EN
Emerson Process Management logo
Official user manual

Emerson Process Management Micro Motion 2400S

188 pages·2.5 MB·Satellite Radio·PDF·ENDEFRITNLJA
Emerson Process Management Micro Motion 2400S
Table of Contents 193 sections Contents · Before You Begin · 1.1 Overview · 1.2 Safety · … ShowHide
Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 1 of the Emerson Process Management Micro Motion 2400S user manual — Configuration and Use Manual P/N MMI-20007739, Rev. B July 2008
Page 1 · click to enlarge
Page 1

Configuration and Use Manual P/N MMI-20007739, Rev. B July 2008

Micro Motion ®

Model 2400S Transmitters for DeviceNet ™

Page 2 of the Emerson Process Management Micro Motion 2400S user manual
Page 2 · click to enlarge
Page 2

©2008, Micro Motion, Inc. All rights reserved. ELITE and ProLink are registered trademarks, and MVD and MVD Direct Connect are trademarks of Micro Motion, Inc., Boulder, Colorado. Micro Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. All other trademarks are property of their respective owners.

Page 3 of the Emerson Process Management Micro Motion 2400S user manual — Table of Contents
Page 3 · Contents
Contents

Contents

Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 9 of the Emerson Process Management Micro Motion 2400S user manual — 2400S*X*X******
Page 9 · click to enlarge
Page 9

Chapter 1 Before You Begin

Startup Using ProLink II Transmitter User Interface Before You Begin

1.1 Overview

This chapter provides an orientation to the use of this manual, and includes a configuration overview flowchart and a pre-configuration worksheet. This manual describes the procedures required to start, configure, use, maintain, and troubleshoot the Micro Motion® Model 2400S transmitter for DeviceNet™ (the Model 2400S DN transmitter).

If you do not know what transmitter you have, see Section 1.3 for instructions on identifying the transmitter type from the model number on the transmitter’s tag.

1.2 Safety

Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.

1.3 Determining transmitter information

Transmitter type, user interface option, and output options are encoded in the model number located on the transmitter tag. The model number is a string of the following form:

2400S*X*X******

In this string:

  • 2400S identifies the transmitter family.
  • The first X (the seventh character) identifies the I/O option:

- C = DeviceNet

  • The second X (the ninth character) identifies the user interface option:

- 1 = Display with glass lens

- 3 = No display

- 4 = Display with non-glass lens

Page 10 of the Emerson Process Management Micro Motion 2400S user manual — 1.6 Communication tools
Page 10 · click to enlarge
Page 10

Before You Begin

1.4 DeviceNet functionality

The Model 2400S DN transmitter implements the following DeviceNet functionality:

  • Baud rates:
  • I/O slave messaging:
  • Configuration methods:

- EDS

1.5 Determining version information

Table 1-1 lists the version information that you may need and describes how to obtain the information.

Table 1-1 Obtaining version information

Component With ProLink II With DeviceNet tool (1)

With display

Transmitter software revision(2)

ProLink II title bar or View/Installed Options/ Software Revision

Identity Object (0x01) Instance 1 Attribute 198

OFF-LINE MAINT/VER

Software revision corresponding to revision specified on ODVA certificate

Not available Identity Object (0x01) Instance 1 Attribute 4

Hardware revision Not available Identity Object (0x01) Instance 1 Attribute 105

(1) See Chapter 5 for more information.

(2) Also represents the core processor version.

1.6 Communication tools

Most of the procedures described in this manual require the use of a communication tool. The following communication tools can be used:

  • Transmitter display, if the transmitter was ordered with a display. The display provides only partial configuration functionality.
  • ProLink ® II software, v2.5 and later. ProLink II provides complete configuration functionality for the transmitter, but does not provide DeviceNet configuration functionality.
  • Pocket ProLink software, v1.3 and later. Pocket ProLink provides complete configuration functionality for the transmitter, but does not provide DeviceNet configuration functionality.
  • Customer-supplied DeviceNet tool. Capabilities depend on the tool.
Show 9 more labels / short text on this page
- 125 kBaud · - 250 kBaud · - 500 kBaud · - Polling · - Cyclic · - Hardware switches · - Custom software · Not available · Not available
Page 11 of the Emerson Process Management Micro Motion 2400S user manual — 1.7 Planning the configuration
Page 11 · click to enlarge
Page 11

Before You Begin

In this manual:

  • Basic information on using the transmitter’s user interface is provided in Chapter 3.

Startup Using ProLink II Transmitter User Interface Before You Begin

  • Basic information on using ProLink II or Pocket ProLink, and connecting ProLink II or Pocket ProLink to your transmitter, is provided in Chapter 4. For more information, see the ProLink II or Pocket ProLink manual, available on the Micro Motion web site (<a href="http://www.micromotion.com" rel="nofollow noopener" target="_blank">www.micromotion.com</a>).
  • Basic information on using a customer-supplied DeviceNet tool is provided in Chapter 5. For more information, see the documentation provided with the tool.

1.7 Planning the configuration

Refer to the configuration overview flowchart in Figure 1-1 to plan transmitter configuration. In general, perform configuration steps in the order shown here.

Page 12 of the Emerson Process Management Micro Motion 2400S user manual — 1.8 Pre-configuration worksheet
Page 12 · click to enlarge
Page 12

Before You Begin

Figure 1-1 Configuration overview

Chapter 1 Before You Begin

Chapter 9 Pressure Compensation and Temperature Compensation Fill out pre-configuration

Chapter 8 Optional Configuration

Configure pressure compensation (optional)

Chapter 2 Flowmeter Startup

Configure temperature compensation (optional)

Chapter 10 Measurement Performance

Configure DeviceNet communications parameters

Zero the flowmeter (optional)

Chapter 6 Required Configuration

Configure status alarm severity

Configure petroleum measurement application or enhanced density application

1.8 Pre-configuration worksheet

The pre-configuration worksheet provides a place to record basic information about your flowmeter (transmitter and sensor) and your application. This information will affect your configuration options as you work through this manual. You may need to consult with transmitter installation or application process personnel to obtain the required information.

If you are configuring multiple transmitters, make copies of this worksheet and fill one out for each individual transmitter.

Show 19 more labels / short text on this page
worksheet · Configure volume flow · measurement for gas · Configure cutoffs · Start the flowmeter · Configure damping · Configure flow direction · (optional) · Configure events · Perform initial meter · verification tests · Characterize the flowmeter · Configure slug flow · (if required) · Configure measurement units · Configure display functionality · Configure digital communications · Configure device settings · Configure sensor parameters
Page 13 of the Emerson Process Management Micro Motion 2400S user manual — Table 1-2 Flowmeter documentation resources
Page 13 · click to enlarge
Page 13

Before You Begin

Pre-configuration worksheet Transmitter

Startup Using ProLink II Transmitter User Interface Before You Begin

Item Configuration data

Core processor (transmitter) software revision

Measurement units Mass flow

Installed applications Meter verification software Petroleum measurement application Enhanced density application

1.9 Flowmeter documentation

Table 1-2 lists documentation sources for additional information.

Table 1-2 Flowmeter documentation resources

Topic Document

DeviceNet device profile Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile shipped with the product or available on the Micro Motion web site (www.micromotion.com)

Sensor installation Sensor documentation

Transmitter installation Micro Motion® Model 2400S Transmitters: Installation Manual

Hazardous area installation See the approval documentation shipped with the transmitter, or download the appropriate documentation from the Micro Motion web site (www.micromotion.com)

Show 15 more labels / short text on this page
Transmitter model number · ______________________________________ · DeviceNet node address · ______________________________________ · DeviceNet baud rate · ______________________________________ · ______________________________________ · Volume flow · ______________________________________ · Density · ______________________________________ · Pressure · ______________________________________ · Temperature · ______________________________________
Page 14 of the Emerson Process Management Micro Motion 2400S user manual — Before You Begin
Page 14 · click to enlarge
Page 14

Before You Begin

1.10 Micro Motion customer service

For customer service, phone the support center nearest you:

  • In the U.S.A., phone 800-522-MASS (800-522-6277) (toll-free)
  • In Canada and Latin America, phone +1 303-527-5200
  • In Asia:

- In Japan, phone 3 5769-6803

- In other locations, phone +65 6777-8211 (Singapore)

  • In Europe:

- In the U.K., phone 0870 240 1978 (toll-free)

- In other locations, phone +31 (0) 318 495 555 (The Netherlands)

Customers outside the U.S.A. can also email Micro Motion customer service at International.MMISupport@EmersonProcess.com.

Page 15 of the Emerson Process Management Micro Motion 2400S user manual — WARNING
Page 15 · click to enlarge
Page 15

Chapter 2 Flowmeter Startup

Startup Using ProLink II Transmitter User Interface Before You Begin

2.1 Overview

This chapter describes the following procedures:

  • Setting the DeviceNet node address and baud rate – see Section 2.2
  • Bringing the transmitter online – see Section 2.3

2.2 Setting the DeviceNet node address and baud rate

The default node address for the Model 2400S DN transmitter is 63. The default baud rate is 125 kBaud.

If desired, you can use the hardware switches on the face of the device to change these two settings before bringing the transmitter online. See Sections 8.10.1 and 8.10.2 for more information.

2.3 Bringing the transmitter online

The DeviceNet cable used to connect the Model 2400S DN transmitter to the network provides both power and communications. The transmitter is prewired with a male sealed Micro Connector (Eurofast).

To bring the transmitter online:

1. Follow appropriate procedures to ensure that the process of configuring and commissioning the Model 2400S DN transmitter does not interfere with existing measurement and control loops.
2. Ensure that all transmitter and sensor covers and seals are closed.

WARNING

Operating the flowmeter without covers in place creates electrical hazards that can cause death, injury, or property damage.

To avoid electrical hazards, ensure that the transmitter housing cover and all other covers are in place before connecting the transmitter to the network.

Page 16 of the Emerson Process Management Micro Motion 2400S user manual — Flowmeter Startup
Page 16 · click to enlarge
Page 16

Flowmeter Startup

3. Insert an appropriate DeviceNet cable into the connector on the transmitter.

When the transmitter receives power, it will automatically perform diagnostic routines, and the module LED flashes red and green. When the flowmeter has completed its power-up sequence, the status LED will show a solid green. See Section 7.4 for information on LED behavior. If the status LED exhibits different behavior, an alarm condition is present. See Section 7.5.

4. Ensure that the transmitter is visible on the network. For information on establishing communications between the Model 2400S DN transmitter and a DeviceNet tool, see Chapter 5 .

Note: If this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, the flowmeter is ready to receive process fluid approximately one minute after power-up. However, it may take up to ten minutes for the electronics in the flowmeter to reach thermal equilibrium. During this warm-up period, you may observe minor measurement instability or inaccuracy.

Page 17 of the Emerson Process Management Micro Motion 2400S user manual — 3.2 User interface without or with display
Page 17 · click to enlarge
Page 17

Chapter 3 Using the Transmitter User Interface

Startup Using ProLink II Transmitter User Interface Before You Begin

3.1 Overview

This chapter describes the user interface of the Model 2400S DN transmitter. The following topics are discussed:

  • Transmitters without or with display – see Section 3.2
  • Removing and replacing the transmitter housing cover – see Section 3.3
  • Using the Scroll and Select optical switches – see Section 3.4
  • Using the display – see Section 3.5

3.2 User interface without or with display

The user interface of the Model 2400S DN transmitter depends on whether it was ordered with or without a display:

  • If ordered without a display, there is no LCD panel on the user interface. The user interface provides the following features and functions:
- Three LEDsa status LED, a module LED, and a network LED

- Digital communications hardware switches, used to set the DeviceNet node address and baud rate

- Service port clips

For all other functions, either ProLink II or a customer-supplied DeviceNet tool is required.

  • If ordered with a display, no zero button is provided (you must zero the transmitter with the display menu, ProLink II, or a DeviceNet tool) and the following features are added:

- An LCD panel, which displays process variable data and also provides access to the off-line menu for basic configuration and management. Optical switches are provided for LCD control.

- An IrDA port which provides wireless access to the service port

Figures 3-1 and 3-2 show the user interface of the Model 2400S DN transmitter without and with a display. In both illustrations, the transmitter housing cover has been removed.

- Zero button

Page 18 of the Emerson Process Management Micro Motion 2400S user manual — Figure 3-2 User interface – Transmitters with display
Page 18 · click to enlarge
Page 18

Using the Transmitter User Interface

Figure 3-1 User interface – Transmitters without display

Emerson Process Management Micro Motion 2400S — Using the Transmitter User Interface diagram (page 18)
Fig. 1 · Using the Transmitter User Interface

Figure 3-2 User interface – Transmitters with display

Emerson Process Management Micro Motion 2400S — Figure 3-2 User interface – Transmitters with display diagram (page 18)
Fig. 2 · Figure 3-2 User interface – Transmitters with displa…

If the transmitter does not have a display, the transmitter housing cover must be removed to access all user interface features and functions.

If the transmitter has a display, the transmitter housing cover has a lens. All of the features shown in Figure 3-2 are visible through the lens, and the following functions may be performed through the lens (i.e., with the transmitter housing cover in place):

  • Viewing the LEDs
  • Viewing the LCD panel
  • Using the Select and Scroll optical switches
  • Making a service port connection via the IrDA port

All other functions require removal of the transmitter housing cover.

Show 19 more labels / short text on this page
Digital communications · hardware switches · Zero button · Status LED · Module LED · Network LED · Service port clips · Digital communications · hardware switches · Status LED · Module LED · Unit of measure · Network LED · Optical switch indicator · Optical switch indicator · Scroll optical switch · Select optical switch · IrDA port · Service port clips
Page 19 of the Emerson Process Management Micro Motion 2400S user manual — CAUTION
Page 19 · click to enlarge
Page 19

Using the Transmitter User Interface

For information on:

  • Using the digital communications hardware switches, see Section 8.10.

Startup Using ProLink II Transmitter User Interface Before You Begin

  • Using the LEDs, see Section 7.4.
  • Making a service port connection, see Chapter 4.
  • Using the zero button, see Section 10.5.

3.3 Removing and replacing the transmitter housing cover

For some procedures, you must remove the transmitter housing cover. To remove the transmitter housing cover:

1. If the transmitter is in a Division 2 or Zone 2 area, disconnect the DeviceNet cable to remove power from the unit.

WARNING

Removing the transmitter housing cover in a Division 2 or Zone 2 area while the transmitter is powered up can cause an explosion.

To avoid the risk of an explosion, disconnect the DeviceNet cable to remove power from the transmitter before removing the transmitter housing cover.

2. Loosen the four captive screws.
3. Lift the transmitter housing cover away from the transmitter.

When replacing the transmitter housing cover, first grease the gasket, then replace the cover. Tighten the screws so that no moisture can enter the transmitter housing.

3.4 Using the optical switches

The Scroll and Select optical switches are used to navigate the display menus. To activate an optical switch, touch the lens in front of the optical switch or move your finger over the optical switch close to the lens. There are two optical switch indicators: one for each switch. When an optical switch is activated, the associated optical switch indicator is a solid red.

CAUTION

Attempting to activate an optical switch by inserting an object into the opening can damage the equipment.

To avoid damage to the optical switches, do not insert an object into the openings. Use your fingers to activate the optical switches.

Page 20 of the Emerson Process Management Micro Motion 2400S user manual — 3.5.2 Viewing process variables
Page 20 · click to enlarge
Page 20

Using the Transmitter User Interface

3.5 Using the display

The display can be used to view process variable data or to access the transmitter menus for configuration or maintenance.

3.5.1 Display language

The display can be configured for the following languages:

  • English
  • French
  • Spanish
  • German

Due to software and hardware restrictions, some English words and terms may appear in the non-English display menus. For a list of the codes and abbreviations used on the display, see Appendix D.

For information on configuring the display language, see Section 8.9.

In this manual, English is used as the display language.

3.5.2 Viewing process variables

In ordinary use, the Process variable line on the LCD panel shows the configured display variables, and the Units of measure line shows the measurement unit for that process variable.

  • See Section 8.9.5 for information on configuring the display variables.
  • See Appendix D for information on the codes and abbreviations used for display variables.

If more than one line is required to describe the display variable, the Units of measure line alternates between the measurement unit and the additional description. For example, if the LCD panel is displaying a mass inventory value, the Units of measure line alternates between the measurement unit (for example, G) and the name of the inventory (for example, MASSI).

Auto Scroll may or may not be enabled:

  • If Auto Scroll is enabled, each configured display variable will be shown for the number of seconds specified for Scroll Rate.
  • Whether Auto Scroll is enabled or not, the operator can manually scroll through the configured display variables by activating Scroll .

For more information on using the display to view process variables or manage totalizers and inventories, see Chapter 7.

Page 21 of the Emerson Process Management Micro Motion 2400S user manual — Figure 3-3 Entering the display menu system
Page 21 · click to enlarge
Page 21

Using the Transmitter User Interface

3.5.3 Using display menus

Startup Using ProLink II Transmitter User Interface Before You Begin

To enter the display menu system, see the flowchart shown in Figure 3-3.

Figure 3-3 Entering the display menu system

Emerson Process Management Micro Motion 2400S — Figure 3-3 Entering the display menu system diagram (page 21)
Fig. 3 · Figure 3-3 Entering the display menu system

The unlock sequence prevents unintentional entry to the offline menu. A prompt is shown for each step, and the user has 10 seconds to perform the action.

If no optical switch activity occurs for two minutes, the transmitter will exit the off-line menu system and return to the process variable display.

To move through a list of options, activate Scroll.

To select from a list or to enter a lower-level menu, Scroll to the desired option, then activate Select. If a confirmation screen is displayed:

  • To confirm the change, activate Select .
  • To cancel the change, activate Scroll .

To exit a menu without making any changes

  • Use the EXIT option if available.
  • Otherwise, activate Scroll at the confirmation screen.
Page 22 of the Emerson Process Management Micro Motion 2400S user manual — Figure 3-4 Numeric values in decimal notation
Page 22 · click to enlarge
Page 22

Using the Transmitter User Interface

3.5.4 Display password

Some of the display menu functions, such as accessing the off-line menu, can be protected by a display password. For information about enabling and setting the display password, refer to Section 8.9.

If a password is required, the word CODE? appears at the top of the password screen. Enter the digits of the password one at a time by using Scroll to choose a number and Select to move to the next digit.

If you encounter the display password screen but do not know the password, wait 60 seconds without activating any of the display optical switches. The password screen will time out automatically and you will be returned to the previous screen.

3.5.5 Entering floating-point values with the display

Certain configuration values, such as meter factors or output ranges, are entered as floating-point values. When you first enter the configuration screen, the value is displayed in decimal notation (as shown in Figure 3-4) and the active digit is flashing.

Figure 3-4 Numeric values in decimal notation

SX.XXXX

Sign For positive numbers, leave this space blank. For negative numbers, enter a minus sign (–).

Digits Enter a number (maximum length: eight digits, or seven digits and a minus sign). Maximum precision is four.

To change the value:

1. Select to move one digit to the left. From the leftmost digit, a space is provided for a sign. The sign space wraps back to the rightmost digit.
2. Scroll to change the value of the active digit: 1 becomes 2 , 2 becomes 3 , ..., 9 becomes 0 , 0 becomes 1 . For the rightmost digit, an E option is included to switch to exponential notation.

To change the sign of a value:

1. Select to move to the space that is immediately left of the leftmost digit.
2. Use Scroll to specify – (for a negative value) or [blank] (for a positive value).

In decimal notation, you can change the position of the decimal point up to a maximum precision of four (four digits to the right of the decimal point). To do this:

1. Select until the decimal point is flashing.
2. Scroll. This removes the decimal point and moves the cursor one digit to the left.
3. Select to move one digit to the left. As you move from one digit to the next, a decimal point will flash between each digit pair.
4. When the decimal point is in the desired position, Scroll. This inserts the decimal point and moves the cursor one digit to the left.
Page 23 of the Emerson Process Management Micro Motion 2400S user manual — Figure 3-5 Numeric values in exponential notation
Page 23 · click to enlarge
Page 23

Using the Transmitter User Interface

To change from decimal to exponential notation (see Figure 3-5):

1. Select until the rightmost digit is flashing.

Startup Using ProLink II Transmitter User Interface Before You Begin

2. Scroll to E , then Select . The display changes to provide two spaces for entering the exponent.
3. To enter the exponent:

a. Select until the desired digit is flashing.

b. Scroll to the desired value. You can enter a minus sign (first position only), values between 0 and 3 (for the first position in the exponent), or values between 0 and 9 (for the second position in the exponent).

c. Select.

Figure 3-5 Numeric values in exponential notation

SX.XXXEYY

Digits Enter a four-digit number; three digits must fall to the right of the decimal point. E

Sign or Digit (0–3)

To change from exponential to decimal notation:

1. Select until the E is flashing.
2. Scroll to d .
3. Select . The display changes to remove the exponent.

To exit the menu:

  • If the value has been changed, Select and Scroll simultaneously until the confirmation screen is displayed.

- Select to apply the change and exit.

- Scroll to exit without applying the change.

  • If the value has not been changed, Select and Scroll simultaneously until the previous screen is displayed.

Sign · Digit (0–9) · Exponent indicator

Page 24 of the Emerson Process Management Micro Motion 2400S user manual — 3.5.4 Display password
Page 24 · click to enlarge
Page 24
Page 24 of the Emerson Process Management Micro Motion 2400S user manual — 3.5.4 Display password
Page 25 of the Emerson Process Management Micro Motion 2400S user manual — 4.3 Configuration upload/download
Page 25 · click to enlarge
Page 25

Chapter 4 Connecting with ProLink II or Pocket ProLink Software

Startup Using ProLink II Transmitter User Interface Before You Begin

4.1 Overview

ProLink II is a Windows-based configuration and management tool for Micro Motion transmitters. It provides access to most transmitter functions and data. Pocket ProLink is a version of ProLink II that runs on a Pocket PC.

This chapter provides basic information for connecting ProLink II or Pocket ProLink to your transmitter. The following topics and procedures are discussed:

  • Requirements – see Section 4.2
  • Configuration upload/download – see Section 4.3
  • Connecting to a Model 2400S DN transmitter – see Section 4.4

The instructions in this manual assume that users are already familiar with ProLink II or Pocket ProLink software. For more information on using ProLink II, see the ProLink II manual. For more information on using Pocket ProLink, see the Pocket ProLink manual. Instructions in this manual will refer only to ProLink II.

4.2 Requirements

To use ProLink II with the Model 2400S DN transmitter, ProLink II v2.5 or later is required. In addition, you must have either the ProLink II installation kit appropriate to your PC and connection type, or the equivalent equipment. See the ProLink II manual or quick reference guide for details.

To use Pocket ProLink, v1.3 or later is required. In addition:

  • If you will connect to the transmitter via the service port clips, you must have either the Pocket ProLink installation kit or the equivalent equipment. See the Pocket ProLink manual or quick reference guide for details.
  • If you will connect via the IrDA port, no additional equipment is required.

4.3 Configuration upload/download

ProLink II and Pocket ProLink provide a configuration upload/download function which allows you to save configuration sets to a file on the PC or Pocket PC. This allows:

  • Easy backup and restore of transmitter configuration
  • Easy replication of configuration sets

Micro Motion recommends that all transmitter configurations be saved to a file as soon as the configuration is complete. See the ProLink II or Pocket ProLink manual for details.

Page 26 of the Emerson Process Management Micro Motion 2400S user manual — 4.4.3 Connecting via the service port clips
Page 26 · click to enlarge
Page 26

Connecting with ProLink II or Pocket ProLink Software

4.4 Connecting to a Model 2400S DN transmitter

To connect to the Model 2400S DN transmitter using ProLink II or Pocket ProLink, you must use a service port connection.

4.4.1 Connection options

The service port can be accessed via the service port clips or the IrDA port.

The service port clips have priority over the IrDA port:

  • If there is an active connection via the service port clips, access via the IrDA port is disabled.
  • If there is an active connection via the IrDA port and a connection attempt is made via the service port clips, the IrDA connection is terminated.

Additionally, access via the IrDA port may be disabled altogether. In this case, it is not available for connections at any time. By default, access via the IrDA port is disabled. See Section 8.10.6 for more information.

4.4.2 Service port connection parameters

The service port uses default connection parameters. Both ProLink II and Pocket ProLink automatically use these default parameters when Protocol is set to Service Port.

Additionally, to minimize configuration requirements, the service port employs an auto-detection scheme when responding to connection requests. The service port will accept all connection requests within the limits described in Table 4-1. If you are connecting to the service port from another tool, ensure that configuration parameters are set within these limits.

Table 4-1 Service port auto-detection limits

Parameter Option

Protocol Modbus ASCII or Modbus RTU(1)

Address Responds to both:

  • Service port address (111)
  • Configured Modbus address (default=1) (2)

Standard rates between 1200 and 38,400

Stop bits 1, 2

Parity Even, odd, none

(1) Service port support for Modbus ASCII may be disabled. See Section 8.10.5.

(2) See Section 8.10.4 for information on configuring the Modbus address.

(3) This is the baud rate between the service port and the connecting program. It is not the DeviceNet baud rate.

4.4.3 Connecting via the service port clips

To connect to the service port via the service port clips:

1. Attach the signal converter to the serial or USB port of your PC, using the appropriate connectors or adapters (e.g., a 25-pin to 9-pin adapter or a USB connector).
2. Remove the transmitter housing cover from the transmitter (see Section 3.3), then connect the signal converter leads to the service port clips. See Figure 4-1.

Baud rate(3)

Page 27 of the Emerson Process Management Micro Motion 2400S user manual — Figure 4-1 Serial port connections to service port clips
Page 27 · click to enlarge
Page 27

Connecting with ProLink II or Pocket ProLink Software

Emerson Process Management Micro Motion 2400S — Connecting with ProLink II or Pocket ProLink Software diagram (page 27)
Fig. 4 · Connecting with ProLink II or Pocket ProLink Softwar…

Startup Using ProLink II Transmitter User Interface Before You Begin Startup Using ProLink II Transmitter User Interface Before You Begin Startup Using ProLink II Transmitter User Interface Before You Begin Startup Using ProLink II Transmitter User Interface Before You Begin

Removing the transmitter housing cover in a hazardous area can cause an explosion.

Because the transmitter housing cover must be removed to connect to the service port clips, the service port clips should be used only for temporary connections, e.g., for configuration or troubleshooting purposes.

When the transmitter is in an explosive atmosphere, use a different method to connect to your transmitter.

Figure 4-1 Serial port connections to service port clips

Emerson Process Management Micro Motion 2400S — Figure 4-1 Serial port connections to service port clips diagram (page 27)
Fig. 5 · Figure 4-1 Serial port connections to service port c…
3. Start ProLink II or Pocket ProLink. In the Connection menu, click Connect to Device . In the screen that appears, specify:
  • Protocol : Service Port
  • COM Port : as appropriate

No other parameters are required.

4. Click Connect . The software will attempt to make the connection.
5. If an error message appears:

a. Swap the leads between the two service port clips and try again.

b. Ensure that you are using the correct COM port.

c. Check all the wiring between the PC and the transmitter.

d. Verify the RS-485 to RS-232 signal converter.

Page 28 of the Emerson Process Management Micro Motion 2400S user manual — 4.5 ProLink II language
Page 28 · click to enlarge
Page 28

Connecting with ProLink II or Pocket ProLink Software

4.4.4 Connecting via the IrDA port

To connect to the service port via the IrDA port:

1. Ensure that the IrDA port is enabled (see Section 8.10.6). By default, the IrDA port is disabled.
2. Ensure that there is no connection via the service port clips.
3. Position the IrDA device for communication with the IrDA port (see Figure 3-2). You do not need to remove the transmitter housing cover.
4. Start Pocket ProLink software. In the Connection menu, click Connect to Device . In the screen that appears, specify:
  • Protocol: Service Port
  • IrDA Port

No other parameters are required.

5. Click Connect . The software will attempt to make the connection.
6. If an error message appears:

a. Ensure that you are using the correct port.

b. Ensure that the IrDA port is enabled.

4.5 ProLink II language

ProLink II can be configured for the following languages:

  • English
  • French
  • German

To configure the ProLink II language, use the Tools menu. See Figure B-1.

In this manual, English is used as the ProLink II language.

Page 29 of the Emerson Process Management Micro Motion 2400S user manual — 5.3 Using the DeviceNet device profile
Page 29 · click to enlarge
Page 29

Chapter 5 Using a DeviceNet Tool

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

5.1 Overview

A customer-supplied DeviceNet tool can be used to communicate with the Model 2400S DN transmitter. This chapter provides basic information on using a customer-supplied DeviceNet tool.

However, because there are a variety of DeviceNet tools available, this chapter does not provide detailed information for using any one tool. For detailed information on your DeviceNet tool, see the documentation supplied with the tool.

5.2 Connecting to the Model 2400S DN transmitter

To connect to the Model 2400S DN transmitter:

1. Default connection values for this transmitter are as follows:
  • DeviceNet node address = 63
  • Baud rate = 125 kBaud

If required, use the digital communications hardware switches on the device to set the DeviceNet node address and baud rate for this transmitter. To do this, see Sections 8.10.1 and 8.10.2.

2. Connect to the network where the transmitter is installed.
3. Using the same methods that you use for other DeviceNet devices, establish a connection to the Model 2400S DN transmitter, using the appropriate node address and baud rate.

5.3 Using the DeviceNet device profile

All DeviceNet devices employ a device profile with an object-instance-attribute structure.

In general, process and configuration data is stored in attributes, and operational functions are performed by using services or setting attributes to specific values.

Two standard services are used to read or write single attributes:

  • The Get Single Attribute service (0x0E) performs an explicit read and returns a single value from the transmitter.
  • The Set Single Attribute service (0x10) performs an explicit write and writes a single value to the transmitter.

In this manual, these two services are referenced as the Get and Set services.

Other services are used to reset values to 0, start or stop calibrations, to acknowledge alarms, etc. These services are identified by name and by service code (a hexadecimal label).

Input assemblies are used to publish multiple values to the DeviceNet bus. A summary of the input assemblies is provided in Table 7-2. Output assemblies can be used to read data from the DeviceNet bus or to perform totalizer and inventory control. Summaries of the output assemblies are provided in Tables 7-9 and 9-1.

Page 30 of the Emerson Process Management Micro Motion 2400S user manual — 5.4.2 Type B tools
Page 30 · click to enlarge
Page 30

Using a DeviceNet Tool

For complete documentation of the Model 2400S DN transmitter’s device profile, including input and output assemblies, see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile.

5.4 Using a DeviceNet tool

Micro Motion supplies an Electronic Data Sheet (EDS) for the Model 2400S transmitter. The EDS file is named MMI2400S-MassFlow.eds. The EDS presents the device profile in a format designed to be read and interpreted by other devices.

DeviceNet tools fall into two basic categories:

  • Type A: Tools that use the EDS to build a unique user interface for the specific device
  • Type B: Tools that do not use the EDS, and instead rely on the user to supply the object-instance-attribute information required to interact with the device

5.4.1 Type A tools

If you are using a Type A tool:

1. Use your tool’s standard methods to read or import the supplied EDS into the network configuration tool (e.g., RSLinx).
2. Use your tool’s standard user interface to configure, view, and manage the transmitter.
3. If you want to perform a function that isn’t available through your tool, see the instructions for Type B tools.

5.4.2 Type B tools

If you are using a Type B tool, or if you want to access features that are not available through your tool’s user interface, you must reference the feature by class, instance, and attribute, use the appropriate service, and supply an attribute value if required. Depending on the attribute, the value may be a numeric or character value or a code. Values must be entered in the data type appropriate to the attribute.

For example:

  • To configure the mass flow cutoff, you must:

a. Specify the Analog Input Point class.

b. Specify the Mass Flow instance.

c. Specify the cutoff attribute.

d. Use the Set service to set the attribute value to the desired cutoff.

  • To read the mass flow process variable, you can use either of the following methods:

- Use the Get service to read the value of the corresponding attribute.

- Use one of the input assemblies that contains the mass flow process variable.

This manual provides class, instance, attribute, data type, and service information for most configuration parameters and for all procedures. Complete documentation of the Model 2400S DN transmitter’s device profile is provided in the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile.

Page 31 of the Emerson Process Management Micro Motion 2400S user manual — 21 BOOL REAL REAL REAL REAL REAL
Page 31 · click to enlarge
Page 31

Using a DeviceNet Tool

5.5 Default assemblies

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

The default assemblies used by the Model 2400S DN transmitter are listed and described in Table 5-1. To change the default assemblies, see the flowchart in Figure 5-1.

Table 5-1 Default DeviceNet assemblies

Connection type Assembly type Instance ID Description Size (bytes) Data type

Polled Input 6 Status Mass flow Mass total Mass inventory Temperature Density

21 BOOL REAL

Output 54 Reset all totalizer values

1 BOOL

Cyclic Input 6 Status Mass flow Mass total Mass inventory Temperature Density

21 BOOL REAL

Figure 5-1 Changing the default DeviceNet assemblies

Class: Connection Object (0x95) Instance: 1 Attribute ID: 100 Data type: UINT Value: See Table 7-2 Service: Set

Polled connection:

Class: Connection Object (0x95) Instance: 1 Attribute ID: 101 Data type: UINT Value: See Tables 7-8 and 9-1 Service: Set

Polled connection:

Class: Connection Object (0x95) Instance: 1 Attribute ID: 102 Data type: UINT Value: See Table 7-2 Service: Set

Cyclic connection:

Input assembly · Output assembly · Input assembly

Page 32 of the Emerson Process Management Micro Motion 2400S user manual — 5.5 Default assemblies
Page 32 · click to enlarge
Page 32
Page 32 of the Emerson Process Management Micro Motion 2400S user manual — 5.5 Default assemblies
Page 33 of the Emerson Process Management Micro Motion 2400S user manual — 6.2.2 Characterization parameters
Page 33 · click to enlarge
Page 33

Chapter 6 Required Transmitter Configuration

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

6.1 Overview

This chapter describes the configuration procedures that are usually required when a transmitter is installed for the first time.

The following procedures are discussed:

  • Characterizing the flowmeter – see Section 6.2
  • Configuring measurement units – see Section 6.3

This chapter provides basic flowcharts for each procedure. For more detailed flowcharts, see the flowcharts for your communication tool, provided in the appendices to this manual.

