Meets ADT Security Services Triple Standards Requirements:
LISTED Standards for Security and Fire

Standard for False Alarm Reduction
7 167-0495:110 California State Fire Marshal Approval
K5309V3 6/02 Model SASW3000EN

For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the Customer Care Center in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines).
Early warning fire detection is important in a home. Smoke and heat detectors have played a key role in reducing fire deaths in the United States. With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's National Fire Alarm Code (NFPA 72). These recommendations can be found on page 34 of this manual.
This manual is a step-by-step guide that will acquaint you with the system's features and benefits. It defines the components and their functions, describes their operation, and provides clear step-by-step instructions for normal and emergency procedures. Keep this manual in a convenient place so that you can refer to it as necessary.





Congratulations on your ownership of an ADT Partitioned Security System. You've made a wise decision in choosing it, for it represents the latest in security protection technology today, and millions of premises are protected by ADT systems.
This system provides:
Burglary Protection · Fire Protection · Security Codes

Arming, Step-Arming and Disarming Burglary Protection

The Voice Touchpads feature a voice message center that lets you record and playback one message.
LCD DISPLAY
AND UP VOLUME RECORD
VOLUME
KEY SPEAKER
KEY
1 OFF
AWAY
STAY
RECORD VOLUME PLAY
TEST
BYPASS
MESSAGE
CHIME INSTANT
CODE
MIC
READY
6160VADT-50-003-V0
MICROPHONE
KEY STATUS
VOICE
FUNCTION
DOWN VOLUME
KEY
KEY


Your touchpads are functionally the same, but may have different types of displays, depending on the type installed with your system. To access the keys on the touchpad, simply open the swing-down door.
Custom English 2-line Custom English display touchpads feature a 2-line, Display 32-character alphanumeric LCD which displays system messages in friendly English. These touchpads can also be programmed with custom zone descriptors.
English Display English display touchpads are functionally identical to Custom English display touchpads, but the LCD display uses pre- designated words to identify the nature and location of occurrences.

(QJOLVK'LVSOD\7RXFKSDG
AWAY: All burglary zones, interior and perimeter, are armed.
TEST NOT READY CHIME BAT
BYPASS STAY
STAY: Perimeter burglary zones, such as protected windows and doors, are armed.
CHECK INSTANT
ENGLISH DISPLAY TOUCHPAD
INSTANT: Entry delay is turned off: Lit with STAY = Instant mode Lit with AWAY = Maximum mode
BYPASS: This appears when one or more burglary protection zones have been bypassed.
NOT READY: Appears when burglary portion of the system is not ready for arming (due to open protection zones). The system is ready to arm when this message disappears and the READY indicator light comes on.
NO AC: Appears when AC power has been cut off. System is operating on backup battery power.
AC: Appears when AC power is present.
CHIME: Appears when the CHIME feature is activated.
BAT: Low battery condition in a wireless sensor (if zone number displayed) or low system battery (if no zone number displayed).
ALARM: Appears when an intrusion has been detected and the system is armed (also appears during a fire alarm or audible emergency alarm). Accompanied by the protection zone in alarm.
CHECK: Appears when a malfunction is discovered in the system at any time or if an open is detected in a FIRE zone at any time or a fault in a DAY/NIGHT burglary zone during a disarmed period. Accompanied by a display of zone number in trouble.
FIRE: Appears when a fire alarm is present. Accompanied by a display of the zone in alarm.
A FIRE display also appears when a fire alarm is manually activated, accompanied by a display of emergency key zone number programmed for fire.

