Instruction/ maintenance manual of the product EPM 5300 GE
Go to page of 134
EPM 5300 Power Metering System Chapter 1: GE Consumer & Industrial Multilin Instruction Manual GE Multilin 215 Anderson Avenue, Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 F ax: (905) 201-2098 Internet: http://www .
.
TABLE OF CONTENTS DISTRIBUTED DIGIT AL FAULT RECORDER – INSTRUCTION MANUAL TOC–I Table of Contents 1: AC POWER MEASUREMENT SINGLE PHASE SYST EM .......................................................................................................
TOC–II DISTRIBUT ED DIGITAL FAULT RECORDER – INSTRUCTION MANUAL TABLE OF CONTENTS 6: PROGRAMMING OVERVIEW GENERAL PROCEDURE ............................................................................................................. ..... 45 SWITCH PACKS .
TABLE OF CONTENTS DISTRIBUTED DIGIT AL FAULT RECORDER – INSTRUCTION MANUAL TOC–III 13: PHASE REVERSAL AND PHASE IMBALANCE SET LIMITS/RELAYS PHASE REVERSAL AND PHASE IMBALANC E ................................................................ ......
TOC–IV DISTRIBUT ED DIGITAL FAULT RECORDER – INSTRUCTION MANUAL TABLE OF CONTENTS.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 1–1 EPM 5300 Series Meters Chapter 1: AC Power Measurement GE Consumer & Industrial Multilin AC Power Measurement The economics of electric power distribution networking dictat e several conf igurations of AC power transmission.
1–2 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL SINGLE PHASE SYSTEM CHAPTER 1: AC POWER MEASUREMENT The power ( W ) in a single phase syst em is: E = potential, I = current , and cos Θ = phase difference between the potential and the current .
CHAPTER 1: AC POWER MEAS UREMENT THREE-PHASE SYSTEM EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 1–3 1.2 Three-Phase System A three- phase syst em delivers higher levels of power for industrial and commercial applica tions; the three phases correspond to three potential lines.
1–4 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL THREE-PHASE SYSTEM CHAPTER 1: AC POWER MEASUREMENT FIGURE 1–4: Poly Phase System: (1) Delta, (2) Wye N A B C 2) Wye X E I CN C X X.
CHAPTER 1: AC POWER MEASUREMENT CONSU MPTION, DEMAND AND POOR POWER FACTO R EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 1–5 1.3 Consumption, Demand and Poor Power Fact or CONSUMPTION : W = instantaneous power T = time in hours The total electric energy usage over a time period is the consumption of WH.
1–6 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL WAVEFORM AND HARMONICS CHAPTER 1: AC POWER MEASUREMENT 1.4 Waveform and Harmonics Ideal power distribution has sinusoidal waveforms on voltages and currents. In r eal-life applica tions, where inverters, comput ers, and motor controls are used, distor ted waveforms are generated.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 2–1 EPM 5300 Series Meters Chapter 2: Mechanical Installation GE Consumer & Industrial Multilin Mechanical Installation 2.1 Mechanical Installat ion These diagrams display the various possible me chanical installations and Communication Converter installation .
2–2 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL MECHANICAL INSTALLATION CHAPTE R 2: MECHANICAL INSTALLATION FIGURE 2–2: Installation with K-110 option for limited space conditions FIGURE 2–3: Standard cutout 4.375 SQ. 0.890 2.45 2.
CHAPTER 2: MECHANICAL INSTA LLATION MECHANICAL INSTALLATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 2–3 FIGURE 2–4: Optional Communication Conv erter or DC Output Module Installation * Recommended wire gauge is 20 AWG for DC Output or RS-485 options.
2–4 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL MECHANICAL INSTALLATION CHAPTE R 2: MECHANICAL INSTALLATION.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–5 EPM 5300 Series Meters Chapter 3: Electrical Installation GE Consumer & Industrial Multilin Electric al Installation 3.1 Connecting the Current Circuit Install the wiring for the current at 600V AC insulation as a minimum.