For optional transmitter configuration parameters and procedures, see Chapter 8.

6.2 Characterizing the flowmeter

Characterizing the flowmeter adjusts the transmitter to compensate for the unique traits of the sensor it is paired with. The characterization parameters, or calibration factors, describe the sensor’s sensitivity to flow, density, and temperature.

6.2.1 When to characterize

If the transmitter and sensor were ordered together, then the flowmeter has already been characterized. You need to characterize the flowmeter only if the transmitter and sensor are being paired together for the first time.

6.2.2 Characterization parameters

The characterization parameters that must be configured depend on your flowmeter’s sensor type: “T-Series” or “Other” (also referred to as “Straight Tube” and “Curved Tube,” respectively), as listed in Table 6-1. The “Other” category includes all Micro Motion sensors except T-Series.

The characterization parameters are provided on the sensor tag. See Figure 6-1 for illustrations of sensor tags.

Page 34 of the Emerson Process Management Micro Motion 2400S user manual — Flow calibration values
Page 34 · click to enlarge
Page 34

Required Transmitter Configuration

Table 6-1 Sensor calibration parameters

Sensor type

Parameter

T-Series Other

K1 ✓ ✓

K2 ✓ ✓

FD ✓ ✓

D1 ✓ ✓

D2 ✓ ✓

Temp coeff (DT)(1)

FCF ✓

FTG ✓

FFQ ✓

DTG ✓

DFQ1 ✓

DFQ2 ✓

(1) On some sensor tags, shown as TC.

(2) See the section entitled “Flow calibration values.”

Figure 6-1 Sample calibration tags

Emerson Process Management Micro Motion 2400S — Figure 6-1 Sample calibration tags diagram (page 34)
Fig. 6 · Figure 6-1 Sample calibration tags
Emerson Process Management Micro Motion 2400S — Figure 6-1 Sample calibration tags diagram (page 34)
Fig. 7 · Figure 6-1 Sample calibration tags

Flow calibration values

Two factors are used to define flow calibration:

  • The flow calibration factor, which is a 6-character string (five numbers and a decimal point)
  • The temperature coefficient for flow, which is a 4-character string (three numbers and a decimal point)

These values are concatenated on the sensor tag, but different labels are used for different sensors. As shown in Figure 6-1:

  • For T-Series sensors, the value is called the FCF value.
  • For other sensors, the value is called the Flow Cal value.
Show 4 more labels / short text on this page
✓ ✓ · Flowcal ✓(2) · T-Series · Other sensors
Page 35 of the Emerson Process Management Micro Motion 2400S user manual — Figure 6-2 Characterizing the flowmeter
Page 35 · click to enlarge
Page 35

Required Transmitter Configuration

When configuring the flow calibration factor:

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

  • With ProLink II, enter the concatenated 10-character string exactly as shown, including the decimal points. For example, using the Flow Cal value from Figure 6-1, enter 19.0005.13 .
  • With a DeviceNet tool, enter the two factors separately, i.e., enter a 6-character string and a 4-character string. Include the decimal point in both strings. For example, using the Flow Cal value from Figure 6-1:

- Enter 19.000 for the flow calibration factor.

- Enter 5.13 for the temperature coefficient for flow.

6.2.3 How to characterize

To characterize the flowmeter:

1. See the menu flowcharts in Figure 6-2.
2. Ensure that the correct sensor type is configured.
3. Set required parameters, as listed in Table 6-1.

Figure 6-2 Characterizing the flowmeter

DeviceNet tool ProLink II

Class: Sensor Information Object (0x67) Instance: 1 Attribute ID: 3 Data type: USINT Value: · 0: Curved tube · 1: Straight tube Service: Set

Device · Sensor type

Class: Calibration Object (0x65) Instance: 1 Attribute ID 1: Flow calibration factor Attribute ID 2: Temperature coefficient for flow Data type: REAL Service: Set

Class: Calibration Object (0x65) Instance: 1 Attribute ID 7: K1 Attribute ID 8: K2 Attribute ID 9: FD Attribute ID 12: D1 Attribute ID 13: D2 Attribute ID 17: DT Attribute ID 18: FTG Attribute ID 19: FFQ Attribute ID 20: DTG Attribute ID 21: DFQ1 Attribute ID 22: DFQ2 Data type: REAL Service: Set

Show 13 more labels / short text on this page
ProLink > Configuration · Sensor type · Straight · tube Sensor type? · Curved · tube · Flow · Flow · Flow values · Density · Density · T Series Config · Density values
Page 36 of the Emerson Process Management Micro Motion 2400S user manual — Required Transmitter Configuration
Page 36 · click to enlarge
Page 36

Required Transmitter Configuration

6.3 Configuring the measurement units

For each process variable, the transmitter must be configured to use the measurement unit appropriate to your application.

To configure measurement units for process variables, see the menu flowcharts in Figure 6-3. For details on measurement units for each process variable, see Sections 6.3.1 through 6.3.4.

The measurement units used for totalizers and inventories are assigned automatically, based on the measurement unit configured for the corresponding process variable. For example, if kg/hr (kilograms per hour) is configured for mass flow, the unit used for the mass flow totalizer and mass flow inventory is kg (kilograms). DeviceNet codes used for the measurement units are listed in Tables C-12 through C-14.

Page 37 of the Emerson Process Management Micro Motion 2400S user manual — Required Transmitter Configuration
Page 37 · click to enlarge
Page 37

Required Transmitter Configuration

Figure 6-3 Configuring measurement units

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Off-line maint > Off-line config

Class: Analog Input Point Object (0x0A) Instance: 1 Attribute ID: 102 Value: See Table 6-2 Service: Set

Class: Analog Input Point Object (0x0A) Instance: 2 Attribute ID: 102 Value: See Table 6-3 Service: Set

Class: Analog Input Point Object (0x0A) Instance: 3 Attribute ID: 102 Value: See Table 6-5 Service: Set

Class: Analog Input Point Object (0x0A) Instance: 4 Attribute ID: 102 Value: See Table 6-6 Service: Set

ClassCalibration Object (0x65) Instance: 1 Attribute ID: 29 Value: See Table 6-7 Service: Set
Show 19 more labels / short text on this page
Display ProLink II · ProLink > Configuration · Flow · Units · Density · Mass · Temperature · Vol (or GSV) · Pressure · Density · Temperature · DeviceNet tool · Pressure · Mass flow unit · Volume flow unit · (liquid) · Density unit · Temperature unit · Pressure unit
Page 38 of the Emerson Process Management Micro Motion 2400S user manual — Table 6-3 Volume flow measurement units – Liquid
Page 38 · click to enlarge
Page 38

Required Transmitter Configuration

6.3.1 Mass flow units

The default mass flow measurement unit is g/s. See Table 6-2 for a complete list of mass flow measurement units.

Table 6-2 Mass flow measurement units

Mass flow unit

Unit description Display ProLink II DeviceNet tool DeviceNet code

G/S g/s g/s 0x0800 Grams per second

G/MIN g/min g/min 0x140F Grams per minute

G/H g/hr g/hr 0x0801 Grams per hour

KG/S kg/s kg/s 0x0802 Kilograms per second

KG/MIN kg/min kg/min 0x0803 Kilograms per minute

KG/H kg/hr kg/hr 0x1410 Kilograms per hour

KG/D kg/day kg/day 0x0804 Kilograms per day

T/MIN mTon/min MetTon/min 0x0805 Metric tons per minute

T/H mTon/hr MetTon/hr 0x0806 Metric tons per hour

T/D mTon/day MetTon/day 0x0807 Metric tons per day

LB/S lbs/s lb/s 0x140B Pounds per second

LB/MIN lbs/min lb/min 0x140C Pounds per minute

LB/H lbs/hr lb/hr 0x140D Pounds per hour

LB/D lbs/day lb/day 0x0808 Pounds per day

ST/MIN sTon/min ShTon/min 0x0809 Short tons (2000 pounds) per minute

ST/H sTon/hr ShTon/hr 0x080A Short tons (2000 pounds) per hour

ST/D sTon/day ShTon/dayr 0x080B Short tons (2000 pounds) per day

LT/H lTon/hr LTon/h 0x080C Long tons (2240 pounds) per hour

LT/D lTon/day LTon/day 0x080D Long tons (2240 pounds) per day

6.3.2 Volume flow units

The default volume flow measurement unit is l/s (liters per second).

Two different sets of volume flow measurement units are provided:

  • Units typically used for liquid volume – see Table 6-3
  • Units typically used for gas standard volume – see Table 6-4

By default, only liquid volume flow units are listed. To access the gas standard volume flow units, you must first configure Volume Flow Type, and additional configuration is required. See Section 8.2 for more information.

Table 6-3 Volume flow measurement units – Liquid

Volume flow unit

Display ProLink II DeviceNet tool DeviceNet code Unit description

CUFT/S ft3/sec ft3/s 0x0814 Cubic feet per second

CUF/MN ft3/min ft3/min 0x1402 Cubic feet per minute

CUFT/H ft3/hr ft3/hr 0x0815 Cubic feet per hour

Page 39 of the Emerson Process Management Micro Motion 2400S user manual — Table 6-4 Volume flow measurement units – Gas
Page 39 · click to enlarge
Page 39

Required Transmitter Configuration

Table 6-3 Volume flow measurement units – Liquid continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Volume flow unit

Display ProLink II DeviceNet tool DeviceNet code Unit description

CUFT/D ft3/day ft3/day 0x0816 Cubic feet per day

M3/S m3/sec m3/s 0x1405 Cubic meters per second

M3/MIN m3/min m3/min 0x080F Cubic meters per minute

M3/H m3/hr m3/hr 0x0810 Cubic meters per hour

M3/D m3/day m3/day 0x0811 Cubic meters per day

USGPS US gal/sec gal/s 0x1408 U.S. gallons per second

USGPM US gal/min gal/min 0x1409 U.S. gallons per minute

USGPH US gal/hr gal/hr 0x140A U.S. gallons per hour

USGPD US gal/d gal/day 0x0817 U.S. gallons per day

MILG/D mil US gal/day MillionGal/dday 0x0820 Million U.S. gallons per day

L/S l/sec l/s 0x1406 Liters per second

L/MIN l/min l/min 0x0812 Liters per minute

L/H l/hr l/hr 0x0813 Liters per hour

MILL/D mil l/day MillionL/day 0x0821 Million liters per day

UKGPS Imp gal/sec ImpGal/s 0x0818 Imperial gallons per second

UKGPM Imp gal/min ImpGal/min 0x0819 Imperial gallons per minute

UKGPH Imp gal/hr ImpGal/hr 0x081A Imperial gallons per hour

UKGPD Imp gal/day ImpGal/day 0x081B Imperial gallons per day

BBL/S barrels/sec bbl/s 0x081C Barrels per second(1)

BBL/MN barrels/min bbl/min 0x081D Barrels per minute(1)

BBL/H barrels/hr bbl/hr 0x081E Barrels per hour(1)

BBL/D barrels/day bbl/day 0x081F Barrels per day(1)

BBBL/S Beer barrels/sec Beer bbl/s 0x0853 Beer barrels per second(2)

Beer bbl/min 0x0854 Beer barrels per minute(2)

BBBL/H Beer barrels/hr Beer bbl/hr 0x0855 Beer barrels per hour(2)

Beer bbl/day 0x0856 Beer barrels per day(2)

(1) Unit based on oil barrels (42 U.S. gallons). (2) Unit based on beer barrels (31 U.S. gallons).

Table 6-4 Volume flow measurement units – Gas

Volume flow unit

Display ProLink II DeviceNet tool DeviceNet code Unit description

NM3/S Nm3/sec Nml m3/s 0x0835 Normal cubic meters per second

NM3/MN Nm3/min Nml m3/min 0x0836 Normal cubic meters per minute

NM3/H Nm3/hr Nml m3/hr 0x0837 Normal cubic meters per hour

NM3/D Nm3/day Nml m3/day 0x0838 Normal cubic meters per day

NLPS NLPS Nml l/s 0x083D Normal liter per second

BBBL/MN Beer barrels/min · BBBL/D Beer barrels/day

Page 40 of the Emerson Process Management Micro Motion 2400S user manual — Table 6-5 Density measurement units
Page 40 · click to enlarge
Page 40

Required Transmitter Configuration

Table 6-4 Volume flow measurement units – Gas continued

Volume flow unit

Display ProLink II DeviceNet tool DeviceNet code Unit description

NLPM NLPM Nml l/min 0x1401 Normal liter per minute

NLPH NLPH Nml l/hr 0x083E Normal liter per hour

NLPD NLPD Nml l/day 0x083F Normal liter per day

SCFS SCFS Std ft3/s 0x0831 Standard cubic feet per second

SCFM SCFM Std ft3/min 0x0832 Standard cubic feet per minute

SCFH SCFH Std ft3/hr 0x0833 Standard cubic feet per hour

SCFD SCFD Std ft3/day 0x0834 Standard cubic feet per day

SM3/S Sm3/S Std m3/s 0x0839 Standard cubic meters per second

SM3/MN Sm3/min Std m3/min 0x083A Standard cubic meters per minute

SM3/H Sm3/hr Std m3/hr 0x083B Standard cubic meters per hour

SM3/D Sm3/day Std m3/day 0x083C Standard cubic meters per day

SLPS SLPS Std l/s 0x0840 Standard liter per second

SLPM SLPM Std l/min 0x0841 Standard liter per minute

SLPH SLPH Std l/hr 0x0842 Standard liter per hour

SLPD SLPD Std l/day 0x0843 Standard liter per day

6.3.3 Density units

The default density measurement unit is g/cm3. See Table 6-2 for a complete list of density measurement units.

Table 6-5 Density measurement units

Density unit

Unit description Display ProLink II DeviceNet tool DeviceNet code

SGU SGU SGU 0x0823 Specific gravity unit (not temperature corrected)

G/CM3 g/cm3 g/cm3 0x2F08 Grams per cubic centimeter

G/L g/l g/l 0x0828 Grams per liter

G/ML g/ml g/ml 0x0826 Grams per milliliter

KG/L kg/l kg/l 0x0827 Kilograms per liter

KG/M3 kg/m3 kg/m3 0x2F07 Kilograms per cubic meter

LB/GAL lbs/Usgal lb/gal 0x0824 Pounds per U.S. gallon

LB/CUF lbs/ft3 lb/ft3 0x0825 Pounds per cubic foot

LB/CUI lbs/in3 lb/in3 0x0829 Pounds per cubic inch

ST/CUY sT/yd3 ShTon/yd3 0x082A Short ton per cubic yard

D API degAPI degAPI 0x082B Degrees API

Page 41 of the Emerson Process Management Micro Motion 2400S user manual — Table 6-7 Pressure measurement units
Page 41 · click to enlarge
Page 41

Required Transmitter Configuration

6.3.4 Temperature units

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

The default temperature measurement unit is °C. See Table 6-6 for a complete list of temperature measurement units.

Table 6-6 Temperature measurement units

Temperature unit

Unit description Display ProLink II DeviceNet tool DeviceNet code

°C °C degC 0x1200 Degrees Celsius °F °F degF 0x1201 Degrees Fahrenheit °R °R degR 0x1202 Degrees Rankine °K °K Kelvin 0x1203 Kelvin

6.3.5 Pressure units

The flowmeter does not measure pressure. You need to configure the pressure units if either of the following is true:

  • You will configure pressure compensation (see Section 9.2). In this case, configure the pressure unit to match the pressure unit used by the external pressure device.
  • You will use the Gas Wizard, you will enter a reference pressure value, and you need to change the pressure unit to match the reference pressure value (see Section 8.2).

If you do not know whether or not you will use pressure compensation or the Gas Wizard, you do not need to configure a pressure unit at this time. You can always configure the pressure unit later.

The default pressure measurement unit is PSI. See Table 6-7 for a complete list of pressure measurement units.

Table 6-7 Pressure measurement units

Pressure unit

Unit description Display ProLink II DeviceNet tool DeviceNet code

FTH2O Ft Water @ 68°F FtH2O(68F) 0x082D Feet water @ 68 °F

INW4C In Water @ 4°C InH2O(4C) 0x0858 Inches water @ 4 °C

INW60 In Water @ 60°F InH2O(60F) 0x0859 Inches water @ 60 °F

INH2O In Water @ 68°F InH2O(68F) 0x082C Inches water @ 68 °F

mmW4C mm Water @ 4°C mmH2O(4C) 0x085A Millimeters water @ 4 °C

mmH2O mm Water @ 68°F mmH2O(68F) 0x082E Millimeters water @ 68 °F

mmHG mm Mercury @ 0°C mmHg(0C) 0x1303 Millimeters mercury @ 0 °C

INHG In Mercury @ 0°C InHg(0C) 0x1304 Inches mercury @ 0 °C

PSI PSI psi 0x1300 Pounds per square inch

BAR bar bar 0x1307 Bar

mBAR millibar mbar 0x1308 Millibar

G/SCM g/cm2 g/cm2 0x082F Grams per square centimeter

KG/SCM kg/cm2 kg/cm2 0x0830 Kilograms per square centimeter

PA pascals PA 0x1309 Pascals

KPA Kilopascals kPA 0x130A Kilopascals

Page 42 of the Emerson Process Management Micro Motion 2400S user manual — Pressure unit
Page 42 · click to enlarge
Page 42

Required Transmitter Configuration

Table 6-7 Pressure measurement units continued

Pressure unit

Unit description Display ProLink II DeviceNet tool DeviceNet code

MPA megapascals MPA 0x085B Megapascals

TORR Torr @ 0C torr 0x1301 Torr @ 0 °C

ATM atms ATM 0x130B Atmospheres

Page 43 of the Emerson Process Management Micro Motion 2400S user manual — 7.2 Recording process variables
Page 43 · click to enlarge
Page 43

Chapter 7 Using the Transmitter

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

7.1 Overview

This chapter describes how to use the transmitter in everyday operation. The following topics and procedures are discussed:

  • Recording process variables – see Section 7.2
  • Viewing process variables – see Section 7.3
  • Viewing transmitter status and alarms – see Section 7.5
  • Handling status alarms – see Section 7.6
  • Viewing and controlling the totalizers and inventories – see Section 7.7

7.2 Recording process variables

Micro Motion suggests that you make a record of the process variables listed below, under normal operating conditions. This will help you recognize when the process variables are unusually high or low, and may help in fine-tuning transmitter configuration.

Record the following process variables:

  • Flow rate
  • Density
  • Temperature
  • Tube frequency
  • Pickoff voltage
  • Drive gain

To view these values, see Section 7.3. For information on using this information in troubleshooting, see Section 11.13.

Page 44 of the Emerson Process Management Micro Motion 2400S user manual — 7.3.2 With ProLink II
Page 44 · click to enlarge
Page 44

Using the Transmitter

7.3 Viewing process variables

Process variables include measurements such as mass flow rate, volume flow rate, mass total, volume total, temperature, and density.

You can view process variables with the display (if your transmitter has a display), ProLink II, or a DeviceNet tool.

7.3.1 With the display

By default, the display shows the mass flow rate, mass total, volume flow rate, volume total, temperature, density, and drive gain. If desired, you can configure the display to show other process variables. See Section 8.9.5.

The LCD panel reports the abbreviated name of the process variable (e.g., DENS for density), the current value of that process variable, and the associated unit of measure (e.g., G/CM3). See Appendix D for information on the codes and abbreviations used for display variables.

To view a process variable with the display:

  • If Auto Scroll is enabled, wait until the desired process variable appears on the LCD panel.
  • If Auto Scroll is not enabled, Scroll until the name of the desired process variable either:

- Appears on the process variable line, or

- Begins to alternate with the units of measure

See Figure 3-2.

The display precision can be configured separately for each process variable (see Section 8.9.5). This affects only the value shown on the display, and does not affect the actual value as reported by the transmitter via digital communications.

Process variable values are displayed using either standard decimal notation or exponential notation:

  • Values smaller than 100,000,000 are displayed in decimal notation (e.g., 1234567.89 ).
  • Values greater than 100,000,000 are displayed using exponential notation (e.g., 1.000E08 ).

- If the value is less than the precision configured for that process variable, the value is displayed as 0 (i.e., there is no exponential notation for fractional numbers).

- If the value is too large to be displayed with the configured precision, the displayed precision is reduced (i.e., the decimal point is shifted to the right) as required so that the value can be displayed.

7.3.2 With ProLink II

The Process Variables window opens automatically when you first connect to the transmitter. This window displays current values for the standard process variables (mass, volume, density, temperature, external pressure, and external temperature).

To view the standard process variables with ProLink II, if you have closed the Process Variables window, click ProLink > Process Variables.

To view API process variables (if the petroleum measurement application is enabled), click ProLink > API Process Variables.

Page 45 of the Emerson Process Management Micro Motion 2400S user manual — Table 7-1 Process data in DeviceNet objects
Page 45 · click to enlarge
Page 45

Using the Transmitter

To view enhanced density process variables (if the enhanced density application is enabled), click ProLink > ED Process Variables. Different enhanced density process variables are displayed, depending on the configuration of the enhanced density application.

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

7.3.3 With a DeviceNet tool

There are two methods that can be used to view process variables with a DeviceNet tool:

  • You can execute Gets to read the current values of individual process variables from the appropriate objects. Table 7-1 lists the most commonly used process variables, by class, instance, attribute, and data type. For more information, see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile .
  • You can use the predefined input assemblies. The predefined input assemblies are summarized in Table 7-2. For more information, see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile .

Table 7-1 Process data in DeviceNet objects

Attribute ID

Data type Description

Class Instance

Analog Input Point Object (0x04)

1 (mass) 3 REAL Mass flow rate

100 REAL Mass total

101 REAL Mass inventory

102 UINT Mass flow measurement unit

103 UINT Mass total and mass inventory measurement unit

2 (liquid volume) 3 REAL Liquid volume flow rate

100 REAL Liquid volume total

101 REAL Liquid volume inventory

102 UINT Liquid volume flow measurement unit

103 UINT Liquid volume total and liquid volume inventory measurement unit

3 (density) 3 REAL Density

102 UINT Density measurement unit

4 (temperature) 3 REAL Temperature

102 UINT Temperature measurement unit

Gas Standard Volume Object (0x64)

1 (gas standard volume)

1 REAL Gas standard volume flow rate

2 REAL Gas standard volume total

3 REAL Gas standard volume inventory

5 REAL Gas standard volume flow measurement unit

6 REAL Gas standard volume total and gas standard volume inventory measurement unit

Page 46 of the Emerson Process Management Micro Motion 2400S user manual — Table 7-2 Summary of input assemblies
Page 46 · click to enlarge
Page 46

Using the Transmitter

Table 7-1 Process data in DeviceNet objects continued

Attribute ID

Data type Description

Class Instance

API Object (0x69)(1) 1 1 REAL Temperature-corrected density

2 REAL Temperature-corrected (standard) volume flow

3 REAL Temperature-corrected (standard) volume total

4 REAL Temperature-corrected (standard) volume inventory

5 REAL Batch weighted average density

6 REAL Batch weighted average temperature

7 REAL CTL

Enhanced Density Object (0x6A)(2) 1 1 REAL Density at reference temperature

2 REAL Density (fixed SG units)

3 REAL Standard volume flow rate

4 REAL Standard volume flow total

5 REAL Standard volume flow inventory

6 REAL Net mass flow rate

7 REAL Net mass flow total

8 REAL Net mass flow inventory

9 REAL Net volume flow rate

10 REAL Net volume flow total

11 REAL Net volume flow inventory

13 REAL Density (fixed Baume units)

(1) Requires petroleum measurement application. See Section 8.13 (2) Requires enhanced density application. See Section 8.14.

Table 7-2 Summary of input assemblies

Instance ID Data description Size (bytes) Data type Description

  • Status
  • Mass flow 5
  • BOOL
  • REAL Mass flow
  • 2 (1)
  • Status
  • Volume flow 5
  • BOOL
  • REAL Volume flow
  • Status
  • Mass flow
  • Mass total
  • BOOL
  • REAL
  • REAL

Mass flow and total

  • 4 (1)
  • Status
  • Volume flow
  • Volume total
  • BOOL
  • REAL
  • REAL

Volume flow and total

  • 5 (1)
  • Status
  • Mass flow
  • Temperature
  • Density
  • Volume flow
  • Drive gain
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

12 REAL Concentration · Basic process variables

Page 47 of the Emerson Process Management Micro Motion 2400S user manual — Instance ID Data description Size (bytes) Data type Description
Page 47 · click to enlarge
Page 47

Using the Transmitter

Table 7-2 Summary of input assemblies continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Instance ID Data description Size (bytes) Data type Description

  • Status
  • Mass flow
  • Mass total
  • Mass inventory
  • Temperature
  • Density
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Mass flow, mass totals, and other process variables

  • 7 (1)
  • Status
  • Volume flow
  • Volume total
  • Volume inventory
  • Temperature
  • Density
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Volume flow, volume totals, and other process variables

  • 8 (2)
  • Status
  • Mass flow
  • Mass total
  • Temperature
  • Gas standard volume flow
  • Gas standard volume total
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Gas standard volume flow

  • 9 (2)
  • Status
  • Mass flow
  • Temperature
  • Gas standard volume flow
  • Gas standard volume total
  • Gas standard volume inventory
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Gas standard volume flow

  • 10 (2)
  • Status
  • Temperature
  • Drive gain
  • Gas standard volume flow
  • Gas standard volume total
  • Gas standard volume inventory
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Gas standard volume flow

  • 11 (2)
  • Status
  • Gas standard volume flow 5
  • BOOL
  • REAL Gas standard volume flow
  • 12 (2)
  • Status
  • Gas standard volume flow
  • Gas standard volume total
  • Gas standard volume inventory
  • 13
  • BOOL
  • REAL
  • REAL
  • REAL

Gas standard volume flow

  • 13 (1)(3)
  • Status
  • Volume flow
  • Volume total
  • Volume inventory
  • API temperature-corrected volume flow
  • API temperature-corrected volume total
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 14 (1)(3)
  • Status
  • Volume flow
  • Volume total
  • API temperature-corrected density
  • API temperature-corrected volume flow
  • API temperature-corrected volume inventory
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 15 (1)(3)
  • Status
  • Mass flow
  • Mass total
  • Volume flow
  • Volume total
  • API temperature-corrected density
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

Petroleum measurement application · Petroleum measurement application · Petroleum measurement application

Page 48 of the Emerson Process Management Micro Motion 2400S user manual — Instance ID Data description Size (bytes) Data type Description
Page 48 · click to enlarge
Page 48

Using the Transmitter

Table 7-2 Summary of input assemblies continued

Instance ID Data description Size (bytes) Data type Description

  • 16 (1)(3)
  • Status
  • API temperature-corrected density
  • API temperature-corrected volume flow
  • API temperature-corrected volume inventory
  • API average temperature-corrected density
  • API average temperature
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 17 (1)(4)
  • Status
  • Mass flow
  • Volume flow
  • Temperature
  • Enhanced density reference density
  • Enhanced density specific gravity
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 18 (1)(4)
  • Status
  • Mass flow
  • Volume flow
  • Temperature
  • Density
  • Enhanced density concentration
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 19 (1)(4)
  • Status
  • Mass flow
  • Volume flow
  • Temperature
  • Density
  • Enhanced density Baume
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 20 (4)
  • Status
  • Temperature
  • Density
  • Enhanced density net mass flow
  • Enhanced density net mass total
  • Enhanced density net mass inventory
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 21 (4)
  • Status
  • Temperature
  • Density
  • Enhanced density net volume flow
  • Enhanced density net volume total
  • Enhanced density net volume inventory
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 22 (4)
  • Status
  • Mass Flow
  • Temperature
  • Density
  • Enhanced density reference density
  • Enhanced density net mass flow
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 23 (1)(4)
  • Status
  • Volume flow
  • Temperature
  • Density
  • Enhanced density reference density
  • Enhanced density net volume flow
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
Show 8 more labels / short text on this page
Petroleum measurement application · Enhanced density application · Enhanced density application · Enhanced density application · Enhanced density application · Enhanced density application · Enhanced density application · Enhanced density application
Page 49 of the Emerson Process Management Micro Motion 2400S user manual — 7.4.1 Using the module LED
Page 49 · click to enlarge
Page 49

Using the Transmitter

Table 7-2 Summary of input assemblies continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Instance ID Data description Size (bytes) Data type Description

  • 24 (1)(4)
  • Status
  • Mass flow
  • Volume flow
  • Density
  • Enhanced density reference density
  • Enhanced density standard volume flow
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 25 (4)
  • Status
  • Mass flow
  • Temperature
  • Density
  • Enhanced density reference density
  • Enhanced density concentration
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL
  • 26 (5)
  • Status
  • User-specified variable 1
  • User-specified variable 2
  • User-specified variable 3
  • User-specified variable 4
  • User-specified variable 5
  • 21
  • BOOL
  • REAL
  • REAL
  • REAL
  • REAL
  • REAL

(1) Available only if Gas Standard Volume is not enabled. (2) Available only if Gas Standard Volume is enabled. (3) Requires the petroleum measurement application. (4) Requires the enhanced density application. (5) Default variables are mass flow, temperature, density, volume flow, and drive gain, respectively. See Section 8.10.3 for information

on specifying the variables.

7.4 Using the LEDs

The user interface module provides three LEDs: a status LED, a module LED, and a network LED (see Figures 3-1 and 3-2).

  • For transmitters with a display, the LEDs can be viewed with the transmitter housing cover in place.
  • For transmitters without a display, the transmitter housing cover must be removed to view the LEDs (see Section 3.3).

For more information:

  • On using the module LED, see Section 7.4.1.
  • On using the network LED, see Section 7.4.2.
  • On using the status LED, see Section 7.5.1.

7.4.1 Using the module LED

The module LED indicates whether or not the transmitter has power and is operating properly. Table 7-3 lists the different states of the module LED, defines each state, and provides recommendations for correcting problem states.

Enhanced density application · Enhanced density application · Configurable assembly

Page 50 of the Emerson Process Management Micro Motion 2400S user manual — 7.5.1 Using the status LED
Page 50 · click to enlarge
Page 50

Using the Transmitter

Table 7-3 Module LED states, definitions, and recommendations

Module LED state Definition Recommendations

Off No power Check the connection to the DeviceNet network.

Solid green No processor faults No action required.

Flashing green Needs DeviceNet configuration; may be in Standby state

Indicates an A006 alarm. Characterization parameters are missing. See Section 6.2.

Solid red Non-recoverable fault Power cycle the transmitter. If condition does not clear, call Micro Motion customer service.

Flashing red Recoverable fault Check for any status alarms.

Flashing red/green Device in self-test Wait until self-test is complete. Check the Identity Object (0x01) for device states.

7.4.2 Using the network LED

The behavior of the network LED is standard, and is defined by the DeviceNet protocol. Table 7-4 lists the different states of the network LED and defines each state.

Table 7-4 Network LED states, definitions, and recommendations

Network LED state Definition Recommendations

Off Device not online The device is not connected to the network.(1) Check the wiring if this LED is lit.

Solid green Device online and connected No action required.

Flashing green Device online but not connected The device is connected to the network, but has not been allocated by a host. No action required.

Solid red Critical link failure The most common cause is duplicate MAC IDs (node addresses) on the network. Check for duplicate MAC IDs. Other causes include incorrect baud rate setting or other network failure.

Flashing red Connection timeout Power cycle the device, or release and re-allocate the device from the DeviceNet master. If desired, increase the timeout value (Expected Packet Rate) in the DeviceNet Object (0x03).

Flashing red/green Communication faulted state Not implemented in the Model 2400S DN transmitter.

(1) If the transmitter is the only device on the network, and there is no host on the network, this is the expected LED state, and no action

is required.

7.5 Viewing transmitter status

You can view transmitter status using the status LED, ProLink II, or a DeviceNet tool. Depending on the method chosen, different information is displayed.

7.5.1 Using the status LED

The status LED shows transmitter status as described in Table 7-5. Note that the status LED does not report event status or alarm status for alarms with severity level set to Ignore (see Section 8.8).

Page 51 of the Emerson Process Management Micro Motion 2400S user manual — 7.6 Handling status alarms
Page 51 · click to enlarge
Page 51

Using the Transmitter

Table 7-5 Transmitter status LED

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Status LED state Alarm priority Definition

Green No alarm Normal operating mode

Flashing yellow A104 alarm Zero or calibration in progress

  • Solid yellow Low severity (information) alarm
  • Alarm condition: will not cause measurement error
  • Digital communications report process data
  • Red High severity (fault) alarm
  • Alarm condition: will cause measurement error
  • Digital communications go to configured fault indicator (see Section 8.10.7)

7.5.2 Using ProLink II

ProLink II provides a Status window that displays:

  • Device (alarm) status
  • Event status
  • Assorted other transmitter data

7.5.3 Using a DeviceNet tool

Status information is located in the Diagnostics Object (0x66), Instance 1. This Object includes, among other data:

  • Alarm status (Attributes 12–17, Attributes 40–41)
  • Event status (Attribute 11)
  • Drive gain (Attribute 20)
  • Tube frequency (Attribute 21)
  • Left and right pickoff voltages (Attributes 23 and 24)

Use the Get service to read the required data. See Table C-7, or see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile for detailed information.

7.6 Handling status alarms

Specific process or flowmeter conditions cause status alarms. Each status alarm has an alarm code.

Status alarms are classified into three severity levels: Fault, Information, and Ignore. Severity level controls how the transmitter responds to the alarm condition.

The transmitter maintains two status flags for each alarm:

  • The first status flag indicates “active” or “inactive.”
  • The second status flag indicates “acknowledged” or “unacknowledged.”
Page 52 of the Emerson Process Management Micro Motion 2400S user manual — 7.6.1 Using the display
Page 52 · click to enlarge
Page 52

Using the Transmitter

In addition, the transmitter maintains alarm history for the 50 most recent alarm occurrences. Alarm history includes:

  • The alarm code
  • The “alarm active” timestamp
  • The “alarm inactive” timestamp
  • The “alarm acknowledged” timestamp

When the transmitter detects an alarm condition, it checks the severity level of the specific alarm and performs the actions described in Table 7-6.

