Falcon Uninterruptible Power Supply (FN3KRM-2)

43 pages·3.7 MB·Power Supply·PDF·ENDEFRITNLJA
Falcon Uninterruptible Power Supply (FN3KRM-2)
Table of Contents 80 sections OWNER'S OPERATING · MANUAL · FN Series TM Rackmount UPS Plus ® · Uninterruptible Power Supply Models: · … ShowHide
OWNER'S OPERATINGp.1MANUALp.1FN Series TM Rackmount UPS Plus ®p.1Uninterruptible Power Supply Models:p.1FN3KRM-2, -2TX & -2TXI FN4KRM-2, -2TX & -2TXI FN5KRM-2, -2TX, & -2TXIp.1FN6KRM-2, -2TX & -2TXIp.1FN Series TM Parallelable and N+1 Redundant UPS Featuresp.3FN -2TXI Model Double Conversion On-line UPS Block Diagramp.3IMPORTANT SAFETY INSTRUCTIONS,p.4SAVE THESE INSTRUCTIONSp.4RETAIN THIS USER MANUAL!p.4STORAGE AND TRANSPORTATIONp.4INSTALLATIONp.4WARNINGp.41.0 INTRODUCTIONp.5Manual Overviewp.5FN Rackmount Overviewp.52.0 FN RACKMOUNT UPS CIRCUIT DESCRIPTIONSp.6Galvanically Isolated Outputp.6Input & Power Factor Correctionp.6DC/DC Converterp.6DC/AC Inverterp.6Battery Packsp.7Internal Battery Chargerp.7Static Bypass Functionp.7Automatic Bypass Transfersp.7Output Filterp.73.0 UNPACKING THE UPS AND BATTERY BANKp.83.1 Unpacking Instructionsp.84.0 PRE-INSTALLATION DETAILSp.94.1 Floor Loading Requirementsp.94.2 UPS Input Power Requirementsp.104.3 UPS Input/Output Requirementsp.104.4 UPS Output Rating Detailsp.114.5 FN Rackmount System Rear Panel Overviewp.114.6 Output Transformer Module Hardwire Terminal Block Wiring Detailsp.124.7 UPS Module Hardwire Terminal Block Wiring Detailsp.124.8 System Installation Wiring Diagram (single rackmount UPS system)p.134.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount)p.13FN6KBC-5A-2 5 Amp External Battery Charger Modulep.14FN6KBC-5A-2 Battery Charger Module Terminal Block Wiring Detailsp.14Battery Charger Module/UPS System Wiring Diagramp.145.0 DISPLAY & CONTROLSp.155.1 Control Button and LCD Locationsp.155.2 Control Button Operationp.15Control Panelp.155.3 LED Display Modesp.165.4 LCD Display Overviewp.17LCD Displayp.175.5 LCD Icon Descriptionsp.175.6 Status and Error Code Descriptionsp.176.0 OPERATIONp.196.1 How to start up the UPS with utility power presentp.196.4 How to completely shutdown the UPSp.216.5 How to display readingsp.226.6 How to Display Programmed Settingsp.246.7 How to Change the Programmed Settingsp.277.0 COMMUNICATIONSp.327.1 Advanced Communications Option Cards Available:p.327.2 RS-232 Portp.32The UPS & PC Computer DB-9 pin designations are as follows:p.32The supplied Falcon RS-232 interface cable pin designations are as follows:p.33UPS Side RS-232C Interface Computer Sidep.33The computer RS-232 Port settings should be set to the following:p.337.3 Optional Remote Emergency Power Off (REPO)p.337.4 Optional Communications Interface Board Detailsp.33UA88380 Second RS-232 Interface Option Boardp.33UA88381 RS-485 Interface Option Boardp.33CN2p.33CN3p.33UA88382 USB Interface Option Cardp.34UA88383 Dry Contact Interface Option Cardp.34USHA SNMP/HTTP Agent Option Cardp.348.0 MAINTENANCEp.351. The UPS and Battery Carep.352. Storing the UPS and Batteriesp.353. When to Replace Batteriesp.354. Battery Replacementp.359.0 PARALLEL MODE OPERATIONp.3610.0 ENVIRONMENTALp.37
Page 1 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN3KRM-2, -2TX & -2TXI FN4KRM-2, -2TX & -2TXI FN5KRM-2, -2TX, & -2TXI
Page 1 · click to enlarge
Page 1
Falcon Uninterruptible Power Supply (FN3KRM-2) — OWNER'S OPERATING diagram (page 1)
Fig. 1

OWNER'S OPERATING

MANUAL

FN Series TM Rackmount UPS Plus ®

Parallel or N+1 Redundant 3kVA to 24kVA Hardwire models with a 208-240Vac Input and 120Vac & 240Vac Outputs

Uninterruptible Power Supply Models:

FN3KRM-2, -2TX & -2TXI FN4KRM-2, -2TX & -2TXI FN5KRM-2, -2TX, & -2TXI

FN6KRM-2, -2TX & -2TXI

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN3KRM-2, -2TX & -2TXI FN4KRM-2, -2TX & -2TXI FN5KRM-2, -2TX, & -2TXI diagram (page 1)
Fig. 2

FALCON® Electric, Inc., 5106 Azusa Canyon Rd., Irwindale, California 91706, (626) 962-7770, Fax (626) 962-7720, Email: sales@falconups.com

2009 Falcon® Electric Inc. All rights reserved. All other brand names and trademarks are the property of their respective owners. The information stated in this document is subject to change without notice. 2009-9-16 Falcon®, Falcon® Electric, FN and UPS Plus logos are registered trademarks of Falcon Electric, Inc.

Page 2 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — OWNER'S OPERATING
Page 2 · click to enlarge
Page 2
Page 2 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — OWNER'S OPERATING
Page 3 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN -2TXI Model Double Conversion On-line UPS Block Diagram
Page 3 · click to enlarge
Page 3

FN Series TM Parallelable and N+1 Redundant UPS Features

Parallel Mode and N+1 Redundant Mode Operation True Double Conversion On-Line Sinewave Design Output Galvanic Isolation LCD Display with Advanced Monitoring Remote Emergency Power Off (REPO) Option Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout, Surge and Transient Protection Frequency Converter Operation User-Replaceable and Hot-Swappable Battery Pack Optional Extended Battery Banks & Chargers RS-232, USB & Optional SNMP/HTTP Communications UPSilon UPS Monitoring & Management Software Two-Year Warranty

FN -2TXI Model Double Conversion On-line UPS Block Diagram

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN -2TXI Model Double Conversion On-line UPS Block Diagram diagram (page 3)
Fig. 3 · FN -2TXI Model Double Conversion On-line UPS Block D…
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN -2TXI Model Double Conversion On-line UPS Block Diagram diagram (page 3)
Fig. 4 · FN -2TXI Model Double Conversion On-line UPS Block D…
Page 4 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — WARNING
Page 4 · click to enlarge
Page 4

IMPORTANT SAFETY INSTRUCTIONS,

SAVE THESE INSTRUCTIONS

RETAIN THIS USER MANUAL!

This manual contains important instructions which must be followed during the installation, operation and maintenance of the FN Series UPS, battery banks transformer box and options. Please read all instructions before operating this equipment and save this manual for future reference.

All of the models presented herein are designed for installation and use in a temperature-controlled environment, free of contamination.

This UPS operates from utility power and contains a number of high current back-up batteries; this information is important to all personnel involved. Please read this manual first before continuing to unpack, install or operate this UPS.

STORAGE AND TRANSPORTATION

This UPS must be handled with care and given special attention due to the high amount of energy stored within its internal sealed, lead acid batteries. Please retain the UPS shipping container in the event the UPS needs to be returned for service. It has been designed to ship the UPS safely, without shipping damage.

INSTALLATION

This UPS must be installed in a clean environment, free from moisture, flammable gases or fumes and corrosive substances. Operate the UPS in an indoor environment with an ambient temperature range of 32ºF to +104ºF (0ºC to +40ºC).

This UPS is designed for use with industrial, scientific or data processing class equipment. DO NOT USE TO POWER LIFE SUPPORT EQUIPMENT OR OTHER DESIGNATED “LIFE CRITICAL” APPLICATIONS.

The maximum UPS output load (in watts) must never exceed that shown on the UPS rating label. NEVER CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners or hair dryers.

Storing magnetic media on top of the UPS may result in data loss or corruption.

WARNING

This UPS must be installed according to the instructions in this manual. Failure to do so could result in unsafe operation and could invalidate your warranty.

WARNING

Once batteries have reached the end of their life, ensure they are disposed of properly. PLEASE REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY RECYCLING REQUIREMENTS. NEVER DISPOSE OF BATTERIES IN A LAND FILL.

Do not dispose of battery pack or batteries in a fire. The battery may explode. Do not open or mutilate the battery pack. Released electrolyte is harmful to skin and eyes. It may be toxic.

WARNING

A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:

* Remove watches, rings, and other metal objects. * Use tools with insulated handles.

