Emerson Radar Level Transmitter (5300)

42 pages·942 KB·TV Converter Box·PDF·ENDEFRITNLJA
Emerson Radar Level Transmitter (5300)
Table of Contents 50 sections Safety Messages · Introduction · Workflow · Mechanical Installation · … ShowHide
Safety Messagesp.2Introductionp.3Workflowp.3Mechanical Installationp.4Electrical Installationp.4Connection Terminalsp.6RS-485 Busp.7Installation casesp.7Star Topologyp.8External HART Devices (Slaves)p.9Establish HART Communicationp.10Connect to the MA/MB terminalsp.10Connect to the HART terminalsp.12Transmitter Configurationp.13Modbus Communication Protocol Configurationp.14Using RRM to change communication parametersp.14Using a Field Communicator to change communication parametersp.16Modbus RTU Communication Setupp.16Modbus RTU Parameter Configuration Examplep.16Levelmaster Communication Setupp.17Levelmaster Parameter Configuration Examplep.18Modbus ASCII Communication Setupp.20Modbus ASCII Parameter Configuration Examplep.20Alarm Handlingp.22Verify Alarm Outputp.24Use status information to evaluate measurement validityp.24Use Heartbeat to detect errorsp.24Common Modbus Host Configurationp.25Input Registersp.25Measurement Unitsp.29Specific Modbus Host Configurationp.30Baud Ratep.30Floating Point Format Codep.30RTU Data Typep.30Input Register Base Numberp.30Emerson Process Management ROC800 Seriesp.30Emerson Process Management FloBoss 107p.31ABB TotalFlowp.31Thermo Electron Autopilotp.32Bristol ControlWave Microp.32ScadaPackp.33Kimray DACC 2000/3000p.33Troubleshootingp.34No communication on RS-485 bus (MA, MB)p.34No 5300/5400 communication in RRMp.34No communication with Modbus RTU protocolp.34No communication with Modbus ASCII protocolp.34No communication with Levelmaster protocolp.34HMC Firmware Upgrade in Rosemount Radar Masterp.35Specificationsp.40
Page 1 of the Emerson Radar Level Transmitter (5300) user manual — Rosemount 5300/5400 Series with HART to Modbus Converter
Page 1 · click to enlarge
Page 1

Rosemount 5300/5400 Series with HART to Modbus Converter

Safety Messages page 1-2 Introduction page 1-3 Workflow page 1-3 Mechanical Installation page 1-4 Electrical Installation page 1-4 Establish HART Communication page 1-10 Transmitter Configuration page 1-13 Modbus Communication Protocol Configuration page 1-14 Alarm Handling page 1-22 Common Modbus Host Configuration page 1-25 Specific Modbus Host Configuration page 1-30 Troubleshooting page 1-34 HMC Firmware Upgrade in Rosemount Radar Master . . page 1-35 Specifications page 1-40

This instruction is a supplement to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

www.rosemount.com

Page 2 of the Emerson Radar Level Transmitter (5300) user manual — Safety Messages
Page 2 · click to enlarge
Page 2

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.

Failure to follow safe installation and service guidelines could result in death or serious injury

  • Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
  • Use the equipment only as specified in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026), and in this Manual Supplement. Failure to do so may impair the protection provided by the equipment.
  • Do not perform any services other than those contained in this manual unless you are qualified.

Explosions could result in death or serious injury

  • Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations specifications.
  • To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
  • Before connecting a HART ® or F OUNDATION ™ fieldbus based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
  • To avoid process leaks, only use o-ring designed to seal with the corresponding flange adapter.

Electrical shock can result in death or serious injury

  • Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
  • Make sure the main power to the Rosemount 5300 Series transmitter or Rosemount 5400 Series transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.

Probes with non-conducting surfaces

  • Probes covered with plastic and/or with plastic discs may generate an ignition-capable level of electrostatic charge under certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
Page 3 of the Emerson Radar Level Transmitter (5300) user manual — Introduction
Page 3 · click to enlarge
Page 3

INTRODUCTION The Rosemount 5300 Series and Rosemount 5400 Series transmitters are Modbus compatible measurement devices that support communication with a Remote Terminal Unit (RTU) using a subset of read, write, and diagnostic commands used by most Modbus compatible host controllers. The transmitters also support communication through Levelmaster and Modbus ASCII protocols.

The HART® to Modbus Converter (HMC) module is located inside the Rosemount 5300 and Rosemount 5400 transmitter enclosure and provides power to and communicates with the transmitter through a HART interface.

Figure 1-1. System Overview

HART 5300/5400 signals HART to transmitter Modbus electronics ConverterModbus and Levelmaster communication Remote Terminal Unit HART signals Rosemount Radar Master/ Field CommunicatorRemote Terminal Unit Rosemount Radar Master/ Field Communicator

During normal operation, the HMC “mirrors” the contents of process variables from the 5300/5400 transmitter to the Modbus registers. To configure the 5300/5400 transmitter, it is possible to connect a configuration tool to the HMC. See “Transmitter Configuration” on page 1-13 for more information.

WORKFLOW Overview of workflow for commissioning a Rosemount 5300 or a Rosemount 5400 transmitter with Modbus protocol:

1. Mount the transmitter on the tank.
2. Connect the power and communication wires.
3. Establish HART communication with the transmitter through Rosemount Radar Master, or a Field Communicator. This is done by:
  • Connecting to the HART terminals, or
  • Connecting to the MA/MB terminals (tunneling mode)
4. Configure the transmitter.
5. Configure the Modbus communication.
6. Configure Modbus host.
7. Verify output values as reported by the transmitter.