3–6 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL CT CONNECTION CHAPTER 3: ELECTRICAL INSTALLATION 3.2 CT Connection If the meter is connected d irectly to the curr ent (up to 10 Amps max.), maintain the exact connection to avoid incorrect polarity.
CHAPTER 3: ELECTRICAL INSTALLATI ON CONNECTING THE VOLTAGE CIRCUIT EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–7 3.3 Connecting the Voltage C irc uit For proper meter operation, the voltage connection must be maintained. The voltage must correspond to the corr ect terminal.
3–8 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL SELECTING THE VOLTAGE FUSES CHAPTER 3: ELECTRICAL INSTALLATION 3.4 Selecting the Voltage Fuses We strongly recommend using fuses on each of the sense voltages and the control power , although connection d iagrams do not show them.
CHAPTER 3: ELECTRICAL INSTALLATION CONNECTION TO THE MAIN POWER SUPPLY EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–9 3.5 Connection to th e Main Power Supply The meter requires separate control power to operate. Listed are the f i ve different power supply options and corresponding suff ixes.
3–10 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ELECTRICAL CONNECTIO N INSTALLATION CHAPTER 3: ELECTRICAL INSTA LLATION 3.6 Electrical Connection Installation Choose the diagram that best suits your appl ication and maintain the CT polarity.
CHAPTER 3: ELECTRICAL INSTALLATION ELECTRICAL CONNECTION INSTA LLATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–11 FIGURE 3–1: Three Phase, Three-Wire System Delta with Direct Voltage an d CTs Note Remember to make sur e Open Delta bit is programmed in the meters (See Chapt er 9).
3–12 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ELECTRICAL CONNECTIO N INSTALLATION CHAPTER 3: ELECTRICAL INSTA LLATION Note Remember to make sur e Open Delta bit is programmed in the meter (see section 9.
CHAPTER 3: ELECTRICAL INSTALLATION ELECTRICAL CONNECTION INSTA LLATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–13 FIGURE 3–5: Three Phase Four-Wir e Wye with CT and PT s 7 6.
3–14 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL THE EPM 5300P-S CHAPTER 3: ELECTRICAL INSTALLATION 3.7 The EPM 5300P-S The EPM 5300P-S is essentially the 5300P , where through the Progr amming Mode calculations are changed to reflect either Single Phase or Dual Phase read ings.
CHAPTER 3: ELECTRICAL INSTALLATION THE EPM 5300P-S EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–15 FIGURE 3–7: Dual-Phase with CTs and PTs FIGURE 3–8: Three-Phase Four -Wire WYE with 2.5 Element Note The 2.5 element option must be custom conf ig ured fro m the factory.
3–16 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RELAY, PROTECTION AND PULSE OUTPUT CHAPTER 3: ELECTRICAL INSTALLATION 3.8 Relay, Pr ot ection and Pulse Output (This section appl ies only to the -NL or -NL2 Relay Option.) 3.8.1 EPM 5300P Relay Over view The EPM 5300P offers dry co ntact relay output capab ility.
CHAPTER 3: ELECTRICAL INSTALLATION RELAY, PROTECTIO N AND PULSE OUTPUT EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–17 Relay connection (see Figure 3.6, below): Form C relays, rated 250V , 5A– 2 each . KYZ relay output (Form C), rated 200V , 100mA– 1 each .
3–18 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RELAY, PROTECTION AND PULSE OUTPUT CHAPTER 3: ELECTRICAL INSTALLATION 3.8.3 Standar d Rate Table for W atts* *Units can be K ilowatts or Megawatts. Decimal Point Placement (Kw/mw) Change in Level 9999.
CHAPTER 3: ELECTRICAL INSTALLATION KYZ PULSE OUTPUTS: NL2 OPTION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 3–19 3.9 KYZ Pulse Outp uts: NL2 Option The -NL2 option for the met er is equipped with three KYZ outputs. KY Z relays pr ovide pulses for energy management systems or any other type of recording device.
3–20 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL KYZ PULSE OUTPUTS: NL2 OPTION CHAPTER 3: ELECTRIC AL INSTALLATION.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 4–21 EPM 5300 Series Meters Chapter 4: Communication Installation GE Consumer & Industrial Multilin Communication Installa tion 4.1 RS-232C (This section appl ies to the RS-232C or RS-485.