Page 5 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN Rackmount Overview
Page 5 · click to enlarge
Page 5

1.0 INTRODUCTION

Manual Overview

This user manual has been written to provide basic information about Falcon FN Series -2TXI rackmount models. The FN Series is a rugged, double conversion, "on-line" UPS. It has galvanic output isolation config- ured for single or dual voltage output(s). The FN Series provides continuous power conditioning and accepts a wide range input voltage, while providing tight voltage regulation and a true sinewave output. The FN Series UPS is specifically designed to protect sensitive computers, laboratory and industrial equipment against the widest range of power problems. These problems include power failures, voltage sags, voltage surges, brownouts, utility line noise, high voltage spikes, frequency variations, common mode noise, switching transients, and harmonic distortion.

This manual also details unpacking, unit installation and the major features of the FN Series UPS, in addition to detailed UPS operation, configuration and troubleshooting information.

The specifications section at the end of this manual provides detailed operating parameters and general information on approvals and certifications.

FN Rackmount Overview

The Falcon FN Series UPS system consists of (1) 2U Rackmount UPS module, (1) 3U rackmount battery module and (1) 2U rackmount output isolation transformer module. An optional input isolation transformer module is also available. The modules are designed to be easily installed in a standard 19” equipment rack. The equipment rack must be equipped with hard mounted shelves to properly support the weight of the mod- ules. The modules do not support the mounting of equipment slide rails.

The FN Series front panel features a graphical LCD display, providing detailed operational information at a glance. The display enables the user or field service engineer to easily monitor and troubleshoot localized power problems, in addition to UPS operation. UPS control and programming are easily accessed using pushbuttons located adjacent to the LCD display.

FN rackmount UPS, Battery and Transformer module rear panels have the following features and functions:

a. Circuit Breakers. b. Hardwire input/output terminal blocks. c. Maintenance Bypass Switch The maintenance bypass switch is located behind a protective cover plate on the transformer box rear panel. The UPS must be placed into manual static bypass mode prior to switching the maintenance bypass switch.

d. RS-232 Port - This port may be used to provide communications between the UPS and a network server or other computer system. When used in conjunction with the supplied UPSilon software, remote UPS monitoring and control are facilitated. The software will automatically save all open computer files and initiate an unattended, orderly operating system shutdown in the event of a utility power outage. UPSilon supports most MS Windows and Linux operating systems. An optional UNIX version is available through Falcon at an additional cost.

e. Two Communications Option Board Expansion Slots - The slots support the installation of an optional SNMP/HTTP Agent or contact closure interface boards. The SNMP/HTTP Agent board is a TCP-IP addressable solution to remote UPS monitoring and management via LAN, WAN or the Internet. The agent board is supplied with client software that will remotely shut down multiple servers or computers through the Ethernet LAN. A CD containing software clients and a SNMP MIB II compliant MIB is provided that supports most popular operations systems.

f. Two RJ45 connectors for connection of UPS parallel operation or remote maintenance

bypass interface cables. Used when UPS and transformer modules, or multiple UPS systems are connected in parallel.

Page 6 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — DC/AC Inverter
Page 6 · click to enlarge
Page 6

g. One Local Maintenance Bypass Switch. The switch is located on the transformer module rear panel and provides a manual means of placing the UPS into bypass mode to allow for servicing to be performed on the UPS and battery modules.

2.0 FN RACKMOUNT UPS CIRCUIT DESCRIPTIONS

Galvanically Isolated Output

The FN -2TXI output isolation transformer module provides a galvanically isolated, 120/240Vac, hardwire out- put. To meet UL and code requirements, a dedicated electrical panel should be provided by your electrical contractor or electrician. The FN -2TXI output configuration can be configured for a 120Vac, 208, 220, 230, or 240Vac output. It may also be configured for a dual voltage or 120/240Vac split-phase hardwire output. This configuration allows for the use of a standard electrical panel and readily available branch rated circuit break- ers It also simplifies the distribution to 240Vac and 120Vac loads. The outputs of up to four FN -2TXI units may be connected in parallel. Please refer to pages 12-13 of this manual for wiring details.

Additionally, the FN galvanic output isolation in conjunction with a derived neutral greatly reduces common mode noise and ground loops.

Input & Power Factor Correction

All FN rackmount models require a 2 wire plus ground type 208-240Vac power source, at 50 or 60Hz. Each UPS module input must be connected to a dedicated circuit having a branch rated circuit breaker. If multiple FN units are to be connected in parallel, care must be taken to verify the source electrical panel has enough capacity. It must be rated to supply the total input power requirements of all FN Series units being connected, including all optional extended battery chargers, in addition to any other circuits that may be connected to the panel. Please have your electrical contractor review the FN datasheet located at the end of this manual and perform a site survey several weeks in advance of the installation date.

While the FN Series UPS is operating from the utility power, it’s internal power factor correction circuit converts utility AC power into regulated DC power for inverter use. The circuit also corrects the input current to maintain the phase relationships between both current and voltage sine waveforms. this also minimize the amount of current distortion that is reflected back to the utility line.

DC/DC Converter

The DC/DC converter utilizes energy from the batteries and boosts up the DC voltage to a level required by the inverter. This allows the inverter to operate continuously at optimum efficiency and voltage. The converter incorporates a patented circuit which reduces the amount of ripple current and EMI interference to the battery, increasing the overall battery life.

DC/AC Inverter

In utility mode operation, the inverter utilizes the regulated DC output and converts it back into clean, regulated sinewave AC power. When utility power fails, the inverter will receive its energy from the battery through the DC/DC converter. In both modes of operation, the UPS inverter is online and continuously generates clean, regulated AC output power to the load. The IGBT, PWM inverter is of a very robust design and produces a pure sinewave output with a +/-2% voltage regulation. Having a very low output impedance, it can supply the high current demands of high inrush and non-linear loads.

Page 7 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — Output Filter
Page 7 · click to enlarge
Page 7

Battery Packs

FN rackmount battery modules utilize flame retardant batteries. They consist of (20) 12V, 7AH valve-regulat- ed, sealed lead acid (VRLA) batteries in each module (Yuasa NP7-12). See replacement instructions on page 34.

To maintain the optimum battery life, the UPS should be installed in an environment with an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC). Due to the battery manufacturer specification, the FN Series UPS batteries may be operated at 32ºF to 104ºF (0ºC - 40ºC) , but battery life will be substantially reduced if con- tinuously operated at the higher temperature levels. Optional extended battery modules and external battery charger modules are available through Falcon to extend the amount of battery runtime.

Internal Battery Charger

The internal battery charger located inside the UPS module utilizes energy from the utility power source to continuously charge the UPS batteries. The charger operates in "constant power" mode. The UPS batteries are being charged whenever the UPS is plugged in, turned on and operating from utility power. The internal UPS battery charger output is rated at 1.9 amps.

Static Bypass Function

A manual static bypass pushbutton is located on the FN front control panel. When the UPS is operating from utility in the normal utility mode on-line state, depressing this button will cause the UPS to transfer to bypass. Depressing the bypass button again will return the UPS to normal inverter operation.

Automatic Bypass Transfers

The FN Series UPS module will automatically switch to bypass mode under the following conditions: To energize the connected load when the UPS is first turned on; encounters an overload; encounters an over temperature condition; or upon a UPS failure condition. Should any of these events occur, the UPS will automatically transfer to bypass mode, sound an audible alarm and provide a "bypass" indication on the UPS module LCD display.

Output Filter

As with the input filter stage, the output filter maintains conducted (EMC) and RFI levels below FCC Class A limits.

Page 8 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 3.1 Unpacking Instructions
Page 8 · click to enlarge
Page 8

3.0 UNPACKING THE UPS AND BATTERY BANK

Due to their size and weight the FN rackmount UPS, battery and transformer modules are packaged inside shipping cartons that are secured to a shipping pallet. Removal of the UPS, transformer and battery bank modules should never be attempted by one person.

Upon unpacking the UPS, transformer or battery bank, verify the following items were shipped. Should you have not received any of the items listed below, please contact Falcon Electric Customer Service at 1-800- 842-6940.

FN Rackmount UPS Module FNBRM-1S7 Battery Module Shipping pallet contents: Shipping pallet contents:

(1) FN Rackmount UPS (verify model shipped) (1) FN Extended Battery Bank (1) RS-232 Cable (1) Interface Cable (1) UPSilon Software CD (1) Installation Kit (1) Software Interface Cable (1) Owner’s Manual (1) Installation Kit

FNITRM-2 Rackmount Output Transformer Module (1) Installation kit (2) UPS Communications Interface Cables

3.1 Unpacking Instructions

1. Cut the bands securing the protective carton and lift it off of the UPS, Transformer and battery modules in their shipping cartons. Due to the weight of the units, a second person will be required. 2. Remove the Individual modules from their shipping cartons. Take care to remove separate cables, software, hardware packages and any other items shipped with the modules.

recommended that you attempt to lift and remove them from the shipping pallet without the proper equipment.