Table 7-6 Transmitter responses to status alarms

Transmitter response

Alarm severity level (1)

Digital communications fault action

Status flags Alarm history

  • Fault
  • “Alarm active” status flag set immediately
  • “Alarm unacknowledged” status flag set immediately

“Alarm active” record written to alarm history immediately

Activated after configured fault timeout has expired (if applicable)(2)

  • Informational
  • “Alarm active” status flag set immediately
  • “Alarm unacknowledged” status flag set immediately

“Alarm active” record written to alarm history immediately

  • Ignore
  • “Alarm active” status flag set immediately
  • “Alarm unacknowledged” status flag set immediately

No action Not activated

(1) See Section 8.8 for information on setting the alarm severity level.

(2) See Sections 8.10.7 and 8.10.8 for more information on digital communications fault action and fault timeout.

When the transmitter detects that the alarm condition has cleared:

  • The first status flag is set to “inactive.”
  • Digital communications fault action is deactivated (Fault alarms only).
  • The “alarm inactive” record is written to alarm history (Fault and Informational alarms only).
  • The second status flag is not changed.

Operator action is required to return the second status flag to “acknowledged.” Alarm acknowledgment is not necessary. If the alarm is acknowledged, the “alarm acknowledged” record is written to alarm history.

7.6.1 Using the display

The display shows information only about active Fault or Informational alarms, based on alarm status bits. Ignore alarms are filtered out, and you cannot access alarm history via the display.

To view or acknowledge alarms using the display menus, see the flowchart in Figure 7-1.

If the transmitter does not have a display, or if operator access to the alarm menu is disabled (see Section 8.9.3), alarms can be viewed and acknowledged using ProLink II or a DeviceNet tool. Alarm acknowledgment is not required.

Additionally, the display may be configured to enable or disable the Ack All function. If disabled, the Ack All screen is not displayed and alarms must be acknowledged individually.

Not activated

Page 53 of the Emerson Process Management Micro Motion 2400S user manual — Status window
Page 53 · click to enlarge
Page 53

Using the Transmitter

Figure 7-1 Viewing and acknowledging alarms with the display

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Scroll and Select simultaneously

SEE ALARM

ACK ALL (1)

(1) This screen is displayed only if the ACK ALL

function is enabled (see Section 8.9.3) and there are unacknowledged alarms.

EXIT

NO ALARM

ACK

EXIT

7.6.2 Using ProLink II

ProLink II provides two ways to view alarm information:

  • The Status window
  • The Alarm Log window

Status window

The Status window displays the current status of the alarms considered to be most useful for information, service, or troubleshooting, including Ignore alarms. The Status window reads alarm status bits, and does not access alarm history. The Status window does not display acknowledgment information, and you cannot acknowledge alarms from the Status window.

Show 19 more labels / short text on this page
for 4 seconds · Select · Yes · No · Select · Scroll · Select · Scroll · Active/ unacknowledged · alarms? · No Yes · Alarm code · Scroll · Select · Scroll · Yes · No · Select · Scroll
Page 54 of the Emerson Process Management Micro Motion 2400S user manual — 7.6.3 Using a DeviceNet tool
Page 54 · click to enlarge
Page 54

Using the Transmitter

In the Status window:

  • Alarms are organized into three categories: Critical, Informational, and Operational. Each category is displayed on a separate panel.
  • If one or more alarms is active on a panel, the corresponding tab is red.
  • On a panel, a green LED indicates “inactive” and a red LED indicates “active.”

To use the Status window:

1. Click ProLink > Status .
2. Click the tab for the alarm category you want to view.

Alarm Log window

The Alarm Log window selects information from alarm history, and lists all alarms of the following types:

  • All active Fault and Information alarms
  • All inactive but unacknowledged Fault and Information alarms

Ignore alarms are never listed.

You can acknowledge alarms from the Alarm Log window.

In the Alarm Log window:

  • The alarms are organized into two categories: High Priority and Low Priority. Each category is displayed on a separate panel.
  • On a panel, a green LED indicates “inactive but unacknowledged” and a red LED indicates “active.”

To use the Alarm Log window:

1. Click ProLink > Alarm Log .
2. Click the tab for the alarm category you want to view.
3. To acknowledge an alarm, click the Ack checkbox. When the transmitter has processed the command:

- If the alarm was inactive, it will be removed from the list.

- If the alarm was active, it will be removed from the list as soon as the alarm condition clears.

7.6.3 Using a DeviceNet tool

Using the Diagnostics Object (0x66), you can view the status of a group of preselected alarms, view information about a specific alarm, acknowledge an alarm, and retrieve information from alarm history. For detailed information on the Diagnostics Object, see Table C-7, or see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile.

To view the status of a group of preselected alarms, execute a Get for Attributes 12–17, 40, or 41.

Page 55 of the Emerson Process Management Micro Motion 2400S user manual — 7.7 Using the totalizers and inventories
Page 55 · click to enlarge
Page 55

Using the Transmitter

To view information about a single alarm:

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

1. Execute a Set for Attribute 18, specifying the code for the alarm you want to check.
2. Execute a Get for Attribute 42, and interpret the data using the following codes:
  • 0x00 = Acknowledged and cleared
  • 0x01 = Active and acknowledged
  • 0x10 = Not acknowledged, but cleared
  • 0x11 = Not acknowledged, and active
3. Other information about the indexed alarm is available in the following attributes:
  • Attribute 43: Number of times this alarm has become active
  • Attribute 44: The time this alarm was last posted
  • Attribute 45: The time this alarm was last cleared

To acknowledge an alarm:

1. Execute a Set for Attribute 18, specifying the code for the alarm you want to acknowledge.
2. Execute a Set for Attribute 42, specifying a value of 0x00 .

To retrieve information from alarm history:

1. Execute a Set for Attribute 46, specifying the number of the alarm record you want to check. Valid values are 0–49 .
2. Execute Gets for the following attributes:
  • Attribute 47: The alarm type
  • Attribute 49: The time that this alarm changed status
  • Attribute 48: The type of status change:

- 1 = Alarm posted

- 2 = Alarm cleared

7.7 Using the totalizers and inventories

The totalizers keep track of the total amount of mass or volume measured by the transmitter over a period of time.

The inventories track the same values as the totalizers. Whenever totalizers are started or stopped, all inventories (including the API volume inventory and enhanced density inventories) are started or stopped automatically. However, when totalizers are reset, inventories are not reset automatically – you must reset inventories separately. This allows you to use the inventories to keep running totals across multiple totalizer resets.

You can view all totalizer and inventory values using any of the commmunication tools: the display, ProLink II, or a DeviceNet tool. Specific starting, stopping, and resetting functionality depends on the tool you are using.

Page 56 of the Emerson Process Management Micro Motion 2400S user manual — TOTAL
Page 56 · click to enlarge
Page 56

Using the Transmitter

7.7.1 Viewing current values for totalizers and inventories

You can view current values for the totalizers and inventories with the display (if your transmitter has a display), ProLink II, or a DeviceNet tool.

With the display

You cannot view current totalizer or inventory values with the display unless the display has been configured to show them. See Section 8.9.5.

To view a totalizer or inventory value, refer to Figure 7-2 and:

1. Check for the word TOTAL in the lower left corner of the LCD panel.
  • If Auto Scroll is enabled, wait until the desired value appears on the LCD panel. You can also Scroll until the desired value appears.
  • If Auto Scroll is not enabled, Scroll until the desired value appears.
2. Check the unit of measure to identify the process variable being displayed (e.g., mass, liquid volume, gas standard volume).
3. Check the unit of measure line to determine whether you are viewing a totalizer value or an inventory value:
  • Totalizer value: the unit of measure is a steady display.
  • Inventory value: the unit of measure alternates with one of the following:

- MASSI (for Mass Inventory)

- LVOLI (for Liquid Volume Inventory)

- GSV I (for Gas Standard Volume Inventory)

- TCORI (for API Temperature Corrected Inventory)

- STDVI (for ED Standard Volume Inventory)

- NETVI (for ED Net Volume Inventory)

- STDMI (for ED Net Mass Inventory)

4. Read the current value from the top line of the display.

Figure 7-2 Totalizer values on display

Emerson Process Management Micro Motion 2400S — Figure 7-2 Totalizer values on display diagram (page 56)
Fig. 8 · Figure 7-2 Totalizer values on display

TOTAL

Show 4 more labels / short text on this page
Current value · Unit of measure · Scroll optical switch · Select optical switch
Page 57 of the Emerson Process Management Micro Motion 2400S user manual — Figure 7-3 Controlling totalizers and inventories with the display
Page 57 · click to enlarge
Page 57

Using the Transmitter

With ProLink II

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

To view current totals for the totalizers and inventories with ProLink II:

1. Click ProLink .
2. Select Process Variables , API Process Variables, or ED Process Variables.

With a DeviceNet tool

To view current totals for the totalizers and inventories with a DeviceNet tool, see Section 7.3.3.

7.7.2 Controlling totalizers and inventories

Specific starting, stopping, and resetting functionality depends on the tool you are using.

With the display

If the required value is shown on the display, you can use the display to start and stop all totalizers and inventories simultaneously, or to reset individual totalizers. See the flowchart in Figure 7-3. You cannot reset any inventories with the display.

Figure 7-3 Controlling totalizers and inventories with the display

Emerson Process Management Micro Motion 2400S — Figure 7-3 Controlling totalizers and inventories with the display diagram (page 57)
Fig. 9 · Figure 7-3 Controlling totalizers and inventories wi…

(1) Displayed only if configured as a display variable. (2) The petroleum measurement application or enhanced density application must be enabled. (3) The Event Setpoint screens can be used to define or change Setpoint A for Event 1 or Event 2 only. These screens are displayed

only for specific types of events. To change the setpoint for an event defined on mass total, you must enter the totalizer management menu from the mass total screen. To change the setpoint for an event defined on volume total, you must enter the totalizer management menu from the volume total screen. See Section 8.6.3 for more information. (4) The display must be configured to allow stopping and starting. See Section 8.9.3. (5) All totalizers and inventories will be stopped and started together, including API and enhanced density totalizers and inventories. (6) The display must be configured to allow totalizer resetting. See Section 8.9.3. (7) Only the totalizer currently shown on the display will be reset. No other totalizers will be reset, and no inventories will be reset.

Be sure that the totalizer you want to reset is displayed before performing this reset.

Page 58 of the Emerson Process Management Micro Motion 2400S user manual — Table 7-7 Totalizer and inventory control functions supported by ProLink II
Page 58 · click to enlarge
Page 58

Using the Transmitter

With ProLink II

The totalizer and inventory control functions available with ProLink II are listed in Table 7-7. Note the following:

  • ProLink II does not support separate resetting of the API volume totalizer and API volume inventory. To reset these, you must reset all totalizers or all inventories.
  • By default, the ability to reset inventories from ProLink II is disabled. To enable it:

a. Click View > Preferences.

b. Check the Enable Inventory Totals Reset checkbox.

c. Click Apply.

Table 7-7 Totalizer and inventory control functions supported by ProLink II

Inventory reset

Object Function Disabled Enabled

Starting and stopping as a group ✓ ✓

Totalizers Resetting all ✓ ✓

Resetting mass totalizer separately ✓ ✓

Resetting volume totalizer separately ✓ ✓

Resetting enhanced density totalizers separately ✓ ✓

Resetting API volume totalizer separately Not supported Not supported

Inventories Resetting all ✓

Resetting mass inventory separately ✓

Resetting volume inventory separately ✓

Resetting enhanced density inventories separately ✓

Resetting API volume inventory separately Not supported Not supported

To start or stop all totalizers and inventories:

1. Click ProLink > Totalizer Control or ProLink > ED Totalizer Control (if the enhanced density application is enabled).
2. Click the All Totals Start or All Totals Stop button.

To reset all totalizers:

1. Click ProLink > Totalizer Control or ProLink > ED Totalizer Control (if the enhanced density application is enabled).
2. Click the All Totals Reset button.

To reset all inventories:

1. Click ProLink > Totalizer Control or ProLink > ED Totalizer Control (if the enhanced density application is enabled).
2. Click the All Totals Reset Inventories button.

Totalizers and inventories

Page 59 of the Emerson Process Management Micro Motion 2400S user manual — To accomplish this Use this device profile data
Page 59 · click to enlarge
Page 59

Using the Transmitter

To reset an individual totalizer or inventory:

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

1. Click ProLink > Totalizer Control or ProLink > ED Totalizer Control (if the enhanced density application is enabled).
2. Click the appropriate button (e.g., Reset Mass Total , Reset Volume Inventory , Reset Net Mass Total ).

With a DeviceNet tool

Using a DeviceNet tool, three methods are available for totalizer and inventory control:

  • EDS – If you have imported the EDS into your DeviceNet tool, you can perform the following functions from the EDS user interface:

- Reset mass totalizer

- Reset mass inventory

- Reset liquid volume totalizer

- Reset liquid volume inventory

- Reset API reference volume total

- Reset API reference volume inventory

- Reset gas standard volume totalizer

- Reset gas standard volume inventory

- Reset ED standard volume total

- Reset ED net mass total

- Reset ED net volume total

- Reset ED standard volume inventory

- Reset ED net mass inventory

- Reset ED net volume inventory

  • Explicit write – Using a Set, a Reset Total, or a Reset Inventory service, you can perform the functions listed in Table 7-8.
  • Output assemblies – Five output assemblies are provided, supporting the functions listed in Table 7-9. See the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile for detailed information.

Table 7-8 Totalizer and inventory control with a DeviceNet tool using explicit write

To accomplish this Use this device profile data

Stop all totalizers and inventories Analog Input Point Object (0x0A) Instance: 0 Attribute ID: 100 Service: Set Value: 0

Start all totalizers and inventories Analog Input Point Object (0x0A) Instance: 0 Attribute ID: 100 Service: Set Value: 1

Reset all totalizers Analog Input Point Object (0x0A) Instance: 0 Attribute ID: 101 Service: Set Value: 1

Page 60 of the Emerson Process Management Micro Motion 2400S user manual — To accomplish this Use this device profile data
Page 60 · click to enlarge
Page 60

Using the Transmitter

Table 7-8 Totalizer and inventory control with a DeviceNet tool using explicit write continued

To accomplish this Use this device profile data

Reset all inventories Analog Input Point Object (0x0A) Instance: 0 Attribute ID: 102 Service: Set Value: 1

Reset mass totalizer Analog Input Point Object (0x0A) Instance: 1 Service: Reset Total (0x32)

Reset mass inventory Analog Input Point Object (0x0A) Instance: 1 Service: Reset Inventory (0x33)

Reset liquid volume totalizer Analog Input Point Object (0x0A) Instance: 2 Service: Reset Total (0x32)

Reset liquid volume inventory Analog Input Point Object (0x0A) Instance: 2 Service: Reset Inventory (0x33)

Reset gas standard volume totalizer Gas Standard Volume Object (0x64) Instance: 1 Service: Reset Total (0x4B)

Reset gas standard volume inventory Gas Standard Volume Object (0x64) Instance: 1 Service: Reset Inventory (0x4C)

Reset API reference volume total API Object (0x69) Instance: 1 Service: Reset Total (0x4B)

Reset API reference volume inventory API Object (0x69) Instance: 1 Service: Reset Inventory (0x4C)

Reset ED standard volume total Enhanced Density Object (0x6A) Instance: 1 Service: Reset Total (0x4B)

Reset ED net mass total Enhanced Density Object (0x6A) Instance: 1 Service: Reset Total (0x4C)

Reset ED net volume total Enhanced Density Object (0x6A) Instance: 1 Service: Reset Total (0x4D)

Reset ED standard volume inventory Enhanced Density Object (0x6A) Instance: 1 Service: Reset Inventory (0x4F)

Reset ED net mass inventory Enhanced Density Object (0x6A) Instance: 1 Service: Reset Inventory (0x50)

Reset ED net volume inventory Enhanced Density Object (0x6A) Instance: 1 Service: Reset Inventory (0x51)

Page 61 of the Emerson Process Management Micro Motion 2400S user manual — Instance ID Data description Size (bytes) Data type
Page 61 · click to enlarge
Page 61

Using the Transmitter

Table 7-9 Output assemblies used for totalizer and inventory control

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Instance ID Data description Size (bytes) Data type

  • 53
  • Start/stop all totalizers and inventories 1
  • BOOL
  • 54
  • Reset all totalizer values 1
  • BOOL
  • 55
  • Reset all inventory values 1
  • BOOL
  • 56
  • Start/stop all totalizers and inventories
  • Reset all totalizer values 2
  • BOOL
  • BOOL
  • 57
  • Start/stop all totalizers and inventories
  • Reset all totalizer values
  • Reset all inventory values
  • BOOL
  • BOOL
  • BOOL
Page 62 of the Emerson Process Management Micro Motion 2400S user manual — 7.7.2 Controlling totalizers and inventories
Page 62 · click to enlarge
Page 62
Page 62 of the Emerson Process Management Micro Motion 2400S user manual — 7.7.2 Controlling totalizers and inventories
Page 63 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-1 Configuration map
Page 63 · click to enlarge
Page 63

Chapter 8 Optional Configuration

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

8.1 Overview

This chapter describes transmitter configuration parameters that may or may not be used, depending on your application requirements. For required transmitter configuration, see Chapter 6.

Table 8-1 lists the parameters that are discussed in this chapter. Default values and ranges for the most commonly used parameters are provided in Appendix A.

Table 8-1 Configuration map

Tool

Topic Subtopic ProLink II DeviceNet tool Display Section

Volume flow measurement for gas

✓ ✓ 8.2

Cutoffs ✓ ✓ 8.3

Damping ✓ ✓ 8.4

Flow direction ✓ ✓ 8.5

Events ✓ ✓ 8.6

Slug flow ✓ ✓ 8.7

Status alarm severity ✓ ✓ 8.8

Page 64 of the Emerson Process Management Micro Motion 2400S user manual — 8.2 Configuring volume flow measurement for gas
Page 64 · click to enlarge
Page 64

Optional Configuration

Table 8-1 Configuration map continued

Tool

Topic Subtopic ProLink II DeviceNet tool Display Section

Display(1) Update period ✓ ✓ ✓ 8.9.1

Display language ✓ ✓ ✓ 8.9.2

Totalizer start/stop ✓ ✓ ✓ 8.9.3

Totalizer reset ✓ ✓ ✓

Auto scroll ✓ ✓ ✓

Scroll rate ✓ ✓ ✓

Offline menu ✓ ✓ ✓

Password ✓ ✓ ✓

Alarm menu ✓ ✓ ✓

Ack all ✓ ✓ ✓

Backlight on/off ✓ ✓ ✓ 8.9.4

Backlight intensity ✓ ✓

Display variables ✓ ✓ 8.9.5

Display precision ✓ ✓

DeviceNet node address ✓ (2) 8.10.1

DeviceNet baud rate ✓ (2) 8.10.2

DeviceNet configurable input assembly

✓ 8.10.3

Modbus address ✓ ✓ ✓ 8.10.4

Modbus ASCII support ✓ ✓ ✓ 8.10.5

IrDA port usage ✓ ✓ ✓ 8.10.6

Digital communications fault action

✓ ✓ 8.10.78.10. 7

Fault timeout ✓ ✓ 8.10.8

Device settings ✓ ✓ 8.11

Sensor parameters ✓ ✓ 8.12

✓ ✓ 8.13

✓ ✓ 8.14

(1) These parameters apply only to transmitters with a display. (2) Cannot be set with the display menus, but can be set with digital communications hardware switches on the face of the transmitter.

8.2 Configuring volume flow measurement for gas

Two types of volume flow measurement are available:

  • Liquid volume (the default)
  • Gas standard volume

Digital communication · Petroleum measurement application · Enhanced density application

Page 65 of the Emerson Process Management Micro Motion 2400S user manual — Using the Gas Wizard
Page 65 · click to enlarge
Page 65

Optional Configuration

Only one type of volume flow measurement can be performed at a time (i.e., if liquid volume flow measurement is enabled, gas standard volume flow measurement is disabled, and vice versa). Different sets of volume flow measurement units are available, depending on which type of volume flow measurement is enabled (see Tables 6-3 and 6-4). If you will use a gas standard volume flow unit, additional configuration is required.

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

The method used to configure volume flow measurement for gas depends on the tool you are using: ProLink II or a DeviceNet tool.

8.2.1 Using ProLink II

To configure volume flow measurement for gas using ProLink II:

1. Click ProLink > Configure > Flow .
2. Set Vol Flow Type to Std Gas Volume .
3. Select the measurement unit you want to use from the Std Gas Vol Flow Units dropdown list. The default is SCFM .
4. Configure the Std Gas Vol Flow Cutoff (see Section 8.3). The default is 0 .
5. If you know the standard density of the gas that you are measuring, enter it in the Std Gas Density field. If you do not know the standard density, you can use the Gas Wizard. See the following section.

Using the Gas Wizard

The Gas Wizard is used to calculate the standard density of the gas that you are measuring.

To use the Gas Wizard:

1. Click ProLink > Configure > Flow .
2. Click the Gas Wizard button.
3. If your gas is listed in the Choose Gas dropdown list:

a. Enable the Choose Gas radio button.

b. Select your gas.

4. If your gas is not listed, you must describe its properties.

a. Enable the Enter Other Gas Property radio button.

b. Enable the method that you will use to describe its properties: Molecular Weight, Specific Gravity Compared to Air, or Density.

c. Provide the required information. Note that if you selected Density, you must enter the value in the configured density units and you must provide the temperature and pressure at which the density value was determined.

Page 66 of the Emerson Process Management Micro Motion 2400S user manual — 8.3 Configuring cutoffs
Page 66 · click to enlarge
Page 66

Optional Configuration

5. Click Next .
6. Verify the reference temperature and reference pressure. If these are not appropriate for your application, click the Change Reference Conditions button and enter new values for reference temperature and reference pressure.
7. Click Next . The calculated standard density value is displayed.
  • If the value is correct, click Finish . The value will be written to transmitter configuration.
  • If the value is not correct, click Back and modify input values as required.

8.2.2 Using a DeviceNet tool

The Gas Standard Volume Object is used to configure volume flow measurement for gas. See the flowchart in Figure 8-1.

Figure 8-1 Gas standard volume flow measurement – DeviceNet tool

  • Class: Gas Standard Volume Object (0x64) Instance: 1 Attribute ID: 7 Data type: BOOL Value:
  • 0 = disabled (and liquid volume flow enabled)
  • 1 = enabled (and liquid volume flow disabled) Service: Set

Class: Gas Standard Volume Object (0x64) Instance: 1 Attribute ID: 5 Data type: UINT Value: See Table 6-4 Service: Set

Class: Gas Standard Volume Object (0x64) Instance: 1 Attribute ID: 8 Data type: REAL Service: Set

(1) See Section 8.3. (2) The Gas Wizard is provided only

with ProLink II. If you are not using ProLink II, you must supply the required reference density.

Class: Gas Standard Volume Object (0x64) Instance: 1 Attribute ID: 4 Data type: REAL Service: Set

8.3 Configuring cutoffs

Cutoffs are user-defined values below which the transmitter reports a value of zero for the specified process variable. Cutoffs can be set for mass flow, liquid volume flow, gas standard volume flow, and density.

See Table 8-2 for cutoff default values and related information. See Section 8.3.1 for information on how the cutoffs interact with other transmitter measurements.

Show 6 more labels / short text on this page
Enable gas standard · volume flow measurement · Set unit · Set cutoff(1) · Set reference density · of gas(2)
Page 67 of the Emerson Process Management Micro Motion 2400S user manual — 8.4 Configuring the damping values
Page 67 · click to enlarge
Page 67

Optional Configuration

Table 8-2 Cutoff default values

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Cutoff type Default Comments

Mass flow 0.0 g/s Recommended setting: 5% of the sensor’s rated maximum flowrate

Liquid volume flow 0.0 L/s Limit: the sensor’s flow calibration factor in liters per second, multiplied by 0.2

Gas standard volume flow

0.0 No limit

Density 0.2 g/cm 3 Range0.0–0.5 g/cm 3

To configure cutoffs:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Tables C-1, C-2, C-3, and C-5.

8.3.1 Cutoffs and volume flow

If you are using liquid volume flow measurement:

  • The density cutoff is applied to the volume flow calculation. Accordingly, if the density drops below its configured cutoff value, the volume flow rate will go to zero.
  • The mass flow cutoff is not applied to the volume flow calculation. Even if the mass flow drops below the cutoff, and therefore the mass flow indicators go to zero, the volume flow rate will be calculated from the actual mass flow process variable.

If you are using gas standard volume flow measurement, neither the mass flow cutoff nor the density cutoff is applied to the volume flow calculation.

8.4 Configuring the damping values

A damping value is a period of time, in seconds, over which the process variable value will change to reflect 63% of the change in the actual process. Damping helps the transmitter smooth out small, rapid measurement fluctuations.

  • A high damping value makes the output appear to be smoother because the output must change slowly.
  • A low damping value makes the output appear to be more erratic because the output changes more quickly.

Damping can be configured for flow, density, and temperature.

When you change the damping value, the specified value is automatically rounded down to the nearest valid damping value. Valid damping values are listed in Table 8-3.

Before setting the damping values, review Section 8.4.1 for information on how the damping values affect other transmitter measurements.

Page 68 of the Emerson Process Management Micro Motion 2400S user manual — 8.5 Configuring the flow direction parameter
Page 68 · click to enlarge
Page 68

Optional Configuration

Table 8-3 Valid damping values

Process variable Valid damping values

Flow (mass and volume) 0, 0.04, 0.08, 0.16, ... 40.96

Density 0, 0.04, 0.08, 0.16, ... 40.96

Temperature 0, 0.6, 1.2, 2.4, 4.8, ... 76.8

To configure damping values:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Tables C-1, C-3, and C-4.

8.4.1 Damping and volume measurement

When configuring damping values, note the following:

  • Liquid volume flow is derived from mass and density measurements; therefore, any damping applied to mass flow and density will affect liquid volume measurement.
  • Gas standard volume flow is derived from mass flow measurement, but not from density measurement. Therefore, only damping applied to mass flow will affect gas standard volume measurement.

Be sure to set damping values accordingly.

8.5 Configuring the flow direction parameter

The flow direction parameter controls how the transmitter reports flow rate and how flow is added to or subtracted from the totalizers, under conditions of forward flow, reverse flow, or zero flow.

  • Forward (positive) flow moves in the direction of the arrow on the sensor.
  • Reverse (negative) flow moves in the direction opposite of the arrow on the sensor.

Options for flow direction include:

  • Forward only
  • Reverse only
  • Absolute value
  • Bidirectional
  • Negate/Forward only
  • Negate/Bidirectional

For the effect of flow direction on flow totals and flow values, see Table 8-4.

Page 69 of the Emerson Process Management Micro Motion 2400S user manual — 8.6.1 Defining events
Page 69 · click to enlarge
Page 69

Optional Configuration

Table 8-4 Effect of flow direction on totalizers and flow values

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Forward flow (1)

Flow direction value

Flow totals Flow values

Forward only Increase Positive

Reverse only No change Positive

Absolute value Increase Positive(2)

Negate/Forward only No change Negative

Reverse flow (3)

Flow direction value

Flow totals Flow values

Forward only No change Negative

Reverse only Increase Negative

Absolute value Increase Positive(2)

Negate/Forward only Increase Positive

(1) Process fluid flowing in same direction as flow direction arrow on sensor.

(2) Refer to the digital communications status bits for an indication of whether flow is positive or negative.

(3) Process fluid flowing in opposite direction from flow direction arrow on sensor.

To configure flow direction:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Table C-1.

8.6 Configuring events

An event occurs if the real-time value of a user-specified process variable varies above or below a user-specified value, or inside or outside a user-specified range. You can configure up to five events.

You may optionally specify one or more actions that will occur if the event occurs. For example, if Event 1 occurs, you may specify that the transmitter will stop all totalizers and inventories and reset the mass totalizer.

8.6.1 Defining events

To define an event:

  • Using ProLink II, see Figure B-3.
  • Using a DeviceNet tool, event specifications reside in the Diagnostics Object (0x66), Instance 1. See Table C-7.

The following general steps are required:

1. Select the event to define (Attribute 6).
2. Specify the event type (Attribute 7). Event Type options are defined in Table 8-5.
Show 4 more labels / short text on this page
Bidirectional Increase Positive · Negate/Bidirectional Decrease Negative · Bidirectional Decrease Negative · Negate/Bidirectional Increase Positive
Page 70 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-6 Event actions
Page 70 · click to enlarge
Page 70

Optional Configuration

3. Assign a process variable to the event (Attribute 10).
4. Specify the event’s setpoint(s) – the value(s) at which the event will occur or switch state (ON to OFF, or vice versa).
  • If Event Type is High or Low, only Setpoint A is used (Attribute 8)
  • If Event Type is In Range or Out of Range, both Setpoint A and Setpoint B (Attributes 9 and 10) are required.
5. Assign the event to an action or actions, if desired. Possible actions are listed in Table 8-6. To do this:
  • Using ProLink II, open the Discrete Input panel in the Configuration window, identify the action to be performed, then specify the event using the dropdown list. See Figure B-3.
  • Using the display, see Figure B-6 and use the ACT submenu.
  • Using a DeviceNet tool, refer to Table C-7, use Attribute 84 to specify the action to be performed, and set Attribute 85 to specify which event will initiate the action.

Table 8-5 Event types

DeviceNet code Description

Type

High (> A) 0 Default. Discrete event will occur if the assigned variable is greater than the setpoint (A).(1)

Low (< A) 1 Discrete event will occur if the assigned variable is less than the setpoint (A).(1)

In Range 2 Discrete event will occur if the assigned variable is greater than or equal to the low setpoint (A) and less than or equal to the high setpoint (B).(2)

Out of Range 3 Discrete event will occur if the assigned variable is less than or equal to the low setpoint (A) or greater than or equal to the high setpoint (B).(2)

(1) An event does not occur if the assigned variable is equal to the setpoint.

(2) An event occurs if the assigned variable is equal to the setpoint.

Table 8-6 Event actions

DeviceNet code Description

ProLink II label Display label

Start sensor zero START ZERO 1 Initiates a zero calibration procedure

Reset mass total RESET MASS 2 Resets the value of the mass totalizer to 0

Reset volume total RESET VOL 3 Resets the value of the liquid volume totalizer to 0(1)

Reset gas std volume total RESET GSV 21 Resets the value of the gas standard volume totalizer to 0(2)

Reset API ref vol total RESET TCORR 4 Resets the value of the API temperature-corrected volume totalizer to 0(3)

Reset ED ref vol total RESET STD V 5 Resets the value of the ED standard volume totalizer to 0(4)

Reset ED net mass total RESET NET M 6 Resets the value of the ED net mass totalizer to 0(4)

Reset ED net vol total RESET NET V 7 Resets the value of the ED net volume totalizer to 0(4)

Page 71 of the Emerson Process Management Micro Motion 2400S user manual — DeviceNet code Description
Page 71 · click to enlarge
Page 71

Optional Configuration

Table 8-6 Event actions continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

DeviceNet code Description

ProLink II label Display label

Reset all totals RESET ALL 8 Resets the value of all totalizers to 0

Start/stop all totalization START STOP 9 If totalizers are running, stops all totalizers If totalizers are not running, starts all totalizers

Increment current ED curve

INCR CURVE 18 Changes the active enhanced density curve from 1 to 2, from 2 to 3, etc.(4)

(1) Displayed only if Volume Flow Type = Liquid. (2) Displayed only if Volume Flow Type = Gas. (3) Available only if the petroleum measurement application is installed. (4) Available only if the enhanced density application is installed.

Example Define Event 1 to be active when the mass flow rate in forward or backward direction is less than 2 lb/min. Additionally, if this occurs, all totalizers should be stopped.

Using ProLink II:

1. Specify lb/min as the mass flow unit. See Section 6.3.1.
2. Configure the Flow Direction parameter for bidirectional flow. See Section 8.5.
3. Select Event 1.
4. Configure:
  • Event Type = Low
  • Process Variable (PV) = Mass Flow Rate
  • Low Setpoint (A) = 2
5. In the Discrete Input panel, open the dropdown list for Start/Stop All Totalization and select Discrete Event 1.

Using a DeviceNet tool:

1. Specify lb/min as the mass flow unit. See Section 6.3.1.
2. Configure the Flow Direction parameter for bidirectional flow. See Section 8.5.
3. In the Diagnostics Object (0x66), Instance 1, set the following attributes:
  • Discrete event index (Attribute 6) = 0
  • Discrete event action (Attribute 7) = 1
  • Discrete event process variable (Attribute 10) = 0
  • Discrete event setpoint A (Attribute 8) = 2
  • Discrete event action code (Attribute 84) = 9
  • Discrete event assignment (Attribute 85) = 57
Page 72 of the Emerson Process Management Micro Motion 2400S user manual — 8.7 Configuring slug flow limits and duration
Page 72 · click to enlarge
Page 72

Optional Configuration

8.6.2 Checking and reporting event status

There are several ways that event status can be determined:

  • ProLink II automatically displays event information on the Informational panel of the Status window.
  • The status of each event is stored in the Diagnostics Object (0x66), Instance 1, Attribute 11. For more information, see Table C-7, or see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile .

8.6.3 Changing event setpoints from the display

For Event 1 or Event 2 only, the value of Setpoint A can be changed from the display, under the following circumstances:

  • Mass total or volume total (gas or liquid) must be assigned to the event.
  • The event type must be either High or Low.
  • Mass total or volume total must be configured as a display variable (see Section 8.9.5).

Then, to reset Setpoint A from the display:

1. Referring to the totalizer management flowchart in Figure 7-3, Scroll to the appropriate display screen:
  • To reset the setpoint for an event defined on mass total, Scroll to the mass total screen.
  • To reset the setpoint for an event defined on volume total, Scroll to the volume total screen.
2. Select .
3. Enter the new setpoint value. See Section 3.5.5 for instructions on entering floating-point values with the display.

8.7 Configuring slug flow limits and duration

Slugs – gas in a liquid process or liquid in a gas process – occasionally appear in some applications. The presence of slugs can significantly affect the process density reading. The slug flow parameters can help the transmitter suppress extreme changes in process variables, and can also be used to identify process conditions that require correction.

