Page 3 of the Field Controls CC 2000 user manual — Background
Page 3 · click to enlarge
Page 3

Background

This product study evaluates the effectiveness of the UV-Aire air purifier in reducing the levels of bacteria with a single pass through a simulated air duct system. This device is designed to irradiate the air as it circulates through the home, so the single pass evaluation is the worst-case scenario use of this device. The air in the home will pass through the heating and air conditioning system many times a day, as the air is circulated throughout the home. Knowing the effectiveness of the UV-Aire in a single pass application, enables us to project how effectively the device will treat the air with multiple passes a day.

UV light technology has been successfully used for the disinfection of drinking water for years. Applications for air disinfection with the use of UV light technology include: commercial air treatment in hospitals, clean rooms, meat packing plants, bakeries, dairies, breweries, bottling plants and large commercial HVAC systems. ORGANISM: Serratia marcescens (ATCC 14756) was chosen as the test bacterium. The distinctive red colonies made it easy to evaluate from any background organisms. A raw test suspension of the organism of approximately 95,000 CFU/ml was used. As dispersed into the test system, this suspension yielded bacterial counts of 269 CFU/ft3 @ 500 ft/min airflow and 107.5 CFU/ft3 @ 1000 ft/min airflow. (CFU = Colony Forming Units) TESTING STRUCTURE: An 18” x 18” galvanized air duct, 38 feet long was constructed as the test chamber (see Figure 1). A fan was mounted at the exit end of the chamber and the treated air exhausted to the outdoors. To reduce contamination of the intake air, all air intakes on the exhaust side of the building were sealed. The exhaust fan was equipped with a flow adjustment to allow for adjustable air speeds measured in feet per minute (FPM) through the duct. TESTING AIRFLOW RATE: The airflow rate through the ductwork was adjusted to two nominal velocities of 500 ft/min and 1000 ft/min. The airflow velocities were measured at the center of the duct at the intake end of the test duct.

Page 4 of the Field Controls CC 2000 user manual — Test Apparatus
Page 4 · click to enlarge
Page 4

ORGANISM APPLICATOR: An atomizing humidifier spray nozzle mounted at the center of the test duct intake was used to distribute the organism into the air stream. The application flow rate was 0.45 gallons per hour. UV DEVICE: A Field Controls UV-Aire air purifier model UV-18 was mounted onto the center of the side of the test duct 6 feet from the exit end of the chamber. The lamp is a UVC germicidal lamp (non ozone producing) 18 inches long with a UV output rating of 73 µW/cm2 at 1 meter from the lamp. AIR SAMPLING METHOD: An Andersen N6 single stage “bioaerosal” sampler was used to take the air samples and distribute the sampled air onto agar medium. The test medium was Tryptic Soy Agar from PathCon, Inc. The air sampling pump airflow rate was 1 CFM.

The Anderson sampler method requires corrections to the actual colony counts on the plates. This provides a more accurate measure of the bacteria per cubic foot of the sample air. In the following tables, the Serratia marcescens Positive Hole Count values are the actual plate counts and the Corrected Particle Count values are corrected value based on Anderson correction tables.

Test Apparatus

Field Controls CC 2000 — Test Apparatus diagram (page 4)
Fig. 4 · Test Apparatus
Page 5 of the Field Controls CC 2000 user manual — Test Apparatus
Page 5 · click to enlarge
Page 5

Testing Procedure The testing was performed in two stages. The first stage operated the test chamber with the lamp off. (See table 1) This developed the control data or the base line bacterial levels for the comparison. The second stage operated the test chamber with the lamp on. (See table 2)

Two airflow rates were used to evaluate the lamp effectiveness based on exposure time. Airflow velocities through the ducts of a typical residential heating and cooling system range from 300 to 500 feet per min (fpm). For this study a base air velocity of 500 fpm was used. To decrease the exposure time, a second test was conducted with the airflow in the duct doubled to 1000 fpm. Since the effectiveness of UV lamps is based on the UV light output and exposure time, doubling the airflow reduces the effectiveness of the lamp.

The bacterium was cultured and the cells harvested to provide a suspension of known cell density. This was further diluted to provide gallon quantities of a test suspension containing an estimated 95,000 CFU/ml. This suspension was pumped through the spray nozzle mounted in the center of the duct inlet.