Page 9 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4.1 Floor Loading Requirements
Page 9 · click to enlarge
Page 9

4.0 PRE-INSTALLATION DETAILS

Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually inspect the equipment for freight damage. If any equipment has been damaged during shipment, retain the shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “shipping damage” with the carrier. If you discover damage after acceptance, file a claim for “concealed damage”.

To file a claim for shipping damage or concealed damage:

a. YOU MUST file with the carrier within 15 days of receipt of the equipment; b. YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.

WARNING

The UPS, Transformer and Battery Modules are very heavy. Use the proper lifting equipment and take the proper precautions when lifting or moving them.

1. Always install the FN system indoors in a controlled environment. 2. Install the FN modules in a location with unrestricted airflow around the front and rear sides of the modules, away from water, flammable liquids, gases, corrosive, and conductive contaminants. 3. Maintain a minimum clearance of 4 inches in the front and rear of the UPS. 4. Maintain an ambient temperature range of 32ºF to 104ºF (0ºC to 40ºC). To assure the maximum life of the batteries, operation in an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC) is recommended.

OPERATION IN TEMPERATURES ABOVE 77ºF (25ºC) WILL REDUCE BATTERY LIFE.

5. The FN Series Rackmount system modules must be installed in a standard 19” equipment rack having hard mounted shelves under the modules to properly support their weight. 6. When selecting a suitable rack location for the UPS, Transformer and battery bank(s) always verify the floor loading capabilities:

4.1 Floor Loading Requirements

a. VERIFY THE FLOOR OR SUPPORTING SURFACE UNDER THE EQUIPMENT RACK IS RATED TO SUPPORT THE WEIGHT OF THE TOTAL WEIGHT OF THE RACK, THE FN MODULES AND ALL OTHER EQUIPMENT INSIDE THE RACK.

UPS Module:

(1) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 53 lbs. (24 kg) (2) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 106 lbs. (48 kg) (3) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 159 lbs. (72 kg) (4) FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 212 lbs. (96 kg)

Battery Bank Modules (for all FN Rackmount models)

(1) FNBRM-1S7 = 150 lbs. (68 kg) (2) FNBRM-1S7 = 300 lbs. (136 kg) (3) FNBRM-1S7 = 450 lbs. (204 kg) (4) FNBRM-1S7 = 600 lbs. (272 kg)

Output Transformer Module (for all FN Rackmount models) (1) FNITRM-2 = 91 lbs. (41 kg) (2) FNITRM-2= 181 lbs. (82 kg) (3) FNITRM-2= 272 lbs. (123 kg) (4) FNITRM-2= 362 lbs. (164 kg)

Page 10 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4.3 UPS Input/Output Requirements
Page 10 · click to enlarge
Page 10

4.2 UPS Input Power Requirements

a. VERIFY THE PROPER UPS INPUT POWER IS AVAILABLE (for each UPS installed)

FN3KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 20A, single-phase, 2 wire plus ground FN4KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground FN5KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground FN6KRM-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 40A, single-phase, 2 wire plus ground

4.3 UPS Input/Output Requirements

a. VERIFY THE INPUT AND OUTPUT WIRING REQUIREMENTS

FN3KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage -- Input, 12 awg. - Output, 10 awg. Terminal Block Screw Torque -- 20 inch-pounds Required Branch Rated input circuit breaker -- 20A (40A with 3 external battery charger module

options installed) Required Branch Rated output circuit breaker -- 20A

FN4KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage -- Input, 10 awg. - Output, 8 awg. Terminal Block Screw Torque -- 20 inch-pounds Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

options installed) Required Branch Rated output circuit breaker -- 30A

FN5KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage -- Input, 10 awg. - Output, 8 awg. Terminal Block Screw Torque -- 20 inch-pounds Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

options installed) Required Branch Rated output circuit breaker -- 30A

FN6KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage -- Input, 8 awg. - Output, 4 awg. Terminal Block Screw Torque -- 25-30 inch-pounds Required Branch Rated input circuit breaker -- 40A (60A with 3 external battery charger module

options installed) Required Branch Rated output circuit breaker -- 40A

Page 11 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4.5 FN Rackmount System Rear Panel Overview
Page 11 · click to enlarge
Page 11

4.4 UPS Output Rating Details

a. VERIFY THE LOAD TO BE CONNECTED DOES NOT EXCEED THE UPS OUTPUT RATING for the single or combined paralleled UPS units.

(1) FN3KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,100W, split-phase, 3 wire plus ground (2) FN3KRM-2TXI Not N+1 4,200W N+1 2,100W (3) FN3KRM-2TXI Not N+1 6,300W N+1 4,200W (4) FN3KRM-2TXI Not N+1 8,400W N+1 6,300W

1. FN4KRM-2TXI Not N+1 Hardwire, 120/240Vac, 2,800W, split-phase, 3 wire plus ground (2) FN4KRM-2TXI Not N+1 5,600W N+1 2,800W (3) FN4KRM-2TXI Not N+1 8,400W N+1 5,600W (4) FN4KRM-2TXI Not N+1 11,200W N+1 8,400W

(1) FN5KRM-2TXI Not N+1 Hardwire, 120/240Vac, 3,500W, split-phase, 3 wire plus ground (2) FN5KRM-2TXI Not N+1 7,000W N+1 3,500W (3) FN5KRM-2TXI Not N+1 10,500W N+1 7,000W (4) FN5KRM-2TXI Not N+1 14,000W N+1 10,500W

(1) FN6KRM-2TXI Not N+1 Hardwire, 120/240Vac, 4,200W, split-phase, 3 wire plus ground (2) FN6KRM-2TXI Not N+1 8,400W N+1 4,200W (3) FN6KRM-2TXI Not N+1 12,600W N+1 8,400W (4) FN6KRM-2TXI Not N+1 16,800W N+1 12,600W

4.5 FN Rackmount System Rear Panel Overview

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.5 FN Rackmount System Rear Panel Overview diagram (page 11)
Fig. 5 · 4.5 FN Rackmount System Rear Panel Overview
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.5 FN Rackmount System Rear Panel Overview diagram (page 11)
Fig. 6 · 4.5 FN Rackmount System Rear Panel Overview
Page 12 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4.7 UPS Module Hardwire Terminal Block Wiring Details
Page 12 · click to enlarge
Page 12

4.6 Output Transformer Module Hardwire Terminal Block Wiring Details

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.6 Output Transformer Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 7 · 4.6 Output Transformer Module Hardwire Terminal Bloc…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.6 Output Transformer Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 8 · 4.6 Output Transformer Module Hardwire Terminal Bloc…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.6 Output Transformer Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 9 · 4.6 Output Transformer Module Hardwire Terminal Bloc…

4.7 UPS Module Hardwire Terminal Block Wiring Details

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.7 UPS Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 10 · 4.7 UPS Module Hardwire Terminal Block Wiring Detail…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.7 UPS Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 11 · 4.7 UPS Module Hardwire Terminal Block Wiring Detail…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.7 UPS Module Hardwire Terminal Block Wiring Details diagram (page 12)
Fig. 12 · 4.7 UPS Module Hardwire Terminal Block Wiring Detail…
Page 13 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount)
Page 13 · click to enlarge
Page 13

4.8 System Installation Wiring Diagram (single rackmount UPS system)

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.8 System Installation Wiring Diagram (single rackmount UPS system) diagram (page 13)
Fig. 13 · 4.8 System Installation Wiring Diagram (single rackm…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.8 System Installation Wiring Diagram (single rackmount UPS system) diagram (page 13)
Fig. 14 · 4.8 System Installation Wiring Diagram (single rackm…

4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount)

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount) diagram (page 13)
Fig. 15 · 4.9 System Installation Wiring Diagram (typical mult…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount) diagram (page 13)
Fig. 16 · 4.9 System Installation Wiring Diagram (typical mult…

4.10 UPS & Transformer Modules Communications Bus Cabling Use one UA88385 parallel communications bus cabling kit for each UPS to be connected to the system output trans- former module or to paralleled UPS systems. Connect the supplied cables as shown below. Note the first and last con- nectors on the first and last UPS are connected using the longer of the supplied cables. Switch on the termination resis- tor dip switch next to the long cable. For the transformer module, daisy chain the cables from the UPS to the transformer module in a similar manner using the communications connectors located on the transformer module rear panel.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 4.9 System Installation Wiring Diagram (typical multiple parallel UPS units, Rackmount) diagram (page 13)
Fig. 17 · 4.9 System Installation Wiring Diagram (typical mult…
Page 14 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — Battery Charger Module/UPS System Wiring Diagram
Page 14 · click to enlarge
Page 14

4.11 External Battery Charger Option Installation Wiring Detail (Typical UPS unit with optional FN6KBC-5A-2, for use with external battery banks only)

FN6KBC-5A-2 5 Amp External Battery Charger Module

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN6KBC-5A-2 5 Amp External Battery Charger Module diagram (page 14)
Fig. 18 · FN6KBC-5A-2 5 Amp External Battery Charger Module

FN6KBC-5A-2 Battery Charger Module Terminal Block Wiring Details

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN6KBC-5A-2 Battery Charger Module Terminal Block Wiring Details diagram (page 14)
Fig. 19 · FN6KBC-5A-2 Battery Charger Module Terminal Block Wi…
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN6KBC-5A-2 Battery Charger Module Terminal Block Wiring Details diagram (page 14)
Fig. 20 · FN6KBC-5A-2 Battery Charger Module Terminal Block Wi…

Battery Charger Module/UPS System Wiring Diagram

Falcon Uninterruptible Power Supply (FN3KRM-2) — Battery Charger Module/UPS System Wiring Diagram diagram (page 14)
Fig. 21 · Battery Charger Module/UPS System Wiring Diagram
Falcon Uninterruptible Power Supply (FN3KRM-2) — Battery Charger Module/UPS System Wiring Diagram diagram (page 14)
Fig. 22 · Battery Charger Module/UPS System Wiring Diagram
Page 15 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 5.2 Control Button Operation
Page 15 · click to enlarge
Page 15

5.0 DISPLAY & CONTROLS

The pictures below outline the various control panel, LED and LCD functions and locations.