5300/5400 transmitter enclosure

Page 4 of the Emerson Radar Level Transmitter (5300) user manual — ELECTRICAL INSTALLATION
Page 4 · click to enlarge
Page 4

MECHANICAL INSTALLATION

For instructions on how to mount the Rosemount 5300/5400 transmitter, refer to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

ELECTRICAL INSTALLATION

To connect the Rosemount 5300/5400:

1. Disconnect/shut off the electrical power to transmitter head and then open the instrument cover. Do not remove the cover in an explosive atmosphere with a live circuit.
2. Pull the cable through the cable gland/conduit. For the RS-485 bus, use shielded twisted pair wiring, preferably with an impedance of 120 (typically 24 AWG) in order to comply with the EIA-485 standard and EMC regulations. The maximum cable length is 4000 ft/1200 m.
3. Make sure that the transmitter housing is grounded, then connect wires according to Figure 1-2 and Table 1-1. Connect the lead that originates from the “A” line from the RS-485 bus to the terminal marked MB, and the lead that originates from the “B” line to the terminal marked MA.
4. If it is the last transmitter on the bus, connect the 120 termination resistor.
5. Connect the leads from the positive side of the power supply to the terminal marked POWER +, and the leads from the negative side of the power supply to the terminal marked POWER -. The power supply cables must be suitable for the supply voltage and ambient temperature, and approved for use in hazardous areas, where applicable.
6. Attach and tighten the housing cover. Tighten the cable gland, then plug and seal any unused terminals, and connect the power supply.
Page 5 of the Emerson Radar Level Transmitter (5300) user manual — HART -
Page 5 · click to enlarge
Page 5

Figure 1-2. Field Wiring Connections

Emerson Radar Level Transmitter (5300) — Mechanical Installation diagram (page 5)
Fig. 1 · Mechanical Installation

In case it is the last transmitter on the bus, connect the 120termination resistor

HART -

HART +

Ambients > 60 ºC Use wiring rated for min 90 ºC

Page 6 of the Emerson Radar Level Transmitter (5300) user manual — + HART +
Page 6 · click to enlarge
Page 6

Connection Terminals The connection terminals are described in Table 1-1 below:

Table 1-1. Connection Terminals

Connector labelDescriptionComment HART +Positive HART connectorConnect to PC with RRM software, Field Communicator, or other HART configurators. HART -Negative HART connector MAModbus RS-485 B connection (RX/TX+)(1)Connect to RTU MBModbus RS-485 A connection (RX/TX-)(1) POWER +Positive Power input terminalApply +8 Vdc to +30 Vdc (max. rating) POWER -Negative Power input terminal

(1) The designation of the connectors do not follow the EIA-485 standard, which states

that RX/TX- should be referred to as 'A' and RX/TX+ as 'B'.

Figure 1-3. Connection Terminals for Rosemount 5300/5400 with HART to Modbus Converter

HART to Modbus Converter

MB

MA

MODBUS

(RS-485)

HART -

- +

POWER

HART

Ambients > 60 ºC Use wiring rated for min 90 ºC

+ HART +

Page 7 of the Emerson Radar Level Transmitter (5300) user manual — RS-485 Bus
Page 7 · click to enlarge
Page 7

RS-485 Bus • The 5300/5400 transmitters do not provide electrical isolation between the RS-485 bus and the transmitter power supply

  • Maintain a bus topology and minimize stub length
  • Figure 1-4 identifies multidrop wiring topology, where up to 32 devices may be wired on one RS-485 bus
  • The RS-485 bus needs to be terminated once at each end, but should not be terminated elsewhere on the bus

Installation cases Install the Rosemount 5300/5400 Series Transmitters as shown in Figure 1-4.

  • Use common ground for Modbus Master and Power Supply
  • The Power cables and RS-485 Bus are in the same cable installation
  • An ground cable is installed and shall be used (cable size ≥4 mm according to IEC60079-14, or size according to applicable national regulations and standards). A properly installed threaded conduit connection may provide sufficient ground.
  • The cable shielding is grounded at master site (optional)

Figure 1-4. Multidrop Connection of 5300/5400 Transmitters

Emerson Radar Level Transmitter (5300) — RS-485 Bus diagram (page 7)
Fig. 2 · RS-485 Bus

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Internal Ground Screw External Ground Screw

External Ground Screw

Page 8 of the Emerson Radar Level Transmitter (5300) user manual — Star Topology
Page 8 · click to enlarge
Page 8

Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed as shown in Figure 1-5. If this wiring layout is used, there is an increased risk for communication disturbances due to differences in potential between grounding points. By using the same grounding point for Modbus Master and Power Supply, this risk is reduced.

Figure 1-5. Alternative Multidrop Connection of 5300/5400 Transmitters

Emerson Radar Level Transmitter (5300) — Star Topology diagram (page 8)
Fig. 3 · Star Topology

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Star Topology

For a Star Topology Connection of the 5300/5400 transmitters, the transmitter with the longest cable run needs to be fitted with a 120- termination resistor.

Figure 1-6. Star Topology Connection of 5300/5400 Transmitters

Emerson Radar Level Transmitter (5300) — Star Topology diagram (page 8)
Fig. 4 · Star Topology

For Star Topology connection, connect the 120 termination resistor to the transmitter with the longest cable run.

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Ambients > 60 ºC Use wiring rated for min 90 ºC

Page 9 of the Emerson Radar Level Transmitter (5300) user manual — MB
Page 9 · click to enlarge
Page 9

External HART Devices (Slaves)

The HMC supports up to four external HART devices. The external devices are separated by using the HART address. The address must be different between the external devices and only addresses 1 to 5 are allowed for multiple slaves. Connect the devices one at a time and change the short address prior to connecting the next device by using a HART Configuration Tool such as RRM, or a Field Communicator.

The HMC cyclically polls the HART devices for measurement values. The update rate depends on the number of connected devices and is shown in Table 1-2.

Table 1-2. Approximate update rates for measurement values

No. of devices (slaves)Approx. update rate 12 seconds 23 seconds 34 seconds 45 seconds 55 seconds

Figure 1-7. The HMC Module supports up to four external devices (slaves)

Power Supply RS-485 Bus

HART to Modbus Converter

MB

MODBUS

(RS-485)

MA

POWER

HART

Ambients > 60 ºC Use wiring rated for min 90 ºC

Up to four external devices

External HART device 2

External HART device 1

- + · +

Page 10 of the Emerson Radar Level Transmitter (5300) user manual — Connect to the MA/MB terminals
Page 10 · click to enlarge
Page 10

ESTABLISH HART COMMUNICATION

The Rosemount 5300 Series and Rosemount 5400 Series can be configured using the Rosemount Radar Master (RRM) PC software or a Field Communicator. Configuration is done by sending HART commands through the HART to Modbus Converter (HMC) to the 5300/5400 transmitter electronics. To establish HART communication, connect to the MA/MB terminals, or to the HART terminals. Both alternatives are described below.

