1.0 Introductionp.51.1 Equipment Inspectionp.51.2 Outside Enclosure Overviewp.6Figure 1 Small enclosure—external featuresp.6Figure 2 Large enclosure—internal featuresp.61.3 Typical Sequencep.7Figure 3 Example of typical sequence: Analog input reaches high setpointp.71.4 Controller Board Overviewp.8Table 1 Controller board componentsp.81.5 LED Indicatorsp.10Table 2 LED indicators summaryp.102.0 Installationp.112.1 Installation Considerationsp.112.1.1 Unpacking and Preliminary Inspectionp.11Packing Contentsp.11Table 3 Packing manifestp.112.2 Surface-Mounting the Liquitect Panelp.12Required toolsp.122.2.1 Mounting the Panelp.12Figure 4 Mounting dimensionsp.122.3 Flush-Mounting the Liquitect Panelp.13Required toolsp.132.3.1 Mounting the Panelp.132.4 Connect Power to the Liquitect Panelp.142.4.1 Input Power Connections - Small Enclosurep.14Figure 5 Electrical connections to panelp.142.4.2 Input and Output Power Connections - Large Enclosurep.15Input Power Connectionsp.1524 VAC Output Power Connectionsp.15Figure 6 Power wiring to TM115p.15Figure 7 Power wiring to TM230p.15Troubleshooting - Transformer Modulep.153.0 Connections and Configurationp.16Table 4 Wiring specificationsp.163.1 Connecting Leak Detection Cable Inputsp.173.1.1 Attaching Leak Detection Connection Cable to the Panelp.173.1.2 Connecting Leak Detection Cable to the Connection Cablep.18Figure 8 Fittings on leak detection cable (LT500Y) and connection cable (CONNECT10)p.18Figure 9 Typical leak detection cable layoutp.18Figure 10 Installation of holddown clips in pairsp.19Figure 11 Cable laid in straight patternsp.19Figure 12 Cable laid in circular patternsp.19Figure 13 90˚ turn in cablep.193.2 Connecting Alarm Outputsp.203.3 Connecting to a Building Maintenance System or External Alarm Systemp.203.4 RS422 SiteScan Web Connectorp.213.5 Disable the Audible Hornp.214.0 Overview of Menusp.224.1 View Status Overviewp.224.2 System and Control Overviewp.22Figure 14 Menu overviewp.225.0 View Status Optionsp.23Figure 15 Menu overview - View Status menup.235.1 View Cable Statusp.245.1.1 Cable Status Screensp.24Viewing Additional Screensp.24Overall Conditionp.24Table 5 Overall cable conditionsp.24Cable Length & Current Valuep.245.2 View Alarm Historyp.255.2.1 Alarm History Logp.25Table 6 Alarm History Log conditionsp.25Viewing Additional Screensp.255.3 View Zone Trendp.265.3.1 Zone Trend Logp.26Viewing Additional Screensp.266.0 System and Control Optionsp.27Table 7 Valid characters for data entryp.276.1 Loginp.27Figure 16 Menu overview - System and Control menup.286.2 Setup System - Overviewp.296.3 Setup System - Setup ZN1 Zone 1p.29Table 8 Default settings - Zone 1p.296.3.1 Identify the Zone as Connectedp.306.3.2 Change Zone Labelp.306.3.3 Change Units Labelp.306.3.4 Auto Calibrationp.316.3.5 Set Up Sensitivity for Water Detectionp.316.3.6 Set Up Sensitivity for Contamination Detectionp.326.4 Setup System - Setup ZN2 Zone 2p.336.5 Setup System - Setup Alarm Outputsp.34Table 9 Default settings - alarm outputsp.346.5.1 Specify Longest Cable Lengthp.35Table 10 Operation of 420mA outputsp.356.5.2 Define Relays as Normally Open or Normally Closedp.356.5.3 Define Alarms as Latched or Unlatchedp.35Liquitect System’s Response to Alarms - Both Latched and Unlatchedp.36Latched Alarms Onlyp.36Unlatched Alarms Onlyp.366.6 Setup System - Setup Re-Alarm Delayp.366.7 Setup System - Setup Mapmodep.37Table 11 Default mapping valuesp.376.7.1 View Last Mapp.386.8 Setup System - Setup System Infop.396.8.1 Change Passwordp.39Change the Passwordp.39Reset Password to the Factory Default (“AAAA”)p.396.8.2 Change Date & Time/Automatic Daylight Saving Timep.406.8.3 Factory Defaultsp.40Table 12 Factory default settingsp.406.9 Reset Latched Alarmsp.416.10 Clear Alarm Historyp.426.11 Clear Zone Trendp.437.0 Specificationsp.447.1 Liquitect Panel Specificationsp.44
Page 1 of the Emerson MC68HC16Z1 user manual — M ONITORING
Page 1 · click to enlarge
Page 1

M ONITORING

L IQUI - TECT M ONITORING S YSTEM

U SER M ANUAL

Emerson MC68HC16Z1 — M ONITORING diagram (page 1)
Fig. 1
Page 2 of the Emerson MC68HC16Z1 user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson MC68HC16Z1 user manual
Page 3 of the Emerson MC68HC16Z1 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

1.0 Introductionp.51.1 Equipment Inspectionp.51.2 Outside Enclosure Overviewp.6Figure 1 Small enclosure—external featuresp.6Figure 2 Large enclosure—internal featuresp.61.3 Typical Sequencep.7Figure 3 Example of typical sequence: Analog input reaches high setpointp.71.4 Controller Board Overviewp.8Table 1 Controller board componentsp.81.5 LED Indicatorsp.10Table 2 LED indicators summaryp.102.0 Installationp.112.1 Installation Considerationsp.112.1.1 Unpacking and Preliminary Inspectionp.11Packing Contentsp.11Table 3 Packing manifestp.112.2 Surface-Mounting the Liquitect Panelp.12Required toolsp.122.2.1 Mounting the Panelp.12Figure 4 Mounting dimensionsp.122.3 Flush-Mounting the Liquitect Panelp.13Required toolsp.132.3.1 Mounting the Panelp.132.4 Connect Power to the Liquitect Panelp.142.4.1 Input Power Connections - Small Enclosurep.14Figure 5 Electrical connections to panelp.142.4.2 Input and Output Power Connections - Large Enclosurep.15Input Power Connectionsp.1524 VAC Output Power Connectionsp.15Figure 6 Power wiring to TM115p.15Figure 7 Power wiring to TM230p.15Troubleshooting - Transformer Modulep.153.0 Connections and Configurationp.16Table 4 Wiring specificationsp.163.1 Connecting Leak Detection Cable Inputsp.173.1.1 Attaching Leak Detection Connection Cable to the Panelp.173.1.2 Connecting Leak Detection Cable to the Connection Cablep.18Figure 8 Fittings on leak detection cable (LT500Y) and connection cable (CONNECT10)p.18Figure 9 Typical leak detection cable layoutp.18Figure 10 Installation of holddown clips in pairsp.19Figure 11 Cable laid in straight patternsp.19Figure 12 Cable laid in circular patternsp.19Figure 13 90˚ turn in cablep.193.2 Connecting Alarm Outputsp.203.3 Connecting to a Building Maintenance System or External Alarm Systemp.203.4 RS422 SiteScan Web Connectorp.213.5 Disable the Audible Hornp.214.0 Overview of Menusp.224.1 View Status Overviewp.224.2 System and Control Overviewp.22Figure 14 Menu overviewp.225.0 View Status Optionsp.23Figure 15 Menu overview - View Status menup.235.1 View Cable Statusp.245.1.1 Cable Status Screensp.24Viewing Additional Screensp.24Overall Conditionp.24Table 5 Overall cable conditionsp.24Cable Length & Current Valuep.245.2 View Alarm Historyp.255.2.1 Alarm History Logp.25Table 6 Alarm History Log conditionsp.25Viewing Additional Screensp.255.3 View Zone Trendp.265.3.1 Zone Trend Logp.26Viewing Additional Screensp.266.0 System and Control Optionsp.27Table 7 Valid characters for data entryp.276.1 Loginp.27Figure 16 Menu overview - System and Control menup.286.2 Setup System - Overviewp.296.3 Setup System - Setup ZN1 Zone 1p.29Table 8 Default settings - Zone 1p.296.3.1 Identify the Zone as Connectedp.306.3.2 Change Zone Labelp.306.3.3 Change Units Labelp.306.3.4 Auto Calibrationp.316.3.5 Set Up Sensitivity for Water Detectionp.316.3.6 Set Up Sensitivity for Contamination Detectionp.326.4 Setup System - Setup ZN2 Zone 2p.336.5 Setup System - Setup Alarm Outputsp.34Table 9 Default settings - alarm outputsp.346.5.1 Specify Longest Cable Lengthp.35Table 10 Operation of 420mA outputsp.356.5.2 Define Relays as Normally Open or Normally Closedp.356.5.3 Define Alarms as Latched or Unlatchedp.35Liquitect System’s Response to Alarms - Both Latched and Unlatchedp.36Latched Alarms Onlyp.36Unlatched Alarms Onlyp.366.6 Setup System - Setup Re-Alarm Delayp.366.7 Setup System - Setup Mapmodep.37Table 11 Default mapping valuesp.376.7.1 View Last Mapp.386.8 Setup System - Setup System Infop.396.8.1 Change Passwordp.39Change the Passwordp.39Reset Password to the Factory Default (“AAAA”)p.396.8.2 Change Date & Time/Automatic Daylight Saving Timep.406.8.3 Factory Defaultsp.40Table 12 Factory default settingsp.406.9 Reset Latched Alarmsp.416.10 Clear Alarm Historyp.426.11 Clear Zone Trendp.437.0 Specificationsp.447.1 Liquitect Panel Specificationsp.44
Page 4 of the Emerson MC68HC16Z1 user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

1.0 Introductionp.51.1 Equipment Inspectionp.51.2 Outside Enclosure Overviewp.6Figure 1 Small enclosure—external featuresp.6Figure 2 Large enclosure—internal featuresp.61.3 Typical Sequencep.7Figure 3 Example of typical sequence: Analog input reaches high setpointp.71.4 Controller Board Overviewp.8Table 1 Controller board componentsp.81.5 LED Indicatorsp.10Table 2 LED indicators summaryp.102.0 Installationp.112.1 Installation Considerationsp.112.1.1 Unpacking and Preliminary Inspectionp.11Packing Contentsp.11Table 3 Packing manifestp.112.2 Surface-Mounting the Liquitect Panelp.12Required toolsp.122.2.1 Mounting the Panelp.12Figure 4 Mounting dimensionsp.122.3 Flush-Mounting the Liquitect Panelp.13Required toolsp.132.3.1 Mounting the Panelp.132.4 Connect Power to the Liquitect Panelp.142.4.1 Input Power Connections - Small Enclosurep.14Figure 5 Electrical connections to panelp.142.4.2 Input and Output Power Connections - Large Enclosurep.15Input Power Connectionsp.1524 VAC Output Power Connectionsp.15Figure 6 Power wiring to TM115p.15Figure 7 Power wiring to TM230p.15Troubleshooting - Transformer Modulep.153.0 Connections and Configurationp.16Table 4 Wiring specificationsp.163.1 Connecting Leak Detection Cable Inputsp.173.1.1 Attaching Leak Detection Connection Cable to the Panelp.173.1.2 Connecting Leak Detection Cable to the Connection Cablep.18Figure 8 Fittings on leak detection cable (LT500Y) and connection cable (CONNECT10)p.18Figure 9 Typical leak detection cable layoutp.18Figure 10 Installation of holddown clips in pairsp.19Figure 11 Cable laid in straight patternsp.19Figure 12 Cable laid in circular patternsp.19Figure 13 90˚ turn in cablep.193.2 Connecting Alarm Outputsp.203.3 Connecting to a Building Maintenance System or External Alarm Systemp.203.4 RS422 SiteScan Web Connectorp.213.5 Disable the Audible Hornp.214.0 Overview of Menusp.224.1 View Status Overviewp.224.2 System and Control Overviewp.22Figure 14 Menu overviewp.225.0 View Status Optionsp.23Figure 15 Menu overview - View Status menup.235.1 View Cable Statusp.245.1.1 Cable Status Screensp.24Viewing Additional Screensp.24Overall Conditionp.24Table 5 Overall cable conditionsp.24Cable Length & Current Valuep.245.2 View Alarm Historyp.255.2.1 Alarm History Logp.25Table 6 Alarm History Log conditionsp.25Viewing Additional Screensp.255.3 View Zone Trendp.265.3.1 Zone Trend Logp.26Viewing Additional Screensp.266.0 System and Control Optionsp.27Table 7 Valid characters for data entryp.276.1 Loginp.27Figure 16 Menu overview - System and Control menup.286.2 Setup System - Overviewp.296.3 Setup System - Setup ZN1 Zone 1p.29Table 8 Default settings - Zone 1p.296.3.1 Identify the Zone as Connectedp.306.3.2 Change Zone Labelp.306.3.3 Change Units Labelp.306.3.4 Auto Calibrationp.316.3.5 Set Up Sensitivity for Water Detectionp.316.3.6 Set Up Sensitivity for Contamination Detectionp.326.4 Setup System - Setup ZN2 Zone 2p.336.5 Setup System - Setup Alarm Outputsp.34Table 9 Default settings - alarm outputsp.346.5.1 Specify Longest Cable Lengthp.35Table 10 Operation of 420mA outputsp.356.5.2 Define Relays as Normally Open or Normally Closedp.356.5.3 Define Alarms as Latched or Unlatchedp.35Liquitect System’s Response to Alarms - Both Latched and Unlatchedp.36Latched Alarms Onlyp.36Unlatched Alarms Onlyp.366.6 Setup System - Setup Re-Alarm Delayp.366.7 Setup System - Setup Mapmodep.37Table 11 Default mapping valuesp.376.7.1 View Last Mapp.386.8 Setup System - Setup System Infop.396.8.1 Change Passwordp.39Change the Passwordp.39Reset Password to the Factory Default (“AAAA”)p.396.8.2 Change Date & Time/Automatic Daylight Saving Timep.406.8.3 Factory Defaultsp.40Table 12 Factory default settingsp.406.9 Reset Latched Alarmsp.416.10 Clear Alarm Historyp.426.11 Clear Zone Trendp.437.0 Specificationsp.447.1 Liquitect Panel Specificationsp.44
Page 5 of the Emerson MC68HC16Z1 user manual — 1.1 Equipment Inspection
Page 5 · click to enlarge
Page 5