5.1 Control Button and LCD Locations

1. LCD Display 2. N+1 Status LED 3. Utility Status Indicator LED 4. Bypass Input Status LED 5. UPS On / Alarm Silence Control Button 6. Previous Page / Change Setting Button 7. Confirm Button 8. Next Page Button 9. UPS Off / Bypass Button 10. Function Button 11. Economy/Green Mode Status LED 12. UPS Alarm LED
Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.1 Control Button and LCD Locations diagram (page 15)
Fig. 23 · 5.1 Control Button and LCD Locations
Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.1 Control Button and LCD Locations diagram (page 15)
Fig. 24 · 5.1 Control Button and LCD Locations

5.2 Control Button Operation

Control Panel

1. When utility power is present and the UPS input circuit breakers are in the “On” position, depressing and holding this button for 5 seconds will turn on the UPS. 2. When utility power is not present or the UPS input circuit breaker is in the “Off” position, depressing and holding this button for 5 seconds will initiate a preliminary startup sequence. When “Off” or “BPS” is displayed on the LCD, depressing the “On” button again for 6 seconds will start up the UPS in battery mode (cold start). 3. When the UPS is in utility or battery mode, depressing this button will silence any audible alarms.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.2 Control Button Operation diagram (page 15)
Fig. 25 · 5.2 Control Button Operation
2. When the LCD is in the “Display Programmed Settings” mode, depressing the Function Button will return the LCD to normal mode.
1. When the UPS is operating in utility or battery mode, depressing and holding this button until an audible beep is sounded will leave the load powered in bypass mode. To completely shut down the UPS and connected load, press the Off/Bypass button until “Off” is displayed on the LCD, and then turn off the UPS and Bypass input circuit breakers. The UPS will shut down in about one minute.

The LCD display will also return to “Normal Mode” automatically after 30 seconds of button inactivity.

Previous Page/Change Setting Button

1. When the LCD display is in “Normal Mode”, repeated pressing of this button will sequence up through the input/output/battery parameters and readings will be displayed. 2. When in “Programming Mode”, pressing this button will change the selected parameter setting. The new setting will be displayed on the LCD Measurement display.
1. When the UPS is operating in utility or battery mode, depressing the Function Button will switch the LCD to display the “Programmed Parameter” settings. When in this mode, depressing the “Next Page” button will display the next programmed parameter setting. Repeatedly depress the “Next Page” button to display all of the programmed parameter settings.

On/Alarm Silence Button · Off/Bypass Button · Function Button

Page 16 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 5.3 LED Display Modes
Page 16 · click to enlarge
Page 16

1. When the LCD display is in “Normal Mode”, repeated pressing of this button will sequence down through the input/output/battery parameters and readings. 2. When the UPS is displaying “OFF” or “BPS”, depressing the “Next Page” and “Function” buttons at the same time will place the UPS into “Programming Mode”. Refer to the “How to Change the Programmed Settings” section of this manual for more details. 3. When in “Programming Mode”, repeated pressing of this button will sequentially select the various programmable parameters. Refer to page 27, “How to Change the Programmed Settings” section of this manual for more details.

1. When in “Programming Mode” and prompted on the LCD display to SAVE settings, pressing this button will save all changed parameters.

5.3 LED Display Modes

Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.3 LED Display Modes diagram (page 16)
Fig. 26 · 5.3 LED Display Modes

Utility (AC Source 1) UPS Input Power Present LED (Green) -- Indicates utility power is present and the UPS input circuit breakers is turned on. If the utility voltage is out of tolerance the LED will turn off.

Bypass (AC Source 2) Bypass Input Power Present LED (Green)-- Indicates bypass power is present and the Bypass circuit breaker is turned on. If bypass power is out of range, the LED will turn off.

N+1 Mode Enabled (Green) - Indicates multiple UPS units are connected in parallel and have been properly configured and programmed for Parallel N+1 mode operation.

Economy/Green Mode Enabled (Yellow) -- Indicates Economy/Green mode has been enabled.

Alarm Condition Present (Red) -- Indicates the UPS in an alarm condition.

Next Page Button · Confirm Button

Page 17 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 5.6 Status and Error Code Descriptions
Page 17 · click to enlarge
Page 17

5.4 LCD Display Overview

LCD Display

Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.4 LCD Display Overview diagram (page 17)
Fig. 27 · 5.4 LCD Display Overview
Falcon Uninterruptible Power Supply (FN3KRM-2) — 5.4 LCD Display Overview diagram (page 17)
Fig. 28 · 5.4 LCD Display Overview

Shown in Test Mode

5.5 LCD Icon Descriptions

1. Bypass input is out of tolerance, UPS failed to transfer to bypass, or bypass input is out of tolerance when the UPS is in Economy/Green Mode. 2. Utility loss or the utility input is out of tolerance. 3. UPS lost inverter output and transferred to bypass. 4. Battery voltage is out of tolerance, or defective batteries. 5. The UPS output is overloaded. 6. The UPS is presently in maintenance mode. 7. MIMIC Display showing Line, UPS, Battery and Load. When referenced in conjunction with arrows 8, 9 and 11, it defines the operational state of the UPS. They also indicate the source of the input/output/battery parameter readings displayed on the Measurement Display (12). 8, 9 & 11. MIMIC display and Measurement location indicators. 10. Battery and Low Battery Icons. The battery icon is displayed as part of the MIMIC display. In the event of a utility loss that depletes that battery charge, the Low Battery icon is displayed until the batteries have recharged to a reasonable level. In the event of a complete battery discharge, the low battery icon will be displayed along with an audible alarm. When the batteries have recharged to a reasonable level, the normal battery icon will be displayed. 12. Measurement Display. The Measurement display is used to show the input/output/battery readings, program mode settings, status and error codes.

5.6 Status and Error Code Descriptions

OFF or BPS-- Displayed when the UPS is turned off with the “Off” button, EPO or remote shutdown. EPO -- When an optional EPO communications board is installed, EPO is displayed alternately with the OFF or BPS message, after an EPO signal has been applied to the EPO interface connector. After an EPO condition, the UPS input circuit breaker must be turned off and the “Off” button must be depressed twice for 5 seconds to reset the UPS prior to turning the UPS

and Bypass input circuit breakers back on.

Page 18 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 5.4 LCD Display Overview
Page 18 · click to enlarge
Page 18

Er04 -- Error code 04 indicates the UPS inverter has malfunctioned. Contact Falcon Service. Er05 -- Error code 05 indicates the UPS batteries are weak or dead and must be replaced. Call Falcon Service upon receiving the message for further instructions. Er06 -- Error code 06 indicates the UPS output has a short circuit connected to it. Remove the connected equipment load from the UPS output and restart the UPS. If the shorted output condition is corrected, determine the location of the shorted wiring or equipment. Er07 -- EPO Mode. Er08 -- DC Bus high voltage level out of specification. Contact Falcon Service. Er09 -- DC Bus low voltage level out of specification. Contact Falcon Service. Er10 -- Error code 10 indicates the UPS inverter has encountered an over-current condition. This could indicate the connected equipment exceeds the output rating of the UPS. Disconnect some of the connected equipment in an attempt to correct the condition. Er11 -- Error code 11 indicates the UPS is in an over-temperature condition. Verify the ambient operating temperature is not too high. Verify the UPS cooling fan operation. Er12 -- Error code 12 indicates the UPS output is overloaded, similar to error code 10. This could indicate the connected equipment exceeds the output rating of the UPS. Disconnect some of the connected equipment in an attempt to correct the condition. Er13 -- Battery charger malfunction. Contact Falcon Service. Er14 -- Cooling fan failure. Contact Falcon Service. Er15 -- Maintenance bypass initiated improperly. Refer to page 31, Maintenance Bypass section. Er18 -- Internal software error, UPS programming reset to default values. Er22 -- Static bypass malfunction. Contact Falcon Service. Er24 -- Fixed 50 or 60Hz output mode programmed without turning off the bypass input circuit breaker Should a fixed 50 or 60Hz output be desired, turn the bypass input circuit breaker off. To clear error code 24, startup the UPS with the Bypass input circuit breaker turned off. Er26 -- PFC over-current condition. Verify the UPS output is or has been overloaded. Er28 -- The UPS output has experienced a 120% overload in bypass for over 2 minutes. Bypass has been shutdown. Er29 -- The battery charger is overcharging the batteries. Contact Falcon Service. Er** -- Other error code, consult with Falcon Service.