Connect to the MA/MB terminals

The 5300/5400 level transmitter can be configured with RRM using the MA, MB terminals.

An RS-485 Converter is required to connect to the transmitter.

The transmitter will try to establish communication using different protocols during 20 second timeslots from time of startup.

Figure 1-8. RS-485 Communication after startup

Configured protocol (Modbus RTU, Levelmaster, or Modbus ASCII) 20 seconds

Configured protocol (Modbus RTU, Levelmaster, or Modbus ASCII) 20 seconds

HART 20 seconds Modbus RTU 20 seconds

0 s 20 s 40 s 60 s 80 s 100 s

The transmitter will continue to use a communication protocol once communication has been established.

HART 20 seconds · Time

Page 11 of the Emerson Radar Level Transmitter (5300) user manual — Establish HART Communication
Page 11 · click to enlarge
Page 11

To configure the 5300/5400 level transmitter using RRM and the MA, MB terminals, do the following:

1. Connect the RS-485 Converter to the MA, MB connectors.
2. Start RRM and open Communication Preferences.
3. Enable HART communication and make sure the port for the RS-485 Converter is selected. Use the following settings:
Emerson Radar Level Transmitter (5300) — Establish HART Communication diagram (page 11)
Fig. 5 · Establish HART Communication
4. Connect the power wires (or cycle power) to the transmitter.
5. Wait 20 seconds and then open the Search Device window in RRM (also see note below). Make sure HART address 1 is being scanned.
Emerson Radar Level Transmitter (5300) — Establish HART Communication diagram (page 11)
Fig. 6 · Establish HART Communication
Page 12 of the Emerson Radar Level Transmitter (5300) user manual — Connect to the HART terminals
Page 12 · click to enlarge
Page 12
6. Connect to the transmitter and perform the necessary configuration.
7. After completing the configuration, disconnect the RS-485 Converter, connect the Modbus communication wires and cycle power to the transmitter
8. Verify communication between the transmitter and the RTU is established (can take up to 60 seconds from startup).

NOTE

Take the following into consideration if there are multiple 5300/5400 Modbus units on the bus:

By default, the transmitters have HART address 1. It will not be possible to establish communication on HART address 1 if several transmitters have the same address. In this case, there are alternative solutions to establish communication:

1. Select the Scan by Tag option in the Search Device window in RRM and enter the HART Device Tag of the transmitter. Communication can now be established with an individual transmitter even if several devices have the same HART address.
Emerson Radar Level Transmitter (5300) — NOTE diagram (page 12)
Fig. 7
2. Make sure the 5300/5400 transmitter is alone on bus. Disconnect or turn off power from any other devices.

Connect to the HART terminals

To configure the 5300/5400 transmitter, connect the communicator or PC to the HART terminals using a HART modem, see Figure 1-3 on page 1-6. Both the configuration tool and the RS-485 bus can be connected simultaneously. Configuration data is sent with HART commands through the HMC to the 5300/5400 transmitter electronics, as illustrated in Figure 1-1 on page 1-3. Note that the power supply must be connected during configuration, see also “Electrical Installation” on page 1-4.

Page 13 of the Emerson Radar Level Transmitter (5300) user manual — TRANSMITTER CONFIGURATION
Page 13 · click to enlarge
Page 13

TRANSMITTER CONFIGURATION

Configuration data such as Tank Height, Upper Null Zone, dielectric constants, and other basic parameters are configured in the same way as for a standard Rosemount 5300/5400 transmitter. For more information, see the Rosemount 5300 Series Quick Installation Guide (Document No. 00825-0100-4530), and the Rosemount 5400 Series Quick Installation Guide (Document No. 00825-0100-4026).

Make sure that the measurement unit of the Primary Variable (PV) matches the configuration of the Modbus Host since the transmitter output value does not include any information on associated measurement units.

For further information on basic configuration, see the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

Page 14 of the Emerson Radar Level Transmitter (5300) user manual — Using RRM to change communication parameters
Page 14 · click to enlarge
Page 14

MODBUS COMMUNICATION PROTOCOL CONFIGURATION

The Rosemount 5300/5400 level transmitter can communicate with RTUs using Modbus RTU (often referred to as just “Modbus”), Modbus ASCII, and Levelmaster (also known as “ROS,” “Siemens,” or “Tank” protocol).

Table 1-3. List of RTUs’ Supported Protocols

ABB Totalflow Modbus RTU, Levelmaster

Bristol ControlWave Micro Modbus RTU

Emerson Process Management ROC800 Series

Modbus RTU, Levelmaster(1)

Modbus RTU, Levelmaster(1)

Emerson Process Management FloBoss 107

Kimray DACC 2000/3000 Levelmaster

Thermo Electron Autopilot Modbus RTU, Levelmaster

(1) Levelmaster protocol should be used when using the Emerson

Process Management Digital Level Sensor (DLS) User Program or Application Module together with the device. Use Modbus RTU in other cases.

Modbus ASCII is not commonly used, since it doubles the amount of bytes for the same message as the Modbus RTU.

If you do not have any of these RTUs, check your RTU manual to see which protocols it supports.