4–22 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RS-485 CHAPTER 4: COMMUNICATION INSTALLATION 4.2 RS-485 Each EPM 5300P or 5200P instrument has a unique address up to four digits long. This allows the user to communicat e with up to 10,000 instruments .
CHAPTER 4: COMMUNICATION INSTALLATION RS-485 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 4–23 FIGURE 4–3: 2-Wire RS-485 Communication Conne ction Installation half duplex (closed .
4–24 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RS-485 CHAPTER 4: COMMUNICATION INSTALLATION FIGURE 4–5: 4-Wire RS-485 Communication Connection Installation full duplex Connecti.
CHAPTER 4: COMMUNICATION INSTALLATION RS-485 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 4–25 FIGURE 4–6: 4-Wire RS-485 Communication Conne ction Installation full dupl ex, detail.
4–26 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL NETWORK OF INSTRUMENTS AND LONG DISTANCE COMMU NICATION CHAPTER 4: COMMUNICATION INSTALLATION 4.3 Network of Instruments and Long Distance Communication The RS-485 Transceiver is required for a large network of instruments.
CHAPTER 4: COMMUNICATION INSTALLATION NETWORK OF INST RUMENTS AND LONG DISTANCE COMMUNIC ATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 4–27 designed a Modem Manager RS-485 to RS-232C converter . This device automatically programs the modem to the proper conf iguratio n.
4–28 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL NETWORK OF INSTRUMENTS AND LONG DISTANCE COMMU NICATION CHAPTER 4: COMMUNICATION INSTALLATION Necessary to communicate with r emot e modem conne cted to EPM 5300P .
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–29 EPM 5300 Series Meters Chapter 5: Overview GE Consumer & Industrial Multilin Over view The EPM 5300P displays 17 instantaneous el ectrical parameter s. Values fo r each parameter are accessed through the keypad on the meter's front panel (see Figure 5.
5–30 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL CHAPTER 5: OVERVIEW FIGURE 5–1: The EPM 5300P front panel with disp lay and keypad MA X/MIN LIMITS KVAR PF KW KVA FREQ KWH KVAH A.
CHAPTER 5: OVERVIEW ACCESSING THE POWER FUNCTIONS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–31 5.1 Accessing the Power Functions Note For KWH readings: The f irst digit on the left of the KWH count er will blank out on the display when rollover at 199999 KWH occurs.
5–32 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ACCESSING VOLTAGE AND CURRENT PHASES CHAPTER 5: OVERVIEW 5.2 Accessing Voltage and Curr ent Phases The EPM5300P displays four current measuremen ts (phases A, B, C, and Neutral) and six voltage measurements (phase-to- phase: A-B, B-C, C-A and phase-to-neutra l: A-N, B-N, C-N).
CHAPTER 5: OVERVIEW ACCESSING %THD FUNCTIONS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–33 5.3 Accessing %THD Functions Harmonic Measurement r eadings are avail able o n the EPM 5300P meter . The EPM 5300P displays 6 paramet ers of total harmonic dist ortion.
5–34 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL VIEWING INDIVIDUAL PHASE INDI CATION FOR POWER FUNCTIONS CHAPTER 5: OVERVIEW 5.4 V iewing Individual Phase In dication for Power Functions The EPM 5300P normally displays a three- phase indi cation for PF , KW , KV AR , KVA r ead ings.
CHAPTER 5: OVERVIEW ACCESSING MAX/MIN VALUES EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–35 5.5 Accessing Max/Min Values Max/min values repr esent the highest and lowest average demand over a user programmable time period known as the Integration Inter val .
5–36 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RESETTING VALUES CHAPTER 5: OVERVIEW 5.6 Resetting V alues Use the reset functio n if a new value is desire d. It is av ailable in two d ifferent modes. 1. UNPR OTECTED MODE : Allows quick and easy resetting of max/min values.
