Modular Refrigerant Leak Detection
Sensor (MRLDS) Installation and
Operation Manual





Computer Process Controls, Inc.
1640 Airport Road Suite #104 Kennesaw, GA 31044
The information contained in this manual has been carefully checked and is believed to be accurate. However, Computer Process Controls, Inc. assumes no responsibility for any inaccuracies that may be contained herein. In no event will Computer Process Controls, Inc. be liable for any direct, indirect, special, incidental, or consequential damages resulting from any defect or omission in this manual, even if advised of the possibility of such damages. In the interest of continued product development, Com- puter Process Controls, Inc. reserves the right to make improvements to this manual, and the products described herein, at any time without notice or obligation.
Computer Process Controls, Inc. products may be covered by one or more of the fol- lowing Computer Process Controls U.S. patents: 6360553, 6449968, 6378315, 6502409, 6779918, and Computer Process Controls Australian patent No. 775,199 No- vember 4, 2004.
This device complies with Part 15 of the FCC Rules. Operation is subject to the fol- lowing two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Phone 770-425-2724 · Fax 770-425-9319





CPC specs a modular refrigerant leak detection sensor (MRLDS) that continuously monitors for low levels of refrigerants most commonly used in commercial refrigera- tion systems.
The MRLDS communicates with the E2 controller via a Gateway board connected to the RS485 I/O Network, or via the analog input on a MultiFlex board.
Figure 1-1 - Sensor Base Opening With Screw Terminals
Table 1-2 - Available MRLDS Models
Table 1-3 - MRLDS Transformer Specifications
The MRLDS unit requires a separate UL Listed/CSA Certified 24VAC Class 2 transformer power supply. One 24VAC, 10VA Class 2 transformer is sufficient for up to three (3) MRLDS units.
CPC supplies several sizes of transformers for power- ing multiple MRLDS units (three or more). Note that polarity must be maintained when connecting more than one MRLDS to a single transformer.
Table 1-1 - MRLDS Unit Specifications
*De-icer: for environments below 32°F to keep ice from forming on the surface of enclosure.
Specifications Overview • 1

If a transformer is shared between MRLDS units, the “ACN” of each MRLDS must be wired to the same phase of the transformer.

120VAC 24VAC
ACN
Figure 1-2 - Powering Multiple MRLDS Units
Figure 2-1 - Sensor Base And Cover
2.1 Mounting The Sensor
The refrigeration monitor comprises two basic parts: the base and the cover. The cover incorporates the circuit board with the sensing elements.
Proper location of the refrigerant sensor is necessary to ensure accurate measurement of representative air sam- ples.
Mount the sensor:
Do not mount the sensor:
ground terminal labeled . Connect to earth ground with 14 AWG wire that is less than 6 inches.
Transformer



Figure 2-2 - Attaching and Removing Cover

Figure 3-1 - Analog MRLDS Network Layout Example
For analog MRLDS units, connect to a MultiFlex board via the analog input (use Belden 8761 cable).

INPUT 13 INPUT 14 INPUT 15 INPUT 16 1 2 3 4 5 6 7 8 0V SIG 0V SIG SIG SIG 0V 0V
be shared between MRLDS and the MultiFlex board. A
Figure 2-3 - MRLDS Mounting Dimensions
If a transformer is shared between MRLDS units, the “ACN” of each MRLDS must be wired to the same phase of the transformer.
EARTH SHIELD NEAR THE MULTIFLEX BOARD. CONNECT THE SHIELD TO THE 0V INPUT ON THE MULTIFLEX BOARD.
Wire MultiFlex SIG to MRLDS OUT(V). Wire MultiFlex 0V to MRLDS Ground ( ).
Figure 3-2 - Analog MRLDS Wiring
MRLDS Dimensions MRLDS Analog Version (809-100x) • 3