1.0 I NTRODUCTION

The Liebert Liqui-tect Monitoring System is the ultimate in leak detection and retrofitting capabili- ties for computer rooms and other large areas. The Liqui-tect Monitoring System provides direct-read at the control unit location, as well as the ability to communicate with the Liebert SiteScan Web enterprise monitoring system or a building management system.

The Liqui-tect Monitoring System features an easy-to-use liquid crystal display (LCD) panel with readout of normal and alarm conditions, as well as leak location. Display and measurement modules are contained in a single compact package.

The Liqui-tect Monitoring System can monitor up to 10,000 ft. (3048m) of Liebert LT500Y leak detec- tion cable. Points along the cable may be mapped by one person, making it easy to configure within the critical space and pinpoint the location of leaks when they occur. The system determines the loca- tion of the water on the detection cable and reports the distance from the Liqui-tect panel in feet or meters. To ensure proper protection, the system continuously monitors operation, signaling system normal, leak detected and cable fault.

The Liqui-tect panel offers these and other features to protect your installation from leak damage:

  • audible and visual alarms
  • adjustable sensitivity setpoints for leaks and contamination
  • continuous scrolling of data
  • history logs
  • connection to a building management system
  • automatic detection of broken cables and contaminated cables
  • password protection
  • retention of configuration after a power failure

Two interfaces permit easy access and configuration of the Liqui-tect panel:

  • LCD on the front of the enclosure
  • Liebert’s SiteScan Web enterprise monitoring system through a dedicated connection port

1.1 Equipment Inspection

Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme- diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.

Introduction

Page 6 of the Emerson MC68HC16Z1 user manual — 1.2 Outside Enclosure Overview
Page 6 · click to enlarge
Page 6

1.2 Outside Enclosure Overview

The enclosure for the Liqui-tect panel’s controller board comes in two sizes:

  • The large enclosure is designed to accommodate the Transformer Module and future components, in addition to the controller board.
  • The small enclosure is built to hold the controller board only.

Both enclosures are 2-3/4" deep.

Both enclosures have a built-in liquid crystal display (LCD) and a key lock, as shown in the example below. The metal enclosures accommodate secure conduit fittings and protect components against external forces and debris.

Figure 1 Small enclosure—external features

Emerson MC68HC16Z1 — 1.2 Outside Enclosure Overview diagram (page 6)
Fig. 2 · 1.2 Outside Enclosure Overview

LCD for configuration and operation

The enclosure has knockouts and access slots on top and bottom for cables and wires.

The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in 2.0 - Installation. Knockouts and access slots on the top and bottom allow easy connection of wires and cables (see 3.0 - Connections and Configuration) with either mounting type.

Figure 2 Large enclosure—internal features

Emerson MC68HC16Z1 — 1.2 Outside Enclosure Overview diagram (page 6)
Fig. 3 · 1.2 Outside Enclosure Overview

Knockouts and access slots (top and bottom) Power receptacle

Ground wire for LCD

Show 5 more labels / short text on this page
Introduction · Key lock · Transformer Module · Back of LCD · Controller Board
Page 7 of the Emerson MC68HC16Z1 user manual — RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE
Page 7 · click to enlarge
Page 7

1.3 Typical Sequence

Figure 3 shows a typical sequence of how the Liqui-tect Monitoring System functions after detecting a leak, contamination or cable break in either Zone 1 or Zone 2. Responses depend on configuration settings. This example shows what happens when a leak is detected.

Figure 3 Example of typical sequence: Analog input reaches high setpoint

RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE

Emerson MC68HC16Z1 — RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE diagram (page 7)
Fig. 4

ALARM CONDITION DETECTED A leak is sensed along the cable defining Zone 1.

RETURN TO NORMAL The leak is controlled.

Emerson MC68HC16Z1 — RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE diagram (page 7)
Fig. 5

The alarm is cleared (automatically if Unlatched; must be cleared manually if Latched)

The horn sounds (audible horn on the controller board—silence horn by pressing any key on the LCD keypad)

The horn stops sounding (if user hasn’t silenced it)

The LCD stops flashing

Entry in Alarm History Log (if alarms defined as Latched) ZONE 1 LEAK @ 3495ft 29-AUG-03 09:29:10

Entry in Alarm History Log

Entry in Zone Trend Log (if alarms defined as Unlatched)

Introduction · The LCD flashes

Page 8 of the Emerson MC68HC16Z1 user manual — 1.4 Controller Board Overview
Page 8 · click to enlarge
Page 8

1.4 Controller Board Overview

The Liqui-tect panel’s controller board, as shown below, has connectors for two digital outputs for leak detection alarms, two digital outputs for cable break alarms, two inputs for leak detection cables and two analog outputs for connecting to a building management system. The board comes complete with light-emitting diodes (LEDs) to display the status of monitored zones, power connections and other features necessary to monitor and protect your operation.

Emerson MC68HC16Z1 — 1.4 Controller Board Overview diagram (page 8)
Fig. 6 · 1.4 Controller Board Overview
O N 12345678 R4 SW2 KKK124 K5DDDSSS345RRR111678 U24 U15C26 R38 U1C 627 C28TB3 U2C333 U24C40 R4 DD4 SS87L RE es D eO tF R Da 4Su 0l 6t R1 DS1 O N Pwr On 12345678 SW1 A 24V Pow Interlface LCD U2C232 C46O N 12345678 R4 SW2 KKK124 K5DDDSSS345RRR111678 U24 U15C26 R38 U1C 627 C28TB3 U2C333 U24C40 R4 DD4 SS87L RE es D eO tF R Da 4Su 0l 6t U29 ON TX RX

E-Digital alarm outputs (Zone 1)

F-Alarm output LEDs (Zones 1&2)

G-Digital alarm outputs (Zone 2) H-Status LEDs

I-4/20mA output (Zone 2)

J-4/20mA output (Zone 1)

K-Input cable connector (Zone 2)

T-Power On/ Off switch

Table 1 Controller board components

ItemDescriptionMore Information A-Power On/Off LEDIndicates when power is supplied to the2.4: Connect Power to the Liqui-tect Panel panel. 1.5: LED Indicators B-DIP switch 1DIP switch used for resetting password and disabling the audible alarm.to default 3.5: Disable the Audible Horn 6.8.1: Change Password C-DIP switch 2Not used.N/A D-Audible hornProvides audible notification when an alarm occurs. 3.5: Disable the Audible Horn E-Digital alarm outputs (Zone 1) and G-Digital alarm outputs (Zone 2)The Cable Break output connection is a point (ON/OFF, energized/de-energized cable is broken or becomes contaminate is created and the contact is energized. The Leak Detected output connection is point (ON/OFF, energized/de-energized water is detected, an alarm is created a contact is energized. Each output can be used to connect to a warning device such as a horn, light or b management system.two-state ). When the d, an alarm 3.0: Connections and Configuration a two-state 3.2: Connecting Alarm Outputs ). When 5.1: View Cable Status nd the 6.5: Setup System - Setup Alarm Outputs secondary uilding F-Alarm output LEDs (Zones 1&2)Indicates the status of the alarm outputs. 1.5: LED Indicators G-Digital alarm outputs (Zone 2)(See description and references for E-Digital alarm outputs (Zone 1) above)
Show 12 more labels / short text on this page
Introduction · A-Power On/Off LED · B-DIP switch 1 · C-DIP switch 2 · D-Audible horn · Z-Transformer Module · X-Reset switch · V-LCD connector · U-24VAC connector · S-Power receptacle · P-SiteScan Web LEDs · O-SiteScan Web connector
Page 9 of the Emerson MC68HC16Z1 user manual — 1.4 Controller Board Overview
Page 9 · click to enlarge
Page 9

Table 1 Controller board components

ItemDescriptionMore Information H-Status LEDsIndicates the operational status of the panel.1.5: LED Indicators I-4/20mA output (Zone 2)Provides the distance liquid is detected, normal status and cable fault. Used to provide status to a building management system or remote monitoring system.3.0: Connections and Configuration 3.3: Connecting to a Building Maintenance System or External Alarm System 5.1: View Cable Status 6.5: Setup System - Setup Alarm Outputs J-4/20mA output (Zone 1)Provides the distance liquid is detected, normal status and cable fault. Used to provide status to a building management system or remote monitoring system.3.0: Connections and Configuration 3.3: Connecting to a Building Maintenance System or External Alarm System 5.1: View Cable Status 6.5: Setup System - Setup Alarm Outputs K-Input cable connector (Zone 2)Connection to Liebert leak detection cable.3.0: Connections and Configuration 3.1: Connecting Leak Detection Cable Inputs 5.1: View Cable Status 6.4: Setup System - Setup ZN2 Zone 2 L-Input cable connector (Zone 1)Connection to Liebert leak detection cable.3.0: Connections and Configuration 3.1: Connecting Leak Detection Cable Inputs 5.1: View Cable Status 6.3: Setup System - Setup ZN1 Zone 1 M-RS232 LEDsIndicates the connection status between the Liqui-tect panel and an RS232 device.1.5: LED Indicators N-RS232 connectorConnection for a laptop. Used by factory personnel. Requires a null modem cable for connectivity (P/N 201258P1).N/A O-SiteScan Web connectorConnection to monitor Liqui-tect panel from Liebert’s SiteScan Web enterprise monitoring system.3.0: Connections and Configuration 3.4: RS422 SiteScan Web Connector P-SiteScan Web LEDsIndicates the connection status between the Liqui-tect panel and SiteScan Web.1.5: LED Indicators Q-RS485 LEDsNot presently used.N/A R-RS485 connectorNot presently used.N/A S-Power receptacle (Transformer Module)115VAC power receptacle to power laptop during configuration and diagnostics. Receptacle not available on 230VAC Transformer Module.2.4.2: Input and Output Power Connections - Large Enclosure 3.0: Connections and Configuration T-Power On/Off switch (Transformer Module)Power switch to turn power On/Off to both Transformer Module 24VAC connectors and power receptacle.2.4.2: Input and Output Power Connections - Large Enclosure 3.0: Connections and Configuration U-24VAC connector (Transformer Module)One of the two 24VAC connectors for power (the second is also on the right side of the Transformer Module near the top). Each connector is rated for 40VA.2.4.2: Input and Output Power Connections - Large Enclosure 3.0: Connections and Configuration V-LCD connectorConnection for the LCD located on the front door.N/A W-LCD contrast adjustmentAdjustment contrast for the LCD located on the front door.N/A X-Reset switchReset switch to reset the panel. Same as repowering the panel.N/A Y-24VAC power connectorPower connection for the controller. Requires 24VAC.2.4: Connect Power to the Liqui-tect Panel Z-Transformer ModuleTransformer Module used to convert 115VAC or 230VAC to 24VAC. Available only in the large enclosure.2.4.2: Input and Output Power Connections - Large Enclosure

Introduction

Page 10 of the Emerson MC68HC16Z1 user manual — 1.5 LED Indicators
Page 10 · click to enlarge
Page 10

1.5 LED Indicators

The Liqui-tect panel’s controller board has LED indicators that show the status of inputs, outputs and other board components.