for other users of the system.
When on, the opening of windows or doors while the system is disarmed will sound 3 beeps at the touchpad(s).
the system without use of a security code (if programmed). [FUNCTION] Used to enable voice and volume functions.
RECORD, VOLUME, and PLAY functions.
silences alarms and audible trouble indicators, and clears visual display after problem's correction. [RECORD] Used to record up to a 2.5-minute message.
zones. [STATUS] Used to announce system status and faulted zones (if any exist). 14. KEYS 0–9: Numeric keys used to enter your security code(s). 15. MIC: Microphone for Message Center recordings. 16. MESSAGE LED: (red). Flashes red when message waiting or lights steady red when recording a message. 17. READY INDICATOR: (green) Lit when the system is ready to be armed (no faults present). While the system is disarmed, this indicator will go on and off as protection zones are closed and opened. 18. ARMED INDICATOR: (red) Lit when the system has been armed. 19. FUNCTION KEYS: Keys A, B, C, D may have been programmed for a variety of functions, including panic (emergency) functions. For details, see the Function Keys section. 20. INTERNAL SPEAKER: The built-in speaker mimics the alarm sounder during alarms, and will also "beep" during certain system functions. The speaker also provides voice playback for any recorded messages.
perimeter and interior. [VOLUME] Used with the desired ↑ [3] or ↓ [6] keys to set playback and system announcement volume.
system only. Interior protection is not armed, allowing movement within premises without causing an alarm. [PLAY] Used to playback a recorded message. [↑] Used with VOLUME key to raise volume.
a numeric key.
disarmed. Refer to Testing The System section for test procedures.
from being monitored by the system. [↓]Used with VOLUME key to lower volume.
mode, but without the entry delay feature. Entering via an entry/exit door will cause an instant alarm.


Custom English Display Voice Touchpad
(shown without swing-down front door)

within 10 seconds of one another. If 10 seconds elapse without a key depression, the entry will be aborted and must be repeated from its beginning. Be sure to observe this precaution when performing any of the procedures in this manual.

Entry Delays give you time to disarm the system when you re-enter through the designated entrance door. You must disarm the system (simply enter your security code) before the entry delay period ends, or an alarm will occur. The touchpad beeps during the entry delay period, reminding you to disarm the system. There are two entry delays (if programmed). The first is for your primary entrance and the second can be used for a secondary entrance, where a longer delay is required to walk to the touchpad to disarm the system.
You can also arm the system with no entry delay at all by using the INSTANT arming mode. This mode provides greater security while on the premises or while away for extended periods of time.
See your installer for your delay times.
Exit delay gives you time to leave through the designated exit door without setting off an alarm. Exit delay begins immediately after arming your system in any arming mode and Custom Display touchpads display the message “You May Exit Now.” When “You may exit now” disappears, the system is fully armed. If programmed, a slow beeping will sound during the exit delay period, until the last 10 seconds, which then changes to fast beeping (alerting you to the end of exit delay). If you cannot leave by this time, you should stop, disarm the system, and start over to avoid a false alarm.
Exit Delay Restart (if programmed): If you wish to open the entry/exit door to let someone in after arming STAY, you can re-start the exit delay at any time – simply press the [,] key, then let that person in. The system automatically re-arms when exit delay expires, which avoids having to disarm the system and then re-arm it again. In addition, when the system is armed AWAY, reopening and closing the entry/exit door before exit delay time expires (e.g., reentering to get a forgotten item) will reset the exit delay time.
Partition 1 · Partition 2

Whenever you arm the system, the exit delay begins. If an entry/exit door or interior zone is faulted when the exit delay ends (e.g., exit door left open), the system sounds an alarm and starts the entry delay timer. If you disarm the system before the entry delay ends, the alarm sound stops and the message "CANCELED ALARM" or "CA" is displayed on the touchpad, along with a zone number indicating the faulted zone. No message is sent to the Customer Care Center.
To clear the exit alarm condition, the open zone must be made intact; to clear the display, enter your code plus OFF.
If you do not disarm the system before the entry delay ends, and an entry/exit door or interior zone is still open, the alarm sound continues and an "exit alarm" message is sent to the Customer Care Center. The message ""EXIT ALARM" or "EA" is displayed on the touchpad, along with a zone number indicating the faulted zone. To stop the alarm, the system must be disarmed (your code plus OFF); to clear the display, enter your code plus OFF a second time. An “exit alarm” also results if an entry/exit door or interior zone is faulted within two minutes after the end of the exit delay.
Your system may have been programmed for this feature to minimize false alarms sent to the Customer
Care Center. Ask your installer if "Exit Alarm" is active in your system. If so, check this box.

Before arming your system, all protected doors, windows and other protection zones must be closed or bypassed, otherwise the touchpad will display a "Not Ready" message.
Custom Display:
(-7%61)( 46)77 ∗ 83 7,3; *%9087
Voice Status: Voice Touchpads (if installed), can announce system status and faulted zones (up to 3 zone descriptors) if the Voice Status feature is turned on.
To turn the Voice Status feature on/off: # + 0 + 2 + 4
(also turns on Voice Chime mode; see Chime mode section) To announce Status: Press [∗] STATUS key once. To announce faulted zones: Press the [∗] STATUS key a second time within 5 seconds of the first press.


