a MXL or XLS point in a Map Descriptor.

0. 255

Used to indicate the type of Entity on the panel.. . Refer to Appendix A.6 for more information

Inputs, Outputs, (If all elements are Input or Output) OR specify each element of the entity individually e.g. IOIOIOO

De-energize, Energize, (If all elements are Energize or De-energize) OR specify each element of the entity individually, e.g. EDED---DED

Used to control the entity on the panel. Refer to Appendix A.6 for more information.

4.4.3 Timing Parameters

Column Title Function Legal Values Scan_Interval* Rate at which data is polled ≥0.001s ,1.0s

8 Refer to Appendix A.6 9 Refer to Appendix A.5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Show 6 more labels / short text on this page
Block_Number · Length · Msg_Type · Block_Offset · Entity_Types · Entity_Energizations
Page 12 of the FieldServer FS-8700-40 user manual — Map Descriptor example 1 - Monitoring a MXL/XLS Device for Events
Page 12 · click to enlarge
Page 12

4.4.4 Map Descriptor example 1 - Monitoring a MXL/XLS Device for Events

To monitor a MXL/XLS device we need only one “poller” Map Descriptor as shown below. The function of this Map Descriptor’s is to continuously check the MXL device for events from panels. Only one poller Map Descriptor per FieldServer port is required when monitoring more than one MXL/XLS device. The Node_Name will indicate on which port this Map Descriptor resides.

// Client Side Map Descriptors Map_Descriptors

Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type CD_Poller1 ,Event_Counts1 ,0 ,RDBC ,Panel1 ,1 ,19 ,poller

Specify length in multiples of 19 events according to Block Number used.

Choose a Node_Name from the passive Map Descriptors in the next section to specify the port on which this poller will be active.

Specifies Data Array that will hold event counters. Data Array length must be equal or greater than Data Array offset plus Map Descriptor length.

Specifies offset into event counters Data Array where event counts will be stored.

Specifies lowest panel number from which events will be received. Refer to Appendix A for more information.

Specify poller message type for this Map Descriptor.

Refer to Appendix A for more information.

CD – Client Descriptor

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 13 of the FieldServer FS-8700-40 user manual — Map Descriptor example 1 - Monitoring a MXL/XLS Device for Events
Page 13 · click to enlarge
Page 13

Passive Map Descriptors must be added for each event per panel to be monitored:

// Client Side Map Descriptors Map_Descriptors

Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type CD_Fire1 ,Fire ,0 ,Passive ,Panel1 ,1 ,1024 ,Fire CD_Fire_Ack1 ,Fire_Ack ,0 ,Passive ,Panel1 ,1 ,1024 ,Fire_Ack CD_Trouble1 ,Trouble ,0 ,Passive ,Panel1 ,1 ,1024 ,Trouble CD_Trouble_Ack1 ,Trouble_Ack ,0 ,Passive ,Panel1 ,1 ,1024 ,Trouble_Ack CD_Super1 ,Super ,0 ,Passive ,Panel1 ,1 ,1024 ,Super CD_Super_Ack1 ,Super_Ack ,0 ,Passive ,Panel1 ,1 ,1024 ,Super_Ack CD_Secur1 ,Secur ,0 ,Passive ,Panel1 ,1 ,1024 ,Secur CD_Secur_Ack1 ,Secur_Ack ,0 ,Passive ,Panel1 ,1 ,1024 ,Secur_Ack CD_Status1 ,Status ,0 ,Passive ,Panel1 ,1 ,1024 ,Status CD_Test1 ,Test ,0 ,Passive ,Panel1 ,1 ,1024 ,Test CD_Audible1 ,Audible ,0 ,Passive ,Panel1 ,- ,1 ,Audible CD_Reset1 ,Reset ,0 ,Passive ,Panel1 ,- ,1 ,Reset CD – Client Descriptor

Node Name specifies the panel number for which events will be stored.

Block Number specifies the starting module number under which points are mapped.

Length specifies the number of points. There are 256 points per module. A length of 1024 holds points for 4 modules.

1 All passive Map Descriptors are optional. Specific Map Descriptors may be defined for particular events to be monitored as per the Msg_Type. Should events happen for which no Map Descriptors are defined, error messages will occur on the FieldServer. It may therefore be useful to add dummy Map Descriptors especially for ack responses to prevent nuisance error messages.