Power On/Off LEDR1 DS1 O N O N Pwr On 12345678 12345678 SW1 R4 SW2 A 24V Pow KKK124 K5DDDSSS345RRR111678 Interlface U24 LCD U15C26 R38 U1C 627 C28TB3 U2C232 U2C333 U24C40 R4 DD4 SS87L RE es D eO tF R Da 4Su 0l 6t U2C946 ON TX RXAlarm output (Zones 1&2) K1DS2 TB2 R15 K2 R16 DS3 K3 R17 DS4 R18 K4DS5 Status LEDs R38 Fault DS6 R40 LEDO Reset DS7 DS8 R44 R1 DS1 O N O N Pwr On 12345678 12345678 SW1 R4 SW2 A 24V Pow KKK124 K5DDDSSS345RRR111678 Interlface U24 LCD U15C26 R38 U1C 627 C28TB3 U2C232 U2C333 U24C40 R4 DD4 SS87L RE es D eO tF R Da 4Su 0l 6t U2C946 ON TX RX
Emerson MC68HC16Z1 — 1.5 LED Indicators diagram (page 10)
Fig. 7 · 1.5 LED Indicators

Table 2 LED indicators summary

LEDColorDescription Power On/Off LED Pwr OnGreen Indicates whether power is connected Zone 1 & 2 Alarm Outputs LEDs K1 – Zone 1 Leak DetectedGreen Indicates leak detected for Zone 1 K2 – Zone 1 Cable BreakGreen Indicates cable problem for Zone 1 K3 – Zone 2 Leak DetectedGreen Indicates leak detected for Zone 2 K4 – Zone 2 Cable BreakGreen Indicates cable problem for Zone 2 Status LEDs LEDOGreen Indicates the panelis working properly – will flash slowly when working FaultRed Indicates an alarm is present ResetRed Indicates the panelis being reset RS232 LEDs RS232 TXGreen Liqui-tect panel is transmitting information via the RS232 port RS232 RXGreen Liqui-tect panel is receiving information via the RS232 port RS422 LEDs RS422 TXGreen Liqui-tect panel is transmitting information over the RS422 port RS422 RXGreen Liqui-tect panel is receiving information over the RS422 port RS485 LEDs RS485 TXGreen Not presently used RS485 RSGreen Not presently used

Introduction

Page 11 of the Emerson MC68HC16Z1 user manual — Packing Contents
Page 11 · click to enlarge
Page 11

2.0 I NSTALLATION

2.1 Installation Considerations

The Liqui-tect panel must be installed indoors and may be mounted on the surface of a wall or flush- mounted, depending on the user’s application and the type of wall the unit will be mounted on. The unit’s location must meet the following criteria:

  • The panel must be placed close enough to the areas to be monitored to permit proper connection of the leak detection cable. The panel will monitor two zones; each zone can accommodate up to 5,000 ft. (1524m) of leak detection cable.
  • The Liqui-tect panel should be mounted where it can be easily accessed. Personnel would access the unit through the LCD on its front cover or through SiteScan.
  • The site also must have electrical service and must permit connection of the panel’s four digital outputs, two inputs for leak detection cables and two analog outputs for connecting to a building management system or external alarm.
  • The wall material must be capable of supporting the weight of the Liqui-tect panel: see 7.0 - Specifications .

NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

  • 2.1.1 Unpacking and Preliminary Inspection
  • Before unpacking the Liqui-tect panel, inspect the shipping carton for damage or signs of mishandling, such as gashes or holes in the carton or severely flattened corners.
  • Open the shipping container carefully. Use care to avoid puncturing the container with sharp objects that might damage the contents.
  • Inspect the Liqui-tect panel and all included components for damage.
  • If any damage from shipping or mishandling is observed, immediately file a damage claim with the shipping agency and forward a copy to:

Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Packing Contents

Table 3 Packing manifest

Liqui-tect panel - large or small enclosure

Keys (2) to panel door lock

Connection cables (2) (CONNECT10)

End terminators (2) (LT500-ET)

Installation · Standard Components · User Manual

Page 12 of the Emerson MC68HC16Z1 user manual — SMALL ENCLOSURE
Page 12 · click to enlarge
Page 12

2.2 Surface-Mounting the Liqui-tect Panel

After determining where to place the unit, check to ensure that you have all the hardware required to install the panel on the surface of a wall. Obtain the needed tools and material. Required tools

  • Electric drill (if surface is too hard to drive screws without pilot holes)
  • Screwdriver
  • Marker to denote layout of holes
  • Four screws, each #10

2.2.1 Mounting the Panel

! CAUTION Check building plans and other relevant documents to determine whether mounting the Liqui-tect panel at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.

1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 4). 2. Drill holes, if required, to install the four #10 screws that will secure the Liqui-tect panel to the wall. Clean up the debris. 3. If the wall material is not strong enough to hold the screws securely, use wall anchors. 4. Install the top two screws—the screw heads must be small enough to slip through the larger, bottom portion of the pear-shaped mounting slot in the Liqui-tect panel (see inset in illustration at right). The screws must also be large enough to extend over the edges of the top of the mounting slot. 5. Hang the Liqui-tect panel on the screws, letting the panel slip down until the screws are in the smaller, upper portion of the slot. 6. Tighten the screws until they are snug. 7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.

Figure 4 Mounting dimensions

LARGE ENCLOSURE

Emerson MC68HC16Z1 — LARGE ENCLOSURE diagram (page 12)
Fig. 8

SMALL ENCLOSURE

Emerson MC68HC16Z1 — SMALL ENCLOSURE diagram (page 12)
Fig. 9

0.213" (5.4mm) Bottom hole diameter

0.213" (5.4mm) Bottom hole diameter

Installation · Mounting Slot

Page 13 of the Emerson MC68HC16Z1 user manual — 2.3.1 Mounting the Panel
Page 13 · click to enlarge
Page 13

2.3 Flush-Mounting the Liqui-tect Panel

The rectangular access doors on the top and bottom of the Liqui-tect panel must be removed from the outside of the panel and reinstalled on the inside of the panel. Leaving the doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall.

The Liqui-tect panel may be flush mounted according to company practices—either with screws through the sides of the panel into wall supports or with hanging hardware that attaches to the back of the panel. After determining how and where to place the unit, check to ensure that you have all the hardware required to install the panel in the wall. Obtain the needed tools.

Required tools

  • Saw
  • Electric drill
  • Screwdriver
  • Marker to denote layout of the hole to accommodate the Liqui-tect panel
  • Trim ring and associated hardware
  • Mounting hardware

2.3.1 Mounting the Panel

! CAUTION Check building plans and other relevant documents to determine whether mounting the Liqui-tect panel at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.

1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template. 2. Drill a pilot hole for the saw blade, if required. 3. Use the saw to cut out the marked section of the wall (if not new construction). 4. Rest the Liqui-tect panel in the wall and mark where mounting screws will be inserted into the wall studs or other support member. 5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the debris. 6. Reverse the slide direction of the rectangular access doors on the top and bottom of the Liqui-tect panel. Leaving the access doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall. 7. Attach any field-supplied mounting hardware. 8. Reinsert the assembly into the wall. 9. Insert and tighten the screws or wall anchors.

Installation

Page 14 of the Emerson MC68HC16Z1 user manual — TB1
Page 14 · click to enlarge
Page 14

2.4 Connect Power to the Liqui-tect Panel

The Liqui-tect panel requires 24VAC for proper operation. Liebert recommends using the optional Transformer Module manufactured by Liebert or another UL-approved Class 2 power unit to obtain proper voltage. If the power unit is not a Class 2 circuit, it must be protected with an IEC 5 x 20mm time lag 2A fuse. For information, consult your local dealer, Liebert representative or the Liebert Worldwide Support Group.

! WARNING Check that power is removed from wires prior to installation.

! CAUTION The Liqui-tect panel is designed for use on properly grounded (earthed) 24VAC power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud located next to the 24VAC terminal block).

This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes.

! WARNING Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any wiring to this unit.

2.4.1 Input Power Connections - Small Enclosure

To connect electrical power:

1. Run conduit and electrical wiring from building to the Liqui-tect panel. 2. Use copper wires only; proper wiring to use for 24VAC power is 18-22 AWG stranded and shielded (18 AWG is recommended—see Table 4 ). Strip wires 1/2".

Figure 5 Electrical connections to panel

External wiring through knockout

Emerson MC68HC16Z1 — 2.4.1 Input Power Connections - Small Enclosure diagram (page 14)
Fig. 10 · 2.4.1 Input Power Connections - Small Enclosure
Emerson MC68HC16Z1 — 2.4.1 Input Power Connections - Small Enclosure diagram (page 14)
Fig. 11 · 2.4.1 Input Power Connections - Small Enclosure
Emerson MC68HC16Z1 — 2.4.1 Input Power Connections - Small Enclosure diagram (page 14)
Fig. 12 · 2.4.1 Input Power Connections - Small Enclosure
Emerson MC68HC16Z1 — 2.4.1 Input Power Connections - Small Enclosure diagram (page 14)
Fig. 13 · 2.4.1 Input Power Connections - Small Enclosure
Emerson MC68HC16Z1 — 2.4.1 Input Power Connections - Small Enclosure diagram (page 14)
Fig. 14 · 2.4.1 Input Power Connections - Small Enclosure

TB1

R4

TVS3

FB2

SW3 EGND1

24VAC input connector 24VAC wiring (red & white)

3. Secure the incoming electrical service wires to the Liqui-tect panel’s 24VAC input by sliding the wires into TB1, the 24VAC input terminal block. There is no polarity requirement when connecting to TB1. The ground wire must be connected to the earth ground terminal located on the side of the panel (see Figure 5 ).
Show 5 more labels / short text on this page
Installation · Ground wire (black) · Earth ground terminal · 24V Power · Reset
Page 15 of the Emerson MC68HC16Z1 user manual — Troubleshooting - Transformer Module
Page 15 · click to enlarge
Page 15

2.4.2 Input and Output Power Connections - Large Enclosure

! CAUTION The 115VAC/230VAC Transformer Module must be connected to a branch circuit with 15A branch circuit protection. This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded connections to ensure compliance with the technical standards and national and local electrical codes. The Transformer Module shall be used only as indicated by the manufacturer.

! WARNING Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any wiring to this unit.

Input Power Connections

To connect electrical power to the Transformer Module:

1. Install electrical wiring from utility power to the Transformer Module. 2. Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground. 3. For the TM230 only: strip wires 3/8" (9.6mm). Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory. 4. Connect the wiring as follows:

TM115 TM230 Connection Type White wire Neutral (L2) Neutral Black wire Line (L1) Power (Line) Green wire Ground lead Ground

5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in Figure 6 or to the TM230 connectors as shown in Figure 7 .

24 VAC Output Power Connections

To connect to the 24VAC outputs:

1. Install electrical wiring from device requiring 24VAC power to the Transformer Module. 2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip wire 1/4". 3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as shown in Figures 6 and 7 . TB1 and TB2 are NOT polarity sensitive. 4. Secure the wires to the connector.

Figure 6 Power wiring to TM115 Figure 7 Power wiring to TM230

Emerson MC68HC16Z1 — 24 VAC Output Power Connections diagram (page 15)
Fig. 15 · 24 VAC Output Power Connections
Emerson MC68HC16Z1 — 24 VAC Output Power Connections diagram (page 15)
Fig. 16 · 24 VAC Output Power Connections

TM115

TM230

Knockout for external wiring

Knockout for external wiring

Wire nuts connecting electrical wiring

Troubleshooting - Transformer Module

A common problem and possible solution are shown in the table below. For further information or if you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert Worldwide Support Group.