Before arming, close all perimeter doors and windows and make sure the Ready to Arm message is displayed.
Quick Arming If "Quick Arming" was programmed by the installer, the [#] key can be pressed in place of the security code when arming the system in any of its arming modes. However, the security code must always be used to disarm the system.
Function Key Arming For any arming command, a function key may have also been programmed for your system. If so, you can press and hold the appropriate function key for 2 seconds to arm the system. See your installer for the designated functions (see Single Button Arming section).
Refer to the Accessing Other Partitions section for information on multi-partiion arming.
Modes of Arming

The “A”, “B”, “C”, and/or “D” keys on your touchpad may have been programmed for single-button arming. Note that while it will not be necessary to use a security code for arming, a security code must always be used to disarm the system.
Before arming, close all perimeter doors and windows.
(-7%61)( 6)%(= 83 %61
OFF
AWAY
STAY
TEST
BYPASS
INSTANT
CODE
CHECK
# 0 *
D
READY
ADT3000-007-V0
%61)(%;%= =39 1%= )
Single-Button “Step” arming may have been programmed into one of the lettered keys (A, B, C, or D). Check with your installer to see if this has been done in your system.
Ø
Ø
Ø
A, B, C, D Armed-STAY Armed Night-STAY

Your system may be equipped with a keyswitch for use when arming and disarming. Red and green lights on the keyswitch plate indicate the status of your system as follows: Green Light: Lights when the system is disarmed and ready to be armed (no
open zones). If the system is disarmed and the green light is off, it indicates the system is not ready (one or more zones are open).
Red Light: Lights or flashes when system is armed in AWAY or STAY mode. See your installer for the meanings of the lit red light:
Lit Steady = system armed AWAY or
system armed STAY and exit delay has expired
Flashing = system armed STAY and exit delay timer active
Rapid flashing = an alarm has occurred (memory of alarm).
Before arming, close all perimeter doors and windows.
To arm in the AWAY mode:
Turn the key to the right for 1/2 second and release. Touchpads beep twice and the red indicator lights or flashes.
To arm in the STAY mode:
Turn the key to the right and hold for longer than 1 second, then release. Touchpads beep three times and the red indicator lights or flashes.
To disarm the system:
Turn the key to the right and release. The red light turns off

The OFF key is used to disarm the system, silence alarm and trouble sounds, and clear alarm memories.
IMPORTANT: If you return and the main burglary sounder is on, DO NOT ENTER, but CONTACT THE POLICE from a nearby safe location. If you return after an alarm has occurred and the main sounder has shut itself off, the touchpad will beep rapidly upon your entering, indicating that an alarm has occurred during your absence. LEAVE AT ONCE, and CONTACT THE POLICE from a nearby safe location.
(-7%61)( 6)%(= 83 %61
(Security Code) OFF The “READY” indicator light will be lit if all zones are secure, and the touchpad will emit a single tone to confirm that the system is disarmed.

Use this key when you want to arm your system with one or more zones intentionally unprotected.
Vent Zones: Your system may have certain windows set as “vent” zones, which are automatically bypassed if left open when arming the system (you do not need to manually bypass them). However, if a vent zone window is closed after arming, it becomes protected and will cause an alarm if opened again while the system is armed.
(-7%61)( 46)77 83 7,3; *%9087
(Security Code) BYPASS Enter the 2-digit zone number(s) for the zone(s) to be bypassed (e.g., 06, 10, 13, etc.). Single digit zone numbers must be preceded by a zero (e.g. 05, 06).
(-7%61)( &=4%77 6)%(= 83 %61

If programmed, "Quick Bypass" allows you to easily bypass all open (faulted) zones without having to enter zone numbers individually. This feature is useful if, for example, you routinely leave certain windows open when arming at night.
(-7%61)( 46)77 83 7,3; *%9087
(Security Code) BYPASS In a few moments, all open zones will be displayed and automatically bypassed. Make sure that only those zones that you wish to leave unprotected are bypassed, and that there are no other zones unintentionally left open.
(-7%61)( &=4%77 6)%(= 83 %61

