THE FURNACE CONTAINS FOIL COVERED FIBERGLASS INSULATION. INHALATION OF FIBERGLASS PARTICLES IS ASSOCIATED WITH RESPIRATORY DISEASE INCLUDING CANCER.
THIS INDICATES A POTENTIALLY HAZARDOUS SITUATION, WHICH, IF NOT AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.
THE FUEL SUPPLIER NORMALLY ODORIZES NATURAL GAS AND PROPANE. IN SOME CASES, THE ODORANT MAY NOT BE PERCEIVABLE. INSTALLATION OF UL AND CUL RECOGNIZED FUEL GAS DETECTORS INSTALLED IN ACCORDANCE WITH THEIR MANUFACTURER’S INSTRUCTIONS IS RECOMMENDED AS AN ADDITIONAL MARGIN OF SAFETY.
FIRE OR EXPLOSION HAZARD
If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury or loss of life.
MAKE SURE TO REMOVE FOAM BLOWER HOUSING SHIPPING SUPPORTS BEFORE OPERATING FURNACE.
SHIPPING SUPPORTS ARE LOCATED ON THE BOTTOM RIGHT AND BOTTOM LEFT SIDES OF BLOWER HOUSING.

DANGER
WHAT TO DO IF YOU SMELL GAS:
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR TO PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN THE GARAGE.
THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES.
FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
This furnace must be installed:
IMPROPER INSTALLATION, OPERATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO THIS MANUAL FOR PROPER INSTALLATION, OPERATION, SERVICE, AND MAINTENANCE INSTRUCTIONS. A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER MUST PERFORM INSTALLATION AND SERVICE.
Electrical connections must be made in accordance with:
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS FURNACE. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS, OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
Suite 1, 243 Consumers Road
North York, ON, M2J 5E3
THE EXHAUST GASES FROM THIS FURNACE CONTAIN CHEMICALS, WHICH ON SOME OCCASIONS MAY INCLUDE CARBON MONOXIDE (CO). CARBON MONOXIDE IS AN ODORLESS, TASTELESS, CLEAR COLORLESS GAS, WHICH IS HIGHLY TOXIC. EVEN LOW CONCENTRATIONS ARE SUSPECTED OF CAUSING BIRTH DEFECTS AND OTHER REPRODUCTIVE HARM.
UL AND CUL RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS SHOULD BE INSTALLED IN ACCORDANCE WITH THEIR MANUFACTURER’S INSTRUCTIONS AND APPLICABLE LOCAL BUILDING CODES.


This furnace comes assembled for installation in the upflow position and ready for vertical venting. In the event that the furnace will be installed in another position, the following guidelines should be followed.
A partial list of these contaminants includes:
- Aerosols, particularly CFC based aerosols - Air fresheners - “Airplane” glue and similar cements - Ammonia, as is commonly found in permanent wave
WHEN INSTALLED IN THE COUNTERFLOW POSITION ON A COMBUSTIBLE FLOOR, SUBBASE KIT #30476 IS REQUIRED. FAILURE TO INSTALL SUBBASE KIT COULD RESULT IN FIRE, DEATH OR SERIOUS INJURY.
solutions used in women’s hair dressing salons - Anti-static fabric softeners used in clothes dryers - Carbon tetrachloride - Chlorinated cleaners and waxes - Chlorine and bromine based swimming pool chemicals
The opening in the floor must provide adequate clearances to the combustible material.
According to the Clearances to Combustibles Table 2 on page 5, 1/2 inches clearance will be required between the plenum and the combustible material. If installed on a non-combustible material, zero clearance is required.
and treatments - Deicing salts or chemicals, rock salt, etc. - Dry cleaning solutions such as perchloroethylene - Halogen based refrigerants including R-12 and R-22 - Hydrochloric acid, muriatic acid, or other acid based
Inducer position changes required shall be performed in accordance with the inducer rotation instructions in the Furnace Venting section on page 8 of this manual. In the counterflow installation, this furnace can only vent through the left or right side of the furnace.
masonry washing compounds - Polyurethane and similar derivatives fumes - Printer’s inks, paint removers, furniture strippers,
varnishes, varsol, toluene, etc. - Water softener salts and chemicals INSTALLATION POSITIONS
Inducer position changes required shall be performed in accordance with the inducer rotation instructions in the Furnace Venting section on page 8 of this manual. In the horizontal installation, it is not permissible to vent downwards. Therefore the orientation of left or right horizontal position will determine the inducer orientation.
Maintain clearances to combustibles as outlined in Table 2 on page 5. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet.
AIR CONDITIONING
Refer to Figure 1 (below). Maintain clearances to combustibles as outlined in Table 2 on page 5. The furnace may be suspended by field fabricating a cradle of angle iron and threaded rod. Secure the furnace with 2 inch minimum slotted angle or equivalent, as shown in Figure 1 (below). The furnace must be supported in such a way as not to allow twisting or sagging of the cabinet. Position the supports so as not to interfere with accessing the burner and blower compartments.
This furnace may be used as part of an air conditioning system. The furnace wiring and control system are “air conditioning ready”. There are the following factors to consider:
SUGGESTED METHOD FOR SUSPENDING HORIZONTAL FURNACE ALLOW ENOUGH ANGLE IRON OVERHANG TO PERMIT OPENING THE BLOWER DOOR
3/8 INCH THREADED ROD 2 INCH ANGLE IRON JAM NUTS LOCK WASHER FLAT WASHER
If an air conditioning coil is not to be used in the supply air plenum, it is recommended that the outlet duct be provided with a removable access panel, which is accessible when installed so the heat exchanger may be viewed for possible openings using light assistance or a probe that can be inserted for sampling the air stream. The access cover must be fabricated in such a manner as to prevent leaks.

FIGURE 2: DIMENSIONS
Table 2 (below) provides the certified clearances to combustibles.
K
IMPORTANT:
This furnace requires a minimum of 24-inches of front clearance for service purposes. For this purpose, service clearance takes precedence over clearance to combustibles.
J
TABLE 2: CLEARANCES TO COMBUSTIBLES
G B
H
D
* 24 inches required for service ** Supply air end 1 inch / return air end 0 inches *** Certified for closet installation on combustible flooring **** Certified for installation on combustible flooring only when installed on special base (part # 30476).
See the appliance rating plate affixed to the furnace for specific model number, serial number and clearance to combustibles information.
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET.
THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
UPFLOW FURNACES ARE DESIGN CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. THIS SHALL BE INTERPRETED AS A WOOD FLOOR ONLY.
THE FURNACE MUST NOT BE INSTALLED DIRECTLY ON CARPETING, VINYL TILE, OR OTHER COMBUSTIBLE MATERIAL EXCEPT WOOD. INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1 Vent outlet 4” - Use reducer fittings. 2 Two return air openings required