Problem Possible Solution Replacement Fuse Part Numbers 24VAC power not available from TB1 or TB2

Check fuse for respective output (TB1 or TB2).

  • LITTLEFUSE 218002
  • BUSSMANN GDC-2A
Show 5 more labels / short text on this page
Installation · Neutral (L2) · Line (L1) · 24VAC output (TB1) · 24VAC output (TB1)
Page 16 of the Emerson MC68HC16Z1 user manual — (TB7)
Page 16 · click to enlarge
Page 16

3.0 C ONNECTIONS AND C ONFIGURATION

! CAUTION Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any wiring to this unit or changing input or output connections.

Input and output connections to the Liqui-tect panel may be made in any order—it is not necessary, for example, to make all input connections before making any output connections. Use copper conduc- tors only for all wiring.

Table 4 Wiring specifications

Connection Supported Wire Type Maximum Wire Length Rating

4 wire Liebert Connection Cable (CONNECT10) - furnished with Liqui-tect panel

Connection cable - 10 ft. (3m) Leak detection cable - 5000 ft. (1524m) N/A

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740

18 AWG* @ 1A 200 ft. (60m)

24VAC @ 1A 20 AWG @ 1A 100 ft. (30m)

22 AWG @ 1A 75 ft. (23m)

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740

750 ft. (225m) 4-20mA Signal Output

RS232 Null Modem Cable 50 ft. (15m) N/A

18-22 AWG Stranded & Shielded 22 AWG* (recommended) Non Plenum - Belden 9461 Plenum - Belden 88761

1000 ft. (300m) N/A

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 8770 Plenum - Belden 88770

150 ft. (45m) 24VAC @ 1A

(TB7)

Show 10 more labels / short text on this page
Connections and Configuration · Cable · Input · Alarm Output · Analog Output · Communication · Communication · IGM422 SiteScan · 24VAC Power Connection · * Recommended
Page 17 of the Emerson MC68HC16Z1 user manual — Y B G R
Page 17 · click to enlarge
Page 17

3.1 Connecting Leak Detection Cable Inputs

The leak detection cable inputs are found on the lower right side of the Liqui-tect panel’s printed wir- ing assembly board. There are two terminal blocks for the inputs; the lower terminal block is for the Zone 1 cable and the terminal block above it is for a second leak detection cable, Zone 2.

To determine the proper wire size, see Table 4 - Wiring specifications.

After making the connections, push the removed piece back into the portion attached to the printed wiring assembly until the terminal block pieces lock together.

3.1.1 Attaching Leak Detection Connection Cable to the Panel

To attach a leak detection connection cable:

1. Disconnect electrical power to the Liqui-tect panel. 2. Locate the Zone 1 and Zone 2 cable connectors on the controller board. They can be found on the lower right corner of the board (see 1.4 - Controller Board Overview). The Zone 1 connector is Cable 1 or TB9. The Zone 2 connector (Cable 2 or TB6) is just above it. 3. If necessary, remove a conduit knockout to permit wire entry into the Liqui-tect panel enclosure. 4. Bring the white connection cable (CONNECT10) into the Liqui-tect panel enclosure through a conduit knockout or access slot. 5. Loosen a screw on the terminal block and slip the stripped end of the appropriate wire into the terminal block according to the color-coded wiring key (see illustration at right). Note that the WHITE wire connects to the “Y” slot. The red wire connects to the “R” slot, the green wire connects to the “G” slot and the black wire to the “B” slot. 6. Tighten the screw until it holds the wire snugly. 7. Repeat for each of the four wire strands in the connection cable.

Leak Detection Cable Terminal BlocksZone 2 Zone 1

Y B G R

TB6

WIRING CONNECTIONS

Y B G R

TB9

Show 6 more labels / short text on this page
Connections and Configuration · Cable 1 · Red Wire · Green Wire · Black Wire · WHITE Wire
Page 18 of the Emerson MC68HC16Z1 user manual — 3.1.2 Connecting Leak Detection Cable to the Connection Cable
Page 18 · click to enlarge
Page 18

3.1.2 Connecting Leak Detection Cable to the Connection Cable

The connection cable has a black fitting on one end that will fasten securely to the fitting on one end of the leak detection cable—see Figure 8. Push these ends together, being careful to insert the pro- truding ends of the leak detection cable into the holes in the connection cable connector. Twist the connector ring to securely link the cables.

Figure 8 Fittings on leak detection cable (LT500Y) and connection cable (CONNECT10)

Leak detection connection cable

Emerson MC68HC16Z1 — 3.1.2 Connecting Leak Detection Cable to the Connection Cable diagram (page 18)
Fig. 17 · 3.1.2 Connecting Leak Detection Cable to the Connect…

After making this connection, lay the leak detection cable around the area to be monitored.

The monitored area would include any equipment or objects that might be damaged by water. Figure 9 shows one possible layout. In the example, the detection cable crosses between air condi- tioning units and computers to alert personnel when the electronic equipment is threatened by a leak. If there is a liquid source in the ceiling, the cable can be placed there. If a raised floor is used for cool- ing, the cable can be placed underneath the raised surface.

Figure 9 Typical leak detection cable layout

Emerson MC68HC16Z1 — 3.1.2 Connecting Leak Detection Cable to the Connection Cable diagram (page 18)
Fig. 18 · 3.1.2 Connecting Leak Detection Cable to the Connect…

Leak detection cable terminus (attach end terminator here) Leak detection cable

Follow these steps in laying the detection cable: 1. Attach the end terminator to the last length of leak detection cable required to monitor the selected area. 2. Verify power is connected and test the detection cable by touching the detection cable with a clean, moist cloth or paper towel. If the cables are connected properly, the audible horn should sound and the LCD screen should flash. Dry the detection cable to remove the alarm condition. (A hair dryer can be used to speed up the drying.) Note: Do not try to saturate the detection cable for testing! It requires only a small amount of water to alarm. The detection cable will have to dry for the alarm condition to clear.

Show 7 more labels / short text on this page
Connections and Configuration · Connect to · Liqui-tect · panel · Liqui-tect Monitoring · System · (yellow)
Page 19 of the Emerson MC68HC16Z1 user manual — DETECTION CABLE PLACEMENT PRECAUTIONS
Page 19 · click to enlarge
Page 19
3. Once the cable passes the test, lay it in the pattern desired. Pay special attention to the following cable placement precautions.

DETECTION CABLE PLACEMENT PRECAUTIONS

  • Do not use detection cable that is damaged or dirty—for example, from plaster, spackle or debris.
  • Detection cable should not be dragged through contaminants (dirty or greasy areas). Floor must be clean for the detection cable to function properly and for the hold-down clips to adhere to the floor surface.
  • Careful consideration should be taken to place detection cable out of the direct discharge airflow path of environmental equipment. This type of equipment can discharge moisture into the airflow. Place cable 6 ft. (1.8m) from discharge to avoid nuisance alarms during humidification.
  • Tools or heavy objects can do permanent damage when dropped, rolled, or set on the detection cable. Avoid foot traffic on the detection cable as well.
  • Do not use any type of adhesive tape to secure the detection cable.
  • Do not allow soldering or welding near the detection cable without providing protection from heat and contaminants. (Also avoid installing the detection cable in or near these type of areas.)
  • Mild dishwashing liquid can be used to clean the detection cable of many contaminants.

4. Install the hold-down clips in pairs, as shown in Figure 10, with the following considerations: a. The adhesive used to install the hold-down clips must NOT come in contact with the detection cable. b. One pair every 6 to 8 ft. (1.8-2.4m) in straight patterns (see Figure 11). c. One pair every 3 to 4 ft. (0.9-1.2m) in circular patterns (see Figure 12). d. One pair at the beginning and end of the arc when turning 90 degrees (see Figure 13). e. One pair as needed to maintain consistent uniform contact between the floor and detection cable.

Figure 10 Installation of hold- down clips in pairs

Figure 11 Cable laid in straight patterns

Figure 12 Cable laid in circular patterns

Emerson MC68HC16Z1 — DETECTION CABLE PLACEMENT PRECAUTIONS diagram (page 19)
Fig. 19
Emerson MC68HC16Z1 — DETECTION CABLE PLACEMENT PRECAUTIONS diagram (page 19)
Fig. 20

every 6-8 ft.

every 3-4 ft.

(0.9-1.2m)

(1.8-2.4m) along straight

Figure 13 90° turn in cable

5. Once adhesive is completely dry, snap the cable into each hold-down clip. 6. Check that there are no gaps between the floor and detection cable. (Add clips as required.) 7. Be certain there are no alarms present on the module. 8. Do final testing as per instruction in Step 2 .
Show 7 more labels / short text on this page
Connections and Configuration · Hold-down clips · Hold-down clips · sections · Hold-down clips · at beginning & · end of arc
Page 20 of the Emerson MC68HC16Z1 user manual — R18
Page 20 · click to enlarge
Page 20

3.2 Connecting Alarm Outputs

The Zone 1 and Zone 2 alarm outputs, found in the top right corner of the Liqui-tect panel, provide a contact output for a leak and a cable break for each zone. As an example, the outputs may provide alarms to an auxiliary alarm panel or building management sys- tem. To determine the proper wire size, see Table 4 - Wiring spec- ifications.

NO

NC

NO

NC

A wiring key beside each terminal block indicates whether the con- nected output is wired for Normally Open (NO) or Normally Closed (NC).

Zone 1 Zone 2

DS4 K4

R17

An alarm relay wired as an unsupervised point (energized for alarm) must be wired to the Normally Open (NO) and Common (C) contacts.

NO

Key to output status

NC

NO

NC

An alarm relay wired as a supervised point (de-energized for alarm) must be wired to the Normally Closed (NC) and Common (C) con- tacts.

To connect an output:

1. Disconnect electrical power to the Liqui-tect panel. 2. If necessary, remove a conduit knockout to permit wire entry into the Liqui-tect panel enclosure. 3. Bring the wire(s) into the Liqui-tect panel enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.

3.3 Connecting to a Building Maintenance System or External Alarm System

Two analog output connector blocks permit the user to connect aux- iliary notification equipment to monitor the distance of the leak and cable fault alarms. The terminal blocks are on the right side of the Liqui-tect panel printed circuit board, just above the leak detection cable connectors. To determine the proper wire size, see Table 4 - Wiring specifications.

TB4

To connect an input:

TB5

1. Disconnect electrical power to the Liqui-tect panel. 2. If necessary, remove a conduit knockout to permit wire entry into the Liqui-tect panel enclosure. 3. Bring the wire(s) into the Liqui-tect panel enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.

R18

Show 7 more labels / short text on this page
Connections and Configuration · Alarm outputs · + · Analog output connectors · lout Cable 2 · + · lout Cable 1
Page 21 of the Emerson MC68HC16Z1 user manual — 3.5 Disable the Audible Horn
Page 21 · click to enlarge
Page 21
Emerson MC68HC16Z1 — 3.4 RS422 SiteScan Web Connector diagram (page 21)
Fig. 21 · 3.4 RS422 SiteScan Web Connector

The Liqui-tect panel will interface with Liebert’s SiteScan Web enterprise monitoring system. SiteScan can be used to monitor the Liqui-tect panel from a host computer and silence the audible alarm. The terminal block connector, TB8, is on the bottom edge of the board, near the left corner.

To connect the SiteScan Web to the Liqui-tect panel:

1. Disconnect electrical power to the Liqui-tect panel. 2. If necessary, remove a conduit knockout to permit wire entry into the Liqui-tect panel enclosure. 3. Bring the wire(s) into the Liqui-tect panel enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. Note that the wires are polarity sensitive. 5. Tighten the screw until it holds the wire snugly.

RS422 SiteScan Web connector

3.5 Disable the Audible Horn

The panel’s audible horn is enabled by default. You may disable it as follows:

1. Set DIP switch 1, the first switch, to the ON position (up) to disable the audible horn. 2. Press the reset button to initiate the change.

DIP switch 1 Audible horn

Emerson MC68HC16Z1 — 3.5 Disable the Audible Horn diagram (page 21)
Fig. 22 · 3.5 Disable the Audible Horn

To re-enable the horn, set DIP switch 1, the first switch, to the OFF position (down) and press the reset button.