2 Passive Map Descriptors with Node_Name the same as the poller Map Descriptor will only be able to store events from a panel with the same Node_ID e.g. Node_ID of 1 will only store events from panel 1. To store events from panel 2, it is necessary to add passive Map Descriptors with Node ID of 2 etc. Do not add poller Map Descriptors for other panels.

Most SBT-FSI panels have device point numbers starting at one instead of zero. The FieldServer MXL driver reserves Data Array offset zero for points with device numbers of zero although they are currently not used. Triggering the first alarm point on a MXL panel will thus result in a point status change at Data_Array_Offset of one instead of zero.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 14 of the FieldServer FS-8700-40 user manual — Map Descriptor example 2 – Monitoring Analog Loop Devices
Page 14 · click to enlarge
Page 14

4.4.5 Map Descriptor example 2 – Monitoring Analog Loop Devices

Analog devices on a loop can be monitored for detector voltage, sensitivity voltage and threshold voltage using three analog Map Descriptors:

// Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type ,Analog_Device ,Scan_Interval CD_Analog_Volts1 ,Analog_Volts ,0 ,Rdbc ,Panel1 ,1 ,60 ,Analog_Volts ,0 ,300s CD_Analog_Sens1 ,Analog_Sense ,0 ,Rdbc ,Panel1 ,1 ,60 ,Analog_Sense ,0 ,300s CD_Analog_Thres1 ,Analog_Thres ,0 ,Rdbc ,Panel1 ,1 ,60 ,Analog_Thres ,0 ,300s

0. devices 1-60 1 : devices 61-121 2 : devices 122-182 3 : devices 183-243 4 : devices 244-252

Scan Interval on analog pollers may not be shorter than 300s to prevent flooding the Foreign Systems Interface.

Use Float Data Arrays for the analog Map Descriptors to get the full analog value.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 15 of the FieldServer FS-8700-40 user manual — 5 ADVANCED CLIENT CONFIGURATION – USING BIDIRECTIONAL CAPABILITY
Page 15 · click to enlarge
Page 15

5 ADVANCED CLIENT CONFIGURATION – USING BIDIRECTIONAL CAPABILITY

The driver has the ability to:

  • Ack Fire, Trouble, Supervisory and Security Alarms.
  • (Un)Silence the Audible.
  • Reset the MXL/XLS system.
  • Set the MXL/XLS system’s date and time.

Please refer to the Advanced Driver Manual for using and enabling these functions.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 16 of the FieldServer FS-8700-40 user manual — 6 CONFIGURING THE FIELDSERVER AS A SBT-FSI SERVER
Page 16 · click to enlarge
Page 16

6 CONFIGURING THE FIELDSERVER AS A SBT-FSI SERVER

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a SBT-FSI Client.

The driver can be used to emulate a MXL/XLS Server device. Other protocol drivers could then poll other remote devices and access the local MXL/XLS Server data to set or clear events. In this configuration an existing SBT-FSI system could be replaced with an MXL/XLS emulation. Existing Clients could poll the emulation driver on the FieldServer to get the same data as from a conventional MXL/XLS Server.

Up to 99 panels can be emulated with the driver. A Map Descriptor has to be defined for each type of remote device that would normally exist in a MXL/XLS Server. The following types can be used:

Device Type Fire Alarm In Fire Alarm Out Fire Alarm Acknowledge Trouble In Trouble Out Trouble Acknowledge Supervisory In Supervisory Out Supervisory Acknowledge Security Alarm In Security Alarm Out Security Alarm Acknowledge Status Event Test Event Analog Voltage Analog Sensitivity Voltage Analog Threshold Voltage The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for SBT-FSI communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 17 of the FieldServer FS-8700-40 user manual — Server Side Connection Descriptors
Page 17 · click to enlarge
Page 17

6.1 Server Side Connection Descriptors

Section Title Connections Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer P1-P8, R1-R210 Protocol Specify protocol used Cerberus, SBT-FSI

Enables legacy or enhanced protocol.. MXL panels do not currently support Enhanced_Protocol, so this parameter must be set to “No” for MXL. The parameter is normally set to “Yes” for XLS, but may be set to “No” if problems are being experienced.

