Emerson ADTS

13 pages·805 KB·Switch·PDF·ENDEFRITNLJA
Emerson ADTS
Table of Contents 52 sections Operator’s · 4000 Series ADTS Automatic Delayed–Transition Transfer Switches · Manual · J–design 150–600A, H–design 800–1200A, · … ShowHide
Page 2 of the Emerson ADTS user manual — H 380
Page 2 · click to enlarge
Page 2

Catalog Number Identification

Typical 4000 Series catalog no. for J–design, 2 pole, 260 amp, 240 V, ADTS in Type 1 enclosure:

J design prefix letter

4ADTS A 2 260 F 5 C

Amperes Voltage Controller Enclosure

3. three Ø 2 – single Ø B 120

A 115

J 400

5. standard

C – type 1

B – switched 5X – if

K 415

F – type 3R

G – type 4

H – type 4X

D 220

M 460

E 230

N 480

L – type 12

G 277 F 240

Q 575 P 550

blank – open type

H 380

R 600

Emerson ADTS — H 380 diagram (page 2)
Fig. 1

field connections terminal block TB

J–design 260 ampere size in typical enclosure with location of customer connections

Show 15 more labels / short text on this page
Phase Poles Neutral · A – solid · accessories · C – overlapping · 600 800 · 2600 3000 · ordered · blank – none · power connections · transfer · control & lights · Transfer · Switch · Group 5 Controller · power connections
Page 3 of the Emerson ADTS user manual — Testing Power Conductors
Page 3 · click to enlarge
Page 3

SECTION 1 INSTALLATION

ASCO 4000 SeriesAutomatic Delayed–TransitionTrans- fer Switches are factory wired and tested. Field installa- tion simply requires mounting and connection of service cables, and auxiliary control circuits (if required).

should be tested to verify that they are not defective or have been damaged during installation.

Connecting Power Conductors

Remove the Shipping Skid

AWiringDiagramis furnishedwith theASCO 4000Series 4ADTS (separate from this manual). Refer to this drawing. All wiring must be made in accordance with the National Electrical Code and local codes.

For large switches, open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.

After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solder- less screw type and will accept the wire sizes listed on the drawings provided with the switch. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.

Supporting Foundation

The supporting foundation for the enclosure must level and straight. Refer to the applicable enclosure outline drawing included with the 4ADTS for all mounting details including door opening space.

If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.

Do not run cables in front of or behind the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum for 150-400 amps, 1 inch minimum over 400 amps.

Mounting

Refer to the outlineand mountingdiagram providedwith the ATS; it shows all mounting details and instructions.

It is not necessary to remove the barriers from the transfer switches to install the cables. If you do remove them,however, be sure to reinstall the barriers carefully.

Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the automatic switch switch.

Bus Connections

Mount the ATS vertically to a rigid supporting structure. Levelallmountingpointsbyusing flatwashers behindthe holes to avoid distortion of the switch.

For large switches use grade 5 hardware to connect bus to appropriate terminal plates. Wipe off the bus surfaces beforetheyarejoined. Ifthe busis verydirty, gentlyclean the surfaces with a non---flammable solvent. Avoid touching the cleaned surfaces.

The controller is mounted on the cabinet door. An add- on DIN rail is provided for some optional accessoriesand is mounted below controller on the door.

Tighten bolted joints to the torque specified in Table A.

De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.

The reliability of the connection depends

on how clean and how tight the joint is.

Table A. Tightening torque values for bolted joints

Testing Power Conductors

Bolt Diameter in inchesTightening Torque in foot pounds 1/47 5/1612 3/820 1/250 5/895 3/4155

Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they

(Grade 5 hardware)

Page 4 of the Emerson ADTS user manual — COMMON
Page 4 · click to enlarge
Page 4

Controller Ground

Emerson ADTS — Controller Ground diagram (page 4)
Fig. 2 · Controller Ground

A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.

Signals 5 amps, 32 V DC 5 amps resistive 28 V DC or 120 V AC max.

Feature 14A & 14B

Harnesses

10 amps, 32 V DC 10 amps 250 V AC general purpose

TB Terminal Block (field connections) accepts wire range 22–12 AWG

The transfer switch is connected to the left side of the control panel by a plug-in harness (two plugs).

Emerson ADTS — Harnesses diagram (page 4)
Fig. 3 · Harnesses

Auxiliary Circuits

FEATURE 7

FEATURE 8

Connect auxiliary circuit wires to appropriate terminals on the transfer switch. Note the control features that are furnished on this switch. Make the necessary auxiliary connections by referring to the Wiring Diagram.

