Typical 4000 Series catalog no. for J–design, 2 pole, 260 amp, 240 V, ADTS in Type 1 enclosure:
J design prefix letter
Amperes Voltage Controller Enclosure
J 400
C – type 1
B – switched 5X – if
F – type 3R
G – type 4
H – type 4X
M 460
E 230
N 480
L – type 12
Q 575 P 550
blank – open type
R 600

field connections terminal block TB
J–design 260 ampere size in typical enclosure with location of customer connections

ASCO 4000 SeriesAutomatic Delayed–TransitionTrans- fer Switches are factory wired and tested. Field installa- tion simply requires mounting and connection of service cables, and auxiliary control circuits (if required).
should be tested to verify that they are not defective or have been damaged during installation.
Remove the Shipping Skid
AWiringDiagramis furnishedwith theASCO 4000Series 4ADTS (separate from this manual). Refer to this drawing. All wiring must be made in accordance with the National Electrical Code and local codes.
For large switches, open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solder- less screw type and will accept the wire sizes listed on the drawings provided with the switch. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
The supporting foundation for the enclosure must level and straight. Refer to the applicable enclosure outline drawing included with the 4ADTS for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Do not run cables in front of or behind the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum for 150-400 amps, 1 inch minimum over 400 amps.
Refer to the outlineand mountingdiagram providedwith the ATS; it shows all mounting details and instructions.
It is not necessary to remove the barriers from the transfer switches to install the cables. If you do remove them,however, be sure to reinstall the barriers carefully.
Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the automatic switch switch.
Mount the ATS vertically to a rigid supporting structure. Levelallmountingpointsbyusing flatwashers behindthe holes to avoid distortion of the switch.
For large switches use grade 5 hardware to connect bus to appropriate terminal plates. Wipe off the bus surfaces beforetheyarejoined. Ifthe busis verydirty, gentlyclean the surfaces with a non---flammable solvent. Avoid touching the cleaned surfaces.
The controller is mounted on the cabinet door. An add- on DIN rail is provided for some optional accessoriesand is mounted below controller on the door.
Tighten bolted joints to the torque specified in Table A.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.
The reliability of the connection depends
on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints
Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they
(Grade 5 hardware)


A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Signals 5 amps, 32 V DC 5 amps resistive 28 V DC or 120 V AC max.
Feature 14A & 14B
10 amps, 32 V DC 10 amps 250 V AC general purpose
TB Terminal Block (field connections) accepts wire range 22–12 AWG
The transfer switch is connected to the left side of the control panel by a plug-in harness (two plugs).

FEATURE 7
FEATURE 8
Connect auxiliary circuit wires to appropriate terminals on the transfer switch. Note the control features that are furnished on this switch. Make the necessary auxiliary connections by referring to the Wiring Diagram.
Engine Starting Contacts The engine control contact connections (if used) are located on the transfer switch. Connect signal wires to appropriate terminals as specified in Table B and shown in Figures 1–1 and 1–2. See the wiring diagram too.
Figure 1-2. Connections to engine starting contact
terminal block located on 1600 through 3000 amp.
G–design transfer switches.
Table B. Engine start connections
left side of transfer switch


Signals 5 amps, 32 V DC 5 amps resistive 28 V DC or 120 V AC max.
FEATURE 7 closes to start FEATURE 8 opens to start
Feature 14A & 14B
FEATURE 14B closed on emergency
10 amps, 32 V DC 10 amps 250 V AC general purpose
FEATURE 14A closed on normal
Optional TS Auxiliary Contacts Feature 14AA & 14BA
FEATURE 14BA closed on emergency FEATURE 14AA closed on normal
10 amps, 32 V DC 10 amps 250 V AC general purpose
Figure 1-1. Connections to engine starting contact
terminal block for 150 through 1200 amp.
J & H–design transfer switches.

