SG Series UPS Plus ®
Uninterruptible Power Supply Models:
SG5K-2T. SG5K-2TC SG5K-2TX, SG5K-2TXC
SG6K-1TX SG6K-2T, SG6K-2TC

® Electric Inc., 5106 Azusa Canyon Rd., Irwindale, California 91706, (626) 962-7770, Fax 626-962-7720, Email: sales@falconups.com
2004 Falcon® Electric Inc. All rights reserved. All other brand names and trademarks are the property of their respective owners. The information stated in this document is subject to change without notice. 2004-01-06 Falcon®, Falcon® Electric and UPS Plus logos are registered trademarks of Falcon Electric Inc. OM48021-5-6K Rev. F


Models available with either 120V or 208-240Vac Input True Double Conversion On-Line Design Input Power Factor Correction Dual Output Models Available with 120 & 208-240Vac Wide Input Voltage Window Pure Sinewave Output Precision Output Voltage Regulation Superior Brownout, Surge and Transient Protection Internal System Bypass Eliminates Generator Frequency & Voltage Drift Microprocessor Control & RS-232 Communications UPSILON® Monitoring & Shutdown Software Optional Frequency Conversion Optional Extended Battery Packs & Chargers Optional External Maintenance Bypass Switch Optional Internal SNMP/HTTP Interface Card
SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM


SAVE THESE INSTRUCTIONS
This manual contains important instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference.
All of the models presented herein are designed for installation and use in a temperature controlled environment, free of contamination.
This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble. This unit contains no user replaceable parts. Refer all servicing to Falcon Electric, Inc.
THIS UPS IS NOT INTENDED TO BE USED IN CONJUNCTION WITH LIFE SUPPORT OR OPERATING ROOM EQUIPMENT.
Always turn off the input and battery circuit beakers prior to cleaning and never apply liquid or spray detergent on the UPS.
Never attempt to service batteries. High voltage exists within the unit, which could cause electrical shock. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing the UPS batteries, use the same number and type of batteries.
Allow at least 24 hours, after the UPS is first installed and turned on, to fully charge the internal battery and assure the maximum backup time is available.
DO NOT connect the input of this UPS to its own output, as this may damage the UPS.
DO NOT remove or unplug the UPS input when it is turned on. This removes the safety ground from the UPS and the equipment connected to the UPS.
This UPS contains its own energy source (batteries). The output receptacles may carry live voltage even when the UPS is not connected to an AC source.
Should the SG Series UPS unit be stored for more than two weeks, it is mandatory that the battery circuit breaker be turned off prior to storage or battery damage will result.

As new and innovative technologies have become the backbone of today's businesses, maxi- mum system availability is critical and downtime is more expensive than ever. Increasingly, busi- nesses need a UPS that not only protects against blackouts, but also virtually eliminates more frequent and subtle power disturbances. Surges, sags, line noise and brownouts can disrupt proper operation of sensitive equipment. These disturbances may also create unnecessary pro- duction, service, and data recovery costs.
A True Regenerative On-Line UPS provides the highest level of protection against the widest spectrum of power problems. The incoming AC utility source is converted to a regulated DC voltage. From this DC voltage, a new AC voltage is regenerated, providing continuous, clean, tightly regulated power to your equipment. Line-interactive and Off-line designs leave your equip- ment connected directly to dirty utility power. They only provide minimal transient, voltage and backup protection. If your equipment operation is "Mission Critical", a true double conversion On-Line UPS, such as Falcon® Electric's SG SeriesTM UPS Plus®, is the only clear choice.
All SG Series UPS Plus models include state-of-the-art Input Power Factor Correction. This greatly reduces the amount of current demanded from your building wiring system, yielding a highly efficient, "building friendly" UPS.
Falcon Electric's SG Series UPS incorporates advanced microprocessor technology. This tech- nology makes possible a high level of internal UPS control and management. With the supplied UPSILON® software, all SG Series UPS models support unattended shutdown, management, data logging, and self-diagnostics. The software supports MS Windows® 95, 98, NT, 2000, 2000 Server, ME, XP, Novell Netware® 5 & 6, LINUX and FreeBSD. UPSILON for UNIX may be purchased seperately and supports most popular UNIX platforms and OS versions.
Our SNMP/HTTP Agent board provides remote management and monitoring over any Ethernet LAN, WAN or the Internet utilizing a 10BaseT-type connection. The optional SNMP/HTTP agent installs via an option slot located behind a cover plate on the back panel of every SG Series model.
All SG Series models have a continuous duty inverter and support the addition of optional exter- nal battery/charger packs. Whether your application requires a few additional minutes or hours, the SG Series will be ready. Falcon also offers optional battery charger upgrades for faster recharging. Please specify your extended battery and charger requirements at the time of your initial order.
With a factory modification at the time of order, any SG Series model can be configured for use as an international frequency converter. This makes the SG Series UPS Plus an ideal choice for worldwide power applications. Without this modification, all SG series models will detect the incoming utility line frequency and automatically set its output frequency to match.