Using RRM to change communication parameters

RTU Protocols · ScadaPack Modbus RTU

Page 15 of the Emerson Radar Level Transmitter (5300) user manual — Modbus Communication Protocol Configuration
Page 15 · click to enlarge
Page 15

To change the Modbus address and communication parameters in Rosemount Radar Master (RRM):

1. Start RRM and connect to the transmitter.
2. In RRM, select Setup>General .
Emerson Radar Level Transmitter (5300) — Modbus Communication Protocol Configuration diagram (page 15)
Fig. 8 · Modbus Communication Protocol Configuration
3. Select the Communication tab.
4. Click the Modbus Setup button.
Emerson Radar Level Transmitter (5300) — Modbus Communication Protocol Configuration diagram (page 15)
Fig. 9 · Modbus Communication Protocol Configuration
5. In the Modbus Setup window, select Modbus protocol and type the desired Modbus address.
6. Enter the baud rate, parity, and stop bits, then click the OK button.

It is also possible to enter a user-defined Modbus Message in the Modbus String area.

See separate sections below for more details regarding each Modbus protocol.

Modbus Setup

Page 16 of the Emerson Radar Level Transmitter (5300) user manual — HMC
Page 16 · click to enlarge
Page 16

Using a Field Communicator to change communication parameters

The Modbus communication parameters can be changed by entering a text string in the HART Message parameter. See separate sections below for details regarding each Modbus protocol and what strings to use.

When using the Field Communicator, the Message Area is reached using HART command [2,2,1], and then selecting Message (menu item 11 for Rosemount 5300 and menu item 10 for Rosemount 5400).

Modbus RTU Communication Setup

The Rosemount 5300/5400 is configured with the default Modbus RTU address 246, and with the following Modbus RTU communication parameter default settings:

Table 1-4. Modbus RTU Communication Parameters

Parameter Default Value Configurable Values

Baud Rate 9600 1200, 2400, 4800, 9600, 19200

Data Bits(1) Eight Eight

Parity None None, Odd, Even

Stop Bits One One or Two

Address range 246 1-255

(1) Start Bits and Data Bits cannot be changed.

To reset the communication parameters to default Modbus RTU settings, use the following Modbus Message:

HMC

Modbus RTU Parameter Configuration Example

You want to use address 44 for the 5300/5400 transmitter, and the following communication parameters are used by the host:

Table 1-5. Communication Parameters Used by the Host (example)

Show 8 more labels / short text on this page
Start Bits(1) · One One · Parameter Value · Baud Rate 4800 · Start Bits One · Data Bits Eight · Parity Odd · Stop Bits Two
Page 17 of the Emerson Radar Level Transmitter (5300) user manual — HMC M2
Page 17 · click to enlarge
Page 17

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the HART Slave 1 Message Area:

HMC A44 B4800 PO S2.

HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.

A44: A indicates that the following number is the new address (address 44). Leading zeroes are not needed.

B4800: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

PO: P identifies the following letter as parity type (O = odd, E = even, and N = none).

S2: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

Only values that differ from the current values need to be included. For example, if only the address is changed, the following text string is written into the 5300/5400 (HART Slave 1) Message Area:

HMC A127 ,

indicates that 127 is the new address.

Levelmaster Communication Setup

The default and configurable parameter values can be found in Table 1-6.

Table 1-6. Levelmaster Communication Parameters

Parameter Default value Configurable value

Baud Rate 9600 1200, 2400, 4800, 9600, 19200

Start Bits One One

Data Bits Seven Seven, Eight

Parity None None, Odd, Even

Stop Bits One One or Two

To reset the communication parameters to default Levelmaster settings, use the following Modbus Message:

HMC M2

Address 1 1-99

Page 18 of the Emerson Radar Level Transmitter (5300) user manual — Levelmaster Parameter Configuration Example
Page 18 · click to enlarge
Page 18

Levelmaster Parameter Configuration Example

You want to use address 2 for the 5300/5400 transmitter and the host uses the following parameters:

Table 1-7. Parameters Used by the Host (in case of Levelmaster, example)

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area.

HMC M2 A2 B9600 D7 PN S1.

HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.

M2: This means that the Levelmaster protocol is to be used.

A2: A indicates that the following is the new address (address 2). Leading zeroes are not needed.

B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight).

PN: P identifies the following letter as parity type (O = odd, E = even, and N = none).

S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

Show 6 more labels / short text on this page
Parameter Value · Baud Rate 9600 · Start Bits One · Data Bits Seven · Parity None · Stop Bits One
Page 19 of the Emerson Radar Level Transmitter (5300) user manual — Levelmaster Parameter Configuration Example
Page 19 · click to enlarge
Page 19

In Table 1-8 and Table 1-9 is a description of the implemented functions of Levelmaster protocol in the HMC.

Table 1-8. Implemented Functions of Levelmaster Protocol

Input format Description Output format

UnnN? Return ID number UnnNnnCcccc

UnnNmm Set ID number UnnNOKCcccc

UnnF? Return number of floats UnnFxCcccc

UnnFx? Set number of floats UnnFOKCcccc

Unn? Return floats and other data UnnDddd.ddFfffEeeee WwwwCcccc(1)

(1) In this case, number of floats is set to 1. If number of floats is set to 2, the Output Format

would beUnnDddd.ddDddd.ddFfffEeeeeWwwwCcccc

Table 1-9. Letters and Expressions Used in Previous Tables

nn is used to identify slave to respond, nn is a number 00-99 or ** (wildcard). The EmulCtrl Address Holding register can be configured to a higher value than 99. In that case, the address will be truncated to 99.

mm mm is the new ID number for the slave; mm is a number 00-99.

x x is the number of floats returned when slave receives Unn?, x is a number 0-2.

cccc Is the 16 bit CRC checksum, cccc are hexadecimal characters.

ddd.dd ddd.dd is the distance value from slave 1. Note that the first d can also be a ‘-’ (minus).

Float 1 Slave 1 PV.

Float 0 Slave 1 SV.

fff The temperature value. Configured by Holding Register 3208 in HMC.(1)

An error value. Bit 0: Invalid SV value (Float 0). Bit 8: Invalid Temperature value. Bit 12: Invalid PV value (Float 1).

Wwww A warning value, not used in this implementation.

(1) Any of the four available variables from any of the five HART slaves can be selected as

the temperature source. The least four significant bits (bit 0-3) select the variable number. Bits 4-7 select the HART slave address. If invalid values are used, the temperature value will be invalid, with no Error bit set. For example, if we want to use FV from HART Slave 3 as temperature source, we have to write the value 34 Hex (52 decimal).