DUCTWORK STEPS: 1. Position the furnace to minimize ductwork length and fittings. 2. Cut open a return air inlet. The choices are: a) either side b) furnace bottom c) any combination, i.e. two sides or a side and the
Proper airflow is required for the correct operation of this furnace. Insufficient airflow may cause erratic operation, could cause the furnace to cycle on the high temperature limit, and may damage the heat exchanger. Excessive airflow may result in an excessively noisy duct system and may result in undesirable consequences such as creating uncomfortable drafts and causing drapes or curtains to blow around.
bottom. Note: 2 return openings required for 70-4, 100-5, 115-5 and 135-5.
If air conditioning is to be used with the furnace, the duct system must be capable of delivering the correct amount of airflow for each system.
DO NOT USE THE REAR PANEL AS A RETURN AIR INLET. THERE IS INSUFFICIENT ROOM TO PERMIT ADEQUATE AIRFLOW.
The ductwork should be sized and constructed in accordance with accepted industry standards. Duct sizing and construction information may be obtained from:
In all cases, cut the inlet air opening the full width of the knockouts. NOTE: When two return air inlets are used, both must be equipped with filters. 3. Install the filter rack(s) (field supplied). 4. Connect the return air duct or fitting to the furnace. The connection should be as air tight as possible to prevent entraining combustion gases from an adjacent fuel burning appliance, or entraining combustion air for this furnace . 5. Ensure that there is adequate space and accessibility for the air filter. 6. If an air conditioning evaporator coil is required, position it on the top of the furnace. Ensure that no air can bypass the evaporator coil. 7. Connect the supply air plenum to the supply air outlet. Flexible duct connectors are an effective device to prevent the telegraphing of mechanical noise from the furnace to other parts of the home via the ductwork. If using flexible connectors, ensure that the adjoining duct is independently supported. Adequate provisions for combustion and ventilation air must be in accordance with ANSI Z223.1 (NFPA 54), section 5.3 "Air for Combustion and Ventilation" in the United States, and CAN/CGA B149 in Canada. Check with local authorities for any additional building codes, bylaws or regulations.
All of the above professional organizations have duct sizing manuals available.
The total static pressure drop of the air distribution system should not exceed 0.5 inches water column.
UNITS 70-4, 100-5, 115-5 AND 135-5 MUST HAVE DUAL RETURN AIR INLETS FOR OPTIMAL AIRFLOW AND AIR FILTRATION. IF NOT SPECIFICALLY STATED BY THE FILTER MANUFACTURER, FOR EFFECTIVE AIR FILTRATION, ASSUME A MAXIMUM VELOCITY OF 300 FPM FOR DISPOSABLE TYPE FILTERS, OR 600 FPM FOR PERMANENT TYPE FILTERS.
Filter free area (in2) = 144 x (CFM / desired velocity (fpm))
NEVER ALLOW THE PRODUCTS OF COMBUSTION FROM THE FLUE TO ENTER THE RETURN AIR OR SUPPLY AIR DUCTWORK.
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR SUPPLY AIR DUCTWORK TO OR FROM ANY OTHER HEAT-PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY, LOSS OF LIFE, OR PROPERTY DAMAGE.
ALL RETURN AIR DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS. TAPE THE SHEET METAL SEAMS IN THE VICINITY OF THE FURNACE WITH DUCT TAPE OR SIMILAR MATERIAL.
WHEN THE FURNACE IS MOUNTED ON A PLATFORM WITH RETURN AIR THROUGH THE BOTTOM, IT MUST BE SEALED AIR TIGHT BETWEEN THE FURNACE AND THE RETURN AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT OF THE FURNACE WITHOUT SAGGING, CRACKS OR GAPS AROUND THE BASE, PROVIDING A SEAL BETWEEN THE SUPPORT AND THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCULATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.

DETERMING COMBUSTION AIR NOTE: If using grilles to cover the two openings, factor in the free area of the grille. Typically, a grille will have a free area approximately 50% of its nominal size. Consequently, if the required opening is 10 inches x 10 inches , it will have to be doubled if using a sidewall grille with 50% free area.
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT OR SUPPLY COMBUSTION AIR TO THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING, OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
DANGER
FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR FROM ATTIC OR CRAWL SPACE
THIS FURNACE AND ANY OTHER FUEL BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE BROUGHT TO THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE PERSONAL INJURY OR DEATH FROM CARBON MONOXIDE POISONING.
In this circumstance, refer to the appropriate installation code for the free area of the combustion and ventilation air openings. If other fuel burning appliances are present, their combustion air and ventilation air requirements must be added to those of the furnace.
CASE 1:
FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR DUCTED HORIZONTALLY
Unconfined space does not necessarily mean that combustion and ventilation will not have to be introduced from the outdoors, particularly in airtight homes. Refer to the appropriate installation code requirements regarding the minimum combustion air required for all fuel burning appliances located within the unconfined area.
Similar to CASE 3, outdoor air for combustion and ventilation may be drawn through horizontal ducting. Consult the appropriate installation code for the free area for openings. If other fuel burning appliances are present, their combustion air and ventilation air requirements must be added to those of the furnace.
If the amount of combustion and ventilation air is insufficient to properly operate the furnace and other fuel burning appliances within the unconfined area, it will be necessary to supply it from the outdoors based on the criteria used when calculating the air supply for a confined space.
DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH JOIST SPACES THAT ARE USED FOR RETURN AIR PURPOSES. DO NOT USE JOIST SPACES FOR RETURN AIR PURPOSES IF THE JOIST SPACE ALREADY CONTAINS PLUMBING STACKS, CHIMNEY COMPONENTS, ETC. UNLESS THE PORTION USED FOR RETURN AIR PURPOSES CAN BE COMPLETELY ISOLATED FROM PORTIONS WITH OTHER USAGES.
FURNACE LOCATED IN A CONFINED SPACE
A confined space, (any space smaller than the minimums discussed in CASE 1), must have two air openings one within 12 inches of the ceiling and the other within 12 inches of the floor. The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or outdoors, the method outdoor air (if used) is introduced, and taking into account any other fuel burning appliances in the confined space.
If sufficient indoor combustion and ventilation air is available for the furnace and all other fuel burning appliances, even when clothes dryers, bathroom fans, range hoods, etc. are running, size each opening according to the appropriate installation codes.

"Vent" and "Chimney" refer to open passageways that convey vent gases from the furnace, or its vent connector, to the outside. Vents and chimneys usually run vertically or nearly vertically. When they serve only one gas appliance, they are called "dedicated" vents or chimneys. When they serve multiple gas appliances, they are called "common" vents or chimneys.
"Vent Connector" refers to a pipe or duct that connects the furnace to a vent or chimney. Vent connectors usually run from the furnace’s vent collar to the vent or chimney. Vent connectors may have vertical and horizontal runs.
"Venting System" refers to a continuous open passageway from the vent collar to the outside. Venting systems usually have a vent connector(s) and a vent or chimney. Venting systems commonly serve a single furnace, or a single furnace and a hot water heater. Other multiple appliance venting systems are less common.
"Fan Assisted Combustion System" refers to an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. This series furnace uses a draft inducer to draw combustion products through the heat exchanger and is considered to have a fan assisted combustion system. Category I furnaces with fan assisted combustion systems must not be vented into single wall metal vents. DESIGN CONSIDERATIONS The furnace is design certified as a Category I appliance, which means that the furnace relies on the buoyancy of combustion products to vent properly. Since buoyancy decreases proportionately with temperature, the chimney size and properties are very important. An oversized chimney, or one that is exposed to the cold will not maintain the required buoyancy as well as it should, and may allow excessive condensation to form. IMPORTANT: Do not common vent the furnace with Cate- gory III or IV gas-fired appliances. The furnace must be vented in accordance with these instructions, the Venting Tables and rules published in the current editions of ANSI Z223.1 / NFPA 54, National Fuel Gas Code in the United States, or B149, Natural Gas and Propane Installation Code in Canada, and within the requirements of the codes of the local authority having jurisdiction. Refer to section 5.3 of ANSI Z2213.1/NFPA 54 or sections 7.2, 7.3 or 7.4 of CSA B149 for venting requirements. The furnace is not equipped with a draft hood to introduce dilution air to the chimney. The products of combustion will therefore have a higher concentration of water vapor within them. If the furnace is the only appliance served by the chimney, a tiled masonry chimney, regardless of tile size, must not be used without a suitably sized certified chimney liner and termination. Consider dedicated venting with a B Vent used as a liner in this case. See Dedicated Venting on page 11. Multistory and common venting with other Category I gas fired appliances is permitted. The venting system must be in accordance with the National Gas Code, B149 in Canada, ANSI Z223.1/NFPA 54 in the United States, local codes, and approved engineering practices.
SELECT APPROPRIATE VENTING MATERIALS AND ENSURE PROPER CLEARANCES TO COMBUSTIBLES. INADEQUATE VENTING OR FAILURE TO MAINTAIN PROPER CLEARANCES TO COMBUSTIBLES MAY ALLOW THE ACCUMULATION OF THE PRODUCTS OF COMBUSTION WITHIN THE BUILDING RESULTING IN FIRE, NAUSEA, OR ASPHYXIATION.
DO NOT USE AN UNLINED MASONRY CHIMNEY TO VENT THIS FURNACE. THE USE OF AN UNLINED MASONRY CHIMNEY INCREASES THE RISK OF CONDENSATE FORMATION, WHICH MAY CAUSE THE CHIMNEY TO DETERIORATE, ALLOWING COMBUSTION PRODUCTS AND CONDENSATE TO COLLECT IN THE BUILDING.

