Safety Messages page 1-2 Introduction page 1-3 Workflow page 1-3 Mechanical Installation page 1-4 Electrical Installation page 1-4 Establish HART Communication page 1-10 Transmitter Configuration page 1-13 Modbus Communication Protocol Configuration page 1-14 Alarm Handling page 1-22 Common Modbus Host Configuration page 1-25 Specific Modbus Host Configuration page 1-30 Troubleshooting page 1-34 HMC Firmware Upgrade in Rosemount Radar Master . . page 1-35 Specifications page 1-40
This instruction is a supplement to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Failure to follow safe installation and service guidelines could result in death or serious injury
Explosions could result in death or serious injury
Electrical shock can result in death or serious injury
Probes with non-conducting surfaces

INTRODUCTION The Rosemount 5300 Series and Rosemount 5400 Series transmitters are Modbus compatible measurement devices that support communication with a Remote Terminal Unit (RTU) using a subset of read, write, and diagnostic commands used by most Modbus compatible host controllers. The transmitters also support communication through Levelmaster and Modbus ASCII protocols.
The HART® to Modbus Converter (HMC) module is located inside the Rosemount 5300 and Rosemount 5400 transmitter enclosure and provides power to and communicates with the transmitter through a HART interface.
Figure 1-1. System Overview
During normal operation, the HMC “mirrors” the contents of process variables from the 5300/5400 transmitter to the Modbus registers. To configure the 5300/5400 transmitter, it is possible to connect a configuration tool to the HMC. See “Transmitter Configuration” on page 1-13 for more information.
WORKFLOW Overview of workflow for commissioning a Rosemount 5300 or a Rosemount 5400 transmitter with Modbus protocol:
5300/5400 transmitter enclosure

For instructions on how to mount the Rosemount 5300/5400 transmitter, refer to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).
To connect the Rosemount 5300/5400:

Figure 1-2. Field Wiring Connections

In case it is the last transmitter on the bus, connect the 120termination resistor
HART +
Ambients > 60 ºC Use wiring rated for min 90 ºC

Table 1-1. Connection Terminals
(1) The designation of the connectors do not follow the EIA-485 standard, which states
that RX/TX- should be referred to as 'A' and RX/TX+ as 'B'.
Figure 1-3. Connection Terminals for Rosemount 5300/5400 with HART to Modbus Converter
HART to Modbus Converter
MA
MODBUS
(RS-485)
HART -
- +
POWER
HART
Ambients > 60 ºC Use wiring rated for min 90 ºC

RS-485 Bus • The 5300/5400 transmitters do not provide electrical isolation between the RS-485 bus and the transmitter power supply
Installation cases Install the Rosemount 5300/5400 Series Transmitters as shown in Figure 1-4.
Figure 1-4. Multidrop Connection of 5300/5400 Transmitters

Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC
Internal Ground Screw External Ground Screw
External Ground Screw

Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed as shown in Figure 1-5. If this wiring layout is used, there is an increased risk for communication disturbances due to differences in potential between grounding points. By using the same grounding point for Modbus Master and Power Supply, this risk is reduced.
Figure 1-5. Alternative Multidrop Connection of 5300/5400 Transmitters

Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC
For a Star Topology Connection of the 5300/5400 transmitters, the transmitter with the longest cable run needs to be fitted with a 120- termination resistor.
Figure 1-6. Star Topology Connection of 5300/5400 Transmitters

For Star Topology connection, connect the 120 termination resistor to the transmitter with the longest cable run.
Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC
Ambients > 60 ºC Use wiring rated for min 90 ºC

The HMC supports up to four external HART devices. The external devices are separated by using the HART address. The address must be different between the external devices and only addresses 1 to 5 are allowed for multiple slaves. Connect the devices one at a time and change the short address prior to connecting the next device by using a HART Configuration Tool such as RRM, or a Field Communicator.
The HMC cyclically polls the HART devices for measurement values. The update rate depends on the number of connected devices and is shown in Table 1-2.
Table 1-2. Approximate update rates for measurement values
Figure 1-7. The HMC Module supports up to four external devices (slaves)
Power Supply RS-485 Bus
HART to Modbus Converter
MODBUS
(RS-485)
MA
POWER
HART
Ambients > 60 ºC Use wiring rated for min 90 ºC
Up to four external devices
External HART device 2
External HART device 1
- + · +