Slug flow parameters are as follows:

  • Slug flow low limit – the point below which a condition of slug flow will exist. Typically, this is the lowest density point in your process’s normal density range. Default value is 0.0 g/cm 3 ; range is 0.0–10.0 g/cm 3 .
  • Slug flow high limit – the point above which a condition of slug flow will exist. Typically, this is the highest density point in your process’s normal density range. Default value is 5.0 g/cm3 ; range is 0.0–10.0 g/cm 3 .
  • Slug flow duration – the number of seconds the transmitter waits for a slug flow condition ( outside the slug flow limits) to return to normal ( inside the slug flow limits). Default value is 0.0 sec ; range is 0.0–60.0 sec .
Page 73 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-7 Alarm severity levels and fault reporting
Page 73 · click to enlarge
Page 73

Optional Configuration

If the transmitter detects slug flow:

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

  • A slug flow alarm is posted immediately.
  • During the slug duration period, the transmitter holds the mass flow rate at the last measured pre-slug value, independent of the mass flow rate measured by the sensor. The reported mass flow value is set to this value, and all internal calculations that include mass flow rate will use this value.
  • If slugs are still present after the slug duration period expires, the transmitter forces the mass flow rate to 0 , independent of the mass flow rate measured by the sensor. Mass flow rate is reported as 0 and all internal calculations that include mass flow rate will use 0 .
  • When process density returns to a value within the slug flow limits, the slug flow alarm is cleared and the mass flow rate reverts to the actual measured value.

To configure slug flow parameters:

  • Using ProLink II, use the Density panel in the Configuration window. See Figure B-2.
  • Using a DeviceNet tool, set Attributes 3, 4, and 5 in the Diagnostics Object (0x66), Instance 1. See Table C-7.

8.8 Configuring status alarm severity

The Model 2400S transmitter can report faults in the following ways:

  • Setting the “alarm active” status bit
  • Writing an “alarm active” record to alarm history
  • Implementing the digital communications fault action (see Section 8.10.7)

Status alarm severity determines which methods the transmitter will use when a specific alarm condition occurs, as described in Table 8-7. (See Section 7.6 for a more detailed discussion.)

Table 8-7 Alarm severity levels and fault reporting

Transmitter action if condition occurs

“Alarm active” status bit set?

“Alarm active” record written to history?

Digital communications fault action activated? (1)

Severity level

Fault Yes Yes Yes

Informational Yes Yes No

Ignore Yes No No

(1) For some alarms, the digital communications fault action will not begin until the fault timeout has expired. To configure fault timeout,

see Section 8.10.8. Other fault reporting methods occur as soon as the fault condition is recognized. Table 8-8 includes information on which alarms are affected by the fault timeout

Page 74 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-8 Status alarms and severity levels
Page 74 · click to enlarge
Page 74

Optional Configuration

Some alarms can be reclassified. For example:

  • The default severity level for Alarm A020 (calibration factors unentered) is Fault , but you can reconfigure it to either Informational or Ignore .
  • The default severity level for Alarm A102 (drive over-range) is Informational , but you can reconfigure it to either Ignore or Fault .

For a list of all status alarms and default severity levels, see Table 8-8. (For more information on status alarms, including possible causes and troubleshooting suggestions, see Table 11-2.)

To configure alarm severity:

  • Using ProLink II, see Figure B-3.
  • Using a DeviceNet tool, refer to Table C-7 and:

a. Set the alarm index (Attribute 18).

b. Set the severity for that alarm (Attribute 19).

Table 8-8 Status alarms and severity levels

Default severity Configurable?

Affected by fault timeout?

Alarm code ProLink II message

A001 (E)EPROM Checksum Error (CP) Fault No No

A002 RAM Error (CP) Fault No No

A003 Sensor Failure Fault Yes Yes

A004 Temperature Sensor Failure Fault No Yes

A005 Input Overrange Fault Yes Yes

A006 Not Configured Fault Yes No

A008 Density Overrange Fault Yes Yes

A009 Transmitter Initializing/Warming Up Ignore Yes No

A010 Calibration Failure Fault No No

A011 Zero Too Low Fault Yes No

A012 Zero Too High Fault Yes No

A013 Zero Too Noisy Fault Yes No

A014 Transmitter Failed Fault No No

A016 Line RTD Temperature Out-of-Range Fault Yes Yes

A017 Meter RTD Temperature Out-of-Range Fault Yes Yes

A020 Calibration Factors Unentered (FlowCal) Fault Yes No

A021 Incorrect Sensor Type (K1) Fault No No

A029 PIC/Daughterboard Communication Failure Fault No No

A030 Incorrect Board Type Fault No No

A031 Low Power Fault No No

A032 Meter Verification/Outputs In Fault Fault No No

A033 Sensor OK, Tubes Stopped by Process Fault Yes Yes

A102 Drive Overrange/Partially Full Tube Info Yes No

A104 Calibration in Progress Info Yes(1) No

A105 Slug Flow Info Yes No

A107 Power Reset Occurred Info Yes No

Page 75 of the Emerson Process Management Micro Motion 2400S user manual — 8.9.3 Enabling and disabling display functions
Page 75 · click to enlarge
Page 75

Optional Configuration

Table 8-8 Status alarms and severity levels continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Default severity Configurable?

Affected by fault timeout?

Alarm code ProLink II message

A116 APITemperature Outside Standard Range Info Yes No
A117 APIDensity Outside Standard Range Info Yes No
A120 EDUnable to Fit Curve Data Info No No
A121 EDExtrapolation Alarm Info Yes No

A131 Meter Verification/Outputs at Last Value Info Yes No

A132 Simulation Mode Active Info Yes No

A133 PIC UI EEPROM Error Info Yes No

(1) Can be set to either Informational or Ignore, but cannot be set to Fault.

8.9 Configuring the display

If your transmitter has a display, you can configure a variety of parameters that control the display functionality.

8.9.1 Update period

The Update Period (or Display Rate) parameter controls how often the display is refreshed with current data. The default is 200 milliseconds; the range is 100 milliseconds to 10,000 milliseconds (10 seconds).

To configure Update Period:

  • Using ProLink II, see Figure B-3.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.

8.9.2 Language

The display can be configured to use any of the following languages for data and menus:

  • English
  • French
  • German
  • Spanish

To set the display language:

  • Using ProLink II, see Figure B-3.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.

8.9.3 Enabling and disabling display functions

Table 8-9 lists the display functions and describes their behavior when enabled (shown) or disabled (hidden).

Page 76 of the Emerson Process Management Micro Motion 2400S user manual — 8.9.4 Configuring the LCD backlight
Page 76 · click to enlarge
Page 76

Optional Configuration

Table 8-9 Display functions

Parameter Enabled (shown) Disabled (hidden)

Totalizer start/stop Operators can start or stop totalizers using the display.

Operators cannot start or stop totalizers using the display.

Totalizer reset Operators can reset the mass and volume totalizers using the display.

Operators cannot reset the mass and volume totalizers using the display.

The display automatically scrolls through each process variable at a configurable rate.

Operators must Scroll to view process variables.

Off-line menu Operators can access the off-line menu (zero, simulation, and configuration).

Operators cannot access the off-line menu.

Operators must use a password to access the off-line menu.

Operators can access the off-line menu without a password.

Alarm menu Operators can access the alarm menu (viewing and acknowledging alarms).

Operators cannot access the alarm menu.

Operators are able to acknowledge all current alarms at once.

Operators must acknowledge alarms individually.

(1) If enabled, you may want to configure Scroll Rate.

(2) If enabled, the off-line password must also be configured.

To configure these parameters:

  • Using ProLink II, see Figure B-3.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.
  • If you use the display to disable access to the off-line menu, the off-line menu will disappear as soon as you exit the menu system. If you want to re-enable access, you must use ProLink II or a DeviceNet tool.
  • Scroll Rate is used to control the speed of scrolling when Auto Scroll is enabled. Scroll Rate defines how long each display variable (see Section 8.9.5) will be shown on the display. The time period is defined in seconds; e.g., if Scroll Rate is set to 10 , each display variable will be shown on the display for 10 seconds.
  • The off-line password prevents unauthorized users from gaining access to the off-line menu. The password can contain up to four numbers.
  • If you are using the display to configure the display:

- You must enable Auto Scroll before you can configure Scroll Rate.

- You must enable the off-line password before you can configure the password.

8.9.4 Configuring the LCD backlight

The backlight of the LCD panel on the display can be turned on or off. To turn the backlight on or off,

  • Using ProLink II, see Figure B-3.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.

Auto scroll(1) · Off-line password(2) · Acknowledge all alarms

Page 77 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-10 Example of a display variable configuration
Page 77 · click to enlarge
Page 77

Optional Configuration

In addition, if you are using ProLink II or a DeviceNet tool, you can control the intensity of the backlight. You can specify any value between 0 and 63; the higher the value, the brighter the backlight. To control the intensity of the backlight:

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

  • Using ProLink II, see Figure B-3.
  • Using a DeviceNet tool, see Table C-9.

8.9.5 Configuring the display variables and display precision

The display can scroll through up to 15 process variables in any order. You can configure the process variables to be displayed and the order in which they should appear. Additionally, you can configure display precision for each display variable. Display precision controls the number of digits to the right of the decimal place. Precision can be set to any value from 0 to 5.

  • To configure display variables or display precision using ProLink II, see Figure B-3.
  • To configure display variables using a DeviceNet tool, see Table C-9.
  • To configure display precision using a DeviceNet tool, refer to Table C-9 and:

a. Set the process variable index (Attribute 29) to the process variable to be configured.

b. Set the precision (Attribute 30) for that process variable.

Table 8-10 shows an example of a display variable configuration. Notice that you can repeat variables, and you can also specify None for any display variable except Display Var 1. For information on how the display variables will appear on the display, see Appendix D.

Table 8-10 Example of a display variable configuration

Display variable Process variable

Display variable 1(1)

Display variable 2 Mass totalizer

Display variable 3 Volume flow

Display variable 4 Volume totalizer

Display variable 5 Density

Display variable 6 Temperature

Display variable 7 External temperature

Display variable 8 External pressure

Display variable 9 Mass flow

Display variable 10 None

Display variable 11 None

Display variable 12 None

Display variable 13 None

Display variable 14 None

Display variable 15 None

(1) Display variable 1 cannot be set to None.

Mass flow

Page 78 of the Emerson Process Management Micro Motion 2400S user manual — 8.10.1 DeviceNet node address
Page 78 · click to enlarge
Page 78

Optional Configuration

8.10 Configuring digital communications

The digital communications parameters control how the transmitter will communicate using digital communications. The following digital communications parameters can be configured:

  • DeviceNet node address (MAC ID)
  • DeviceNet baud rate
  • DeviceNet configurable input assembly
  • Modbus address
  • Modbus ASCII support
  • IrDA port usage
  • Digital communications fault action
  • Fault timeout

8.10.1 DeviceNet node address

The default node address for the Model 2400S DN transmitter is 63. The valid range of node addresses is 0–63.

The DeviceNet node address can be set using digital communications hardware switches or a DeviceNet tool.

To set the node address using digital communications hardware switches:

1. Remove the transmitter housing cover as described in Section 3.3.
2. Identify the two addresses switches (the left and center switches) on the user interface module of your transmitter (see Section 3.3). The left switch, labeled MSD (Most Significant Digit), sets the first digit of the node address, and the center switch, labeled LSD (Least Significant Digit), sets the second digit.
3. For each switch, insert a small blade into the slot to rotate the arrow to the desired position. For example, to set the node address to 60 :

a. Rotate the arrow in the left switch to point to the digit 6.

b. Rotate the arrow in the center switch to point to the digit 0.

4. Replace the transmitter housing cover.
5. Either power cycle the transmitter or send a Reset service (0x05) to the Identity Object (0x01), Instance 1.

To set the node address using a DeviceNet tool:

1. Use the digital communications hardware switches to set the node address to any value in the Program range (values 64–99 ). This essentially disables the digital communications hardware switches and allows external control of the node address.
2. Set the MAC ID in the DeviceNet Object (0x03), Instance 1, Attribute 1, data type USINT.
3. Either power cycle the transmitter or send a Reset service (0x05) to the Identity Object (0x01), Instance 1.
Page 79 of the Emerson Process Management Micro Motion 2400S user manual — 8.10.3 DeviceNet configurable input assembly
Page 79 · click to enlarge
Page 79

Optional Configuration

8.10.2 DeviceNet baud rate

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

The default baud rate for the Model 2400S DN transmitter is 125 kBaud. Valid baud rates are listed in Table 8-11.

The baud rate can be set using a digital communications hardware switch or a DeviceNet tool. If the device cannot determine what its baud rate should be, it defaults to 500 kBaud.

To set the baud rate using the digital communications hardware switch:

1. Remove the transmitter housing cover as described in Section 3.3.
2. Identify the baud rate switch (the right switch) on the user interface module of your transmitter. See Section 3.3.
3. Insert a small blade into the slot on the switch and rotate the arrow to the desired position. See Table 8-11 for the baud rate codes. The arrow should point to the code representing the desired baud rate.

Table 8-11 Baud rate codes

Switch position Baud rate

3–9 (Program range) Controlled by DeviceNet system

4. Replace the transmitter housing cover.
5. Either power cycle the transmitter or send a Reset service (0x05) to the Identity Object (0x01), Instance 1.

To set the baud rate using a DeviceNet tool:

1. Use the digital communications hardware switch to set the baud rate to any value in the Program range (values 3–9 ). This essentially disables the digital communications hardware switch and allows external control of the baud rate.
2. Set the baud rate in the DeviceNet Object (0x03), Instance 1, Attribute 2, data type USINT.
3. Either power cycle the transmitter or send a Reset service (0x05) to the Identity Object (0x01), Instance 1.

8.10.3 DeviceNet configurable input assembly

The Model 2400S transmitter provides 25 predefined input assemblies and one configurable input assembly. The configurable input assembly allows you to specify five process variables to be published to the network.

0 125 kBaud · 1 250 kBaud · 2 500 kBaud

Page 80 of the Emerson Process Management Micro Motion 2400S user manual — 8.10.5 Modbus ASCII support
Page 80 · click to enlarge
Page 80

Optional Configuration

The Assembly Object is used to configure the configurable input assembly. See the flowchart in Figure 8-2.

Figure 8-2 Configurable input assembly – DeviceNet tool

ClassAssembly Object (0x0A) Instance: 26 Attribute ID: 100 Value: See Table C-15 Service: Set
ClassAssembly Object (0x0A) Instance: 26 Attribute ID: 101 Value: See Table C-15 Service: Set
ClassAssembly Object (0x0A) Instance: 26 Attribute ID: 102 Value: See Table C-15 Service: Set
ClassAssembly Object (0x0A) Instance: 26 Attribute ID: 103 Value: See Table C-15 Service: Set
ClassAssembly Object (0x0A) Instance: 26 Attribute ID: 104 Value: See Table C-15 Service: Set

8.10.4 Modbus address

Note: The Modbus address is applicable only when you are connecting to the service port from a tool that uses Modbus protocol. After initial startup, service port connections are typically used only for troubleshooting or for specific procedures such as temperature calibration. ProLink II is typically used for service port connections, and by default ProLink II will use the standard service port address rather than the configured Modbus address. See Section 4.4 for more information.

The set of valid Modbus addresses depends on whether or not support for Modbus ASCII is enabled or disabled (see Section 8.10.5). Valid Modbus addresses are as follows:

  • Modbus ASCII enabled: 1–15 , 32–47 , 64–79 , 96–110
  • Modbus ASCII disabled: 0–127

To configure the Modbus address:

  • Using ProLink II, see Figure B-2.
  • Using the display menus, see Figure B-6.

8.10.5 Modbus ASCII support

When support for Modbus ASCII is enabled, the service port can accept connection requests that use either Modbus ASCII or Modbus RTU. When support for Modbus ASCII is disabled, the service port cannot accept connection requests that use Modbus ASCII. Only Modbus RTU connections are accepted.

Show 10 more labels / short text on this page
User-specified · variable 1 · User-specified · variable 2 · User-specified · variable 3 · User-specified · variable 4 · User-specified · variable 5
Page 81 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-12 Digital communications fault action options
Page 81 · click to enlarge
Page 81

Optional Configuration

The primary reason to disable Modbus ASCII support is to allow a wider range of Modbus addresses for the service port.

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

To enable or disable Modbus ASCII support:

  • Using ProLink II, see Figure B-2.
  • Using the display menus, see Figure B-6.

8.10.6 IrDA port usage

The IrDA port on the display can be enabled or disabled. If enabled, it can be set for read-only or read/write access.

To enable or disable the IrDA port:

  • Using ProLink II, see Figure B-2.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.

To configure the IrDA port for read-only or read-write access:

  • Using ProLink II, see Figure B-2.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Table C-9.

8.10.7 Digital communications fault action

Digital communications fault action controls how digital communications will be affected by fault conditions. Table 8-12 lists the options for digital communications fault action.

Table 8-12 Digital communications fault action options

Option

Definition ProLink II label DeviceNet label DeviceNet code

Upscale Upscale 0 Process variables indicate the value is greater than the upper sensor limit. Totalizers stop counting.

Downscale Downscale 1 Process variables indicate the value is less than the lower sensor limit. Totalizers stop counting.

Zero Zero 2 Flow rates go to the value that represents zero flow. Density and temperature go to zero. Totalizers stop counting.

NAN 3 Process variables report IEEE NAN. Totalizers stop counting.

Flow to Zero Flow goes to zero 4 Flow rates go to the value that represents zero flow; other process variables are not affected. Totalizers stop counting.

None (default) None 5 Process variables reported as measured.

Not-A-Number (NAN)

Page 82 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-13 Device settings
Page 82 · click to enlarge
Page 82

Optional Configuration

To configure digital communications fault action:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Table C-7.

8.10.8 Fault timeout

By default, the transmitter activates the digital communications fault action as soon as the fault is detected. The fault timeout allows you to delay the digital communications fault action for a specified interval, for certain faults only. During the fault timeout period, digital communications behaves normally.

Note: The fault timeout applies only to the digital communications fault action. The “alarm active” status bit is set as soon as the fault is detected (all alarm severity levels), and the “alarm active” record is written to history immediately (Fault and Informational alarms only). For more information on alarm handling, see Section 7.6. For more information on alarm severity, see Section 8.8.

The fault timeout applies only to specific faults. Other faults are reported immediately, regardless of the fault timeout setting. For information on which faults are affected by the fault timeout, see Table 8-8.

To configure fault timeout:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Table C-7.

8.11 Configuring device settings

The device settings are used to describe the flowmeter components. Table 8-13 lists and defines the device settings.

Table 8-13 Device settings

Parameter Description

Descriptor Any user-supplied description. Not used in transmitter processing, and not required. Maximum length: 16 characters.

Message Any user-supplied message. Not used in transmitter processing, and not required. Maximum length: 32 characters.

Date Any user-selected date. Not used in transmitter processing, and not required.

To configure device settings, you must use ProLink II. See Figure B-2. If you are entering a date, use the left and right arrows at the top of the calendar to select the year and month, then click on a date.

Page 83 of the Emerson Process Management Micro Motion 2400S user manual — CTL derivation methods
Page 83 · click to enlarge
Page 83

Optional Configuration

8.12 Configuring sensor parameters

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

The sensor parameters are used to describe the sensor component of your flowmeter. They are not used in transmitter processing, and are not required. The following sensor parameters can be changed:

  • Serial number (can be set only once)
  • Sensor material
  • Sensor liner material
  • Sensor flange type

To configure sensor parameters:

  • Using ProLink II, see Figure B-2.
  • Using a DeviceNet tool, see Table C-8.

8.13 Configuring the petroleum measurement application

The API parameters determine the values that will be used in API-related calculations. The API parameters are available only if the petroleum measurement application is enabled on your transmitter.

8.13.1 About the petroleum measurement application

Some applications that measure liquid volume flow or liquid density are particularly sensitive to temperature factors, and must comply with American Petroleum Institute (API) standards for measurement. The petroleum measurement enables Correction of Temperature on volume of Liquids, or CTL.

Terms and definitions

The following terms and definitions are relevant to the petroleum measurement application:

  • API – American Petroleum Institute
  • CTL – Correction of Temperature on volume of Liquids. The CTL value is used to calculate the VCF value
  • TEC – Thermal Expansion Coefficient
  • VCF – Volume Correction Factor. The correction factor to be applied to volume process variables. VCF can be calculated after CTL is derived

CTL derivation methods

There are two derivation methods for CTL:

  • Method 1 is based on observed density and observed temperature.
  • Method 2 is based on a user-supplied reference density (or thermal expansion coefficient, in some cases) and observed temperature.
Page 84 of the Emerson Process Management Micro Motion 2400S user manual — Optional Configuration
Page 84 · click to enlarge
Page 84

Optional Configuration

API reference tables

Reference tables are organized by reference temperature, CTL derivation method, liquid type, and density unit. The table selected here controls all the remaining options.

  • Reference temperature:

- If you specify a 5x, 6x, 23x, or 24x table, the default reference temperature is 60 °F, and cannot be changed.

- If you specify a 53x or 54x table, the default reference temperature is 15 °C. However, you can change the reference temperature, as recommended in some locations (for example, to 14.0 or 14.5 °C).

  • CTL derivation method:

- If you specify an odd-numbered table (5, 23, or 53), CTL will be derived using method 1 described above.

- If you specify an even-numbered table (6, 24, or 54), CTL will be derived using method 2 described above.

  • The letters A , B , C , or D that are used to terminate table names define the type of liquid that the table is designed for:

- A tables are used with generalized crude and JP4 applications.

- B tables are used with generalized products.

- C tables are used with liquids with a constant base density or known thermal expansion coefficient.

- D tables are used with lubricating oils.

  • Different tables use different density units:

- Relative density (SG)

- Base density (kg/m3)

- Degrees API

Page 85 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-15 API parameters
Page 85 · click to enlarge
Page 85

Optional Configuration

Table 8-14 summarizes these options.

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Table 8-14 API reference temperature tables

CTL derivation method Base temperature

Density unit and range

Table

Degrees API Base density Relative density

5A Method 1 60 °F, non-configurable 0 to +100

5B Method 1 60 °F, non-configurable 0 to +85

5D Method 1 60 °F, non-configurable –10 to +40

23A Method 1 60 °F, non-configurable 0.6110 to 1.0760

23B Method 1 60 °F, non-configurable 0.6535 to 1.0760

23D Method 1 60 °F, non-configurable 0.8520 to 1.1640

53A Method 1 15 °C, configurable 610 to 1075 kg/m3

53B Method 1 15 °C, configurable 653 to 1075 kg/m3

53D Method 1 15 °C, configurable 825 to 1164 kg/m3

Reference temperature Supports

6C Method 2 60 °F, non-configurable 60 °F Degrees API

24C Method 2 60 °F, non-configurable 60 °F Relative density

54C Method 2 15 °C, configurable 15 °C Base density in kg/m3

8.13.2 Configuration procedure

The API configuration parameters are listed and defined in Table 8-15.

Table 8-15 API parameters

Variable Description

Table type Specifies the table that will be used for reference temperature and reference density unit. Select the table that matches your requirements. See API reference tables.

User defined TEC(1)

Thermal expansion coefficient. Enter the value to be used in CTL calculation.

Read-only. Displays the unit used for reference temperature in the reference table.

Density units Read-only. Displays the unit used for reference density in the reference table.

Read-only unless Table Type is set to 53x or 54x. If configurable:

  • Specify the reference temperature to be used in CTL calculation.
  • Enter reference temperature in °C.

(1) Configurable if Table Type is set to 6C, 24C, or 54C.

(2) In most cases, the temperature unit used by the API reference table should also be the temperature unit configured for the transmitter

to use in general processing. To configure the temperature unit, see Section 6.3.

To configure the petroleum measurement application:

  • Using ProLink II, see Figure B-3 .
  • Using a DeviceNet tool, see Table C-10.

Temperature units(2) · Reference temperature

Page 86 of the Emerson Process Management Micro Motion 2400S user manual — Table 8-16 Standard curves and associated measurement units
Page 86 · click to enlarge
Page 86

Optional Configuration

For the temperature value to be used in CTL calculation, you can use the temperature data from the sensor, or you can configure external temperature compensation to use either a static temperature value or temperature data from an external temperature device.

  • To use temperature data from the sensor, no action is required.
  • To configure external temperature compensation, see Section 9.3.

8.14 Configuring the enhanced density application

Micro Motion sensors provide direct measurements of density, but not of concentration. The enhanced density application calculates enhanced density process variables, such as concentration or density at reference temperature, from density process data, appropriately corrected for temperature.

8.14.1 About the enhanced density application

The enhanced density calculation calculation requires an enhanced density curve, which specifies the relationship between temperature, concentration, and density for the process fluid being measured. Micro Motion supplies a set of six standard enhanced density curves (see Table 8-16). If none of these curves is appropriate for your process fluid, you can configure a custom curve or purchase a custom curve from Micro Motion.

The derived variable, specified during configuration, controls the type of concentration measurement that will be produced. Each derived variable allows the calculation of a subset of enhanced density process variables (see Table 8-17). The available enhanced density process variables can be used in process control, just as mass flow rate, volume flow rate, and other process variables are used. For example, an event can be defined on an enhanced density process variable.

  • For all standard curves, the derived variable is Mass Conc (Dens).
  • For custom curves, the derived variable may be any of the variables listed in Table 8-17.

The transmitter can hold up to six curves at any given time, but only one curve can be active (used for measurement) at a time. All curves that are in transmitter memory must use the same derived variable.

Table 8-16 Standard curves and associated measurement units

Name Description Density unit Temperature unit

Deg Balling Curve represents percent extract, by mass, in solution, based on °Balling. For example, if a wort is 10 °Balling and the extract in solution is 100% sucrose, the extract is 10% of the total mass.

Deg Brix Curve represents a hydrometer scale for sucrose solutions that indicates the percent by mass of sucrose in solution at a given temperature. For example, 40 kg of sucrose mixed with 60 kg of water results in a 40 °Brix solution.

Deg Plato Curve represents percent extract, by mass, in solution, based on °Plato. For example, if a wort is 10 °Plato and the extract in solution is 100% sucrose, the extract is 10% of the total mass.

g/cm3 °F · g/cm3 °C · g/cm3 °F

Page 87 of the Emerson Process Management Micro Motion 2400S user manual — Derived variable – ProLink II label and definition
Page 87 · click to enlarge
Page 87

Optional Configuration

Table 8-16 Standard curves and associated measurement units continued

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Name Description Density unit Temperature unit

HFCS 42 Curve represents a hydrometer scale for HFCS 42 (high fructose corn syrup) solutions that indicates the percent by mass of HFCS in solution.

HFCS 55 Curve represents a hydrometer scale for HFCS 55 (high fructose corn syrup) solutions that indicates the percent by mass of HFCS in solution.

HFCS 90 Curve represents a hydrometer scale for HFCS 90 (high fructose corn syrup) solutions that indicates the percent by mass of HFCS in solution.

Table 8-17 Derived variables and available process variables

Available process variables

Density at reference temperature

Standard volume flow rate

Concentration Net mass flow rate

Net volume flow rate

Derived variable – ProLink II label and definition

Density @ Ref Density at reference temperature Mass/unit volume, corrected to a given reference temperature

SG Specific gravity The ratio of the density of a process fluid at a given temperature to the density of water at a given temperature. The two given temperature conditions do not need to be the same.

Mass Conc (Dens) Mass concentration derived from reference density The percent mass of solute or of material in suspension in the total solution, derived from reference density

✓

Mass Conc (SG) Mass concentration derived from specific gravity The percent mass of solute or of material in suspension in the total solution, derived from specific gravity

✓

Volume Conc (Dens) Volume concentration derived from reference density The percent volume of solute or of material in suspension in the total solution, derived from reference density

✓

Show 6 more labels / short text on this page
g/cm3 °C · g/cm3 °C · g/cm3 °C · Specific gravity · ✓ ✓ · ✓ ✓ ✓
Page 88 of the Emerson Process Management Micro Motion 2400S user manual — 8.14.2 Configuration procedure
Page 88 · click to enlarge
Page 88

Optional Configuration

Table 8-17 Derived variables and available process variables continued

Available process variables

Density at reference temperature

Standard volume flow rate

Concentration Net mass flow rate

Net volume flow rate

Derived variable – ProLink II label and definition

✓

Volume Conc (SG) Volume concentration derived from specific gravity The percent volume of solute or of material in suspension in the total solution, derived from specific gravity

Conc (Dens) Concentration derived from reference density The mass, volume, weight, or number of moles of solute or of material in suspension in proportion to the total solution, derived from reference density

Conc (SG) Concentration derived from specific gravity The mass, volume, weight, or number of moles of solute or of material in suspension in proportion to the total solution, derived from specific gravity

✓

8.14.2 Configuration procedure

Complete configuration instructions for the enhanced density application are provided in the manual entitled Micro Motion Enhanced Density Application: Theory, Configuration, and Use. Because of the complexity of this procedure, Micro Motion recommends using ProLink II for detailed configuration.

If it is necessary to use a DeviceNet tool, refer to the enhanced density manual for application information, and to the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile for complete device profile information.

Basic information on setting up the enhanced density application using a DeviceNet tool is provided in Figure 8-3.

Specific gravity · ✓ ✓ ✓

Page 89 of the Emerson Process Management Micro Motion 2400S user manual — Optional Configuration
Page 89 · click to enlarge
Page 89

Optional Configuration

Figure 8-3 Configuring the enhanced density application – DeviceNet tool

Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool Required Configuration Optional Configuration Using the Transmitter Using a DeviceNet Tool

Class: Enhanced Density Object (0x64) Instance: 1 Attribute ID: 39 Data type: BOOL Value: · 0: Disabled · 1: Enabled Service: Set

Enable the enhanced density application

Set transmitter density measurement unit to match curve unit · For standard curves, see Table 8-16 · For custom curves, see the information provided with the curve

Class: Analog Input Point Object (0x0A) Instance: 3 Attribute ID: 102 Value: See Table 6-5 Service: Set

Set transmitter temperature measurement unit to match curve unit · For standard curves, see Table 8-16 · For custom curves, see the information provided with the curve

Class: Analog Input Point Object (0x0A) Instance: 4 Attribute ID: 102 Value: See Table 6-6 Service: Set

Class: Enhanced Density Object (0x64) Instance: 1 Attribute ID: 15 Data type: USINT Value: See Table D-17 Service: Set

Set derived variable · For standard curves, use Mass Conc (Dens) · For custom curves, see the information provided with the curve

Class: Enhanced Density Object (0x64) Instance: 1 Attribute ID: 16 Data type: USINT Value: 0 – 5 Service: Set

Specify the active curve

Page 90 of the Emerson Process Management Micro Motion 2400S user manual — 8.14.2 Configuration procedure
Page 90 · click to enlarge
Page 90
Page 90 of the Emerson Process Management Micro Motion 2400S user manual — 8.14.2 Configuration procedure
Page 91 of the Emerson Process Management Micro Motion 2400S user manual — 9.2.1 Options
Page 91 · click to enlarge
Page 91

Chapter 9 Pressure Compensation and Temperature Compensation

Measurement Performance Defaults Troubleshooting Compensation

9.1 Overview

This chapter describes the following procedures:

  • Configuring pressure compensation – see Section 9.2
  • Configuring external temperature compensation – see Section 9.3
  • Obtaining external pressure or temperature data – see Section 9.4

9.2 Pressure compensation

The Model 2400S DN transmitter can compensate for the effect of pressure on the sensor flow tubes. Pressure effect is defined as the change in sensor flow and density sensitivity due to process pressure change away from calibration pressure.

9.2.1 Options

There are two ways to configure pressure compensation:

  • If the operating pressure is a known static value, you can configure that value in the transmitter.
  • If the operating pressure varies significantly, you must write a pressure value to the transmitter at appropriate intervals, using an appropriate output assembly. See Section 9.4.
Page 92 of the Emerson Process Management Micro Motion 2400S user manual — Figure 9-1 Configuring pressure compensation with ProLink II
Page 92 · click to enlarge
Page 92

Pressure Compensation and Temperature Compensation

9.2.2 Pressure correction factors

When configuring pressure compensation, you must provide the flow calibration pressure – the pressure at which the flowmeter was calibrated (which therefore defines the pressure at which there will be no effect on the calibration factor). Enter 20 PSI unless the calibration document for your sensor indicates a different calibration pressure.

Two additional pressure correction factors may be configured: one for flow and one for density. These are defined as follows:

  • Flow factor – the percent change in the flow rate per psi
  • Density factor – the change in fluid density, in g/cm 3 /psi

Not all sensors or applications require pressure correction factors. For the pressure correction values to be used, obtain the pressure effect values from the product data sheet for your sensor, then reverse the signs (e.g., if the pressure effect is 0.000004, enter a pressure correction factor of –0.000004).

9.2.3 Configuration

To enable and configure pressure compensation:

  • With ProLink II, see Figure 9-1.
  • With a DeviceNet tool, see Figure 9-2.

Figure 9-1 Configuring pressure compensation with ProLink II

Set measurement unit(1)

ProLink > Configuration > Pressure

ProLink > Configuration > Pressure

Use static pressure value? No

assembly(2) Enter External

(1) Pressure measurement unit must be configured to match pressure

unit used by external device. See Section 6.3. (2) See Section 9.4.

Show 17 more labels / short text on this page
Enable · Configure · View > Preferences · Enable External Pressure · Compensation · Enter Pressure units · Enter Flow factor · Apply · Apply · Enter Density factor · Enter Cal pressure · Apply · Yes · Set up output · Pressure · Apply · Done
Page 93 of the Emerson Process Management Micro Motion 2400S user manual — 9.3 External temperature compensation
Page 93 · click to enlarge
Page 93

Pressure Compensation and Temperature Compensation

Figure 9-2 Configuring pressure compensation with a DeviceNet tool

Measurement Performance Defaults Troubleshooting Compensation

ClassCalibration Object (0x65) Instance: 1 Attribute ID: 29 Value: See Table 6-7 Service: Set

(1) Pressure measurement unit must

be configured to match pressure unit used by external device. See Section 6.3. (2) See Section 9.4.