Page 19 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.1 How to start up the UPS with utility power present
Page 19 · click to enlarge
Page 19

6.0 OPERATION

The following sections outline the operation and programming of the FN -2TXI UPS models. Please read and understand them completely prior to connecting any equipment to the UPS output.

6.1 How to start up the UPS with utility power present

1. Verify the UPS input wiring is correct and connected to a live circuit. 2. Turn on the UPS and Bypass input circuit breakers located on the UPS rear panel, and the following LCD Display will be displayed. The UPS output will be immediately turned on, with the UPS in bypass mode.
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 29 · 6.1 How to start up the UPS with utility power prese…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 30 · 6.1 How to start up the UPS with utility power prese…

Display A is an LCD test display and is shown for about 3 seconds after the input circuit breaker is turned on.

Next, display B is shown (OFF or BPS displayed). The UPS is OFF with the load supported by the bypass output. The UPS will remain in this state until the “On” button is depressed. When the UPS is turned off using the “Off” button, it will return to this state until the input circuit breaker is turned off.

3. Depress the “On” button for 3 seconds until two audible beeps are sounded. 4. The UPS fans will turn on and the following LCD display will be shown:
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 31 · 6.1 How to start up the UPS with utility power prese…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 32 · 6.1 How to start up the UPS with utility power prese…

The UPS will sound two short beeps continuously until the following is displayed.

5. The UPS will now sequence up to on-line mode and display the following:
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 33 · 6.1 How to start up the UPS with utility power prese…
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.1 How to start up the UPS with utility power present diagram (page 19)
Fig. 34 · 6.1 How to start up the UPS with utility power prese…

The UPS initiates a self-test.

Go to the next page.

Page 20 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.0 OPERATION
Page 20 · click to enlarge
Page 20
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.0 OPERATION diagram (page 20)
Fig. 35
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.0 OPERATION diagram (page 20)
Fig. 36

If the UPS passes the self-test, “OK” is displayed.

If the UPS fails the self-test, “FAIL” is displayed alternately with an error code. Please note the error code and contact Falcon Service.

The UPS is now turned on and in on-line inverter mode. Using an AC volt meter, verify the UPS input voltage measurement.

Page 21 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.4 How to completely shutdown the UPS
Page 21 · click to enlarge
Page 21

6.2 How to start up the UPS without utility power present (Cold Start)

1. Press the “On” button for 6 seconds to awaken the UPS. The UPS will beep twice and display G below. Immediately upon G being displayed, press the “On” button for another 6 seconds. The UPS will beep twice again and sequence through H and I.
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.4 How to completely shutdown the UPS diagram (page 21)
Fig. 37 · 6.4 How to completely shutdown the UPS
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.4 How to completely shutdown the UPS diagram (page 21)
Fig. 38 · 6.4 How to completely shutdown the UPS
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.4 How to completely shutdown the UPS diagram (page 21)
Fig. 39 · 6.4 How to completely shutdown the UPS
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.4 How to completely shutdown the UPS diagram (page 21)
Fig. 40 · 6.4 How to completely shutdown the UPS

After depressing the “On” button for 6 seconds the first time, the UPS will beep twice and “OFF” or “BPS” will be displayed.

After depressing the “On” button the second time for 6 seconds, the UPS will display input voltage H and I. The UPS output voltage will be present and the UPS will continue to run on battery until the batteries are discharged or the “Off” button is pressed for 3 seconds.

6.3 How to turn off the UPS inverter and place the UPS into bypass mode

1. While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD will display “OFF” or “BPS”. The connected load will now be powered directly from the utility source. The UPS will continue to operate in bypass mode until:

a. The “On” button is depressed for three seconds, which will return the UPS to normal

inverter mode operation. b. The UPS and Bypass Input circuit breakers are turned off, which will shut down the UPS and

the connected load completely.

6.4 How to completely shutdown the UPS

1. While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS

sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD will display “OFF” or “BPS”. 2. Turn off the UPS and Bypass input circuit breakers, which will shutdown the UPS and the connected load completely. Note, the UPS may continue to run for 30 seconds to one minute prior to turning off.

Page 22 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.5 How to display readings
Page 22 · click to enlarge
Page 22

6.5 How to display readings

1. The bypass input voltage is displayed immediately after the UPS and Bypass circuit breakers are turned on and has sequenced up to inverter mode as shown in I1. Depressing the “Next Page” button will change to display the utility frequency as shown in J below.
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 41 · 6.5 How to display readings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 42 · 6.5 How to display readings

The “b” denotes the reading is for the bypass. The arrow under the LINE indicates the reading is for the bypass input voltage.

Depress the “Next Page” button.

The “r” denotes the reading is for utility. The arrow under the LINE indicates the reading is for the utility frequency.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 43 · 6.5 How to display readings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 44 · 6.5 How to display readings

Depress the “Next Page” button.

The “b” denotes the reading is for the bypass.

Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 45 · 6.5 How to display readings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 22)
Fig. 46 · 6.5 How to display readings

The arrow under the LOAD indicates the reading is for the UPS output voltage.

Depress the “Next Page” button.

The arrow under the LOAD indicates the reading is for the UPS output frequency.

Depress the “Next Page” button.

The arrow under the LOAD indicates the reading is for the UPS output and indicates the percentage of output load connected to the UPS.

Page 23 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.5 How to display readings
Page 23 · click to enlarge
Page 23
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 23)
Fig. 47 · 6.5 How to display readings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.5 How to display readings diagram (page 23)
Fig. 48 · 6.5 How to display readings

Depress the “Next Page” button.

The arrow next to the battery icon indicates the reading is for the battery voltage.

Depress the “Next Page” button.

The degree C symbol indicates the reading is for the internal UPS temperature.

Depressing the “Next Page” button again will return the display to reading I1.

Page 24 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.6 How to Display Programmed Settings
Page 24 · click to enlarge
Page 24

6.6 How to Display Programmed Settings

1. The UPS must be turned on and operating in on-line inverter mode prior to attempting to read the “programmed settings”. 2. Depress the “Function” button and the following first function parameter will be displayed:
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 49 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 50 · 6.6 How to Display Programmed Settings

The first function status displayed will be the audible alarm buzzer status. It is shown here to be turned on.

If the “Previous Page/Change Setting” button is pressed, the audible alarm will be turned off. Depressing the button again will turn the alarm back on. Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 51 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 52 · 6.6 How to Display Programmed Settings

Next, the self-test status is displayed. Here the self-test is shown to be in the “Test Not On” state.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 53 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 54 · 6.6 How to Display Programmed Settings

If the “Previous Page/Change Setting” button is pressed, a UPS self-test will be initiated and the following displays will be shown.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 55 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 24)
Fig. 56 · 6.6 How to Display Programmed Settings

Depress the “Next Page” button.

Go to the next page.

Page 25 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.6 How to Display Programmed Settings
Page 25 · click to enlarge
Page 25

displayed and must have their settings changed using another programming method referenced later in the manual. As the other programming method requires turning the UPS off to perform, they are accessible here as a convenient reference while the UPS is in normal online operation.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 25)
Fig. 57 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 25)
Fig. 58 · 6.6 How to Display Programmed Settings

The next parameter displayed shows the “bypass input voltage acceptable window” setting. The voltage window can be set to “Lo” (184-260Vac) or “Hi” (195-260Vac), which is shown below.

Depress the “Next Page” button.

The next parameter displayed shows acceptable input frequency window. The window can be set to +/-3Hz (shown), or +/-1Hz (not shown).

Depress the “Next Page” button.

The next parameter display is the inverter output voltage setting. The inverter output voltage can be set to 200Vac (not shown), 220Vac (shown), 230Vac (not shown) or 240Vac (not shown).

Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 25)
Fig. 59 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 25)
Fig. 60 · 6.6 How to Display Programmed Settings

The following V1, V2, V3 and V4 show the operational status setting of the UPS. This function may be set to one of four modes. “Normal” indicates none of the other modes are set.

Economy/Green ModeIndicates the UPS will

automatically transfer to bypass mode to save energy, one minute after the output load drops below 10% of the UPS output rating.

Page 26 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.6 How to Display Programmed Settings
Page 26 · click to enlarge
Page 26
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 61 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 62 · 6.6 How to Display Programmed Settings

Fixed or constant frequency output mode: In normal mode the UPS output frequency will automatically be set to the utility frequency and is

synchronized with that frequency. When set to cf50Hz mode, the UPS inverter output frequency will always be 50Hz. When set to cf60Hz mode, the UPS inverter output frequency will always be 60Hz.