In most cases the nominal UPS output voltage should be set to match the incoming utility voltage. This will assure a close matching voltage in the event the UPS is placed on bypass. NOTE: Disregard the "ON" marking on the side of the actual dip switch housing; use the tables in this manual or the silkscreen on the UPS rear panel only.
Dip switch 3 "enables" or "disables” the "Green Mode" function. The UPS is shipped from the factory with the switch set in the "disabled" position (up). If SW3 is switched down or to the "enabled" position, the Green Mode function is activated. When the load connected to the output of the UPS drops to under 10% of the full rated UPS output for 30 seconds, the UPS is automatically placed into bypass and the inverter is turned off. NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.
Dip switch settings must be made while the UPS is turned off. Any changes made while the UPS is turned on will not take effect until the UPS is turn off and back on again since the switch settings are read by the microprocessor only during initial UPS power up.
NEVER TURN THE BATTERY CIRCUIT BREAKER OFF WHILE THE UPS AC CIRCUIT BREAKER IS TURNED ON AND OPERATING FROM THE UTILITY VOLTAGE, OR UPS DAMAGE MAY RESULT. UPS MUST BE COMPLETELY SHUT DOWN PRIOR TO DISABLING THE INTERNAL BATTERY SUPPLY.
In the event this UPS is to be turned off or stored for more than two weeks, the battery circuit breaker must be turned to the off position to prevent battery discharge. If placed in long-term storage, every four months the UPS must be plugged in and turned on for 24 hours to allow the batteries to recharge and prevent battery damage. Failure to follow these procedures will invalidate your warranty.

(LOCATED ON THE UPS REAR PANEL)



VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.
SG5K-2T & SG6K-2T UPS MODELS = 216 lbs. (98 kg) SG5K-2TC & SG6K-2TC UPS MODELS = 239 lbs. (108 kg) SG5K-1TX, SG5K-2TX, SG6K-1TX, SG6K-2TX UPS MODELS = 299 lbs. (136 kg) SG5K-1TXC, SG5K-2TXC, SG6K-2TXC UPS MODELS = 322 lbs. (146 kg) FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)
a. Verify the flooring at the UPS or battery bank installation location is rated for
the weight of the equipment. b. Roll the UPS or extended battery bank to the final installation location. c. Locate the position of the (4) levelling feet underneath the UPS near its four
corners. (see picture below). d. Using your fingers and a 12mm open end wrench, screw the levelling feet in
a clockwise direction, lowering the feet until all four feet are securely against the floor.


1.0 UPS Input & Output Requirements.
MODEL REQUIRED INPUT CIRCUIT BREAKER SG5K-1TX:- 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire 50A SG5K-2T - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire 30A SG5K-2TX - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire 30A SG6K-1TX - 120Vac, 50/60Hz, 46.6A, 1 phase, 3 wire 70A SG6K-2T - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire 30A SG6K-2TX - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire 30A
WIRE GAUGE CHART MODEL AC INPUT -1 = 120 Vac -2 = 208-240 Vac
AC OUTPUT(S) 120 Vac 208-240 Vac
BATTERY
SG5K-1TX 8 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU
12 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU SG5K-2T 12 Awg. 600V 75°C CU N/A 12 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU SG5K-2TX 12 Awg. 600V 75°C CU
12 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU SG6K-1TX 6 Awg. 600V 75°C CU 8 Awg. 600V 75°C CU
10 Awg. 600V 75°C CU
10 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU SG6K-2T 10 Awg. 600V 75°C CU N/A 10 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU SG6K-2TX 10 Awg. 600V 75°C CU
10 Awg. 600V 75°C CU 10 Awg. 600V 75°C CU External Battery & Charger System
8 Awg. 600V 75°C CU
16 Awg, 600V 75°C CU N/A N/A 10 Awg. 600V 75°C CU

UPS & BATTERY BANK Wire Gauge Torque (inch pounds) 18 - 10 Awg. 20 8-6 Awg 25 - 30
To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the
Code, ANSI/NFPA 70.
240 dc

IMPORTANT
CIRCUIT BREAKER SG5K-1TX:
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A SG5K-2T
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: None SG5K-2TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A SG6K-1TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A SG6K-2T
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: None SG6K-2TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A
1 2 3 4 5 6 7 8 9 10

This terminal block is located on the UPS rear panel and shown with the conduit mounting and
access cover plates removed.
Use only the lower terminals and wire securing screws when making wiring connections to
the UPS.
Refer to the Wire Gauge Table on Page 7 for recommended wire sizes. Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified. Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.


Terminal Block as Viewed Through the Opening in the UPS Rear Panel

Terminal Block as Viewed Through the Opening in the UPS Rear Panel


Terminal Block as Viewed Through the Opening in the UPS Rear Panel
Optional Extended Battery banks are available for the SG5 & 6kVA models providing extended battery backup up to many hours. Each extended battery is a completely self-contained battery system. If equipped with the optional battery charger, it will require the additional connection to the utility source, incorporating "branch rated" circuit breaker protection which can also be used as a disconnect for the system. Hardwire model extended battery systems are not provided with an input power switch or AC disconnect device. As the optional charger is designed to maintain a continuous charge to the batteries, it must remained powered from the utility source. A battery disconnect is provided on the rear panels of both the UPS and battery bank and must be in the off position during installation or when the system is being turned off or stored for more than two weeks.

VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.
FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)
EXTENDED BATTERY BANK SELECTION GUIDE (Please specify a hardwire configuration at the time of order)
SGB2S7-6K6 SGB2S7-6K6 SGB2S7-6K6 SGB2S7-6K6 SGB2S7-6K6
BATTERIES 40 Pieces 12V, 7AH 80 Pieces 12V, 7AH 60 Pieces 12V, 7AH 80 Pieces 12V, 7AH 160 Pieces 12V, 7AH BATTERIES IN UPS 20 each of 12V, 7AH # of CASES
8 Floor Standing 32.1 x 10.2 x 21.8 (814 x 259 x 554) RUN TIME @ 1000W 190 Min. 340 Min. 500 Min. 820 Min. 1400 Min. RUN TIME @ 1750W 92 Min. 180 Min. 265 Min. 450 Min. 740 Min. RUN TIME @ 2500W 60Min. 112 Min. 180 Min. 305 Min. 505 Min. RUN TIME @ 3500W
1 Floor Standing 32.1 x 10.2 x 21.8 (814 x 259 x 554)
2 Floor Standing 32.1 x 10.2 x 21.8 (814 x 259 x 554)
3 Floor Standing 32.1 x 10.2 x 21.8 (814 x 259 x 554))
4 Floor Standing 32.1 x 10.2 x 21.8 (814 x 259 x 554)
5kVA Full Load 37.5 Min. 78 Min. 120 Min. 210 Min. 340 Min.
6kVA Full Load 29 Min. 60 Min. 92 Min. 165 Min. 270 Min.
MODELS With 120Vac Charger
BATTERY OPTION
SGB2S7-6K6-2 SGB2S7-6K6-2 SGB2S7-6K6-2 SGB2S7-6K6-2 SGB2S7-6K6-2
CHARGER OUTPUT 275Vdc @ 1.3A 275Vdc @ 1.3A 275Vdc @ 1.3A 275Vdc @ 1.3A 275Vdc @ 1.3A # OF CHARGERS 1 2 3 4 8
Battery run times are for reference only and may vary due to application, environment and the condition of the batteries.

(Hardwire Model Shown)

wiring USE COPPER CONDUCTORS ONLY
GAUGE & TYPE REFERENCED IN THE PRECEEDING WIRING
AC Input Voltage --- 208-240 Vac AC Input Current --- 4.5A max Charger Current --- 3.9A DC Output Voltage --- 240 Vdc DC Output Current --- 30A
specifications in this manual prior to making
connections.
G N D
L 1 L 1 L 2 L 2 240 Vdc
To reduce the risk of fire, connect only to a circuit provided with a "branch rated" over-current protection device in accordance with the National Electrical Code, ANSI/NFPA 70.

1.0 UPS Input & Output Requirements.
anyone providing the specified outlet, circuit and circuit protections are available. Other plug and receptacle configurations are available, please reference page 14 or contact the factory should an unlisted configuration e required..
MODEL REQUIRED REQUIRED INPUT RECEPTACLE CIRCUIT BREAKER SG5K-1TXC - 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire L5-50R 50A SG5K-2TC - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire L6-30R 30A SG5K-2TXC - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire L6-30R 30A SG6K-2TC - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire L6-30R 30A SG6K-2TXC - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire L6-30R 30A
To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the
specified "branch rated" over current protection device in accordance with the National Electrical
Code, ANSI/NFPA 70.
or 240Vac split-phase operation. Output 1 (208-230Vac) is powered directly from the UPS inverter while Output 2 (120Vac) is created from the inverter output, through an isolation transformer. A new neutral for the 120Vac output is derived at the output of the transformer. This configuration provides the advantage of providing the full rated output of the UPS at output 1, output 2, or a combination of both.
Output 1: 208, 220, 230 or 240Vac selectable, 3500W* (1) L6-30R (2) KLKD 30 Output 2: 115, 120, 125 or 130Vac, (follows output 1), 3500W* (2) Duplex 5-20R (2) KLKD 20 SG5K-2TC
Output 1: 208, 220, 230 or 240Vac selectable, 3500W (1) L6-30R (2) KLKD 30 Output 2: None SG5K-2TXC
Output 1: 208, 220, 230 or 240Vac selectable, 3500W* (1) L6-30R (2) KLKD 30 Output 2: 115, 120, 125 or 130Vac, (follows output 1) 3500W* (2) Duplex 5-20R (2) KLKD 20 SG6K-2TC
Output 1: 208, 220, 230 or 240Vac selectable, 4200W (1) L6-30R (2) KLKD 30 Output 2: None SG6K-2TXC
Output 1: 208, 220, 230 or 240Vac selectable, 4200W* (1) L6-30R (2) KLKD 30 Output 2: 115, 120, 125 or 130Vac, (follows output 1) 4200W* (2) Duplex 5-20R (2) KLKD 20 * Maximum load at outputs 1 & 2. All UPS outputs are protected by fuses. Always replace these fuses with the same type and rating.

