RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS What You Need To Know About Safety Instructions
You have made a major investment in a fine piece of equipment. Keep your investment sound by reading these instructions before installing this unit. This will ensure that the full potential of this equipment is achieved. It will also be helpful in avoiding any needless service costs or operational problems. Included in these instructions are safety rules, installation, operation, and maintenance instructions.
Only the highest quality components were used in the construction of your unit. With proper maintenance, your system should provide years of economical, trouble-free service.
Always contact your dealer, distributor, service agent or manufacturer about problems or conditions you do not understand.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
The words “SHALL” and “MUST” indicate a requirement which is essential to satisfactory and safe product performance. The words “SHOULD” and “MAY” indicate a recommendation or advice which is not essential and not required but which may be useful or helpful.
Installation and service personnel are required by some locales to be licensed. Persons not qualified SHALL NOT install this equipment nor interpret these instructions.
This installation and maintenance manual is provided to ensure the proper installation and the most satisfactory performance of your equipment. The instructions contained herein SHALL NOT be deemed to extend, modify, alter or expand any of the representations contained in the limited warranty.
A QUALIFIED INSTALLER MUST PERFORM INSTALLATION AND SERVICE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE, MAINTENANCE, OR USE CAN CAUSE EXPLOSION FIRE, ELECTRICAL SHOCK, OR OTHER CONDITIONS WHICH MAY CAUSE DEATH, PERSONAL INJURY, OR PROPERTY DAMAGE AND WILL VOID THE WARRANTY. REFER TO THIS MANUAL FOR PROPER INSTRUCTIONS.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
A thorough inspection of the shipping container should be made immediately upon receiving the unit. Look for any punctures or openings, and if it appears damage has occurred, it should be noted on the freight bill before signing. The delivering carrier should be contacted immediately to inspect damage, and no installation work should begin until this inspection is completed. Locate rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specification.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS, OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DAMAGE TO EQUIPMENT, OR DEATH.
CONSULT A QUALIFIED INSTALLER FOR INFORMATION OR ASSISTANCE.
CODES The installer SHALL comply with all local, state, and federal codes and/or regulations pertaining to this type of equipment and its installation. Such codes and/or regulations should take precedence over any recommendations contained herein in lieu of local codes. Installations SHALL be made in accordance with the National Electrical Code, local codes and recommendations made by the National Board of Fire Underwriters. Consult local building codes and National Electrical Code (NEC) for special requirements.
Rating plate located inside control box cover


Locating the condenser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop, and will make the system less susceptible to liquid migrations due to less refrigerant charge.
The condensing unit should be located outdoors as close as possible to the evaporator. Consider the following factors: Clearances
The air inlet should be located at least 12" from a wall or other obstruction for unrestricted air flow. The air outlet should be located so as to direct discharged air away from the building. Three feet of clearance around the unit and a minimum of six feet clearance above the unit is required to avoid recirculation of condenser discharge air on vertical discharge models. Avoid locating unit under low overhanging roofs. Support

BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DEATH OR DAMAGE TO EQUIPMENT.
Mount the unit on a sturdy base approximately four to six inches above the ground. In areas known for snow accumulation, the unit should be elevated at least 18" above the ground. A concrete slab is recommended. Concrete slab should not contact the building foundation to prevent possible sound or vibration transmission. Rooftop installation is acceptable in areas of low snow accumulations, provided the roof will support the unit and provisions are made for water drainage and the noise or vibration through the structure. Exposure
ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN. IMPROPER ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN CREATE A HAZARD, CAUSE PERSONAL INJURY OR DEATH, AND WILL VOID THE WARRANTY.
Placement of the unit should be in a well-drained area, or the unit must be supported high enough so run-off will not enter the unit. Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
Opening for line voltage conduit or cable
Do not locate where heat, lint or exhaust fumes will be discharged on the unit (as from dryer or furnace vent).
Opening for low-voltage wiring
Proximity to Evaporator · Control box cover

Evacuation The outdoor unit is factory charged. Evacuation is necessary on the uncharged portions of the total system. Purge the system with dry nitrogen. Then connect a vacuum pump and a vacuum gage capable of accurately measuring below 1,000 microns vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water.
IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS, HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE.
Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Opening the Service Valve (Step Valve) NOTE: This is not a back-seating valve.
Braze joints 1. Remove the valve core from the schrader port. Wrap a quenching cloth around the service valve. Clean and flux the joint and braze with brazing rod containing at least 10% silver (such as silphos type brazing rod). DO NOT USE SOFT SOLDER. Replace the schrader valve core after brazing has cooled.
Remove cap Replace cap Open valve
Opening the Service Valve (Straight Valve) NOTE: This is not a back-seating valve.
Open the valve by using an adjustable wrench to turn the adjusting flange 1/4 turn counter-clockwise. The flange will come to a stop and the seal is now complete.
ALWAYS USE SAFETY GLASSES, PROTECTIVE CLOTHING, AND WORK GLOVES.