Setting the UPS to a fixed or constant output frequency should be done when the input source is a generator.

Depress the “Next Page” button.

The next parameter displayed shows the inverter output voltage adjustment. The adjustment can be set to 0% (shown), +1%, -1%, +2%, -2%, +3%or -3% (not shown).

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 63 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 64 · 6.6 How to Display Programmed Settings

Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 65 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 66 · 6.6 How to Display Programmed Settings

The next parameter displayed shows the UPS unit address. If only one UPS is being used, the address should be set to “d0” as shown.

If multiple parallel UPS units are connected in a parallel configuration of 6, 12, 18 or 24kVA, or 6, 12, 18kVA N+1 operation, the units would be addressed “d0”, “d1”, “d2” and “d3”. See the parallel mode configuration section on page 30 of this manual for more details.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 67 · 6.6 How to Display Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.6 How to Display Programmed Settings diagram (page 26)
Fig. 68 · 6.6 How to Display Programmed Settings

Depress the “Next Page” button.

The next parameter displayed shows the UPS position when it is used in a parallel configuration. The positions are “01”, “02”, “03”, or “04”.

If only one UPS is being configured, the position should be set to “01” as shown.

Page 27 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.7 How to Change the Programmed Settings
Page 27 · click to enlarge
Page 27

6.7 How to Change the Programmed Settings

following parameter settings.

1. To enter programming mode depress the “On” and “Next Page” buttons at the same time and hold them down until the UPS sounds two beeps. The audible alarm status parameter setting will be displayed.
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 27)
Fig. 69 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 27)
Fig. 70 · 6.7 How to Change the Programmed Settings

The audible alarm parameter settings cannot be set in this programming mode. Refer to section 6 of this manual for setup instructions.

Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 27)
Fig. 71 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 27)
Fig. 72 · 6.7 How to Change the Programmed Settings

Self-test parameter settings cannot be set in this programming mode. Refer to section 6 of this manual for setup instructions.

Depress the “Next Page” button and go to the next page.

Page 28 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.7 How to Change the Programmed Settings
Page 28 · click to enlarge
Page 28
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 28)
Fig. 73 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 28)
Fig. 74 · 6.7 How to Change the Programmed Settings

The next parameter displayed shows the “bypass input voltage acceptable window” setting. The voltage window can be set to “Lo” (184-260Vac) or “Hi” (195-260Vac), which is shown below.

To change the settings, depress the “Previous Page/Change Setting” button. To change to the alternate setting, press the button again. All setting changes will be saved when prompted at the end of the parameter sequence.

Depress the “Next Page” button.

The next parameter displayed shows the acceptable input frequency window. The window can be set to +/-3Hz (shown), or +/-1Hz (not shown).

To change the settings, depress the “Previous Page/Change Setting” button. To change to the alternate setting, press the button again. All setting changes will be saved when prompted at the end of the parameter sequence.

Depress the “Next Page” button.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 28)
Fig. 75 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 28)
Fig. 76 · 6.7 How to Change the Programmed Settings

The next parameter display is the inverter output voltage setting. The inverter output volt- age can be set to 200Vac (not shown), 220Vac (shown), 230Vac (not shown) or 240Vac (not shown).

To change the settings, depress the “Previous Page/Change Setting” button. To change to another voltage setting, repeat pressing the button until the desired voltage is displayed. All setting changes will be saved when prompted at the end of the parameter sequence.

Depress the “Next Page” button and go to the next page.

Page 29 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.7 How to Change the Programmed Settings
Page 29 · click to enlarge
Page 29
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 29)
Fig. 77 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 29)
Fig. 78 · 6.7 How to Change the Programmed Settings

The following V1, V2, V3 and V4 show the operational status setting of the UPS. This function may be set to one of four modes. “Normal”: which indicates none of the other modes are set.

The Economy/Green Mode: indicates the UPS will automatically transfer to bypass mode to save energy, should the output load drop below 10% of the UPS output rating.

Fixed or constant frequency output mode: In normal mode the UPS output frequency will automatically be set to the utility frequency and is synchronized with that frequency. When set to cf50Hz mode, the UPS inverter output frequency will always be 50Hz. When set to cf60Hz mode, the UPS inverter output frequen- cy will always be 60Hz.

Setting the UPS to a fixed or constant output frequency should be done when the input source is a generator.

To change between these settings, depress the”Previous Page/Change Setting” button. Repeat pressing the button until the desired mode setting is displayed. All setting changes will be saved when prompted at the end of the parameter sequence.

Depress the “Next Page” button.

The next parameter displayed shows the inverter output voltage adjustment. The adjustment can be set to 0% (shown), +1%, -1%, +2%, -2%, +3%or -3% (not shown).

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 29)
Fig. 79 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 29)
Fig. 80 · 6.7 How to Change the Programmed Settings

To change between these settings, depress the “Previous Page/Change Setting” button. Repeat pressing the button until the desired mode setting is displayed. All setting changes will be saved when prompted at the end of the parameter sequence.

Page 30 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.7 How to Change the Programmed Settings
Page 30 · click to enlarge
Page 30

The next parameter displayed shows the UPS unit address. If only one UPS is being used, the address should be set to “d0” as shown.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 30)
Fig. 81 · 6.7 How to Change the Programmed Settings

If multiple parallel UPS units are connected on a parallel configu- ration of 6, 12, 18 or 24kVA, or 6, 12, 18kVA N+1 operation, the units would be addressed “d0”, “d1”, “d2” and “d3”. See the parallel mode configuration sec- tion of this manual for more details.

To change between these settings, depress the “Previous Page/Change Setting” button. Repeat pressing the button until the desired address setting is displayed. All setting changes will be saved when prompted at the end of the parameter setup.

Depress the “Next Page” button.

The next parameter displayed shows the UPS position when used in a parallel configuration. The positions are “01”, “02”, “03”, or “04”.

If only one UPS is being configured, the position should be set to “01” as shown.

To change between these settings, depress the “Previous Page/Change Setting” button. Repeat pressing the button until the desired UPS position setting is displayed. All setting changes will be saved when prompted at the end of the parameter setup.

Depress the “Next Page” button.

At the end of the parameter setup mode, you will be prompt- ed to save the settings.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 30)
Fig. 82 · 6.7 How to Change the Programmed Settings
Falcon Uninterruptible Power Supply (FN3KRM-2) — 6.7 How to Change the Programmed Settings diagram (page 30)
Fig. 83 · 6.7 How to Change the Programmed Settings

To save the settings press the “Confirm” button. If you do not wish to save the settings, press the Off / Bypass button for five seconds. The LCD will display OFF to indicate the settings are not saved.

Page 31 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 6.7 How to Change the Programmed Settings
Page 31 · click to enlarge
Page 31

6.8 How to Use the Maintenance Bypass Switch Located on the Rear Panel

1. Press the”Off/Bypass” button for 5 seconds to place the UPS into bypass mode. 2. On the rear of the transformer module, remove the two phillips screws securing the upper and lower sides of the maintenance bypass security cover plate. 3. On the rear of the transformer module, turn the Maintenance Bypass Switch to “Bypass”. The maintenance bypass icon will be displayed on the LCD display. 4. The output transformer is now in maintenance bypass mode. 5. To return to normal UPS mode operation, switch the Maintenance Bypass Switch to INV. Replace the switch cover plate and secure it with the screws previously removed. 6. Press the “On” button on the UPS module to return the UPS to normal inverter operation.

Page 32 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — The UPS & PC Computer DB-9 pin designations are as follows:
Page 32 · click to enlarge
Page 32

7.0 COMMUNICATIONS

All FN models are provided with the following communication ports: RS-232 port with standard DB-9F serial port connector located on the UPS module rear panel. Two advanced communications option slots are provided on the rear panel of the UPS module. Unless an advanced communications option board has been previously purchased and installed, the port will be covered with a small cover plate. This plate will be secured with (2) screws.

7.1 Advanced Communications Option Cards Available:

a. USHA TYPE SNMP/HTTP Agent Board b. Dry Contact with EPO Interface Board (P/N UA88383) c. USB & EPO Interface Board (P/N UA88382) d. RS485 & EPO Interface Board (P/N UA88381) e. Second RS-232 Interface Card (P/N UA88380)

7.2 RS-232 Port

The UPS is equipped with (1) RS-232 port located on the UPS module rear panel. A standard RS-232C inter- face cable is provided to allow for the connection of the UPS to another RS-232 port found on most comput- ers. When an RS-232 cable has been connected, and the supplied UPSilon computer shutdown and management software has been properly installed on the connected computer, a high level of UPS management and protection against lost or corrupted files is in effect. Please follow the installation and setup instructions supplied on the UPSilon software CD.

The UPSilon users manual is also located on the UPSilon CD supplied with this unit. UPSilon supports most popular operating systems. Should you have special UNIX requirements, please contact Falcon Sales for information and pricing of UPSilon for UNIX.