CHAPTER 5: OVERVIEW RESETTING VA LUES EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–37 5.6.2 PROTECTED RESET Step 1 : a. Press MAX/MIN/LIMITS once to access max value; twice to acces s min va lue. Step 2 : a. While the value is display, press PHASE/NEXT to commence protected reset .
5–38 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RESETTING HOUR READINGS CHAPTER 5: OVERVIEW 5.7 Resetting Hour Re adings Step 1: a. Pre ss PO WE R once. b. Press PHASE/NEX T for the desired hour function. This example uses KWH function.
CHAPTER 5: OVERVIEW ACCESSING THE LM1/LM2 SET LIMITS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–39 5.8 Accessing the LM1/LM2 Set Limits The EPM 5300P has two manual set limits whic h monitor the instantaneous readings and warn the user of any abnormal conditions.
5–40 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL VOLTAGE PHASE REVERSAL AND IM BALANCE CHAPTER 5: OVERVIEW 5.9 Voltage Phase R e versal and Imbalance In a three- p hase power distribution syst em, normal phase shift between each line is 120 ° .
CHAPTER 5: OVERVIEW ACCESS MODES EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–41 5.10 Access Modes The following access c ommands allow the user t o perform spec if ic operations .
5–42 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL PRINT OPERATING DATA CHAPTER 5: OVERVIEW 5.11 Print Operating Data This function sends data to a serial printe r , creating a hard copy of the instantaneous and max/min data of all functions and the WH, V AH, and WH counters.
CHAPTER 5: OVERVIEW PRINT PROGRAMMING DATA EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 5–43 5.12 Print Programming Data This function sends the programming data (or the meter setup) to a serial print er for verif ication and qui ck refer ence.
5–44 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ACCESSING FIRMWARE VERSION/LED TEST CHAPTER 5: OVERVIEW 5.13 Accessing Firmwa re Ve r s io n /L E D Te s t The EPM 5300P accesses the f irmwar e vers ion number of the analog and digital micropro cessors.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 6–45 EPM 5300 Series Meters Chapter 6: Programming Overview GE Consumer & Industrial Multilin Programming Overview 6.1 General Pr ocedure Programming tasks are arranged into nine ma jor GROUPS.
6–46 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL SWITCH PACKS CHAPTER 6: PROGRAMMING OVERVIEW 6.2 Swit ch Packs GROUPS, Function s, and Switch P ACKS • GROUPS are the main category. • Functions are sub categories of GR OUPS. • Switch P ACKS are sub categorie s of FUNCTIO NS.
CHAPTER 6: PROGRAMMING OVERVIEW PROGRAMMING MODE DATA ENTRY EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 6–47 6.3 Progra mming Mode Data Entry The EPM 5300P and EPM 5200P programming mode utilizes only three out of the f ive- keypad buttons: the MAX/MIN/LIMIT S , VOL TS/THD , and AMPS/TH D buttons.
6–48 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL STANDARD NUMERIC DATA ENTRY CHA PTER 6: PROGRAMMING OVERVIEW 6.4 Standar d Numeric Data Entry Programmable FUNCTION values are always four digit numerical f ields desig ned to accept any value between 0000 and 9999 (a blank signif ies a zero).
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 7–49 EPM 5300 Series Meters Chapter 7: EPM 5200P GE Consumer & Industrial Multilin EPM 5200P 7.1 EPM 5200P The EPM 5200P is similar to the re gular EPM 5300P with the following exceptions: 1.
7–50 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL EPM 5200P CHAPTER 7: EPM 5200P Note The Ethernet model, EPM 5350P , is covered in detail in Chapte r 16 of this manual. See p. 40 for a comparison of the three models covered in this manual.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 8–51 EPM 5300 Series Meters Chapter 8: Entering Programming Mode GE Consumer & Industrial Multilin Enteri ng Programming Mode 8.
8–52 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL PASSWORD ENTRY CHAPTER 8: ENTERING PROGRAMMING MODE 8.2 Password Entry The EPM 5300P and 5200P are password pr ot ected. To enter the Pr ogramming Mode, key in the following password: 555 .