This furnace can be installed in upflow, counterflow and horizontal applications. The furnace is capable of being vented vertically through the top panel, left or right through the side panels. Each furnace is assembled and supplied set up for vertical venting applications. If the installer chooses to vent through the side panels such as in horizontal or counterflow applications, rotation of the inducer will be required. In addition, the pressure switch will require relocation in the event of a right hand inducer discharge installation.
INDUCER ROTATION STEPS ON 70-3, 70-4, 85-3, 85-4, 100-3, 100-4, 100-5, 115-5 and 135-5 (See Figure 4A below for Right Exhaust, Figure 4B below for Left exhaust)
require the use of screws to plug the holes.
OFF
ON
Inducer Plate mounting screws (all models except 35-2, 50-3)
OFF
ON

INDUCER ROTATION STEPS ON 35-2, 50-3 (See Figures
5A and 5B below)
require the use of screws to plug the holes.
F
N
FIGURE 5B: RIGHT INDUCER POSITION (35-2, 50-3)
35-2 50-3 70-3 70-4 85-3 85-4
12 1/2” 12 1/2” 13 1/2” 13 1/2” 13 1/2” 13 1/2”
100-3 100-4 100-5 115-5 135-5
13 1/2” 13 1/2” 13 1/2” 13 1/2” 13 1/2”

DEDICATED VENTING
Terminate all vertical vents with a listed vent cap or roof assembly unless local codes require otherwise. Locate the termination in an area free of positive pressure or wind eddies. Eddies may occur when wind swirls over roof peaks. They can cause downdrafts and interfere with normal vent operation.
Figure 7 (below) shows a good method to permit dedicated venting making use of B-Vent within a masonry chimney.
When using this method, provide support for the B-Vent.
Some manufactured vent caps are resistant to wind and eddies; their use is recommended.
The vent termination must be a minimum of 5 feet above the highest gas appliance connection. The vent must extend a minimum of 3 feet above the point that it passes through the roof. The vent termination must be a minimum of 2 feet higher than any part of the building horizontally within 10 feet of the vent.
1" MIN. CLEARANCE
5" MIN.
FIGURE 6: VENT TERMINATION
10 FT.
2 FT. MIN
3 FT. MIN
1" MIN. CLEARANCE TO COMBUSTIBLES
B-1 VENT RIGID OR FLEXIBLE
SLOPE UP MIN. 1/4" PER FT.
FAILURE TO PROPERLY TERMINATE THE VENT OR CHIMNEY SYSTEMS COULD ALLOW COMBUSTION PRODUCTS TO COLLECT INSIDE THE BUILDING CAUSING PERSONAL INJURY OR DEATH.

If this furnace is to replace a Category I type furnace connected to a chimney serving other appliances, steps must be taken to ensure that this furnace and the remaining appliances will vent properly after the removal of the existing furnace. There is a chance that the existing chimney will be too large.
THIS FURNACE IS FACTORY EQUIPPED TO BURN NATURAL GAS ONLY.
CONVERSION TO L.P. GAS REQUIRES SPECIAL KIT No. 30482.
Check the size of the existing vent or chimney. It should be sized as though this is a new installation. If it is not, undertake remedies to correct the size.
FAILURE TO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE, EXPLOSION, CARBON MONOXIDE POISONING, PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
Check the condition of the existing vent or chimney. Examine vent or chimney cleanouts to make sure that they remain tightly closed when not in use. Ensure that the vent or chimney passageway is clear and free from obstructions. Look for evidence of condensation damage or deterioration in the vent or chimney. Either of these conditions indicates an inadequate vent. Missing mortar in the top few courses of brick in a masonry chimney is a definite sign of condensation damage.
CONVERSION OF THIS FURNACE REQUIRES SPECIALIZED EQUIPMENT. A TRAINED AND QUALIFIED INSTALLER, SERVICE AGENCY OR GAS SUPPLIER MUST COMPLETE CONVERSION.
If the vent or chimney is found to be damaged or inadequate, it must be repaired or replaced. The repaired or replacement vent or chimney must meet the standards prescribed in ANSI Z223.1 National Fuel Gas Code (NEPA 54), in the United States or CAN/CSA-B149, Natural Gas and Propane Installation Code in Canada.
CONNECT THIS FURNACE ONLY TO GAS SUPPLIED BY A COMMERCIAL UTILITY OR SUPPLIER. PRIVATE GAS WELLS DO NOT GENERALLY PROVIDE GAS WITH CONSISTENT, UNIFORM AND PREDICTABLE HEATING VALUES AND DENSITIES. MANY NONCOMMERCIAL WELLS CONTAIN IMPURITIES SUCH AS SULPHUR, WHICH MAY DAMAGE THE FURNACE. THIS FURNACE CANNOT OPERATE PROPERLY OR SAFELY USING FUELS OUTSIDE NORMAL COMMERCIAL STANDARDS.
When the new furnace is connected to a common vent, the new furnace and the other appliances connected to the common vent must be tested individually following these steps:
In the United States, the gas piping should be installed in accordance with ANSI Z223.1 / NFPA 54 and any local codes. In Canada, the gas piping should be installed in accordance with CAN/CSA-B149, and in accordance with any local codes.
The gas piping may enter the furnace from either side.
Install a BMI ground joint union between the gas valve and the side panel to allow easy removal of the burner for service purposes.
Install a manual gas shutoff valve and dirt pocket as close to the furnace as possible. Some local codes call for the manual gas shutoff valve to be located between 4 to 5 feet above floor level to prevent tampering by small children. Ensure that the valve is readily accessible.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.

ENSURE THAT THE MANUAL SHUTOFF VALVE AND GAS VALVE ARE NOT SUBJECTED TO HIGH PRESSURES.
This series furnace is manufactured as a natural gas (sea level) appliance. It may be converted to L.P. gas with the use of Kit No. 30482 (contact manufacturer for availability). The kit contains the orifices needed for all models, the regulator spring for the gas valve, and a label to affix adjacent to the appliance rating plate to alert subsequent service technicians of the conversion.
DISCONNECT THE MANUAL SHUTOFF VALVE AND GAS VALVE DURING ANY PRESSURE TESTING THAT EXCEEDS 1/2 P.S.I.G. (3.45 KPA).
The natural gas inlet supply pressure should be 5 to 7 inches water column (w.c.), 7 inches w.c. is recommended.
Although the furnace is manufactured initially as a natural gas appliance, if after an L.P. Gas conversion it becomes necessary to convert back to natural gas, and if the original parts are unavailable, Kit No. 30551 may be purchased. It is similar in nature and content to the L.P. Gas conversion kit.
The L.P. gas inlet supply pressure should be 11 to 14 inches w.c., 12 inches w.c. is recommended.
These pressures must be maintained while all other gas fired appliances are operating at maximum conditions.
Do not exceed 14 inches w.c. inlet pressure with LP. Do not exceed 10.5 inches w.c. inlet pressure with NG.
CONVERSION STEPS To convert from sea level to high altitude, from natural gas to L.P. gas, or from L.P. gas to natural gas, follow these steps: Turn off gas supply to the furnace if applicable. 1. Shut off electrical power to the furnace if applicable. 2. Remove the upper front door to expose the gas train and burner assembly. 3. Unfasten the ground joint union between the gas valve and gas supply piping if applicable. 4. Unfasten the burner manifold pipe from the burner assembly. It is held in place by 2 screws on either end of the manifold pipe. 5. Remove the existing orifices with a 7/16 inch socket, box or openend wrench. Install the replacement orifices. The orifice spuds are brass, and do not normally require pipe dope. A light grease may be used to lubricate the threads. The orifice spuds have tapered threads; do not overtighten them. If completing a fuel conversion, remove the protective screw cap from the gas valve regulator adjustment. Remove the regulator adjustment screw by turning it counterclockwise. Remove the existing regulator spring. 6. Install the new regulator spring. NOTE: If converting the White-Rodgers gas valve, the regulator spring is tapered. The tapered end (small end) is inserted back into the gas valve regulator adjustment cavity. Reinstall the adjustment. Give it 3 full clockwise turns initially. Do not reinstall the protective screw cap yet. 7. Reinstall the burner manifold pipe assembly following steps 4, 5, and 6 in reverse order. If, in all other respects the furnace is ready to be fired, continue with the installation. If not, complete the remainder of the installation then return to these steps before starting the Startup & Setup section.
The gas valve has an adjustable internal regulator for controlling burner manifold pressure. Burner manifold pressure is listed on the furnace rating plate.
All new gas piping installations should be pressure tested as specified by CAN/CGA-B149 or NFPA 54 ANSI Z223.1 or ANSI/NFPA 58, Standard for the Storage and Handling of Liquefied Petroleum Gases.
Gas piping that has not been pressure tested, from the manual shutoff valve to the furnace gas valve for example, should be leak tested using an electronic combustible gas detector, a commercially prepared leak detector such as Gas Leak Detector® or Search®, or other locally approved method. A leak detector solution can be prepared by mixing a small quantity of dish detergent with water and daubing it onto the gas piping and connections.
NEVER PURGE A GAS LINE INTO THE COMBUSTION CHAMBER.
NEVER USE A MATCH, TAPER, CIGARETTE LIGHTER, FLAME OR ANY OTHER IGNITION SOURCE TO CHECK FOR LEAKS IN A GAS LINE.
FAILURE TO ADHERE TO THIS WARNING CAN CAUSE A FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
HIGH ALTITUDE
In the United States, the modifications for high altitude are based on a 4 percent reduction of input capacity for every 1000 feet above sea level. Table 4 on page 14 illustrates the impact of altitude for selected elevations. Ratings shown apply to the highest elevation in range.
Consult with local fuel suppliers or authorities to determine local regulations or customs.
In Canada, the furnace may be converted for high altitude (2000 - 4500 feet) by changing the burner orifices. Use Kit No. 30552. The kit contains both natural gas and L.P. gas orifices; see Table 5 on page 14. *Model F80A035 is not approved for LP.