The Rosemount 5300 Series and Rosemount 5400 Series can be configured using the Rosemount Radar Master (RRM) PC software or a Field Communicator. Configuration is done by sending HART commands through the HART to Modbus Converter (HMC) to the 5300/5400 transmitter electronics. To establish HART communication, connect to the MA/MB terminals, or to the HART terminals. Both alternatives are described below.
The 5300/5400 level transmitter can be configured with RRM using the MA, MB terminals.
An RS-485 Converter is required to connect to the transmitter.
The transmitter will try to establish communication using different protocols during 20 second timeslots from time of startup.
Figure 1-8. RS-485 Communication after startup
Configured protocol (Modbus RTU, Levelmaster, or Modbus ASCII) 20 seconds
Configured protocol (Modbus RTU, Levelmaster, or Modbus ASCII) 20 seconds
HART 20 seconds Modbus RTU 20 seconds
0 s 20 s 40 s 60 s 80 s 100 s
The transmitter will continue to use a communication protocol once communication has been established.
HART 20 seconds · Time

To configure the 5300/5400 level transmitter using RRM and the MA, MB terminals, do the following:



Take the following into consideration if there are multiple 5300/5400 Modbus units on the bus:
By default, the transmitters have HART address 1. It will not be possible to establish communication on HART address 1 if several transmitters have the same address. In this case, there are alternative solutions to establish communication:

To configure the 5300/5400 transmitter, connect the communicator or PC to the HART terminals using a HART modem, see Figure 1-3 on page 1-6. Both the configuration tool and the RS-485 bus can be connected simultaneously. Configuration data is sent with HART commands through the HMC to the 5300/5400 transmitter electronics, as illustrated in Figure 1-1 on page 1-3. Note that the power supply must be connected during configuration, see also “Electrical Installation” on page 1-4.

Configuration data such as Tank Height, Upper Null Zone, dielectric constants, and other basic parameters are configured in the same way as for a standard Rosemount 5300/5400 transmitter. For more information, see the Rosemount 5300 Series Quick Installation Guide (Document No. 00825-0100-4530), and the Rosemount 5400 Series Quick Installation Guide (Document No. 00825-0100-4026).
Make sure that the measurement unit of the Primary Variable (PV) matches the configuration of the Modbus Host since the transmitter output value does not include any information on associated measurement units.
For further information on basic configuration, see the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

The Rosemount 5300/5400 level transmitter can communicate with RTUs using Modbus RTU (often referred to as just “Modbus”), Modbus ASCII, and Levelmaster (also known as “ROS,” “Siemens,” or “Tank” protocol).
Table 1-3. List of RTUs’ Supported Protocols
ABB Totalflow Modbus RTU, Levelmaster
Bristol ControlWave Micro Modbus RTU
Emerson Process Management ROC800 Series
Modbus RTU, Levelmaster(1)
Modbus RTU, Levelmaster(1)
Emerson Process Management FloBoss 107
Kimray DACC 2000/3000 Levelmaster
Thermo Electron Autopilot Modbus RTU, Levelmaster
(1) Levelmaster protocol should be used when using the Emerson
Process Management Digital Level Sensor (DLS) User Program or Application Module together with the device. Use Modbus RTU in other cases.
Modbus ASCII is not commonly used, since it doubles the amount of bytes for the same message as the Modbus RTU.
If you do not have any of these RTUs, check your RTU manual to see which protocols it supports.
RTU Protocols · ScadaPack Modbus RTU

To change the Modbus address and communication parameters in Rosemount Radar Master (RRM):


It is also possible to enter a user-defined Modbus Message in the Modbus String area.
See separate sections below for more details regarding each Modbus protocol.
Modbus Setup