To turn Chime Mode on/off (system must be disarmed):
(-7%61)( 6)%(= 83 %61
(Security Code) CHIME The CHIME message appears when on. Perimeter zones will cause a tone when faulted.
(-7%61)( ',-1) 6)%(= 83 %61
The CHIME message disappears when Chime mode is off.
Voice Chime: You can set the Voice Touchpads (if installed) to announce faulted (opened) entry/exit or perimeter zones whenever normal Chime mode is on.
To turn Voice Chime Mode on or off: # + 0 + 2 + 4
(normal Chime mode must be on first) When Voice Chime is on, any faulted zone(s) causes a voice status announcement, chime and display. When off, the sounder still provides chime if normal Chime mode is on.
+ 9

The system lets you view its time and date setting.
+[#] + [6] [3]
(-7%61)( 6)%(= 83 %61
(Security Code) OR, press the function key (A, B, C, or D) for viewing
current date and time, if programmed.
A typical time/date display is shown. The display will remain on for about 30 seconds. 8-1)(%8) 7%8 %1C
If one of the above keys has been programmed for the date/time display feature, place a check mark in the box beneath that key.
You can set the time and date by doing the following:
(-7%61)( 6)%(= 83 %61
8-1)(%8) 7%8 41
8-1)(%8) 7%8 4
(Security Code) · Current time display · Time/date editing display

Your system may have been programmed to use special keys to manually activate emergency (panic) functions as follows:

This Function Sends this signal* With This Sounding… Silent Alarm silent alarm no audible alarm or any visual display indicating that a silent alarm has been initiated. Audible Alarm audible alarm a loud, steady alarm at touchpad(s) and at any external sounders that may be connected. Personal Alarm auxiliary alarm steady alarm sound at touchpad(s), but not at external bells or sirens. Fire Alarm fire alarm temporal (pulsing) sound at external bells and sirens. *All panic functions send signals to the Customer Care Center, if connected.
To activate a Panic Function:
(-7%61)( 6)%(= 83 %61
Press and hold down for at least 2 seconds whichever lettered key on the touchpad has been programmed for the desired emergency function.
Typical Panic Display:
Press both keys of the assigned key pair at the same time.
PRESS BOTH KEYS OF DESIRED PAIR AT THE SAME TIME
OFF
AWAY
STAY
A B C D
ZONE 96 ZONE 95
READY
TEST
BYPASS
CHIME INSTANT
CODE
READY
ARMED
OFF
AWAY
STAY
6160ADT-50-002-V0
6160ADT-50-003-V0
READY
TEST
BYPASS
CHIME INSTANT
CODE
READY
ZONE 99
Lettered Panic Keys Panic Key Pairs
See your installer and use the chart provided in the Features Programmed in Your System section to note the functions that have been programmed for your system.
%0%61 · 0 # · 0 #

The “A”, “B”, “C” or “D” keys can be used to automatically activate a series of commands of up to 16 keystrokes, if programmed for this function. These keystrokes, as a group, are called “macros” and are stored in the system's memory.
See the chart at the back of this manual for the key(s) assigned for macros.
(-7%61)( 6)%(= 83 %61
7)0)'8 1%'63
To exit this mode (and keep the existing macro definition), press any key except the [∗] key. The system returns to normal mode. To define a macro for the selected key, press [∗] and continue with the next prompt.
Enter the first of the series of desired commands, (do not include your user code when programming a macro), then press/hold the “D” key for at least two seconds to complete the first command. This key terminates each separate command, and appears as an “F” in the touchpad display.
(Security Code) · 1%'63 (-740%= · 1%'63 4+1

Typical Macro Display:
The touchpad beeps to acknowledge your input and displays the command you entered (followed by “F”). 4. Enter the next command, followed by press/holding the “D” key for at least two seconds. The touchpad beeps and displays the keystrokes entered so far. 5. Repeat until the all the desired commands (up to 16 characters including the “F”s) have been entered. Be sure to check your keystrokes before continuing. If you made a mistake, you must start over. 6. To exit, press/hold the “D” key for at least two seconds. The display returns to system status and indicates system is ready.
1%'63 4+1 * # * *
Suppose you want to (1) bypass the two upstairs window zones, then (2) turn on an exterior light, and then (3) arm the security system in the AWAY mode. The procedures in the table that follows show you how you would program this macro:

Press [#] and 7 keys for “device ON”, and [01] key for selecting device 1. * #
(-7%61)( 6)%(= 83 %61
)28)6 97)6 '3()

Your system may be set up so that it can control certain lights or other devices.
To Activate Devices:
(-7%61)( 6)%(= 83 %61
+ [#] + [7] + 2-digit device number
(Security Code) Devices associated with that device number activate.
To Deactivate Devices:
+ [#] + [8] + 2-digit device number
(Security Code) Devices associated with that device number deactivate.