Yes (XLS) No (MXL)

System_Type Specifies Siemens Panel type MXL, XLS Echo Specifies if the server should echo the client’s polls Yes, No

110. 115200, standard baud rates only, 19200

Baud* Specify baud rate

Parity* Specify parity Even, Odd, None, Mark, Space Data_Bits* Specify data bits 7, 8

Stop_Bits* Specify stop bits 1 (Vendor limitation) Handshaking11 Specify hardware handshaking * None

Specifies time FieldServer will reserve Server side connection while waiting for the Client side to update data in Data_Array (if necessary)

>1.0s

FieldServer FS-8700-40 — Server Side Connection Descriptors diagram (page 17)
Fig. 15 · Server Side Connection Descriptors

// Server Side Connections Connections Port ,Protocol ,Baud ,Parity ,Data_Bits P1 ,SBT-FSI ,19200 ,Even ,7

10 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. 11 Handshaking is not supported.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Enhanced_Protocol · Server_Hold_Timeout · Example

Page 18 of the FieldServer FS-8700-40 user manual — Server Side Node Descriptors
Page 18 · click to enlarge
Page 18
FieldServer FS-8700-40 — Server Side Node Descriptors diagram (page 18)
Fig. 16 · Server Side Node Descriptors

Up to 32 alphanumeric characters Node_ID Panel number 1-99 Protocol Specify protocol used Cerberus, SBT-FSI

Specifies time FieldServer will reserve Server side connection while waiting for the Client side to update data in Data_Array (if necessary)

// Server Side Nodes Nodes Node_Name ,Node_ID ,Protocol ,12 Panel1 ,1 ,SBT-FSI

6.3 Server Side Map Descriptors

FieldServer FS-8700-40 — Server Side Node Descriptors diagram (page 18)
Fig. 17 · Server Side Node Descriptors

Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters

One of the Data Array names from “Data Array” section above

Data_Array_Name Name of Data Array where point data is to be fetched from

Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above Function Function of Server Map Descriptor Server

Specifies time FieldServer will reserve Server side connection while waiting for the Client side to update data in Data_Array (if necessary)

12 Note that no port information is necessary on Server side.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 19 of the FieldServer FS-8700-40 user manual — Driver Specific Map Descriptor Parameters
Page 19 · click to enlarge
Page 19

6.3.2 Driver Specific Map Descriptor Parameters

Column Title Function Legal Values

Node_Name Name of Node or panel for which this Map Descriptor holds points

One of the node names specified in “Client Node Descriptor” above

Module number (Note that this only specifies one module number as opposed to a starting module number as in the Client Map Descriptor)

1. 256

Sub_Module Sub module in XLS system 0 – 99 Component_Address Component address in XLS system 0 – 99

Length of Map Descriptor Specifies number of points for the indicated module. Note that MXL systems typically has only 256 points per module.

1. 256

Fire; Fire_Ack; Trouble; Trouble_Ack; Secur; Secur_Ack; Super; Super_Ack; Status; Test; Audible; Reset; Analog_Volts; Analog_Sense; Analog_Thres

Type of event message Note that a poller message type may not be used in a Server Map Descriptor.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Block_Number · Length · Msg_Type

Page 20 of the FieldServer FS-8700-40 user manual — Map Descriptor example 1 - Emulating a MXL/XLS device with events
Page 20 · click to enlarge
Page 20

6.3.3 Map Descriptor example 1 - Emulating a MXL/XLS device with events

The following list of Map Descriptors emulates a MXL Server,

SD – Server Descriptor

// Server Side Map Descriptors Map Descriptors

Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type SD_Fire1 ,Fire ,0 ,Server ,Panel1 ,1 ,256 ,Fire SD_Fire_Ack1 ,Fire_Ack ,0 ,Server ,Panel1 ,1 ,256 ,Fire_Ack SD_Trouble1 ,Trouble ,0 ,Server ,Panel1 ,1 ,256 ,Trouble SD_Trouble2 ,Trouble ,256 ,Server ,Panel1 ,2 ,256 ,Trouble SD_Trouble_Ack1 ,Trouble_Ack ,0 ,Server ,Panel1 ,1 ,256 ,Trouble_Ack SD_Super1 ,Super ,0 ,Server ,Panel1 ,1 ,256 ,Super SD_Super_Ack1 ,Super_Ack ,0 ,Server ,Panel1 ,1 ,256 ,Super_Ack SD_Secur1 ,Secur ,0 ,Server ,Panel1 ,1 ,256 ,Secur SD_Secur_Ack1 ,Secur_Ack ,0 ,Server ,Panel1 ,1 ,256 ,Secur_Ack SD_Status1 ,Status ,0 ,Server ,Panel1 ,1 ,256 ,Status SD_Audible1 ,Audible ,0 ,Server ,Panel1 ,- ,1 ,Audible SD_Reset1 ,Reset ,0 ,Server ,Panel1 ,- ,1 ,Reset

Specifies the number of points represented within the indicated module.