The jumper settings for refrigerant types are located on the label inside the MRLDS sensor cover (shown in Fig- ure 1-1). Set the jumpers according to how they are indi- cated on the label.
The MRLDS supports three different refrigerant types. Select the desired refrigerant type by setting one jumper to the J2 or J1 sockets (Figure 2-1) respective per the inside label.
If the device is configured and powered correctly, a value will be visible under the Value column on the Input Status screen. 3.4.2 Einstein/E2 Controllers Prior to Version 2.5
For Einstein and E2 controllers prior to version 2.5, follow the steps below, set the sensor type to Linear, and manually enter the parameters:
J2 J1
Figure 3-3 - Analog Jumper Layout (Inside Lower Portion of Cover) Enlarged To Show Detail
Table 3-1 - Refrigerant Jumper Settings
(Set the alarm failure to < -10PPM.)
If the device is configured and powered correctly, a value will be visible under the Value column on the Input Status screen.
Analog Jumpers · refrigerant type jumpers



be shared between MRLDS and the Gateway board. A
If a transformer is shared between MRLDS units, the “ACN” of each MRLDS must be wired to the same phase of the transformer.
Figure 3-4 - Analog Input Screen Settings Example for E2
For RMCC-type controllers, set the Gain parameter to 250 and Offset to -1000.
Figure 4-2 - Modbus MRLDS Wiring
Modbus network settings are set on jumpers J5, J4, and J3. Refer to Table 4-1 (also included on the inside label of the MRLDS) for network addressing with corre- sponding jumper settings.
If more than one MRLDS is on the network, each unit must have a unique address and be numbered according to the inside label (Table 4-1) specifications.


(Up to 12 MRLDS units on the network per Gateway)
Figure 4-3 - MRLDS Jumpers (Inside Lower Portion of Cover)
Figure 4-1 - Network Layout Example
Network Layout MRLDS Modbus Version (809-101x) • 5

the J2 or J1 sockets respective per the inside label.


Figure 4-4 - Modbus Jumper Layout (Inside Lower Portion of Cover) Enlarged To Show Detail

Table 4-2 - Refrigerant Jumper Settings
The MRLDS has a built-in, on-board means of termi- nation, so an external termination block is not necessary for terminating. When the device is located at the end of a daisy chain, jumper JP6 for termination.

Table 4-1 - MRLDS Modbus Address Jumper Settings
The jumper settings for refrigerant types are located on the label inside the MRLDS sensor cover (shown in Fig- ure 1-1). Set the jumpers according to how they are indi- cated on the label.
The MRLDS supports three different refrigerant types. Select the desired refrigerant type by setting one jumper to
Figure 4-5 - MRLDS Termination (Inside Lower Left of Cover)
See Table 4-3 below for Modbus registers in the MRLDS Unit. Baud rate: 19,200; each byte is 8 (eight)

bits with no parity and 2 (two) stop bits.

Figure 4-6 - I/O Network Modes
Factory Mode 4 (Lsb)
Up to 12 MRLDS units may be connected to the Gate- way board (P/N 810-3040). The Gateway board can inter- face with a site controller as a 16AI or as an IRLDS. If the site controller is an Einstein or E2, it is recommended to interface them as an IRLDS. Multiple Gateways can be used, each with up to 12 connected MRLDS units. 4.3.3 The Gateway Board
Trouble Mode 8 (Lsb)
0x0001 2 0 to 40

R-22 = 6 R-404A = 27 R-134a = 15
Modbus versions of the MRLDS must be connected to the 810-3040 MRLDS Gateway. The MRLDS Gateway can be mapped in either of two ways: it can be set up on I/O Net as an IRLDS application or as a 16AI board. Select by setting the Gateway’s dip switch #5 to the OFF or ON position (Figure 4-6).
Figure 4-7 - MRLDS Gateway Board Layout (810-3040)
MRLDS Gateway MRLDS Modbus Version (809-101x) • 7
Cal/Setup 2 (Lsb) · Gas Number



The Gateway Board communicates with the MRLDS via the Modbus network, which is connected to the Gate- way’s “Receiver Bus” network terminal. The Gateway communicates with the E2 via the RS485 I/O Network. 4.3.4 Powering the Gateway Board
Input Voltage 24VAC, Class 2, Center-Tapped 50/60Hz
Figure 4-8 - Pinout for the 56VA (640-0056) and 80VA (640- 0080) Transformers
Table 4-4 - Gateway Power Requirements
The Gateway board requires 24VAC power from a Class 2 center-tapped transformer. CPC supplies several sizes of center-tapped transformers for powering multiple 16AIs, 8ROs, and other RS485 peripheral boards.
Figure 4-8 shows how to connect the 56VA and 80VA transformers to the Gateway power connector.
Each E2, Einstein, or REFLECS site controller that will communicate with one or more MRLDS units must have a Gateway Board installed on its RS485 I/O Net- work. For Einstein controllers, this means the Gateway will be installed on the RS485 I/O Network; for RMCC, BEC, BCU, and other REFLECS products, the Gateway will be installed on the COM A or COM D network. 4.3.6 Wire Connections
Power Rating 56 VA 80 VA
Table 4-5 - Power Ratings for CPC Transformers
Using shielded three-conductor network cable (Belden #8641 or equivalent), connect the RS485 I/O Network wire to the three-terminal connector on the Gateway board as shown in Figure 4-9. For further information about how RS485 networks are configured, refer to your site
Power 5VA · Three-Board Six-Board