All models referenced on the previous page come equipped with a (4) bay power distribution center mounted on the rear of the UPS. The Power Distribution center is shown in the “standard” or “base” configuration. Custom configurations are available; see the table below or contact the factory.

Red = +240Vdc Black = - 240Vdc Green = Chassis Ground
The configuration of the panels on the power distribution center are installed by the factory. Custom configurations must be specified when the UPS order is placed.
Optional SG 5 & 6kVA Output Panel Configurations Panel Configuration
Voltage (2) 5-20R Duplex (1 fuse) Full SG5/6K-P1* 120 Vac (1) L6-30R Outlet ( 2 fuses) Full SG5/6K-P2* 200-240 Vac * Denotes the default factory configuration. (1) L5-20R (1 fuse) Half SG5/6K-P3 120 Vac (1) L5-30R (1 fuse) Half SG5/6K-P4 120 Vac (1) L6-20R (2 fuses) Half SG5/6K-P5 208-240 Vac SG5/6K-P6 (2) L5-20R (2 fuses) Full SG5/6K-P7 120 Vac (2) L5-30R ( 2 fuses) Full SG5/6K-P8 120 Vac (1) L5-20R (1 fuse) (1) L5-30R (1 fuse) Full SG5/6K-P9 120 Vac
(1) L6-20R (2 fuses) (1) L6-30R (2 fuses) Full SG5/6K-P10 208-240 Vac
(1) L5-20R (1 fuse) (1) L6-20R (2 fuses) Full SG5/6K-P11 120 Vac 208-240 Vac (1)L5-30R (1 fuse) (1) L6-30R (2 fuses) Full SG5/6K-P12 120 Vac 208-240 Vac (1) L5-30R (1 circuit breaker) Full SG5/6K-P13 120 Vac (2) L5-15 Duplex (2 fuses) Full SG5/6K-P14 120 Vac (1) L5-20R (1 circuit breaker) Full SG5/6K-P15 120Vac (1) L6-20R (1 circuit breaker) Full SG5/6K-P16 208-240 Vac (1) L6-30R (1 circuit breaker) Full SG5/6K-P17 208-240 Vac Note: Other options available; please consult the factory.

Typical SG5 & 6kVA Rear Panel Layout (Shown with Power Distribution Center )

Output Voltage & Green Mode
SWITCH
REFER TO PAGE 20 FOR OPERATING INSTRUCTIONS
COOLING FANS DO NOT BLOCK AIR FLOW
UPS HAS BEEN PLACED INTO MANUAL BYPASS, OR THE UPS
HAS BEEN TURNED OFF
ALWAYS TURN ON AFTER THE
BATTERY CIRCUIT BREAKER
BATTERY CIRCUIT BREAKER &
HAS BEEN TURNED ON
DISCONNECT
VERIFY THIS DISCONNECT IS IN THE OFF POSITION WHEN:
* The UPS is being installed. * The UPS is to be turned off or stored for more than five days. * Connecting external battery banks. * Servicing the UPS.
CENTER (see page 14)
OPERATING FROM UTILITY. POWER OR DAMAGE MAY RESULT.
FIRST.
SWITCH THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL TO THE “OFF” POSITION AND PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS. THE UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUT DOWN. DO NOT PRESS THE ON/OFF BUTTON OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUT DOWN PROPERLY. SHOULD THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS DOWN.

Please refer to the battery bank selection guide on page 11 for more model details.
(All models except hardwire)

To the Battery Connector on the second Battery Bank Detailed
To UPS Battery Connector
To the Battery Connector on

the next Battery Bank
1. Verify the battery disconnect circuit breaker on the UPS and all external battery banks to be connected are in the off position. 2. Locate the battery interconnect cable(s). 3. Connect one end of the battery interconnect cable to the the UPS battery connector located on the power distribution center (see page 14). Connect the other end of the cable to the battery connector on the first battery bank as shown. 4. If a second battery bank is to be connected, connect the second battery interconnect cable to the lower (second) battery connector on the first battery bank, and the other end to the upper battery connector of the second battery bank. All subsequent battery banks will be connected in the same manner. 5. Follow the instructions in the proceeding step for additional battery banks. 6. Turn the battery disconnect circuit breaker to the “on” position for the UPS and all extended battery banks. 7. For all battery banks having the internal battery charger option installed from the factory, perform the following:
a. Verify the battery charger circuit breaker is in the off (down) position. b. On the battery bank nameplate label located on the rear panel, verify the battery charger input voltage matches your utility source (120Vac or 230Vac). c. Connect the input line cord(s) to the battery bank(s) power inlet. d. Plug the other end of the power cord into a utility receptacle. e. The batteries in the external battery banks are now being charged. NOTE: Internal battery bank chargers do not charge the batteries inside the UPS. NOTE: When the battery banks and UPS need to be shut down or stored for more than two weeks, turn off the battery charger circuit breaker and turn off the UPS battery circuit breaker, otherwise battery damage may occur due to excessive discharge.
View