The Modbus communication parameters can be changed by entering a text string in the HART Message parameter. See separate sections below for details regarding each Modbus protocol and what strings to use.
When using the Field Communicator, the Message Area is reached using HART command [2,2,1], and then selecting Message (menu item 11 for Rosemount 5300 and menu item 10 for Rosemount 5400).
The Rosemount 5300/5400 is configured with the default Modbus RTU address 246, and with the following Modbus RTU communication parameter default settings:
Table 1-4. Modbus RTU Communication Parameters
Parameter Default Value Configurable Values
Baud Rate 9600 1200, 2400, 4800, 9600, 19200
Data Bits(1) Eight Eight
Parity None None, Odd, Even
Stop Bits One One or Two
Address range 246 1-255
(1) Start Bits and Data Bits cannot be changed.
To reset the communication parameters to default Modbus RTU settings, use the following Modbus Message:
Modbus RTU Parameter Configuration Example
You want to use address 44 for the 5300/5400 transmitter, and the following communication parameters are used by the host:
Table 1-5. Communication Parameters Used by the Host (example)

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the HART Slave 1 Message Area:
HMC A44 B4800 PO S2.
HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.
A44: A indicates that the following number is the new address (address 44). Leading zeroes are not needed.
B4800: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).
PO: P identifies the following letter as parity type (O = odd, E = even, and N = none).
S2: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).
Only values that differ from the current values need to be included. For example, if only the address is changed, the following text string is written into the 5300/5400 (HART Slave 1) Message Area:
indicates that 127 is the new address.
The default and configurable parameter values can be found in Table 1-6.
Table 1-6. Levelmaster Communication Parameters
Parameter Default value Configurable value
Baud Rate 9600 1200, 2400, 4800, 9600, 19200
Start Bits One One
Data Bits Seven Seven, Eight
Parity None None, Odd, Even
Stop Bits One One or Two
To reset the communication parameters to default Levelmaster settings, use the following Modbus Message:
Address 1 1-99

You want to use address 2 for the 5300/5400 transmitter and the host uses the following parameters:
Table 1-7. Parameters Used by the Host (in case of Levelmaster, example)
To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area.
HMC M2 A2 B9600 D7 PN S1.
HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.
M2: This means that the Levelmaster protocol is to be used.
A2: A indicates that the following is the new address (address 2). Leading zeroes are not needed.
B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).
D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight).
PN: P identifies the following letter as parity type (O = odd, E = even, and N = none).
S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

In Table 1-8 and Table 1-9 is a description of the implemented functions of Levelmaster protocol in the HMC.
Table 1-8. Implemented Functions of Levelmaster Protocol
Input format Description Output format
UnnN? Return ID number UnnNnnCcccc
UnnNmm Set ID number UnnNOKCcccc
UnnF? Return number of floats UnnFxCcccc
UnnFx? Set number of floats UnnFOKCcccc
Unn? Return floats and other data UnnDddd.ddFfffEeeee WwwwCcccc(1)
(1) In this case, number of floats is set to 1. If number of floats is set to 2, the Output Format
Table 1-9. Letters and Expressions Used in Previous Tables
nn is used to identify slave to respond, nn is a number 00-99 or ** (wildcard). The EmulCtrl Address Holding register can be configured to a higher value than 99. In that case, the address will be truncated to 99.
mm mm is the new ID number for the slave; mm is a number 00-99.
x x is the number of floats returned when slave receives Unn?, x is a number 0-2.
cccc Is the 16 bit CRC checksum, cccc are hexadecimal characters.
ddd.dd ddd.dd is the distance value from slave 1. Note that the first d can also be a ‘-’ (minus).
Float 1 Slave 1 PV.
Float 0 Slave 1 SV.
fff The temperature value. Configured by Holding Register 3208 in HMC.(1)
An error value. Bit 0: Invalid SV value (Float 0). Bit 8: Invalid Temperature value. Bit 12: Invalid PV value (Float 1).
Wwww A warning value, not used in this implementation.
(1) Any of the four available variables from any of the five HART slaves can be selected as
the temperature source. The least four significant bits (bit 0-3) select the variable number. Bits 4-7 select the HART slave address. If invalid values are used, the temperature value will be invalid, with no Error bit set. For example, if we want to use FV from HART Slave 3 as temperature source, we have to write the value 34 Hex (52 decimal).
Letter Description · nn · eeee

