User Manual

The documentation and the software included with this product are copy- righted 2006 by Advantech Co., Ltd. All rights are reserved. Advantech Co., Ltd. reserves the right to make improvements in the products described in this manual at any time without notice. No part of this man- ual may be reproduced, copied, translated or transmitted in any form or by any means without the prior written permission of Advantech Co., Ltd. Information provided in this manual is intended to be accurate and reli- able. However, Advantech Co., Ltd. assumes no responsibility for its use, nor for any infringements of the rights of third parties, which may result from its use.
Intel and Pentium are trademarks of Intel Corporation.
Microsoft Windows and MS-DOS are registered trademarks of
Microsoft Corp.
All other product names or trademarks are properties of their respective owners.
Part No. 2003476100 1st Edition
Printed in Taiwan March 2006
USB-4761 User Manual ii
Copyright · Acknowledgements

Product Warranty (2 years)
Advantech warrants to you, the original purchaser, that each of its prod- ucts will be free from defects in materials and workmanship for two years from the date of purchase.
This warranty does not apply to any products which have been repaired or altered by persons other than repair personnel authorized by Advantech, or which have been subject to misuse, abuse, accident or improper instal- lation. Advantech assumes no liability under the terms of this warranty as a consequence of such events.
Because of Advantech’s high quality-control standards and rigorous test- ing, most of our customers never need to use our repair service. If an Advantech product is defective, it will be repaired or replaced at no charge during the warranty period. For out-of-warranty repairs, you will be billed according to the cost of replacement materials, service time and freight. Please consult your dealer for more details.
If you think you have a defective product, follow these steps:

This product has passed the CE test for environmental specifications when shielded cables are used for external wiring. We recommend the use of shielded cables. This kind of cable is available from Advantech. Please contact your local supplier for ordering information.
Technical Support and Assistance
where you can find the latest information about the product.
tomer service center for technical support if you need additional assistance. Please have the following information ready before you call: - Product name and serial number - Description of your peripheral attachments - Description of your software (operating system, version, appli- cation software, etc.) - A complete description of the problem - The exact wording of any error messages
To assist us in making improvements to this manual, we would welcome comments and constructive criticism. Please send all such - in writing to: support@advantech.com
Safety Precaution - Static Electricity
Follow these simple precautions to protect yourself from harm and the products from damage.
USB-4761 User Manual iv
Document Feedback


Thank you for buying the Advantech’s USB-4761 data acquisition mod- ule. The Advantech USB-4761 is a powerful data acquisition (DAS) module for the USB port. It features a unique circuit design and complete functions for data acquisition and control.
USB-4761 has the most requested measurement & control functions:

1.1.1 Robust Protection The USB-4761 digital input channels feature a robust isolation protection for industrial, lab and machinery automation applications. It durably withstands voltage up to 2,500 VDC, preventing your host system from any incidental harms. If connected to an external input source with surge protection, the USB-4761 can offer up to a maximum of 2,000 VDC ESD (Electrostatic Discharge) protection.
1.1.2 Wide Input Range The USB-4761 has a wide range of input voltage from 5 to 30 VDC, and it is suitable for most industrial applications with 12 and 24 VDC input volt- age.
1.1.3 Reset Protection for Industrial Applications When the system has undergone a hot reset (i.e. without turning off the system power), USB-4761 can either retain outputs values of each chan- nel, or return to its default configuration as open status, depending on its onboard jumper setting. This function protects the system from wrong operations during unexpected system resets.
1.1.4 Plug & Play Function USB-4761 is a portable Plug-&-Play device that fully complies with the USB 2.0 specification. During module installation, all bus-related config- urations such as base I/O address and interrupts are conveniently taken care of by the Plug-&-Play function. You have virtually no need to set any jumpers or DIP switches.

Before you install your USB-4761 module, please make sure you have the following necessary components:
Some application software is also available for enhanced operation. USB- 4761 works with ActiveDAQ, ActiveDAQ Pro, and other third-party software packages.
After you have the necessary components and maybe some accessories for enhanced operation of your USB DAS module, you can then begin the installation procedure. Figure 1.1 on the next page provides a concise flow chart to give a broad picture of the software and hardware installa- tion procedures.



Advantech offers a rich set of DLL drivers, third-party driver support and application software to help fully exploit the functions of your USB-4761 module:
1.4.1 Programming Choices for DA&C Module: You may use Advantech application software like Advantech Device Drivers. On the other hand, advanced users are allowed to use register- level programming as another option, although this is not recommended due to its laborious and time-consuming nature.
1.4.2 Device Drivers The Advantech Device Drivers software is included on the companion CD-ROM. Advantech’s Device Drivers features a complete I/O function library to help boost your application performance. The Advantech Device Drivers for Windows 2000/XP works seamlessly with develop- ment tools such as Visual C++, Visual Basic, Inprise C++ Builder, and Inprise Delphi.