*The first or bottom LED is lit when the output load is greater than 25% of the ` rated output of the UPS. *The second LED is lit when the output load is greater than 50% of the rated output of the UPS. *The third LED is lit when the output load is greater than 75% of the rated output of the UPS.
*The third or top LED is lit when the battery is fully charged. *The second LED is lit when the battery level is above the low battery warning level.led *The first LED is lit when the battery level is above the battery cutoff voltage.
For models configured for standard 120 volt domestic usage, this LED is lit to a steady “on” state when Utility voltage is present. However, should the led flash on and off, it is an indication that the HOT and NEUTRAL wires are reversed some where in the building wiring. (Typically at the wall outlet.)
This LED is lit when the unit is operating from battery.

When this led is lit, the UPS bypass is active. Should the Alarm led be lit at the same time, the UPS detected an internal failure and the UPS must be serviced.
When this led is lit, the UPS inverter is operating and powering the connected load.
This led is lit when the connected output load of the UPS drops to under 10% of the full rated output of the UPS, providing SW3 is in the "down" position (Green Mode Enabled) as shown on page 7. The UPS is automatically set to bypass mode and the inverter is turned off, reducing the power requirement. NO BATTERY BACKUP IS PROVIDED IN THIS MODE. (The UPS is shipped from the factory with SW3 in the "up" or disabled position.) 8. OVER CREST INDICATOR LED
This led lights up when the connected load is close to the peak current rating of the UPS.
a. The inverter voltage is too high or low. b. UPS over-temperature condition. c. The battery voltage is too high. d. The internal DC Bus has an under or over voltage condition. e. The internal microprocessor or memory failure.
or with the UPS input circuit breaker in the off position, will cause the UPS to DC start and run on internal battery momentarily and shutdown. b. Pressing this button while the UPS is on, and utility is present, will place the UPS
into bypass mode. c. Pressing this button when the UPS input circuit breaker has been turned off, or
when the utility voltage is not present, will turn off the UPS.
TO TURN UPS ON: CONNECT THE UPS TO UTILITY POWER AND TURN ON THE BATTERY DISCONNECT CIRCUIT BREAKER FIRST, THEN TURN ON THE MAIN AC CIRCUIT BREAKER LOCATED ON THE REAR PANEL. DO NOT PRESS THE “ON” BUTTON LOCATED ON THE FRONT PANEL OR THE UPS WILL BE PLACED INTO BYPASS MODE.
TO TURN UPS OFF: TURN OFF THE MAIN CIRCUIT BREAKER LOCATED ON THE REAR PANEL AND DEPRESS THE "ON/OFF" BUTTON UNTIL THE UPS BEEPS AND WAIT FOR THE UPS TO SHUT DOWN AND TURN OFF (ABOUT 30 SECONDS).
diagnostic. c. Pressing the Test button while in battery mode will turn the battery Audible alarm
off. Depressing it again will turn the Audible alarm back on.

Audible alarm signals are divided into two different levels of alarm status. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. 1. Category one alarms: a. Two short beeps followed by three short beeps.
Notifies the user that the SG UPS is configured with the optional battery pack and is in BATTERY MODE.
- = SG UPS IS IN BATTERY MODE b. A continuous short beep.
The SG UPS is operating from battery and is in a LOW BATTERY operation.
- = SG UPS IS IN A LOW BATTERY CONDITION c. One long beep prior to a short beep.
The SG UPS is in an OVER LOADED, OVER CREST CONDITION. Remove some load from the UPS output to correct this condition.
- = SG UPS IS IN OVERLOAD OR OVER CREST d. One short beep is sounded when either the ON/OFF or TEST buttons are
pressed and held. This notifies the user the associated actions have been initiated by the UPS.
- = WHEN SG UPS FRONT PANEL ON, OFF AND TEST BUTTONS ARE DEPRESSED.
operating range.
- - - = SG UPS OUTPUT VOLTAGE IS OUT OF PROPER RANGE. b. Four short beeps indicate the SG UPS output frequency is out of proper
operating range. The UPS must be repaired.
- = SG UPS OUTPUT FREQUENCY IS OUT OF PROPER RANGE.
c. Five short beeps indicate the SG UPS is in an over-temperature condition.
Check for proper UPS cooling fan operation or blockage.
- = SG UPS INTERNAL TEMPERATURE IS TOO HIGH. d. Should the internal POWER UP SELF-TEST fail, the SG UPS will sound the
* A continuous rapid beeping for about 5 seconds, then the SG UPS shuts down - The UPS output voltage is out of range.
- = UPS OUTPUT VOLTAGE IS OF RANGE. * A continuous rapid beeping for about 2 seconds and the SG UPS shuts down - The SG UPS performed a DC start, but there is no output frequency set in the UPS memory. Plug the UPS into your local utility power and turn the UPS on to set it for your local utility power frequency.
- = The SG UPS performed a DC start, but there is no output frequency set in memory. Connect the UPS to your local utility power and turn on the UPS. Your local utility frequency is now set into the UPS memory. The next time the UPS is DC Started, its output frequency will be set automatically.