Letter Description · nn · eeee

Page 20 of the Emerson Radar Level Transmitter (5300) user manual — HMC M1
Page 20 · click to enlarge
Page 20

Modbus ASCII Communication Setup

The parameter, default, and configurable values are shown in Table 1-10 below.

Table 1-10. Modbus ASCII Communication Parameters

Parameter Default value Configurable values

Baud Rate 9600 1200, 2400, 4800, 9600, 19200

Start Bits One One

Data Bits Seven Seven, Eight

Parity None None, Odd, even

Stop Bits One One or Two

To reset the communication parameters to default Modbus ASCII settings, use the following Modbus Message:

HMC M1

Modbus ASCII Parameter Configuration Example

You want to use address 246 for the 5300/5400 transmitter and the host uses the following parameters:

Table 1-11. Parameters Used by the Host (in case of Modbus ASCII, example)

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area.

HMC M1 A246 B9600 D7 PN S1.

HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.

M1: This means that the Modbus ASCII protocol is to be used.

A246: A indicates that the following number is the new address (address 246). Leading zeroes are not needed.

B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

Show 7 more labels / short text on this page
Address 1 1-255 · Parameter Value · Baud Rate 9600 · Start Bits One · Data Bits Seven · Parity None · Stop Bits One
Page 21 of the Emerson Radar Level Transmitter (5300) user manual — Modbus ASCII Communication Setup
Page 21 · click to enlarge
Page 21

D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight).

PN: P identifies the following letter as parity type (O = odd, E = even, and N = none).

S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

Page 22 of the Emerson Radar Level Transmitter (5300) user manual — Alarm Handling
Page 22 · click to enlarge
Page 22

ALARM HANDLING NOTE If the Modbus communication setup has been changed, but the transmitter has not yet started to use the new configuration, then you need to disconnect the HART modem and wait up to 60 seconds for the change to take effect.

In case the MA/MB terminals are used for connection to the HMC, disconnect the RS-485 Converter, cycle power to the transmitter and wait up to 60 seconds for the change to take effect.

The Modbus communication settings will otherwise be lost if you write a new message to the transmitter.

The output from the Modbus transmitter in case of an error (such as a field device malfunction) can be configured. The values for Modbus registers corresponding to PV, SV, TV, and QV will be changed accordingly (applicable registers in area 1300, 2000, 2100, and 2200).

The default alarm output value for each protocol is defined on the next page. Configuring alarm output value is optional.

Use the Modbus string to configure the alarm output. To enter a Modbus string in RRM, do the following (Modbus RTU shown):

1. Start RRM and connect to the transmitter.
2. In RRM, select Setup>General .

Modbus Setup

Page 23 of the Emerson Radar Level Transmitter (5300) user manual — Modbus ASCII
Page 23 · click to enlarge
Page 23
3. Select the Communication tab.
4. Click the Modbus Setup button.
Emerson Radar Level Transmitter (5300) — Alarm Handling diagram (page 23)
Fig. 10 · Alarm Handling
5. Enter the Modbus string, and click OK . See below for available Alarm Output Modbus strings.

Modbus RTU

String Alarm Output HMC EN Not a number (NaN), default HMC EF Freeze, hold last value HMC EU U-0.1 User defined value, -0.1 in this example

Levelmaster

String Alarm Output HMC M2 EH High value, 999.99, default HMC M2 EL Low value, -99.99 HMC M2 EF Freeze, hold last value HMC M2 EU U0 User defined value (range -99.99 to 999.99), 0 in this example

Modbus ASCII

String Alarm Output HMC M1 EN Not a number (NaN), default HMC M1 EF Freeze, hold last value HMC M1 EU U-0.1 User defined value (range -99.99 to 999.99), -0.1 in this example

In case the MA/MB terminals are used for connection to the HMC, disconnect the RS-485 Converter, cycle power to the transmitter, and wait up to 60 seconds for the change to take effect.

Page 24 of the Emerson Radar Level Transmitter (5300) user manual — Use Heartbeat to detect errors
Page 24 · click to enlarge
Page 24

Verify Alarm Output To verify the Alarm Output, use RRM to simulate a device failure:

1. Establish HART communication with the transmitter through RRM.
2. Select Simulation Mode in the Tools menu.
Emerson Radar Level Transmitter (5300) — Verify Alarm Output diagram (page 24)
Fig. 11 · Verify Alarm Output
3. Click Enable Device Failure Alarm (simulated) .
4. Click the Start button.
5. Disconnect HART modem.
6. Verify that the configured alarm output is available in the Modbus host.
7. Use RRM to turn off simulation mode.

Use status information to evaluate measurement validity

The transmitter updates status information about the current measurement, and this status information is available as a bitfield register through Modbus communication.

By monitoring the status information it is possible to determine if the current measurement output value is valid. See “Common Modbus Host Configuration” on page 1-25 for details about the individual status bits.

Use Heartbeat to detect errors

By reading and evaluating the Heartbeat value from the device, it is possible to verify that the communication link between the transmitter, HMC, RTU and even the control system communicating with the RTU is working.

Assign Heartbeat to one of the transmitter variables (SV, TV, or QV). Heartbeat is increased by one for each measurement cycle in the device (until it eventually starts over at zero again).

In case this value is not updated, it means that the communication link is broken.

Page 25 of the Emerson Radar Level Transmitter (5300) user manual — COMMON MODBUS HOST CONFIGURATION
Page 25 · click to enlarge
Page 25

COMMON MODBUS HOST CONFIGURATION

When using Modbus RTU or Modbus ASCII, the registers to receive status and variables must be configured in the host system.

The transmission of single-precision (4 bytes) IEEE 754 floating point numbers can be rearranged in different byte orders specified by the Floating Point Format Code. The format code information, stated for each Remote Terminal Unit (RTU) respectively, specifies which registers to poll from the 5300/5400 transmitter in order for the RTU to correctly interpret floating point numbers. The byte transmission order for each format code is demonstrated in Table 1-12 below.

