Liebert Liqui-tect® Leak Detection Sensors install quickly and work simply for reliable detection of conductive aqueous fluid leaks. The Liqui-tect 460 Sensor provides zone protection using the easy-to- install and quick-drying Liebert leak detection cable. LEDs located on the top cover of the module provide visual indication. A reset button provides optional manual acknowledgement of alarms. The top cover is hinged, allowing easy access to the electronics housed inside the steel enclosure. Terminal blocks allow easy interconnection of power and alarm outputs. Dual Form-C relay outputs can simultaneously signal the local alarm panel and remote monitoring system. The Liqui-tect 460 Sensor fea- tures supervised operation through alarms for cable faults, circuit fail- ure or loss of power, ensuring a completely self-monitored leak detection system. The LT460 is conveniently available in packaged kits with 20, 25, 30, 35 or 45 feet of leak detection cable and hold-down clips. Note that additional cable cannot be added to packaged kits. The LT460 sensor can also be purchased independently. The sensor can accommodate up to 100 feet of leak detection cable if the sensor and leak detection cables are purchased as independent components. Exterior Dimensions and Mounting Details



To a Liebert environmental
unit and an optional*
To external power supply or directly from unit (see Power Wiring on page 3) LT460
Leak detection zone (directly beneath unit)
* Output connections to external alarm monitoring panels such as the Liebert contact closure alarm panels
monitoring · panel · Leak detection cable

The LT460 is rated for 24 VAC, 50/60 Hz and 0.12 amp.

Liebert DS, Deluxe System/3, Challenger, Himod or Mini-Mate2 (8 ton) LT460
Liebert Deluxe Sys/3, Challenger, Himod or MM2 (8 Ton)
* Requires a 24V external transformer (there are no designated terminal connections on the unit)

The LT460 has two Form-C dry contact alarm output contacts (TB2 & TB3). Each contact is rated for 24 VAC at 3 amp.

Liebert Deluxe Sys/3, Challenger, Himod or MM2 (8 Ton)


A four-position DIP switch is used to select two alarm (filter) delays and three mutually exclusive alarm modes. The switches are located next to the wiring termination blocks.

SS1 selects the leak detect filter delay, the interval for which a leak condition must be continuously detected before an alarm is triggered:
OFF = 10 seconds (default) ON = 2 minutes This feature is useful for eliminat- ing nuisance alarms. SS1 works independently of the settings of SS2 and SS3. While the alarm delay is selectable (factory default is OFF=10 seconds), the cable fault delay is preset at approximately 2 seconds.
SS2 selects latching or non-latching alarms, the setting in which an alarm will latch ON until manually reset:
OFF = Non-latching (default) ON = Latching The factory default is OFF=Non-latching. If the sensor is in latching mode (ON=Latching) and the leak condition clears itself in the interim, a manual reset is required. While the alarm is latched, the sensor goes into a “sleep” mode and power to the leak detection cable is discontinued. De-powering the cable prevents damage to the cable should it be in contact with the conductive liquid for an extended duration. After a manual reset, the sensor resumes its normal opera- tion, continuously checking for leaks. If the leak condition has not yet cleared but the sensor is manually reset, the sensor will re-alarm after the appropriate leak detect filter delay. SS2 in the ON position will disable the operation of SS3.

SS3 selects the alarm retest delay, the setting in which an alarm is latched and retested every hour.
OFF = Non-latching (default) ON = Latching-retest each hour The factory default is OFF=Non-latching. If SS3=ON and a leak is detected, the alarm condition is latched, the sensor goes into a “sleep” mode and power to the leak detection cable is discontinued. After one hour, the sensor will automatically retest if the leak is still present. If the leak has cleared itself, the sensor deactivates the alarm, resets itself and resumes normal operation; if the leak is still present, the alarm condition remains activated and the sensor goes to “sleep” and retests in another hour. This procedure will repeat indefinitely until the leak is cleared or until the alarm is manually reset. A manual reset can be initiated at any time. If the leak condition has not yet cleared, the sensor re-alarms after the selected leak detect fil- ter delay; if the leak has cleared, the sensor deactivates the alarm and resets itself. SS3 is disabled if SS2=ON. The factory default settings of SS2=OFF and SS3=OFF place the sensor in a non-latching, continuous retest mode. The sensor does not go to “sleep” after detecting a leak—instead, it continually checks to determine whether the leak condition has cleared itself. Alarms auto- matically reset when the leak condition clears. Initiating a manual reset will cause the sensor to trigger the alarm again after the selected leak detect filter delay. The leak detect cable remains powered at all times. SS4 is not used.


System Normal (Green): • ON continuously when power is applied to sensor.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environ- ment. This equipment generates, uses, and can radiate radio fre- quency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio commu- nications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. In the event of a severe leak causing submersion or partial-submer- sion of the enclosure and/or the electronic circuitry inside the enclo- sure, the entire module should be returned to the factory for inspection.

1. Attach the leak detection cable to the LT460 module. 2. Activate module and test detection cable. (Touch detection cable with a clean moist cloth or paper towel.) Dry detection cable to remove the alarm condition. (A hair dryer can be used to speed up the drying.) Note: Do not try to saturate the detection cable for testing! It only requires a small amount of water to alarm. The detection cable will have to dry for the alarm condition to clear.


a. One pair every 6 to 8 feet in straight patterns (see Figure 6). b. One pair every 3 to 4 feet in circular patterns (see Figure 7). c. One pair at the beginning and end of the arc when turning
90 degrees (see Figure 8). d. One pair as needed to maintain consistent uniform contact
between the floor and detection cable.
Figure 7 Cable laid in circular patterns


3-4 ft.
6-8 ft.
clips at beginning &


Unit Detection on sides and in front of unit
Unit Detection on sides and in front of unit



Ensuring The High Availability Of Mission-Critical Data And Applications.
Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246
Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center
Philippines +63 2 687 6615 Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is the registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
Power Switching & Controls
Racks & Integrated Cabinets
Infrastructure Management & Monitoring
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.