Unless configured as a frequency converter, SG 5 & 6kVA models are equipped with an internal maintenance bypass switch. The switch is located on the rear panel of the UPS and is clearly identified, See page 15. The maintenance bypass switch is a manual second bypass primarily provided for service purposes and should not be confused with the internal UPS static bypass. It provides a means of changing the internal UPS batteries while maintaining power to the critical loads connected to the output of the UPS. It also can a provide method of supplying power to the critical load around the UPS electronics in the event of a hard UPS failure.
Improper use of the maintenance bypass switch will result in damage to the UPS.
The following procedures must be followed to assure proper UPS operation.
To place the UPS on Maintenance Bypass when the UPS is functioning normally perform the following:
When the UPS is off, the Maintenance Bypass switch may be turned to “Bypass” position and the input AC circuit breaker turned on to power the loads connected to the UPS output.

Location:
The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector.

BAUD RATE 2400bps DATA LENGTH 8 bits STOP BIT 1 bit PARITY None

Pin # Function explanation I/O 9 RS 232 Rx INPUT 6 RS 232 Tx OUTPUT 7 Ground
When making a connection between a computer and the UPS RS-232 port, always use the green cable supplied with the UPS.
There are communications options that WILL DISABLE the RS-232 port and render it inoperable. The options are as follows:
a. Internal SNMP/HTTP agent option installed into the UPS communications option slot.
a. Falcon Opto Coupler based signal interface board installed in the communications option slot. b. Any Falcon relay-based, dry contact signal interface board installed in the communications option slot.
DB-9 Signals are not isolated and intended for connection to like RS-232 interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!

Typical Falcon Dry Contact Relay Board

UA88374 RELAY OPTION BOARD
(no on-bypass signal)
PIN DESCRIPTION 1 Low Battery ( When UPS reaches low battery, contact activates) (J1, 1-2 short = N.O) (J1, 2-3 short = N.C) 2 JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only 3 Utility Loss N.O. ( At loss of utility voltage, contact activates) 4 Utility Loss N.C. ( At loss of utility voltage, contact activates) 5 JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only 6 Remote Shutdown common 7 Remote Shutdown (J2, 1-2 short = outside power) (J2, 2-3 short = inside power) 1-2 shorted. Applying an external 12V signal across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off. 2-3 shorted. Applying a short directly across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off. 8 Alarm (Upon a UPS fault or failure the contact activates) (J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.) 9 JP3 shorted = Alarm common & all other shorted JP commons JP3 open = Alarm common only
UA88376 RELAY OPTION BOARD
(with on-bypass signal)
DB-9F PIN & JUMPER ASSIGNMENTS PIN DESCRIPTION 1 Low Battery ( When UPS reaches low battery, contact activates) (J1, 1-2 short = N.O) (J1, 2-3 short = N.C) 2 JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only 3 Utility Loss N.O. ( At loss of utility voltage, contact activates) 4 Utility Loss N.C. ( At loss of utility voltage, contact activates) 5 JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only 6 Remote Shutdown common 7 Remote Shutdown (J2, 1-2 short = outside power) (J2, 2-3 short = inside power) 1-2 shorted. Applying an external 12V signal across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off. 2-3 shorted. Applying a short directly across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off. 8 On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure the contact activates) (J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.) 9 JP3 shorted = On bypass, Alarm common & all other shorted JP commons JP3 open = On bypass, Alarm common only


(no-bypass signal)

PIN DESCRIPTION 1 Not Used 2 Utility Loss (N.O.) (Closes upon utility loss) 3 Utility Loss (N.C.) (Opens upon utility loss) 4 Common for pins 2, 3 & 5 5 Low Battery (N.O.) (Closes at low battery) 6 Remote Shutdown Applying a +5-+12Vdc voltage level for >500ms, while the UPS is on battery will shutdown the UPS 7 Not Used 8 Not Used 9 Not Used


Maintenance & Technical Support
Battery Replacement Must Be Performed by Qualified Personnel.
Never attempt to service batteries. High voltage exists within the unit, which could cause electrical shock. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing the UPS batteries, use the same number and type of batteries.
A. NEVER dispose of batteries in a fire, as batteries will explode. B. NEVER dispose of used batteries or the UPS in the trash or landfill as it is
against federal and state laws. The UPS and Batteries must be recycled. For UPS and battery recycling information, please contact our service department for the name and address of the nearest battery recycling facility.
A. Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic. B. A battery can present a risk of electrical shock and has a high short circuit
current.
REFER ALL BATTERY SERVICING OR REPLACEMENT TO A QUALIFIED SERVICE TECHNICIAN. NEVER ATTEMPT TO REPLACE THE BATTERIES YOURSELF.