Table 1-12. Byte Transmission Order is specified by the Floating Point Format Code

0 [AB] [CD] Straight word order, most significant byte first

1 [CD] [AB] Inverse word order, most significant byte first

2 [DC] [BA] Inverse word order, least significant byte first

3 [BA] [DC] Straight word order, least significant byte first

Between host system and device, it is recommended to use 60 seconds or less between polls, and three retries.

Input Registers The register area starting with 1300 can be configured to have any of the four format codes. The configuration is done by setting FloatingPointFormatCode register (holding register 3000) to 0-3, as shown in Table 1-12. This configuration can be done with the Rosemount Radar Master program.

Show 4 more labels / short text on this page
Format · Byte transmission · Code · order Description
Page 26 of the Emerson Radar Level Transmitter (5300) user manual — Common Modbus Host Configuration
Page 26 · click to enlarge
Page 26

Table 1-13. Output Variables for the Configurable Floating Point Format (default code 1)

Bit information in bitfield. Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 Non PV. Bit 2: Invalid Measurement Slave 1 Non PV. Bit 3: Invalid Measurement Slave 1 Non PV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV. i.e. all three bits are set simultaneously.

Slave 1 Status Conf 1300

Slave 1 PV Conf 1302 Primary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.

Slave 1 SV Conf 1304 Secondary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.

Slave 1 TV Conf 1306 Tertiary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.

Slave 1 FV Conf 1308 Fourth variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register.

Slave 2 data 1310-1318 Same data as for Slave 1.

Slave 3 data 1320-1328 Same data as for Slave 1.

Slave 4 data 1330-1338 Same data as for Slave 1.

Slave 5 data 1340-1348 Same data as for Slave 1.

The Rosemount 5300/5400 register area starting with register 2000 is used for hosts that require Floating Point Format Code 0 (see Table 1-14).

Floating Point Format Codes 2 and 3 use register areas 2100 and 2200, respectively (see Table 1-15 and Table 1-16).

Register Name Register · Number Note

Page 27 of the Emerson Radar Level Transmitter (5300) user manual — Common Modbus Host Configuration
Page 27 · click to enlarge
Page 27

Table 1-14. Output Variables for Floating Point Format Code 0

Register Name Register Number Note

Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.

Slave 1 Status 2000

Slave 1 PV 2002 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.

Slave 1 SV 2004 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.

Slave 1 TV 2006 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.

Slave 1 FV (QV) 2008 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0.

Table 1-15. Output Variables for Floating Point Format Code 2

Register Name Register Number Note

Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.

Slave 1 Status 2100

Slave 1 PV 2102 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.

Page 28 of the Emerson Radar Level Transmitter (5300) user manual — Common Modbus Host Configuration
Page 28 · click to enlarge
Page 28

Register Name Register Number Note

Slave 1 SV 2104 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.

Slave 1 TV 2106 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.

Slave 1 FV (QV) 2108 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2.

Table 1-16. Output Variables for Floating Point Format Code 3

Register Name Register Number Note

Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously.

Slave 1 Status 2200

Slave 1 PV 2202 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.

Slave 1 SV 2204 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.

Slave 1 TV 2206 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.

Slave 1 FV (QV) 2208 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3.

Page 29 of the Emerson Radar Level Transmitter (5300) user manual — Measurement Units
Page 29 · click to enlarge
Page 29

Measurement Units

Measurement units for the various HART slaves are stored in input registers as a Unit Code presented in Table 1-17. Conversion from Unit Code to measurement unit is given in Table 1-18 on page 1-29.

Table 1-17. Measurement units and corresponding input registers

Register Name Register Number Note

Slave 1 PV Units 104

See Table 1-18 for conversion from Unit Code to Measurement Unit. Slave 1 SV Units 108

Slave 1 TV Units 112

Slave 1 FV (QV) Units 116

Table 1-18. Conversion of Unit Code to Measurement Unit

Unit Code Measurement Unit Unit Code Measurement Unit

40 US Gallon 44 Feet

41 Liters 45 Meters

42 Imperial Gallons 47 Inches

43 Cubic Meters 48 Centimeters

46 Barrels 49 Millimeters

111 Cubic Yards Temperature

112 Cubic Feet 33 Degree Fahrenheit

113 Cubic Inches 32 Degree Celsius

Volume Length

Page 30 of the Emerson Radar Level Transmitter (5300) user manual — Emerson Process Management ROC800 Series
Page 30 · click to enlarge
Page 30

SPECIFIC MODBUS HOST CONFIGURATION

The Remote Terminal Unit needs to be configured to communicate and correctly interpret data when reading input registers from the Rosemount 5300/5400 transmitter.

Baud Rate

The specified Baud Rates below are recommendations. If other Baud Rates are used, make sure that the 5300/5400 and the RTU are configured for the same communication speed.

Floating Point Format Code

See Section “Common Modbus Host Configuration” on page 1-25.

RTU Data Type

The RTU Data Type specifies which configuration to use in the RTU in order for the RTU to correctly interpret a floating point number transmitted from the 5300/5400 transmitter with Modbus.

Input Register Base Number

Data registers in the 5300/5400 transmitter with Modbus are numbered exactly as they are transmitted in the Modbus communication. Some RTUs use different naming conventions and to configure the RTU to poll the correct registers from the 5300/5400 Modbus, an Input Register Base Number is stated for each RTU respectively. E.g. if the input register base number is 1 for the RTU, the 5300/5400 Modbus input register 1302 has to be entered in the RTU address as input register 1303.