The Functional Test consists of three checks:
❐1 — Manual OperationTest, pages1–3 through1–6
❐2 — Voltage Checks, page 1–7
contact position indicators (right side)
❐3 — Electrical Operation, page 1–8
O is open C is closed
Do these checks in the order presented
to avoid damaging the ATS.
Read all instructions on the Wiring Diagram and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding.
Figure 1-3. Contact position indicators on 150–600 amp. J–design transfer switches . Shown with Emergency open and Normal closed.
Continue to 1 – Manual Operation Test starting below.
A detachable operator handle is provided on the transfer switch for maintenance purposes only. Manual operation of the transfer switch must be checked before it is operated electrically.
contact position indicators (right side)
O is open C is closed
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
Figure 1-4. Contact position indicators on 800–1200 amp. H–design transfer switches . Shown with Emergency open and Normal closed.
150–1200 amp J, H–designs Fig. 1-3, -4, -6 thru -11. Attach the manual handle onto the shaft hub, left side of the operator. 1600 – 3000 amp. G–design See Figures 1-5, 1-12. Installthehub (withpin) ontothe shaftand insertthe manual firmly into the side hole in the hub. Push in or pull out hub to engage opposite source contacts.

4000 amp. F–design See Figure 1-13. Insert the manual handle into the hole in the weight.
Figure 1-5. Contact position indicators on 1600–3000 amp. G–design transfer switches . Shown with Emergency closed and Normal open.



H–design 800–1200 amp
left side of transfer switch
left side of transfer switch
prevent both N & E contacts
from being closed at the
Normal source contact shaft hub
Normal source contact shaft hub
Figure 1-6. Maintenance handle on 150–600 amp. J–design transfer switches. Hubs shown with Normal
Figure 1-9. Maintenance handle on 800–1200 amp.
H–design transfer switches. Hubs shown with
contacts closed & Emergency open.
Normal contacts closed & Emergency open.

UP opens the Emergency source contacts
UP opens the Emergency source contacts
UPPER SHAFT
DOWN closes the Emergency source contacts frame
DOWN closes the Emergency source contacts frame
Figure 1-7. Emergency (upper shaft) operation
Figure 1-10. Emergency (upper shaft) operation
on 150–600 amp. J–design transfer switches.
on 800–1200 amp. H–design transfer switches.
UP closes the Normal source contacts
UP closes the Normal source contacts
LOWER SHAFT
DOWN opens the Normal source contacts frame
DOWN opens the Normal source contacts frame
Figure 1-8. Normal (lower shaft) operation on 150–600 amp. J–design transfer switches..
Figure 1-11. Normal (lower shaft) operation on 800–1200 amp. H–design transfer switches..

Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
Table C. Maintenance handle positions on 150–1200 amp. transfer switches. .

Turn counterclockwise to OPEN contacts.
into hole (spring fully compressed)
Grasp handle firmly with both hands
Turn clockwise to CLOSE contacts.
Slide the hub onto the shaft and insert the pin.
counterclockwise DOWN OPENS the contacts Pull out shaft to open Emergency source contacts (upper) Push in shaft to open Normal source contacts (lower)
clockwise DOWN OPENS the contacts Pull out shaft to close Emergency source contacts (upper) Push in shaft to close Normal source contacts (lower)
contact position indicators (left side)
Figure 1-12. Removable maintenance handle and positions on 1600 – 3000 amp. G–design transfer switches.

Figure 1-13. Removable maintenance handle on
4000 amp. F–design transfer switch.
Verify that the maintenance handle has been removed and stored properly before proceeding!
Now continue to 2 – Voltage Checks on page 1–7.


Press for 15 Sec.
Figure 1-14. Standard controls and indicators.
First check the nameplate on the transfer switch; the rated voltage must be the same as the normal and emergency line voltages.
Verify that the feeders have been connected to the proper terminal lugs.
Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–14.
❍White circle means light is off.
* If necessary, adjust the voltage regulator on the generator according to the manufacturer’s recommenda- tions. The automatic transfer switch will respond only to the rated voltage specified on the transfer switch nameplate. Note: Refer to Section 3 of the Group 5 Controller User’s Guide 381333–126 for how to display the status of the ATS and the voltage and frequency of each source. Note: Press the Lamp Test button to verify that all five lights work.
Now continue to 3 --- Electrical Operation on next page.
observe these lights