Connections and Configuration · Reset switch

Page 22 of the Emerson MC68HC16Z1 user manual — 5.0 VIEW STATUS > SYSTEM AND CONTROL
Page 22 · click to enlarge
Page 22

4.0 O VERVIEW OF M ENUS

The Liqui-tect panel displays the Opening Screen at startup, as shown in Figure 14.

If any alarms are active, the Current Alarm screen appears. (Pressing any key on the LCD keypad will silence the audible alarm.)

If no alarms are present, the LCD screen will alternately display the Opening Screen and a screen showing NO ALARMS PRESENT.

If no alarms are present and the Enter ↵ (Return) key is pressed, the Main Menu appears and pre- sents two choices that lead to all functions within the panel:

  • View Status (see 5.0 - View Status Options for step-by-step instructions)
  • System and Control (see 6.0 - System and Control Options for detailed instructions)

4.1 View Status Overview

The View Status features are available to all users—no password is required. This permits all person- nel to check on the status of any equipment or location being monitored. From this menu, any user may:

  • View cable status, the monitored cable length and the amount of current present (both zones)
  • View data stored in the Alarm History Log
  • View data stored in the Zone Trend Log

4.2 System and Control Overview

The System and Control options require a password. Authorized users may:

  • Configure the Liqui-tect panel
  • Reset any latched alarms
  • Delete all records from the Alarm History Log
  • Delete all records from the Zone Trend Log

Figure 14 Menu overview

LIQUI-TECT PANEL DD-MON-YY HR:MM:SS

(If any alarm is detected, it appears automatically)

VERSION X.X.X PRESS ↵ =STATUS/SETUP

VIEW STATUS SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

“View Status” selected See Section “System & Control” selected See Section > VIEW STATUS

5.0 VIEW STATUS > SYSTEM AND CONTROL

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

↑↓ =NEXT ↵ =SELECT

View Status Menu (All users - no password) See Section

System & Control Menu (Password required) See Section VIEW CABLE STATUS VIEW ALARM HISTORY VIEW ZONE TREND

5.1 5.2 5.3

SETUP SYSTEM RESET LATCHED ALARM CLEAR ALARM HISTORY CLEAR ZONE TREND

6.2 6.9 6.10 6.11

Overview of Menus · Opening Screen · Main Menu

Page 23 of the Emerson MC68HC16Z1 user manual — 5.0 V IEW S TATUS O PTIONS
Page 23 · click to enlarge
Page 23

5.0 V IEW S TATUS O PTIONS

The View Status menu allows any user to view the status of cables in both zones, an alarm history log and a trend log for both zones. The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item.

This section presents step-by-step instructions for each of the following options:

  • View Cable Status
  • View Alarm History
  • View Zone Trend

Figure 15 shows the main options available from the View Status menu.

Figure 15 Menu overview - View Status menu

Emerson MC68HC16Z1 — 5.0 V IEW S TATUS O PTIONS diagram (page 23)
Fig. 23

VIEW CABLE STATUS VIEW ALARM HISTORY VIEW ZONE TREND ↑↓=NEXT ↵=SELECT

View Alarm History > ALARM RECORD 100/100 ZONE 1 CABLE OK 29-AUG-03 12:04:00

View Zone Trend > ZONE TREND 288/288 ZONE 1 0 UA ZONE 2 0 UA 29-AUG-03 12:04:00

See Section 5.1

See Section 5.2

See Section 5.3

Emerson MC68HC16Z1 — 5.0 V IEW S TATUS O PTIONS diagram (page 23)
Fig. 24
Emerson MC68HC16Z1 — 5.0 V IEW S TATUS O PTIONS diagram (page 23)
Fig. 25
STATUS ZN1 ZONE 1 LENGTH1000FT CURRENT: 0UA ↑↓ =NEXT ↵ =DONE
STATUS ZN2 ZONE 2 LENGTH3500FT CURRENT: 0UA ↑↓ =NEXT ↵ =DONE
Show 4 more labels / short text on this page
View Status Options · Opening Screen · View Status options · View Cable Status
Page 24 of the Emerson MC68HC16Z1 user manual — Cable Length & Current Value
Page 24 · click to enlarge
Page 24

5.1 View Cable Status

The Cable Status screens display the overall status of the cable con- nected to each of the two zones monitored by the Liqui-tect panel, as well as the length of the cable being monitored and the amount of cur- rent present in each cable.

> VIEW STATUS

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To view the status of the cable:

View Status Menu > VIEW CABLE STATUS

  • From the Main Menu, use the arrows ↑↓ to choose View Status , as shown at right, and then press Enter ↵ .
  • From the View Status Menu, use the arrows ↑↓ to choose View Cable Status and press Enter ↵ .

VIEW ALARM HISTORY VIEW ZONE TREND ↑↓=NEXT ↵=SELECT

5.1.1 Cable Status Screens

Each Cable Status screen displays the zone name (ZN1 or ZN2) and its label (for example, ZONE 1 or ZONE 2) at the top.

STATUS ZN1 ZONE 1

NORMAL ↑↓ =NEXT

Viewing Additional Screens

There are four Cable Status screens—two for each zone.

Length & Current (ZN1)

  • To view additional screens, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.
  • When finished viewing the last screen, press Enter ↵ .
STATUS ZN1 ZONE 1 LENGTH1000FT CURRENT: 0UA ↑↓ =NEXT ↵ =DONE

Overall Condition

The first screen for each zone shows:

STATUS ZN2 ZONE 2

  • the zone name ( ZN1 or ZN2 ) and its label (for example, ZONE 1 or ZONE 2 )
  • the current overall condition of the cable (for example, NORMAL )

NORMAL ↑↓ =NEXT

The cable conditions tracked by the Liqui-tect panel appear in Table 5.

Length & Current (ZN2)

Table 5 Overall cable conditions

STATUS ZN2 ZONE 2 LENGTH3500FT CURRENT: 0UA ↑↓ =NEXT ↵ =DONE

SOURCE Cable CONDITIONS RECORDED

NORMAL CABLE BREAK LEAK DETECTED (& location, e.g., LEAK @ 99 FT) CONTAMINATED (& location, e.g., CONTAM @ 44 FT) NOT INSTALLED

Cable Length & Current Value

The second screen for each zone shows:

  • the zone name ( ZN1 or ZN2 ) and its label (for example, ZONE 1 or ZONE 2 )
  • the length of cable being monitored (for example, 1000FT )—this value may change dynamically by up to 0.5% as the panel is continuously calculating the distance of the connected cable
  • the current reading ( 0UA , where UA represents µA or microAmps)
Show 4 more labels / short text on this page
View Status Options · Main Menu · Overall Condition (ZN1) · Overall Condition (ZN2)
Page 25 of the Emerson MC68HC16Z1 user manual — HISTORY LOG EMPTY
Page 25 · click to enlarge
Page 25

5.2 View Alarm History

The Alarm History Log contains up to 100 records of alarms that have occurred. Records are added to this log as alarms occur.

> VIEW STATUS

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To view the Alarm History Log:

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Alarm History , then press Enter ↵ .

VIEW CABLE STATUS > VIEW ALARM HISTORY

VIEW ZONE TREND ↑↓ =NEXT ↵ =SELECT

5.2.1 Alarm History Log

The Alarm History Log screen displays up to 100 records showing alarms generated from the cable, panel operations, return from alarm and loss of power. If the log contains any alarm records, the Alarm His- tory Log screen displays details for each alarm:

Alarm History Log > ALARM RECORD 01/100

ZONE 1 CABLE OK 29-AUG-03 12:04:00

  • the source of the alarm (for example, ZONE 1 or ZONE 2 )
  • a brief description of the problem ( CABLE OK )
  • the date and time the alarm occurred

Table 6 shows conditions that the alarm history log records for analog inputs and the panel itself.

Table 6 Alarm History Log conditions

Source Cable Input Panel CONDITIONS RECORDED

CABLE BREAK LEAK DETECTED (& location, e.g., LEAK @ 99 FT) CONTAMINATED (& location, e.g., CONTAM @ 44 FT) NO LEAK CABLE OK

LOSS OF POWER ALARM SILENCED H/W RESET ALARM RESET

If there are no alarms in the log, the screen displays the message:

HISTORY LOG EMPTY

Viewing Additional Screens

There may be up to 100 records of alarm data.

  • To view additional records, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.

View Status Options · Main Menu · View Status Menu

Page 26 of the Emerson MC68HC16Z1 user manual — TREND DATA EMPTY
Page 26 · click to enlarge
Page 26

5.3 View Zone Trend

The Zone Trend Log contains up to 288 records that are recorded at regular intervals (every 24 hours) to assist users with verifying opera- tional and troubleshooting problems. Records are added the beginning of the log as they occur.

> VIEW STATUS

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To view the Zone Trend Log:

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Zone Trend , then press Enter ↵ .

VIEW CABLE STATUS VIEW ALARM HISTORY > VIEW ZONE TREND

↑↓ =NEXT ↵ =SELECT

5.3.1 Zone Trend Log

Zone Trend Log > ZONE TREND 01/288 ZONE 1 0UA ZONE 2 0UA 29-AUG-03 12:04:00

The Zone Trend Log screen displays up to 288 recent readings for each zone. If the log contains any records, the Zone Trend Log screen dis- plays details for each zone:

  • the name of the zone (for example, ZONE 1 or ZONE 2 )
  • the value for the amount of current present on each cable (for example, 0UA , where UA represents µA or microAmps)
  • the date and time of the reading

If there are no records in the log, the screen displays the message:

TREND DATA EMPTY

Viewing Additional Screens

There may be up to 288 records of trend data for each zone.

  • To view additional records, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.

View Status Options · Main Menu · View Status Menu

Page 27 of the Emerson MC68HC16Z1 user manual — AAAA ↑↓ =SELECT ↵ =NEXT/END
Page 27 · click to enlarge
Page 27

6.0 S YSTEM AND C ONTROL O PTIONS

The System and Control menu allows you to configure the Liqui-tect panel—setting up inputs and outputs and system features such as date and time. This menu also provides a vehicle for mapping points, clearing latched alarms and deleting records from the Liqui-tect panel’s alarm and trend logs.

The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item and enter new information. Table 7 shows characters that may be entered in labels and values.

Table 7 Valid characters for data entry

Alphanumeric Special characters A-Z, 0-9 space ! " # $ % & ( ) * + - / , . ; < = > @

The System and Control options require a password to prevent unauthorized users from making changes to the system.

This section presents step-by-step instructions for each of the following:

  • Login - enter the password
  • Setup System - configure the Liqui-tect panel, system features
  • Reset Latched Alarm - clear and reset any latched alarms
  • Clear Alarm History - delete all records from the Alarm History Log
  • Clear Zone Trend - delete all records from the Zone Trend Log

6.1 Login

Users must enter a password to access any of the system and control options. The password consists of four characters (see Table 7 for valid characters).

VIEW STATUS > SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

The default password is AAAA. Changing the password to “0000” eliminates the login requirement and prevents the login screen from appearing. (To set up or change the password, see 6.8.1 - Change Password.)

LOGIN

To log in:

AAAA ↑↓ =SELECT ↵ =NEXT/END

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ , as shown at right.
  • Use the arrows ↑↓ to choose System and Control , and press Enter ↵ . The Login menu appears.
  • To enter your password:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

System & Control Menu > SETUP SYSTEM

RESET LATCHED ALARM CLEAR ALARM HISTORY ↑↓=NEXT ↵=SELECT CLEAR ZONE TREND

The System and Control Menu appears next, with these options that are described in the following sections:

  • Setup System ( Section 6.2 - Section 6.8 )
  • Reset Latched Alarm ( Section 6.9 )
  • Clear Alarm History ( Section 6.10 )
  • Clear Zone Trend ( Section 6.11 )

Main Menu · Login

Page 28 of the Emerson MC68HC16Z1 user manual — AAAA
Page 28 · click to enlarge
Page 28

Figure 16 shows the main options available from the System & Control menu.