MODEL
ALTITUDE
OUTPUT
NAT. ORIFICE
L.P. ORIFICE
w.c. MODEL FAN
TERN AL STATIC PRESURE - Inches
QTY.
0.10 0.20 0.30 0.40 0.50 0.60
HIGH 8 92 900 910 907 899 884 ME D- HI 7 21 730 751 763 769 757 MED-LO 5 89 603 614 625 632 632 35-2 10-4 DD
1/4 LO W 519 527 539 547 556 551
5000 - 6000 26,600 21280 1.70 mm 1.05 mm 0 - 2000 50,000 40,000 1.95 mm 1.20 mm 2000 - 3000 44,000 35,200 1.83 mm 1.13 mm 3000 - 4000 42,000 33,600 1.79 mm 1.10 mm 4000 - 5000 40,000 32,000 1.74 mm 1.07 mm 50
HIGH 1 512 1496 1448 1406 1337 1272 ME D- HI 1 322 1311 1288 1249 1208 1140 MED-LO 9 80 971 963 954 929 896 50-3 10-7 DD
1/3 LO W 754 746 738 735 723 690
5000 - 6000 38,000 30,400 1.70 mm 1.05 mm 0 - 2000 68,000 54,400 1.95 mm 1.20 mm 2000 - 3000 59,840 47,872 1.83 mm 1.13 mm 3000 - 4000 57,120 45,696 1.79 mm 1.10 mm 4000 - 5000 54,400 43,520 1.74 mm 1.07 mm 70
HIGH 1 688 1643 1589 1527 1465 1389 MED- HI 1 415 1401 1386 1356 1306 1250 MED-LO 9 88 992 1008 1008 1001 970 70-3 10-8 DD
1/3 LO W 721 736 763 768 765 765
5000 - 6000 51,680 41,344 1.70 mm 1.05 mm 0 - 2000 85,000 68,000 1.95 mm 1.20 mm 2000 - 3000 74,800 59,840 1.83 mm 1.13 mm 3000 - 4000 71,400 57,120 1.79 mm 1.10 mm 4000 - 5000 68,000 54,400 1.74 mm 1.07 mm 85
HIGH 1 710 1681 1655 1612 1559 1485 ME D- HI 1 384 1398 1405 1401 1387 1364 MED-LO 9 26 948 975 990 980 964
1/2 LO W 714 728 757 763 760 687
HIGH 1 624 1608 1582 1533 1483 1409 MED HI 1 407 1399 1388 1355 1313 1254 MED LO 990 995 999 1005 992 968 85-3 10-8 DD
5000 - 6000 64,600 51,680 1.70 mm 1.05 mm 0 - 2000 100,000 80,000 1.95 mm 1.20 mm 2000 - 3000 88,000 70,400 1.83 mm 1.13 mm 3000 - 4000 84,000 67,200 1.79 mm 1.10 mm 4000 - 5000 80,000 64,000 1.74 mm 1.07 mm 100
1/3 LO W 742 752 766 774 774 769
HIGH 2 106 2083 2028 1943 1862 1753 ME D- HI 1 856 1840 1816 1777 1705 1620 MED-LO 1 577 1587 1600 1580 1530 1465
85-4 2 Side Returns
5000 - 6000 76,000 60,800 1.70 mm 1.05 mm 0 - 2000 115,000 92,000 1.95 mm 1.20 mm 2000 - 3000 101,200 80,960 1.83 mm 1.13 mm 3000 - 4000 96,600 77,280 1.79 mm 1.10 mm 4000 - 5000 92,000 73,600 1.74 mm 1.07 mm 115
1/2 LO W 1325 1342 1368 1386 1371 1314
HIGH 1 766 1747 1738 1711 1653 1602 ME D- HI 1 440 1444 1448 1459 1434 1397 MED-LO 9 88 1008 1027 1042 1060 1005 100-4 10-10 DD
5000 - 6000 87,400 69,920 1.70 mm 1.05 mm
1/2 LO W 768 780 794 747 704 664
2000 - 3000 118,800 95,040 1.83 mm 1.13 mm 3000 - 4000 113,400 90,720 1.79 mm 1.10 mm
HIGH 2 195 2168 2102 2028 1950 1846 ME D- HI 1 915 1900 1892 1854 1785 1713 MED-LO 1 610 1621 1621 1594 1612 1550
100-5 1 Side Return
4000 - 5000 108,000 86,400 1.74 mm 1.07 mm
3/4 LO W 1357 1372 1401 1419 1394 1360
5000 - 6000 102,600 82,080 1.70 mm 1.05 mm
HIGH 2 399 2359 2290 2219 2146 2070 ME D- HI 2 175 2116 2070 2007 1959 1892 MED-LO 1 991 1959 1909 1875 1841 1788
100-5 2 Side Returns
TABLE 5: HIGH ALTITUDE SPECIFICATIONS - CANADA
3/4 LO W 1671 1636 1624 1587 1537 1498
ALTITUDE
OUTPUT
NAT. ORIFICE
L.P. ORIFICE QTY.
HIGH 2 413 2334 2280 2197 2126 2051 ME D- HI 2 253 2197 2111 2051 1990 1911 MED-LO 2 140 2096 2021 1959 1895 1845
115-5 2 Side Returns
0 - 2000 35,000 28,000 1.95 mm 1.20 mm 35 2000 - 4500 31,500 25,200 1.90 mm 1.15 mm 0 - 2000 50,000 40,000 1.95 mm 1.20 mm 50 2000 - 4500 45,000 36,000 1.90 mm 1.15 mm 0 - 2000 68,000 54,400 1.95 mm 1.20 mm 70 2000 - 4500 61,200 48,960 1.90 mm 1.15 mm 0 - 2000 85,000 68,000 1.95 mm 1.20 mm 85 2000 - 4500 76,500 61,200 1.90 mm 1.15 mm 0 - 2000 100,000 80,000 1.95 mm 1.20 mm 100 2000 - 4500 90,000 72,000 1.90 mm 1.15 mm 0 - 2000 115,000 92,000 1.95 mm 1.20 mm 115 2000 - 4500 103,500 82,800 1.90 mm 1.15 mm 0 - 2000 135,000 108,000 1.95 mm 1.20 mm 135 2000 - 4500 121,500 97,200 1.90 mm 1.15 mm
3/4 LO W 1820 1789 1735 1679 1644 1597
HIGH 2 100 2082 2054 2012 1954 1910 ME D- HI 1 782 1763 1738 1746 1704 1670 MED-LO 1 433 1437 1444 1440 1422 1411
3/4 LO W 1231 1234 1238 1238 1237 1233
HIGH 2550 2468 2403 2323 2239 2167 MED-HI 2309 2239 2182 2108 2047 1984 MED-LO 2182 2123 2077 2015 1968 1902
135-5 2 Side Returns
3/4 LOW
1833 1800 1779 1723 1653 1618
HIGH 2135 2128 2094 2060 2019 1955 MED-HI 1822 1807 1800 1791 1768 1736 MED-LO 1473 1482 1496 1509 1492 1468
12 x 10 DD
3/4 1241 1258 1270 1278 1270 1265