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–53 EPM 5300 Series Meters Chapter 9: Programming Group 0 - Global Meter Setup GE Consumer & Industrial Multilin Programming Group 0 - Global Meter Setup The Global Meter Setup includes FUNCTIONS 0 through 7 that control conf iguration and basic operation.
9–54 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 0—THE INTEGRATION INTERVAL CHAP TER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP 9.1 Group 0, Function 0—The Integration Inter val INTEGRATION INTER VAL: T ime whi ch all instantaneous readings are averaged to obtain a max and min demand.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETU P GROUP 0, FUNCTION 0—THE INTEGRATION INTERVAL EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–55 METER ADDRESS : Identif ies the met er when communicating with d igital communications.
9–56 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 2 — BAUD RATE CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP 9.2 Group 0, Function 2 — Baud Rate BAUD RATE : Speed at which data is transmitt ed between meter and remote comput er or serial printer .
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP GROUP 0, FUNCTION 3 — SYSTEM CONFIGURATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–57 9.3 Group 0, Function 3 — System Conf iguration The Syst em Conf iguration sets the EPM 5300P ’ s basic operational pa rameters.
9–58 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 3 — SYSTEM CO NFIGURATION CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METE R SETUP 9.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP GROUP 0, FUNCTION 3 — SYSTEM CONFIGURATION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–59 9.3.2 Switching Communication Protocols, EI-BUS, MODBUS RTU/ASCII, DNP 3.0 • For EI-BUS pr otocol: PACK 2, Switch C is DOWN, Switch D is DOWN.
9–60 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL MODBUS PLUS CAPABILITY CHAPTER 9: PROG RAMMING GROUP 0 - GLOBAL METER SETUP 9.4 Modbus Plus Capability When using the MPI Modbus Plus adapt er , the meter values should be set t o speak to Modbus RTU with a meter address of 0 001 and a baud rate of 9600 baud.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SE TUP GROUP 0, FUNCTION 3—PROGRAMMING PROCEDURE EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–61 9.
9–62 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RELAY MODE CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP 9.6 Relay Mode Note Relays are not available for the EPM 5200P . The Switch PACKS in FUNCTIONS 4 and 5 of programming GROUP 0 control the relay position.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP RELAY MODE EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–63 Programming Steps: Z Enter in GROUP 0, FUNCTION 4, P A CK ‘P’ , Segm ent C and D: UP , UP . Z Enter in GROUP 5, FUNCTION 4, LI MIT 1, Segments B, C, and D: DOWN, UP , DOWN.
9–64 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL RELAY MODE CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP Step 1: a. Enter Group Level of Programming Mode (see Chp . 8). b. Press MAX/MIN/LIMITS until 0. appears in upper dis play .
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUPGROUP 0, FUNCTIONS 4–5—TIME DELAY FOR RELAYS 1 & 2 (OPTION – NL) EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–65 9.
9–66 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTIONS 4–5—TIME DELAY FOR RE LAYS 1 & 2 (OPTION – NL)CHAPTER 9 : PR OGRAMMING GROUP 0 - GLOBAL METER SETUP Step 1: a. Enter Group Level of Programming Mode (see Chp.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETU P GROUP 0, FUNC TION 6—KYZ PARAMETER SELECTION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–67 9.8 Group 0, Function 6—KYZ Parameter Selection Note FUNCTION 6 applies only if Option -NL or -NL2 was ordere d.
9–68 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 6—KYZ PARAMETER SELECTION CHAPT ER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP Step 1: a. Enter Group Level of Programming Mode (see Chp . 8). b. Press MAX/MIN/LIMITS until 0.
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETU P GROUP 0, FUNC TION 6—KYZ PARAMETER SELECTION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–69 Note The unit WH refers t o the counter value on th e meter , where the unit equals K ilo or Mega user-def ined.
9–70 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 6—KYZ PARAMETER SELECTION CHAPT ER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP 9.8.2 How to Use KYZ Pulse Value Table for Division: S ITUATION 3: FSW=99.99 Selection is Multiply by 20 This means that every .