Optional 16-digits for Account numbers, PIN numbers, or any other data; programmed by the installer, if required.
A 3-digit code that
describes the event that has occurred in your system (see for event codes table below)
911 = 811 = 101 = 102 =
Alarms. The 4-digit number (CCCC) following this code is the zone number that has caused the alarm.
Troubles. The 4-digit number (CCCC) following this code is the zone number that has caused the trouble.
Open (system disarmed). The 4-digit number (CCCC) that follows this code is the user number that has disarmed the system.
Close (system armed).
The 4-digit number (CCCC) that follows this code is the user number that has armed the system.

Examples of typical 7-digit pager displays follow.
Ex. 1. ³ = Reporting of an alarm (911) caused by a fault on zone 4 (0004) in
partition 1.
Ex. 2. ³ = Reporting of a closing–system arming (102)– by user 5 (0005) in
partition 2.
Your system may be set up so you can manually send a message to up to four pagers.
(-7%61)( 6)%(= 83 %61
(pager no.) Press and hold the programmed Paging Key for at least 2 seconds (wait for beep), then press the pager number (1-4)* representing the pager intended to receive the message. 2. The recipient, on seeing the 999–9999 message, will understand the prearranged meaning of this signal. * If no number is pressed, the message is sent to pager 1.
You can program a schedule that causes a pager report to be sent if the system is not DISARMED by the scheduled time (see Scheduling section, event “03”). For example, a working parent might want a message to be sent to a pager if their child did not arrive home from school and disarm the system by a certain time. If programmed, the message that is sent is: 7 7 7 – 7 .
Pager Display

Authority levels define the system functions a particular user can/cannot perform.
Level Title Explanation N/A System Master Reserved for user 02; Can perform all system functions and assign codes in both partitions; can change its own code as follows: Master code + [8] + 02 + new master code + new master code again
0 Standard User Can only perform security functions in assigned partition. Cannot perform other system functions. 1 Arm Only Can only arm the system. Cannot disarm or do other functions. 2 Guest Can arm the system in assigned partitions, but cannot disarm the system unless the system was armed with this code. This code is typically assigned to someone (such as a babysitter or cleaner) who has a need to arm/disarm the system only at certain times. The user of this code should not use the “Quick Arming” feature. 3 Duress Code Intended for use when you are forced to disarm or arm the system under threat. When used, the system will act normally, but can silently notify the Customer Care Center of your situation, if that service has been provided. 4 Partition Master Can do everything a standard user can do, and can assign
user codes to users in their partition.

The following lists the various command strings for adding user codes and attributes. Refer to the User Setup chart at the back of this manual for factory assignments of user attributes and to keep a record of user programming.
(Users 03/33 are preset User 01 = installer User 03 = partition 1 master to partition masters, User 02 = master User 33 = partition 2 master but can be changed.) The Touchpad beeps once to confirm that new user was added. Delete User Code: System/Partition Master code + [8] + [user no.] + [#] [0] The user code and all attributes* programmed for this user number, including any associated RF keys, are erased from the system. (*except assigned partition) Authority Level: System/Partition Master code + [8] + [user no.] + [#] [1]+ auth. level
Factory Assignments: Authority Levels (see definitions on previous page): users 04-32/34-49 = 0 0 = standard user 3 = duress users 03/33 = 4 1 = arm only 4 = partition master 2 = guest Access Group: System/Partition Master Code + [8] + [user no.] + [#] [2]+ group (1-8)
Factory Assignments: none You can assign users to a group, then set an access schedule that defines the times this group of users can operate the system. The system ignores these users outside the scheduled times. User’s Partition: System Master Code + [8] + [user no.] + [#] [3]+ 0 + partition(s) + [#]
Factory Assignments: This command assigns the partitions the user can access. If more than Part. 1 = users 03-32 one, enter partition numbers sequentially, then press [#] to end. Part. 2 = users 33-49 E.g., master code + [8] + [user no.] + [#] [3] + [0] + [1] [2] + [#] gives the user access to partitions 1 and 2 and the common partition. Partition Entries: 1 = partition 1 and common 2 = partition 2 and common 3 = common partition only RF User Number: System/Partition Master Code + [8] + [user no.] + [#] [4]+ zone no.
Factory Assignments: none Use this command to assign a wireless button device (keyfob) to this user (keyfob must be enrolled in system first; see installer). Zone number: enter the zone number assigned to a button on the keyfob that will be used for arming/disarming by this user. Pager On/Off: System/Partition Master Code + [8] + [user no.] + [#] [5] + 0 or 1
Factory Assignments: You can program a user so that a message is sent to a pager users 01-04 = 0 (off) whenever this code is used to arm or disarm the system. users 05-49 = 1 (on) Paging On/Off: 1 = allow paging; 0 = no paging for this user