The parameter, default, and configurable values are shown in Table 1-10 below.
Table 1-10. Modbus ASCII Communication Parameters
Parameter Default value Configurable values
Baud Rate 9600 1200, 2400, 4800, 9600, 19200
Start Bits One One
Data Bits Seven Seven, Eight
Parity None None, Odd, even
Stop Bits One One or Two
To reset the communication parameters to default Modbus ASCII settings, use the following Modbus Message:
Modbus ASCII Parameter Configuration Example
You want to use address 246 for the 5300/5400 transmitter and the host uses the following parameters:
Table 1-11. Parameters Used by the Host (in case of Modbus ASCII, example)
To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area.
HMC M1 A246 B9600 D7 PN S1.
HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.
M1: This means that the Modbus ASCII protocol is to be used.
A246: A indicates that the following number is the new address (address 246). Leading zeroes are not needed.
B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight).
PN: P identifies the following letter as parity type (O = odd, E = even, and N = none).
S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

ALARM HANDLING NOTE If the Modbus communication setup has been changed, but the transmitter has not yet started to use the new configuration, then you need to disconnect the HART modem and wait up to 60 seconds for the change to take effect.
In case the MA/MB terminals are used for connection to the HMC, disconnect the RS-485 Converter, cycle power to the transmitter and wait up to 60 seconds for the change to take effect.
The Modbus communication settings will otherwise be lost if you write a new message to the transmitter.
The output from the Modbus transmitter in case of an error (such as a field device malfunction) can be configured. The values for Modbus registers corresponding to PV, SV, TV, and QV will be changed accordingly (applicable registers in area 1300, 2000, 2100, and 2200).
The default alarm output value for each protocol is defined on the next page. Configuring alarm output value is optional.
Use the Modbus string to configure the alarm output. To enter a Modbus string in RRM, do the following (Modbus RTU shown):
Modbus Setup


String Alarm Output HMC EN Not a number (NaN), default HMC EF Freeze, hold last value HMC EU U-0.1 User defined value, -0.1 in this example
String Alarm Output HMC M2 EH High value, 999.99, default HMC M2 EL Low value, -99.99 HMC M2 EF Freeze, hold last value HMC M2 EU U0 User defined value (range -99.99 to 999.99), 0 in this example
String Alarm Output HMC M1 EN Not a number (NaN), default HMC M1 EF Freeze, hold last value HMC M1 EU U-0.1 User defined value (range -99.99 to 999.99), -0.1 in this example
In case the MA/MB terminals are used for connection to the HMC, disconnect the RS-485 Converter, cycle power to the transmitter, and wait up to 60 seconds for the change to take effect.

Verify Alarm Output To verify the Alarm Output, use RRM to simulate a device failure:

The transmitter updates status information about the current measurement, and this status information is available as a bitfield register through Modbus communication.
By monitoring the status information it is possible to determine if the current measurement output value is valid. See “Common Modbus Host Configuration” on page 1-25 for details about the individual status bits.
By reading and evaluating the Heartbeat value from the device, it is possible to verify that the communication link between the transmitter, HMC, RTU and even the control system communicating with the RTU is working.
Assign Heartbeat to one of the transmitter variables (SV, TV, or QV). Heartbeat is increased by one for each measurement cycle in the device (until it eventually starts over at zero again).
In case this value is not updated, it means that the communication link is broken.

When using Modbus RTU or Modbus ASCII, the registers to receive status and variables must be configured in the host system.
The transmission of single-precision (4 bytes) IEEE 754 floating point numbers can be rearranged in different byte orders specified by the Floating Point Format Code. The format code information, stated for each Remote Terminal Unit (RTU) respectively, specifies which registers to poll from the 5300/5400 transmitter in order for the RTU to correctly interpret floating point numbers. The byte transmission order for each format code is demonstrated in Table 1-12 below.
Table 1-12. Byte Transmission Order is specified by the Floating Point Format Code
0 [AB] [CD] Straight word order, most significant byte first
1 [CD] [AB] Inverse word order, most significant byte first
2 [DC] [BA] Inverse word order, least significant byte first
3 [BA] [DC] Straight word order, least significant byte first
Between host system and device, it is recommended to use 60 seconds or less between polls, and three retries.
Input Registers The register area starting with 1300 can be configured to have any of the four format codes. The configuration is done by setting FloatingPointFormatCode register (holding register 3000) to 0-3, as shown in Table 1-12. This configuration can be done with the Rosemount Radar Master program.