Engine Starting Contacts The engine control contact connections (if used) are located on the transfer switch. Connect signal wires to appropriate terminals as specified in Table B and shown in Figures 1–1 and 1–2. See the wiring diagram too.

Figure 1-2. Connections to engine starting contact

terminal block located on 1600 through 3000 amp.

G–design transfer switches.

Table B. Engine start connections

When normal source failsTerminals on transfer switch contact closesTB1 and TB2 contact opensTB1 and TB3

left side of transfer switch

Emerson ADTS — Auxiliary Circuits diagram (page 4)
Fig. 4 · Auxiliary Circuits
Emerson ADTS — Auxiliary Circuits diagram (page 4)
Fig. 5 · Auxiliary Circuits

COMMON

Signals 5 amps, 32 V DC 5 amps resistive 28 V DC or 120 V AC max.

FEATURE 7 closes to start FEATURE 8 opens to start

COMMON

Feature 14A & 14B

FEATURE 14B closed on emergency

10 amps, 32 V DC 10 amps 250 V AC general purpose

FEATURE 14A closed on normal

Optional TS Auxiliary Contacts Feature 14AA & 14BA

COMMON

FEATURE 14BA closed on emergency FEATURE 14AA closed on normal

10 amps, 32 V DC 10 amps 250 V AC general purpose

Figure 1-1. Connections to engine starting contact

terminal block for 150 through 1200 amp.

J & H–design transfer switches.

Show 6 more labels / short text on this page
Engine Starting · TS Auxiliary Contacts · closes to start · opens to start · Engine Starting · TS Auxiliary Contacts
Page 5 of the Emerson ADTS user manual — 1 – Manual Operation Test
Page 5 · click to enlarge
Page 5

Functional Test

The Functional Test consists of three checks:

❐1 — Manual OperationTest, pages1–3 through1–6

❐2 — Voltage Checks, page 1–7

contact position indicators (right side)

❐3 — Electrical Operation, page 1–8

O is open C is closed

Do these checks in the order presented

to avoid damaging the ATS.

Read all instructions on the Wiring Diagram and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding.

Figure 1-3. Contact position indicators on 150–600 amp. J–design transfer switches . Shown with Emergency open and Normal closed.

Continue to 1 – Manual Operation Test starting below.

1 – Manual Operation Test

A detachable operator handle is provided on the transfer switch for maintenance purposes only. Manual operation of the transfer switch must be checked before it is operated electrically.

contact position indicators (right side)

O is open C is closed

Do not manually operate the transfer switch

until both power sources are disconnected:

open both circuit breakers.

Figure 1-4. Contact position indicators on 800–1200 amp. H–design transfer switches . Shown with Emergency open and Normal closed.

1. Select the appropriate switch design / amp. size and follow directions for installing and using the handle:

150–1200 amp J, H–designs Fig. 1-3, -4, -6 thru -11. Attach the manual handle onto the shaft hub, left side of the operator. 1600 – 3000 amp. G–design See Figures 1-5, 1-12. Installthehub (withpin) ontothe shaftand insertthe manual firmly into the side hole in the hub. Push in or pull out hub to engage opposite source contacts.

Emerson ADTS — 1 – Manual Operation Test diagram (page 5)
Fig. 6 · 1 – Manual Operation Test

4000 amp. F–design See Figure 1-13. Insert the manual handle into the hole in the weight.

2. Move the handle as shown to manually operate the Transfer Switch. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris. Repeat the manual operation check on the other Transfer Switch.
3. Return the transfer switch to the N (closed on normal) position. If removable, remove the maintenance handle and store it on the transfer switch in the place provided.

Figure 1-5. Contact position indicators on 1600–3000 amp. G–design transfer switches . Shown with Emergency closed and Normal open.

Show 16 more labels / short text on this page
Emergency contacts · (upper shaft) · window indicators · Normal contacts · (lower shaft) · Emergency contacts · (upper shaft) · window indicators · Normal contacts · (lower shaft) · Emergency contacts · window indicators · contact position indicators · OPEN or CLOSED · (left side) · Normal contacts
Page 6 of the Emerson ADTS user manual — LOWER SHAFT
Page 6 · click to enlarge
Page 6
Emerson ADTS — J–design 150–600 amp diagram (page 6)
Fig. 7 · J–design 150–600 amp
Emerson ADTS — J–design 150–600 amp diagram (page 6)
Fig. 8 · J–design 150–600 amp

J–design 150–600 amp

H–design 800–1200 amp

left side of transfer switch

left side of transfer switch

prevent both N & E contacts

from being closed at the

Normal source contact shaft hub

Normal source contact shaft hub

Figure 1-6. Maintenance handle on 150–600 amp. J–design transfer switches. Hubs shown with Normal

Figure 1-9. Maintenance handle on 800–1200 amp.