Specifies the panel number being emulated by this Server Map Descriptor.

Specifies the module number. A typical Cerberus Server has 256 points per module.

1 MXL/XLS Server Map Descriptor fields differ in many respects from MXL/XLS Client Map Descriptors. Please follow the examples clearly and read all notes to ensure a working configuration. No poller Map Descriptors may be defined in a configuration file that is used to configure a MXL/XLS Server.

2 Only one module specified by Block_Number can be emulated with a Server Map Descriptor whereas a Client Map Descriptor specifies a starting module number with one module for every 256 counts of the Map Descriptor length. You have to use separate Map Descriptors for each module to emulate when doing a Server configuration.

3 More than one Msg_Type Map Descriptor may be used to represent other modules.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 21 of the FieldServer FS-8700-40 user manual — Map Descriptor example 2 - Emulating a MXL/XLS device with analogs
Page 21 · click to enlarge
Page 21

6.3.4 Map Descriptor example 2 - Emulating a MXL/XLS device with analogs

The following list of Map Descriptors emulate a MXL Server:

FieldServer FS-8700-40 — Map Descriptor example 2 - Emulating a MXL/XLS device with analogs diagram (page 21)
Fig. 18 · Map Descriptor example 2 - Emulating a MXL/XLS devic…

// Server Side Map Descriptors Map Descriptor Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type SD_Analog_Volts1 ,Volts ,0 ,Server ,Panel1 ,1 ,252 ,Analog_Volts SD_Analog_Sense1 ,Sense ,0 ,Server ,Panel1 ,1 ,252 ,Analog_Sense SD_Analog_Thres1 ,Thres ,0 ,Server ,Panel1 ,1 ,252 ,Analog_Thres

Use Float Data Arrays for the analog Map Descriptors to get the full analog value.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 22 of the FieldServer FS-8700-40 user manual — Advanced Topics
Page 22 · click to enlarge
Page 22

Appendix A. Advanced Topics

Appendix A.1. Specifying a Poller Map Descriptor length

The poller Map Descriptor is responsible for checking a remote MXL/XLS device for events. When events are received the poller Map Descriptor increments counters at various offsets in the Data Array specified by the poller Map Descriptor. The offsets and their meanings are explained under the Client configuration section of this Driver Manual.

The poller Map Descriptor’s Data Array contains sets of 19 elements or counters. Each set of counters represents the events from a panel. The Block_Number is used to specify the lowest panel number from which events will be received. The highest Node_ID of any passive Map Descriptor on the same port as the poller Map Descriptor specifies the highest panel number from which events will be received. The poller Map Descriptor’s length has to be at least 19 and has to incremented by 19 for every extra panel above the Block_Number from which events will be received.

If a poller Map Descriptor length is set below 19 and for example, event “System Reset” is received which needs to be mapped at offset 18 in the Data Array, the following kernel message will be printed:

“Cannot store alarm event type counts!”, 11010” ‘offset=%u,da=%s”

Example 1Only receive events from panel 7
  • Passive event Map Descriptor’s Node Id = 7 (X)
  • Poller Map Descriptor’s Block_Number = 7 (Y)
  • Poller Map Descriptor’s Length = (X – Y) * 19 + 19 = 19
  • Event counters for panel 7 will reside in the first 19 elements.
Example 2Receive events from panel 7 and 6
  • Passive event Map Descriptor’s Node Id = 7 (X)
  • Poller Map Descriptor’s Block_Number = 6 (Y)
  • Poller Map Descriptor’s Length = (X – Y) * 19 + 19 = 38
  • Event counters for panel 6 will reside in the first 19 elements and those for panel 7 in the next 19 elements.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 23 of the FieldServer FS-8700-40 user manual — Interpreting Panel Error Messages
Page 23 · click to enlarge
Page 23

Appendix A.2. Interpreting Panel Error Messages

A NAK is sent by the panel when it is unable to respond to a message. The format will be as follows:

T02> DRV-> CERPanel replied with NAK on last message! T02> DRV-> CER : Reason: 1

The following table lists the reason for the failure and the suggested corrective action. Note that the messages are generated by the panel, not the FieldServer.