Figure 16 Menu overview - System and Control menu

LIQUI-TECT PANEL DD-MON-YY HR:MM:SS

VERSION X.X.X PRESS ↵ =STATUS/SETUP

VIEW STATUS > SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

LOGIN

AAAA ↑↓ =SELECT ↵ =NEXT/END

System & Control options

> SETUP SYSTEM

See Section 6.2

See Section 6.9

See Section 6.10

See Section 6.11

SETUP SYSTEM > RESET LATCHED ALARM

SETUP SYSTEM RESET LATCHED ALARM > CLEAR ALARM HISTORY

SETUP SYSTEM RESET LATCHED ALARM CLEAR ALARM HISTORY > CLEAR ZONE TREND

RESET LATCHED ALARM CLEAR ALARM HISTORY CLEAR ZONE TREND

CLEAR ALARM HISTORY CLEAR ZONE TREND

CLEAR ZONE TREND

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

RESET LEAK & FAULT LATCHED ALARMS? Y

CLEAR ALARM HISTORY ARE YOU SURE? Y

CLEAR ZONE TREND ARE YOU SURE? Y

↑↓ =Y/N ↵ =END

↑↓ =Y/N ↵ =END

↑↓ =Y/N ↵ =END

Setup Zone 1 Menu

See Section 6.3

See Section 6.5

See Section 6.7

SETUP ZN1 ZONE 1 CONNECTEDN LABEL: ZONE 1 UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

SELECT LONGEST CABLE CONNECTED > 0-500FT (0-152.4 M)

SELECT ZONE TO MAP > ZN1 ZONE 1

ZN2 ZONE 2 VIEW LAST MAP

0-1000FT (0-304.8M) 0-1500FT (0-472.2M) 0-2000FT (0-609.6M) 0-2500FT (0-762.0M) 0-3000FT (0-914.4M) 0-4000FT(0-1219.2M) 0-5000FT(0-1524.0M)

MAPPING ZN1 ZONE 1 CURRENT0UA DISTANCE: ---- ENTRIES:0 ESC=EXIT

Setup Zone 2 Menu

SETUP ZN2 ZONE 2 CONNECTEDN LABEL: ZONE 2 UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

See Section 6.4

Normally Open / Closed

ARE LEAK & FAULT RELAYS NORMAL OPEN OR NORMAL CLOSED? NO ↑↓=NO/NC ↵=END

CHANGE REALARM DELAY

See Section 6.6

5 MINUTES ↑↓ =SELECT ↵ =END

IS LEAK & FAULT ALARM LATCHED? Y

↑↓ =Y/N ↵ =END

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME FACTORY DEFAULTS

See Section 6.8

Setup System Info options

Change Password Change Date & Time Factory Defaults CHANGE PASSWORD

See Section 6.8.1

CHANGE DATE & TIME DAYLIGHT SVG TIME: Y

See Section 6.8.2

RESTORE ALL DEFAULTS ARE YOU SURE? N

See Section 6.8.3

AAAA

18-MAY-02 10:56:30

Show 17 more labels / short text on this page
Opening Screen · Main Menu · Login Screen · Setup System · Reset Latched Alarm · Clear Alarm History · Clear Zone Trend · Reset Latched Alarms · Clear Alarm History · Clear Zone Trend · Setup System options · Setup Alarm Outputs · Setup Mapmode · Mapping Options · Change Realarm Delay · Latched / Unlatched · Setup System Info
Page 29 of the Emerson MC68HC16Z1 user manual — SETUP ZN1 ZONE 1 > CONNECTED: N
Page 29 · click to enlarge
Page 29

6.2 Setup System - Overview

The Setup System screen displays six options that allow you to configure zones with cable, alarm outputs, the re-alarm delay time, log points to create a map and system details, such as changing the login password or the system date and time:

  • Setup ZN1 Zone 1
  • Setup ZN2 Zone 2
  • Setup Alarm Outputs
  • Setup Re-Alarm Delay
  • Setup Mapmode
  • Setup System Info

6.3 Setup System - Setup ZN1 Zone 1

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that may be configured individually. Each zone can monitor up to 5,000 ft. (1524m) of cable.

> SETUP ZN1 ZONE 1

SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

If neither zone is configured as connected, the screen displays the message:

WARNING! NO ZONES ARE INSTALLED

To configure the first zone:

Setup Zone 1 Menu

SETUP ZN1 ZONE 1 > CONNECTED: N

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

LABEL: ZONE 1 ↑↓=NEXT ↵=SELECT UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

Select Zone 1 to Configure

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup ZN1 Zone 1 and press Enter ↵ .
  • Use the steps following Table 8 to change the default settings for Zone 1.

Table 8 shows the features you may change for Zone 1, along with the default settings. By default, Zone 1 is not connected.

To activate Zone 1, you must specify it as connected. Other features that may be altered include the name of the zone, the measurement units, and the sensitivity for detection of water and of contamina- tion. You may also initiate automatic calibration, during which the Liqui-tect panel determines the length of cable and parameters.

Table 8 Default settings - Zone 1

Feature Default Other Options

CONNECTED N (Not connected) Y (Connected)

LABEL ZONE 1 Any name (up to eight characters)

UNITS FT (feet) M (meters)

AUTO CALIBRATE Automatically calculates cable length Allows adjustment to calculated length of cable

SENSITIVITY FOR WATER DETECT 150 UA Can define between 25µA and 300µA

SENSITIVITY FOR CONTAMINATED 50 UA Can define between 20µA and 300µA

Setup System Menu

Page 30 of the Emerson MC68HC16Z1 user manual — AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA
Page 30 · click to enlarge
Page 30

6.3.1 Identify the Zone as Connected

Setup Zone 1 Menu

To make use of the zone ZN1, you must specify it as Connected (Y). By default, ZN1 is Not connected (N). See 3.1 - Connecting Leak Detec- tion Cable Inputs for instructions on connecting the cable to this zone.

SETUP ZN1 ZONE 1 > CONNECTED: N

LABEL: ZONE 1 ↑↓=NEXT ↵=SELECT UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

  • From the Setup Zone 1 Menu, choose Connected , as shown at right, and press Enter ↵ .
  • To change this feature, use the arrows ↑↓ to choose Y (Yes - Connected) or N (No - Not connected), then press Enter ↵ .

IS CABLE CONNECTED TO THIS ZONE? Y

↑↓ =Y/N ↵ =END

6.3.2 Change Zone Label

Setup Zone 1 Menu

ZN1 has a default label (Zone 1) that you may change to a more descriptive name, such as “SRVR RM1.” The label may consist of up to eight characters (see Table 7 for valid characters).

SETUP ZN1 ZONE 1 CONNECTEDY > LABEL: ZONE 1
↑↓ =NEXT ↵ =SELECT UNITSFT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA
  • From the Setup Zone 1 Menu, choose Label , then press Enter ↵ .
  • To change the label, which may consist of up to eight characters:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

CHANGE ZONE LABEL

LABEL: ZONE 1 ↑↓ =SELECT ↵ =NEXT/END

6.3.3 Change Units Label

Setup Zone 1 Menu

You may specify measurement units as feet (FT) or meters (M). The default designation is FT (feet). The same measurement unit will apply to both zones. For example, if you choose FT for Zone 1, Zone 2 will display in FT also.

SETUP ZN1 ZONE 1 CONNECTEDY LABEL: ZONE 1 ↑↓ =NEXT ↵ =SELECT > UNITS: FT
  • From the Setup Zone 1 Menu, choose Units , then press Enter ↵ .
  • To change the units label:
  • Use the arrows ↑↓ to choose FT (feet) or M (meters).
  • Press Enter ↵ .

AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

CHANGE UNITS

UNITS: FT

↑↓ =FT/M ↵ =END

Zone Connected · Change Zone Label · Change Units Label

Page 31 of the Emerson MC68HC16Z1 user manual — CHANGE SENSITIVITY
Page 31 · click to enlarge
Page 31

6.3.4 Auto Calibration

Setup Zone 1 Menu

The auto calibration feature is designed to allow compensation for the resistance tolerances in the two legs of the sensing wires.

SETUP ZN1 ZONE 1 CONNECTEDY LABEL: ZONE 1 ↑↓ =NEXT ↵ =SELECT UNITS: FT > AUTO CALIBRATE

As soon as cable is connected, the panel begins calculating the cable length. Initiating the auto calibration feature allows the user to mod- ify the distance to account for any discrepancies. Once the new dis- tance is entered, the panel adjusts for the required offset between the calculated value and the user value.

WATER DETECT:150 UA CONTAMINATED:050 UA

To initiate automatic calibration for ZN1:

  • From the Setup Zone 1 Menu, choose Auto Calibrate , as shown at right, and press Enter ↵ .
  • At the Change Maximum Length screen, you may change the maximum length of cable protecting this zone:

CHANGE MAX LENGTH

1000 FT ↑↓ =SELECT ↵ =ACCEPT

  • To begin calibration without changing this value, press Enter ↵ .
  • To change the value, press and hold one of the arrow keys ↑↓ to scroll through the numbers, then press Enter ↵ .
  • The next screen displays the progress of calibration.

THIS SCREEN WILL SHOW AUTO CALIBRATION TAKING PLACE

6.3.5 Set Up Sensitivity for Water Detection

Setup Zone 1 Menu

Each zone may be set up with a sensitivity level at which water is detected.

SETUP ZN1 ZONE 1 CONNECTED: Y LABEL: ZONE 1 ↑↓=NEXT ↵=SELECT UNITS: FT AUTO CALIBRATE > WATER DETECT:150 UA

  • The most sensitive setting is 25 µA—minimal water is required to trigger an alarm.
  • The least sensitive setting is 300 µA. At this setting, the cable will be submerged in water for a longer period before an alarm is triggered.

CONTAMINATED:050 UA

To change the setting:

  • From the Setup Zone 1 Menu, choose Water Detect , as shown at right, and press Enter ↵ .
  • The Water Detection Sensitivity screen displays the value for detection of water (in the example at right, 150 UA , where UA represents µA or microAmps):

CHANGE SENSITIVITY

FOR WATER DETECT

150 UA ↑↓ =SELECT ↵ =END

  • To change the value, press and hold one of the arrow keys ↑↓ to scroll through the numbers 25-300.
  • Press Enter ↵ .

Change Maximum Length · Auto Calibration Progress · Water Detection Sensitivity

Page 32 of the Emerson MC68HC16Z1 user manual — CHANGE SENSITIVITY
Page 32 · click to enlarge
Page 32

6.3.6 Set Up Sensitivity for Contamination Detection

Setup Zone 1 Menu

Each zone may be set up with a sensitivity level at which contamina- tion on the cable is detected. Examples are construction debris and dust.

SETUP ZN1 ZONE 1 CONNECTED: Y LABEL: ZONE 1 ↑↓=NEXT ↵=SELECT UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA > CONTAMINATED:050 UA

  • The most sensitive setting is 20 µA—light contamination will trigger an alarm.
  • The least sensitive setting is 300 µA. This setting requires heavy contamination to activate an alarm.

Increase the setting if nuisance alarms occur.

CHANGE SENSITIVITY

FOR CONTAMINATED

50 UA ↑↓ =SELECT ↵ =END

  • From the Setup Zone 1 Menu, choose Contaminated , as shown above right, and press Enter ↵ .
  • The Contaminated Detection Sensitivity screen displays the value for detection of contamination (in the example at right, 50 UA , where UA represents µA or microAmps):
  • To change the value, press and hold one of the arrow keys ↑↓ to scroll through the numbers 20-300.
  • Press Enter ↵ .

Contamination Detection Sensitivity

Page 33 of the Emerson MC68HC16Z1 user manual — SETUP ZN2 ZONE 2 > CONNECTED: N
Page 33 · click to enlarge
Page 33

6.4 Setup System - Setup ZN2 Zone 2

SETUP ZN1 ZONE 1 > SETUP ZN2 ZONE 2

SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that may be configured individually. Each zone can monitor up to 5,000 ft. (1524m) of leak detection cable.

To configure the second zone:

Setup Zone 2 Menu

SETUP ZN2 ZONE 2 > CONNECTED: N

  • In the Setup System Menu, choose Setup ZN2 Zone 2 (see above right).
  • Follow the same procedures used in setting up Zone 1, as described in the previous section, 6.3 - Setup System - Setup ZN1 Zone 1 .

LABEL: ZONE 2 ↑↓=NEXT ↵=SELECT UNITS: FT AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA

Setup System Menu

Page 34 of the Emerson MC68HC16Z1 user manual — IS LEAK & FAULT ALARM LATCHED? Y
Page 34 · click to enlarge
Page 34

6.5 Setup System - Setup Alarm Outputs

The Liqui-tect panel has six alarm outputs—three types for each zone:

  • Digital alarm output for cable break detection - a change in state indicates a broken cable or contamination on the cable
  • Digital alarm output for leak detection - a change in state indicates a leak on the cable
  • Analog alarm output for 4-20mA - the signal may indicate normal operation, the location of a leak, a cable break or contamination

These outputs may have a wide variety of Liebert or other manufacturers’ equipment connected to receive alarm notification.