H–design transfer switches. Hubs shown with

contacts closed & Emergency open.

Normal contacts closed & Emergency open.

Emerson ADTS — J–design 150–600 amp diagram (page 6)
Fig. 9 · J–design 150–600 amp

UP opens the Emergency source contacts

UP opens the Emergency source contacts

UPPER SHAFT

UPPER SHAFT

DOWN closes the Emergency source contacts frame

DOWN closes the Emergency source contacts frame

Figure 1-7. Emergency (upper shaft) operation

Figure 1-10. Emergency (upper shaft) operation

on 150–600 amp. J–design transfer switches.

on 800–1200 amp. H–design transfer switches.

UP closes the Normal source contacts

UP closes the Normal source contacts

LOWER SHAFT

LOWER SHAFT

DOWN opens the Normal source contacts frame

DOWN opens the Normal source contacts frame

Figure 1-8. Normal (lower shaft) operation on 150–600 amp. J–design transfer switches..

Figure 1-11. Normal (lower shaft) operation on 800–1200 amp. H–design transfer switches..

Show 20 more labels / short text on this page
lobes on weights · maintenance · handle · same time · Emergency source · contact shaft hub · Emergency source · contact shaft hub · clip · maintenance · handle · clips · handle · handle · hub · hub · handle · handle · hub · hub
Page 7 of the Emerson ADTS user manual — J–design 150–600 amp
Page 7 · click to enlarge
Page 7

Do not manually operate the transfer switch

until both power sources are disconnected:

open both circuit breakers.

Table C. Maintenance handle positions on 150–1200 amp. transfer switches. .

Transfer Switch PositionJ–design 150---600 A Interlocked Shafts 1 Link between contact shafts prevents closing both N & E contactsH–design 800---1200 A Interlocked Weights 2 Lobes prevent closing both N & E contactsMaintenance HandleShaft Indicators NormalE Nhub cont ac t s h a fts link hubweight hub lobe lobe hub weightupE = O upper contacts open N = C lower contacts closed up Load DisconnectedE NupE = O upper contacts open N = O lower contacts open down EmergencyE NdownE = C upper contacts closed N = O lower contacts open down
Page 8 of the Emerson ADTS user manual — J–design 150–600 amp
Page 8 · click to enlarge
Page 8

Turn counterclockwise to OPEN contacts.

into hole (spring fully compressed)

Grasp handle firmly with both hands

Turn clockwise to CLOSE contacts.

Slide the hub onto the shaft and insert the pin.

counterclockwise DOWN OPENS the contacts Pull out shaft to open Emergency source contacts (upper) Push in shaft to open Normal source contacts (lower)

clockwise DOWN OPENS the contacts Pull out shaft to close Emergency source contacts (upper) Push in shaft to close Normal source contacts (lower)

contact position indicators (left side)

Figure 1-12. Removable maintenance handle and positions on 1600 – 3000 amp. G–design transfer switches.

Emerson ADTS — J–design 150–600 amp diagram (page 8)
Fig. 10 · J–design 150–600 amp

Figure 1-13. Removable maintenance handle on

4000 amp. F–design transfer switch.

Verify that the maintenance handle has been removed and stored properly before proceeding!

Now continue to 2 – Voltage Checks on page 1–7.

Show 9 more labels / short text on this page
Insert handle · Emergency contacts · window indicators · OPEN or CLOSED · Normal contacts · weight · hole · maintenance · handle
Page 9 of the Emerson ADTS user manual — 2 --- Voltage Checks
Page 9 · click to enlarge
Page 9
Emerson ADTS — 2 --- Voltage Checks diagram (page 9)
Fig. 11 · 2 --- Voltage Checks

Press for 15 Sec.

Figure 1-14. Standard controls and indicators.