The following precautions should be observed by a qualified technician when working with batteries.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
a. Reorient or relocate the receiving antenna. b. Increase the separation between the equipment and the receiver. c. Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected. d. Consult the dealer or an experienced radio/television technician for
assistance.

Your FALCON® Electric SG Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service.
Falcon Electric, Inc. 5106 Azusa Canyon Road Irwindale, CA. 91706 Service 800.842.6940 Voice 626.962.7770 Fax 626.962.7720 Email: service@falconups.com WWW.FALCONUPS.COM
Please have your UPS model, serial numbers and date of purchase on hand prior to your call. The model & serial numer information is located on labels located on the rear panel of the unit. This information is essential in retrieving your unit’s historical records. Should our service department determine service is required, you will be given a Return Material Authorization number (RMA) along with return shipping instructions.
The RMA number issued must appear on the outside of the shipping carton. The original shipping container must be used when returning any SG Series product. Falcon® Electric will not assume any responsibility for shipping damage. In the event of shipping damage, you will be notified of the damage and be instructed to file a claim with the freight carrier. You will be billed for all repairs caused by the shipping damage. You must submit a copy of our repair invoice to the carrier for reimbursement.
All units must be returned prepaid. The address and shipping instructions will be given to you at the time the RMA is issued.
You may request technical information or support by email or telephone.
You may contact a FALCON support engineer directly by calling the FALCON support line between 9:00 am and 4:00 pm PST.
800.842.6940 8. FALCON Web Support Product data sheets, specifications and owner’s manuals are available in Adobe® Acrobat .PDF format on our corporate website.

FALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two years following date of shipment. This Limited New Product Warranty Agreement only applies to covered repairs to the product occurring within the United States and Canada.
1. DAMAGE DUE TO ACCIDENTS, FRAUD, INTENTIONAL NEGLIGENCE, MISUSE, IMPROPER INSTALLATION, UNAUTHORIZED ADJUSTMENTS, MODIFICATIONS, ALTERATIONS, DISCONNECTION, TAMPERING: Accidents or acts of nature or other events beyond the control of Falcon Electric, damage from impact, contaminants, fire, or water, misuse of the product such as sustained overloading, improper installation or operation, operation in an uncontrolled environment. 2. DAMAGE DUE TO IMPROPER INSTALLATION OR LACK OF MAINTENANCE: Lack of proper maintenance as outlined in the owner's manual. 3. NORMAL MAINTENANCE: Cleaning, replacement of leaking or outdated batteries. 4. DAMAGE DUE TO ALTERATIONS: Alterations by changing or adding to the product by any unauthorized personnel or service organization. 5. DAMAGE CAUSED BY OTHER THAN ORIGINAL EQUIPMENT PARTS. Any malfunctions caused by the use of other than Falcon Electric original equipment parts such as batteries, line cords and plugs, output receptacles, or any other part. 6. BROKEN OR TAMPERED WARRANTY SEALS: Falcon Electric will deem all warranties null and void in the event warranty seals are broken or show signs of removal or tampering. 7. CONSEQUENTIAL DAMAGES: This Limited New Product Warranty does not cover any consequential or secondary damages that may be suffered as a result of usage of the product or the need to repair or replace a warranted part except to the extent coverage of such damage is required by the state whose law governs the Falcon Electric Limited New Product Warranty. 8. REPAIRS BY UNAUTHORIZED SERVICE ORGANIZATIONS OR PERSONNEL: Otherwise covered repairs when the prescribed repair is not performed by the Falcon Electric Service Center or by a Falcon Electric authorized third party service organization. 9. LIABILITY FROM USE OF THE PRODUCT: Liability for damage to property or injury or death of any person arising out of the operation, maintenance, or use of the product weather. 10. Warranty void if the battery is allowed to discharge below the minimum battery cutoff point. To prevent such discharge, remove the battery fuse, or switch the battery disconnect to the off position when the unit is to be stored without the AC power being supplied to the UPS for more than two days. The battery must be recharged every three to four months when not in use. 11. This product is not recommended, and Falcon Electric Inc. will not knowingly sell this product, for use with life support and other designated “critical devices". ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL FALCON ELECTRIC INC. BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES.
LIMITATION OF LIABILITY: THERE IS NO LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL LOSS OR DAMAGE UNDER THESE WARRANTIES INCLUDING BUT NOT LIMITED TO, LIABILITY FOR INJURY, LOSS OF LIFE, PROPERTY DAMAGE, LOSS OF USE, LOSS OF DATA, LOSS OF TIME, INCONVENIENCE OR COMMERCIAL LOSS, OR BREACH OF IMPLIED OR EXPRESSED WARRANTIES. ANY AND ALL SUCH LIABILITY IS EXPRESSLY EXCLUDED. IN NO EVENT SHALL FALCON ELECTRIC BE RESPONSIBLE FOR ANY AMOUNT EXCEEDING THE ACTUAL MARKET VALUE OF THE PRODUCT. Some states do not permit the exclusions of limitations of incIdental or consequential damages, so these limitations may not apply to you.
TRANSFER: This Falcon Electric Limited New Product Warranty is not transferable in the event of the product ownership being transferred during the warranty cov- erage period.
Effective January 1, 2000, FALCON® ELECTRIC hereby warrants product shipped under this Agreement to be free from defective workman ship for a period of two years following date of shipment. Coverage under this Falcon Electric New Product Warranty Agreement commences with the date of shipment defined as the date on the Bill of Lading. If no Bill of Lading is issued, the date of shipment shall be shown on seller's shipping document. The Falcon Electric Limited New Product Warranties expire two years from the aforementioned commencement date. Falcon Electric Inc. reserves the right to make changes, additions, and/or other improvements in its products without incurring any obligation to install them on its products previously sold. This Warranty is valid for product as sold.
1. For product located in the continental United States and Canada deemed by Falcon Electric to be covered under this warranty, Falcon Electric will pay shipping costs associated with the return and repair of product under the following conditions only: a. Falcon Electric will pay shipping costs both to and from our U.S. Service Center for the first 30 days from the original date of invoice. During this 30 day period, Falcon Electric may elect to ship a new unit to replace the defective product. b. After the first 30 days and up to 90 days from the original date of invoice, the end-user is responsible for shipping costs associated with sending the defective unit to the Falcon Electric U.S. Service Center. Falcon Electric will pay shipping costs associated with returning the repaired product to the end-user. During this 60 day period Falcon Electric may elect to offer a loaner unit, providing the end-user agrees to pay for all shipping costs associated with transportation of the loaner unit both from and return to the Falcon Electric U.S. Service Center. c. All shipping costs for product submitted beyond 90 days of the original date of invoice is the responsibility of the end- user.