To configure all alarm outputs:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 > SETUP ALARM OUTPUTS

↑↓=NEXT ↵=SELECT SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

Select Setup Alarm Outputs

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Alarm Outputs and press Enter ↵ .

Table 9 shows alarm output features and their default settings: you may specify the maximum cable length of analog alarm outputs, define digital alarm output relays as Normally Open or Closed, and set up alarms as Latched or Unlatched.

SELECT LONGEST CABLE CONNECTED > 0-500FT (0-152.4 M)

↑↓=NEXT ↵=SELECT 0-1000FT (0-304.8M) 0-1500FT (0-472.2M) 0-2000FT (0-609.6M) 0-2500FT (0-762.0M) 0-3000FT (0-914.4M) 0-4000FT(0-1219.2M) 0-5000FT(0-1524.0M)

To change the default settings, use the steps following Table 9.

Table 9 Default settings - alarm outputs

Feature Default Other Options

LONGEST CABLE LENGTH 0-1000 ft. (0-304.8m) Up to 5000 ft. (1524m)

LEAK & FAULT RELAYSNORMALLY OPEN/CLOSED NO (Normally Open) NC (Normally Closed)

Normally Open / Closed ARE LEAK & FAULT RELAYS NORMAL OPEN OR NORMAL CLOSED? NO ↑↓=NO/NC ↵=END

LEAK & FAULT ALARMLATCHED/UNLATCHED Y (Latched) N (Unlatched)

IS LEAK & FAULT ALARM LATCHED? Y

↑↓ =Y/N ↵ =END

Setup System Menu · Maximum Cable Length · Latched / Unlatched

Page 35 of the Emerson MC68HC16Z1 user manual — ↑↓ =Y/N ↵ =END
Page 35 · click to enlarge
Page 35

6.5.1 Specify Longest Cable Length

You may specify the length of the longest cable connected to either of the 4-20mA alarm outputs. The default value is 0-1000 ft. (0-304.8m). Valid entries range from 0-500 ft. (0-152.4m) to 0-5000 ft. (0-1524m), as shown in the Maximum Cable Length screen, below right.

Select the longer cable length installed on either zone. For example, if Zone 1 has 2000 ft. (609.6m) of cable and Zone 2 has 3500 ft. (1066.8m), select 0-4000 ft. (0-1219.2m).

The chosen setting applies to both zones and is correlated to the 4-20mA output of each zone to pro- vide the distance of the leak. Once the range is selected, the following correlation will be applied:

5mA = 0 ft. (0m) 19mA = 4000 ft. (1219.2m)

Table 10 shows the operation of the 4-20mA outputs.

Table 10 Operation of 4-20mA outputs

0mA Indicates cable cannot be monitored

4mA Indicates normal operation

5mA 0 ft. (0m)

19mA Longest cable length (ft.)—for example, 4000 ft. (1219.2m)

20mA Indicates cable fault / contamination

To specify the maximum cable length:

  • From the Maximum Cable Length screen, below right, use the arrows ↑↓ to choose the correct range—for example, 0-4000FT(0-1219.2M) .
  • Press Enter ↵ .

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 > SETUP ALARM OUTPUTS

↑↓=NEXT ↵=SELECT SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

6.5.2 Define Relays as Normally Open or Normally Closed

All four digital alarm outputs may be set up as Normally Open (NO) or Normally Closed (NC). The default setting is NO (Normally Open). The chosen setting applies to all cable fault/contamination and leak relays for both zones.

SELECT LONGEST CABLE CONNECTED > 0-500FT (0-152.4 M)

To change the normal state:

  • From the Normally Open / Closed screen, below right, use the arrows ↑↓ to choose NO (Normally Open) or NC (Normally Closed).

↑↓=NEXT ↵=SELECT 0-1000FT (0-304.8M) 0-1500FT (0-472.2M) 0-2000FT (0-609.6M) 0-2500FT (0-762.0M) 0-3000FT (0-914.4M) 0-4000FT(0-1219.2M) 0-5000FT(0-1524.0M)

  • For a non-supervised mode , select Normally Open. The relays energize for an alarm condition.
  • For a supervised mode , select Normally Closed. The relays de-energize for an alarm condition or loss of power.
  • Press Enter ↵ .

6.5.3 Define Alarms as Latched or Unlatched

Normally Open / Closed ARE LEAK & FAULT RELAYS NORMAL OPEN OR NORMAL CLOSED? NO ↑↓=NO/NC ↵=END

All four digital alarm outputs may be set up as Latched (Y) or Unlatched (N). When configured as Latched, alarms must be manually reset by an operator after they are cleared, as described in 6.9 - Reset Latched Alarms. The default setting is Latched (Y). The chosen set- ting applies to cable fault and leak relays for both zones.

To change this setting:

IS LEAK & FAULT ALARM LATCHED? Y

  • From the Latched / Unlatched screen, shown at right, use the arrows ↑↓ to choose Y (Latched) or N (Unlatched).
  • Press Enter ↵ .

↑↓ =Y/N ↵ =END

Show 4 more labels / short text on this page
Signal Operation · Setup System Menu · Maximum Cable Length · Latched / Unlatched
Page 36 of the Emerson MC68HC16Z1 user manual — CHANGE REALARM DELAY
Page 36 · click to enlarge
Page 36

Following are some similarities and differences between Latched and Unlatched alarms.

Liqui-tect System’s Response to Alarms - Both Latched and Unlatched

When a leak or cable break is detected:

  • An alarm occurs,
  • A record is created in the Alarm History Log and
  • The leak-detected or cable-break alarm output contact changes state.

Latched Alarms Only

The user must reset latched alarms before another leak or cable break alarm can occur.

Unlatched Alarms Only

When an alarm output returns to its normal state, the alarms automatically clear and the system returns to normal.

If two leaks occur simultaneously on the same cable, the system creates a record with the distance of the first leak and displays an average distance for the two leaks. Always check the Alarm History Log (see 5.2 - View Alarm History) when leak detected alarms occur in unlatched mode.

6.6 Setup System - Setup Re-Alarm Delay

The re-alarm delay may be set to provide an audible, reminder alarm notification after an alarm has been silenced. The timer begins when the original alarm is silenced; the reminder alarm will occur after the specified delay time has expired. The default setting is 5 minutes. The delay time ranges from 0 to 999 minutes.

To set up the re-alarm delay:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT > SETUP REALARM DELAY

Select Setup Re-Alarm Delay

SETUP MAPMODE SETUP SYSTEM INFO

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Realarm Delay and press Enter ↵ .
  • From the Change Realarm Delay screen, shown at right, press and hold one of the arrow keys ↑↓ to scroll through the numbers, then press Enter ↵ .

CHANGE REALARM DELAY

5 MINUTES ↑↓ =SELECT ↵ =END

Setup System Menu · Change Realarm Delay

Page 37 of the Emerson MC68HC16Z1 user manual — SELECT ZONE TO MAP > ZN1 ZONE 1
Page 37 · click to enlarge
Page 37

6.7 Setup System - Setup Mapmode

Mapping involves measuring the exact location of various points along the leak detection cable. This greatly simplifies the use of the Liqui-tect Monitoring System to quickly pinpoint the location of a leak. The Liqui-tect Monitoring System determines the location of a leak by computing its distance along the leak detection cable. By setting off alarms with a damp paper towel or sponge and marking each reading on a map of the floor, you can define various points along the cable for later reference in finding a leak. Up to 254 points can be mapped.

After the leak detection cable has been laid and properly connected, as described in 3.1 - Connecting Leak Detection Cable Inputs, follow these steps to map the system:

1. Draw a floor plan that shows the routing of the leak detection cable, including any jumpers used (non-sensing cable). 2. Using the LCD on the front panel of the Liqui-tect Monitoring System:

Log In and Choose Setup System a. From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter ↵ (see 6.1 - Login for help). b. Enter your password at the Login screen. c. From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter ↵.

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT SETUP REALARM DELAY > SETUP MAPMODE

Select Setup Mapmode d. From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Mapmode and press Enter ↵. e. Use the following instructions to set up the mapping of each zone.

SETUP SYSTEM INFO

Select Zone to Map

Set Up Mapping for Zone 1 or Zone 2 f. Use the arrows ↑↓ to choose a zone—either ZN1 Zone 1 or ZN2 Zone 2—from the Select Zone to Map Menu, and press Enter ↵. The Liqui-tect Monitoring System is now ready for you to short the cable, as described in steps 3 through 6. 3. Select the first point to be mapped and mark it on the floor map as point “X” (where X represents 1 for the first point, 2 for the second, and so on, up to 254). Determine the exact location of the point by measuring the distance from the panel to the point or otherwise describing its location (for example, “at front of chiller”). 4. Wrap a damp paper towel or sponge around the selected point on the cable to cause a short in the cable and trigger an alarm. 5. After about 30 seconds, the Liqui-tect panel annunciates a short beep. The LCD displays the computed distance to the leak. 6. Remove the paper towel and dry the cable. In approximately 20 seconds, the Liqui-tect panel annunciates a long beep indicating the short has been removed. 7. Go to the next point and repeat this process (steps 3 through 6) until the entire cable has been mapped. Up to 254 points can be mapped.

SELECT ZONE TO MAP > ZN1 ZONE 1

ZN2 ZONE 2 ↑↓=NEXT ↵=SELECT VIEW LAST MAP

Mapping Options MAPPING ZN1 ZONE 1 CURRENT: 0UA DISTANCE: ENTRIES:0 ESC=EXIT

When complete, press the ESC key on the LCD to exit mapping mode and return to the previous screen.

Table 11 shows the default mapping settings for each zone.

Table 11 Default mapping values

Current 0UA, where UA represents µA or microAmps

Setup System Menu · Option Default setting · Distance (none)

Page 38 of the Emerson MC68HC16Z1 user manual — THERE ARE NO MAPPED POINTS LOGGED
Page 38 · click to enlarge
Page 38

6.7.1 View Last Map

The View Last Map option allows you to review the mapped points from the last mapping of a zone. This feature is the data logger for the mapmode process described in the previous section, 6.7 - Setup Sys- tem - Setup Mapmode.

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT SETUP REALARM DELAY > SETUP MAPMODE

In the View Last Map mode, the Liqui-tect panel shows the mapped distance to a particular point along the leak detection cable, identify- ing each point with an entry number that corresponds to point “X” (where X represents 1 for the first point, 2 for the second, and so on).

SETUP SYSTEM INFO

Select Zone to Map

The user may view the entry number for point “X” and see the corre- sponding distance to that point. This may be used either to record that distance on the floor map or to verify the distance already recorded on the map.

SELECT ZONE TO MAP ZN1 ZONE 1 ZN2 ZONE 2 ↑↓=NEXT ↵=SELECT > VIEW LAST MAP

When a leak occurs, the Liqui-tect Monitoring System displays the distance of the leak. By referring to the final floor map, you can easily determine the location of the leak.

Mapping for Last Map MAPPING FOR LAST MAP CURRENT: 0UA DISTANCE: ENTRIES:0 ESC=EXIT

To view the last map:

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Mapmode and press Enter ↵ .
  • Use the arrows ↑↓ to choose View Last Map from the Select Zone to Map Menu, and press Enter ↵ . (If no points have been mapped, the screen displays a message, as shown below right.)
  • If you haven’t already done so, record the distance for each point on the final floor map next to the respective positions of each short labeled “X” (for points 1, 2, 3 and so on as described in step 3 in the previous section).
  • Use the arrows ↑↓ to display the mapping data for the next point.
  • When finished, press Enter ↵ .