Emerson Process Management ROC800 Series

Figure 1-9. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management ROC800 Series

Emerson Radar Level Transmitter (5300) — Emerson Process Management ROC800 Series diagram (page 30)
Fig. 12 · Emerson Process Management ROC800 Series

Table 1-19. Parameter Values (in case of Emerson Process Management ROC800 Series)

Emerson Radar Level Transmitter (5300) — Emerson Process Management ROC800 Series diagram (page 30)
Fig. 13 · Emerson Process Management ROC800 Series

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

Page 31 of the Emerson Radar Level Transmitter (5300) user manual — ABB TotalFlow
Page 31 · click to enlarge
Page 31

Emerson Process Management FloBoss 107

Figure 1-10. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management FloBoss 107

RS-485

MA MB POWER + POWER -

A B NC NC PWR GND

+ 8 to + 30 Vdc

(max. rating)

GND

Table 1-20. Parameter Values (in case of Emerson Process Management FloBoss 107)

Floating Point Format Code 0

RTU Data Type Conversion Code 66

Input Register Base Number 0

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

ABB TotalFlow

Figure 1-11. Wiring diagram for connecting 5300/5400 Modbus to ABB TotalFlow

Table 1-21. Parameter Values (in case of ABB TotalFlow)

Floating Point Format Code 0

RTU Data Type 16 Bit Modicon

Input Register Base Number 1

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

Show 7 more labels / short text on this page
FloBoss 107 · 5300/5400 Modbus · Power Supply · Parameter Value · Baud Rate 9600 · Parameter Value · Baud Rate 9600
Page 32 of the Emerson Radar Level Transmitter (5300) user manual — TXD+
Page 32 · click to enlarge
Page 32

Thermo Electron Autopilot

Figure 1-12. Wiring Diagram for Connecting 5300/5400 Modbus to Thermo Electron Autopilot

CEB TB1

MA MB POWER + POWER -

1 RX + 2 RX -

+ 8 to + 30 Vdc

(max. rating)

GND

Table 1-22. Parameter Values (in case of Thermo Electron Autopilot)

Floating Point Format Code 1

RTU Data Type IEEE Flt 2R

Input Register Base Number 0

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc.

Bristol ControlWave Micro

Figure 1-13. Wiring Diagram for Connecting 5300/5400 Modbus to Bristol ControlWave Micro

Com Port 3 (C3) RS-485

MA MB POWER + POWER -

6 7 8 9

TXD-

Power Supply + 8 to + 30 Vdc

TXD+

GND

(max. rating)

Table 1-23. Parameter Values (in case of Bristol ControlWave Micro)

Floating Point Format Code 2 (FC 4)

RTU Data Type 32-bit registers as 2 16-bit registers

Input Register Base Number 1

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

Show 10 more labels / short text on this page
AutoPILOT · 5300/5400 Modbus · Power Supply · Parameter Value · Baud Rate 9600 · ControlWave Micro · 5300/5400 Modbus · GND DB9 Male · Parameter Value · Baud Rate 9600
Page 33 of the Emerson Radar Level Transmitter (5300) user manual — REF
Page 33 · click to enlarge
Page 33

ScadaPack

Figure 1-14. Wiring Diagram for Connecting 5300/5400 Modbus to SCADAPack 32

1 +5 V 2 RX- 3 TX- 4 GND 5 RX+ 6 TX+ 7 Not Used 8 Not Used

MA MB POWER + POWER -

+ 8 to + 30 Vdc

(max. rating)

REF

Table 1-24. Parameter Values (in case of SCADAPack 32)

Floating Point Format Code 0

RTU Data Type Floating Point

Input Register Base Number 30001

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 31303 entered as the address etc.

Kimray DACC 2000/3000 This table shows input types in Kimray IMI software and the corresponding value. The communication port must be configured to use “Tank Levels” protocol.

Table 1-25. Kimray Input Types and Corresponding Values

Kimray Inp type 5300/5400 variable Format

Tank Level1 PV ddd.dd.alt. -dd.dd

Tank Level2 SV ddd.dd.alt -dd.dd

Show 6 more labels / short text on this page
SCADAPack32 · RS-485 on COM1 · 5300/5400 Modbus · Power Supply · Parameter Value · Baud Rate 9600
Page 34 of the Emerson Radar Level Transmitter (5300) user manual — No communication with Levelmaster protocol
Page 34 · click to enlarge
Page 34

TROUBLESHOOTING No communication on RS-485 bus (MA, MB)

  • Check that the cables are connected
  • Check that PWR+ is connected to + and PWRis connected to - on the power supply
  • Make sure the 5300/5400 transmitter is supplied with 8-30 Vdc (max. rating)
  • Try alternating MA/MB if you are unsure of the polarity
  • If an RS-485 converter is used, make sure it is properly installed and configured
  • The last 5300/5400 transmitter may need a terminating 120resistor connected between MA and MB

No 5300/5400 communication in RRM

  • Using HART+, HART-
  • HART modem is not properly connected
  • Polling address is incorrect in RRM (default 1)
  • Using MA, MB
  • See No communication on RS-485 bus
  • Polling address is incorrect in RRM (default 1)
  • Cycle the power and wait 20 seconds before polling

No communication with Modbus RTU protocol

  • See No communication on RS-485 bus
  • Make sure the “Modbus Communication Protocol Configuration” is done properly
  • Make sure the Modbus RTU address is unique on the bus
  • Cycle the power and try to connect
  • Check the RTU communication settings

No communication with Modbus ASCII protocol

  • See No communication on RS-485 bus
  • Make sure the “Modbus Communication Protocol Configuration” is done properly
  • Make sure the Modbus ASCII address is unique on the bus
  • Cycle the power, waiting 40 seconds before communication begins
  • Check the RTU communication settings

No communication with Levelmaster protocol

  • See No communication on RS-485 bus
  • Make sure the “Modbus Communication Protocol Configuration” is done properly
  • Make sure the Levelmaster address is unique on the bus
  • Cycle the power, waiting 40 seconds before communication begins
  • Check the RTU communication settings
Page 35 of the Emerson Radar Level Transmitter (5300) user manual — HMC FIRMWARE UPGRADE IN ROSEMOUNT RADAR MASTER
Page 35 · click to enlarge
Page 35

HMC FIRMWARE UPGRADE IN ROSEMOUNT RADAR MASTER

The HMC’s firmware is upgraded using Rosemount Radar Master (RRM). A detailed description on how to carry out the firmware upgrade is shown on the following pages.