controller’s user manual.


Figure 4-9 - Connecting the Gateway to the E2 RS485 Network
To connect the Gateway to an MRLDS, feed the wires through the rectangular opening in the sensor base as indi- cated in Figure 1-1. Locate the RS485 connector and secure the wire leads to the connector orienting them as shown in Figure 4-10. Connect multiple MRLDS units in a daisy-chain configuration as shown in Figure 4-1.
Figure 4-11 -MRLDS Gateway Termination
Set the address on the I/O Network with switches 1-4. There can be more than one MRLDS Gateway with each supporting up to 12 MRLDS units.

Switch 5 indicates whether the MRLDS will be mapped as an IRLDS or 16AI. Set switch 5 to the OFF position for IRLDS emulation or to the ON position for 16AI emulation.

I/O NET MODE ON = 16AI OFF = IRLDS
Figure 4-10 - Connecting the Gateway to MODBUS
As part of a site controller’s RS485 I/O (COM A or COM D) Network, a Gateway must be terminated if it is the end device of a daisy chain. The Gateway on the Mod- bus Network should always be terminated and always located at the end of the daisy chain.
Refer to the site controller’s user manual for informa- tion about daisy chain networks and how they are termi- nated.
To terminate the Gateway (the Modbus jumpers should always be terminated on the Gateway), set the receiver bus jumpers to the RIGHT position (Figure 4-11).
Figure 4-12 - Network Layout Example
MRLDS Gateway MRLDS Modbus Version (809-101x) • 9

Dip switches 6 and 7 control the baud rate at which the Gateway communicates with the site controller on the RS485 Network. These switches must be set to the same baud rate setting as the controller you are using (Einstein, RMCC, or E2), and defaults to 9600 baud. Dip switch 8 controls the baud rate at which the Gateway communicates with the MRLDS. For 9600 baud, set dip switch 8 to the OFF position. For 19200 baud, set dip switch 8 to the ON position (always use 19200 baud for MRLDS).
MOD BAUD: 19200
Figure 4-15 - Baud Rate/Address Screen
The Baud Rate/Address screen displays the Gateway I/O Network address (I/O ADDR), the I/O Network baud rate between the Gateway and the E2 (I/O BAUD), and the Modbus baud rate between the Gateway and the MRLDS devices (MOD BAUD). 4.3.10.2 Select Screen
Press the down arrow again to navigate to the Select screen (or press F2). From the Select screen you can see status, setup, and firmware version information.
I/O NETWORK OR COM A AND D BAUD RATE
OFF = 9600 BAUD ON MODBUS ON = 19200 BAUD ON MODBUS ON
To select, press the right arrow until it appears next to SELECT and press 1, 2, or 3 in the list. Press the down arrow twice to move to the desired screen.
2 3 4 5 6 7 8 1
I/O NET BAUD RATE SETTINGS
1 - STATUS
ALWAYS USE 19200 BAUD WITH MRLDS
2 - SETUP/ONLINE 3 - FW REVISION
Figure 4-16 - Select Screen
Figure 4-13 - Dip Switch Settings for Gateway Baud Rate
4.3.10 Hand-Held Terminal Settings
The hand-held terminal can be used to view status information, enable unit addresses, and is connected directly to the Gateway board via the hand-held terminal jack.
Possible states (ST) are:
MRLDS GATEWAY 810-3040 VER:1.10B03 ( PRESS ) FAIL I/O NET
Figure 4-14 - MRLDS HHT Home Screen
From the HHT Home screen (F1), press the down arrow key to navigate to the Baud Rate/Address screen (Figure 4-15).
(GW to E2) · (GW to MRLDS) · 9600 19200