SETTING THE MANIFOLD (Outlet) GAS PRESSURE (F92-1003 36G Valve Pressure Check Kit) 1. Shut off the gas upstream of valve and move valve switch to “OFF”. 2. Using the 3/32 inch hex wrench that is included in the valve pressure check kit, rotate outlet pressure tap screw one revolution counter-clockwise. 3. Attach the 5/16 inch hose that is included in the valve pressure check kit to the outlet pressure boss of the valve. Hose should overlap boss 3/8 inch. 4. Connect 5/16 inch side of connector that is included in the valve pressure check kit to the hose on outlet boss. Connect 1/4 inch side of connector to manometer hose. 5. Turn on gas supply to valve and move valve switch to the “ON” position. 6. Turn on furnace following manufacturer’s instructions. 7. Using a leak detection solution check for leaks at hose connections.
A TRAINED, QUALIFIED TECHNICIAN MUST DO ALL REGULATOR ADJUSTMENTS. IMPROPER MODIFICATIONS OR ADJUSTMENTS CAN RESULT IN FIRE OR EXPLOSION CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR LOSS OF LIFE.
In some circumstances, high inlet pressure can be remedied with the use of an inline appliance regulator. If an inline appliance regulator is used, ensure that it has the capacity to adequately handle the gas volume required by the furnace and any other appliances receiving gas from the header serving the furnace.
SHUT OFF GAS AND FIX LEAKS IMMEDIATELY BEFORE PROCEEDING.
8. Read manometer. This reading is the system outlet/supply pressure. 9. Follow manufacturer’s instructions to adjust outlet /supply pressure, if necessary. 10. Shut off gas supply upstream of valve and move the valve switch to the “OFF” position. 11. Remove manometer and hose from outlet boss. 12. Turn outlet pressure tap screw clockwise to seal the pressure point using the supplied hex wrench. Tighten to 13 in-lbs. minimum. 13. Turn on gas supply to valve and move valve switch to the “ON” position. 14. Turn on furnace following manufacturer’s instructions. 15. Using leak detection solution check for leaks at outlet pressure tap. Shut off gas and fix all leaks immediately before proceeding. If problems were encountered with obtaining enough pressure on the manifold, first examine the gas piping system to ensure that it is correctly sized. Pipe sizing is specified in ANSI Z223.1 / NFPA 54 in the U.S., or the B148 Natural Gas and Propane Installation Code in Canada. CHECKING THE SUPPLY (Inlet) GAS PRESSURE (F92-1003 Valve Pressure Check Kit) Check inlet pressure following steps 1 through 15 above using the inlet/supply pressure tap boss.
Inlet Pressure Boss (Optional)
Regulator Adjustment Connection Terminals
Before proceeding with the electrical connections, ensure that the available electrical supply is compatible with the voltage, frequency, and phase listed on the appliance rating plate.
All furnaces are rated 120 VAC, 60 Hz, 1 phase. The amperage rating is indicated on the furnace rating plate.
Each furnace requires a dedicated overcurrent device either a circuit breaker or a Type D, time delay fuse. It is permissible to connect furnace accessories such as humidifier transformers, condensate pumps and electronic air cleaners. If adding accessory equipment to the furnace circuit, ensure that the combined amperages listed on the appliance rating plates do not exceed the rating of the over current device.
SHUT OFF ELECTRICAL POWER AT THE FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.

Outlet Pressure Boss · Regulator Vent · On/Off Switch

DANGER
THE FURNACE CABINET MUST HAVE AN UNINTERRUPTED GROUND.
The low voltage terminals are located on the control board mounted to the blower assembly; see Figure 11 on page 19.
The furnace is prewired for air conditioning. Insert the thermostat and air conditioner contactor low voltage wiring through the bushing provided in the side panel. Route the control wiring through the blower compartment to the 24 volt terminal screws.
A GROUND WIRE IS PROVIDED IN THE ELECTRICAL JUNCTION BOX.
DO NOT USE GAS PIPING AS A GROUND.
FAILING TO GROUND THE FURNACE PROPERLY CAN RESULT IN ELECTRIC SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
The room thermostat must be compatible with the integrated control in the furnace. Electromechanical thermostats should be rated 30 V / 1.5 amps.
In the United States, all electrical work must be in accordance with the latest edition of the National Electrical Code, ANSI / NFPA 70, in Canada, all electrical work must be in accordance with the latest edition of CSA-C22.1, Canadian Electrical Code Part 1, and any applicable local code. Although a suitably located circuit breaker may serve as a service switch, a separate service switch is recommended. A separate in service switch is necessary if the circuit breaker is in a location where accessing it would require getting close to the furnace, or if the furnace is located between the main electrical panel and the entry to the furnace room. The furnace switch (service switch) should be clearly labeled and installed in a location where it is not likely to be mistaken as being a light switch or similar control. FURNACE CONNECTION 120V: The furnace is shipped fully wired except for the connections to the house wiring. The furnace power connections are made in a junction box inside the blower compartment. The junction box is factory installed on the left hand side however, it may be moved to the right hand side. The junction box contains a BLACK wire to be connected with L1 (hot), a WHITE wire to be connected with L2, the Neutral, and a GREEN wire to be connected to the ground. Use good quality wire nuts; e.g. Marrette® connectors, Ideal® wire nuts, etc. IMPORTANT: USE COPPER CONDUCTORS ONLY If the junction box must be moved to the right hand side:
Most electronic or microprocessor based thermostats except those with "current robbing" circuits should work satisfactorily. Consult the instructions of the thermostat manufacturer for technical and installation details.
Most compatibility problems can be overcome by the use of an isolation relay. The isolation relay should be SPST with a 24- volt coil. The switch ratings should be a minimum of 0.5 amps; see figure 9 below.
The thermostat and control wiring should be a minimum of 18 AWG copper. Excessive lengths of wire may result in enough voltage drop to impair the proper functioning of the furnace. For thermostat wires in excess of 25 feet, use 16 AWG; 50 feet, use 14 AWG.
R
G
COOLING CONTACTOR
Y
Y
W
G
FAN RELAY
1. Unfasten the junction box from the left hand side. 2. Remove the right side panel knockout. 3. Remove the junction box cover hook screw and reinstall it on the opposite side of the box. 4. Fasten the junction box to the right hand panel. NOTE: L1 (hot) and L2 (Neutral) polarity must be observed when making field connections to the furnace. The ignition control may not sense flame if L1 and L2 are reversed. The ground is also essential. NOTE: The furnace shall be installed so the electrical components are protected from water.
HEATING RELAY 24V 115V
THERMOSTAT LOCATION
The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps or appliances, exposure to sunlight, heat from inside wall stacks, etc.
THIS FURNACE IS EQUIPPED WITH A BLOWER DOOR SAFETY SWITCH. DO NOT DISABLE THIS SWITCH. FAILURE TO FOLLOW THIS WARNING CAN RESULT IN ELECTRICAL SHOCK, PERSONAL INJURY, OR LOSS OF LIFE.
See page 21 for information on connecting optional accessories such as electronic air cleaners and power humidifiers.
ELECTRICAL WIRING AND COMPONENTS MUST BE PROTECTED FROM MOISTURE, INCLUDING WATER AND CONDENSATE.