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETU P GROUP 0, FUNC TION 6—KYZ PARAMETER SELECTION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–71 T o change the KYZ pulse value: Ste p 1: a. Enter Group Level of Programming Mode, (see Chp.
9–72 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 0, FUNCTION 7—NUMBER OF PHASES CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP 9.9 Group 0, Function 7—Number of Phases Note E NTER 1 FOR SINGLE PHASE / SINGLE WIRE . Enter 2 for single phase/two wire.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 10–73 EPM 5300 Series Meters Chapter 10: Programming Group 1 – Voltage, Amp And Watt Scale Settings GE Consumer & Industrial Multi.
10–74 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 1, FUNCTION 0 CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS 10.
CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AM P AND WATT SCALE SETT INGS GROUP 1, FUNCTION 0 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 10–75 Step 1: a. Enter Group Level of Programming Mode (see Chp . 8). b. Press MAX/MIN/LIMITS until 1.
10–76 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 1, FUNCTION 0 CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS Step 5: Middle display ind icates present Full Scale for volts. Four dashes appear in lower display.
CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AM P AND WATT SCALE SETT INGS GROUP 1, FUNCTION 1 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 10–77 10.2 Group 1, Function 1 - AMPERAGE FULL SCALE - Also note that the met er reads with digital ac curacy to a 2000 count range.
10–78 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 1, FUNCTION 1 CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS Entering the Scale Factor : Step 3: a. Press AMPS to begin Data Entry Sequence. Lower display is replaced with a single dash.
CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AM P AND WATT SCALE SETT INGS GROUP 1, FUNCTION 2 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 10–79 10.3 Group 1, Function 2 - SCALE SELECTION AND DECIMAL PL ACEMENT FOR W A T TS - Programming GROUP 1 also provides decimal positioning for maximum resolution.
10–80 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 1, FUNCTION 2 CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS T o change the scale factor setting for wattage: Note Press MAX/MIN/LIMITS at any time to cancel before storing the last d igit or switch.
CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AM P AND WATT SCALE SETT INGS GROUP 1, FUNCTION 2 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 10–81 Entering the Scale Factor : Step 3: a. Press AMPS to begin Data Entry Sequence. Lower display is replaced with a single dash.
10–82 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 1, FUNCTION 2 CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 11–83 EPM 5300 Series Meters Chapter 11: Programming Group 2 - Meter Calibration GE Consumer & Industrial Multilin Programming Group.
11–84 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL CALIBRATION REQUIREMENTS CHAPTER 11: PR OGRAMMING GROUP 2 - METER CALIBRATION 11.1 Calibration Requirements Calibration on the EPM 5300P requires pr ecise inputs of 120 Volts, 5 Amps, and 2.
CHAPTER 11: PROGRAMMING GROUP 2 - METER CALIBRATION GROUP 2, FUNCTIONS 0–2 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 11–85 11.2 Group 2 , Functions 0–2 - HIGH END CALIBRA TIO.
11–86 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 2, FUNCTIONS 0–2 CHAPTER 11: PR OGRAMMING GROUP 2 - METER CALIBRATION For Amps Low End (Function 2): Note Press MAX/MIN/LIMITS at any time to cancel before storing the last d igit or switch.
CHAPTER 11: PROGRAMMING GROUP 2 - METER CALIBRATION GROUP 2, FUNCTIONS 0–2 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 11–87 Step 1: a. Enter Group Level of Programming Mode (see Chp. 8 ). b. Press MAX/MIN/LIMITS until 2. appears in upper disp la y.
11–88 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 2, FUNCTIONS 0–2 CHAPTER 11: PR OGRAMMING GROUP 2 - METER CALIBRATION.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–89 EPM 5300 Series Meters Chapter 12: Groups 4, 5 and 6— Set Limits and Relays GE Consumer & Industrial Multilin Groups 4, 5 and 6—S et Limits and Relays The EPM 5300P -NL offers a comprehensive limit and set point functionality.
12–90 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL TRIP RELAY CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS 12.1 T rip Relay The EPM 5300P -NL has two relays. These re lays are linked throug h the program to Set Limits LM1 and LM2.