ClassCalibration Object (0x65) Instance: 1 Attribute ID: 32 Data type: REAL Service: Set
ClassCalibration Object (0x65) Instance: 1 Attribute ID: 30 Data type: REAL Service: Set
ClassCalibration Object (0x65) Instance: 1 Attribute ID: 31 Data type: REAL Service: Set

Class: Calibration Object (0x65) Instance: 1 Attribute ID: 27 Data type: BOOL Value: · 0 = disabled · 1 = enabled

Use static pressure value? No

ClassCalibration Object (0x65) Instance: 1 Attribute ID: 28 Data type: REAL Service: Set

9.3 External temperature compensation

External temperature compensation can be used with the petroleum measurement application or the enhanced density application.

Show 11 more labels / short text on this page
Set pressure unit · Set flow calibration · pressure · Set flow factor · Set density factor · Enable pressure · compensation · Yes · Set up output · Set static value · assembly(2)
Page 94 of the Emerson Process Management Micro Motion 2400S user manual — Figure 9-3 Configuring external temperature compensation with ProLink II
Page 94 · click to enlarge
Page 94

Pressure Compensation and Temperature Compensation

There are two ways to configure external temperature compensation:

  • If the operating temperature is a known static value, you can configure that value in the transmitter.
  • If the operating temperature varies significantly, you must write a temperature value to the transmitter at appropriate intervals, using an appropriate output assembly. See Section 9.4.

To enable and configure external temperature compensation:

  • With ProLink II, see Figure 9-3.
  • With a DeviceNet tool, see Figure 9-4.

Figure 9-3 Configuring external temperature compensation with ProLink II

View Menu > Preferences

Use static temp value?

ProLink > Configuration > Temperature

Apply (1) Temperature measurement unit must be

Enter Temperature units(1)

configured to match temperature unit used by external device. See Section 6.3. (2) See Section 9.4.

Show 13 more labels / short text on this page
Enable · Configure · Enable Use External · Temperature · No · Yes · Apply · Enter External · Temperature · Apply · Set up output · assembly(2) · Done
Page 95 of the Emerson Process Management Micro Motion 2400S user manual — REAL REAL
Page 95 · click to enlarge
Page 95

Pressure Compensation and Temperature Compensation

Figure 9-4 Configuring external temperature compensation with a DeviceNet tool

Class: Analog Input Point Object (0x0A) Instance: 4 Attribute ID: 102 Value: See Table 6-6 Service: Set

Measurement Performance Defaults Troubleshooting Compensation

(1) Temperature measurement unit

must be configured to match temperature unit used by external device. See Section 6.3. (2) See Section 9.4.

Class: Calibration Object (0x65) Instance: 1 Attribute ID: 25 Data type: BOOL Value: · 0 = disabled · 1 = enabled

Use static temp value? No

ClassCalibration Object (0x65) Instance: 1 Attribute ID: 26 Data type: REAL Service: Set

9.4 Obtaining external pressure and temperature data

The DeviceNet output assemblies used to obtain external pressure and/or temperature data are listed in Table 9-1. Use standard DeviceNet methods to implement the required connection.

Table 9-1 Output assemblies used for pressure or temperature compensation

Instance ID Data description Size Bytes Data type

50 External pressure 4 bytes Bytes 0–3 REAL

51 External temperature 4 bytes Bytes 0–3 REAL

52 External pressure External temperature

8 bytes Bytes 0–3 Bytes 4–7

REAL REAL

Show 7 more labels / short text on this page
Set temperature unit · Enable temperature · compensation · Yes · Set up output · assembly(2) · Set static value
Page 96 of the Emerson Process Management Micro Motion 2400S user manual — 9.4 Obtaining external pressure and temperature data
Page 96 · click to enlarge
Page 96
Page 96 of the Emerson Process Management Micro Motion 2400S user manual — 9.4 Obtaining external pressure and temperature data
Page 97 of the Emerson Process Management Micro Motion 2400S user manual — 10.2 Meter validation, meter verification, and calibration
Page 97 · click to enlarge
Page 97

Chapter 10 Measurement Performance

Measurement Performance Defaults Troubleshooting Compensation

10.1 Overview

This chapter describes the following procedures:

  • Meter verification – see Section 10.3
  • Meter validation and adjusting meter factors – see Section 10.4
  • Zero calibration – see Section 10.5
  • Density calibration – see Section 10.6
  • Temperature calibration – see Section 10.7

10.2 Meter validation, meter verification, and calibration

The Model 2400S transmitter supports the following procedures for the evaluation and adjustment of measurement performance:

  • Meter verification – establishing confidence in the sensor’s performance by analyzing secondary variables associated with flow and density
  • Meter validation – confirming performance by comparing the sensor’s measurements to a primary standard
  • Calibration – establishing the relationship between a process variable (flow, density, or temperature) and the signal produced by the sensor

Meter validation and calibration are available on all Model 2400S DN transmitters. Meter verification is available only if the meter verification option was ordered with the transmitter.

These three procedures are discussed and compared in Sections 10.2.1 through 10.2.4. Before performing any of these procedures, review these sections to ensure that you will be performing the appropriate procedure for your purposes.

Page 98 of the Emerson Process Management Micro Motion 2400S user manual — 10.2.3 Calibration
Page 98 · click to enlarge
Page 98

Measurement Performance

10.2.1 Meter verification

Meter verification evaluates the structural integrity of the sensor tubes by comparing current tube stiffness to the stiffness measured at the factory. Stiffness is defined as the load per unit deflection, or force divided by displacement. Because a change in structural integrity changes the sensor’s response to mass and density, this value can be used as an indicator of measurement performance. Changes in tube stiffness are typically caused by erosion, corrosion, or tube damage.

Meter verification does not affect measurement in any way. Micro Motion recommends performing meter verification at regular intervals.

10.2.2 Meter validation and meter factors

Meter validation compares a measurement value reported by the transmitter with an external measurement standard. Meter validation requires one data point.

If the transmitter’s mass flow, volume flow, or density measurement is significantly different from the external measurement standard, you may want to adjust the corresponding meter factor. A meter factor is the value by which the transmitter multiplies the process variable value. The default meter factors are 1.0, resulting in no difference between the data retrieved from the sensor and the data reported externally.

Meter factors are typically used for proving the flowmeter against a weights and measures standard. You may need to calculate and adjust meter factors periodically to comply with regulations.

10.2.3 Calibration

The flowmeter measures process variables based on fixed points of reference. Calibration adjusts those points of reference. Three types of calibration can be performed:

  • Zero, or no flow
  • Density calibration
  • Temperature calibration

Density and temperature calibration require two data points (low and high) and an external measurement for each. Zero calibration requires one data point. Calibration produces a change in the offset and/or the slope of the line that represents the relationship between the actual process value and the reported value.

Micro Motion flowmeters with the Model 2400S transmitter are calibrated at the factory, and normally do not need to be calibrated in the field. Calibrate the flowmeter only if you must do so to meet regulatory requirements. Contact Micro Motion before calibrating your flowmeter.

Page 99 of the Emerson Process Management Micro Motion 2400S user manual — 10.3 Performing meter verification
Page 99 · click to enlarge
Page 99

Measurement Performance

10.2.4 Comparison and recommendations

When choosing among meter verification, meter validation, and calibration, consider the following factors:

Measurement Performance Defaults Troubleshooting Compensation

  • Process interruption

- Meter verification requires approximately four minutes to perform. During these four minutes, flow can continue (provided sufficient stability is maintained); however, current process data will not be reported.

- Meter validation for density does not interrupt the process. However, meter validation for mass flow or volume flow requires process down-time for the length of the test.

- Calibration requires process down-time. In addition, density and temperature calibration require replacing the process fluid with low-density and high density fluids, or low-temperature and high-temperature fluids. Zero calibration requires stopping flow through the sensor.

  • External measurement requirements

- Meter verification does not require external measurements.

- Zero calibration does not require external measurements.

- Density calibration, temperature calibration, and meter validation require external measurements. For good results, the external measurement must be highly accurate.

  • Measurement adjustment

- Meter verification is an indicator of sensor condition, but does not change flowmeter internal measurement in any way.

- Meter validation does not change flowmeter internal measurement in any way. If you decide to adjust a meter factor as a result of a meter validation procedure, only the reported measurement is changed – the base measurement is not changed. You can always reverse the change by returning the meter factor to its previous value.

- Calibration changes the transmitter’s interpretation of process data, and accordingly changes the base measurement. If you perform a zero calibration, you can return to the previous zero or the factory zero. However, if you perform a density calibration or a temperature calibration, you cannot return to the previous calibration factors unless you have manually recorded them.

Micro Motion recommends that you purchase the meter verification option and perform meter verification frequently.

10.3 Performing meter verification

The meter verification procedure can be performed on any process fluid. It is not necessary to match factory conditions. Meter verification is not affected by any parameters configured for flow, density, or temperature.

During the test, process conditions must be stable. To maximize stability:

  • Maintain a constant temperature and pressure.
  • Avoid changes to fluid composition (e.g., two-phase flow, settling, etc.).
  • Maintain a constant flow. For higher test certainty, stop flow.

If stability varies outside test limits, the meter verification procedure will be aborted. Verify the stability of the process and retry the test.

Page 100 of the Emerson Process Management Micro Motion 2400S user manual — Figure 10-1 Meter verification procedure – ProLink II
Page 100 · click to enlarge
Page 100

Measurement Performance

During meter verification, you can choose between setting digital communications process variable values to the configured fault indicator or the last measured value. The values will remain fixed for the duration of the test (approximately four minutes). Disable all control loops for the duration of the procedure, and ensure that any data reported during this period is handled appropriately.

To perform meter verification:

  • Using ProLink II, follow the procedure illustrated in Figure 10-1.
  • Using the display menu, follow the procedure illustrated in Figure 10-2. For a complete illustration of the meter verification display menu, see Figure B-8.
  • Using a DeviceNet tool, follow the procedure illustrated in Figure 10-3.

For a discussion of meter verification results, see Section 10.3.1.

Figure 10-1 Meter verification procedure – ProLink II

Tools > Meter Verification > Structural Integrity Method

View previous test data

Enter optional test data

View report (option to print

Initialize and start meter

(1) If the graph was viewed at the beginning of the procedure,

clicking Back here will return to the beginning of the procedure (along the dotted line). (2) The results of the meter verification test are not saved until

Finish is clicked.

Show 24 more labels / short text on this page
Verify configuration · parameters · Next · Back(1) · Graph of results · Next · Next · or save) · verification · Finish(2) · Start · Fault configuration · Hold last · value · Progress bar shows · Abort · test in progress · Back Abort · Pass Fail · Yes · Next · Rerun · No · test?
Page 101 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 101 · click to enlarge
Page 101

Measurement Performance

Figure 10-2 Meter verification procedure – Display menu

Emerson Process Management Micro Motion 2400S — Measurement Performance diagram (page 101)
Fig. 10 · Measurement Performance

Measurement Performance Defaults Troubleshooting Compensation

(1) Either Unstable Flow or Unstable Drive Gain may

be displayed, indicating that the standard deviation of the flow or drive gain is outside limits. (2) Represents the percentage completion of the

x%(2) UNSTABLE FLOW(1)

Page 102 of the Emerson Process Management Micro Motion 2400S user manual — CAUTION
Page 102 · click to enlarge
Page 102

Measurement Performance

Figure 10-3 Meter verification procedure – DeviceNet tool

Step 1 Set output state (optional)

See Table 10-1 for the device profile information for each step.

Step 2 Set uncertainty limit (optional)

Step 3 Start/abort procedure

Step 4 Check current algorithm state

Running? Step 5 Read percent complete

Step 6 Check algorithm abort state

Step 9 Check abort code

Step 7 Check inlet stiffness

Within limits? No (>0)

CAUTION

Step 8 Check outlet stiffness

Within limits? No (>0)

CAUTION

PASS

Show 8 more labels / short text on this page
Manual abort (optional) · Yes (>0) · No (=0) · Able to complete? · No (<16) · Yes (=16) · Yes (=0) · Yes (=0)
Page 103 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 103 · click to enlarge
Page 103

Measurement Performance

Table 10-1 DeviceNet interface for meter verification

Step number Step description Interface

Measurement Performance Defaults Troubleshooting Compensation

1 Set output state ClassDiagnostics Object (0x66) Instance: 1 Attribute ID: 58 Data type: USINT Value:
  • 0: Last measured value (default)
  • 1: Fault Service: Set

2 Set uncertainty limit Class: Diagnostics Object (0x66) Instance: 1 Attribute ID: 59 Data type: REAL Range: 0.0025 to 0.05 Default: 0.04 Service: Set

3 Start/abort procedure ClassDiagnostics Object (0x66) Instance: 1
  • 0: Abort
  • 1: Start Service: 0x50

4 Check current algorithm state Class: Diagnostics Object (0x66) Instance: 1 Attribute ID: 54 Data type: USINT Service: Get

5 Read percent complete ClassDiagnostics Object (0x66) Instance: 1 Attribute ID: 57 Data type: USINT Service: Get

6 Check algorithm abort state Class: Diagnostics Object (0x66) Instance: 1 Attribute ID: 56 Data type: USINT Service: Get

7 Check inlet stiffness ClassDiagnostics Object (0x66) Instance: 1 Attribute ID: 61 Data type: USINT
  • 0: Within uncertainty limit
  • 1: Outside uncertainty limit Service: Get
8 Check outlet stiffness ClassDiagnostics Object (0x66) Instance: 1 Attribute ID: 62 Data type: USINT
  • 0: Within uncertainty limit
  • 1: Outside uncertainty limit Service: Get

9 Read abort code Class: Diagnostics Object (0x66) Instance: 1 Attribute ID: 55 Data type: USINT Codes: See Table C-7 Service: Get

Page 104 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 104 · click to enlarge
Page 104

Measurement Performance

10.3.1 Uncertainty limit and test results

The result of the meter verification test will be a percent uncertainty of normalized tube stiffness. The default limit for this uncertainty is ±4.0%. This limit is stored in the transmitter, and can be changed with ProLink II or a DeviceNet tool when optional test parameters are entered. For most installations, it is advisable to leave the uncertainty limit at the default value.

When the test is completed, the result will be reported as Pass, Fail/Caution (depending on the tool you are using), or Abort:

  • Pass – The test result is within the specified uncertainty limit. If transmitter zero and configuration match factory values, the sensor will meet factory specifications for flow and density measurement. It is expected that the meter will pass meter verification every time the test is run.
  • Fail/Caution – The test result is not within the specified uncertainty limit. Micro Motion recommends that you immediately re-run the meter verification test. If the meter passes the second test, the first Fail/Caution result can be ignored. If the meter fails the second test, the flow tubes may be damaged. Use the knowledge of your process to consider the type of damage and determine the appropriate action. These actions might include removing the meter from service and physically inspecting the tubes. At minimum, you should perform a flow validation (see Section 10.4) and a density calibration (see Section 10.6).
  • Abort – A problem occurred with the meter verification test (e.g., process instability). Check your process and retry the test.

ProLink II provides more detailed test data. See Section 10.3.2.

Page 105 of the Emerson Process Management Micro Motion 2400S user manual — 10.4 Performing meter validation
Page 105 · click to enlarge
Page 105

Measurement Performance

10.3.2 Additional ProLink II tools for meter verification

In addition to the Pass, Fail/Caution, and Abort result provided by the procedure, ProLink II provides the following additional meter verification tools:

Measurement Performance Defaults Troubleshooting Compensation

  • Test metadata – ProLink II allows you to enter a large amount of metadata about each test so that past tests can be audited easily. ProLink II will prompt you for this optional data during the test.
  • Visibility of configuration and zero changes – ProLink II has a pair of indicators that show whether the transmitter’s configuration or zero has changed since the last meter verification test. The indicators will be green if configuration and zero are the same, and red otherwise. You can find out more information about changes to configuration and zero by clicking the button next to each indicator.
  • Plotted data points – ProLink II shows the exact stiffness uncertainty on a graph. This allows you to see not only whether the meter is operating within specification, but also where the results fall within the specified limits. (The results are shown as two data points: Inlet and Outlet. The trending of these two points can help identify if local or uniform changes are occurring to the flow tubes.)
  • Trending – ProLink II has the ability to store a history of meter verification data points. This history is displayed on the results graph. The rightmost data points are the most recent. This history lets you see how your meter is trending over time, which can be an important way of detecting meter problems before they become severe. You can view the graph of past results at either the beginning or the end of the meter verification procedure. The graph is shown automatically at the end. Click View Previous Test Data to view the graph at the beginning.
  • Data manipulation – You can manipulate the graphed data in various ways by double-clicking the graph. When the graph configuration dialog is open, you can also export the graph in a number of formats (including “to printer”) by clicking Export .
  • Detailed report form – At the end of a meter verification test, ProLink II displays a detailed report of the test, which includes the same recommendations for pass/caution/abort results that are found in Section 10.3.1. You have the options of printing the report or saving it to disk as an HTML file.

More information about using ProLink II to perform meter verification can be found in the ProLink II manual and in the on-line ProLink II help system.

10.4 Performing meter validation

To perform meter validation:

1. Determine the meter factor(s) to use. You may set any combination of the mass flow, volume flow, and density meter factors.
  • The mass flow meter factor affects only the value reported for mass flow.
  • The density meter factor affects only the value reported for density.
  • The volume flow meter factor affects only the value reported for volume flow.
Page 106 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 106 · click to enlarge
Page 106

Measurement Performance

Therefore, to adjust volume flow, you must set the meter factor for volume flow. Setting a meter factor for mass flow and a meter factor for density will not produce the desired result. The volume flow calculations are based on original mass flow and density values, before the corresponding meter factors have been applied.

2. Calculate the meter factor as follows:

a. Sample the process fluid and record the process variable value reported by the flowmeter.

b. Measure the sample using an external standard.

c. Calculate the new meter factor using the following formula:

NewMeterFactor ConfiguredMeterFactor ExternalStandard ActualFlowmeterMeasurement × =

If you are calculating the volume flow meter factor, note that proving volume in the field may be expensive, and the procedure may be hazardous for some process fluids. Therefore, because volume is inversely proportional to density, an alternative to direct sampling and measurement is to calculate the volume flow meter factor from the density meter factor. This method provides partial correction by adjusting for any portion of the total offset that is caused by density measurement offset. Use this method only when a volume flow reference is not available, but a density reference is available. To use this method:

a. Calculate the meter factor for density, using the preceding formula.

b. Calculate the volume flow meter factor from the density meter factor, as shown below:

1 MeterFactorDensity =

DensityFlowmeter DensityExternalStandard × =

MeterFactorVolume ConfiguredMeterFactorDensity

3. Ensure that the meter factor is between 0.8 and 1.2 , inclusive. If the calculated meter factor is outside these limits, contact Micro Motion customer service.
4. Configure the meter factor in the transmitter. To configure meter factors:
  • Using ProLink II, see Figure B-2.
  • Using the display menus, see Figure B-6.
  • Using a DeviceNet tool, see Tables C-1, C-2, and C-3.

MeterFactorVolume

Page 107 of the Emerson Process Management Micro Motion 2400S user manual — 10.5 Performing zero calibration
Page 107 · click to enlarge
Page 107

Measurement Performance

Example The flowmeter is installed and proved for the first time. The flowmeter mass measurement is 250.27 lb; the reference device measurement is 250 lb. A mass flow meter factor is determined as follows:

Measurement Performance Defaults Troubleshooting Compensation

MassFlowMeterFactor 1 250 250.27 × 0.9989 = =

The first mass flow meter factor is 0.9989.

One year later, the flowmeter is proved again. The flowmeter mass measurement is 250.07 lb; the reference device measurement is 250.25 lb. A new mass flow meter factor is determined as follows:

MassFlowMeterFactor 0.9989 250.25 250.07 × 0.9996 = =

The new mass flow meter factor is 0.9996.

10.5 Performing zero calibration

Zeroing the flowmeter establishes the flowmeter’s point of reference when there is no flow. The meter was zeroed at the factory, and should not require a field zero. However, you may wish to perform a field zero to meet local requirements or to confirm the factory zero.

When you zero the flowmeter, you may need to adjust the zero time parameter. Zero time is the amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds.

  • A long zero time may produce a more accurate zero reference but is more likely to result in a zero failure. This is due to the increased possibility of noisy flow, which causes incorrect calibration.
  • A short zero time is less likely to result in a zero failure but may produce a less accurate zero reference.

For most applications, the default zero time is appropriate.

If the zero procedure fails, two recovery functions are provided:

  • Restore prior zero, available only from the Calibration dialog box in ProLink II (see Figure B-1), and only if you have not closed the Calibration window or disconnected from the transmitter. Once you have closed the Calibration window or disconnected from the transmitter, you can no longer restore the prior zero.
  • Restore factory zero, available via:

- The display – see Figure B-7

- ProLink II – see Figure B-1

- A DeviceNet tool – use the Diagnostics Object (0x66), Instance 1, Service 0x52. For more information, see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile.

If desired, you can use one of these functions to return the meter to operation while you are troubleshooting the cause of the zero failure (see Section 11.8).

Page 108 of the Emerson Process Management Micro Motion 2400S user manual — 10.5.2 Zero procedure
Page 108 · click to enlarge
Page 108

Measurement Performance

10.5.1 Preparing for zero

To prepare for the zero procedure:

1. Apply power to the flowmeter. Allow the flowmeter to warm up for approximately 20 minutes.
2. Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature.
3. Close the shutoff valve downstream from the sensor.
4. Ensure that the sensor is completely filled with fluid.
5. Ensure that the process flow has completely stopped.

CAUTION

If fluid is flowing through the sensor during zero calibration, the calibration may be inaccurate, resulting in inaccurate process measurement.

To improve the sensor zero calibration and measurement accuracy, ensure that process flow through the sensor has completely stopped.

10.5.2 Zero procedure

To zero the flowmeter:

  • Using the zero button, see Figure 10-4.
  • Using the display menu, see Figure 10-5. For a complete illustration of the display zero menu, see Figure B-7.
  • Using ProLink II, see Figure 10-6.
  • Using a DeviceNet tool, see Figure 10-7.
  • If the transmitter was ordered with a display:

- The zero button is not available.

- If the off-line menu has been disabled, you will not be able to zero the transmitter with the display. For information about enabling and disabling the off-line menu, see Section 8.9.3.

- You cannot change the zero time with the display. If you need to change the zero time, you must use ProLink II or a DeviceNet tool.

  • If the transmitter was ordered without a display, the zero button is available.

- You cannot change the zero time with the zero button. If you need to change the zero time, you must use ProLink II or a DeviceNet tool.

- The zero button is located on the user interface board, beneath the transmitter housing cover (see Figure 3-1). For instructions on removing the transmitter housing cover, see Section 3.3.

- To press the zero button, use a fine-pointed object that will fit into the opening (0.14 in or 3.5 mm). Hold the button down until the status LED on the user interface module begins to flash yellow.

  • During the zero procedure, the status LED on the user interface module flashes yellow.
Page 109 of the Emerson Process Management Micro Motion 2400S user manual — CAL PASS CAL FAIL
Page 109 · click to enlarge
Page 109

Measurement Performance

Figure 10-4 Zero button – Flowmeter zero procedure

Measurement Performance Defaults Troubleshooting Compensation

Figure 10-5 Display menu – Flowmeter zero procedure

Scroll and Select simultaneously

OFF-LINE MAINT

ZERO

ZERO/YES?

CAL PASS CAL FAIL

ZERO

EXIT

Show 19 more labels / short text on this page
Press ZERO button · Status LED flashes · yellow · Status LED · Solid · Solid Green or · Solid Yellow · Red · Troubleshoot · Done · for 4 seconds · Scroll · Select · Scroll · Select · Select · Troubleshoot · Select · Scroll
Page 110 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 110 · click to enlarge
Page 110

Measurement Performance

Figure 10-6 ProLink II – Flowmeter zero procedure

ProLink > Calibration > Zero Calibration

Wait until Calibration in Progress LED turns green

Show 10 more labels / short text on this page
Modify zero time · if required · Perform Auto Zero · Calibration in Progress · LED turns red · Calibration Failure LED · Red · Green · Done · Troubleshoot
Page 111 of the Emerson Process Management Micro Motion 2400S user manual — 10.6 Performing density calibration
Page 111 · click to enlarge
Page 111

Measurement Performance

Figure 10-7 DeviceNet tool – Flowmeter zero procedure

Measurement Performance Defaults Troubleshooting Compensation

Class: Calibration Object (0x65) Instance: 1 Attribute ID: 3 Data type: UINT Units: seconds Service: Set

Modify zero time if

Class: Calibration Object (0x65) Instance: 1 Service: 0x4B (perform or abort zero) Value: · 0: Abort zero calibration · 1: Start zero calibration

ClassDiagnostics Object (0x66) Instance: 1

Attribute ID 16, Bit 0x8000 Value: · 0: Zero complete · 1: Zero in progress Data type: USINT

ClassDiagnostics Object (0x66) Instance: 1

Attribute ID 12, Bit 0x0020 Value: · 0: Zero succeeded · 1: Zero failed Data type: USINT

Class: Calibration Object (0x65) Instance: 1 Attribute ID 4: Zero standard deviation Attribute ID 5: Zero offset Data type: REAL Units: milliseconds

10.6 Performing density calibration

Density calibration includes the following calibration points:

  • All sensors:

- D1 calibration (low-density)

- D2 calibration (high-density)

  • T-Series sensors only:

- D3 calibration (optional)

- D4 calibration (optional)

For T-Series sensors, the optional D3 and D4 calibrations could improve the accuracy of the density measurement. If you choose to perform the D3 and D4 calibration:

  • Do not perform the D1 or D2 calibration.
  • Perform D3 calibration if you have one calibrated fluid.
  • Perform both D3 and D4 calibrations if you have two calibrated fluids (other than air and water).
Show 5 more labels / short text on this page
required · Perform zero · Check status · Check outcome · Check zero values
Page 112 of the Emerson Process Management Micro Motion 2400S user manual — 10.6.2 Density calibration procedures
Page 112 · click to enlarge
Page 112

Measurement Performance

The calibrations that you choose must be performed without interruption, in the order listed here.

You can calibrate for density with ProLink II or a DeviceNet tool.

10.6.1 Preparing for density calibration

Before beginning density calibration, review the requirements in this section.

Sensor requirements

During density calibration, the sensor must be completely filled with the calibration fluid, and flow through the sensor must be at the lowest rate allowed by your application. This is usually accomplished by closing the shutoff valve downstream from the sensor, then filling the sensor with the appropriate fluid.

Density calibration fluids

D1 and D2 density calibration require a D1 (low-density) fluid and a D2 (high-density) fluid. You may use air and water. If you are calibrating a T-Series sensor, the D1 fluid must be air and the D2 fluid must be water.

CAUTION

For T-Series sensors, the D1 calibration must be performed on air and the D2 calibration must be performed on water.

For D3 density calibration, the D3 fluid must meet the following requirements:

  • Minimum density of 0.6 g/cm 3
  • Minimum difference of 0.1 g/cm 3 between the density of the D3 fluid and the density of water. The density of the D3 fluid may be either greater or less than the density of water

For D4 density calibration, the D4 fluid must meet the following requirements:

  • Minimum density of 0.6 g/cm 3
  • Minimum difference of 0.1 g/cm 3 between the density of the D4 fluid and the density of the D3 fluid. The density of the D4 fluid must be greater than the density of the D3 fluid
  • Minimum difference of 0.1 g/cm 3 between the density of the D4 fluid and the density of water. The density of the D4 fluid may be either greater or less than the density of water

10.6.2 Density calibration procedures

To perform a D1 and D2 density calibration:

  • With ProLink II, see Figure 10-8.
  • With a DeviceNet tool, see Figure 10-9.

To perform a D3 density calibration or a D3 and D4 density calibration:

  • With ProLink II, see Figure 10-10.
  • With a DeviceNet tool, see Figure 10-11.
Page 113 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 113 · click to enlarge
Page 113

Measurement Performance

Figure 10-8 D1 and D2 density calibration – ProLink II

Measurement Performance Defaults Troubleshooting Compensation

Close shutoff valve downstream from sensor Fill sensor with D1 fluid Fill sensor with D2 fluid

ProLink Menu > Calibration > Density cal – Point 1

ProLink Menu > Calibration > Density cal – Point 2

Enter density of D1 fluid

Enter density of D2 fluid

Show 15 more labels / short text on this page
D1 calibration · D2 calibration · Do Cal · Do Cal · Calibration in Progress · Calibration in Progress · light turns red · light turns red · Calibration in Progress · Calibration in Progress · light turns green · light turns green · Close · Close · Done
Page 114 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 114 · click to enlarge
Page 114

Measurement Performance

Figure 10-9 D1 and D2 density calibration – DeviceNet tool

Close shutoff valve downstream from sensor

ObjectCalibration object (0x65) Instance: 1 Attribute ID: 12 Data type: REAL Service: Set
ObjectCalibration object (0x65) Instance: 1 Attribute ID: 13 Data type: REAL Service: Set
ObjectCalibration object (0x65) Instance: 1 Service: 0x4C
ObjectCalibration object (0x65) Instance: 1 Service: 0x4D
ObjectDiagnostics object (0x66) Instance: 1 Attribute ID: 16 Bit: 14 Service: Get
ObjectDiagnostics object (0x66) Instance: 1 Attribute ID: 16 Bit: 13 Service: Get

Bit 14 0ff? No

Show 19 more labels / short text on this page
D1 calibration · D2 calibration · Fill sensor with · Fill sensor with · D1 fluid · D2 fluid · Enter density of · Enter density of · D1 fluid · D2 fluid · Start D1 calibration · Start D2 calibration · Monitor status · Monitor status · Yes · No · Bit 13 0ff? · Yes · Done
Page 115 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 115 · click to enlarge
Page 115

Measurement Performance

Figure 10-10 D3 or D3 and D4 density calibration – ProLink II

Measurement Performance Defaults Troubleshooting Compensation

Close shutoff valve downstream from sensor Fill sensor with D3 fluid

Fill sensor with D4 fluid

ProLink Menu > Calibration > Density cal – Point 3

ProLink Menu > Calibration > Density cal – Point 4

Enter density of D3 fluid

Enter density of D4 fluid

Show 16 more labels / short text on this page
D3 calibration · D4 calibration · Do Cal · Do Cal · Calibration in Progress · Calibration in Progress · light turns red · light turns red · Calibration in Progress · Calibration in Progress · light turns green · light turns green · Close · Close · Done · Done
Page 116 of the Emerson Process Management Micro Motion 2400S user manual — Measurement Performance
Page 116 · click to enlarge
Page 116

Measurement Performance

Figure 10-11 D3 or D3 and D4 density calibration – DeviceNet tool

Close shutoff valve downstream from sensor

ObjectCalibration Object (0x65) Instance: 1 Attribute ID: 15 Data type: REAL Service: Set
ObjectCalibration Object (0x65) Instance: 1 Attribute ID: 16 Data type: REAL Service: Set
ObjectCalibration Object (0x65) Instance: 1 Service: 0x4F
ObjectCalibration Object (0x65) Instance: 1 Service: 0x50
ObjectDiagnostics Object (0x66) Instance: 1 Attribute ID: 16 Bit: 7 Service: Get
ObjectDiagnostics Object (0x66) Instance: 1 Attribute ID: 16 Bit: 6 Service: Get

Bit 7 0ff? No

Show 20 more labels / short text on this page
D3 calibration · D4 calibration · Fill sensor with · Fill sensor with · D3 fluid · D4 fluid · Enter density of · Enter density of · D3 fluid · D4 fluid · Start D3 calibration · Start D4 calibration · Monitor status · Monitor status · Yes · No · Bit 6 0ff? · Yes · Done · Done
Page 117 of the Emerson Process Management Micro Motion 2400S user manual — Figure 10-12 Temperature calibration – ProLink II
Page 117 · click to enlarge
Page 117

Measurement Performance

10.7 Performing temperature calibration

Temperature calibration is a two-part procedure: temperature offset calibration and temperature slope calibration. The entire procedure must be completed without interruption.

Measurement Performance Defaults Troubleshooting Compensation

To perform temperature calibration, you must use ProLink II. See Figure 10-12.

Figure 10-12 Temperature calibration – ProLink II

Fill sensor with low-

Fill sensor with high-

Wait until sensor achieves

Wait until sensor achieves

ProLink Menu > Calibration > Temp offset cal

ProLink Menu > Calibration > Temp slope cal

Enter temperature of low-

Enter temperature of high-

Show 21 more labels / short text on this page
Temperature Offset calibration · Temperature Slope calibration · temperature fluid · temperature fluid · thermal equilibrium · thermal equilibrium · temperature fluid · temperature fluid · Do Cal · Do Cal · Calibration in Progress · Calibration in Progress · light turns red · light turns red · Calibration in Progress · Calibration in Progress · light turns green · light turns green · Close · Close · Done
Page 118 of the Emerson Process Management Micro Motion 2400S user manual — 10.7 Performing temperature calibration
Page 118 · click to enlarge
Page 118
Page 118 of the Emerson Process Management Micro Motion 2400S user manual — 10.7 Performing temperature calibration
Page 119 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-1 Troubleshooting topics and locations
Page 119 · click to enlarge
Page 119

Chapter 11 Troubleshooting

Measurement Performance Defaults Troubleshooting Compensation

11.1 Overview

This chapter describes guidelines and procedures for troubleshooting the flowmeter. The information in this chapter will enable you to:

  • Categorize the problem
  • Determine whether you are able to correct the problem
  • Take corrective measures (if possible)
  • Contact the appropriate support agency

WARNING

Using the service port clips to communicate with the transmitter in a hazardous area can cause an explosion.

Before using the service port clips to communicate with the transmitter in a hazardous area, make sure the atmosphere is free of explosive gases.

11.2 Guide to troubleshooting topics

Refer to Table 11-1 for a list of troubleshooting topics discussed in this chapter.