1Close the normal source (utility) circuit breaker. Two two left lights should come on. The normal source Accepted (upper left) and the Transfer Switch Position connected to normal (lower left) lights should be on. 2Carefully use an accurate voltmeter to check the phase to phase and phase to neutral voltages present at the transfer switch normal source terminals. 3Close the emergency source (generator) circuit breaker. (Start generator, if necessary.) Another light should come on. The emergency source Accepted light (upper right) should be on. 4Carefully use an accurate voltmeter to check the phase to phase and phase to neutral voltages present at the transfer switch emergency source terminals.* 5Carefully use a phase rotation meter to check the phase rotation of the emergency source; it must be the same as the phase rotation of the normal source (refer to wiring diagram).A B C 6Shut down the generator, if applicable. The emergency source Accepted light (upper right) should go off. Then set the generator’s starting control switch to automatic. Remove all meters; close enclosure door.

2 --- Voltage Checks

First check the nameplate on the transfer switch; the rated voltage must be the same as the normal and emergency line voltages.

Verify that the feeders have been connected to the proper terminal lugs.

Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–14.

  • Black circle means light is on.

❍White circle means light is off.

* If necessary, adjust the voltage regulator on the generator according to the manufacturer’s recommenda- tions. The automatic transfer switch will respond only to the rated voltage specified on the transfer switch nameplate. Note: Refer to Section 3 of the Group 5 Controller User’s Guide 381333–126 for how to display the status of the ATS and the voltage and frequency of each source. Note: Press the Lamp Test button to verify that all five lights work.

Now continue to 3 --- Electrical Operation on next page.

observe these lights

Page 10 of the Emerson ADTS user manual — Transfer Test
Page 10 · click to enlarge
Page 10
Emerson ADTS — 3 --- Electrical Operation diagram (page 10)
Fig. 12 · 3 --- Electrical Operation

step 2 step 4

If this light is on, the buttons will not work until the controls are unlocked. If this light is blinking, the user controls are unlocked for 5 minutes.

Press for 15 Sec.

Figure 1-15. User controls and indicators.

1The two left lights should be on; the normal source Accepted (upper left) and the Transfer Switch Position connected to normal (lower left) should be on. 2Press and hold the Transfer Test button until the generator starts and runs (this should happen within 15 sec.). The emergency source Accepted light (upper right) should come on. 3Then the transfer switch should operate to emergency. The Transfer Switch Position connected to emergency light (lower right) should come on and the connected to normal light (lower left) should be off. If Feature 2B is used, the transfer to emergency will occur after the time delay. 4The transfer switch should operate back to normal after Feature 3A time delay. For immediate retransfer press the Retransfer to Normal button. The Transfer Switch Position connected to normal light (lower left) should come on and the connected to emergency (lower right) light should be off. 5The generator will stop after Feature 2E time delay (unloaded running engine cooldown). The emergency source Accepted light (upper right) should go off.

3 --- Electrical Operation

This procedure will check the electrical operation of the automatic transfer switch. See Figure 1–15.

Be sure to close the enclosure door before proceeding to prevent personal injury

in case of electrical system fault.

Transfer Test

Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.

Perform steps 1 through 5 at the right. Observe the status lights.

  • Black circle means light is on.

❍White circle means light is off.

If the User Controls Locked light is on, the Transfer Test and Retransfer to Normal buttons will not work until you unlock them.

How to unlock the User Controls Press up or down arrow keys on Transfer Control Center (Group 5 Controller), enter the password, and press Enter key. The user controls are now unlocked for 5 minutes. During that time the light will blink.

To lock or unlock the user controls refer to the Group 5 Controller User’s Guide 381333–126. Password informa- tion and time delay settings are also provided there.

This completes the functional test of the ATS.

press these buttons · observe these lights

Page 11 of the Emerson ADTS user manual — In Canada
Page 11 · click to enlarge
Page 11

SECTION 2 TESTING & SERVICE

TRANSFER TEST

DISCONNECTING THE CONTROLLER

Operate the 4000 Series ADTS at least once a month by following the five–step Electrical Operation Transfer Test procedure on page 1–7.

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:

PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 4000 Series ADTS. An annual preventive maintenance program is recom- mended.

Do not unplug the controller until steps 1a or 1b is completed.

1. Observe the position of the transfer switch.

a. If the transfer switch is in the Normal position, first

ASCO Services, Inc. (ASI) is ASCO Power Technologies’s national service organization. In the US ASI can be contacted at 1-800-800-2726 for in- formation on preventive maintenance agreements.

place standby engine starting control in the off position. Second, then open the emergency source circuit breaker. Third, open the normal source circuit breaker.