Sequence if the furnace does not light up or detect flame:
This furnace is equipped with a hot surface ignition (HSI) device. Each time that the room thermostat calls for heat, the HSI lights the main burners directly. See the lighting instructions on the furnace.
In addition, if during the burner firing, the flame signal is lost, the gas valve will close and the ignition sequence will begin again at Step 4 above. If the flame sensing signal is lost more than 5 times during a furnace cycle, the gas valve will close, and the ignition sequence goes into a 5 second postpurge; the induced blower stops. The ignition system goes into a 60 minute lockout condition then reattempts the sequence at Step 4 above.
The 60 minute lockout sequence will repeat itself indefinitely. Lowering the room thermostat setting below room temperature for approximately 10 seconds, or shutting off the electrical supply to the furnace for approximately 10 seconds may interrupt the 60 minute lockout.
36G22 gas valve may be switched to the “OFF” position.
desired.
SHOULD OVER HEATING OCCUR, OR THE GAS BURNERS FAIL TO SHUT OFF, CLOSE THE MANUAL GAS VALVE FOR THE FURNACE BEFORE SHUTTING OFF THE ELECTRICAL POWER TO THE FURNACE. FAILURE TO DO SO CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
White-Rodgers 36G22 Gas Valve & White-Rodgers 50A55-250 Integrated Furnace Control
Additional information is available in the Troubleshooting section that starts on page 22 of this manual.

TEMPERATURE RISE CHECK When the duct system is complete and the air filter or filters are in place, determine if the airflow is correct.
1. Insert a duct thermometer in the supply air duct. The thermometer should be placed as close as practical to the furnace, but out of the "line of sight" of the heat exchanger (this prevents false readings owing to radiant heat). Ensure that the thermometer location is within the duct air stream. Avoid locations such as the inside radius of an elbow, etc. 2. Insert a duct thermometer in the return air duct as close to the furnace as practical. Ensure that the thermometer location will be unaffected by humidifier bypass ducts, etc. Choose a location well within the main air stream. 3. Operate the furnace long enough to obtain steady state conditions. 4. When the two thermometers have stabilized, usually within 5 - 8 minutes, compare the two readings. Subtract the return air temperature from the supply air temperature. The difference is the temperature rise, also called ∆T. 5. Compare the measured ∆T to the temperature rise range shown on the rating plate. Unless stated differently on the rating plate, the temperature rise should normally range between 30° to 60°F or 35° to 65°F. When adjusting the temperature rise, the ideal temperature is approximately mid-range. If the measured ∆T is above the approved temperature range, there is too little airflow. The airflow must be increased by selecting a faster fan speed, removing restrictions in the ductwork, or adding supply or return ductwork. If the measured ∆T is too low, there is too much airflow. Use a lower speed tap on the multispeed motor. The blow- er speed is changed at the integrated furnace control. Remove the wire from the “HEAT-H” terminal of the 50A55-20 integrated furnace control and plug in the desired wire on the “HEAT-H” terminal. When this config- uration is used, the following color codes are used: Black - High Speed, Blue - Medium-High Speed, Yellow - Medium- Low Speed and Red - Low Speed. The unused leads are connected to the M1, M2 terminals on the 50A55-20 inte- grated furnace control. IMPORTANT: If the heating speed and cooling speed are to be the same, remove the cooling lead from the control, tape it off, then install a "piggyback" connector from the control "HEAT" terminal to the "COOL" terminal. UNDER NO CIRCUMSTANCE MAY TWO MOTOR WINDINGS BE POWERED SIMULTANEOUSLY. The piggyback connector is used for both types of motor wiring configuration wiring block and permanent lead, see figure 10 below.
Input Heating Value of Gas 3600 Time in Sec. for 1 cu. ft = X
Where:
Input is expressed in BTU / Hr.
Heating value of the gas is expressed in BTU / cubic feet
Time means time required for the test dial to indicate 1 cubic foot in seconds.
If using a gas meter with SI (metric) units:
1 cubic foot = 0.0283 cubic meters.
1 cubic meter = 35.315 cubic foot.
0.01cubic meter = 0.3531 cubic foot.
0.5 cubic meter = 1.766 cubic feet.

Remove blue wire from HEAT terminal, tape it off, and replace it with a jumper. Connect the black wire and jumper to COOL.

AIRFLOW For proper furnace operation, airflow over the heat exchanger is of utmost importance. Insufficient airflow accelerates metal fatigue and failure in the heat exchanger and excessive airflow promotes accelerated corrosion of the heat exchanger. IMPORTANT: Do not bypass this step of the start up procedures. CALCULATING AIRFLOW There are circumstances where it may be desirable to know the airflow delivery through the duct system, such as when estimating the amount of airflow available for air condition- ing. This can be done by direct measurement with electronic or sloped manometers and velometers, or by using the for- mula below.
DIP SWITCH
HEAT "OFF" DELAY
Both control systems allow flexibility in the FAN OFF delay function. The control is located in the blower compartment. Follow the same steps as listed in Adjusting Blower Speeds to access the control.
60 ON ON
90 OFF ON
120* ON OFF
180 OFF OFF

These dip switches control the “Blower off” timing
Where:
Cfm is airflow in cubic feet per minute ∆T is the temperature rise
HOW TO REMOVE THE BLOWER 1. Disconnect power from furnace. 2. Remove thermostat wiring from the integrated furnace control. 3. Remove L1, Neutral and Ground connections between the integrated furnace control and the Furnace electrical connection junction box. 4. Remove 12 pin male molex connector from female connection point, and ground connection from integrated furnace control. 5. Unscrew 2 blower housing bolts located in the front blower shroud as indicated in figure 12 below. Remove front blower shroud from furnace. 6. Slide blower assembly towards front of furnace. Blower is mounted on rail system, and will slide forward about 10 inches before blower is clear of rails. HOW TO INSTALL THE BLOWER 1. Place blower into blower compartment. 2. Keep blower assembly tight to top of blower compartment. Line up blower assembly to slide into blower rails. Push blower assembly towards back of furnace ensuring blower assembly is correctly placed in blower rails. Insert blower shroud on the front of the blower housing. Insert blower housing bolts and tighten. 3. Connect thermostat wiring to the integrated furnace control. 4. Connect L1, Neutral and Ground connections between the integrated furnace control and the furnace electrical connection junction box. 5. Connect 12 pin male molex connector to female connection point, and ground connection to the integrated furnace control. 6. Turn on power to the furnace.
Bonnet output is the furnace output capacity from the rating plate.
If the blower speeds require adjusting, follow these steps:
DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE BEFORE ATTEMPTING TO CHANGE THE BLOWER SPEED. FAILURE TO DO SO COULD RESULT IN ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.
1. Remove the blower compartment door. 2. Access the motor electrical wiring. The blower speed is changed at the integrated furnace control. Remove the wire from the "HEAT" terminal of the 50A55-250 integrated furnace control and plug in the desired wire on the HEAT" terminal. When this configuration is used, the following color codes are used: Black - High Speed, Blue - Medium-High Speed, Yellow - Medium-Low Speed, and Red - Low Speed. The unused leads are connected to the “PARK” terminals on the 50A55-250 integrated furnace control. IMPORTANT: If the heating speed and cooling speed are to be the same, remove the cooling lead from the control, tape it off, then install a “piggyback” connector from the control “HEAT” terminal to the “COOL” terminal. UNDER NO CIRCUMSTANCE MAY TWO MOTOR WINDINGS BE POWERED SIMULTANEOUSLY. 3. Slide the blower assembly back into position, and refasten with the sheet metal screws. 4. Reinstall the blower compartment door. 5. Recheck temperature rise. NOTE: Temperature rise should always be rechecked whenever blower speed changes are done.