Table 1-13. Output Variables for the Configurable Floating Point Format (default code 1)
Bit information in bitfield. Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 Non PV. Bit 2: Invalid Measurement Slave 1 Non PV. Bit 3: Invalid Measurement Slave 1 Non PV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV. i.e. all three bits are set simultaneously.
Slave 1 Status Conf 1300
Slave 1 PV Conf 1302 Primary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.
Slave 1 SV Conf 1304 Secondary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.
Slave 1 TV Conf 1306 Tertiary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.
Slave 1 FV Conf 1308 Fourth variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.
Slave 2 data 1310-1318 Same data as for Slave 1.
Slave 3 data 1320-1328 Same data as for Slave 1.
Slave 4 data 1330-1338 Same data as for Slave 1.
Slave 5 data 1340-1348 Same data as for Slave 1.
The Rosemount 5300/5400 register area starting with register 2000 is used for hosts that require Floating Point Format Code 0 (see Table 1-14).
Floating Point Format Codes 2 and 3 use register areas 2100 and 2200, respectively (see Table 1-15 and Table 1-16).
Register Name Register · Number Note

Table 1-14. Output Variables for Floating Point Format Code 0
Register Name Register Number Note
Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.
Slave 1 Status 2000
Slave 1 PV 2002 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.
Slave 1 SV 2004 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.
Slave 1 TV 2006 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.
Slave 1 FV (QV) 2008 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.
Table 1-15. Output Variables for Floating Point Format Code 2
Register Name Register Number Note
Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.
Slave 1 Status 2100
Slave 1 PV 2102 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.

Register Name Register Number Note
Slave 1 SV 2104 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.
Slave 1 TV 2106 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.
Slave 1 FV (QV) 2108 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.
Table 1-16. Output Variables for Floating Point Format Code 3
Register Name Register Number Note
Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.
Slave 1 Status 2200
Slave 1 PV 2202 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.
Slave 1 SV 2204 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.
Slave 1 TV 2206 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.
Slave 1 FV (QV) 2208 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.

Measurement units for the various HART slaves are stored in input registers as a Unit Code presented in Table 1-17. Conversion from Unit Code to measurement unit is given in Table 1-18 on page 1-29.
Table 1-17. Measurement units and corresponding input registers
Register Name Register Number Note
Slave 1 PV Units 104
See Table 1-18 for conversion from Unit Code to Measurement Unit. Slave 1 SV Units 108
Slave 1 TV Units 112
Slave 1 FV (QV) Units 116
Table 1-18. Conversion of Unit Code to Measurement Unit
Unit Code Measurement Unit Unit Code Measurement Unit
40 US Gallon 44 Feet
41 Liters 45 Meters
42 Imperial Gallons 47 Inches
43 Cubic Meters 48 Centimeters
46 Barrels 49 Millimeters
111 Cubic Yards Temperature
112 Cubic Feet 33 Degree Fahrenheit
113 Cubic Inches 32 Degree Celsius
Volume Length

The Remote Terminal Unit needs to be configured to communicate and correctly interpret data when reading input registers from the Rosemount 5300/5400 transmitter.
The specified Baud Rates below are recommendations. If other Baud Rates are used, make sure that the 5300/5400 and the RTU are configured for the same communication speed.
See Section “Common Modbus Host Configuration” on page 1-25.
The RTU Data Type specifies which configuration to use in the RTU in order for the RTU to correctly interpret a floating point number transmitted from the 5300/5400 transmitter with Modbus.
Data registers in the 5300/5400 transmitter with Modbus are numbered exactly as they are transmitted in the Modbus communication. Some RTUs use different naming conventions and to configure the RTU to poll the correct registers from the 5300/5400 Modbus, an Input Register Base Number is stated for each RTU respectively. E.g. if the input register base number is 1 for the RTU, the 5300/5400 Modbus input register 1302 has to be entered in the RTU address as input register 1303.
Figure 1-9. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management ROC800 Series