Five air samples were taken for each of the test velocities at short intervals (typically ½ to 2 minutes). This produced a large sample volume of air and reduced the levels of back ground bacteria and molds counts. The plate counts (colony forming units or CFU) for each of the five tests were totaled and divided by the total test volume of air. This produced the comparison value of (269 CFU/FT3 of air) for the 500 FPM airflow and (107.5 CFU/FT3 of air) for the 1000 FPM airflow. Due to apparent efficiency losses in the sampling method at the 1000 FPM velocity, the bacterium count yielded a 60% drop instead of the anticipated 50% reduction due to the velocity change.

Four air samples were taken at 1, 2.5, 3, 5, 6 & 10 minute intervals for each of the test velocities with the lamp on. The longer sample times with the lamp on were needed to obtain plate counts which would provide reliable estimates of the efficiency of disinfection, but with this, more background organisms were found. The plate counts were (18.00 CFU/FT3 of air for the UV-18 and 2.56 CFU/FT3 of air for the UV-18X) at 500 FPM airflow. They were 31.18 CFU/FT3 of air for the UV-18 and 10.40 CFU/FT3 of air for the UV-18X at 1000 FPM airflow.

Page 6 of the Field Controls CC 2000 user manual — Table 1: Control Data ( testing with lamp off )
Page 6 · click to enlarge
Page 6

Table 1: Control Data ( testing with lamp off )

Field Controls CC 2000 — Table 1: Control Data ( testing with lamp off ) diagram (page 6)
Fig. 5 · Table 1: Control Data ( testing with lamp off )
Sample NumberAir Sampling Duration (min)Airflow Velocity fpmSerratia marcescens Positive hole countCorrected Particle CountsCFU/FT3of air (count/min) 11500181241 21500193263 31500208294 40.5500117138 50.5500118140 Total min. = 4Total Corrected = 1076 Particle counts269.00 121000168218 221000167216 321000169220 41100091103 51100092103 Total min. = 8Total Corrected = 860 Particle counts107.50
Table 2UV-18 Test data and results ( testing with lamp on )
Sample NumberAir Sampling Duration (min)Airflow Velocity (fpm)Serratia marcescens Positive hole countCorrected Particle CountsCFU/FT3 of air (count/min)%Survival CFU/ControlLog Reduction% Effective 1110003031 2110003233 3310008899 461000145180 Total min = 11Total Corrected = 343 Particle Counts31.1829.010.5470.99 Control:107.50 115001313 215001919 335005761 4650092105 Total min = 11Total Corrected = 198 Particle Counts18.006.691.1793.31 Control:269.00
Field Controls CC 2000 — Table 1: Control Data ( testing with lamp off ) diagram (page 6)
Fig. 6 · Table 1: Control Data ( testing with lamp off )
Page 7 of the Field Controls CC 2000 user manual — Table 1: Control Data ( testing with lamp off )
Page 7 · click to enlarge
Page 7
Table 3UV-18X Test data and results ( testing with lamp on )
Sample NumberAir Sampling Duration (min)Airflow Velocity (fpm)Serratia marcescens Positive hole countCorrected Particle CountsCFU/FT3 of air (count/min)%Survival CFU/ControlLog Reduction% Effective 12.510002122 22.510002728 32.510002829 4510004851 Total min = 12.5Total Corrected = 130 Particle Counts10.409.671.0190.33 Control:107.50 1550088 255001010 355001717 4105002829 Total min = 25Total Corrected = 64 Particle Counts2.560.952.0299.05 Control:269.00
Field Controls CC 2000 — Table 1: Control Data ( testing with lamp off ) diagram (page 7)
Fig. 7 · Table 1: Control Data ( testing with lamp off )
Page 8 of the Field Controls CC 2000 user manual — Conclusion
Page 8 · click to enlarge
Page 8

Conclusion

Field Controls CC 2000 — Conclusion diagram (page 8)
Fig. 8 · Conclusion
UV-1850093.316.691.17 UV-18100071.9929.010.54 UV-18X50099.000.952.02 UV-18X100090.339.671.01

Form #4291 08/01

Ask about the Field Controls CC 2000

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Field Controls CC 2000

Be the first to ask — other owners or our team will answer.

Original document

Field Controls CC 2000 manual PDF

8 pages·178 KB·Air Cleaner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…