Bolts

OPERATING TIPS
DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE FURNACE BEFORE ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.
The filter should be inspected frequently and cleaned as necessary. We recommend a monthly inspection at first, perhaps coinciding with the arrival of the monthly fuel bill as a reminder. The frequency may be increased or decreased depending on experience and conditions.
Do not operate the furnace without an air filter.
Both the induced draft blower motor and circulating fan motor are ball bearing type motors. Neither requires routine lubrication.
A qualified installation contractor, service agency or fuel supplier must inspect the furnace annually.
The induced blower motor and circulating fan motor must be cleaned on a periodic basis by a qualified service technician. Dust buildup in the ventilation ports of the motor will cause the motor to not dissipate heat properly resulting in reduced service life.
Your annual inspection will normally cover the following:
The heat exchanger should be inspected for corrosion. The flue passages (heat exchanger tubes) should be free of scale or excessive corrosion. Observe the burner flames. If there appears to be flame distortion, check venting for blockage. Also check for signs of inadequate combustion air supply. If flame distortion continues after eliminating the blockage in the venting as the cause, it may be necessary to replace the tubular heat exchanger. The tubular heat exchanger cannot be field cleaned. If the tubular heat exchanger is blocked by soot or excess scale, replace it. Check NOX baffles (installed in heat exchanger tubes) for any distortion. If distorted, replace NOX baffles.
The exhaust venting between the furnace vent box and chimney should be inspected periodically for sags, pitting, evidence of leakage etc. If any of these conditions exist, contact your installation contractor, service agency or fuel supplier.
HOLES IN THE EXHAUST PIPING OR FURNACE HEAT EXCHANGER CAN ALLOW TOXIC FUMES TO ENTER THE HOME AND CIRCULATE THROUGH THE DUCT SYSTEM RESULTING IN CARBON MONOXIDE POISONING OR DEATH. IF LEAKS ARE FOUND IN THE FURNACE HEAT EXCHANGER, IT MUST BE REPLACED.
The burners should be inspected to ensure that they are free of deterioration, dust and debris, and properly aligned with the heat exchanger. In most cases, a simple vacuuming with a brush attachment will adequately clean the burner assembly and burner compartment.
Be careful when working on the burner assembly. The hot surface igniter is fragile and can break easily.
The flame sensor should be inspected and cleaned with fine steel wool or Scotch-Brite™ scrubbing pad. The wiring connection should be checked to ensure that it is tight and corrosion free.

ACCESSORIES
The induced blower motor should be inspected and cleaned if necessary. Clear any dust buildup from the ventilation ports.
FIELD SUPPLIED AND INSTALLED OPTIONAL ACCESSORIES ELECTRONIC AIR CLEANER
The White-Rodgers integrated furnace control has provisions to supply power and control an electronic air cleaner rated at 120vac, 1.0 amp max.
The condition of the circulating fan should be checked to ensure that it is free of excessive dust buildup, debris, etc. The mechanical fasteners should be inspected and checked for proper tightness and parts alignment. The motor ventilation ports should be cleaned if necessary to prevent restriction to cooling by air over the motor.
50A55-250: Line voltage for an electronic air cleaner may be picked up from the "EAC-N". 120 volt power will be available at these terminals whenever the circulating fan is operating in the heating or cooling modes.
HUMIDIFIER/ ELECTRONIC AIR CLEANERS
The White-Rodgers integrated furnace control has provisions to supply power and to control a line voltage humidifier or the primary of a 120 / 24 volt humidifier step down transformer, rated at 120vac, 1.0 amp max.
DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE FURNACE BEFORE ATTEMPTING THIS MAINTENANCE PROCEDURE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.
50A55-250: Line voltage for a humidifier may be picked up from the "HUM-H" terminal and from the "HUM-N" terminal. 120 volt power will be available at these terminals whenever the circulating fan is operating in the heating mode.
All electrical connections should be examined to ensure that they are tight and corrosion free. Repair any connections that have become loose or corroded.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Always verify proper operation after servicing.
The furnace should be cycled during the annual inspection and servicing to:

THERMOSTAT CALLS FOR HEAT
NO
WAIT FOR AIR PROVING SWITCH TO OPEN
AIR PROVING SWITCH PROVED OPEN?
YES
COMBUSTION AIR BLOWER ON
FIVE MINUTE WAIT PERIOD
NO
AIR PROVING SWITCH PROVED CLOSED
COMBUSTION AIR BLOWER OFF
YES
PREPURGE
HOT SURFACE IGNITER ON FOR WARM-UP TIME
BETWEEN TRIAL PURGE
MAIN VALVE OPENS
HOT SURFACE IGNITER OFF
HOT SURFACE IGNITER OFF
MAIN BURNER LIGHTS AND IS SENSED DURING TRIAL FOR IGNITION?
MAIN VALVE CLOSES
YES YES
TRIALS FOR IGNITION LESS THAN FOUR DURNG THIS IGNITION SEQUENCE?
COMBUSTION AIR BLOWER OFF AFTER POST PURGE
CIRCULATING AIR FAN ON AFTER DELAY
NO
YES
FLAME SENSE LOST? MAIN VALVE CLOSES
NO
NO
THERMOSTAT CALL FOR HEAT ENDS
FLAME SENSE LOST MORE THAN FIVE TIMES IN THIS CALL FOR HEAT?
MAIN VALVE CLOSES
COMBUSTION AIR BLOWER OFF AFTER POST PURGE
CIRCULATING AIR FAN OFF AFTER DELAY
WAIT FOR NEXT CALL FOR HEAT



IF AND CHECK or REPAIR
2 Flash code does not come o n 1. Induced blower wiring.
Induced blower does not energize
Induced blower does not energize
2 Flash code does come on 1. Pressure switch stuck closed.
Induced blower is energized
3 Flash code does not come o n Wait for the pre-purge to expire.
Induced blower turns off 1. Pressure switch stuck in the open position.
3 Flash code comes on
Pre-purge time h as expired
HSI element does not glow r ed within 10 seconds.
HSI element i s glow- ing red.
No other visible control system action Wait for HSI element warm up time to expire.
HSI element warm u p time has expired a nd main valve has been energized.
Main valve does not light within trial for ignition period
Main valve i s de-energized a t the end of the trial for ignition period.
If main flame i s not sensed during trial for ignition, system will shut o ff HSI element and main gas flow, then g o through another purge period and initiate another ignition trial. A total o f 4 ignition trials will be attempted before the system goes into lockout.
Main burner lights within trial for ignition period.
Main burner stays o n after the end of t he trial for ignition p e- riod.
Circulating fan is not turned on after 30-second time delay. 1. Wiring between system control and IFC. Proper operation of 50V51-250 IFC.
Main burner goes o ut before thermostat call for heat ends.
Open high limit switch.
4 Flash code comes on
High limit wiring in good condition and securely connected.
Main burner goes o ut before thermostat call for heat ends.
4 Flash code does not come on
Gas supply / flow reduced or interrupted.
5 Flash code comes on.
Rollout switch wiring in good condition
1 Flash code comes on.
furnace chassis.
After 1-hour lockout reset delay, control will reset and initiate a new ignition s e- quence i f the call f or heat is still present.



MODEL F80A SERIES GAS-FIRED WARM AIR FURNACE
FURNACE COMPONENTS 1
REGULATOR VENT 1
GENERAL SAFETY RULES 1
WHAT TO DO IF YOU SMELL GAS:
TO START THE FURNACE 2
AIR FILTER 3
LUBRICATION 3
ROUTINE EXAMINATION 3
FURNACE APPEARANCE 4
CLEANING 3
DO NOT USE THIS FURNACE IF ANY PART HAS BEEN UNDER WATER. A FLOOD DAMAGED FURNACE IS EXTREMELY DANGEROUS. ATTEMPTS TO USE THE FURNACE CAN RESULT IN FIRE OR EXPLOSION. A QUALIFIED SERVICE AGENCY SHOULD BE CONTACTED TO INSPECT THE FURNACE AND TO REPLACE ALL GAS CONTROLS, CONTROL SYSTEM PARTS, ELECTRICAL PARTS THAT HAVE BEEN WET OR THE FURNACE IF DEEMED NECESSARY.
SEQUENCE OF OPERATION 4
READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING TO OPERATE THIS FURNACE.
This furnace has been designed to deliver many years of efficient, dependable service. With regular maintenance, some of which requires the attention of a qualified installer, service agency or gas supplier, some of which you may do yourself, the furnace will operate satisfactorily over many heating seasons.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE. FAILURE TO FOLLOW SAFETY WARNINGS EXACTLY COULD RESULT IN SERIOUS INJURY, DEATH, OR PROPERTY DAMAGE.
Please read this manual to familiarize yourself with safety procedures, operation, and routine maintenance procedures.