Table 11-1 Troubleshooting topics and locations

Section Topic

Section 11.4 Transmitter does not operate

Section 11.5 Transmitter does not communicate

Section 11.6 Checking the communication device

Section 11.7 Diagnosing wiring problems

Section 11.7.1 Checking the DeviceNet cable and connector

Page 120 of the Emerson Process Management Micro Motion 2400S user manual — 11.5 Transmitter does not communicate
Page 120 · click to enlarge
Page 120

Troubleshooting

Table 11-1 Troubleshooting topics and locations continued

Section Topic

Section 11.7.2 Checking grounding

Section 11.8 Zero or calibration failure

Section 11.9 Fault conditions

Section 11.10 Simulation mode for process variables

Section 11.11 Transmitter LEDs

Section 11.12 Status alarms

Section 11.13 Checking process variables

Section 11.14 Checking slug flow

Section 11.15 Checking the sensor tubes

Section 11.16 Checking the flow measurement configuration

Section 11.17 Checking the characterization

Section 11.18 Checking the calibration

Section 11.19 Checking the test points

Section 11.20 Checking sensor circuitry

11.3 Micro Motion customer service

To speak to a customer service representative, contact the Micro Motion customer service department. Contact information is provided in Section 1.10.

Before contacting Micro Motion customer service, review the troubleshooting information and procedures in this chapter, and have the results available for discussion with the technician.

11.4 Transmitter does not operate

If the transmitter is not receiving power, all three LEDs on the user interface will be off.

1. Check the DeviceNet connector (see Section 11.7.1).
2. Ensure that the network is providing sufficient power to the device.

If at least one LED is lit, perform all of the procedures in Section 11.7.

If the procedures do not indicate a problem with the electrical connections, contact the Micro Motion customer service department.

11.5 Transmitter does not communicate

If the transmitter does not appear to be communicating, the wiring may be faulty or the communications device may be incompatible. Check the wiring and the communication device. See Chapter 4 for ProLink II and Pocket ProLink, or Chapter 5 for a DeviceNet tool.

If you are trying to communicate via the IrDA port, ensure that the port is enabled, that read-write access is enabled, and that there is no active connection via the service port clips. See Section 8.10.6.

Page 121 of the Emerson Process Management Micro Motion 2400S user manual — 11.7.1 Checking the DeviceNet cable and connector
Page 121 · click to enlarge
Page 121

Troubleshooting

If the transmitter is communicating via the service port but not via DeviceNet, if you are experiencing intermittent DeviceNet communications, or if the transmitter appears to be operating normally but you cannot establish a DeviceNet connection:

Measurement Performance Defaults Troubleshooting Compensation

1. Verify the DeviceNet node address and baud rate for the transmitter. If necessary, change their values using the digital communications hardware switches on the user interface (see Sections 8.10.1 and 8.10.2), and retry the connection using the new digital communications parameters.
2. Check the DeviceNet cable and connector as described in Section 11.7.1.
3. A variety of network issues can cause communications problems (e.g., bus errors, bus traffic, too many nodes, insufficient power, shield voltage problems, or flat cable shorts). Follow your site’s standard procedures for diagnosing and correcting these problems.

11.6 Checking the communication device

Ensure that your communication device is compatible with your transmitter.

ProLink II

ProLink II v2.5 or later is required. To check the version of ProLink II:

1. Start ProLink II.
2. Click Help > About ProLink .

Pocket ProLink

Pocket ProLink v1.3 or later is required. To check the version of Pocket ProLink:

1. Start Pocket ProLink.
2. Tap the Information icon (the question mark) at the bottom of the main screen.

DeviceNet tool

The Model 2400S DN transmitter is compatible with all DeviceNet tools. Check that your DeviceNet tool is correctly configured and can make a connection to other devices on the network.

11.7 Diagnosing wiring problems

Use the procedures in this section to check the transmitter installation for wiring problems.

WARNING

Removing the transmitter housing cover in explosive atmospheres while the device is powered can subject the transmitter to environmental conditions that can cause an explosion.

Before removing the transmitter housing cover in explosive atmospheres, be sure to remove power from the device and wait five minutes.

11.7.1 Checking the DeviceNet cable and connector

To check the DeviceNet cable and connector:

1. Follow appropriate procedures to ensure that the process of checking the DeviceNet cable and connector does not interfere with existing measurement and control loops.
2. Disconnect the DeviceNet cable from the connector on the transmitter. See Figure 11-1.
Page 122 of the Emerson Process Management Micro Motion 2400S user manual — 11.10 Simulation mode for process variables
Page 122 · click to enlarge
Page 122

Troubleshooting

3. Visually inspect the cable and connector. Ensure that contact is good at both ends, that the pins are not bent, the cable is not crimped, and the cable covering is intact.
4. Retry the connection using a different cable.

Figure 11-1 DeviceNet connector

Emerson Process Management Micro Motion 2400S — Figure 11-1 DeviceNet connector diagram (page 122)
Fig. 11 · Figure 11-1 DeviceNet connector

11.7.2 Checking grounding

The sensor / transmitter assembly must be grounded. See your sensor installation manual for grounding requirements and instructions.

11.8 Zero or calibration failure

If a zero or calibration procedure fails, the transmitter will send a status alarm indicating the cause of failure. See Section 11.12 for specific remedies for status alarms indicating calibration failure.

11.9 Fault conditions

If a fault is reported, determine the exact nature of the fault by checking the status alarms (see Section 7.6). Once you have identified the status alarm(s) associated with the fault condition, refer to Section 11.12.

Some fault conditions can be corrected by cycling power to the transmitter. A power cycle can clear the following:

  • Zero failure
  • Stopped internal totalizer

11.10 Simulation mode for process variables

Simulation allows you to define arbitrary values for mass flow, temperature, and density. Simulation mode has several uses:

  • It can help determine if a problem is located in the transmitter or elsewhere in the system. For example, signal oscillation or noise is a common occurrence. The source could be the PLC, the meter, improper grounding, or a number of other factors. By setting up simulation to output a flat signal, you can determine the point at which the noise is introduced.
  • It can be used to analyze system response or to tune the loop.
Page 123 of the Emerson Process Management Micro Motion 2400S user manual — 11.11 Transmitter LEDs
Page 123 · click to enlarge
Page 123

Troubleshooting

If simulation mode is active, the simulated values are stored in the same memory locations used for process data from the sensor. Therefore, the simulated values will be used throughout transmitter functioning. For example, simulation will affect:

Measurement Performance Defaults Troubleshooting Compensation

  • All mass flow, temperature, or density values shown on the display or reported via digital communications
  • The mass total and inventory values
  • All volume calculations and data, including reported values, volume total, and volume inventory
  • All related values logged by Data Logger (a ProLink II utility)

Accordingly, do not enable simulation when your process cannot tolerate these effects, and be sure to disable simulation when you have finished testing.

Simulation does not change any diagnostic values.

Simulation mode is available only via ProLink II. To set up simulation, refer to Figure B-3 and follow the steps below.

1. Enable simulation mode.
2. For mass flow:

a. Specify the type of simulation you want: fixed value, sawtooth (triangular wave), or sine wave.

b. Enter the required values.

  • If you specified fixed value simulation, enter a fixed value.
  • If you specified sawtooth or sine wave simulation, enter a minimum value, maximum value, and wave period. Minimum and maximum values are entered in the current measurement units; the wave period is entered in seconds.
3. Repeat Step 2 for temperature and density.

To use simulation mode for problem location, enable simulation mode and check the signal at various points between the transmitter and the receiving device.

Be sure to disable simulation when testing is complete.

11.11 Transmitter LEDs

The user interface board includes three LEDs:

  • A status LED. See Table 7-5 for information on status LED behavior. If the status LED indicates an alarm condition:

a. View the alarm code using the procedures described in Section 7.5.

b. Identify the alarm (see Section 11.12).

c. Correct the condition.

d. If desired, acknowledge the alarm using the procedures described in Section 7.6.

  • A module LED. See Table 7-3 for information on the behavior of the module LED and suggestions on user response.
  • A network LED. See Table 7-4 for information on the behavior of the network LED. The network LED indicates the state of the device on the network, and does not indicate device status. Troubleshooting should focus on the network rather than the device.
Page 124 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-2 Status alarms and remedies
Page 124 · click to enlarge
Page 124

Troubleshooting

11.12 Status alarms

Status alarm codes are reported on the LCD panel (for transmitters that have a display), and status alarms can be viewed with ProLink II or a DeviceNet tool (see Section 7.6). All possible status alarms are listed in Table 11-2, along with the ProLink II message, possible causes, and suggested remedies.

You may find it useful to acknowledge all alarms before beginning the troubleshooting procedures. This will remove inactive alarms from the list and allow you to focus on active alarms.

Table 11-2 Status alarms and remedies

Alarm code

ProLink II message Cause Suggested remedy

A001 (E)EPROM Checksum Error (CP)

An uncorrectable checksum mismatch has been detected

  • Cycle power to the flowmeter.
  • The flowmeter might need service. Contact Micro Motion. See Section 11.3.

A002 RAM Error (CP) ROM checksum error or a RAM location cannot be written to

  • Cycle power to the flowmeter.
  • The flowmeter might need service. Contact Micro Motion. See Section 11.3.

A003 Sensor Failure Continuity failure of drive circuit, LPO, or RPO, or LPO-RPO mismatch when driving

  • Check for slug flow. See Section 11.14.
  • Check the test points. See Section 11.19.
  • Check the sensor circuitry. See Section 11.20.
  • Check sensor tubes for plugging.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A004 Temperature Sensor Failure

Combination of A016 and A017

  • Check the sensor RTD circuitry. See Section 11.20.
  • Verify that process temperature is within range of sensor and transmitter.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A005 Input Overrange The measured flow has exceeded the maximum flow rate of the sensor (ΔT > 200 μs)

  • If other alarms are present (typically, A003, A006, A008, A102, or A105), resolve those alarm conditions first. If the A005 alarm persists, continue with the suggestions here.
  • Verify process and check for slug flow. See Section 11.14.
  • Check the test points. See Section 11.19.
  • Check the sensor circuitry. See Section 11.20.
  • Check the sensor tubes for erosion. See Section 11.15.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A006 Not Configured Combination of A020 and A021

  • Check the characterization. Specifically, verify the FCF and K1 values. See Section 6.2.
  • If the problem persists, contact Micro Motion. See Section 11.3.
  • A008 Density Overrange The measured density has exceeded 0–10 g/cm 3
  • If other alarms are present (typically, A003, A006, A102, or A105), resolve those alarm conditions first. If the A008 alarm persists, continue with the suggestions here.
  • Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes (see Section 11.15).
  • Check for slug flow. See Section 11.14.
  • Check the sensor circuitry. See Section 11.20.
  • Verify calibration factors in transmitter configuration. See Section 6.2.
  • Check the test points. See Section 11.19.
  • If the problem persists, contact Micro Motion. See Section 11.3.
Page 125 of the Emerson Process Management Micro Motion 2400S user manual — Troubleshooting
Page 125 · click to enlarge
Page 125

Troubleshooting

Table 11-2 Status alarms and remedies continued

Alarm code

ProLink II message Cause Suggested remedy

Measurement Performance Defaults Troubleshooting Compensation

A009 Transmitter Initializing/Warming Up

Transmitter in power-up mode

  • Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
  • If alarm does not clear, make sure that the sensor is completely full or completely empty.
  • Check the sensor circuitry. See Section 11.20.

A010 Calibration Failure Mechanical zero: The resulting zero was greater than 3 μs. Temperature/Density Cals: many possible causes.

  • If alarm appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
  • Cycle power to the flowmeter, then retry.
  • If appropriate, restore the factory zero to return the flowmeter to operation.
  • A011 Zero Too Low See A10
  • Ensure that there is no flow through the sensor, then retry.
  • Cycle power to the flowmeter, then retry.
  • If appropriate, restore the factory zero to return the flowmeter to operation.
  • A012 Zero Too High See A10
  • Ensure that there is no flow through the sensor, then retry.
  • Cycle power to the flowmeter, then retry.
  • If appropriate, restore the factory zero to return the flowmeter to operation.
  • A013 Zero Too Noisy See A10
  • Remove or reduce sources of electromechanical noise, then retry. Sources of noise include: - Mechanical pumps - Pipe stress at sensor - Electrical interference - Vibration effects from nearby machinery
  • Cycle power to the flowmeter, then retry.
  • If appropriate, restore the factory zero to return the flowmeter to operation.
  • A014 Transmitter Failed Many possible causes
  • Cycle power to the flowmeter.
  • The transmitter might need service. Contact Micro Motion. See Section 11.3.

A016 Line RTD Temperature Out-Of-Range

The value computed for the resistance of the Line RTD is outside limits

  • Check the sensor RTD circuitry. See Section 11.20.
  • Verify that process temperature is within range of sensor and transmitter.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A017 Meter RTD Temperature Out-of-Range

The value computed for the resistance of the Meter/Case RTD is outside limits

  • Check the sensor RTD circuitry. See Section 11.20.
  • Verify that process temperature is within range of sensor and transmitter.
  • Check the characterization. Specifically, verify the FCF and K1 values. See Section 6.2.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A020 Calibration Factors Unentered (FlowCal)

The flow calibration factor and/or K1 has not been entered since the last master reset

  • Check the characterization. Specifically, verify the FCF and K1 values. See Section 6.2.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A021 Incorrect Sensor Type (K1)

The sensor is recognized as a straight tube but the K1 value indicates a curved tube, or vice versa

  • Check the characterization. Specifically, verify the FCF and K1 values. See Section 6.2.
  • Check the sensor RTD circuitry. See Section 11.20.
  • If the problem persists, contact Micro Motion. See Section 11.3.

A029 PIC/Daughterboard Communication Failure

  • Cycle power to the flowmeter.
  • Contact Micro Motion. See Section 11.3.

Transmitter electronics failure

Page 126 of the Emerson Process Management Micro Motion 2400S user manual — Troubleshooting
Page 126 · click to enlarge
Page 126

Troubleshooting

Table 11-2 Status alarms and remedies continued

Alarm code

ProLink II message Cause Suggested remedy

A030 Incorrect Board Type

The loaded software is not compatible with the programmed board type

  • Contact Micro Motion. See Section 11.3.

A031 Low Power The transmitter is not receiving enough power

  • Check power supply to transmitter. See Section 11.4.

A032 Meter Verification/Outputs In Fault

Meter verification in progress, with outputs set to fault

  • Allow the procedure to complete.
  • If desired, abort the procedure and restart with outputs set to last measured value.

A033 Sensor OK, Tubes Stopped by Process

No signal from LPO or RPO, suggesting that sensor tubes are not vibrating

  • Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes (see Section 11.15).

A102 Drive Overrange/ Partially Full Tube

The drive power (current/voltage) is at its maximum

  • Excessive drive gain. See Section 11.19.3.
  • Check the sensor circuitry. See Section 11.20.
  • If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore (see Section 8.8).

A104 Calibration in Progress

A calibration procedure is in progress

  • Allow the flowmeter to complete calibration.
  • For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration.

A105 Slug Flow The density has exceeded the user-defined slug (density) limits

  • See Section 11.14.

A107 Power Reset Occurred

The transmitter has been restarted

  • No action required.
  • If desired, reconfigure the alarm severity to Ignore (see Section 8.8).
A116 APITemperature Outside Standard Range

The process temperature is outside API-defined extrapolation limits

  • Verify process.
  • Verify API reference table and temperature configuration. See Section 8.13.
A117 APIDensity Outside Standard Range

The process density is outside API-defined extrapolation limits

  • Verify process.
  • Verify API reference table and density configuration. See Section 8.13.
A120 EDUnable to Fit Curve Data

The configured values for density curves do not meet accuracy requirements

  • Verify enhanced density configuration. See Section 8.14.
A121 EDExtrapolation Alarm

Enhanced density calculations are outside the configured data range

  • Verify process temperature.
  • Verify process density.
  • Verify enhanced density configuration. See Section 8.14.

A131 Meter Verification/Outputs at Last Value

Meter verification in progress, with outputs set to last measured value

  • Allow the procedure to complete.
  • If desired, abort the procedure and restart with outputs set to fault.

A132 Simulation Mode Active

Simulation mode is enabled

  • Disable simulation mode. See Section 11.10.

A133 PIC UI EEPROM Error

EEPROM data on the user interface module is corrupt

  • Contact Micro Motion. See Section 11.3.
Page 127 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-3 Process variables problems and remedies
Page 127 · click to enlarge
Page 127

Troubleshooting

11.13 Checking process variables

Micro Motion suggests that you make a record of the process variables listed below, under normal operating conditions. This will help you recognize when the process variables are unusually high or low.

Measurement Performance Defaults Troubleshooting Compensation

  • Flow rate
  • Density
  • Temperature
  • Tube frequency
  • Pickoff voltage
  • Drive gain

To view these values:

  • With ProLink II, use the Status window and the Diagnostic Information window. Both of these windows are opened from the ProLink menu.
  • Using the display, you must configure the display to show them. See Section 8.9.5.
  • Using a DeviceNet tool, see Tables C-1 through C-5 and Table C-7.

For troubleshooting, check the process variables under both normal flow and tubes-full no-flow conditions. Except for flow rate, you should see little or no change between flow and no-flow conditions. If you see a significant difference, record the values and contact Micro Motion customer service for assistance. See Section 11.3.

Unusual values for process variables may indicate a variety of different problems. Table 11-3 lists several possible problems and suggested remedies.

Table 11-3 Process variables problems and remedies

Symptom Cause Suggested remedy

Steady non-zero flow rate under no-flow conditions

Misaligned piping (especially in new installations)

  • Correct the piping.

Open or leaking valve • Check or correct the valve mechanism.

Bad sensor zero • Rezero the flowmeter or restore the factory zero or prior zero. See Section 10.5.

Page 128 of the Emerson Process Management Micro Motion 2400S user manual — Troubleshooting
Page 128 · click to enlarge
Page 128

Troubleshooting

Table 11-3 Process variables problems and remedies continued

Symptom Cause Suggested remedy

Erratic non-zero flow rate under no-flow conditions

Leaking valve or seal • Check pipeline.

Slug flow • See Section 11.14.

Plugged flow tube • Check drive gain and tube frequency. Purge the flow tubes.

Incorrect sensor orientation • Sensor orientation must be appropriate to process fluid. See the installation manual for your sensor.

Wiring problem • Check the sensor circuitry. See Section 11.20.

Vibration in pipeline at rate close to sensor tube frequency

  • Check environment and remove source of vibration.

Damping value too low • Check configuration. See Section 8.4.

Mounting stress on sensor • Check sensor mounting. Ensure: - Sensor is not being used to support

pipe. - Sensor is not being used to correct

pipe misalignment. - Sensor is not too heavy for pipe.

Sensor cross-talk • Check environment for sensor with similar (±0.5 Hz) tube frequency.

Erratic non-zero flow rate when flow is steady

Slug flow • See Section 11.14.

Damping value too low • Check configuration. See Section 8.4.

Plugged flow tube • Check drive gain and tube frequency. Purge the flow tubes.

Excessive or erratic drive gain • See Section 11.19.3.

Output wiring problem • Verify wiring between transmitter and receiving device. See the installation manual for your transmitter.

Problem with receiving device • Test with another receiving device.

Wiring problem • Check the sensor circuitry. See Section 11.20.

Inaccurate flow rate or batch total Bad flow calibration factor • Verify characterization. See Section 6.2.

Inappropriate measurement unit • Check configuration. See Section 11.16.

Bad sensor zero • Rezero the flowmeter or restore the factory zero or prior zero. See Section 10.5.

Bad density calibration factors • Verify characterization. See Section 6.2.

Bad flowmeter grounding • See Section 11.7.2.

Slug flow • See Section 11.14.

Wiring problem • Check the sensor circuitry. See Section 11.20.

Page 129 of the Emerson Process Management Micro Motion 2400S user manual — 11.14 Checking slug flow
Page 129 · click to enlarge
Page 129

Troubleshooting

Table 11-3 Process variables problems and remedies continued

Symptom Cause Suggested remedy

Measurement Performance Defaults Troubleshooting Compensation

Inaccurate density reading Problem with process fluid • Use standard procedures to check quality of process fluid.

Bad density calibration factors • Verify characterization. See Section 6.2.

Wiring problem • Check the sensor circuitry. See Section 11.20.

Bad flowmeter grounding • See Section 11.7.2.

Slug flow • See Section 11.14.

Sensor cross-talk • Check environment for sensor with similar (±0.5 Hz) tube frequency.

Plugged flow tube • Check drive gain and tube frequency. Purge the flow tubes.

Incorrect sensor orientation • Sensor orientation must be appropriate to process fluid. See the installation manual for your sensor.

RTD failure • Check for alarm conditions and follow troubleshooting procedure for indicated alarm.

Physical characteristics of sensor have changed

  • Check for corrosion, erosion, or tube damage. See Section 11.15.

Temperature reading significantly different from process temperature

  • RTD failure
  • Check for alarm conditions and follow troubleshooting procedure for indicated alarm.
  • Verify “Use external temperature” configuration and disable if appropriate. See Section 9.3.

Temperature reading slightly different from process temperature

Sensor leaking heat • Insulate the sensor.

Unusually high density reading Plugged flow tube • Check drive gain and tube frequency. Purge the flow tubes.

Incorrect K2 value • Verify characterization. See Section 6.2.

Unusually low density reading Slug flow • See Section 11.14.

Incorrect K2 value • Verify characterization. See Section 6.2.

Unusually high tube frequency Sensor erosion • Contact Micro Motion. See Section 11.3.

  • Unusually low tube frequency Plugged flow tube, corrosion, or erosion
  • Purge the flow tubes.
  • Perform meter verification. See Section 11.15.

Unusually low pickoff voltages Several possible causes • See Section 11.19.4.

Unusually high drive gain Several possible causes • See Section 11.19.3.

11.14 Checking slug flow

A slug flow alarm is posted whenever the measured process density is outside the configured slug flow limits (i.e., density is higher or lower than the configured normal range). Slug flow is typically caused by gas in a liquid process or liquid in a gas process. See Section 8.7 for a discussion of slug flow functionality.

Page 130 of the Emerson Process Management Micro Motion 2400S user manual — 11.19 Checking the test points
Page 130 · click to enlarge
Page 130

Troubleshooting

If slug flow occurs:

  • Check the process for cavitation, flashing, or leaks.
  • Change the sensor orientation.
  • Monitor density.
  • If desired, enter new slug flow limits (see Section 8.7).

- Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility of slug flow conditions.

- Lowering the low slug flow limit or raising the high slug flow limit will decrease the possibility of slug flow conditions.

  • If desired, increase slug duration (see Section 8.7).

11.15 Checking the sensor tubes

Corrosion, erosion, or damage to the sensor tubes can affect process measurement. To check for these conditions, perform the meter verification procedure. See Chapter 10.

11.16 Checking the flow measurement configuration

Using an incorrect flow measurement unit can cause the transmitter to report unexpected process variable values, with unpredictable effects on the process. Make sure that the configured flow measurement unit is correct. Check the abbreviations; for example, g/min represents grams per minute, not gallons per minute. See Section 6.3.

11.17 Checking the characterization

A transmitter that is incorrectly characterized for its sensor might report inaccurate process variable values. Both the K1 and Flow Cal (FCF) values must be appropriate for the sensor. If these values are incorrect, the sensor may not drive correctly or may send inaccurate process data.

If you discover that any of the characterization data are wrong, perform a complete characterization. See Section 6.2.

11.18 Checking the calibration

Improper calibration can cause the transmitter to report unexpected process variable values. If the transmitter appears to be operating correctly but sends unexpected process variable values, an improper calibration may be the cause.

Micro Motion calibrates every transmitter at the factory. Therefore, you should suspect improper calibration only if the transmitter has been calibrated after it was shipped from the factory. Before performing a calibration, consider meter validation or meter verification and select the appropriate procedure (see Section 10.2). Contact Micro Motion customer service for assistance.

11.19 Checking the test points

Some status alarms that indicate a sensor failure or overrange condition can be caused by problems other than a failed sensor. You can diagnose sensor failure or overrange status alarms by checking the flowmeter test points. The test points include left and right pickoff voltages, drive gain, and tube frequency. These values describe the current operation of the sensor.

Page 131 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-5 Sensor pickoff values
Page 131 · click to enlarge
Page 131

Troubleshooting

11.19.1 Obtaining the test point values

To obtain the test point values:

Measurement Performance Defaults Troubleshooting Compensation

  • With the display, configure the required test points as display variables. See Section 8.9.5.
  • With ProLink II

a. Click ProLink > Diagnostic Information.

b. Observe or record the values displayed for Tube Frequency, Left Pickoff, Right Pickoff, and Drive Gain.

  • With a DeviceNet tool, execute a Get for the attributes listed in Table 11-4.

Table 11-4 Test points with DeviceNet tool

Test point Class Instance Attribute

Drive gain Diagnostics Object (0x66) 1 20

11.19.2 Evaluating the test points

Use the following guidelines to evaluate the test points:

  • If the drive gain is erratic, negative, or saturated, refer to Section 11.19.3.
  • If the value for the left or right pickoff does not equal the appropriate value from Table 11-5, based on the sensor flow tube frequency, refer to Section 11.19.4 .
  • If the values for the left and right pickoffs equal the appropriate values from Table 11-5, based on the sensor flow tube frequency, record your troubleshooting data and contact Micro Motion customer service. See Section 11.3.

Table 11-5 Sensor pickoff values

Sensor (1)

Pickoff value

ELITE® CMF sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency

F025, F050, F100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency

F200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency

H025, H050, H100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency

H200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency

R025, R050, or R100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency

R200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency

T-Series sensors 0.5 mV peak-to-peak per Hz based on sensor flow tube frequency

CMF400 I.S. sensors 2.7 mV peak-to-peak per Hz based on sensor flow tube frequency

(1) If your sensor is not listed, contact Micro Motion. See Section 11.3.

Tube period 21 · Left pickoff 23 · Right pickoff 24

Page 132 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-7 Low pickoff voltage causes and remedies
Page 132 · click to enlarge
Page 132

Troubleshooting

11.19.3 Drive gain problems

Problems with drive gain can appear in several different forms:

  • Saturated or excessive (near 100%) drive gain
  • Erratic drive gain (e.g., rapid shifting from positive to negative)
  • Negative drive gain

See Table 11-6 for a list of possible problems and remedies.

Table 11-6 Drive gain problems, causes, and remedies

Cause Possible remedy

Excessive slug flow • See Section 11.14.

  • Cavitation or flashing
  • Increase inlet or back pressure at the sensor.
  • If a pump is located upstream from the sensor, increase the distance between the pump and sensor.

Plugged flow tube • Purge the flow tubes.

Mechanical binding of sensor tubes • Ensure sensor tubes are free to vibrate. Possible problems include: - Pipe stress. Check for pipe stress and eliminate if present. - Lateral tube shift due to hammer effect. If this is a possibility,

contact Micro Motion. See Section 11.3. - Warped tubes caused by overpressurization. If this is a possibility,

contact Micro Motion.

Incorrect sensor type configured • Verify sensor type configuration, then verify sensor characterization. See Section 6.2.

Open drive or left pickoff sensor coil • Contact Micro Motion. See Section 11.3.

Drive board or module failure, cracked flow tube, or sensor imbalance

  • Contact Micro Motion. See Section 11.3.

11.19.4 Low pickoff voltage

Low pickoff voltage can be caused by several problems. See Table 11-7.

Table 11-7 Low pickoff voltage causes and remedies

Cause Possible remedy

Slug flow • See Section 11.14.

No tube vibration in sensor • Check for plugging.

Moisture in the sensor electronics • Eliminate the moisture in the sensor electronics.

Damaged sensor • Ensure sensor is free to vibrate (no mechanical binding). Possible problems include: - Pipe stress. Check for pipe stress and eliminate if present. - Lateral tube shift due to hammer effect. If this is a possibility,

contact Micro Motion. See Section 11.3. - Warped tubes caused by overpressurization. If this is a possibility,

  • contact Micro Motion.
  • Test sensor circuitry. See Section 11.20.
  • Contact Micro Motion.
Page 133 of the Emerson Process Management Micro Motion 2400S user manual — Troubleshooting
Page 133 · click to enlarge
Page 133

Troubleshooting

11.20 Checking sensor circuitry

Problems with sensor circuitry can cause several alarms, including sensor failure and a variety of out-of-range conditions. Testing involves:

Measurement Performance Defaults Troubleshooting Compensation

  • Inspecting the cable that connects the transmitter to the sensor
  • Measuring the resistances of the sensor's pin pairs and RTDs
  • Ensuring that the circuits are not shorted to each other or to the sensor case
1. Follow appropriate procedures to ensure that the process of checking the sensor circuitry does not interfere with existing measurement and control loops.
2. Disconnect the DeviceNet cable from the DeviceNet connector on the Model 2400S DN transmitter.
3. If the transmitter is in a hazardous environment, wait five minutes.
4. Check the sensor cable and sensor connection:

a. Referring to Figure 11-2, loosen the four captive transmitter housing cover screws and remove the transmitter housing cover.

b. Loosen the two captive user interface screws.

c. Gently lift the user interface module, disengaging it from the connector on the transmitter.

d. Two captive screws (2.5 mm hex head) hold the transmitter in the housing. Loosen the screws and gently lift the transmitter away from the housing. Allow the transmitter to hang by the cable.

e. Check the cable for any signs of damage.

f. Ensure that the cable is fully plugged in and making a good connection. If it is not, reseat the cable, reassemble the transmitter and sensor, and check operation.

Page 134 of the Emerson Process Management Micro Motion 2400S user manual — Troubleshooting
Page 134 · click to enlarge
Page 134

Troubleshooting

Figure 11-2 Exploded view of transmitter and connection to sensor

Emerson Process Management Micro Motion 2400S — Troubleshooting diagram (page 134)
Fig. 12 · Troubleshooting

Feedthrough (mounted on sensor)

5. If the problem is not resolved, unplug the cable from the feedthrough by removing the snap clip (see Figure 11-2), then pulling the connector away from the feedthrough. Set the transmitter aside.
Show 4 more labels / short text on this page
Transmitter housing cover · Transmitter · housing · Clamp
Page 135 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-8 Nominal resistance ranges for flowmeter circuits
Page 135 · click to enlarge
Page 135

Troubleshooting

Figure 11-3 Accessing the feedthrough pins

Measurement Performance Defaults Troubleshooting Compensation

Emerson Process Management Micro Motion 2400S — Troubleshooting diagram (page 135)
Fig. 13 · Troubleshooting
Emerson Process Management Micro Motion 2400S — Troubleshooting diagram (page 135)
Fig. 14 · Troubleshooting

Feedthrough connector Snap clip (assembled) Pull tab to remove Feedthrough pins

6. Using a digital multimeter (DMM), check the sensor internal resistances for each flowmeter circuit. Table 11-8 defines the flowmeter circuits and the resistance range for each. Refer to Figure 11-4 to identify the feedthrough pins. For each circuit, place the DMM leads on the pin pairs and record the values.

In this test:

  • There should be no open circuits, i.e., no infinite resistance readings.
  • Nominal resistance values vary 40% per 100 °C. However, confirming an open or shorted circuit is more important than any slight deviation from the resistance values shown here.
  • The LPO and RPO circuit readings should be the same or very close (± 10%).
  • The readings across pin pairs should be steady.
  • Actual resistance values depend on the sensor model and date of manufacture. Contact Micro Motion for more detailed data.

If a problem appears, or if any resistance is out of range, contact Micro Motion (see Section 11.3).

Table 11-8 Nominal resistance ranges for flowmeter circuits

Circuit Pin pairs Nominal resistance range (1)

Drive Drive + and – 8–1500 Ω

Left pickoff Left pickoff + and – 16–1000 Ω

Right pickoff Right pickoff + and – 16–1000 Ω

Transmitter

Page 136 of the Emerson Process Management Micro Motion 2400S user manual — RTD +
Page 136 · click to enlarge
Page 136

Troubleshooting

Table 11-8 Nominal resistance ranges for flowmeter circuits continued

Circuit Pin pairs Nominal resistance range (1)

Flow tube temperature sensor RTD + and RTD – 100 Ω at 0 °C + 0.38675 Ω / °C

LLC/RTD

  • T-Series sensors RTD – and composite RTD 300 Ω at 0 °C + 1.16025 Ω / °C
  • CMF400 I.S. sensors RTD – and fixed resistor 39.7–42.2 Ω
  • F300 sensors RTD – and fixed resistor 44.3–46.4 Ω
  • All other sensors RTD – and LLC 0

(1) Actual resistance values depend on the sensor model and date of manufacture. Contact Micro Motion for more detailed data.

Figure 11-4 Feedthrough pins

Drive – Drive +

Return for RTD, LLC, composite RTD, or fixed resistor

LLC / Composite RTD / Fixed resistor(1)

RTD +

(1) Lead length compensator (LLC) for all sensors except T-Series, CMF400 I.S., and F300. For T-Series sensors, functions

as composite RTD. For CMF400 I.S. and F300 sensors, functions as fixed resistor.

7. Using the DMM, check each pin as follows:

a. Check between the pin and the sensor case.

b. Check between the pin and other pins as described below:

  • Drive + against all other pins except Drive –
  • Drive – against all other pins except Drive +
  • Left pickoff + against all other pins except Left pickoff –
  • Left pickoff – against all other pins except Left pickoff +
  • Right pickoff + against all other pins except Right pickoff –
  • Right pickoff – against all other pins except Right pickoff +
  • RTD + against all other pins except RTD – and LLC/RTD
  • RTD – against all other pins except RTD + and LLC/RTD
  • LLC/RTD against all other pins except RTD + and RTD –
Show 4 more labels / short text on this page
Left pickoff – · Right pickoff + · Left pickoff + · Right pickoff –
Page 137 of the Emerson Process Management Micro Motion 2400S user manual — Table 11-9 Sensor and cable short to case causes and remedies
Page 137 · click to enlarge
Page 137

Troubleshooting

With the DMM set to its highest range, there should be infinite resistance on each lead. If there is any resistance at all, there is a short to case or a short between pins. See Table 11-9 for possible causes and solutions. If the problem is not resolved, contact Micro Motion (see Section 11.3).

Measurement Performance Defaults Troubleshooting Compensation

Table 11-9 Sensor and cable short to case causes and remedies

Cause Possible remedy

Moisture inside the transmitter housing • Make sure that the transmitter housing is dry and no corrosion is present.