Reason # Error Corrective Action

Reason 1 Checksum or Parity fail

Ensure connection baudrate, start, stopbits and parity match the panel's settings Reason 2 Receive buffer full Increase scan interval on the poller Map Descriptor.

Reason 3 Syntax Error Check integrity of physical connection to panel, route cables away from electromagnetic sources that can generate noise.

Reason 4 Unrecognized message failure Replace hardware?

Appendix A.3. Obtaining Point Addresses from the panel report

In order to configure the FieldServer to capture data from the Panel, the point addresses being used in the panel need to be identified. The Panel report that can be printed out from the panel can be used for this purpose, but matching the Report parameters with the FieldServer configuration parameters is not a trivial exercise. The following notes should assist in identifying the addresses needed for FieldServer configuration

  • The preamble to the report is not relevant to the FieldServer Driver.
  • The first Module can be identified by the title NET Address =1. This corresponds to FieldServer’s “Block 1”.
  • The Module Subaddress corresponds to individual points in the Block Array.

This information is depicted in the following file extract: NET ADDR: 1 ==> ALD-2 2 Analog Loop Module Page: 5

Corresponds to Block Number 1

Corresponds to Block Array point 1

Module Subaddress > 1

DEVICE TYPE > TRI-60/TRX-2/3 1 Switch Input

Message > RCP-01 Trouble Input MM-1

Switch Contact Type > N.O.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

=============================================================================== · Usage > TROUBLE

Page 24 of the FieldServer FS-8700-40 user manual — Using Trouble Codes
Page 24 · click to enlarge
Page 24

Appendix A.4. Using Trouble Codes

In order to see the trouble codes for incoming troubles it is necessary to use a Uint16 or Int16 data array for the trouble instead of the normal Bit. When the driver stores a trouble code of for example 15 into a Bit data array, it will be displayed as 1 since Bit only holds either a zero or a one value. Using a Uint16 or Int16 data array will ensure the value of 15 is displayed.

The following information is taken from Siemens Fire Safety documentation

These codes are sent in Field 5 of the Trouble in, Trouble out and Trouble Acknowledge messages 24H, 25H and 26H. Each code is sent as up to 3 ASCII bytes. Leading zeros are not sent. The Request Trouble Type message (43H) can be used to obtain the text strings shown below for each of these codes. The trouble text string is returned in the Trouble Type message (53H).

Trouble Type Trouble Type Text 0 1 Multiple Response 2 Communication Error 3 Input Dev. Response too low 4 Device Receive Error 5 Dev Detected Waveform Error 6 Not Responding 7 Not Responding 8 Unspecified Dev. Responding 9 Incorrect ID 10 INPUT DE-ISOLATED 11 INPUT ISOLATED 12 Input Disarmed 13 Addressable Relay disarmed 14 Relay Disarmed 15 Signal Circuit Disarmed 16 Solid State Output Disarmed 17 Relay Supervision Failure 18 Signal Circuit Loop Open 19 Loop Disarmed 20 Class A Trouble 21 Relay Driver Inoperative 22 Signal Circuit Shorted 23 ALD Reception Error 24 Coil Open 25 Zone Power Off 26 Power Cycling 27 Short Circuit

Trouble Type Trouble Type Text 28 Open Circuit 29 Voltage Low 30 Zone Power Loss 31 Loop Node 32 Not defined 33 Multiple Response 34 MOI-1 Local Trouble 35 MOI-1 Zone Trouble 36 No database – default in use 37 Too Many ALD-2’s 38 PSR-1 Driver Disarmed 39 Output Disarmed 40 Not Responding 41 Unspecified Module Responding 42 Communication Failure 43 RAM Failure 44 ROM Failure 45 A/D Convert Fail 46 Single Module Zone Code 47 Command Not Valid 48 Network A Pair Fail 49 50 Loss of 24V Input Power 51 Act Power Voltage Low 52 Default Trouble Active 53 Network Disabled 54 Alarm from Isolated Device 55 Printer off-line