step 2 step 4
If this light is on, the buttons will not work until the controls are unlocked. If this light is blinking, the user controls are unlocked for 5 minutes.
Press for 15 Sec.
Figure 1-15. User controls and indicators.
This procedure will check the electrical operation of the automatic transfer switch. See Figure 1–15.
Be sure to close the enclosure door before proceeding to prevent personal injury
in case of electrical system fault.
Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.
Perform steps 1 through 5 at the right. Observe the status lights.
❍White circle means light is off.
If the User Controls Locked light is on, the Transfer Test and Retransfer to Normal buttons will not work until you unlock them.
How to unlock the User Controls Press up or down arrow keys on Transfer Control Center (Group 5 Controller), enter the password, and press Enter key. The user controls are now unlocked for 5 minutes. During that time the light will blink.
To lock or unlock the user controls refer to the Group 5 Controller User’s Guide 381333–126. Password informa- tion and time delay settings are also provided there.
This completes the functional test of the ATS.
press these buttons · observe these lights

DISCONNECTING THE CONTROLLER
Operate the 4000 Series ADTS at least once a month by following the five–step Electrical Operation Transfer Test procedure on page 1–7.
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:
PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 4000 Series ADTS. An annual preventive maintenance program is recom- mended.
Do not unplug the controller until steps 1a or 1b is completed.
a. If the transfer switch is in the Normal position, first
ASCO Services, Inc. (ASI) is ASCO Power Technologies’s national service organization. In the US ASI can be contacted at 1-800-800-2726 for in- formation on preventive maintenance agreements.
place standby engine starting control in the off position. Second, then open the emergency source circuit breaker. Third, open the normal source circuit breaker.
Checklist for Yearly Inspection
b. If the transfer switch is in the Emergency position,
first open the normal source circuit breaker. Sec- ond, place the engine starting control in the test or run position. Third, openthe emergencysource circuit breaker.
Hazardous voltage capable of causing shock, burns, or death is used in this transfer switch.
Deenergize both Normal – Emergency power
sources before performing inspections!
❐Clean the 4ADTS enclosure. Brush and vacuum
away any excessive dust accumulation. Remove any moisture with a clean cloth.
❐Check the transfer switch contacts. Remove the
Do not reconnect the controller until steps 1a or 1b is completed.
transfer switch barriers and check contact condition. Replace the contacts if they become pitted or worn excessively. Reinstall the barriers carefully.
❐Maintain transfer switch lubrication. If the transfer switch is subjected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and linkages. Relubricate the solenoid operator if the TS coil is replaced. Do not use oil; order lubrication kit 75-100.
a. If the transfer switch is in the Normal position,
first be sure that both normal and emergency source circuit breakers are open. Second, be sure that the standby engine starting control is still in the off position.
b. If the transfer switch is in the Emergency position,
first be sure that both normal and emergency source circuit breakers are open.
❐Check all cable connections & retighten them.
Replacement parts are available in kit form. When or- dering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch name- plate. Contact your local ASCO Power Technologies Sales Office or ASI:
a. If the transfer switch is in the Normal position,
first close the normal source circuit breaker. Second, closetheemergencysource circuit break- er. Third, place the standby engine starting control in the automatic position.
call 1 – 800 – 800 – ASCO ( 2726 )
b. If the transfer switch is in the Emergency position,
call 1 – 888 – 234 – ASCO ( 2726 )
first close the emergency source circuit breaker. Second close the normal source circuit breaker.
Disconnecting the Plugs · Reconnecting the Plugs

This procedure will manually transfer the load if the controller is disconnected.
Do not manually operate the transfer switch
until both power sources are disconnected
(all conductors deenergized).
Verify that the maintenance handle has been removed before proceeding!
Hazardous voltage capable of causing shock,
burns, or death is used in this switch. Do not touch the power or load terminals
of the transfer switch!
Table 2-1. Trouble-Shooting Checks.
* These are factory settings. Refer to Group 5 Controller User’s Guide.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI: in the United States, call 1–800–800–2726 or in Canada call 1–888–234–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 1 OPERATION | p.12 | ||
| Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails. | Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting. | p.12 | |
| Transfer switch does not transfer the load to the emergency source after the engine–generator set starts. | Wait for Feature 2B time delay to time out. | p.12 | |
| Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released. | Wait for Feature 3A time delay to time out. | p.12 | |
| Gen. does not stop after load retransfer to normal source. | Wait for Feature 2E time delay to time out. | p.12 |