4) Wiring quick connect terminals (LS-140A) 1) ROMEX connector Installation of a High temperature vent limit switch is recommended for LP and Natural gas fired power vented and natural draft water heaters. This device is installed to limit the vent temperature in either plastic pipe (1400 F temperature limit) or B vent installations (5500 F temperature limit) caused by scaled up tanks and/or inadequate venting. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.
The Field Controls High temperature vent limit switch MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.
The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of gas appliances, who is experienced in such work, familiar with all the precautions required, and has complied with the requirements of the authority having jurisdiction.
Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.
MODEL P/N CONTACT MATERIAL
TYPE APPLICATION AMPS VOLTS
LS-140A 46564100 SILVER 15 A 120 AC 140 AUTOMATIC SPDT PLASTIC VENT APPLICATIONS LS-550A 46564200 SILVER 15 A 120 AC 550 AUTOMATIC SPDT B-VENT APPLICATIONS

2630 Airport Road · Kinston, NC 28504

INSTALLATION OF LS-140A SWITCH ON A POWER VENTED WATER HEATERS WITH PLASTIC PIPE




Wiring the LS-140A Limit switch
Wire the High temperature vent limit switch in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes. THE UNIT MUST BE GROUNDED WHEN WIRED TO ANY 120 VOLT CONTROLS. Check ground circuit to make certain that the unit has been properly grounded. The wiring should be protected by an over current circuit device rated at 15 amperes. Caution must be taken to ensure that the wiring does not come into contact with any heat source. All line voltage and safety control circuits, between the vent damper and the appliance, MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent methods.

BEFORE STARTING WIRING, TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE AT THE APPLIANCE SERVICE SWITCH OR CIRCUIT BREAKER!!
Page 2

connectors on the solenoid valve and route the wires from the solenoid valve connections to the common terminal and the normally close (NC) terminal on the LS-140A limit switch (See Figure 8). Also route installers supplied green grounding wire from the LS-140A limit switch and connect to any convenient grounding surface at the gas valve.



INSTALLATION OF LS-550A SWITCH ON A NATURAL DRAFT WATER HEATER WITH B-VENT


Page 3

Wiring the LS-550A Limit switch
Wire the High temperature vent limit switch in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes. THE UNIT MUST BE GROUNDED WHEN WIRED TO ANY 120 VOLT CONTROLS. Check ground circuit to make certain that the unit has been properly grounded. The wiring should be protected by an over current circuit device rated at 15 amperes. Caution must be taken to ensure that the wiring does not come into contact with any heat source. All line voltage and safety control circuits, between the vent damper and the appliance, MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent methods.
BEFORE STARTING WIRING, TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE AT THE APPLIANCE SERVICE SWITCH OR CIRCUIT BREAKER!!
The application requires a TCA-1 Thermal Couple Junction block and a 6 foot length of 12 ga. two (2) wire conductor