GENERAL SAFETY RULES
Figure 1 (below) is provided to help identify the components of your furnace.
Induced Blower Pressure Switch Limit Switch Gas Valve
2. A furnace needs adequate amounts of combustion and ventilation air to operate properly. Do not block or obstruct air openings on the furnace, or air openings supplying combustion or ventilation air to the area where the furnace is installed. There are many areas from which your furnace could be receiving combustion and ventilation air including from within the heated area (inside air), from outdoors, from an attic or crawl space. If renovations are done, be sure that air supply openings are not inadvertently covered over with insulation, vapor barrier, or similar construction material.
Flame Sensor Burners Rollout Switch Motor Capacitor Control Panel Furnace control Door Switch Junction Box Transformer Blower
Most natural gas systems and all LP gas systems have a service regulator located near the point where the gas piping enters the building. The propane tank will normally have an additional first stage regulator located at the tank outlet valve. All of these regulators (located outdoors) will have a vent; see Fig. 2 (below).
Figure 2:
Keep free of ice, snow, and debris
It is important for these vents to remain clear. Do not allow moisture, which could freeze, to build up in the vent. If you see moisture building up in the regulator vent, contact your gas supplier.
Your gas supplier should periodically inspect and clean the air vent screen to prevent any obstruction. Keep the protective regulator cover in place, as exposure to the elements can cause ice buildup and a regulator failure.
Igniter Rollout Switch · Gas Regulator Vent · Regulator vent

FURNACE SHUTDOWN PROCEDURE
During the heating season, the operation of the furnace is fully automatic.
If you intend to be away from home for lengthy periods of time during the nonheating season, it is advisable to follow the furnace shutdown procedure.
Inlet Pressure Boss (Optional)
Regulator Adjustment Connection Terminals
DEVICES ATTACHED TO EITHER THE VENT OR COMBUSTION AIR INTAKE FOR THE PURPOSES OF EXCEEDING THE LIMITATIONS DESCRIBED IN THE INSTALLATION MANUAL, INCLUDING FIELD INSTALLED INDUCED BLOWER FANS HAVE NOT BEEN TESTED AND ARE NOT INCLUDED IN THE DESIGN CERTIFICATION OF THE FURNACE.
If this is the first time that the furnace has undergone a trial ignition since installation, or if there has been work done on the gas lines, the furnace might not light because of air trapped in the gas supply line.
Simply turn the thermostat down to its lowest setting, wait 5 minutes, then adjust the thermostat to the desired setting. If the problem persists, proceed to the Furnace Shut Down Procedure and call your installer, service agency or gas supplier.
THE MANUFACTURER CANNOT AND WILL NOT SPECULATE ON THE EFFECTS OF SUCH MODIFICATIONS, AND CANNOT AND WILL NOT BE RESPONSIBLE FOR INJURY OR DAMAGE CAUSED BY THE USE OF SUCH UNTESTED AND/OR UNCERTIFIED DEVICES, ACCESSORIES OR COMPONENTS.
If you intend to be away from home for lengthy periods of time during the non-heating season, it is advisable to follow the furnace shut down procedure.
NEVER USE TOOLS TO TURN A MANUAL GAS CONTROL HANDLE. IF THE CONTROL HANDLE WILL NOT TURN BY HAND, DO NOT ATTEMPT TO FORCE IT. DOING SO COULD RESULT IN FIRE OR EXPLOSION RESULTING IN SERIOUS PERSONAL INJURY OR DEATH, OR PROPERTY DAMAGE. CALL A QUALIFIED INSTALLATION CONTRACTOR, SERVICE AGENCY OR GAS SUPPLIER.
FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY, OR YOUR GAS SUPPLIER.

Outlet Pressure Boss · Regulator Vent · Gas Valve Control

ROUTINE EXAMINATION
AIR FILTER
It is good practice to give a quick inspection of your furnace each time you inspect or clean the air filter. Things to check:
REMOVING FILTER 1. Disconnect electrical power to the furnace. 2. Pull the filter out the front. 3. Replace with a fresh filter and reconnect power to the furnace. The filter will have an arrow indicating proper airflow direction. DO NOT OPERATE YOUR FURNACE (OR AIR CONDITIONER) WITHOUT AN AIR FILTER.
DISCONNECT THE ELECTRICAL POWER TO THE FURNACE BEFORE ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO MAY CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Consult your installation contractor or service technician if you have any questions on filters.
LUBRICATION
The furnace exterior finish is a durable automotive-like coating. It may be washed with mild soap if necessary. Galvanized metal surfaces require no maintenance.
Minimal lubrication is required for your furnace. The induced blower assembly motors have sealed bearings. The bearings contain permanent special purpose lubricants. Attempting to force common oil into the induced blower motor bearings will deteriorate the original lubricant and shorten bearing life.
It is advisable to keep dust buildup on warm surfaces to a minimum, since dust, in some cases, can be combustible.
Dust buildup in the circulating fan can impair blower performance; therefore, reduce efficiency. Because the blower wheel is fastened directly to the blower motor, we recommend that major cleaning be left to your service contractor.
DO NOT PERMIT WATER OR CLEANING SOLUTIONS TO ENTER THE ELECTRIC MOTOR.
The burner area should be inspected and cleaned periodically. Be careful when cleaning around the burner area. The hot surface igniter is fragile and will break easily. Do not touch the hot surface igniter or flame rod.
NEVER ATTEMPT TO CLEAN THE BURNER AREA WHILE THE BURNERS ARE OPERATING. DOING SO MAY RESULT IN EXPLOSION OR FIRE RESULTING IN SEVERE PERSONAL INJURY OR DEATH.

ALWAYS DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE BEFORE REMOVING THE BURNER COMPARTMENT ACCESS DOOR.
THE FURNACE SHOULD BE OPERATED WITH ALL PANELS IN PLACE. NEVER OPERATE THE FURNACE WITH THE BLOWER DOOR REMOVED EXCEPT FOR SERVICE PURPOSES.
The furnace achieves its mid-efficiency in two general areas. First, there is no wasteful standing pilot. The furnace consumes no gas in between cycles. Secondly, the furnace is designed to allow very small amounts of excess air in the combustion process. Older furnaces had heat exchangers that were commonly 40% larger than necessary for complete combustion. While this prevented the creation of carbon monoxide, the heated excess air was expelled up the chimney where it could not benefit the interior of the home. Special safety controls now prevent the formation of carbon monoxide.
If your system includes air conditioning, your thermostat (supplied by the installer) will likely have two switches. The first switch is the system switch. The switch settings usually include HEAT, COOL, and OFF. Some thermostats have system switches which include HEAT, COOL, AUTO, and OFF. The system switch must be in the HEAT or AUTO position for the furnace to run.
Your furnace should be cleaned and inspected annually by a trained and qualified service technician.
Your service technician has the knowledge and test equipment to determine the condition of your furnace.
The second switch is the fan switch. It usually has settings of ON and AUTO. The fan switch may be in either position when using the furnace. If the fan switch is set to ON, the main blower will run continuously, and the blower delays mentioned in the sequence of operation points 5 and 9 will be ignored.
THE EXHAUST GASES FROM THIS FURNACE CONTAIN CHEMICALS, WHICH ON SOME OCCASIONS MAY INCLUDE CARBON MONOXIDE (CO). CARBON MONOXIDE IS AN ODORLESS, TASTELESS, CLEAR COLORLESS GAS, WHICH IS HIGHLY TOXIC. EVEN LOW CONCENTRATIONS ARE SUSPECTED OF CAUSING BIRTH DEFECTS AND OTHER REPRODUCTIVE HARM.
UL AND CUL RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS SHOULD BE INSTALLED IN ACCORDANCE WITH THEIR MANUFACTURER’S INSTRUCTIONS AND APPLICABLE LOCAL BUILDING CODES.

The information in this manual supersedes and replaces the previous instruction/operation manual with regards to Warm Air Furnace products. Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice.
For replacement parts contact:
415 Wabash Ave.
CareCo · Effingham, IL 62401
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| to the burner manifold pressure or by changing the burner orifice size. In the previous example where the heating value of the gas is 1100 BTU / cu. ft., the burner manifold pressure can be reduced .3% to 3.4% w.c. which is within the ±0.30 inches w.c. specification to bring the input into compliance. Refer also to Setting the Gas Pressure, and contact the fuel supplier for specific gas heating content values. If using a gas meter to check the furnace input, be sure that all gas fired appliances other than the furnace are off during the test. Any adjustments to the burner manifold pressure should be carried out with the use of a manometer or calibrated magnehelic gauge. Do not adjust the gas valve pressure regulator more than ± 0.30 inches water column. The formula for determining the furnace input via the gas meter test dial is: | p.19 |