Checklist for Yearly Inspection

b. If the transfer switch is in the Emergency position,

first open the normal source circuit breaker. Sec- ond, place the engine starting control in the test or run position. Third, openthe emergencysource circuit breaker.

Hazardous voltage capable of causing shock, burns, or death is used in this transfer switch.

Deenergize both Normal – Emergency power

sources before performing inspections!

2. Separate the two quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.

❐Clean the 4ADTS enclosure. Brush and vacuum

away any excessive dust accumulation. Remove any moisture with a clean cloth.

❐Check the transfer switch contacts. Remove the

Do not reconnect the controller until steps 1a or 1b is completed.

transfer switch barriers and check contact condition. Replace the contacts if they become pitted or worn excessively. Reinstall the barriers carefully.

1. Observe the position of the transfer switch.

❐Maintain transfer switch lubrication. If the transfer switch is subjected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and linkages. Relubricate the solenoid operator if the TS coil is replaced. Do not use oil; order lubrication kit 75-100.

a. If the transfer switch is in the Normal position,

first be sure that both normal and emergency source circuit breakers are open. Second, be sure that the standby engine starting control is still in the off position.

b. If the transfer switch is in the Emergency position,

first be sure that both normal and emergency source circuit breakers are open.

❐Check all cable connections & retighten them.

2. The two harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until both latches click. Close the door!

REPLACEMENT PARTS

Replacement parts are available in kit form. When or- dering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch name- plate. Contact your local ASCO Power Technologies Sales Office or ASI:

3. Restore the two sources in sequence as follows:

a. If the transfer switch is in the Normal position,

first close the normal source circuit breaker. Second, closetheemergencysource circuit break- er. Third, place the standby engine starting control in the automatic position.

In the United States

call 1 – 800 – 800 – ASCO ( 2726 )

In Canada

b. If the transfer switch is in the Emergency position,

call 1 – 888 – 234 – ASCO ( 2726 )

first close the emergency source circuit breaker. Second close the normal source circuit breaker.

Disconnecting the Plugs · Reconnecting the Plugs

Page 12 of the Emerson ADTS user manual — TROUBLE-SHOOTING
Page 12 · click to enlarge
Page 12

TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER

2. Use the maintenance handle to manually operate the transfer switch to the opposite source. First open the closed contacts, then close the other contacts. Do not try to close both Normal and Emergency contact. See Manual Operation on page 1–3 through 1–6.

This procedure will manually transfer the load if the controller is disconnected.

3. Then remove the maintenance handle..

Do not manually operate the transfer switch

until both power sources are disconnected

(all conductors deenergized).

Verify that the maintenance handle has been removed before proceeding!

1. Deenergize both the normal and emergency source conductors (remove fuses or open circuit breakers).
4. If the transfer switch is in the Emergency position manually start the engine generator and then install emergency source fuse or close the circuit breaker.

TROUBLE-SHOOTING

Hazardous voltage capable of causing shock,

burns, or death is used in this switch. Do not touch the power or load terminals

of the transfer switch!

Table 2-1. Trouble-Shooting Checks.

PROBLEMCHECK IN NUMERICAL SEQUENCE 1 OPERATION2 GEN-SET3 VOLTAGE Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails.Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting.Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.--- Transfer switch does not transfer the load to the emergency source after the engine–generator set starts.Wait for Feature 2B time delay to time out.Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (57 Hz for a 60 Hz system.) *Voltmeter should read at least 90% of nominal phase to phase voltage between terminals EA and EC (or EL1 and EL2 for 2 pole switches)* Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.Wait for Feature 3A time delay to time out.---Voltmeter should read at least 90% of nominal phase to phase voltage between terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches). Gen. does not stop after load retransfer to normal source.Wait for Feature 2E time delay to time out.Starting control must be in the automatic position.---

* These are factory settings. Refer to Group 5 Controller User’s Guide.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI: in the United States, call 1–800–800–2726 or in Canada call 1–888–234–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
1 OPERATION p.12
Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails.Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting. p.12
Transfer switch does not transfer the load to the emergency source after the engine–generator set starts.Wait for Feature 2B time delay to time out. p.12
Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.Wait for Feature 3A time delay to time out. p.12
Gen. does not stop after load retransfer to normal source.Wait for Feature 2E time delay to time out. p.12

Ask about the Emerson ADTS

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson ADTS

Be the first to ask — other owners or our team will answer.

Original document

Emerson ADTS manual PDF

13 pages·805 KB·Switch·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…