CONNECT REFRIGERANT PIPING The following guidelines should be followed when installing refrigerant piping. Comply with all local, state, and federal codes and/or regulations pertaining to this type of equipment and its installation.
Precautions Refer to the chart below for the minimum recommended tube outside diameter sizes on liquid and suction lines. Ensure that vapor and liquid tube diameters are appropriate for unit capacity. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
Undersized line sets will increase the refrigerant pressure drop between the indoor evaporator and outdoor unit, resulting in a decrease in system capacity. Oversizing the line sets may result in excessive refrigerant charge, thereby making the system more susceptible to liquid migration.
When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon based caulk.
Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.
When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation.
Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
Condensing units are available with pre-charged, sweat-type copper connecting fittings.
REFRIGERANT LINE LENGTH MUST NOT EXCEED 75’ ON HORIZONTAL RUNS AND 40’ ON VERTICAL RISERS.
LIQUID LINE
LIQUID LINE SIZES
Can only be 20’ vertical separation without additional accessories.
SUCTION LINE
WARNING IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS, HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE. USE ONLY CLEAN AIR CONDITIONING AND REFRIGERATION GRADE SEAMLESS COPPER TUBING. PLUMBING GRADE COPPER IS INADEQUATE. TO ENSURE A CLEAN SYSTEM FREE OF ANY CONTAMINANTS, PURGING WITH DRY NITROGEN AND A DEEP VACUUM IS NECESSARY ON ALL SWEAT-TYPE MODELS AND ON THE UNCHARGED PORTIONS OF ALL MODELS NOT INCORPORATING PRECHARGED LINES. IT IS DESIRABLE TO PULL A VACUUM TO 1,000 MICRONS (29.96” HG) TO ENSURE TROUBLE FREE OPERATION.
* DO NOT EXCEED 75 FT MAX LINE SET LENGTH
20’


FINAL CHECKS FOR INSTALLER 1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub-through or wire pinching. 2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. 3. Tighten service valve stem caps to 1/12 turn past finger tight. 4. Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.


NOMENCLATURE
24 A B 1 V F D C
C = Air Conditoner CH = Heat Pump
V = Sweat Fitting Type
18 = 18000 BTU/H [5.28 kW] 24 = 24000 BTU/H [7.03 kW] 30 = 30000 BTU/H [8.79 kW] 36 = 36000 BTU/H [10.55 kW] 42 = 42000 BTU/H [12.31 kW] 48 = 48000 BTU/H [14.07 kW] 60 = 60000 BTU/H [17.5 kW]
1 = 208/230 Volts, 1 Phase, 60 Hz 2 = 230 Volts, 1 Phase, 50 Hz 3 = 208/230 Volts, 3 Phase, 60 Hz 4 = 460 Volts, 3 Phase, 60 Hz 5 = 230 Volts, 3 Phase, 50 Hz 6 = 380 Volts, 3 Phase, 50 Hz
D = R-22 Refrigerant Z = R-410A Refrigerant
B = 21 1/2” W x 21 1/2” D x H C = 29 1/2” W x 29 1/2” D x H

THE ABOVE CONTAINS THE SOLE AND EXCLUSIVE STATEMENT OF THE EXPRESS WARRANTIES AND ASSOCIATED REMEDIES AVAILABLE WITH THE PRODUCTS DESCRIBED. NO OTHER EXPRESS WARRANTIES ARE MADE. ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, OR IMPLIED WARRANTIES OTHERWISE ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. IN NO EVENT SHALL FEDDERS BE LIABLE FOR ANY INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. NO WARRANTIES, EXPRESS OR IMPLIED, ARE MADE TO ANY BUYER UPON RESALE. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS OR DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS, WHICH MAY VARY FROM STATE TO STATE. NO WARRANTIES ARE MADE FOR UNITS SOLD OUTSIDE THE ABOVE STATED AREAS. YOUR DISTRIBUTOR OR FINAL SELLER MAY PROVIDE A WARRANTY ON UNITS SOLD OUTSIDE OF THESE AREAS.
The information in this manual supersedes and replaces the previous instruction/operation manual. Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice.
For replacement parts please, consult the installing dealer or contractor.