7120 New Buffington Road Florence, KY 41042 Application Engineering: 800 626 2093
9178E Revised April 2012
Installation and Maintenance Manual For IntelliGear Plus™ MD and BW1/BW2 Variable Speed Drives

UL Listed E211799 Ind. Cont EQ. 54 DN
UL is believed to be a registered trade name and/or trademark of Underwriters Laboratories, Inc. and is NOT owned or controlled by Emerson Power Transmission. Emerson Power Transmission Corporation cannot and does not represent or warrant the accuracy of this information.
Emerson Industrial Automation · us

Thank you for choosing an IntelliGear Plus Gearmotor.

1.1 General operating principle 4 1.2 Product name 4 1.3 Environmental characteristics 4 1.4 Radio-frequency interference 5 1.4.1 General 5 1.4.2 Standards (Emissions) 5 1.4.3 Standards (Immunity) 5 1.5 Description of cables and protection devices (Customer Supplied) 5 1.6 UL conformity 5 1.6.1 Specified mains supply 5 1.6.2 Cables 5 1.6.3 Fuses 5 1.8 Dimensions 6-7
2.1 General 8
3.1 Control Terminal Blocks 8 3.2 Power terminal blocks 8 3.3 Wiring diagram based on standard configuration 9 3.4 Terminal Block Assignments and MD Functionality 10
5 Faults - Diagnostics...............................................................................................................................11
5.1 Troubleshooting Guide 11
7 Gear Parts List.......................................................................................................................................13
8 Motor Parts List.....................................................................................................................................14
Contents


1.1 - General operating principle
The IntelliGear Plus is a combination of a 3-phase induction motor and an integrated open loop vector variable speed drive. The motor can be combined with many gear types from Emerson Power Transmission’s range.
In the standard product version, the integrated drive does not require any connection other than the power supply. The options may be used to broaden the application range of the IntelliGear Plus.
IntelliGear Plus motors meet the requirements of the Low Voltage Directive 73/23/EEC, modified by 93/68/EEC. The harmonized standards of the DIN VDE 0160 series in connection with standard VDE 0660, part 500 and EN 60146/VDE 0558 are also applicable.
1.2 - Product name

1.3 - Environmental Characteristics


1.4 - Radio-frequency interference: 1.4.1 - General Variable speed drives use high-speed switches (transistors, semi-conductors) which switch high voltages (around 660V for 3-phase drives) at high frequencies (several kHz). This provides better efficiency and a low level of motor noise. As a result, they generate radio-frequency signals which may disturb operation of other equipment or distort measurements taken by sensors:
These phenomena are of direct interest to the user. The frequency range concerned (radio-frequency) does not affect the energy distribution company. 1.4.2 - Standards (Emission) The maximum emission level is set by (EN 50081-2) and (EN 50081-1). IntelliGear Plus conforms to:
1.4.3 - Standards (Immunity) The maximum immunity level is set by (EN 50082-2) and (EN 50082-1). IntelliGear Plus conforms to:
1.5 - Description of cables and protection devices (Customer Supplied)
1.6 - UL conformity 1.6.1 Special mains supply The drive can be incorporated in an installation with short circuit capacity of 5000 A rms maximum at voltage 264 VAC rms maximum for 230 V (TL) drives or 528 VAC rms maximum for 400 V (T) drives.
1.6.2 Cables Only class 1 copper cables 60/70° C (140/167° F) should be used.
1.6.3 Fuses UL conformity is adhered to if the fuses are UL-listed, fast-blow fuses (class CC up to 30 A) with a rating as indicated in the above table and if the short-circuit symmetrical current does not exceed 5 kA.

1.8 - Dimensions
Ø .280 HOLES
4 @ 90º AS SHOWN
Ø 4.72
Ø 3.1500
Ø .344 + .007 / -.002 HOLES
6.30 5.00


SEEPEXBW2+TS1LS80B14 CCI0109G

Removable screws in terminal block:
After connection, ensure that the seals are firmly in place, and that the screws and cable glands are watertight to ensure drive protection. Clear any condensation from the drain holes at the bottom of the motor.
3.2 Power terminal blocks 3.2.1 Terminal block for power supply PB1 (marked L&N) This terminal block is used to connect the 3 phase power supply when the RFI filter is not used in an IntelliGear Plus. Otherwise, the RFI filter output is screwed onto this connector and the power supply should be attached to the terminals located on top of the filter. (See table below)
2.1 - General
The IntelliGear Plus is usually fitted to the gear and mounted to the machine with flange or foot mounting. The motor fan cools the whole assembly. Make sure that the ventilation air inlet is free of obstruction. The positions of the potentiometer/cable gland supports are specified at the time of ordering. However they may be reversed if necessary.
3.1 - Control Terminal Blocks • Remove the terminal block from it’s fixed holder (unplugged) before making any connections, to avoid putting pressure on the card.