Each touchpad is assigned a default partition for display purposes, and will show only that partition's information.

Condition 2 Ö
Condition 3 Ö
Condition 4 Ö
When both partitions are disarmed, the touchpad in each partition displays zone status for its partition only. The common zone touchpad shows the status in that zone only. See Condition 1 above.
When partition 1 is disarmed and partition 2 is armed, the touchpad in partition 1 shows the status of partition 1 and the common zone. Partition 2 will display the status of partition 2 only. See Condition 2 above.
When partition 1 is armed and partition 2 is disarmed, the touchpad in partition 1 shows the status of partition 1 only. Partition 2 will display the status of partition 2 and the common zone. See Condition 3 above.
As long as any one of the two partitions is disarmed, the common zone will always be disarmed. The common zone will be armed only when both partition 1 and 2 are armed. See Condition 4 above.

If the user is authorized, a touchpad in one partition can be used to perform system functions in the other partition by using the GOTO command.
(-7%61)( 6)%(= 83 %61
0 = return to touchpad’s original partition.
1 = partition 1; 2 = partition 2; 3 = common zone The touchpad beeps to confirm the partition change.
(-7%61)( 6)%(= 83 %61
Some users can be given Multi-Partition arming ability by being assigned to both partitions when programming user attributes. When attempting to arm multi-partitions:
+ [0] + arm command (see list below)
(-7%61)( 6)%(= 83 %61
(Security Code) Multi-Partition Arming Commands
2 = arms all partitions AWAY 3 = arms all partitions STAY 33 = arms all partitions NIGHT-STAY 7 = arms all partitions INSTANT 1 = disarms all partitions
(Security Code)

Your system may have been set up to use a common zone, which is an area shared by users of both partitions, such as a foyer or lobby. If so, please note the following:
Ask your installer if a "common zone" was assigned. If so, check
this box


(see Using Device Commands section for a list of output device numbers used in your system) 02 = set a user access schedule for one or more users (see Security Codes section for an explanation of access groups) 03 = send a “latch-key” report to a pager if the system is not disarmed by a specified time; message sent is “777-7777.” 04 = automatically arm the system in STAY mode at a specified time 05 = automatically arm the system in AWAY mode at a specified time 06 = automatically disarm the system at a specified time 07 = Display the word “REMINDER” at a specified time
Press [∗] to continue.
():-') 291&)6
(Master Code) ·


7834 718;8*7 ,, 11%1
6)4)%8 348-32
6%2(31->) =23 ==)7
78%68 718;8*7 · ,, 11%1

(-7%61)( 6)%(= 83 %61
) 9 4 %1
Pressing [#] displays events forward in time. 4. Exit the event log by pressing any key other than [∗] or [#].
(Master Code)