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

MXL/XLS Trouble Codes

Page 25 of the FieldServer FS-8700-40 user manual — Using Trouble Codes
Page 25 · click to enlarge
Page 25

Trouble Type Trouble Type Text 56 Warm Reset 57 Printer out of Power 58 Tamper Switch 59 Battery Backup Invalid 60 Positive Ground Fault 61 Negative Ground Fault 62 AC Fail/brownout 63 System Signal Power Failure 64 Battery Fuse/Wiring Open 65 66 24 Volt Supply Over/Under 67 High Battery Voltage 68 Battery Charger Off 69 24 Volts on Battery Backup 70 Low Battery voltage 71 Watchdog Triggered 72 Device LED Manually Activated 73 Alarm queue full 74 Supervisory queue full 75 Trouble queue full 76 Security queue full 77 Memory error in Ram text 78 Memory error in ROM text 79 Aux Pwr Class A Fail Pos 80 Aux Pwr Class A Fail Neg 81 Supervisory Point 82 Security Point 83 BELL 2 ISOLATED 84 BELL 2 DE-ISOLATED 85 Configuration Error 86 Addressable Relay Isolated 87 Relay Isolated 88 Single Circuit Isolated 89 Solid State Output Isolated 90 Class A Fault 91 Noise Fault 92 MOI-1 Local Fault 93 MOI-1 Zone Isolated 94 PSR-1 Driver Isolated 95 Fault queue full 96 Isolated Alarm queue full 97 Isolated Alarm point 98 Requires Service 99 MVP General Trouble 100 Valve Tamper queue full

Trouble Type Trouble Type Text 101 Valve Tamper Point 102 WALKTEST Activated 103 Function Recursion Limit Exceeded 104 Trouble Causing Input 105 Carrier Loss 106 107 Missing Device ID Response 108 Annunciator Trouble 109 CMI-300 general trouble 110 ROM SW version error 111 Lamp Supervision Trouble 112 Keyswitch Activated 113 Ancillary Cntrl Funcs Isolated 114 Ancillary Cntrl Funcs De-Isolated 115 Pre-dirty Analog volt reached 116 IEC limit reached. Service Req 117 IEC memory error 118 NET-7 General Trouble 119 Network B Pair Failure 120 MOI-1 Voice System Trouble 121 Style 4 Network mode 122 Aux. RS232 Transmit Fail 123 Module Address Buffer Fail 124 Incorrect Enclosure 125 OCC-1 General Trouble 126 OCC-1 Degrade Mode 127 Backup Tone Card (BTC) 128 Daily detector test abnormal 129 Event log 80% full 130 Event log 90% full 131 Log FULL, events will be lost 132 Audio Riser 1 Trouble 133 Audio Riser 2 Trouble 134 Audio Riser 3 Trouble 135 Mic Key Trouble 136 Mic Pre-amp Trouble 137 Tone Generator Trouble 138 Mic Input Trouble 139 Telephone Riser Trouble 140 Mic Key Trouble 141 Amplifier 1 Trouble 142 Amplifier 2 Trouble 143 Amplifier 3 Trouble 144 Amplifier 1 Backed Up 145 Amplifier 2 Backed Up

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 26 of the FieldServer FS-8700-40 user manual — Using Trouble Codes
Page 26 · click to enlarge
Page 26

Trouble Type Trouble Type Text 146 Amplifier 3 Backed Up 147 Multiple Response 148 Communication Error 149 Not Responding 150 Unspecified Sub-module Responding 151 Incorrect ID 152 Audio Riser 1 Class A Active 153 Audio Riser 2 Class A Active 154 Audio Riser 3 Class A Active 155 Backup Amplifier Trouble 156 Daily Detector Test Abnormal 157 Low IEC voltage. Service Req. 158 Audio Output Shorted 159 Audio Output Class A Active 160 Amplifier 1 Signal Loss 161 Amplifier 2 Signal Loss 162 Amplifier 3 Signal Loss 163 Generic Input Terminal 164 DMU 1 Failure 165 DMU 2 Failure 166 Out of RAM. Call factory 167 Incorrect Node Address 168 Not Responding 169 Unspecified Node Responding 170 Node Disconnected 171 Network CSGM Upload Needed 172 Style 7 Network Mode 173 Network input disarmed 174 Out of task – Call factory 175 Stack Fault – Call factory 176 Software Key Violation 177 Airflow too low 178 Airflow too high 179 Detector Trouble 180 AnaLASER General Trouble 181 Pre1 level 182 Pre2 level 183 Incorrect library version 184 Out of calibration 185 AnaLASER Power Trouble 186 Pre-alarm 187 +15volt fault 188 Strobe power fault