Liquid or moisture inside the sensor case • Contact Micro Motion. See Section 11.3.

Internally shorted feedthrough (sealed passage for wiring from sensor to transmitter)

  • Contact Micro Motion. See Section 11.3.

Faulty cable connecting sensor to transmitter • Visually inspect the cable for damage. To replace cable, contact Micro Motion. See Section 11.3.

To return to normal operation:

1. Follow appropriate procedures to ensure that reconnecting the transmitter does not interfere with existing measurement and control loops.
2. Reach inside the transmitter housing and install the transmitter’s sensor connection onto the feedthrough:

a. Rotate the connector until it engages the pins.

b. Push down until the connector shoulder is flush with the feedthrough notch.

c. Replace the snap clip by sliding the clip tab over the connector shoulder (see instruction label).

3. Replace the transmitter in the transmitter housing, and tighten the screws.
4. Plug the user interface module onto the transmitter. There are four possible positions; select the position that is most convenient.
5. Tighten the user interface screws.
6. Replace the transmitter housing cover on the user interface module, and tighten the screws.
7. Reinsert the DeviceNet cable into the DeviceNet connector on the transmitter.
Page 138 of the Emerson Process Management Micro Motion 2400S user manual — 11.20 Checking sensor circuitry
Page 138 · click to enlarge
Page 138
Page 138 of the Emerson Process Management Micro Motion 2400S user manual — 11.20 Checking sensor circuitry
Page 139 of the Emerson Process Management Micro Motion 2400S user manual — Table A-1 Transmitter default values and ranges
Page 139 · click to enlarge
Page 139

Appendix A Default Values and Ranges

Measurement Performance Defaults Troubleshooting Compensation

A.1 Overview

This appendix provides information on the default values for most transmitter parameters. Where appropriate, valid ranges are also defined.

These default values represent the transmitter configuration after a master reset. Depending on how the transmitter was ordered, certain values may have been configured at the factory.

A.2 Most frequently used defaults and ranges

The table below contains the default values and ranges for the most frequently used transmitter settings.

Table A-1 Transmitter default values and ranges

Type Setting Default Range Comments

Flow Flow direction Forward

Flow damping 0.64 sec 0.0–40.96 sec User-entered value is corrected to nearest lower value in list of preset values. For gas applications, Micro Motion recommends a minimum value of 2.56.

Flow calibration factor 1.00005.13 For T-Series sensors,this value represents the FCF and FT factors concatenated. See Section 6.2.2.

Mass flow units g/s

Mass flow cutoff 0.0 g/s Recommended setting is 5% of the sensor’s rated maximum flowrate.

Volume flow type Liquid volume

Volume flow units L/s

Volume flow cutoff 0/0 L/s 0.0–x L/s x is obtained by multiplying the flow calibration factor by 0.2, using units of liters per second.

Meter factors Mass factor 1.00000

Density factor 1.00000

Volume factor 1.00000

Page 140 of the Emerson Process Management Micro Motion 2400S user manual — D4 0.00000
Page 140 · click to enlarge
Page 140

Default Values and Ranges

Table A-1 Transmitter default values and ranges continued

Type Setting Default Range Comments

Density Density damping 1.28 sec 0.0–40.96 sec User-entered value is corrected to nearest value in list of preset values.

Density units g/cm3

Density cutoff 0.2 g/cm3 0.0–0.5 g/cm3

D1 0.00000

D2 1.00000

K1 1000.00

K2 50,000.00

FD 0.00000

Temp Coefficient 4.44

Slug flow Slug flow low limit 0.0 g/cm3 0.0–10.0 g/cm3

Slug flow high limit 5.0 g/cm3 0.0–10.0 g/cm3

Slug duration 0.0 sec 0.0–60.0 sec

Temperature Temperature damping 4.8 sec 0.0–38.4 sec User-entered value is corrected to nearest lower value in list of preset values.

Temperature units Deg C

Temperature calibration factor 1.00000T0.0000

Pressure Pressure units PSI

Flow factor 0.00000

Density factor 0.00000

Cal pressure 0.00000

T-Series sensor D3 0.00000

D4 0.00000

K3 0.00000

K4 0.00000

FTG 0.00000

FFQ 0.00000

DTG 0.00000

DFQ1 0.00000

DFQ2 0.00000

Events 1–5 Type Low

Setpoint 0.0

Setpoint units g/cm3

Variable Density

Page 141 of the Emerson Process Management Micro Motion 2400S user manual — Type Setting Default Range Comments
Page 141 · click to enlarge
Page 141

Default Values and Ranges

Table A-1 Transmitter default values and ranges continued

Type Setting Default Range Comments

Measurement Performance Defaults Troubleshooting Compensation Measurement Performance Defaults Troubleshooting Compensation Measurement Performance Defaults Troubleshooting Compensation Measurement Performance Defaults Troubleshooting Compensation

Display Backlight on/off On

Backlight intensity 63 0–63

Update period 200 milliseconds 100–10,000 milliseconds

Variable 1 Mass flow rate

Variable 2 Mass total

Variable 3 Volume flow rate

Variable 4 Volume total

Variable 7 Drive gain

Display totalizer start/stop Disabled

Display totalizer reset Disabled

Display auto scroll Disabled

Display offline menu Enabled

Display offline password Disabled

Display alarm menu Enabled

Display acknowledge all alarms

Auto scroll rate 10 sec

Fault timeout 0 seconds 0.0–60.0 sec

Modbus ASCII support Enabled

IrDA port enabled/disabled Disabled

IrDA port write-protect Disabled

Floating-point byte order 3–4–1–2

Show 8 more labels / short text on this page
Variable 5 Density · Variable 6 Temperature · Variable 8–15 None · Enabled · Offline password 1234 · Digital communi- cations · Fault action None · Modbus address 1
Page 142 of the Emerson Process Management Micro Motion 2400S user manual — Default Values and Ranges
Page 142 · click to enlarge
Page 142
Page 142 of the Emerson Process Management Micro Motion 2400S user manual — Default Values and Ranges
Page 143 of the Emerson Process Management Micro Motion 2400S user manual — B.2 Version information
Page 143 · click to enlarge
Page 143

Appendix B Menu Flowcharts

Device Profile Index Display Codes Menus

B.1 Overview

This appendix provides the following menu flowcharts for the Model 2400S DN transmitter:

  • ProLink II menus

- Main menu – see Figure B-1

- Configuration menu – see Figures B-2 and B-3

  • Display menus
- Off-line menuTop level – see Figure B-4
- Off-line maintenanceVersion information – see Figure B-5
- Off-line maintenanceConfiguration – see Figure B-6
- Off-line maintenanceZero – see Figure B-7
- Off-line maintenanceMeter verification – see Figure B-8

For information on the codes and abbreviations used on the display, see Appendix D.

B.2 Version information

These menu flowcharts are based on:

  • Transmitter software v1.0
  • ProLink II v2.5

Menus may vary slightly for different versions of these components.

Page 144 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 144 · click to enlarge
Page 144

Menu Flowcharts

Figure B-1 ProLink II main menu

Load from Xmtr to File Save to Xmtr from File

Connect to Device Disconnect

Options · ProLink II Language · Error Log On

Preferences · Use External Temperature · Enable Inventory Totals Reset · Enable External Pressure Compensation · Copper RTD

Configuration Process Variables Status Alarm Log Diagnostic Information Calibration Test ED Totalizer Control(2)

Totalizer Control Core Processor Diagnostics API Process Variables(3)

(1) For information about using the data logging

function, see the ProLink II manual. (2) Available only if the enhanced density

ED Process Variables(2)

application is installed. (3) Available only if the petroleum measurement

application is installed.

Show 7 more labels / short text on this page
File · View Connection · Tools Plug-ins ProLink · Meter Verification · License · Data Logging(1) · Installed options
Page 145 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 145 · click to enlarge
Page 145

Menu Flowcharts

Figure B-2 ProLink II configuration menu

Device Profile Index Display Codes Menus

· Flow direction · Flow damp · Flow cal · Mass flow cutoff · Mass flow units · Vol flow cutoff(1)

· Density units · Density damping · Slug high limit · Slug low limit · Slug duration · Low density cutoff · K1 · K2 · FD · D1 · D2 · Temp coeff (DT)

· Temp units · Temp cal factor · Temp damping · External temperature

· Flow factor · Dens factor · Cal pressure · Pressure units · External pressure

· Vol flow units(1)

· Vol flow type · Std gas vol flow cutoff(2)

· Std gas flow units(2)

· Std gas density(2)

· Mass factor · Dens factor · Vol factor

· Sensor s/n · Sensor model num · Sensor matl · Liner matl · Flange

Mass flow · Lower sensor limit · Upper sensor limit · Min span

· FTG · FFQ · DTG · DFQ1 · DFQ2 · K3 · D3 · D4 · K4

· Tag · Date · Descriptor · Message · Floating pt ordering · Add comm resp delay · Transmitter serial #

Volume flow · Lower sensor limit · Upper sensor limit · Min span

Digital comm settings · Fault setting · Modbus address · Disable Modbus ASCII · Enable IrDA comm · Enable write protect IrDA port

Density · Lower sensor limit · Upper sensor limit · Min span

Temperature · Lower sensor limit · Upper sensor limit · Min span

Last measured value timeout

(1) Displayed only if Vol Flow Type is set to Liquid Volume. (2) Displayed only if Vol Flow Type is set to Standard Gas Volume. (3) All values on this panel are read-only, and are displayed only for informational purposes.

Show 11 more labels / short text on this page
ProLink > Configuration · Flow · Density · Temperature · Pressure · Additional configuration options · Gas wizard(2) · Sensor · Sensor Limits(3) · T Series · Device
Page 146 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 146 · click to enlarge
Page 146

Menu Flowcharts

Figure B-3 ProLink II configuration menu continued

· Var1 · Var2 · … · Var 15

· Meter fingerprinting · Cryogenic modulus compensation · Meter verification

· Alarm · Severity

Mass flow · Wave form · Fixed value · Period · Minimum · Maximum

Display precision · Var · Number of decimals

Display options · Display start/stop totalizers · Display totalizer reset · Display auto scroll · Display offline menu · Display offline password · Display alarm menu · Display ack all alarms · Display back light on/off

Density · Wave form · Fixed value · Period · Minimum · Maximum

· Event name · Event type · Process variable · Low setpoint · High setpoint

· Start sensor zero · Reset mass total · Reset volume total · Reset all totals · Start/stop all totalization · Reset gas standard volume total · Reset API reference volume total · Reset ED reference volume total · Reset ED net mass total · Reset ED net volume total · Increment current ED curve

Temperatuare · Fixed value · Period · Minimum · Maximum

· Offline password · Auto scroll rate · Update period · Backlight intensity

· Table type · Units

Global config · Active curve · Derived variable · Lock/unlock ED curves

Process fluid density at specified temperature and concentration · Curve being configured · Curve fit max order · Temperature isotherms · Concentration

Curve specific config · Curve configured · Curve name · Reference temperature · Water reference temperature · Water reference density · Trim slope · Trim offset

Curve fit results · Accuracy

Process fluid density at reference temperature and specified concentration · Reference temperature · Concentration

Extrapolation · Alarm limit · Enable density low · Enable density high · Enable temperature low · Enable temperature high

(1) Used to assign events to actions, even though the

Model 2400S DN transmitter does not provide a discrete input. (2) Available only if the petroleum measurement

Concentration · Units · Special unit string

application is installed. (3) Available only if the enhanced density application is

installed.

Show 12 more labels / short text on this page
ProLink > Configuration · Display · Transmitter options · Alarm · Sensor simulation · Enable simulation mode · Discrete events · Discrete input(1) · · Display language · API setup(2) · ED setup(3) · ED curve(3)
Page 147 of the Emerson Process Management Micro Motion 2400S user manual — Figure B-5 Display menu – Off-line maintenance – Version information
Page 147 · click to enlarge
Page 147

Menu Flowcharts

Figure B-4 Display menu – Off-line menu, top level

Emerson Process Management Micro Motion 2400S — Menu Flowcharts diagram (page 147)
Fig. 15 · Menu Flowcharts

Device Profile Index Display Codes Menus

(1) This option is displayed only if the meter verification software is installed on the transmitter.

Figure B-5 Display menu – Off-line maintenance – Version information

Emerson Process Management Micro Motion 2400S — Figure B-5 Display menu – Off-line maintenance – Version information diagram (page 147)
Fig. 16 · Figure B-5 Display menu – Off-line maintenance – Ver…

(1) The option is displayed only if the

corresponding Engineering To Order (ETO) or application is installed on the transmitter.

Page 148 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 148 · click to enlarge
Page 148

Menu Flowcharts

Figure B-6 Display menu – Off-line maintenance – Configuration

Emerson Process Management Micro Motion 2400S — Menu Flowcharts diagram (page 148)
Fig. 17 · Menu Flowcharts

(1) Either Vol or GSV is displayed, depending on Volume Flow Type. See Section 8.2. (2) Displayed only if the petroleum measurement application is installed. (3) Displayed only if the enhanced density application is installed. (4) Displayed only if Auto Scroll is enabled. (5) Displayed only Off-Line Password is enabled.

Page 149 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 149 · click to enlarge
Page 149

Menu Flowcharts

Figure B-7 Display menu – Off-line maintenance – Zero

Emerson Process Management Micro Motion 2400S — Menu Flowcharts diagram (page 149)
Fig. 18 · Menu Flowcharts

Device Profile Index Display Codes Menus

Page 150 of the Emerson Process Management Micro Motion 2400S user manual — Menu Flowcharts
Page 150 · click to enlarge
Page 150

Menu Flowcharts

Figure B-8 Display menu – Off-line maintenance – Meter verification

Emerson Process Management Micro Motion 2400S — Menu Flowcharts diagram (page 150)
Fig. 19 · Menu Flowcharts

(1) Either Unstable Flow or Unstable Drive Gain may be

displayed, indicating that the standard deviation of the flow or drive gain is outside limits. Check the process and retry the procedure. (2) Represents the percentage completion of the

x%(2) UNSTABLE FLOW(1)

Page 151 of the Emerson Process Management Micro Motion 2400S user manual — C.1 Overview
Page 151 · click to enlarge
Page 151

Appendix C Device Profile

Device Profile Index Display Codes Menus

C.1 Overview

This appendix documents the most commonly used portions of the Model 2400S DN transmitter’s device profile, including class/instance/attribute information and required codes.

The following object classes and instances are documented:

  • Analog Input Point Object (0x0A), Instance 1 (mass flow) – see Table C-1
  • Analog Input Point Object (0x0A), Instance 2 (liquid volume flow) – see Table C-2
  • Analog Input Point Object (0x0A), Instance 3 (density) – see Table C-3
  • Analog Input Point Object (0x0A), Instance 4 (temperature) – see Table C-4
  • Gas Standard Volume Object (0x64), Instance 1 – see Table C-5
  • Calibration Object (0x65), Instance 1 – see Table C-6
  • Diagnostics Object (0x66), Instance 1 – see Table C-7
  • Sensor Information Object (0x67), Instance 1 – see Table C-8
  • Local Display Object (0x68), Instance 1 – see Table C-9
  • API Object (0x69), Instance 1 – see Table C-10
  • Enhanced Density Object (0x6A), Instance 1 – see Table C-11

The following codes are documented:

  • Totalizer and inventory measurement unit codes – see Tables C-12 through C-14
  • Process variable codes – see Table C-15
  • Alarm index codes – see Table C-16

For measurement unit codes used for process variables, see Section 6.3.

For complete documentation of the device profile, see the manual entitled Micro Motion Model 2400S Transmitters for DeviceNet: Device Profile.

Page 152 of the Emerson Process Management Micro Motion 2400S user manual — Device Profile
Page 152 · click to enlarge
Page 152

Device Profile

C.2 Analog Input Point Object (0x0A)

Table C-1 Analog Input Point Object (0x0A) – Instance 1 (mass flow)

Attrib ID Name Data type Service Mem Description Comments

3 Value REAL Get V Current value of mass flow process variable

Based on Attribute 8

  • 4 Status BOOL Get V Point status
  • 0 = Good
  • 1 = Alarm state

8 Value data type USINT Get V Data type used to report mass flow process variable

  • 1 = REAL

100 Process total REAL Get Reset(1)

V Current value of mass total

101 Inventory total REAL Get Reset(2)

V Current value of mass inventory

102 Value engineering units

UINT Set NV Mass flow measurement unit

See Table 6-2 for unit codes.

103 Total engineering units

UINT Get V Mass total and inventory units

Transmitter automatically determines this based on Attribute 102. See Table C-12 for unit codes.

  • 104 Damping REAL Set NV Flow damping value
  • Unit = seconds
  • Applied to both mass flow and liquid volume flow

105 Cutoff REAL Set NV Value below which mass flow will be reported as 0

106 Meter factor REAL Set NV A multiplier to the calculated mass flow

107 Flow direction USINT Set NV Determines how flow direction affects reported flow rate and flow totals

  • 0 = Forward only
  • 1 = Reverse only
  • 2 = Bidirectional
  • 3 = Absolute value
  • 4 = Negate/forward only
  • 5 = Negate/ bidirectional

108 Reset mass total USINT Set V Resets the mass total • 1 = Reset

109 Reset mass inventory

USINT Set V Resets the mass inventory

  • 1 = Reset

(1) Service code 0x4B.

(2) Service code 0x4C.

Page 153 of the Emerson Process Management Micro Motion 2400S user manual — 1 (REAL)
Page 153 · click to enlarge
Page 153

Device Profile

Table C-2 Analog Input Point Object (0x0A) – Instance 2 (liquid volume flow)

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

3 Value REAL Get V Current value of liquid volume flow process variable

Based on Attribute 8

  • 4 Status BOOL Get V Point status
  • 0 = Good
  • 1 = Alarm state

8 Value data type USINT Get V Data type used to report volume flow process variable

1 (REAL)

100 Process total REAL Get Reset(1)

V Current value of liquid volume total

101 Inventory total REAL Get Reset(2)

V Current value of liquid volume inventory

102 Value engineering units

UINT Set NV Liquid volume flow measurement unit

See Table 6-3 for unit codes.

103 Total engineering units

UINT Get V Liquid volume total and inventory units

Transmitter automatically determines this based on Attribute 102. See Table C-13 for unit codes.

105 Cutoff REAL Set NV Value below which liquid volume flow will be reported as 0

106 Meter factor REAL Set NV A multiplier to the calculated liquid volume flow

108 Reset volume total

USINT Set V Resets the volume total • 1 = Reset

109 Reset volume inventory

USINT Set V Resets the volume inventory

  • 1 = Reset

(1) Service code 0x4B.

(2) Service code 0x4C.

Table C-3 Analog Input Point Object (0x0A) – Instance 3 (density)

Attrib ID Name Data type Service Mem Description Comments

3 Value REAL Get V Current value of density process variable

Based on Attribute 8

  • 4 Status BOOL Get V Point status
  • 0 = Good
  • 1 = Alarm state

8 Value data type USINT Get V Data type used to report density process variable

1 (REAL)

102 Value engineering units

UINT Set NV Density measurement unit See Table 6-5 for unit codes.

Page 154 of the Emerson Process Management Micro Motion 2400S user manual — C.3 Gas Standard Volume Object (0x64)
Page 154 · click to enlarge
Page 154

Device Profile

Table C-3 Analog Input Point Object (0x0A) – Instance 3 (density) continued

Attrib ID Name Data type Service Mem Description Comments

104 Damping REAL Set NV Density damping value Unit = seconds

105 Cutoff REAL Set NV Value below which density will be reported as 0

106 Meter factor REAL Set NV A multiplier to the calculated density

Table C-4 Analog Input Point Object (0x0A) – Instance 4 (temperature)

Attrib ID Name Data type Service Mem Description Comments

3 Value REAL Get V Current value of temperature process variable

Based on Attribute 8

  • 4 Status BOOL Get V Point status
  • 0 = Good
  • 1 = Alarm state

8 Value data type USINT Get V Data type used to report mass flow process variable

  • 1 = REAL

102 Value engineering units

UINT Set NV Temperature measurement unit

See Table 6-6 for unit codes.

104 Damping REAL Set NV Temperature damping value

C.3 Gas Standard Volume Object (0x64)

Table C-5 Gas Standard Volume Object (0x64) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Gas standard volume flow

REAL Get V Current value of gas standard volume flow process variable

2 Gas standard volume total

REAL Get Reset(1) V Current value of gas standard volume total

3 Gas standard volume inventory

REAL Get Reset(2) V Current value of gas standard volume inventory

REAL Set NV Reference density of gas being measured

5 Gas standard volume flow units

UINT Set NV Gas standard volume flow measurement unit

See Table 6-4 for unit codes.

6 Gas standard volume total and inventory units

UINT Get V Gas standard volume total and inventory units

Transmitter automatically determines this based on Attribute 102. See Table C-14 for unit codes.

Unit = seconds · 4 Reference density

Page 155 of the Emerson Process Management Micro Motion 2400S user manual — C.4 Calibration Object (0x65)
Page 155 · click to enlarge
Page 155

Device Profile

Table C-5 Gas Standard Volume Object (0x64) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

7 Enable gas standard volume

BOOL Set NV Enable or disable gas standard volume measurement(3)

  • 0 = Disabled
  • 1 = Enabled

8 Gas standard volume low flow cutoff

REAL Set NV Value below which gas standard volume flow will be reported as 0

9 Reset gas standard volume total

USINT Set V Resets the gas standard volume total

  • 1 = Reset

10 Reset gas standard volume inventory

USINT Set V Resets the gas standard volume inventory

  • 1 = Reset

(1) Service code 0x4B. (2) Service code 0x4C. (3) If gas standard volume measurement is enabled, liquid volume measurement is disabled, and vice versa.

C.4 Calibration Object (0x65)

Table C-6 Calibration Object (0x65) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Flow calibration factor

REAL Set NV 6-character flow calibration factor

2 Temperature coefficient for flow

REAL Set NV 4-character temperature coefficient

3 Zero time UINT Set V Duration of the zero calibration procedure

4 Zero standard deviation

REAL Get NV The standard deviation result of the zero calibration service

5 Zero offset REAL Set NV The offset result of the zero calibration service

6 Calibration failed value

REAL Get V The value of the calibration parameter if one of the calibration services fails

7 K1 REAL Set NV Density calibration constant 1

8 K2 REAL Set NV Density calibration constant 2

9 FD REAL Set NV Flowing density calibration constant

10 K3 REAL Set NV Density calibration constant 3

11 K4 REAL Set NV Density calibration constant 4

12 D1 REAL Set NV The line-condition density of D1 calibration service

Unit = g/cm3

Show 6 more labels / short text on this page
Unit = seconds · Unit = milliseconds · Unit = milliseconds · Unit = milliseconds · Unit = milliseconds · Unit = milliseconds
Page 156 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 156 · click to enlarge
Page 156

Device Profile

Table C-6 Calibration Object (0x65) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

13 D2 REAL Set NV The line-condition density of D2 calibration service

Unit = g/cm3

14 FD REAL Set NV The line-condition density of FD calibration service

Unit = g/cm3

15 D3 REAL Set NV The line-condition density of D3 calibration service

Unit = g/cm3

16 D4 REAL Set NV The line-condition density of D4 calibration service

Unit = g/cm3

17 Density temperature coefficient

REAL Set NV The DT or TC calibration factor

18 FTG REAL Set NV T-Series: flow TG coefficient

19 FFQ REAL Set NV T-Series: flow FQ coefficient

20 DTG REAL Set NV T-Series: density TG coefficient

21 DFQ1 REAL Set NV T-Series: density FQ coefficient #1

22 DFQ2 REAL Set NV T-Series: density FQ coefficient #2

REAL Set NV Temperature offset

REAL Set NV Temperature slope

25 Enable temperature comp

BOOL Set NV Enable or disable temperature compensation

  • 0 = Disabled
  • 1 = Enabled

REAL Set V The external temperature value from output assembly instance 51 or 52

27 Enable pressure compensation

BOOL Set NV Enable or disable pressure compensation

  • 0 = Disabled
  • 1 = Enabled

REAL Set V The external pressure value from output assembly instance 50 or 52

29 Pressure units UINT Set NV Units used by external pressure input

See Table 6-7 for unit codes.

30 Pressure factor flow

REAL Set NV The pressure correction factor for flow

31 Pressure factor density

REAL Set NV The pressure correction factor for density

32 Flow cal pressure

REAL Set NV The flow calibration pressure

Show 4 more labels / short text on this page
23 Temperature offset · 24 Temperature slope · 26 External temperature · 28 External pressure
Page 157 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 157 · click to enlarge
Page 157

Device Profile

C.5 Diagnostics Object (0x66)

Table C-7 Diagnostics Object (0x66) – Instance 1

Device Profile Index Display Codes Menus

Attrib ID Name Data type Service Mem Description Comments

1 Fault behavior USINT Set NV Specifies the behavior of the process variables when the device is in a fault state

  • 0 = Upscale
  • 1 = Downscale
  • 2 = Zero
  • 3 = NAN
  • 4 = Flow goes to zero
  • 5 = None

2 Fault timeout USINT Set NV The amount of time after a fault ocurrs before the fault behavior (Attribute 1) is implemented

3 Slug time REAL Set NV The amount of time the density is outside the slug low limit and slug high limit before a slug flow condition is declared

4 Slug low limit REAL Set NV The lower limit of a slug flow condition

Unit = g/cm3

5 Slug high limit REAL Set NV The upper limit of a slug flow condition

Unit = g/cm3

6 Discrete event index

USINT Set V The index of the discrete event that is being configured. There are 5 discrete events with the index starting at 0.

0, 1, 2, 3, 4

7 Discrete event type

USINT Set NV The type of the selected discrete event

  • 0 = Greater than Setpoint A
  • 1 = Less than Setpoint A
  • 2 = In Range (A=< x <=B)
  • 3 = Out of Range (A>= x or B<= x )

8 Discrete event Setpoint A

REAL Set NV Setpoint A of the selected discrete event

9 Discrete event Setpoint B

REAL Set NV Setpoint B of the selected discrete event

10 Discrete event process variable

USINT Set NV The process variable on which the selected discrete event is defined

See Table C-15 for process variable codes. All codes are valid except for 52 (Input voltage).

11 Discrete event status

USINT Get V Each bit contains the status of the corresponding discrete event:

  • 0x01 = Event 0
  • 0x02 = Event 1
  • 0x04 = Event 2
  • 0x08 = Event 3
  • 0x10 = Event 4
  • 0 = Inactive
  • 1 = Active

Unit = seconds · Unit = seconds

Page 158 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 158 · click to enlarge
Page 158

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

  • 12 Alarm status 1 UINT Get V A collection of status bits
  • 0x0001 = NV error (CP)
  • 0x0002 = RAM error (CP)
  • 0x0004 = RTI failure
  • 0x0008 = Sensor failure
  • 0x0010 = Temperature out of range
  • 0x0020 = Calibration failed
  • 0x0040 = Other failure
  • 0x0080 = Transmitter initializing
  • 0x0100 = Not used
  • 0x0200 = Not used
  • 0x0400 = Simulation mode On
  • 0x0800 = Not used
  • 0x1000 = Watchdog error
  • 0x2000 = Not used
  • 0x4000 = Not used
  • 0x8000 = Fault
  • 13 Alarm status 2 UINT Get V A collection of status bits
  • 0x0001 = Not used
  • 0x0002 = Not used
  • 0x0004 = Not used
  • 0x0008 = Not used
  • 0x0010 = Density out of range
  • 0x0020 = Drive out of range
  • 0x0040 = CEM communications error
  • 0x0080 = Not used
  • 0x0100 = Non-volatile memory error (CP)
  • 0x0200 = RAM error (CP)
  • 0x0400 = Sensor failure
  • 0x0800 = Temperature out of range
  • 0x1000 = Input out of range
  • 0x2000 = Not used
  • 0x4000 = Transmitter not characterized
  • 0x8000 = RTI failure
Page 159 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 159 · click to enlarge
Page 159

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

  • 14 Alarm status 3 UINT Get V A collection of status bits
  • 0x0001 = Not used
  • 0x0002 = Power reset
  • 0x0004 = Transmitter initializing
  • 0x0008 = Transmitter/sensor communications fault (A28)
  • 0x0010 = Not used
  • 0x0020 = Not used
  • 0x0040 = Not used
  • 0x0080 = Transmitter/sensor communications fault (A26)
  • 0x0100 = Calibration failed
  • 0x0200 = Calibration failed: Low
  • 0x0400 = Calibration failed: High
  • 0x0800 = Calibration failed: Noisy
  • 0x1000 = Transmitter failed
  • 0x2000 = Data loss
  • 0x4000 = Calibration in progress
  • 0x8000 = Slug flow
Page 160 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 160 · click to enlarge
Page 160

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

  • 15 Alarm status 4 UINT Get V A collection of status bits
  • 0x0001 = API: Temperature out of range
  • 0x0002 = API: Density out of range
  • 0x0004 = Line RTD out of range
  • 0x0008 = Meter RTD out of range
  • 0x0010= Reverse flow
  • 0x0020 = Factory data error
  • 0x0040 = ED: bad curve
  • 0x0080 = LMV override
  • 0x0100 = ED: Extrapolation error
  • 0x0200 = Need calibration factor
  • 0x0400 = Non-volatile memory error (2700)
  • 0x0800 = RAM error (2700)
  • 0x1000= Transmitter not characterized
  • 0x2000 = Non-volatile memory error (CP)
  • 0x4000 = Non-volatile memory error (CP)
  • 0x8000 = Non-volatile memory error (CP)
  • 16 Alarm status 5 UINT Get V A collection of status bits
  • 0x0001 = Boot sector (CP)
  • 0x0002 = Not used
  • 0x0004 = Not used
  • 0x0008 = Not used
  • 0x0010 = Not used
  • 0x0020 = Not used
  • 0x0040 = Not used
  • 0x0080 = Not used
  • 0x0100 = D3 calibration in progress
  • 0x0200 = D4 calibration in progress
  • 0x0400 = Temperature slope calibration in progress
  • 0x0800 = Temperature offset calibration in progress
  • 0x1000 = FD calibration in progress
  • 0x2000 = D2 calibration in progress
  • 0x4000 = D1 calibration in progress
  • 0x8000 = Zero calibration in progress
Page 161 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 161 · click to enlarge
Page 161

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

  • 17 Alarm status 6 UINT Get V A collection of status bits
  • 0x0001 = Not used
  • 0x0002 = Not used
  • 0x0004 = Not used
  • 0x0008 = Not used
  • 0x0010 = Not used
  • 0x0020 = Not used
  • 0x0040 = Not used
  • 0x0080 = Not used
  • 0x0100 = Discrete event 0 active
  • 0x0200 = Discrete event 1 active
  • 0x0400 = Discrete event 2 active
  • 0x0800 = Discrete event 3 active
  • 0x1000 = Discrete event 4 active
  • 0x2000 = Not used
  • 0x4000 = Not used
  • 0x8000 = Incorrect board type

18 Alarm index USINT Set V Used to configure or read alarm severity, or to acknowledge alarms

See Table C-16 for alarm index codes.

19 Alarm severity USINT Set NV The alarm severity of the alarm that corresponds with the alarm index

  • 0 = Ignore
  • 1 = Info
  • 2 = Fault

20 Drive gain REAL Get V The drive gain %

21 Raw tube period REAL Get V The tube frequency Unit = Hz

22 Live zero (mass flow)

REAL Get V The unfiltered value of mass flow

Configured mass flow units

23 LPO voltage REAL Get V The left pickoff voltage Unit = volts

24 RPO voltage REAL Get V The right pickoff voltage Unit = volts

REAL Get V The temperature on the board

26 Maximum electronics temperature

REAL Get V The maximum temperature of the electronics

27 Minimum electronics temperature

REAL Get V The minimum temperature of the electronics

28 Average electronics temperature

REAL Get V The average temperature of the electronics

29 Maximum sensor temperature

REAL Get V The maximum temperature of the sensor

30 Minimum sensor temperature

REAL Get V The minimum temperature of the sensor

31 Average sensor temperature

REAL Get V The average temperature of the sensor

Show 8 more labels / short text on this page
25 Board temperature · Unit = °C · Unit = °C · Unit = °C · Unit = °C · Unit = °C · Unit = °C · Unit = °C
Page 162 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 162 · click to enlarge
Page 162

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

32 9-wire cable RTD resistance

REAL Get V The resistance of the 9-wire cable Unit = ohms

33 Meter RTD resistance

REAL Get V The resistance of the meter RTD

34 Number of power cycles

UINT Get V The number of transmitter power cycles

35 Power on time Unsigned 32 Get Reset(1) V The cumlative amount of time the tranmitter has been on since the last reset (Class 0x01, Attribute 0x05)

Seconds since last reset

36 Line RTD REAL Get V The resistance of the process line RTD

37 Actual target amplitude

REAL Get V The amplitude the transmitter is attempting to drive the sensor

38 Input voltage REAL Get V The number of volts on the power input terminals

39 Drive current REAL Get V The drive current Unit = milliamps

  • 40 Alarm 7 UINT Get V A collection of status bits
  • 0x0001 = K1/FCF Combination Unrecognized
  • 0x0002 = Warming Up
  • 0x0004 = Low Power
  • 0x0008 = Tube not Full
  • 0x0010 = Meter Ver Fault
  • 0x0020 = Meter Ver Info
  • 0x0040 =UI PROM error
  • 0x0080 = Not Used
  • 0x0100 = Not Used 0x0200 = Not Used
  • 0x0400 = Not Used
  • 0x0800 = Not Used
  • 0x1000 = Not Used
  • 0x2000 = Not Used
  • 0x4000 = Not Used
  • 0x8000 = Not Used
Show 4 more labels / short text on this page
Unit = ohms · Unit = ohms · Unit = mV/HZ · Unit = volts
Page 163 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 163 · click to enlarge
Page 163

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

  • 41 Alarm 8 UINT Get V A collection of status bits
  • 0x0001 = Not used
  • 0x0002 = Not used
  • 0x0004 = Not used
  • 0x0008 = Not used
  • 0x0010 = Not used
  • 0x0020 = Not used
  • 0x0040 = Not used
  • 0x0080 = Not used
  • 0x0100 = Not used
  • 0x0200 = Not used
  • 0x0400 = Not used
  • 0x0800 = Not used
  • 0x1000 = Not used
  • 0x2000 = Not used
  • 0x4000 = Not used
  • 0x8000 = Not used

42 Alarm status USINT Set V The status of the alarm selected in Attribute 18. Write 0x00 to acknowledge the alarm selected in Attribute 18.