Message if No Mapping

THERE ARE NO MAPPED POINTS LOGGED

ESC=EXIT

Setup System Menu

Page 39 of the Emerson MC68HC16Z1 user manual — Reset Password to the Factory Default (“AAAA”)
Page 39 · click to enlarge
Page 39

6.8 Setup System - Setup System Info

The Setup System Info options allow users to:

  • Change Password —used for access to system setup functions
  • Change Date & Time/Automatic Daylight Saving Time —used to set the Liqui-tect panel’s date and time and to enable automatic time change for Daylight Saving Time
  • Restore Defaults— returns the Liqui-tect panel to its factory settings

To change any Setup System Info features:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2 SETUP ALARM OUTPUTS ↑↓=NEXT ↵=SELECT SETUP REALARM DELAY SETUP MAPMODE > SETUP SYSTEM INFO

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup System Info and press Enter ↵ .
  • Use the following steps to access any of the Setup System Info options.

6.8.1 Change Password

Setup System Info Menu

A password is required to access the Liqui-tect panel’s system and control options, as described in 6.1 - Login. The password consists of four characters (see Table 7 for valid characters). The default pass- word is AAAA.

SETUP SYSTEM INFO > CHANGE PASSWORD

CHANGE DATE & TIME ↑↓=NEXT ↵=SELECT FACTORY DEFAULTS

Changing the password to “0000” eliminates the login requirement and prevents the login screen from appearing.

Change the Password

CHANGE PASSWORD

To change the password:

AAAA ↑↓ =SELECT ↵ =NEXT/END

  • From the Setup System Info Menu, use the arrows ↑↓ to choose Change Password , then press Enter ↵ .
  • To change your password:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

Reset Password to the Factory Default (“AAAA”)

To reset the password to the factory default of AAAA:

  • Locate DIP switch 1 on the unit’s circuit board (see 1.4 - Controller Board Overview ) and move switches 2, 7 and 8 to the OFF position (down).
  • Move the second switch to the ON position, then to the OFF position.
  • Move the seventh switch to the ON position, then to the OFF position.
  • Move the eighth switch to the ON position, then to the OFF position.

The password should now be AAAA.

Setup System Menu · Select Setup System · Change Password

Page 40 of the Emerson MC68HC16Z1 user manual — ↑↓ =Y/N ↵ =END
Page 40 · click to enlarge
Page 40

6.8.2 Change Date & Time/Automatic Daylight Saving Time

The Liqui-tect panel has a built-in, real-time clock that is backed up by an encapsulated lithium bat- tery and set up to adjust automatically for daylight saving time twice a year. The Setup System Info menu allows you to change the date or time or automatic adjustment at any time.

To change the daylight saving time setting, date or time:

Setup System Info Menu

  • From the Setup System Info Menu, use the arrows ↑↓ to choose Change Date & Time , then press Enter ↵ .
  • To change the daylight saving time setting:
  • To the right of Daylight Svg Time? use the arrows ↑↓ to choose Y (Yes - automatically adjust for daylight saving time) or N (No), then press Enter ↵ .
  • The format of the date and time is DD-MMM-YY HR:MM:SS . To change the date or time:

SETUP SYSTEM INFO CHANGE PASSWORD > CHANGE DATE & TIME

↑↓ =NEXT ↵ =SELECT FACTORY DEFAULTS

Change Date & Time

CHANGE DATE & TIME DAYLIGHT SVG TIME? Y

  • Press Enter ↵ to advance to the next character position you want to change.
  • Use the arrows ↑↓ to choose from available entries:

30-APR-03 10:56:30 ↑↓ =SELECT ↵ =NEXT/END

Date Day (DD) 0-31 Month (MMM) JAN-DEC Year (YY) 00-99 Time Hour (HR) 00-23 Minutes (MM) 00-59 Seconds (SS) 00-59

  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

6.8.3 Factory Defaults

Setup System Info Menu

At any time, you may restore all default values for settings in the Liqui-tect panel as it was shipped, as shown in Table 12.

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME ↑↓=NEXT ↵=SELECT > FACTORY DEFAULTS

The password is the sole exception when reverting to the factory default settings. The password can be reset to the factory default of AAAA only through the DIP switches. For details, see Change Password on page 35.

Factory Defaults RESTORE ALL DEFAULTS ARE YOU SURE? Y

Table 12 Factory default settings

Zones 1 & 2 CONNECTED N (Not connected)

↑↓ =Y/N ↵ =END

LABEL ZONE 1

SENSITIVITY FOR WATER DETECT 150 UA

SENSITIVITY FOR CONTAMINATED 50 UA

LONGEST CABLE LENGTH 0-1000 ft. (0-304.8m)

LEAK & FAULT RELAYSNORMALLY OPEN/CLOSED NO (Normally Open)
LEAK & FAULT ALARMLATCHED/UNLATCHED Y (Latched)

Mapping values Current 0UA, where UA represents µA or microAmps

Re-alarm delay Delay in minutes 5 minutes

Show 5 more labels / short text on this page
Feature Default · UNITS FT (feet) · AUTO CALIBRATE Automatic · Alarm outputs · Distance (none)
Page 41 of the Emerson MC68HC16Z1 user manual — ALARMS ARE NOT SET FOR LATCHING
Page 41 · click to enlarge
Page 41

6.9 Reset Latched Alarms

The Reset Latched Alarms menu allows you to clear any leak or fault alarms that have been defined as latched.

VIEW STATUS > SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To clear latched alarms:

Log In and Choose Reset Latched Alarm

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Reset Latched Alarm , then press Enter ↵ .

LOGIN

AAAA ↑↓ =SELECT ↵ =NEXT/END

Choose Y to Reset Alarms

System & Control Menu

SETUP SYSTEM > RESET LATCHED ALARM

  • From the Reset Latched Alarms Menu, use the arrows ↑↓ to choose Y (Yes - reset all latched alarms) or N (No - do not reset alarms). (If no alarms have been set up as latched, the screen displays a message, as shown below right.)
  • Press Enter ↵ .

CLEAR ALARM HISTORY ↑↓=NEXT ↵=SELECT CLEAR ZONE TREND

This is the only way to reset latched alarms. This step is required to return latched points to their normal state. (To set up digital alarm outputs as latched, see 6.5.3 - Define Alarms as Latched or Unlatched.)

RESET LEAK & FAULT LATCHED ALARMS? Y

↑↓ =Y/N ↵ =END

Message if No Latched Alarms

ALARMS ARE NOT SET FOR LATCHING

ESC=EXIT

Main Menu · Login · Reset Latched Alarms

Page 42 of the Emerson MC68HC16Z1 user manual — THERE ARE NO TRENDS
Page 42 · click to enlarge
Page 42

6.10 Clear Alarm History

The Clear Alarm History menu allows you to delete all records from the Alarm History Log, which contains up to 100 records of alarms that have occurred.

VIEW STATUS > SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To delete all records from the Alarm History Log:

Log In and Choose Clear Alarm History

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Clear Alarm History , then press Enter ↵ .

LOGIN

AAAA ↑↓ =SELECT ↵ =NEXT/END

System & Control Menu

Choose Y to Clear the Log

SETUP SYSTEM RESET LATCHED ALARM > CLEAR ALARM HISTORY

  • From the Clear Alarm History Menu, use the arrows ↑↓ to choose Y (Yes - clear the Alarm History Log) or N (No - do not clear the log). (If there are no alarms or trends, the screen displays a message, as shown below right.)
  • Press Enter ↵ .

↑↓ =NEXT ↵ =SELECT CLEAR ZONE TREND

CLEAR ALARM HISTORY ARE YOU SURE? Y

↑↓ =Y/N ↵ =END

Message if No Alarms

THERE ARE NO ALARMS

ESC=EXIT

Message if No Trends

THERE ARE NO TRENDS

ESC=EXIT

Main Menu · Login · Clear Alarm History

Page 43 of the Emerson MC68HC16Z1 user manual — CLEAR ZONE TREND ARE YOU SURE? Y
Page 43 · click to enlarge
Page 43

6.11 Clear Zone Trend

The Clear Zone Trend menu allows you to delete all records from the Zone Trend Log, which contains up to 288 records. These records are created every 24 hours to assist in troubleshooting.

VIEW STATUS > SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

To delete all records from the Zone Trend Log:

Log In and Choose Clear Zone Trend

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.1 - Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Clear Zone Trend , then press Enter ↵ .

LOGIN

AAAA ↑↓ =SELECT ↵ =NEXT/END

System & Control Menu

Choose Y to Clear the Log

SETUP SYSTEM RESET LATCHED ALARM CLEAR ALARM HISTORY ↑↓=NEXT ↵=SELECT > CLEAR ZONE TREND

  • From the Clear Zone Trend Menu, use the arrows ↑↓ to choose Y (Yes - clear the Zone Trend Log) or N (No - do not clear the log).
  • Press Enter ↵ .

CLEAR ZONE TREND ARE YOU SURE? Y

↑↓ =Y/N ↵ =END

Main Menu · Login · Clear Zone Trend

Page 44 of the Emerson MC68HC16Z1 user manual — UL UL3121 UL3121,
Page 44 · click to enlarge
Page 44

7.0 S PECIFICATIONS

7.1 Liqui-tect Panel Specifications

Small Enclosure Large Enclosure NOTE

LPS0240 115VAC LPL1150

230VAC LPL2300

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

24VAC ±10% of nominal; 50/60 Hz, 0.3A, 8VA

115VAC ±10% of nominal;

230VAC ±10% of nominal; 50 Hz, 0.5A, 115VA

60 Hz, 4A, 460VA

Dimensions W x D x H, in. (mm)

14-1/4 x 2-3/4 x 12 (361.95 x 69.85 x 304.8)

18 x 2-3/4 x 18 (457.2 x 69.85 x 457.2)

Weight (Assembled) 7.68 lb. (3.48 kg) 20.56 lb. (9.33 kg)

Enclosure Type NEMA 1

Liquid Crystal Display (LCD) Four line, 20 character, backlit

Mounting Surface Building Wall or Structural Member

32°F to 104°F (0°C to 40°C) 0% RH to 95% RH (non-condensing)

A/D Resolution (Analog IN) 14 bits

Clock Type Real-Time Clock

Clock battery backup type Internal

Clock battery life 10 years, constant, no power

SiteScan Web IGM Protocol, 422

Agency Listings No Transformer Module With Transformer Module

UL UL3121 UL3121,

UL3121,

UL1012

UL1585

CSA C22.2 No. 1010 C22.2 No. 1010,

C22.2 No. 1010, C22.2 No. 107.1

C22.2 No. 66

FCC Compliance CFR 47 Part 15

Inputs & Outputs (Quantity)

Cable Input (2) N/A

Analog Output (2) 4-20mA signal output

Alarm Output (4) 24VAC, 1A

Show 11 more labels / short text on this page
Specifications · Power Requirements · Ambient Operating Environment · Processor Specifics · Model MC68HC16Z1 · Clock speed 20MHz · Total RAM 128Kb · Total FLASH 256Kb · Total NVRam 32Kb · Communications · CE Yes Yes
Page 45 of the Emerson MC68HC16Z1 user manual — NOTES
Page 45 · click to enlarge
Page 45

NOTES

Specifications

Page 46 of the Emerson MC68HC16Z1 user manual — 7.0 Specifications
Page 46 · click to enlarge
Page 46

Specifications

Page 47 of the Emerson MC68HC16Z1 user manual — 7.0 Specifications
Page 47 · click to enlarge
Page 47
Page 47 of the Emerson MC68HC16Z1 user manual — 7.0 Specifications
Page 48 of the Emerson MC68HC16Z1 user manual — The Company Behind the Products
Page 48 · click to enlarge
Page 48

M ONITORING

L IQUI - TECT M ONITORING S YSTEM

U SER M ANUAL

The Company Behind the Products

Technical Support/Service

Web Site www.liebert.com

With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:

Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755

  • Environmental systems—close-control air conditioning from 1 to 60 tons
  • Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
  • Integrated systems that provide both environmental and power protection in a single, flexible package
  • Monitoring and control—from systems of any size or location, on-site or remote
  • Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center

800-222-5877 upstech@liebert.com Outside the US: 614-841-6755

800-543-2378 powertech@liebert.com

Outside the United States

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257

© 2004 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 Fax: +852 2 831 0114

SL-31000 (9/04) Rev. 0

Show 5 more labels / short text on this page
Single-Phase UPS · Three-Phase UPS · Environmental Systems · 800-543-2778 · 614-888-0246
Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
K1Zone 1 Leak Detected p.10
K3Zone 2 Leak Detected p.10
K4Zone 2 Cable Break p.10
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
24VAC power not available from TB1 or TB2Check fuse for respective output (TB1 or TB2). p.15

Ask about the Emerson MC68HC16Z1

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.