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMI TS AND RELAYS TIME DELAYS & RELAY MODE EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–91 12.2 T ime Delays & Relay Mode T ime Delay indicat es whether a delay exists in the relay changing position.
12–92 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 4: FUNCTIONS 0–3—LM1/LM2 SET LIMITS CHAPTE R 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS 12.
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELA YS GROUP 4: PROGRAMMING FORMAT FOR LIMIT CO NDITION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–93 12.
12–94 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 5: FUNCTIONS 0–7—LM1/LM2 SET LIMITS CHAPTE R 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS 12.5 Group 5: Functions 0–7—LM1/LM2 Set Limits GROUP 5 contains LM1 and LM2 set limit values for all power functions.
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS GROUP 5: FUNCTIONS 0–7—LM1/LM2 SET LIMITS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–95 Thus, if K ilowatts exceed 120 W , LM1 is triggered and R elay 1 is tripped. If the Kilowatts fall below 90 W, LM2 is triggered and Relay 2 is tripped.
12–96 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL GROUP 6: LM1/LM2 SET LIMITS: CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS 12.6 Group 6: LM1/LM2 Set Limits: 12.6.1 Group 6: THD Set - Limits / R elays (For Option -h) GROUP 6 contains LM1 and LM2 set l imits for THD.
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYSGROUP 6: FUNCTIONS 0–5—LM1/LM2 SET LIMITS AND RELAY TRIGGERS FOR OVER/UNDER %THD CONDITIONS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–97 12.
12–98 EPM 5300 SERIES ADVANCED POWER ME TERS – INSTRUCTIO N MANUAL LIMITS OR RELAYS PROGRAMMING PROCEDURE CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS 12.8 Limits or Relays Programming Pr ocedure Note The procedure for programming any limit or relay for each group is identical.
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS LIMITS OR RELAYS PROGRAMMING PROCEDURE EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCT ION MANUAL 12–99 Step 3: a.
12–100 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL LIMITS OR RELAYS PROGRAMMING PROCEDURE CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS Step 6: a. Press VOL TS t o sc roll thro ugh d igi ts. b. Press AMPS to se lec t . c. At the last digit , press AMPS twice t o store limit programming.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 13–101 EPM 5300 Series Meters Chapter 13: Phase Reversal and Phase Imbalance Set Limits/Relays GE Consumer & Industrial Multilin Phase Rever sal and Phase Imbalance Set Limits/Relays 13.
13–102 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL TRIP RELAY CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET LIMI TS/RELAYS 13.2 T rip Relay Note All information perta ining to Trip Relays 1 and 2 appl ies only to a meter wi th the –NL option.
CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET LIMI TS/RELAYS GROUP 7, FUNCTION 0—VOLTAGE PHASE REVERSAL DETECTION EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 13–103 13.
13–104 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 7, FUNCTION 0—VOLTAGE PHASE REVE RSAL DETECTION CHAPTER 13: PHASE REVE RSAL AND PHASE IMBALANCE SET LIMITS/ RELAYS Step 2: a. Pre ss AMPS once. Lower display is replaced with two dashes.
CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET LIMITS /RELAYS GROUP 7, FUNCTION 1—PERCENTAGE VOLTAGE PHASE IMBALANCE EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 13–105 13.
13–106 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL GROUP 7, FUNCTION 1—PERCENTAGE VOLTAG E PHASE IMBALANCECHAPTER 13: PHASE REVE RSAL AND PHASE IMBALANCE SET LIMITS/ RELAYS See C hap ter 14 to Exi t . Step 3: a. Press AMPS to begin Data Entry Sequence.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 14–107 EPM 5300 Series Meters Chapter 14: Exiting Programming Mode GE Consumer & Industrial Multilin Exiting Progr amming Mode 14.1 Exiting Programming Mode Note Steps to exit Programming Mode vary depending on the programming stage.
14–108 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL EXITING PROGRAM MING MODE CHAPTE R 14: EXITING PROGRAMMI NG MODE Step 1: E XITING FROM F UNCTION L EVEL a. Press MAX/MIN/LIMITS until the Group number in upper display is followed by E (for Exit).