  • 0x00 = Acked /Cleared
  • 0x01 = Acked/Active
  • 0x10 = Not Acked/Cleared
  • 0x11 = Not Acked/Active

43 Alarm count UINT Get V The number of inactive-to- active transitions of the alarm selected in Attribute 18

44 Alarm last posted

Unsigned 32 Get V The number of seconds since the last reset that the alarm selected in Attribute 18 was posted

Seconds since last reset

45 Alarm last cleared

Unsigned 32 Get V The number of seconds since the last reset that the alarm selected in Attribute 18 was cleared

Seconds since last reset

46 Alarm history index

USINT Set V The entry in the alarm history log

Range0–49

47 Alarm history alarm number

USINT Get V The alarm number that corresponds to the alarm history entry selected in Attribute 45

1 = A001, 2 = A002, etc.

48 Alarm history alarm status changed

USINT Get V The alarm status change that corresponds to the alarm history entry selected in Attribute 45

  • 1 = Posted
  • 2 = Cleared

49 Alarm history alarm status changed timestamp

Unsigned 32 Get V The timestamp of the alarm status change that corresponds to the alarm history entry selected in Attribute 45

Seconds since last reset

54 Meter verification algorithm state

USINT Get V The current state of the meter verification routine

Page 164 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 164 · click to enlarge
Page 164

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

55 Meter verification abort code

USINT Get V The reason the meter verification routine aborted

  • 0 = No error
  • 1 = Manual abort
  • 2 = Watchdog timeout
  • 3 = Frequency drift
  • 4 = High peak drive voltage
  • 5 = High drive current standard deviation
  • 6 = High drive current mean
  • 7 = Drive loop reported error
  • 8 = High Delta T standard deviation
  • 9 = High Delta T value
  • 10 = State running
  • 11 = Verification complete
  • 12 = Wrong verification enable
  • 13 = No factory air verification
  • 14 = No factory water verification
  • 15 = Parameters not set

56 Meter verification algorithm state at abort

USINT Get V The state of the meter verification routine when it aborted

57 Meter verification percent complete

USINT Get V The progress of the meter verification routine

USINT Set NV The state of the outputs when the meter verification routine is running

  • 0 = Last value
  • 1 = Fault

58 Meter verification outputs state

59 Meter verification stiffness limit

REAL Set NV The setpoint of the stiffness limit. Represents percentage.

60 Meter verification validation counter

UINT Get NV Indicates the number of times the meter verification routine has successfully completed

61 Meter verification inlet stiffness out of limits

USINT Get V Is the inlet stiffness out of limits?

  • 0 = No
  • 1 = Yes

62 Meter verification outlet stiffness out of limits

USINT Get V Is the outlet stiffness out of limits?

  • 0 = No
  • 1 = Yes

% · Unitless

Page 165 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 165 · click to enlarge
Page 165

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

63 Meter verification – current inlet stiffness, mean

REAL Get NV The current inlet stiffness calculated as a mean

64 Meter verification – current outlet stiffness, mean

REAL Get NV The current outlet stiffness calculated as a mean

65 Meter verification – current damping, mean

REAL Get NV The current damping calculated as a mean

66 Meter verification – current inlet mass, mean

REAL Get NV The current inlet mass calculated as a mean

67 Meter verification – current outlet mass, mean

REAL Get NV The current outlet mass calculated as a mean

68 Meter verification – current inlet stiffness, SD

REAL Get NV The current inlet stiffness calculated as a standard deviation

69 Meter verification – current outlet stiffness, SD

REAL Get NV The current outlet stiffness calculated as a standard deviation

70 Meter verification – current damping, SD

REAL Get NV The current damping calculated as a standard deviation

71 Meter verification – current inlet mass, SD

REAL Get NV The current inlet mass calculated as a standard deviation

72 Meter verification – current outlet mass, SD

REAL Get NV The current outlet mass calculated as a standard deviation

73 Meter verification – current inlet stiffness, factory cal of air, mean

REAL Get NV The inlet stiffness calculated as a mean during factory calibration of air

74 Meter verification – current outlet stiffness, factory cal of air, mean

REAL Get NV The outlet stiffness calculated as a mean during factory calibration of air

75 Meter verification – current damping, factory cal of air, mean

REAL Get NV The damping calculated as a mean during factory calibration of air

Page 166 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 166 · click to enlarge
Page 166

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

76 Meter verification – current inlet mass, factory cal of air, mean

REAL Get NV The inlet mass calculated as a mean during factory calibration of air

77 Meter verification – current outlet mass, factory cal of air, mean

REAL Get NV The outlet mass calculated as a mean during factory calibration of air

78 Meter verification – current inlet stiffness, factory cal of water, mean

REAL Get NV The inlet stiffness calculated as a mean during factory calibration of water

79 Meter verification – current outlet stiffness, factory cal of water, mean

REAL Get NV The outlet stiffness calculated as a mean during factory calibration of water

80 Meter verification – current damping, factory cal of water, mean

REAL Get NV The damping calculated as a mean during factory calibration of water

81 Meter verification – current inlet mass, factory cal of water, mean

REAL Get NV The inlet mass calculated as a mean during factory calibration of water

82 Meter verification – current outlet mass, factory cal of water, mean

REAL Get NV The outlet mass calculated as a mean during factory calibration of water

Page 167 of the Emerson Process Management Micro Motion 2400S user manual — C.6 Sensor Information Object (0x67)
Page 167 · click to enlarge
Page 167

Device Profile

Table C-7 Diagnostics Object (0x66) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

83 Factory flow signal offset at zero flow

REAL Get NV The flow signal offset at zero flow when calibrated at the factory

84 Discrete event action code

USINT Set V The action that will be performed by the event specified in Attribute 85

  • 1 = Start sensor zero
  • 2 = Reset mass total
  • 3 = Reset volume total
  • 4 = Reset API volume total
  • 5 = Reset ED volume total
  • 6 = Reset ED net mass total
  • 7 = Reset ED net volume total
  • 8 = Reset all totals
  • 9 = Start/stop all totals
  • 18 = Increment ED curve
  • 21 = Reset GSV total

85 Discrete event assignment

USINT Set NV The discrete event that is assigned to the action referenced in Attribute 84

  • 57 = Discrete event 1
  • 58 = Discrete event 2
  • 59 = Discrete event 3
  • 60 = Discrete event 4
  • 61 = Discrete event 5
  • 251 = None

(1) Service code 0x4D.

C.6 Sensor Information Object (0x67)

Table C-8 Sensor Information Object (0x67) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Sensor serial number

UDINT Set NV The serial number of the sensor

2 Sensor type SHORT STRING

Get NV A string that represents the type of sensor

For example, F200, CMF025

3 Sensor type code

  • USINT Set NV The type of sensor
  • 0 = Curved tube
  • 1 = Straight tube

Unit = microseconds

Page 168 of the Emerson Process Management Micro Motion 2400S user manual — C.7 Local Display Object (0x68)
Page 168 · click to enlarge
Page 168

Device Profile

Table C-8 Sensor Information Object (0x67) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

4 Sensor material USINT Set NV The material of the sensor’s case

  • 0 = None
  • 3 = Hastelloy C-22
  • 4 = Monel
  • 5 = Tantalum
  • 6 = Titanium
  • 19 = 316L stainless steel
  • 23 = Inconel
  • 252 = Unknown
  • 253 = Special

5 Liner material USINT Set NV The material of the sensor’s liner

  • 0 = None
  • 10 = PTFE (Teflon)
  • 11 = Halar
  • 16 = Tefzel
  • 251 = None
  • 252 = Unknown
  • 253 = Special

6 Flange type USINT Set NV The type of process connection on the sensor

  • 0 = ANSI 150
  • 1 = ANSI 300
  • 2 = ANSI 600
  • 5 = PN 40
  • 7 = JIS 10K
  • 8 = JIS 20K
  • 9 = ANSI 900
  • 10 = Sanitary clamp fitting
  • 11 = Union
  • 12 = PN 100
  • 252 = Unknown
  • 253 = Special

C.7 Local Display Object (0x68)

Table C-9 Local Display Object (0x68) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Scroll rate USINT Set NV The rate at which each variable will be displayed

2 Backlight control BOOL Set NV Whether the backlight is on or off

  • 0 = Off
  • 1 = On

USINT Set NV The brightness of the backlight

0 (off) to 63 (full on)

4 Display variable 1 USINT Set V Displays the variable associated with the code on the local display

See Table C-15 for codes. All codes are valid except for 251 (None).

Unit = seconds · 3 Backlight intensity

Page 169 of the Emerson Process Management Micro Motion 2400S user manual — Attrib ID Name Data type Service Mem Description Comments
Page 169 · click to enlarge
Page 169

Device Profile

Table C-9 Local Display Object (0x68) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

5 Display variable 2

See Table C-15 for codes. All codes are valid. 6 Display variable 3

USINT Set NV Displays the variable associated with the code on the local display

7 Display variable 4

8 Display variable 5

9 Display variable 6

10 Display variable 7

11 Display variable 8

12 Display variable 9

13 Display variable 10

14 Display variable 11

15 Display variable 12

16 Display variable 13

17 Display variable 14

18 Display variable 15

19 Enable start/stop totals

BOOL Set NV Enable or disable the ability to start and stop totals from the local display

  • 0 = Disabled
  • 1 = Enabled

20 Enable reset totals

BOOL Set NV Enable or disable the ability to reset totals from the local display

  • 0 = Disabled
  • 1 = Enabled

21 Enable auto scroll

BOOL Set NV Enable or disable the auto scroll feature. The scroll rate is set using Attribute 1.

  • 0 = Disabled
  • 1 = Enabled

22 Enable offline menu

BOOL Set NV Enable or disable the offline menu

  • 0 = Disabled
  • 1 = Enabled

23 Enable alarm menu

BOOL Set NV Enable or disable the alarm menu

  • 0 = Disabled
  • 1 = Enabled

24 Enable ACK All alarms

BOOL Set NV Enable or disable the ability to acknowledge all the alarms at once

  • 0 = Disabled
  • 1 = Enabled

25 Enable IrDA write protect

BOOL Set NV Enable or disable the write-protect feature on the IrDA port

  • 0 = Disabled (reading and writing allowed)
  • 1 = Enabled (read only)
Page 170 of the Emerson Process Management Micro Motion 2400S user manual — C.8 API Object (0x69)
Page 170 · click to enlarge
Page 170

Device Profile

Table C-9 Local Display Object (0x68) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

26 Enable offline password

BOOL Set NV Enable or disable the password requirement to access the offline menu

  • 0 = Disabled
  • 1 = Enabled

27 Offline password UINT Set NV The offline password for entering the offline menu

28 Update period UINT Set NV The period in which the display is updated

29 Process variable index

USINT Set V The process variable in which the precision will be set in Attribute 30

See Table C-15 for codes.

30 Process variable precision

USINT Set NV The number of digits displayed to the right of the decimal point for the process variable selected with Attribute 29

31 Language USINT Set NV Display language selection

  • 0 = English
  • 1 = German
  • 2 = French
  • 3 = Katakana (1)
  • 4 = Spanish

32 Enable IrDA port USINT Set NV Enable or disable the IrDA port

  • 0 = Disabled
  • 1 = Enabled

(1) Not available in this release.

C.8 API Object (0x69)

Table C-10 API Object (0x69) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Temperature corrected density

REAL Get V Current value

2 Temperature corrected (standard) volume flow

REAL Get V Current value

3 Temperature corrected (standard) volume total

REAL Get Reset(1) V Current value

4 Temperature corrected (standard) volume inventory

REAL Get Reset(2) V Current value

5 Batch weighted average density

REAL Get V Current value

6 Batch weighted average temperature

REAL Get V Current value

Unit = milliseconds

Page 171 of the Emerson Process Management Micro Motion 2400S user manual — C.9 Enhanced Density Object (0x6A)
Page 171 · click to enlarge
Page 171

Device Profile

Table C-10 API Object (0x69) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

7 CTL REAL Get V Current value

8 API reference temperature

REAL Set NV The reference temperature to use in the API calculations

9 API thermal expansion coefficient

REAL Set NV The thermal expansion coefficient to use in the API calculations

10 API 2540 CTL table type

USINT Set NV The table type to use in the API calculations

  • 17 = Table 5A
  • 18 = Table 5B
  • 19 = Table 5D
  • 36 = Table 6C
  • 49 = Table 23A
  • 50 = Table 23B
  • 51 = Table 23D
  • 68 = Table 24C
  • 81 = Table 53A
  • 82 = Table 53B
  • 83 = Table 53D
  • 100 = Table 54C

11 Reset API reference volume total

USINT Set V Resets the API reference volume total

  • 1 = Reset

12 Reset API reference volume inventory

USINT Set V Resets the API reference volume inventory

  • 1 = Reset

(1) Service code 0x4B. (2) Service code 0x4C.

C.9 Enhanced Density Object (0x6A)

Table C-11 Enhanced Density Object (0x6A) – Instance 1

Attrib ID Name Data type Service Mem Description Comments

1 Density at reference

REAL Get V Current value

2 Density (fixed SG units)

REAL Get V Current value

3 Standard volume flow rate

REAL Get V Current value

4 Standard volume total

REAL Get Reset(1) V Current value

5 Standard volume inventory

REAL Get Reset(2) V Current value

6 Net mass flow rate

REAL Get V Current value

7 Net mass flow total

REAL Get Reset(3) V Current value

Page 172 of the Emerson Process Management Micro Motion 2400S user manual — SHORT STRING
Page 172 · click to enlarge
Page 172

Device Profile

Table C-11 Enhanced Density Object (0x6A) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

8 Net mass flow inventory

REAL Get Reset(4) V Current value

9 Net volume flow rate

REAL Get V Current value

10 Net volume flow total

REAL Get Reset(5) V Current value

11 Net volume flow inventory

REAL Get Reset(6) V Current value

12 Concentration REAL Get V Current value

13 Density (fixed Baume units)

REAL Get V Current value

  • 15 Derived variable USINT Set NV
  • 0 = None
  • 1 = Density at reference temperature
  • 2 = Specific gravity
  • 3 = Mass concentration (density)
  • 4 = Mass concentration (specific gravity)
  • 5 = Volume concentration (density)
  • 6 = Volume concentration (specific gravity)
  • 7 = Concentration (density)
  • 8 = Concentration (specific gravity)

16 Active calculation curve

USINT Set NV The number of the curve that is currently active

38 Curven ASCII string

SHORT STRING

Set NV The name of the active curve

39 Enable enhanced density application

  • BOOL Set NV
  • 0 = Disabled
  • 1 = Enabled

47 Reset standard volume total

USINT Set V Resets the standard volume total

  • 1 = Reset

48 Reset standard volume inventory

USINT Set V Resets the standard volume inventory

  • 1 = Reset

49 Reset net mass total

USINT Set V Resets the net mass total • 1 = Reset

24 characters maximum

Page 173 of the Emerson Process Management Micro Motion 2400S user manual — Table C-13 Liquid volume totalizer and liquid volume inventory measurement unit codes
Page 173 · click to enlarge
Page 173

Device Profile

Table C-11 Enhanced Density Object (0x6A) – Instance 1 continued

Attrib ID Name Data type Service Mem Description Comments

Device Profile Index Display Codes Menus

50 Reset net mass inventory

USINT Set V Resets the net mass inventory

  • 1 = Reset

51 Reset net volume total

USINT Set V Resets the net volume total

  • 1 = Reset

52 Reset net volume inventory

USINT Set V Resets the net volume inventory

  • 1 = Reset

(1) Service code 0x4B. (2) Service code 0x4F. (3) Service code 0x4C. (4) Service code 0x50. (5) Service code 0x4D. (6) Service code 0x51.

C.10 Totalizer and inventory measurement unit codes

Table C-12 Mass totalizer and mass inventory measurement unit codes

Code Description

0x2506 Short ton (2000 pounds)

0x080E Long ton (2240 pounds)

Table C-13 Liquid volume totalizer and liquid volume inventory measurement unit codes

Code Description

0x0857 Beer barrel(2)

(1) Unit based on oil barrels (42 U.S gallons).

(2) Unit based on beer barrels (31 U.S gallons).

Show 10 more labels / short text on this page
0x2501 Gram · 0x2500 Kilogram · 0x2503 Metric ton · 0x2505 Pound · 0x2E08 Gallon · 0x2E02 Liter · 0x0822 Imperial gallon · 0x2E01 Cubic meter · 0x2E0C Barrel(1) · 0x2E06 Cubic foot
Page 174 of the Emerson Process Management Micro Motion 2400S user manual — 33 API: CTL
Page 174 · click to enlarge
Page 174

Device Profile

Table C-14 Gas standard volume totalizer and gas standard volume inventory

measurement unit codes

Code Description

0x0844 Standard cubic feet

0x0845 Normal cubic meters

0x0846 Standard cubic meters

C.11 Process variable codes

Table C-15 Process variable codes

Code Description

0 Mass flow rate

5 Volume flow rate

15 APITemperature-corrected density
16 APITemperature-corrected (standard) volume flow
17 APITemperature-corrected (standard) volume total
18 APITemperature-corrected (standard) volume inventory
19 APIBatch weighted average temperature
20 APIBatch weighted average temperature
21 Enhanced densityDensity at reference temperature
22 Enhanced densityDensity (fixed SG units)
23 Enhanced densityStandard volume flow rate
24 Enhanced densityStandard volume total
25 Enhanced densityStandard volume inventory
26 Enhanced densityNet mass flow rate
27 Enhanced densityNet mass total
28 Enhanced densityNet mass inventory
29 Enhanced densityNet volume flow rate
30 Enhanced densityNet volume total
31 Enhanced densityNet volume inventory
32 Enhanced densityConcentration

33 API: CTL

Show 10 more labels / short text on this page
0x0847 Normal liter · 0x0848 Standard liter · 1 Temperature · 2 Mass total · 3 Density · 4 Mass inventory · 6 Volume total · 7 Volume inventory · 46 Tube frequency · 47 Drive gain
Page 175 of the Emerson Process Management Micro Motion 2400S user manual — C.12 Alarm index codes
Page 175 · click to enlarge
Page 175

Device Profile

Table C-15 Process variable codes continued

Code Description

Device Profile Index Display Codes Menus

49 Left pickoff amplitude

50 Right pickoff amplitude

56 Enhanced densityDensity (Baume)

62 Gas standard volume flow rate

63 Gas standard volume total

64 Gas standard volume inventory

C.12 Alarm index codes

Table C-16 Alarm index codes

Code Description

1 (E)EPROM checksum error (CP)

2 RAM error (CP)

4 Temperature sensor failure

9 Transmitter initializing/warming up

11 Zero too low

12 Zero too high

13 Zero too noisy

16 Line RTD Temperature out-of-range

17 Meter RTD temperature out-of-range

20 Incorrect sensor type (K1)

21 Invalid sensor type

22 NV error (CP)

23 NV error (CP)

24 NV error (CP)

25 Boot failure (core processor)

Show 14 more labels / short text on this page
48 Case temperature · 51 Board temperature · 52 Input voltage · 53 External pressure · 55 External temperature · 69 Live zero · 251 None · 3 Sensor failure · 5 Input overrange · 6 Not configured · 7 RTI failure · 8 Density overrange · 10 Calibration failure · 14 Transmitter failed
Page 176 of the Emerson Process Management Micro Motion 2400S user manual — Device Profile
Page 176 · click to enlarge
Page 176

Device Profile

Table C-16 Alarm index codes continued

Code Description

26 Sensor/transmitter communications error

28 Core processor exception

29 Core processor communications error

30 Invalid board type

32 Meter verification fault alarm

33 Tubes not full

43 Data loss possible

44 Calibration in progress

56 APITemperature out of limits
57 APIDensity out of limits
60 Enhanced densitybad fit
61 Enhanced densityextrapolation alarm

71 Meter verification info alarm

72 Simulation mode active

Show 5 more labels / short text on this page
27 Security breach · 31 Low power · 42 Drive overrange · 45 Slug flow · 47 Power reset
Page 177 of the Emerson Process Management Micro Motion 2400S user manual — Table D-1 Display codes used for display variables
Page 177 · click to enlarge
Page 177

Appendix D Display Codes and Abbreviations

Device Profile Index Display Codes Menus

D.1 Overview

This appendix provides information on the codes and abbreviations used on the transmitter display.

D.2 Codes and abbreviations

Table D-1 lists and defines the codes and abbreviations that are used for display variables (see Section 8.9.5 for information on configuring display variables).

Table D-2 lists and defines the codes and abbreviations that are used in the off-line menu.

Table D-1 Display codes used for display variables

Code or abbreviation Definition Comment or reference

BRD T Board temperature

EXT P External pressure

EXT T External temperature

GSV F Gas standard volume flow

GSV I Gas standard volume flow inventory

LPO_A Left pickoff amplitude

LZERO Live zero flow

MTR T Case temperature

NET M Net mass flow rate Enhanced density application only

NET V Net volume flow rate Enhanced density application only

NETMI Net mass inventory Enhanced density application only

NETVI Net volume inventory Enhanced density application only

PWRIN Input voltage Refers to power input to the core processor

Show 6 more labels / short text on this page
AVE_D Average density · AVE_T Average temperature · CONC Concentration · DGAIN Drive gain · LVOLI Volume inventory · MASSI Mass inventory
Page 178 of the Emerson Process Management Micro Motion 2400S user manual — Table D-2 Display codes used in off-line menu
Page 178 · click to enlarge
Page 178

Display Codes and Abbreviations

Table D-1 Display codes used for display variables

Code or abbreviation Definition Comment or reference

RDENS Density at reference temperature

Enhanced density application only

RPO A Right pickoff amplitude

SGU Specific gravity units

STD V Standard volume flow rate Enhanced density application only

STD V Standard volume flow rate Enhanced density application only

STDVI Standard volume inventory Enhanced density application only

Petroleum measurement application only

Petroleum measurement application only

TCORR Temperature-corrected total Petroleum measurement application only

Petroleum measurement application only

TUBEF Raw tube frequency

Table D-2 Display codes used in off-line menu

Code or abbreviation Definition Comment or reference

ACK Display Ack All menu

ACK ALARM Acknowledge alarm

ACK ALL Acknowledge all

ACT Action Action assigned to the discrete input or to a discrete event

BKLT, B LIGHT Display backlight

CH A Channel A

CH B Channel B

CHANGE PASSW Change password Change the password required for access to display functions

CUR Z Current zero

CUSTODY XFER Custody transfer

DRIVE%, DGAIN Drive gain

DISBL Disable Select to disable

Show 13 more labels / short text on this page
TCDEN Temperature-corrected density · TCORI Temperature-corrected inventory · TCVOL Temperature-corrected volume · WTAVE Weighted average · AO Analog output · ADDR Address · CAL Calibrate · CONFG Configuration · CORE Core processor · DENS Density · DI Discrete input · DO Discrete output · DSPLY Display
Page 179 of the Emerson Process Management Micro Motion 2400S user manual — Display Codes and Abbreviations
Page 179 · click to enlarge
Page 179

Display Codes and Abbreviations

Table D-2 Display codes used in off-line menu

Code or abbreviation Definition Comment or reference

Ex Event x Refers to Event 1 or Event 2 when setting the setpoint.

Device Profile Index Display Codes Menus

ENABL Enable Select to enable

EVNTx Event x

FAC Z Factory zero

FCF Flow calibration factor

FLSWT, FL SW Flow switch

GSV Gas standard volume

GSV T Gas standard volume total

MTR F Meter factor

OFF-LINE MAINT Off-line maintenance menu

OFFLN Display off-line menu

r. Revision

SrC Source Variable assignment for outputs

VOL Volume or volume flow

Show 26 more labels / short text on this page
EXTRN External · FLDIR Flow direction · FO Frequency output · FREQ Frequency · INTRN Internal · IO Inputs/outputs · IRDA Infrared · LANG Display language · M_ASC Modbus ASCII · M_RTU Modbus RTU · MAO mA output · MASS Mass flow · MBUS Modbus · MFLOW Mass flow · MSMT Measurement · POLAR Polarity · PRESS Pressure · SENSR Sensor · SIM Simulation · SPECL Special · TEMPR Temperature · VER Version · VERFY Verify · VFLOW Volume flow · WRPRO Write protect · XMTR Transmitter
Page 180 of the Emerson Process Management Micro Motion 2400S user manual — Display Codes and Abbreviations
Page 180 · click to enlarge
Page 180
Page 180 of the Emerson Process Management Micro Motion 2400S user manual — Display Codes and Abbreviations
Page 182 of the Emerson Process Management Micro Motion 2400S user manual — Table of contents
Page 182 · click to enlarge
Page 182

Table of contents

Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 183 of the Emerson Process Management Micro Motion 2400S user manual — Table of contents
Page 183 · click to enlarge
Page 183

Table of contents

Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 184 of the Emerson Process Management Micro Motion 2400S user manual — Table of contents
Page 184 · click to enlarge
Page 184

Table of contents

Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 185 of the Emerson Process Management Micro Motion 2400S user manual — Table of contents
Page 185 · click to enlarge
Page 185

Table of contents

Contentsp.3Before You Beginp.91.1 Overviewp.91.2 Safetyp.91.3 Determining transmitter informationp.91.4 DeviceNet functionalityp.101.5 Determining version informationp.101.6 Communication toolsp.101.7 Planning the configurationp.111.8 Pre-configuration worksheetp.121.9 Flowmeter documentationp.131.10 Micro Motion customer servicep.14Flowmeter Startupp.152.1 Overviewp.152.2 Setting the DeviceNet node address and baud ratep.152.3 Bringing the transmitter onlinep.15Using the Transmitter User Interfacep.173.1 Overviewp.173.2 User interface without or with displayp.173.3 Removing and replacing the transmitter housing coverp.193.4 Using the optical switchesp.193.5 Using the displayp.203.5.1 Display languagep.203.5.2 Viewing process variablesp.203.5.3 Using display menusp.213.5.4 Display passwordp.223.5.5 Entering floating-point values with the displayp.22Connecting with ProLink II or Pocket ProLink Softwarep.254.1 Overviewp.254.2 Requirementsp.254.3 Configuration upload/downloadp.254.4 Connecting to a Model 2400S DN transmitterp.264.4.1 Connection optionsp.264.4.2 Service port connection parametersp.264.4.3 Connecting via the service port clipsp.264.4.4 Connecting via the IrDA portp.284.5 ProLink II languagep.28Using a DeviceNet Toolp.295.1 Overviewp.295.2 Connecting to the Model 2400S DN transmitterp.295.3 Using the DeviceNet device profilep.295.4 Using a DeviceNet toolp.305.4.1 Type A toolsp.305.4.2 Type B toolsp.305.5 Default assembliesp.31Required Transmitter Configurationp.336.1 Overviewp.336.2 Characterizing the flowmeterp.336.2.1 When to characterizep.336.2.2 Characterization parametersp.336.2.3 How to characterizep.356.3 Configuring the measurement unitsp.366.3.1 Mass flow unitsp.386.3.2 Volume flow unitsp.386.3.3 Density unitsp.406.3.4 Temperature unitsp.416.3.5 Pressure unitsp.41Using the Transmitterp.437.1 Overviewp.437.2 Recording process variablesp.437.3 Viewing process variablesp.447.3.1 With the displayp.447.3.2 With ProLink IIp.447.3.3 With a DeviceNet toolp.457.4 Using the LEDsp.497.4.1 Using the module LEDp.497.4.2 Using the network LEDp.507.5 Viewing transmitter statusp.507.5.1 Using the status LEDp.507.5.2 Using ProLink IIp.517.5.3 Using a DeviceNet toolp.517.6 Handling status alarmsp.517.6.1 Using the displayp.527.6.2 Using ProLink IIp.537.6.3 Using a DeviceNet toolp.547.7 Using the totalizers and inventoriesp.557.7.1 Viewing current values for totalizers and inventoriesp.567.7.2 Controlling totalizers and inventoriesp.57Optional Configurationp.638.1 Overviewp.638.2 Configuring volume flow measurement for gasp.648.2.1 Using ProLink IIp.658.2.2 Using a DeviceNet toolp.668.3 Configuring cutoffsp.668.3.1 Cutoffs and volume flowp.678.4 Configuring the damping valuesp.678.4.1 Damping and volume measurementp.688.5 Configuring the flow direction parameterp.688.6 Configuring eventsp.698.6.1 Defining eventsp.698.6.2 Checking and reporting event statusp.728.6.3 Changing event setpoints from the displayp.728.7 Configuring slug flow limits and durationp.728.8 Configuring status alarm severityp.738.9 Configuring the displayp.758.9.1 Update periodp.758.9.2 Languagep.758.9.3 Enabling and disabling display functionsp.758.9.4 Configuring the LCD backlightp.768.9.5 Configuring the display variables and display precisionp.778.10 Configuring digital communicationsp.788.10.1 DeviceNet node addressp.788.10.2 DeviceNet baud ratep.798.10.3 DeviceNet configurable input assemblyp.798.10.4 Modbus addressp.808.10.5 Modbus ASCII supportp.808.10.6 IrDA port usagep.818.10.7 Digital communications fault actionp.818.10.8 Fault timeoutp.828.11 Configuring device settingsp.828.12 Configuring sensor parametersp.838.13 Configuring the petroleum measurement applicationp.838.13.1 About the petroleum measurement applicationp.838.13.2 Configuration procedurep.858.14 Configuring the enhanced density applicationp.868.14.1 About the enhanced density applicationp.868.14.2 Configuration procedurep.88Pressure Compensation and Temperature Compensationp.919.1 Overviewp.919.2 Pressure compensationp.919.2.1 Optionsp.919.2.2 Pressure correction factorsp.929.2.3 Configurationp.929.3 External temperature compensationp.939.4 Obtaining external pressure and temperature datap.95Measurement Performancep.9710.1 Overviewp.9710.2 Meter validation, meter verification, and calibrationp.9710.2.1 Meter verificationp.9810.2.2 Meter validation and meter factorsp.9810.2.3 Calibrationp.9810.2.4 Comparison and recommendationsp.9910.3 Performing meter verificationp.9910.3.1 Uncertainty limit and test resultsp.10410.3.2 Additional ProLink II tools for meter verificationp.10510.4 Performing meter validationp.10510.5 Performing zero calibrationp.10710.5.1 Preparing for zerop.10810.5.2 Zero procedurep.10810.6 Performing density calibrationp.11110.6.1 Preparing for density calibrationp.11210.6.2 Density calibration proceduresp.11210.7 Performing temperature calibrationp.117Troubleshootingp.11911.1 Overviewp.11911.2 Guide to troubleshooting topicsp.11911.3 Micro Motion customer servicep.12011.4 Transmitter does not operatep.12011.5 Transmitter does not communicatep.12011.6 Checking the communication devicep.12111.7 Diagnosing wiring problemsp.12111.7.1 Checking the DeviceNet cable and connectorp.12111.7.2 Checking groundingp.12211.8 Zero or calibration failurep.12211.9 Fault conditionsp.12211.10 Simulation mode for process variablesp.12211.11 Transmitter LEDsp.12311.12 Status alarmsp.12411.13 Checking process variablesp.12711.14 Checking slug flowp.12911.15 Checking the sensor tubesp.13011.16 Checking the flow measurement configurationp.13011.17 Checking the characterizationp.13011.18 Checking the calibrationp.13011.19 Checking the test pointsp.13011.19.1 Obtaining the test point valuesp.13111.19.2 Evaluating the test pointsp.13111.19.3 Drive gain problemsp.13211.19.4 Low pickoff voltagep.13211.20 Checking sensor circuitryp.133Default Values and Rangesp.139A.1 Overviewp.139A.2 Most frequently used defaults and rangesp.139Menu Flowchartsp.143B.1 Overviewp.143B.2 Version informationp.143Device Profilep.151C.1 Overviewp.151C.2 Analog Input Point Object (0x0A)p.152C.3 Gas Standard Volume Object (0x64)p.154C.4 Calibration Object (0x65)p.155C.5 Diagnostics Object (0x66)p.157C.6 Sensor Information Object (0x67)p.167C.7 Local Display Object (0x68)p.168C.8 API Object (0x69)p.170C.9 Enhanced Density Object (0x6A)p.171C.10 Totalizer and inventory measurement unit codesp.173C.11 Process variable codesp.174C.12 Alarm index codesp.175Display Codes and Abbreviationsp.177D.1 Overviewp.177D.2 Codes and abbreviationsp.177Indexp.181
Page 186 of the Emerson Process Management Micro Motion 2400S user manual — Index
Page 186 · click to enlarge
Page 186

Index

cutoff 58 measurement unit

configuration 30 list 30

W Wiring problems 113

Z Zero calibration 99

failure 114 procedure 100

Volume flow, liquid

Page 187 of the Emerson Process Management Micro Motion 2400S user manual — Index
Page 187 · click to enlarge
Page 187
Page 187 of the Emerson Process Management Micro Motion 2400S user manual — Index
Page 188 of the Emerson Process Management Micro Motion 2400S user manual — ©2008, Micro Motion, Inc. All rights reserved. P/N MMI-20007739, Rev. B *MMI-20007739*
Page 188 · click to enlarge
Page 188

©2008, Micro Motion, Inc. All rights reserved. P/N MMI-20007739, Rev. B *MMI-20007739*

For the latest Micro Motion product specifications, view the PRODUCTS section of our web site at www.micromotion.com

Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 +1 800-522-6277 F +1 303-530-8459

Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556

Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6777-8211 F +65 6770-8003

Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181

Micro Motion Japan Emerson Process Management 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan T +81 3 5769-6803 F +81 3 5769-6844

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson Process Management Micro Motion 2400S

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Process Management Micro Motion 2400S

Be the first to ask — other owners or our team will answer.

Original document

Emerson Process Management Micro Motion 2400S manual PDF

188 pages·2.5 MB·Satellite Radio·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…