If there is an issue with the Gateway board, the HHT Home screen (F1) can give status indicators to report the issue. The Home screen will display a warning if there is a failure associated with the I/O Network or flash on the Gateway board. Select the HHT Status screen to view sta- tus information for each MRLDS unit.
Figure 4-17 - Status Screen
To set up communication on the I/O Network as an IRLDS application:
102:
103 104:
Figure 4-18 - Setup/Online Screen
For mapping the MRLDS unit as a 16AI board, first set dip switch #5 on the Gateway board to the ON position.
Figure 4-19 - Firmware Revision Screen
Follow Steps 1-6 above, but for Step 6 select the num- ber of 16AI boards to equal the number of MRLDS Gate-
Controller Setup for Modbus MRLDS MRLDS Modbus Version (809-101x) • 11

ways.
Navigate to the controller’s Input Status screen and highlight the board and point that you wish to map. Press F1 to go to the Input Setup screen for that board/point. Each point will increase incrementally to correspond with each board. (For example, where the MRLDS is address 1 and the MRLDS address is 100, use board 1, point 1. For an MRLDS address of 101, use point 2.) 4.4.3 E2/Einstein Controllers
Set dip switch 8 to ON and follow the steps for setting up IRLDS IIs through the REFLECS controller interface:
Next, set up the following parameters on the Input Setup screen:
Input Definitions should be set here to show how the sensor control is linked to the zone. The number of devices and IRLDS IIs are connected to the Gateway and enabled is the number of address slots the Gateway will use.

The board number for the IRLDS II setup is the address of the Gateway. If there are three or less IRLDS II control- lers connected to a Gateway, the Gateway address = the IRLDS II address. However, if there are more than three IRLDS controllers, the second Gateway address will be the one entered for the board number, but the IRLDS II con- trollers are set 1 to 3 on the second Gateway.
The Gateway will react as three 16AI boards. The num- ber of IRLDS II controllers plus the real number of 16AIs = the total number of 16AIs to enter in the next step:
Figure 4-20 - Analog Input Screen Settings Example for E2

field to change the name, and press the down or right arrow to move to the (sensor) Type field. Use the “.” and “—” keys to scroll through the options and select IRLDS. (The Gain and Offset parameters are automatically configured for you.)
Locate the screen in the BEC or RMCC where sensors are set up. This is usually a menu option in the Sensors Menu, which may be reached from the Main Menu.
The 0-4.8V signal is a linear signal representing a mea- sured concentration of 0-1200 ppm, and a voltage of 5.0V indicates a fault. In order for the REFLECS to read these voltages correctly, the REFLECS sensor inputs must be configured as linear sensors.
A name for the sensor input may be entered in the Name field. Since each IRLDS zone is set up with two REFLECS sensor inputs, choose names for each input that distinguish the input’s function. For example, the sensor input set up to read leak concentrations on zone 1 should have a name like REFR LK ZN 01, and the input set up to monitor fault sta- tus should have a name like FAULT ZN 01.

All sensor inputs connected to an IRLDS should be set up as linear sensors. Enter (L)inear in the Type field.
The logging interval is the amount of time between log entries in the REFLECS’s Data Log.
Locate the screens in the BEC or RMCC that are used to define input board and points. This is usually achieved by pressing 7 then 1 from the Main Menu. Press the DOWN ARROW key several times until the SENS01- SENS08 inputs are shown.
When choosing a logging interval, keep in mind the amount of time it takes an IRLDS to go through an entire cycle of samplings. For example, a 16-valve IRLDS with 30 second sampling times for each zone takes a total of eight minutes to sample all zones. Choosing a logging in- terval smaller than the IRLDS’s cycle time will simply clutter the REFLECS data log with multiple copies of the same sample. 4.4.5.3 Sensor Setpoints
The 16AI connected to the IRLDS’s output terminals must be set up in the REFLECS’s system software. If the 16AI was given a unique board number by setting the dip switch S3, and wired to the terminals so that each zone number corresponds to a 16AI point number (zone 01 con- nected to point 01, for example), these board and point ad- dresses must now be entered into the REFLECS.