The following table lists the codes that may appear when viewing the Event Log. If the event code is preceded by an “E” (as in the example display on the previous page), it means that the event is new and ongoing; if preceded by an “R,” it means the event has been restored.
Code Definition 110 Fire Alarm 121 Duress 122 Alarm, 24-hour Silent 123 Alarm, 24-hour Audible 131 Alarm, Perimeter
Code Definition 381 RF Supervision Trouble 382 Supervision Auxiliary Wire Zone 383 RF Sensor Tamper 384 RF Sensor Low-battery 393 Clean Me 401 Disarmed, Armed AWAY, Armed STAY 403 Schedule Arm/Disarm AWAY 406 Cancel by User 407 Remote Arm/Disarm (Downloading) 408 Quick Arm AWAY 409 Keyswitch Arm/Disarm AWAY 441 Disarmed/Armed STAY/INSTANT, Quick-Arm STAY/INSTANT 442 Keyswitch Arm/Disarm STAY 570 Bypass 601 Manually Triggered Dialer Test 602 Periodic Test 606 AAV to Follow 607 Walk Test Entered/Exited 623 Event Log 80% Full 625 Real-Time Clock was Changed (log only) 627 Program Mode Entry (log only) 628 Program Mode Exit (log only) 750 - 789 Reserved for Configurable Zone Type report codes (check with central station when using these codes)
135 Alarm, Day/Night 143 Alarm, Expansion Module 145 ECP Module cover tamper 146 Silent Burglary 150 Alarm, 24-Hour Auxiliary/Monitor zone 162 Carbon Monoxide 301 AC Power 302 Low System Battery/Battery Test Fail 305 System Reset (Log only) 309 Battery Test Failure 321 Bell/Siren Trouble 333 Trouble, Expansion Mod. Supervision 341 Trouble, ECP Cover Tamper 344 RF Receiver Jam 351 Telco Line Fault 353 Long Range Radio Trouble 373 Fire Loop Trouble 374 Exit Error Alarm 380 Global Trouble, Trouble Day/Night
132 Alarm, Interior · 134 Alarm, Entry/Exit

Using TEST mode allows each protection point to be checked for proper operation.
1 Disarm the system and close all protected windows, doors, etc. The READY indicator light should come on if all zones are intact (i.e., all protected windows, doors, etc. are closed.
(-7%61)( 6)%(= 83 %61
= (-%0 = ;%0/
(Security Code) TEST The Dial test (option “1”) is intended for the installer and should not be used unless directed to do so by your Customer Care Representative.
beeps from the touchpad. Identification (zone number or zone description) of each faulted protection point should appear on the display. The display clears when the door or window is closed.
8)78 -2 463+6)77

(Security Code) If the test mode is inadvertently left active, it automatically turns off after 4 hours. During the final 5 minutes (after 3 hours 55 minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of Test mode is nearing.

The word CHECK on the touchpad's display, accompanied by a "beeping" at the touchpad, indicates a trouble condition in the system.
To silence the beeping for these conditions, press any key.
Note: A display of CHECK 70 on English Display touchpads indicates that the wiring connection to the external sounder is at fault (opened or shorted), and you should CALL FOR SERVICE. See “BELL FAILURE” on next page. A display of CHECK 90 indicates that RF interference may be impeding the operation of wireless sensors* in the system. See “Rcvr Jam” on next page.
* Not all systems
use wireless sensors.
IF YOU CANNOT CORRECT A "CHECK" DISPLAY, CALL FOR SERVICE.
' , ) ' / & ) ( 6 3 3 1 ; - 2 ( 3 ;
ENGLISH DISPLAY
CUSTOM ENGLISH DISPLAY
TOUCHPAD
TOUCHPAD

Words or letters in parentheses ( ) are those that are displayed on English Display touchpads.
COMM. FAILURE Indicates that a failure has occurred in (or FC) the telephone communication portion of your system. CALL FOR SERVICE.
* Any “beeping” that accompanies a trouble display can be stopped by depressing any key on the touchpad or by entering an OFF sequence (code + OFF)
SYSTEM LO BAT Indicates that a low system battery (or BAT with no condition exists. Display is zone No.) accompanied by "beeping"* at the touchpad. If this condition persists for more than one day (with AC present), CALL FOR SERVICE.
LO BAT Indicates that there is a low battery + zone descriptor condition in the wireless transmitter** (or BAT with number displayed (00 is RF keypad). zone No.) Accompanied by a single "beep"* (about once every 40 seconds) at the touchpad. Either replace the battery yourself, or CALL FOR SERVICE. If the battery is not replaced within 30 days, a CHECK display may occur.
** Not all systems use
wireless sensors.
Rcvr Jam Wireless part of the system is experiencing (or CHECK 90) RF interference which may impede reception from wireless sensors.**
MODEM COMM (or CC)
Indicates that the control is on-line with the Customer Care Center's remote computer. The control will not operate while on-line. Wait a few minutes — the display should disappear.
BELL FAILURE Indicates that the wiring connection to (or CHECK 70) the external sounder is at fault (open or shorted). Accompanied by “beeping” at the touchpad. CALL FOR SERVICE.

