Series 185 Automatic Transfer Switches 100 through 400 ampere sizes
Manual
Refer to the outline and wiring drawings provided with your ASCO Series 185 ATS for all installation details.
ASCO Series 185 Automatic Transfer Switches (ATSs) are Listed under Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby systems in accordance with the National Electrical Code, NEC/NFPA 70, Article 702. This ATS is for use with 2–wire automatic start generators only.
Refer to Application Informaton 381339–292 to confirm that you have selected tha appropriate product for the intended installation.
This automatic transfer switch is intended for standby power applicatons in residential / light commercial use only. This product is not intended for emergency or life–support systems.
An experienced licensed electrician must install the ATS.

If you have more stringent application requirements contact ASCO Power Technologies for other products suitable for critical applications.
Each automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
INSTALLATION 1
CONTROLLER 2–5
FUNCTIONAL TEST 6
SEQUENCE OF OPERATION 7
TROUBLESHOOTING 8–9
INDEX 10
381333–319 A 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
page · 100–230 ampere sizes

Catalog Number Identification
The Transfer Switch nameplate includes data for each specific ASCO Series 185 ATS. Use the ATS only within the limits shown on this nameplate.
A typical Catalog Number is shown below with its elements explained. The example is for a D–design, 2 pole, 200 A, 220–240 V, in a Type 1 indoor enclosure: D 185 A 2 200 F 4 C
load power connections cable spacers (see INSTALLATION)

200 ampere size in typical enclosure with location of customer connections

Installation of the ASCO Series 185 automatic transfer switch (ATS) must be performed by a licensed electrician. It must be installed according to the National Electrical Code (NEC) and all local electrical code requirements. Remove the enclosure cover and inspect the ATS for shipping damage. If damage is evident do not install the ATS.
Refer to the wiring diagram. The ATS must be protected by suitably sized circuit breakers feeding the utility and generator source terminals. The rating of the circuit breakers must be based on the requirements of the National Electrical Code for its nameplate ampere and short circuit withstand ratings.
Refer to the enclosure outline drawing. Mount the ATS according to details and instructions shown on this diagram. Mount the ATS vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the enclosure.
ELECTROCUTION HAZARD Turn off utility power and turn off the generator to prevent electrocution when wiring the transfer switch.
Three cable spacers are included with 200 and 230 ampere transfer switches. Run the copper power cables through the cable spacers as shown in Figure 2. Position the cable spacers approximately 1½ inches from the terminal lugs.
MALFUNCTION or SHORTENED LIFE Protect the ATS from construction grit and metal chips to prevent malfunction or shortened life.
Transfer switches rated 260 and 400 amperes are mounted on an insulator backing piece (installed behind the transfer switch). If the transfer switch is removed from the enclosure and then reinstalled, this insulator must be placed behind the transfer switch. See Figure 1.
CABLE LOOSENING DUE TO SHORT CIRCUIT Install three cable spacers 1 1/2 inches from the power terminals to prevent the cables from loosening during a short–short condition.

FLASH HAZARD – DAMAGE Be sure that the insulator piece is installed behind the 260 and 400 ampere transfer switches.

1 ½ inch approximate
use copper power cables only for 200 and 230 A
Figure 2. Cable spacers for 200 and 230 A.
Figure 1. Insulator for 260 and 400 A.
cable spacers · insulator backing piece · cable spacer

The Group 4 digital Controller is used in ASCO Series 185 automatic transfer switches. It provides the sensing, timing, and control functions for the ATS. This micro– processor–based controller includes built–in control buttons and status lights for control of the ATS and generator.
On the front control display are three push buttons that control the operation of the generator and the ATS.
Before using the transfer test button, be sure that conditions are safe for running the generator and for load transfer.
clock battery cover see page 3

Use this button to test the system. This operation starts the generator and transfers the load. Be sure that conditions are safe to do this operation.
Use this button to cancel the active time delay or exercise period (stops the generator after cooldown).

Use this button to set the automatic generator exerciser (page 3).
Load on Utility light
Bypass Time Delay button
On the front control display are five lights that indicate the status of the sources and the ATS.
Load on Generator light
This light indicates that the utility voltage is acceptable for connection to the load.
Automatic Generator Exerciser light
This light indicates that the generator voltage is acceptable for connection to the load.
Figure 3. Front view of controller.
This light indicates that the generator voltage is acceptable for connection to the load.
This light indicates that the generator voltage is acceptable for connection to the load.
When the utility is acceptable and the load is on the utility, this light flashes the number of days until the next exercise period. When it is off, no exerciser period is set. The light is also off when the generator is running.