This section will provide a roadmap to demonstrate how to build an appli- cation from scratch using Advantech Device Drivers with your favorite development tools such as Visual C++, Visual Basic, Delphi, or C++ Builder. The step-by-step instructions on how to build your own applica- tions using each development tool will be given in the Device Drivers Manual. Moreover, a rich set of example source code is also given for your reference.
1.5.1 Programming Tools Programmers can develop application programs with the following devel- opment tools:
For instructions on how to begin programming in each development tool, Advantech offers a Tutorial Chapter in the Device Drivers Manual for your reference. Please refer to the corresponding sections in this chapter on the Device Drivers Manual to begin your programming efforts. You can also look at the example source code provided for each programming tool, since they can get you very well oriented.
The Device Drivers Manual can be found on the companion CD-ROM. Alternatively, if you have already installed the Device Drivers on your system, The Device Drivers Manual can be readily accessed through the Start button:
Start/Programs/Advantech Automation/Advantech Device Manager /Device Driver’s Manual
The example source code can be found under the corresponding installa- tion folder such as the default installation path:
For information about using other function groups or other development tools, please refer to Creating Windows 2000/XP Applications with Device Drivers chapter and the Function Overview chapter in the Device Drivers Manual.
\Program Files\Advantech\ADSAPI\Examples

1.5.2 Programming with Device Drivers Function Library Advantech Device Drivers offer a rich function library that can be uti- lized in various application programs. This function library consists of numerous APIs that support many development tools, such as Visual C++, Visual Basic, Delphi and C++ Builder.
1.5.3 Troubleshooting Device Drivers Error Driver functions will return a status code when they are called to perform a certain task for the application. When a function returns a code that is not zero, it means the function has failed to perform its designated func- tion. To troubleshoot the Device Drivers error, you can pass the error code to DRV_GetErrorMessage function to return the error message. Alternatively, you can refer to the Device Drivers Error Codes Appendix in the Device Drivers Manual for a detailed listing of Error Codes, Error IDs and the Error Messages.

This chapter has a package item check- list, proper instructions about unpack- ing and step-by-step procedures for both driver and USB installation..
Sections include:

After receiving your USB-4761 package, please inspect its contents first. The package should contain the following items:
The USB-4761 Module harbors certain electronic components vulnerable to electrostatic discharge (ESD). ESD could easily damage the integrated circuits and certain components if preventive measures are not carefully paid attention to. Before removing the module from the antistatic plastic bag, you should take following precautions to ward off possible ESD damage:
After taking out the module, you should first:
Inspect the module for any possible signs of external damage (loose or damaged components, etc.). If the module is visibly damaged, please notify our service department or our local sales representative immedi- ately. Avoid using a damaged module with your system.

We recommend you install the software driver before you install the USB-4761 module into your system, since this will guarantee a smooth installation process.
The 32-bit DLL driver Setup program for the USB-4761 module is included on the companion CD-ROM that is shipped with your module package. Please follow the steps below to install the driver software:


For further information on driver-related issues, an online version of the Device Drivers Manual is available by accessing the following path:
\Advantech Device Manager\Device Driver’s Manual
After the DLL driver installation is completed, you can now go on to install the USB-4761 module in any USB port that supports the USB 2.0 standard, on your computer. It is suggested that you refer to the com- puter’s user manual or related documentation if you have any doubts. Please follow the steps below to install the module on your system.
Start\Programs\Advantech Automation


Note: If your module is properly installed, you should see the device name of your module listed on the Device Manager tab. If you see your device name listed, but marked with an exclamation sign “!” (Fig. 2-4), it means your module has not been correctly installed. In this case, remove the mod- ule from Device Manager by selecting its device name and press the Remove button. Then go through the driver installation process again.


After your module is properly installed with your system, you can now configure your device using the Advantech Device Manager that has itself already been installed on your system during driver setup. A com- plete device installation procedure should include device setup, configu- ration and testing. The following sections will guide you through the Setup, Configuration and Testing of your device.
Advantech Device Manager is a utility that allows you to set up, config- ure and test your devices, and later stores your settings in the system reg- istry. These settings will be used when you call the APIs of Advantech 32-bit DLL drivers.
2.4.1 Setting Up the Device Step 1: To complete the device setup and configuration procedures, you must first install the device along with its driver. (Please refer to the previous section of Chapter 2 for detailed installation instructions).