The UPS & PC Computer DB-9 pin designations are as follows:

Falcon Uninterruptible Power Supply (FN3KRM-2) — The UPS & PC Computer DB-9 pin designations are as follows: diagram (page 32)
Fig. 84 · The UPS & PC Computer DB-9 pin designations are as f…
Falcon Uninterruptible Power Supply (FN3KRM-2) — The UPS & PC Computer DB-9 pin designations are as follows: diagram (page 32)
Fig. 85 · The UPS & PC Computer DB-9 pin designations are as f…
Page 33 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — CN3
Page 33 · click to enlarge
Page 33

The supplied Falcon RS-232 interface cable pin designations are as follows:

Falcon Uninterruptible Power Supply (FN3KRM-2) — The supplied Falcon RS-232 interface cable pin designations are as follows: diagram (page 33)
Fig. 86 · The supplied Falcon RS-232 interface cable pin desig…
Falcon Uninterruptible Power Supply (FN3KRM-2) — The supplied Falcon RS-232 interface cable pin designations are as follows: diagram (page 33)
Fig. 87 · The supplied Falcon RS-232 interface cable pin desig…

UPS Side RS-232C Interface Computer Side

The computer RS-232 Port settings should be set to the following:

Falcon Uninterruptible Power Supply (FN3KRM-2) — UPS Side RS-232C Interface Computer Side diagram (page 33)
Fig. 88 · UPS Side RS-232C Interface Computer Side
Falcon Uninterruptible Power Supply (FN3KRM-2) — UPS Side RS-232C Interface Computer Side diagram (page 33)
Fig. 89 · UPS Side RS-232C Interface Computer Side

7.3 Optional Remote Emergency Power Off (REPO)

A two-pin REPO connector (green connector) is located on the UPS module rear panel. The connector is shipped with no jumper wire installed, and is a normally open interface requiring a CLOSED EPO connection to initiate EPO UPS shutdown.

Upon receiving the remote EPO switch contact closure, the UPS will immediately turn off it’s inverter and bypass outputs, in addition to placing the UPS into an “OFF” state and sounding an audible alarm. “OFF” and “EPO” will be alternately displayed on the LCD panel.

After removal of the EPO contact closure, the UPS must be completely shut down and restarted to clear the EPO condition.

7.4 Optional Communications Interface Board Details

UA88380 Second RS-232 Interface Option Board

This communications board supports the connection of a second RS-232 DB-9 connection to the UPS, in addition to providing (1) two-pin EPO interface connector. The DB-9 pinout is identical to the standard DB-9 RS-232 interface found on the UPS rear panel.

UA88381 RS-485 Interface Option Board

This communications board has (1) RS485 standard interface (CN2), in addition to providing (1) two-pin EPO interface connector (CN1), and (1) two-pin remote power connector (CN3).

Pin 1 - Ground Pin 2 - A/Data+ Pin 3 - B.Data-

CN2

Falcon Uninterruptible Power Supply (FN3KRM-2) — CN2 diagram (page 33)
Fig. 90

1 2 CN1 Pin 1 - REPO 1 Pin 2 - REPO 2

CN3

Pin 1 - AC+ Pin 2 - AC-

Page 34 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — USHA SNMP/HTTP Agent Option Card
Page 34 · click to enlarge
Page 34

UA88382 USB Interface Option Card

This option card supports the connection of (1) USB interface cable for use with UPSilon remote monitoring, management and unattended O/S shutdown software.

Falcon Uninterruptible Power Supply (FN3KRM-2) — UA88382 USB Interface Option Card diagram (page 34)
Fig. 91 · UA88382 USB Interface Option Card

2 Pin 1 - VCC (+5V) Pin 2 - D- Pin 3 - D+ Pin 4 - Ground

1 2 CN1 Pin 1 - REPO 1 Pin 2 - REPO2

UA88383 Dry Contact Interface Option Card

This card provides dry contact closure signals for UPS on bypass, utility normal, inverter on, low battery, abnormal battery, UPS summary alarm. It also provides EPO and remote UPS shutdown capability.

Pin 1 - UPS on Bypass Pin 2 - Utility Abnormal Pin 3 - Utility Normal Pin 4 - Inverter On Pin 5 - Low Battery Pin 6 - Abnormal Battery Pin 7 - UPS Summary Alarm Pin 8 - Common Pin 9 - Shutdown UPS (+) signal Pin 10 - Shutdown UPS (-) signal

1 2 3 4 5 6 7 8 9 10

Falcon Uninterruptible Power Supply (FN3KRM-2) — UA88383 Dry Contact Interface Option Card diagram (page 34)
Fig. 92 · UA88383 Dry Contact Interface Option Card

Pins 9 & 10 apply 6-25Vdc for 5 seconds to activate shutdown.

USHA SNMP/HTTP Agent Option Card

Falcon Uninterruptible Power Supply (FN3KRM-2) — USHA SNMP/HTTP Agent Option Card diagram (page 34)
Fig. 93 · USHA SNMP/HTTP Agent Option Card

Now you can monitor and manage your Falcon Electric FN Series UPS across an Ethernet LAN, WAN, Enterprise Network or via the World Wide Web. With our Universal SNMP/HTTP Agent board (USHA), remote management is easy using a standard web browser or Network Management Software (NMS).

Remote SNMP/HTTP UPS management is a simple matter of inserting our USHA board into the designated option port provided on the rear panel of every FN Series UPS.

The USHA board is supplied with a SNMP UPS MIB II compliant "snap-in" Management Information Base (MIB). The MIB is compatible with HP OpenView and other Network Management Software (NMS).

Remote server and computer shutdown client software is also provided on the CD that is shipped with this option. The software supports the shutdown of multiple servers or computers “in-band” across any Ethernet LAN. The client software may be installed on as many systems as required and supports most MS Windows and server platforms, in addition to LINUX.

Page 35 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 4. Battery Replacement
Page 35 · click to enlarge
Page 35

8.0 MAINTENANCE

The FN Series UPS requires very little maintenance. The batteries are located inside the battery module and consist of (20) Yuasa 12V, 7AH or equivalent, sealed, VRLA, maintenance-free, lead-acid batteries.

Batteries must be kept recharged to prevent excessive self-discharging, which may result in their premature failure. When connected to the battery module, the UPS will continuously recharge the bat- teries when plugged in and turned on. When not in use, batteries must be recharged every 6 months to keep your warranty valid.

1. The UPS and Battery Care

Keep the area around the UPS clean and dust free. If the area around the UPS becomes very dusty, clean it with a vacuum cleaner. To assure the full 3-5 year battery life, keep the UPS battery module at an ambient temperature of 77ºF (25ºC). Other than replacement at three to five years of service, no other battery maintenance is required.

2. Storing the UPS and Batteries

When storing the UPS for any amount of time, it is recommended to connect the battery module and turn on the UPS for at least 24 hours, every four to six months to ensure full recharging of the batteries. This will pre- vent excessive battery self-discharge.

3. When to Replace Batteries

We suggest the battery pack(s) be replaced every 3-5 years for FN units that are operated and maintained in a 77ºF (25ºC) environment. Higher temperature operating environments will decrease the battery life. Typically, if the UPS is installed in a 104ºF (40ºC) or above operating environment, the batteries will need to be replaced once a year.

In order to assure the performance of the FN Series UPS, check the battery every two to three months by performing a UPS self-test. If at any time the UPS LCD panel displays the weak or defective battery icon or error code, the batteries need replacing. Contact the Falcon Electric Service Department to order replacement batteries.

4. Battery Replacement

Battery replacement inside the battery module must be performed by a qualified service technician. Contact Falcon service when battery replacement is required.

Page 36 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 9.0 PARALLEL MODE OPERATION
Page 36 · click to enlarge
Page 36

9.0 PARALLEL MODE OPERATION

9.1 How to configure FN rackmount models for transformer module, parallel or N+1 mode operation.

Up to (4) like kVA FN model UPS units may be connected to their respective transformer modules and/or in parallel, in single UPS increments, to provide a single 3-24kVA UPS output a true N+1 redundant output. This is accomplished by connecting each UPS to be paralleled, wired to a single utility source rated for the com- bined UPS load. The UPS outputs should be connected together. A licensed electrician can provide the hard- wire output connections and circuit. Each individual UPS output must have a branch rated circuit breaker as specified prior, installed between the UPS output and load.

FN models have two special bus connectors located on the UPS rear panel that supports interconnection of the transformer module and/or paralleled UPS units. (1) parallel UPS interface kit must be purchased from Falcon for each UPS to be paralleled. The cable kit is shipped with each transformer module inside the shipping container. The interface kit contains (1) daisy chain bus cable (3076), (1) wrap around bus cable (3077), detailed installation instructions and assorted hardware. The Falcon part number for the kit is UA88385.