5 --- Automatic Generator Exerciser
The generator starting contacts connections are on the controller. Refer to the generator manual. Disconnect the generator battery and verify that the ignition switch is in the OFF position. Connect the generator starting wires to the appropriate terminals on terminal block TB7 as shown on the wiring diagram. For wiring convenience terminal block TB7 has a removable plug. See Figure 4 and Table A.
The built–in automatic generator exerciser can be set to exercise the generator for 20 minutes once every week.
Be sure a fresh battery is installed and turned on. It will maintain the exerciser clock for about 24 hours in case of a power outage.
Recommended 9 volt alkaline batteries are (see Figure 5): Duracell MN 1404, Everready 522, Panasonic 6AM6

Turn on battery by putting S2 DIP switch actuator 10 in the on position (up). See Table B and Figure 6.
1 2 3 4 5 6 7 8 9
TB7 removable terminal block
The generator should be exercised under load or follow the recommendations of the generator manufacturer. Be sure the exerciser is turned on. Then select either exercise with or without load. The ATS will transfer the load to the generator when the exercise with load is selected. See Figure 6 and Table B.
Figure 4. TB7 generator starting contact terminals.
Table B. Generator Exercise Settings
Table A. Generator Start Connections
The time delay and sensor setting in the Group 4 controller are accessible on the inside. Refer to Tables B and C and to Figures 6 and 7. Use a ball–point pen or other pointed tool to slide the DIP switch actuators up or down to match setting shown.
Press and hold (5 seconds) the Set Engine Exerciser button. The exercise period occurs immediately and at the same time weekly thereafter. The status light below the button blinks rapidly to indicate that the exerciser has been set. The number of flashes indicates the number of days until the next exercise period (at approximately the same time the button was pressed).
All power must be off before making any changes.
The factory default settings are shown in Table G on page 5.

cover must be removed to replace 9V battery (use alkaline type)
Press the Set Engine Exerciser button to stop an exercising generator. If exercise with load is set, the ATS retransfers the load to the utility, then stops the generator after cooldown.
Figure 5. Battery replacement.
screw


Figure 6. DIP switches S1 and S2 at the top right.
The time delay settings are shown in Figures 6 and 7 and in Table C. The sensor settings are shown in Figure 6 and in Table D. The standard (factory) settings are shown in Tables C, D, and H.
Figure 7. DIP switch S3 at the bottom center.
Table C. Time Delay Settings

Table D. Voltage and Frequency Settings

* If the dropout voltage is set to 198 V, the pickup voltage must be set to 209 V.

7 --- Factory Settings --- Summary
These remote control features require a customer– supplied normally–closed contact suitable for a 5 V dc low energy circuit. Refer to the wiring diagram provided with the ATS. Activate the appropriate DIP switch S3 actuators as shown in Tables E, F, or G. See Figure 7.
Table H. Factory Settings – Summary

Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load stays on the generator until the remote test circuit is closed.
Table E. Remote test
Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load transfers back to the utility (if acceptable).
Table F. Remote transfer to generator
Normally–closed input. When opened, it bypasses or cancels the generator to utility load transfer time delay. The load transfers back to the utility.
Table G. Bypass load transfer to utility time
delay

After installing the Series 185 automatic transfer switch (ATS) perform the following three–part functional test.

With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers.
A handle is provided on the transfer switch for mainte- nance purposes only. Manual operation of the transfer switch should be checked before it is energized (operated electrically).
weight marked P (utility) and A (generator)
Figure 8. Maintenance handle for 100–230 A.

Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
Figure 9. Maintenance handle for 260–400 A.
This procedure checks the electrical operation of the ATS.
260–400 A Remove the maintenance handle before proceeding!
The ATS is rated for 220–240 V ac 60 or 50 Hz. Verify that both the utility and generator sources are 220–240 V ac 60 or 50 Hz.
This completes the Functional Test.

¡
Utility power good. Electrical loads on utility

3 sec.)
unloaded for 5 min.
© electrical loads



observe these power lights
observe these switch lights
wait 15 min.
for utility to stabilize



wait 10 sec. for generator

This troubleshooting guide describes some of the simple causes of problems with the installation of the automatic transfer switch. Troubleshooting beyond the scope of this guide should not be attempted by the installer. A licensed electrician must perform all internal troubleshooting. ASCO Power Technologies can be contacted at: 1–800–800–2726 or customercare@asco.com
ELECTROCUTION FLASH HAZARD Do not work on the transfer switch until both the utility and generator are off. Turn OFF both circuit breakers.


Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| The Utility Acceptable light does not come on when utility power is connected to the ATS. | 1. Verify that the utility feed is connected and that its circuit breaker is ON. 2. With ALL POWER OFF, verify that the utility feed is 220–240 V ac and 60 Hz. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D for voltage and frequency settings. 3. With ALL POWER OFF, verify that the utility feed is wired to the terminal lugs on the bottom of the transfer switch marked L1 and L5. See the wiring diagram. 4. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight). | p.10 | |
| The generator does not crank when the utility source fails or when the Transfer Test button is pressed. | 1. Hold the Transfer Test button for at least 15 seconds. 2. Verify that the generator starting controls are set for automatic operation (not in manual mode). 3. Verify that the generator battery is connected and that the battery voltage meets the generator manufacturer’s recommendation. 4. Verify that the correct contact (normally open or normally closed) is being utilized (see the generator manual). 5. With ALL POWER OFF, verify engine start low voltage wiring between the controller terminal block and the generator. See the wiring diagram. Check that the plug is properly seated in the receptacle on the controller. | p.10 | |
| The generator cranks but does not start and run when the util- ity source fails or when the Transfer Test button is pressed. | 1. Verify proper generator operation (fuel in tank, oil level, spark plugs --- see generator manual). 2. With ALL POWER OFF, verify engine start low voltage wiring between the controller terminal block and the generator. See the wiring diagram. Check that the plug is properly seated in the receptacle. | p.10 | |
| The generator starts and runs but the Generator Acceptable light does not come on. | 1. Verify that the generator feed is connected and that its circuit breaker is ON. 2. With ALL POWER OFF, verify that the generator feed is 220–240 V ac and 60 Hz. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D for voltage and frequency settings. 3. With ALL POWER OFF, verify that the generator feed is wired to the terminal lugs on the top of the transfer switch marked L2 and L6. See the wiring diagram. 4. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight). 5. Verify generator ac output (voltage and frequency --- see generator manual). | p.10 | |
| The generator starts and runs but the ATS does not transfer the load to the generator. | 1. Verify that the Generator Accepted light is on. If it is off, see previous trouble- shooting problem. The ATS will not transfer the load to an unacceptable source. 2. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight). | p.10 | |
| The ATS does not immediately transfer the load to the generator. | 1. Verify that the Generator Accepted light is on. If it is off, see previous trouble- shooting problem. The ATS will not transfer the load to an unacceptable source. 2. Wait approximately 10 seconds for the transfer to generator time delay. This fixed delay allows the generator output to stabilize before a load is applied to it. 3. Press the Bypass Time Delay button for immediate load transfer to the generator. | p.11 | |
| The ATS transfers the load to the generator, but the genera- tor bogs down (struggles or slows down). The ATS retran- sfers back to the utility. | 1. The generator may be overloaded. Check to see if the generator circuit breaker tripped. Check the sum of the loads to be sure it does not exceed the capacity of the generator. Some motor loads require three times more power for starting. 2. Check for short circuit in a connected load. 3. Observe the Load on Utility and Load on Generator lights. | p.11 | |
| The generator stops after a running for awhile. The ATS retransfers back to the utility (if acceptable). | 1. Verify proper generator operation; it may have run out of fuel or shut down because of low oil level (see generator manual). 2. The generator may be overloaded. Check to see if the generator circuit breaker tripped. Check the sum of the loads to be sure it does not exceed the capacity of the generator. Some motor loads require three times more power for starting. 3. Check for short circuit in a connected load. 4. Observe the Load on Utility and Load on Generator lights. | p.11 | |
| The ATS does not retransfer the load back to the utility. | 1. Verify that the Utility Accepted light is on. The ATS will not transfer the load to an unacceptable source. 2. Wait approximately 15 minutes for the retransfer to utility time delay. The utility must be acceptable for 15 minutes continuously. 3. Press the Bypass Time Delay button for immediate load retransfer to the utility. | p.11 | |
| The ATS retransfers the load back to the utility but the generator keeps running. | 1. Wait approximately 5 minutes for the unloaded running (engine cooldown) time delay. 2. The engine cooldown fixed time delay is important to prevent generator damage. | p.11 | |
| The generator exerciser does not seem to work. | 1. Verify that the Automatic Generator Exerciser light is blinking. When the utility is acceptable and the load is on the utility, this light flashes the number of days until the next exercise period. When the light is off, no exercise period is set. The light is also off when the generator is running. 2. With ALL POWER OFF, verify that the exerciser is turned on. Check DIP switch S1 actuator 7, and S2 actuator 10. See Table B for generator exerciser settings. 3. With ALL POWER OFF, check the 9 volt battery. Replace, if necessary, with a quality alkaline battery: Duracell MN1404, Everready 522, Panasonic 6AM6, or equivalent. See Figure 5. | p.11 | |
| The generator exerciser does not transfer the load to the generator. | 1. With ALL POWER OFF, verify that exercise with load is turned on. Check DIP switch S1 actuator 8. See Table B for generator exerciser settings. | p.11 |