Trouble Type Trouble Type Text 189 Audio fault iso-St 7Tx 190 Audio fault iso-St 7Rx 191 Audio fault iso-St 4Tx 192 Audio fault iso-St 4Rx 193 Multiple Response 194 Global audio riser-St 7 195 Global audio riser-St 4 196 Local audio riser 197 Database Out of Date 298 ASD disabled for test 199 Sys halt – too many ALD/ACM 200 DMC-1 in record mode 201 DMC-1 tone trouble 202 DMC-1 phrase trouble 203 Troubles summarized 204 205 Incorrect custom phrase control 206 Remote node disconnected 207 History manually turned off 208 History manually turned on 209 History manually erased 210 Memory upgrade required 211 Event queue corrupt 212 Current sensor failure 213 EEprom error 214 No application firmware 215 Component disarmed 216 Zone 1 open 217 Zone 2 open 218 Zone 1 short 219 Zone 2 short 220 Zone 1 Class A return fault 221 Zone 2 Class A return fault 222 Input source malfunction 223 Over current fault 224 Log failure, events lost 225 24V 4amp supply shutdown 226 24V 12amp supply shutdown 227 Backplane power shutdown 228 No battery detected 229 Thermistor Trouble 230 Configuration process failure 231 Device(s) with no address

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 27 of the FieldServer FS-8700-40 user manual — Activating and De-activating Entities
Page 27 · click to enlarge
Page 27

Appendix A.5. Activating and De-activating Entities

These examples demonstrate the methodology to activate or de-activate equipment on the MXL/XLS panel as per the SBT-FSI protocol specification. This relates to the opcode Activate/Deactivate Entity 0x7b/0x7c.

The configuration example in Section 4 can be modified as per the example below for Activating and De-activating Entities on the MXL Panel.

// Client Side Connections // Connections Port ,Baud ,Parity ,Data_Bits ,Line_drive_on ,Line_drive_off ,Enhanced_Protocol ,Protocol ,System_Type P1 ,19200 ,Even ,7 ,0.001 ,0.001 ,No ,Cerberus ,MXL

FieldServer FS-8700-40 — Activating and De-activating Entities diagram (page 27)
Fig. 19 · Activating and De-activating Entities

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Block_Offset ,Length ,Msg_Type POLLER_1 ,2.0s ,Counts_1 ,0 ,Rdbc ,Panel1 ,1 ,0 ,19 ,Poller // this is for activation and deactivation of pseudo points PNL_1_Act_Entity ,0s ,Act_Ent ,0 ,Awt ,Panel1 ,1 ,1 ,10 ,Entity_Activate_Deact The configuration example in Section 4 can be modified as per the example below for Activating and De-activating Entities on the XLS panel.

FieldServer FS-8700-40 — Activating and De-activating Entities diagram (page 27)
Fig. 20 · Activating and De-activating Entities
FieldServer FS-8700-40 — Activating and De-activating Entities diagram (page 27)
Fig. 21 · Activating and De-activating Entities

// Client Side Connections // Connections Port ,Baud ,Parity ,Data_Bits ,Line_drive_on ,Line_drive_off ,Enhanced_Protocol ,Protocol ,System_Type P1 ,19200 ,Even ,7 ,0.001 ,0.001 ,Yes ,Cerberus ,XLS

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Block_Offset ,Length ,Msg_Type POLLER_1 ,2.0s ,Counts_1 ,0 ,Rdbc ,Panel1 ,1 ,- ,0 ,19 ,Poller // this is for activation and deactivation of pseudo points PNL_1_Act_Entity ,0s ,Act_Ent ,0 ,Awt ,Panel1 ,10 ,Entity_Activate_Deact

FieldServer FS-8700-40 — Activating and De-activating Entities diagram (page 27)
Fig. 22 · Activating and De-activating Entities

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 28 of the FieldServer FS-8700-40 user manual — Arming and De-Arming Entities
Page 28 · click to enlarge
Page 28

Appendix A.6. Arming and De-Arming Entities

This example demonstrates the methodology to arm or disarm equipment on the MXL/XLS panel as per the SBT-FSI protocol specification. This relates to the opcodes Disarm/manuallycontrol entity – opcode 0x77; Arm entity – opcode 0x78,

The configuration example in Section 4 can be modified as per the example below for Arming and De-arming Entities on the MXL Panel.