Terminal Block for Power Supply
Numbered Controller · Terminal Blocks


3.3 Wiring diagram based on standard configuration

IF AUTO MODE RUN/STOP CONTACT IS NOT USED, 4-20mA INPUT
User supplied male Turck connectors can be secured locally using the
4 pin connector with 4 meter cable attached = Turck # SB4T - 4
5 pin connector with 4 meter cable attached = Turck # SB5T - 4
6 pin connector with 4 meter cable attached = Turck # SB6T - 4
CONNECTOR PINS 5 & 6 MUST BE JUMPERED TO RUN IN AUTO


3.4 Terminal block assignments and MD functionality

seepex Inc. Tel +1(937)864-7150 Fax +1(937)864-7157 sales@seepex.net

DE INTERVENIR 2 MINUTOS ANTES Y ESPERAR AL MENOS DESCONECTAR EL APPARATO CAUTION :RISK OF ELECTRIC SHOCK
ADJUSTMENTS BEFORE MAKING AT LEAST 2 MINUTES DISCONNECT POWER
TENSION ET ATTENDRE 2
MINUTES AU MOINS AVANT
TOUTE INTERVENTION
Falla potencial / Defaut potentiel POTENTIAL FAULT
OVER TEMP
sur/sous tention Alto/Bajo Voltage OVER/UNDER VOLTAGE
Température élevée Temperatura excesiva
Débit bas Bajo flujo LOW FLOW
falla en el bobinado WINDING FAILURE
Défaut d’enroulement
Alta presión HIGH PRESURE
Falla en el impulsor
Défaut d’uentrainement


Series 3000 CbN gearing is shipped with one of the following synthetic lubricants per the table below. The gear reducer has been filled to accommodate any mounting position. In the case of synthetic oil, the lubricant does not require changing, but it is recommended that proper oil level be checked periodically.
No Backstop With Backstop
Manufacturer -25˚ F to 125˚ F (-30˚ C to 50˚ C) Shell Omala RL 100
Acceptable Mineral Oil Lubricants

Orient the gear head vertically and fill to mid-point of the Pri- mary Gear
Size 30 Oil Level
Fuchs is a registered trademark of Fuchs Petrolub; Shell is a registered trademark of Shell Petroleum Incorporated. Omala is a registered trademark of Shell Trademark Management.
Synthetic · Input Opening



062 080 031 077 061 130 090 009 187

Rep Description Quantity 001 Housing 1 009 Output flang ring 1 031 Output shaft 1 042 Pinion 1 052 Gear 1 061 Bearing front 1 062 Bearing back 1 077 Output shaft key 1 080 Gear Key 1

Rep Description Quantity 090 Oil seal 1 097 Input o-ring 1 127 Gearing snap ring* 1 130 Gearing snap ring 1 175 Input bracket screw 4 185 Washer for gear* 1 186 Screw washer* 1 187 Bolt 4 282 Nameplate 1
* Not illustrated on diagram
Typical Maintenance Items - Bearings and Seals

Item Description By Location Bearings Seal (mm) 61 62 90 30 6205 ZZ 6005 25 x 52 x 7 DL nitrile






12 Rotor Assembly (includes items 13 & 14) 1


Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Not running in AUTO or HAND mode- Alarm Light not lit | Power to drive is not on | Check power supply and cord | p.11 |
| Not running in AUTO or HAND mode- Alarm Light not lit | HOA switch is in “OFF” position | Move switch to HAND or AUTO | p.11 |
| Not running in AUTO mode - | HOA switch not in “AUTO” position | Put HOA switch in “AUTO” position | p.11 |
| Alarm light not lit | Pins “5” and “6” of the six pin Turck connector are not “connected” | • Connect Auto Mode Run/Stop contact to pins “5”and “6” of six pin Turck connector. • Make sure Auto Mode Run/Stop contact is closed. • Jumper pins “5” and “6” if Auto Mode Run/ Stop contact is not being utilized | p.11 |
| Unit runs at only Low Speed in AUTO mode | 4-20 mA signal is not present at drive | Check incoming 4-20 mA signal | p.11 |
| Unit runs at only Low Speed in AUTO mode | 4-20 mA to drive installed in reverse into pins “1” and “2” of six pin Turck connector | Reverse 4-20 mA connection polarity | p.11 |
| Unit in AUTO mode will not achieve high RPM output at 20 mA | 4-20 mA signal does not achieve full scale | Check incoming 4-20 mA signal | p.11 |
| Unit in AUTO mode will not achieve high RPM output at 20 mA | Signal to drive is not reaching full 20 mA | Repair signal | p.11 |
| Unit in AUTO mode will not achieve high RPM output at 20 mA | Potentiometer is not in “10” position | Turn potentiometer to “10” position | p.11 |
| Red LED “Alarm” light is on - Unit has stopped | Refer to “badge” below and on top of unit for mechanical/pump and electrical/ motor causes | Check these causes to determine the root cause for fault. Once cleared, un- plug and re-install main power plug with power source | p.11 |