2.4.2 Configuring the Device Step 3: Click “Setup” button and you will see the “Device Setting “dialog box as follow. On the Device Setting dialog box, you can set the DI inter- rupt trigger edge and the power-on DO values.


Start/Programs/Advantech Automation/Advan- tech Device Manager/Device Driver’s Manual
for the firmware download utility guidance and further information.
Following the Setup and Configuration procedures to the last step described in the previous section, you can now proceed to test the device by clicking the Test Button in the I/O Device Installation dialog window. In the Device Test dialog window, you are free to test the functions of USB-4761 on Digital input and Digital output tabs.

2.5.1 Testing Digital Input Function Click the Digital Input tab to show the Digital Input test panel as seen below. By the color of the LEDs, you can easily discern whether the sta- tus of each digital input channel is high or low.

2.5.2 Testing Digital Output Function Click the Digital Output tab to bring up the Digital Output test panel as shown below. By pressing the buttons on each tab, you can easily set each digital output channel as high or low for the corresponding port


Only after your module device is properly set up, configured and tested, can the device installation procedure be considered complete. After the device installation procedure is completed, you can safely proceed to the next chapter, Signal Connections.
Though the Advantech USB modules are hot swappable, we still recom- mend you to follow the hardware un-installation procedure to avoid any unpredictable damages to your device or your system.





This chapter provides useful informa- tion on how to connect input and output signals to the USB-4761 via the I/O connectors..
Sections include:

Maintaining good signal connections is one of the most important factors in ensuring that your application system is sending and receiving data correctly. A good signal connection can avoid unnecessary and costly damage to your PC and other hardware devices.
USB-4761 is equipped with plug-in screw-terminal connectors that facilitate connection to the module without terminal boards or cables.
3.2.1 Pin Assignment Figure 3.1 on next page shows the pin assignments for the five 10-pin I/O connectors on USB-4761.



NO Normally Open pin of relay output
COM Common pin of relay output
NC Normally Close pin of relay output
IDInA Isolated digital input A
IDInB Isolated digital input B
3.2.3 LED Indicator Status Description The USB Module is equipped with a LED indicator to show the current status of the device. When you plug the USB device into the USB port, the LED indicator will blink five times and then stay lit to indicate that it is on. Please refer to the following table for detailed LED indicator status information.
ON Device ready for work
Off Device not ready to work
Slow Blinking (5 times) Device Initialization
Fast Blinking (Depends on data transfer speed).
Signal Name Description · LED Status Description · Device working

3.3.1 Single-ended Channel Connections USB-4761 has 8 isolated digital input channels. Each of isolated digital input channel accepts 10~30 VDC voltage inputs, and accept bi-direc- tional input. It means that you can apply positive or negative voltage to an isolated input pin (Vin ). The figure below shows how to connect an external input source to one of the card's isolated input channels.

After power on, the initial relay output status is shown as below:



Specifications

Optical Isolation 2,500 VDC
Opto-isolator response time 25us
Input Voltage VIH (max.) 30VDC
VIH (min.) 5VDC
Input current 5VDC 1.2mA
12VDC 3.3mA
24VDC 6.9mA
30VDC 8.7mA
Relay Type Form C
Rating (Resistive) 30 VDC@1 A 110 [email protected] A 120 [email protected] A 240 [email protected] A
Max. Switching Power 62.5 VA, 60 W
Max. Switching Voltage 220 VDC,250 VAC
Max. Switching Current 5 A
Breakdown Voltage 1500 V
Operate time 5 ms max.
Release time 4 ms max.
Insulation Resistance 1X109 . (at 500 VDC)
Life Expectancy Mechanical 1X108 operations (typical)
Electrical 12 V@10 mA: 5X107 operations (typical) 6 V@100 mA: 1X107 operations (typical) 60 V@500 mA: 5X105 operations (typical) 30 V@1000 mA: 1X106 operations (typical) 30 V@2000 mA: 2X105 operations (typical)
Channels 8 · VIL (max,) 2VDC · Channels 8

I/O Connector Type Removable 10-pin screw terminal x 5
Dimensions 132 X 80 X 32 mm (5.2” X 3.2” X 1.3”)
Power Consumption 60mA@+5V typical, 400mA@+5V max.
Temperature Operation 0~60 (32~140) (refer to IEC 68-2-1, 2)
Relative Humidity 5%~95% RH non-condensing (refer to IEC 68-2-1, 2)
Storage -20~70 (-4~158) · 29 Appendix A



Function Block


Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.