// Data Arrays // Data_Arrays Data_Array_Name ,Data_Format ,Data_Array_Length Counts_1 ,Uint16 ,19 Arm_Disarm_Ent ,Bit ,10

// Client Side Connections // Connections Port ,Baud ,Parity ,Data_Bits ,Line_Drive_On ,Line_Drive_Off ,Enhanced_Protocol ,Protocol ,System_Type P1 ,19200 ,Even ,7 ,0.001 ,0.001 ,No ,Cerberus ,MXL

FieldServer FS-8700-40 — Arming and De-Arming Entities diagram (page 28)
Fig. 23 · Arming and De-Arming Entities

// Client Side Map Descriptors // Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type POLLER_1 ,2.0s ,Counts_1 ,0 ,Rdbc ,Panel1 ,1 ,19 ,Poller

FieldServer FS-8700-40 — Arming and De-Arming Entities diagram (page 28)
Fig. 24 · Arming and De-Arming Entities

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function .Node_Name ,Block_Number ,Block_Offset ,Length ,Msg_Type ,Entity_Types PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,1 ,1 ,10 ,Entity_Arm_Disarm ,Inputs

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Block_Offset ,Length ,Msg_Type ,Entity_Types ,Entity_Energizations PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,1 ,1 ,10 ,Entity_Arm_Disarm ,Outputs ,De-energize

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Block_Offset ,Length ,Msg_Type ,Entity_Types ,Entity_Energizations PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,1 ,1 ,10 ,Entity_Arm_Disarm ,Outputs ,Energize

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Page 29 of the FieldServer FS-8700-40 user manual — Arming and De-Arming Entities
Page 29 · click to enlarge
Page 29

The configuration example in Section 4 can be modified as per the example below for Arming and De-arming Entities on the XLS panel.

// Data Arrays // Data_Arrays Data_Array_Name ,Data_Format ,Data_Array_Length Counts_1 ,Uint16 ,19 Arm_Disarm_Ent ,Bit ,10

// Client Side Connections // Connections Port ,Baud ,Parity ,Data_Bits ,Line_Drive_On ,Line_Drive_Off ,Enhanced_Protocol ,Protocol ,System_Type P1 ,19200 ,Even ,7 ,0.001 ,0.001 ,Yes ,Cerberus ,XLS

FieldServer FS-8700-40 — Arming and De-Arming Entities diagram (page 29)
Fig. 25 · Arming and De-Arming Entities

// Client Side Map Descriptors // Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Length ,Msg_Type POLLER_1 ,2.0s ,Counts_1 ,0 ,Rdbc ,Panel1 ,1 ,19 ,Poller

FieldServer FS-8700-40 — Arming and De-Arming Entities diagram (page 29)
Fig. 26 · Arming and De-Arming Entities

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Component_Address ,Block_Offset ,Length ,Msg_Type ,Entity_Types PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,10 ,Entity_Arm_Disarm ,Inputs

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Component_Address ,Block_Offset ,Length ,Msg_Type ,Entity_Types ,Entity_Energizations PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,10 ,Entity_Arm_Disarm ,Outputs ,De-energize

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Component_Address ,Block_Offset ,Length ,Msg_Type ,Entity_Types ,Entity_Energizations PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,10 ,Entity_Arm_Disarm ,Outputs ,Energize

Map_Descriptors Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Component_Address ,Block_Offset ,Length ,Msg_Type ,Entity_Types ,Entity_Energizations PNL_1_Arm_Disarm ,0s ,Arm_Disarm_Ent ,0 ,Awt ,Panel1 ,10 ,Entity_Arm_Disarm ,IOIOIOIIOI , EDED---DED

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-40

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-40

Be the first to ask — other owners or our team will answer.

Original document

FieldServer FS-8700-40 manual PDF

29 pages·379 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…