9.2 How to connect the Battery Module to the UPS module. 1. Open the battery connector cover plate from the UPS module rear panel and connect the supplied red, black and green battery cable connectors to the respectively colored mating connectors on the UPS module. 2. On the battery module rear panel verify the battery circuit breaker is in the off position. Next, open the top battery connector cover plate. Connect the red, black and green connectors on the opposite side of the battery cable to the respectively colored mating connectors on the battery module. Turn on the battery module circuit breaker. The UPS may now be powered up. 3. To add a more battery modules, remove the lower cover plate on the first module and connect a the supplied battery cables to this connector on the previous battery module.

Falcon Uninterruptible Power Supply (FN3KRM-2) — 9.0 PARALLEL MODE OPERATION diagram (page 36)
Fig. 94
Falcon Uninterruptible Power Supply (FN3KRM-2) — 9.0 PARALLEL MODE OPERATION diagram (page 36)
Fig. 95

For more details, contact Falcon Sales or Support Engineering.

Page 37 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — 10.2 FCC Considerations
Page 37 · click to enlarge
Page 37

10.0 ENVIRONMENTAL

10.1 Recycling the Used Battery Packs

NEVER discard the UPS module, the UPS battery module, the transformer module or batteries in the trash. Contact your local recycling or hazardous waste center for information on proper disposal of the used battery pack and batteries. The entire spent battery packs may be returned to the Falcon Service Center at the end user’s expense for recycling. Prior to returning the spent battery pack(s), please call the Falcon Service Center and obtain a Return Materials Authorization (RMA) number.

NEVER dispose of batteries in a fire, as batteries will explode.

NEVER dispose of used batteries or the UPS in the trash or a landfill as it is a violation of federal and state laws. The UPS and batteries must be recycled. For UPS and battery recycling information, please contact Falcon Service for the name and address of the nearest battery recycling facility.

NEVER open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. A battery can present a risk of electrical shock and burns due to their high short circuit current capability.

WARNING

Observe all warnings, cautions, and notes before replacing batteries. Batteries can present a risk of electrical shock and burns due to high short circuit current. The following precautions should be observed when working on batteries:

* Remove watches, rings, and other metal objects. * Use tools with insulated handles. * Do not lay tools or metal parts on top of batteries. * Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. * Do not dispose of batteries in a fire. The batteries may explode. Refer to your local codes for disposal requirements. * Do not open or mutilate the battery packs or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

10.2 FCC Considerations

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in an industrial installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

* Reorient or relocate the receiving antenna. * Increase the separation between the equipment and receiver. * Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. * Consult the dealer or an experienced radio/TV technician for help.

Page 38 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — WWW.FALCONUPS.COM
Page 38 · click to enlarge
Page 38

11.0 TECHNICAL SUPPORT In the event your FN Series UPS requires service or should any other technical support be required, write, call, fax or email Falcon Service.

Falcon Electric, Inc. 5106 Azusa Canyon Road Irwindale, CA. 91706 Service 800.842.6940 Voice 626.962.7770 Fax 626.962.7720 Email: service@falconups.com WWW.FALCONUPS.COM

Please have your UPS model, serial number and date of purchase on hand prior to your call. This information is located on the identification label on the rear panel of the UPS. This information is essential in retrieving your unit’s historical records. Should our service department determine service is required, you will be given a Return Material Authorization number (RMA) along with return shipping instructions.

The RMA number issued must appear on the outside of the shipping carton. The original shipping container must be used when returning any FN Series product. Failure to use the original shipping container and packing materials will likely result in the unit being received by Falcon with shipping damage.

Falcon Electric will not assume any responsibility for shipping damage. In the event shipping damage is found, you will be notified of the damage and be instructed to file a claim with the freight carrier. You will be billed for all required repairs due to the shipping damage. You must submit a copy of our repair invoice to the carrier for reimbursement.

All units must be returned prepaid. The address and shipping instructions will be given to you at the time the RMA is issued.

Requesting Technical Information or Support

You may request technical information or support by email or telephone.

Please send your technical or support questions by email to:

[email protected]

You may contact a FALCON support engineer directly by calling the FALCON support line between 9:00 am and 4:00 pm PST.

800.842.6940 FALCON Web Support

Product data sheets, specifications and owner’s manuals are available in Adobe®

Acrobat .PDF format on our corporate website at:

WWW.FALCONUPS.COM

Page 39 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — NEW PRODUCT LIMITED WARRANTY
Page 39 · click to enlarge
Page 39

FALCON ELECTRIC, INC.

NEW PRODUCT LIMITED WARRANTY

Limited Warranty: Falcon warrants that this product will be free from defects in materials and workmanship for a period of two years from the date of shipment by Falcon.

Procedures: Any defective product must be returned to Falcon. No product can be returned without first obtaining a Return Material Authorization (RMA) number from Falcon. Falcon will repair, replace or refund the purchaser price, at Falcon’s sole discretion, for any defective product that is returned to Falcon with an RMA number. For defective product returned within 30 days of shipment, Falcon will pay for shipping costs to and from its service center. For defective product returned after 30 days but within 90 days of shipment, Falcon will only pay for shipping costs in sending the new or repaired product back to the end-user. For defective product returned more than 90 days after shipment, all shipping costs will be borne by the end-user.

Exclusions: This limited warranty does not cover damage caused by: (i) improper installation, misuse or neglect; (ii) unauthorized repairs or modifications or use of unautho- rized parts; (iii) acts or events outside of Falcon’s control, such as fire, accidents, impacts; (iv) normal wear and tear, such as cleaning and replacement of batteries. The warranty is null and void if: (i) the product is used in conjunction with life support equipment; (ii) the factory seal is broken or shows signs of tampering; or (iii) the battery is allowed to discharge below the minimum battery cutoff point. To prevent this discharge, remove the battery fuse, or switch the battery disconnect to the “off” position when the unit is to be stored without the AC power being supplied to the UPS for more than two days. The battery must be recharged every four to six months when not in use. This limited warranty is not transferable.

Limitations: IN NO EVENT IS FALCON RESPONSIBLE FOR ANY SPECIAL, INDIRECT, SECONDARY OR CONSEQUENTIAL DAMAGES, SUCH AS PERSONAL INJURY, DAMAGE TO PROPERTY, LOSS OF DATA, LOST PROFITS, ETC. IN NO EVENT WILL FALCON’S LIABILITY UNDER THIS LIMITED WARRANTY EXCEED THE PURCHASE PRICE PAID FOR THE PRODUCT IN QUESTION.

Disclaimers: The limited warranties set forth in this document are the only warranties that apply to Falcon’s products. ALL OTHER WARRANTIES ARE EXPRESSLY DISCLAIMED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY HAVE OTHER LEGAL RIGHTS THAT VARY FROM STATE TO STATE.

2007-04 Rev. C

Page 40 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN Series TM UPS PLUS ® 3kVA - 12kVA
Page 40 · click to enlarge
Page 40

FN Series TM UPS PLUS ® 3kVA - 12kVA

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 3kVA - 12kVA diagram (page 40)
Fig. 96 · FN Series TM UPS PLUS ® 3kVA - 12kVA
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 3kVA - 12kVA diagram (page 40)
Fig. 97 · FN Series TM UPS PLUS ® 3kVA - 12kVA

Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720

www.falconups.com - emailsales@ falconups.com
Page 41 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN Series TM UPS PLUS ® 4kVA - 16kVA
Page 41 · click to enlarge
Page 41

FN Series TM UPS PLUS ® 4kVA - 16kVA

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 4kVA - 16kVA diagram (page 41)
Fig. 98 · FN Series TM UPS PLUS ® 4kVA - 16kVA
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 4kVA - 16kVA diagram (page 41)
Fig. 99 · FN Series TM UPS PLUS ® 4kVA - 16kVA

Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720

www.falconups.com - emailsales@ falconups.com
Page 42 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN Series TM UPS PLUS ® 5kVA - 20kVA
Page 42 · click to enlarge
Page 42

FN Series TM UPS PLUS ® 5kVA - 20kVA

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 5kVA - 20kVA diagram (page 42)
Fig. 100 · FN Series TM UPS PLUS ® 5kVA - 20kVA
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 5kVA - 20kVA diagram (page 42)
Fig. 101 · FN Series TM UPS PLUS ® 5kVA - 20kVA
Page 43 of the Falcon Uninterruptible Power Supply (FN3KRM-2) user manual — FN Series TM UPS PLUS ® 6kVA - 24kVA
Page 43 · click to enlarge
Page 43

FN Series TM UPS PLUS ® 6kVA - 24kVA

Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 6kVA - 24kVA diagram (page 43)
Fig. 102 · FN Series TM UPS PLUS ® 6kVA - 24kVA
Falcon Uninterruptible Power Supply (FN3KRM-2) — FN Series TM UPS PLUS ® 6kVA - 24kVA diagram (page 43)
Fig. 103 · FN Series TM UPS PLUS ® 6kVA - 24kVA

Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 - Fax 626.962.7720

www.falconups.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Falcon Uninterruptible Power Supply (FN3KRM-2)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Falcon Uninterruptible Power Supply (FN3KRM-2)

Be the first to ask — other owners or our team will answer.

Original document

Falcon Uninterruptible Power Supply (FN3KRM-2) manual PDF

43 pages·3.7 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…