SENSOR SETPOINTS LINEAR INPUT 12:00 #:01 Status:OFF Name:REFR LK ZN 01 Stay ON for:000 min Eng.Unit:PPM Using Diff Of 01 00 00 00 0 Of 0 Gain 250 Offset 00000 mv ON: 0 Dly: 0000 OFF:0 Dly:0000 =PREV =NEXT ->=SET-DATA 0=MENU
The screen above shows how the board and point ad- dresses for zone 1 would be set up for a 16AI board num- bered 1. Both SENS01 and SENS02 are set up as 01:01 so that SENS01 can monitor concentration and SENS02 can monitor fault status.
Set up the remaining sensors using the instructions giv- en above. For each point on the 16AI, set up two sensors with the same addresses. 4.4.5.2 Sensor Setup
Locate the screen in the BEC or RMCC where sensor set points are specified. This is usually a menu option in the Sensors Menu, which may be reached from the Main Menu.

SENSOR SETUP 12:00 #:01 Status:OFF Name:REFR LK ZN 01 Type: Linear
After the linear sensors have been set up, the REFLECS must be told how to interpret the linear voltage given by the IRLDS.
(T)mp (1)00 (5)00 (R)fLeak (K)Watt (H)um (2)00 (D)ig (L)inear L(Q)Lev (6)450 Tmp Dew(P)nt Logging Interval (HH:MM:SS): 00:03:00 =PREV =NEXT ->=SET-DATA 0=MENU
Eng. Unit
The REFLECS does not require any specific engineer- ing unit to be specified for sensor values. However, for eas- ier reading of status screens and data logs, “PPM” should be entered for sensor inputs that read concentration, and
Controller Setup for Modbus MRLDS MRLDS Modbus Version (809-101x) • 13
Name · Type · Logging Interval

“MV” should be entered for sensor inputs that read fault status.
Since the output terminals emit one volt for every 250 ppm of refrigerant detected, the gain for the refrigerant leak sensors must be set to 250 and the Offset to 0.
The sensors configured to detect faults must be given a gain of 1000; this way, the REFLECS can be set up to alarm whenever it detects a 5000 mV signal. 4.4.5.4 Alarm Setpoints
The MRLDS has three LEDs for quick status indica- tion.


Red Flashes at 0.5 Hz during start-up Turns ON solid if concentration reading exceeds 50 ppm
Yellow Flashes at 0.5 Hz if power sup- plied is outside set limits Turns ON solid during other fault conditions
Locate the screen in the BEC or RMCC where sensor alarm set points are specified. This is usually a menu option in the Sensors Menu, which may be reached from the Main Menu.
Table 5-1 - MRLDS LED Status
For analog output models, a fault is signaled by setting the voltage to 0.5V, which indicates the MRLDS should be be replaced. Call the CPC Service Department (770-425- 2724) to verify if the MRLDS unit should be replaced.
The REFLECS should now be capable of interpreting the 0-4.8V output voltage as a refrigerant concentration of 0-1200 ppm and the 5V output voltage as a fault. The de- sired alarm set points must now be specified. When set up correctly, alarms will appear in the REFLECS Alarm log as “Hi Sensor” alarms (refer to the REFLECS manual for alarm descriptions).
In this field, specify a high alarm setpoint for refriger- ant leak alarms between 0 and 1200 ppm. For fault status alarms, enter a setpoint of 4960 mV (slightly below 5V, as a precautionary measure).
If any one or all of the MRLDS sensors encounters a problem, the IRLDS application will alarm and all cell outputs will show NONE. For details on which individual unit is in alarm, go to the MRLDS Gateway and check the Status screen on the HHT. 5.2.2 16AI Mode
The value entered in the Alarms Dly field is the number of minutes the sensor reading must be above the Alarms:High set point before the REFLECS may generate a leak alarm
If an MRLDS has lost communication, the input will go to 1250 PPM, which should force an alarm if enabled. If all MRLDS sensors lose communication, the 16AI will go offline. Check the Status screen on the HHT for details.
When choosing an alarm delay, keep in mind the amount of time it takes an IRLDS to complete a sampling cycle. For example, a 16-valve IRLDS with 30 second sam- pling times for each zone takes a total of eight minutes to sample all zones. Choosing an alarm delay smaller than the IRLDS’s cycle time will cause an alarm to be generated af- ter only one high reading is taken.
Gain and Offset · Alarms/Notices Dly