1. Start RRM and select Communication Preferences in the View menu.
2. Navigate to the Modbus tab and use the following settings:
  • Modem: RS-485
  • Baudrate: According to configuration in HMC (default 9600)
  • Stop Bits: According to configuration in HMC (default 1)
  • Parity: According to configuration in HMC (default None)
  • Handshake: RTS/CTS
  • Response Timeout: 1000 ms
  • Retries: 3
3. Select Enable Modbus Communication and click OK .
Emerson Radar Level Transmitter (5300) — HMC FIRMWARE UPGRADE IN ROSEMOUNT RADAR MASTER diagram (page 35)
Fig. 14
Page 36 of the Emerson Radar Level Transmitter (5300) user manual — HMC Firmware Upgrade in Rosemount Radar Master
Page 36 · click to enlarge
Page 36
4. If the HMC is configured for Modbus ASCII or Levelmaster communication cycle the power to the transmitter (the HMC will then communicate using Modbus RTU for 20 seconds and under that time it is possible to connect with RRM).
5. Open the Search Device window and make sure Modbus is selected in the Protocol list.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 36)
Fig. 15 · HMC Firmware Upgrade in Rosemount Radar Master
6. Search for HMCs by selecting “Scan Address Range”, and choose a start and end address for Modbus. The default HMC Modbus address is 246.
7. Click the Start Scan button.
8. Click OK to connect when the device is found.
9. From the Service menu, choose the Enter Service Mode option.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 36)
Fig. 16 · HMC Firmware Upgrade in Rosemount Radar Master
10. Type password, “admin”.
Page 37 of the Emerson Radar Level Transmitter (5300) user manual — HMC Firmware Upgrade in Rosemount Radar Master
Page 37 · click to enlarge
Page 37
11. From the Service menu, choose the Upload Firmware option.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 37)
Fig. 17 · HMC Firmware Upgrade in Rosemount Radar Master
12. Click Browse.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 37)
Fig. 18 · HMC Firmware Upgrade in Rosemount Radar Master
13. Select the upgrade “.cry” file.
14. Click Open .
Page 38 of the Emerson Radar Level Transmitter (5300) user manual — HMC Firmware Upgrade in Rosemount Radar Master
Page 38 · click to enlarge
Page 38
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 38)
Fig. 19 · HMC Firmware Upgrade in Rosemount Radar Master
15. Click the Upload button to start the firmware upgrade.
16. When upload is finished, select Diagnostics in the Tools menu.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 38)
Fig. 20 · HMC Firmware Upgrade in Rosemount Radar Master
17. Click Device Errors and check for “Checksum”.
18. If it is on the list, choose the Factory Settings option from the Tools menu.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 38)
Fig. 21 · HMC Firmware Upgrade in Rosemount Radar Master

Checksum

Page 39 of the Emerson Radar Level Transmitter (5300) user manual — HMC Firmware Upgrade in Rosemount Radar Master
Page 39 · click to enlarge
Page 39
19. Select All and click OK .
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 39)
Fig. 22 · HMC Firmware Upgrade in Rosemount Radar Master
20. Select “Yes” .
21. Select Restart in the Tools menu to restart the HMC.
22. The checksum error should no longer be present (select Diagnostics in the Tools menu to verify, see Step 16). If it still persists, follow the next steps.
23. Select View Holding Registers in the Service menu and write the value 16760 to register 65510.
Emerson Radar Level Transmitter (5300) — HMC Firmware Upgrade in Rosemount Radar Master diagram (page 39)
Fig. 23 · HMC Firmware Upgrade in Rosemount Radar Master
24. Restart the HMC.
25. If the HMC is configured for Modbus ASCII or Levelmaster communication after upload has been completed, proceed with the following:
1. Close RRM and disconnect the RS-485 converter from the HMC.
2. Cycle the power to the HMC to have it exit Modbus RTU communication mode.
Page 40 of the Emerson Radar Level Transmitter (5300) user manual — SPECIFICATIONS
Page 40 · click to enlarge
Page 40

SPECIFICATIONS

Table 1-26. Specifications

Power supply 8-30 Vdc (max. rating)

Power consumption < 0.5 W (with HART address=1) < 1.2 W (incl. four HART slaves)

Two-wire half duplex RS-485 Modbus. Use shielded twisted pair wiring, preferably with an impedance of 120 (typically 24 AWG), in order to comply with EIA-485 standard and EMC regulations.

The power supply cables must be suitable for the supply voltage and ambient temperature, and approved for use in hazardous areas, where applicable.

Ground (common mode) voltage limit ± 7 V

Bus termination Standard RS-485 bus termination per EIA-485

See the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026) for further specifications.

Signal wiring · Power supply cabling

Page 41 of the Emerson Radar Level Transmitter (5300) user manual — Specifications
Page 41 · click to enlarge
Page 41
Page 41 of the Emerson Radar Level Transmitter (5300) user manual — Specifications
Page 42 of the Emerson Radar Level Transmitter (5300) user manual — Specifications
Page 42 · click to enlarge
Page 42

The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.

Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale

© 2010 Rosemount Inc. All rights reserved.

Emerson Process Management Rosemount Measurement 8200 Market Boulevard Chanhassen MN 55317 USA Tel (USA) 1 800 999 9307 Tel (International) +1 952 906 8888 F +1 952 949 7001

Emerson Process Management Shared Services Ltd Heath Place Bognor Regis West Sussex PO22 9SH England Tel +44 (1243) 863 121 Fax +44 (1243) 867 554

Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore 128461 Tel +65 6777 8211 Fax +65 6777 0947 Service Support Hotline: +65 6770 8711 Email: Enquiries@AP.EmersonProcess.com

00809-0500-4530 Rev AA 10/10

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson Radar Level Transmitter (5300)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Radar Level Transmitter (5300)

Be the first to ask — other owners or our team will answer.

Original document

Emerson Radar Level Transmitter (5300) manual PDF

42 pages·942 KB·TV Converter Box·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…