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 15–109 EPM 5300 Series Meters Chapter 15: Programming Quick Reference GE Consumer & Industrial Multilin Programming Quick Reference 15.1 Entering the Programming Mode Z Hold PHASE/NEX T key and press AMPS key .
15–110 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL DATA ENTRY SEQUENCE CHAPTER 15: PROGRAMMING QUICK REFERENCE 15.2 Data Entry Sequence Z At programmable numerical f ields or Switch Pack f ields, Press AMPS key to begi n Dat a Entry Se quence.
CHAPTER 15: PROGRAMMING QUICK REFERENCE PROGRAMMING GROUPS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 15–111 15.3 Programming Gr oups 15.3.1 Group 0: Global Meter Setup 00. Inter val. 01. Meter Address for Communication. 02. Baud Rate for Communication.
15–112 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL PROGRAMMING GROUPS CHAPTER 15: PROGRAMMING QUICK REFERENCE C Communication Selection D DC-Output/Print Control 04. Relay 1 Pr ogramming 04P . A Imb/Rev Selection B And/or Logic C Relay Control Selection D Relay Control Selection 040.
CHAPTER 15: PROGRAMMING QUICK REFERENCE PROGRAMMING GROUPS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 15–113 15.3.4 Group 3: Calibration Ratios 30. Volt AN 31. Volt BN 32. Volt CN 33. Amp A (High-E nd Ratios) 34. Amp B (High-End Ratios) 35.
15–114 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL PROGRAMMING GROUPS CHAPTER 15: PROGRAMMING QUICK REFERENCE 15.3.8 Group 7: Imbalance/Reversal Limits 70. Detect Reversal 71. Imbalance percent Limit 15.3.9 Group 8: DC output Calibration 8P .
CHAPTER 15: PROGRAMMING QUICK REFERENCE PROGRAMMING GROUPS EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 15–115 89L . Low-End Cal ibration 89H.
15–116 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL PROGRAMMING GROUPS CHAPTER 15: PROGRAMMING QUICK REFERENCE.
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 16–117 EPM 5300 Series Meters Chapter 16: Ethernet Option GE Consumer & Industrial Multilin Ethernet Option The EPM5350P , Met er with the Ethernet Option, has all the components of the standar d Meter PLUS the capabil ity of connecting to multiple devices over Ethernet .
16–118 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ETHERNET MODULE CHAPTER 16: ETHERNET OPTION 16.1 Ethernet Module The Ethernet connection is made w ith a small module added t o the back of the met er . This small but powerful module has simply an RJ-45 Por t and four Status LEDs.
CHAPTER 16: ETHERNET OPTION ETHERNET OPTION SETUP EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 16–119 16.2 Ethernet Option Setup This chapter covers the required steps to get the Ethernet Interface on-l ine and working.
16–120 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ETHERNET OPTION SETUP CHAPTER 16: ETHERNET OPTION 16.2.3 Setting the IP Address The Ethernet Inter face’s IP address must be conf igured before a network connection is available.
CHAPTER 16: ETHERNET OPTION ETHERNET OPTION SETUP EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 16–121 Use a Telnet connection to conf igure the unit over the network. The Ethernet Interface’ s conf igurat ion is stored in nonvolatile memory (NVRam) and is retained without power .
16–122 EPM 5300 SERIES ADVANCED POWER MET ERS – INSTRUCTION MANUAL ETHERNET OPTION SETUP CHAPTER 16: ETHERNET OPTION Baud Rate The Etherne t Interface and att ached seria l device (t he meter) must agr ee on a speed or baud rate used for the serial connection.
An important point after buying a device GE EPM 5300 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought GE EPM 5300 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data GE EPM 5300 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, GE EPM 5300 you will learn all the available features of the product, as well as information on its operation. The information that you get GE EPM 5300 will certainly help you make a decision on the purchase.
If you already are a holder of GE EPM 5300, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime GE EPM 5300.
However, one of the most important roles played by the user manual is to help in solving problems with GE EPM 5300. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device GE EPM 5300 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center