Model Number SG5K-1TX & -
SG5K-2T
SG6K-1TX SG6K-2TX &
SG6K-2T
& -2TC Nominal VA 5000 5000 5000 6000 6000 6000
-2TXC
& -2TC
-2TXC
Electrical Input Nominal AC Voltage 120V 230V 230V 120V 230V 230V AC Voltage Range 87-140V 170-275V 170-275V 87-140V 170-275V 170-275V Current-Amps 38.7 20.3 19.5 46.6 24.3 23.4 Frequency 50/60 Hz ±5% Efficiency (Typical) > 79% > 82% > 79% > 82% Power Factor Correction > 0.95
Electrical Output Watts 3500 4200
208V 220V 230V 240V Isolation Transformer No Yes No No No Yes No No Frequency 60Hz 50/60Hz 50/60Hz 50/60Hz 60Hz 50/60Hz 50/60Hz 50/60Hz Voltage Regulation ±4% ±3% ±4% ±3% Frequency Stability ± 0.3% (Battery Mode) Step Load Change ±7% for 100% load variation THD – Linear Loads < 3% THD – Non-Linear Loads < 7%
120 & 208V or 120 & 220V or 120 & 240V (No Switching)
208V 220V 230V 240V
208V 220V 230V 240V
120 & 208V or 120 & 220V or 120 & 240V (No Switching)
208V 220V 230V 240V
AC Voltage (Switchable except where noted)
9 Minutes 28 Minutes 7 Minutes 18 Minutes Recharge Time 10 Hours to 90% Battery times are approximate. Electrical Connections Input
-2TC
L6-30P
L6-30P
-2TXC
L6-30P
L6-30P
-1TXC
5-20R & (1) L6-30R
-2T Hardwire Hardwire -2TC
(1) L6-30R -2TX Hardwire Hardwire
-2TXC
5-20R & (1) L6-30R
5-20R & (1) L6-30R
Contact the factory for other input/output options. Environmental Operating Temperature 0º C to 35º C (32º F to 95º F) Humidity 10% to 95% Non – Condensing Altitude 7,000 Feet Cooling Low Velocity Forced Air Fans Audible Noise @ 1 Meter < 55dBA
Controls and Indicators LED Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level Audible Alarms DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm Communications RS-232 Serial Port (Bundled UPSilon 2000 Software) Mechanical Dimensions H x W x D inches (mm)
32.1 x 10.2 x 21.8 (815.3 x 259.0 x 553.7) 32.1 x 10.2 x 27.0 (815.3 x 259.0 x 685.8) Weight lb. (kg) T TX TC TXC
Hardwired Models Receptacle Models
216 (98) 299 (136) 239 (108) 322 (146)
Agency Listing UL1778, CUL,
Available Options: Extended Run Time Battery Packs, Make-Before-Break Maintenance Bypass, SNMP/HTTP Network Card, Frequency & Voltage Conversion.
©2004 Falcon® Electric, Inc. All rights reserved. Falcon ® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. All other brand names and trademarks are the property of their respective owners. The information and specifications stated in this document are subject to change without notice.