AN-137 Replacement Instructions for Models ESU14 & ESU20
SUPPLEMENT TO THE ELECTRONIC STEAM POWER HUMIDIFIERS MODEL #S2000 AND S2020
This service bulletin describes the steps that may be necessary to replace your existing Model ESU14 or ESU20 Steam Humidifier, with the new Model S2000 or S2020 Power Steam Humidifier. The new “S” models have been redesigned and improved. There are some differences which must be taken into account when installing this unit or replacing an older model.
1. MOUNTING - First and most important is the mounting of the new humidifier. The new model has a larger reservoir but measures the same width and height as the old “ESU”. The reservoir protrudes deeper into the duct and occupies more space inside the duct. The new “Under Duct Mounting Flange” is an integral part of the reservoir. As a result, the modification to perform when mounting the new S2000 or S2020, is to snip and lengthen the flange dimension on your existing reservoir cutout opening in the warm air supply plenum.

With this modification done, you should be able to insert the new humidifier into the cutout opening and secure the unit with the 8 self tapping screws provided. The hole dimensions on the front plate have not changed and should match up. If necessary, locally reinforce the opening with sheet metal sleeves to insure that the unit will remain level and not sag with the added weight of the water.
A 2nd template is included with the “S” series humidifiers for mounting the unit under the duct on the return or cold air side of the furnace. Note that there is no need to order an under the duct mounting kit, due to the new integrated mounting flange.
P/N 090376A0137 REV. D 10/2011 Copyright © 2011, Field Controls Inc., All Rights Reserved Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214

AN-137 Replacement Instructions for Models ESU14 & ESU20 SUPPLEMENT TO THE ELECTRONIC STEAM POWER HUMIDIFIERS MODEL #S2000 AND S2020
The blower (fan) interlock was connected via the two red wires on the old “ESU” model and usually incorporated a field installed transformer and interlocking relay. Just cut the two red wires and connect them to the “R” and “G2” terminals on the top of the front cover. In this method you can reuse the field relay and transformer which were originally installed with the ESU.
If this is a new install then you can fully utilize the on board relay provided with the “S” series humidifier and interlock your blower “fan” by following the low voltage diagram. There is no need to install a separate transformer or relay.

S2000 & S2020 T ypical W ir ing and B lower I nter lock Diagr am
DO NOT plug the molex connector from the old “ESU” humidifier, into the socket on the side of the front cover on the new “S” series humidifier. That socket connection is now reserved for the automatic drain valve only. Doing so will damage the unit and void the warranty.
P/N 090376A0137 REV. D 10/2011 Copyright © 2011, Field Controls Inc., All Rights Reserved Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214

AN-137 Replacement Instructions for Models ESU14 & ESU20 SUPPLEMENT TO THE ELECTRONIC STEAM POWER HUMIDIFIERS MODEL #S2000 AND S2020
The new “S” series humidifiers have an automatic drain valve which will drain the tank every 12 hours, to minimize chemical buildup inside the tank. The water is allowed to cool down to 140 degrees F. before the water is drained out.
The humidifier drains by gravity only, so it must be mounted at a sufficient height to allow for proper drainage. DO NOT route the drain hoses above the level of the humidifier, and watch for kinks or cuts in the hoses.
If you have a basement installation and require draining into a condensate pump, we recommend a Beckett Model # CU451ULHT or CU551ULHT. These pumps are rated for high temperature water and have built in check valves.
4.WATER - The frequency which the water fill solenoid on the new steam unit will activate can exceed the older model. This more frequent filling of the tank may be noticeable in the form of water hammer noise or spikes in the water line. Install an optional water hammer arrester #WH-100, and the noise will dissipate.
If this Engineering notice does not cover a question or issue that you have encountered during your installation or replacement project, please contact the Technical Support Hotline @ 1-800-446-3110.
P/N 090376A0137 REV. D 10/2011 Copyright © 2011, Field Controls Inc., All Rights Reserved Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214