Table 1-19. Parameter Values (in case of Emerson Process Management ROC800 Series)

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

Figure 1-10. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management FloBoss 107
MA MB POWER + POWER -
A B NC NC PWR GND
+ 8 to + 30 Vdc
(max. rating)
Table 1-20. Parameter Values (in case of Emerson Process Management FloBoss 107)
Floating Point Format Code 0
RTU Data Type Conversion Code 66
Input Register Base Number 0
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.
Figure 1-11. Wiring diagram for connecting 5300/5400 Modbus to ABB TotalFlow
Table 1-21. Parameter Values (in case of ABB TotalFlow)
Floating Point Format Code 0
RTU Data Type 16 Bit Modicon
Input Register Base Number 1
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

Figure 1-12. Wiring Diagram for Connecting 5300/5400 Modbus to Thermo Electron Autopilot
MA MB POWER + POWER -
1 RX + 2 RX -
+ 8 to + 30 Vdc
(max. rating)
Table 1-22. Parameter Values (in case of Thermo Electron Autopilot)
Floating Point Format Code 1
RTU Data Type IEEE Flt 2R
Input Register Base Number 0
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc.
Figure 1-13. Wiring Diagram for Connecting 5300/5400 Modbus to Bristol ControlWave Micro
Com Port 3 (C3) RS-485
6 7 8 9
Power Supply + 8 to + 30 Vdc
GND
(max. rating)
Table 1-23. Parameter Values (in case of Bristol ControlWave Micro)
Floating Point Format Code 2 (FC 4)
RTU Data Type 32-bit registers as 2 16-bit registers
Input Register Base Number 1
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

Figure 1-14. Wiring Diagram for Connecting 5300/5400 Modbus to SCADAPack 32
1 +5 V 2 RX- 3 TX- 4 GND 5 RX+ 6 TX+ 7 Not Used 8 Not Used
+ 8 to + 30 Vdc
(max. rating)
Table 1-24. Parameter Values (in case of SCADAPack 32)
Floating Point Format Code 0
RTU Data Type Floating Point
Input Register Base Number 30001
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 31303 entered as the address etc.
Kimray DACC 2000/3000 This table shows input types in Kimray IMI software and the corresponding value. The communication port must be configured to use “Tank Levels” protocol.
Table 1-25. Kimray Input Types and Corresponding Values
Kimray Inp type 5300/5400 variable Format
Tank Level1 PV ddd.dd.alt. -dd.dd
Tank Level2 SV ddd.dd.alt -dd.dd


The HMC’s firmware is upgraded using Rosemount Radar Master (RRM). A detailed description on how to carry out the firmware upgrade is shown on the following pages.











Checksum




Table 1-26. Specifications
Power supply 8-30 Vdc (max. rating)
Power consumption < 0.5 W (with HART address=1) < 1.2 W (incl. four HART slaves)
Two-wire half duplex RS-485 Modbus. Use shielded twisted pair wiring, preferably with an impedance of 120 (typically 24 AWG), in order to comply with EIA-485 standard and EMC regulations.
The power supply cables must be suitable for the supply voltage and ambient temperature, and approved for use in hazardous areas, where applicable.
Ground (common mode) voltage limit ± 7 V
Bus termination Standard RS-485 bus termination per EIA-485
See the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026) for further specifications.
Signal wiring · Power supply cabling



The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale
© 2010 Rosemount Inc. All rights reserved.
Emerson Process Management Rosemount Measurement 8200 Market Boulevard Chanhassen MN 55317 USA Tel (USA) 1 800 999 9307 Tel (International) +1 952 906 8888 F +1 952 949 7001
Emerson Process Management Shared Services Ltd Heath Place Bognor Regis West Sussex PO22 9SH England Tel +44 (1243) 863 121 Fax +44 (1243) 867 554
Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore 128461 Tel +65 6777 8211 Fax +65 6777 0947 Service Support Hotline: +65 6770 8711 Email: Enquiries@AP.EmersonProcess.com
00809-0500-4530 Rev AA 10/10