AC LOSS The system is operating on battery power (or NO AC) only due to an AC power failure. If only some lights are out on the premises, check circuit breakers and fuses and reset or replace as necessary. If AC power cannot be restored and a “low system battery” message appears (see previous page), CALL FOR SERVICE.
Busy-Standby (or dI)
If this message remains displayed for more than 1 minute, system is disabled. CALL FOR SERVICE.
OPEN CIRCUIT The touchpad is not receiving signals from (or OC) the control. CALL FOR SERVICE.
Long Rng Trbl If part of your system, back-up Long (or bF) Range Radio communication has failed. CALL FOR SERVICE.
TELCO FAULT The telephone line has a problem. (or CHECK 94) CALL FOR SERVICE.
Total Power Failure If there is no touchpad display at all, and the READY indicator
is not lit, operating power (from AC and back-up battery) for the system has stopped and the system is inoperative. CALL FOR SERVICE.
In the event of telephone operational problems, disconnect the control from the phone line by removing the plug from the phone wall jack. We recommend that your installer demonstrate this disconnection on installation of the system. Do not attempt to disconnect the phone connection inside the control. Doing so will result in the loss of your phone lines. If the regular phones work correctly after the control has been disconnected from the phone wall jack, the control has a problem and you should immediately call for service. If upon disconnection of the control, there is still a problem on the phone line, notify the Telephone Company that they have a problem and request prompt phone repair service. The user may not under any circumstances attempt any service or repairs to the security system. Repairs must be made only by ADT authorized service (see the LIMITED WARRANTY statement for information on how to obtain service).
Other Trouble · Displays (Continued)

The components of your security system are designed to be as maintenance-free as possible. However, to make sure that your system is in reliable working condition, do the following: 1. Test your system weekly. 2. Test your system after any alarm occurs.
Silencing Low Battery Warning
You can silence the touchpad’s warning tones by pressing the OFF key, but the touchpad's low battery message display will remain on as a reminder that you have a low battery condition in one or more of your wireless sensors. When you replace the weak battery with a fresh one, the sensor sends a "good battery" signal to the control as soon as the sensor is activated (opening/closing of door, window, etc.), causing the low battery display to turn off. If the sensor is not activated, the display will automatically clear within approximately 1 hour.
Touchpad
Replacing Batteries in Wireless Sensors
Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects a low battery in wireless sensors, including smoke detectors, the personal emergency transmitter, and the portable wireless touchpad and displays a low battery message*. (A low battery in a portable wireless touchpad is detected as soon as one of its keys is pressed, and displayed as 00.). Battery-operated smoke detectors with a low battery also emit a single "chirp" sound approximately once every 20–30 seconds. Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2–4 years of service. 3-volt lithium batteries provide up to 4 or more years of operation. Actual battery life will depend on the environment in which the sensor is used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures or large swings in temperature, may all lead to the reduction of actual battery life in an installation.
Wireless sensors may not have been used in your security system
* The low battery message comes on as a warning that battery replacement in indicated sensor(s) is due within 30 days. In the meantime, a sensor causing a low battery indication is still fully operational.

General Your fire alarm system (if installed) is on 24 hours a day, for continuous protection. In the event of an emergency, the strategically located smoke and heat detectors will sound their alarms and automatically send signals to your system, triggering a loud, interrupted pulsed sound* from the Touchpad(s) and any external sounders. A FIRE message will appear at your Touchpad and remain on until you silence the alarm (see below for silencing fire alarms).
* Temporal pulse sounding is produced for Fire alarms, as follows:
3 pulses–pause–3 pulses–pause–3 pulses–pause. . . , repeated.
ALARM FIRE
AC
* - 6 ) 1 % 7 8 ) 6
Silencing Fire Alarms and Clearing Memory
Depending on the type of smoke detectors in your system, it may be necessary to "reset" the smoke detectors after a fire alarm has been turned off. Check with your installer. This "reset" is accomplished at a touchpad, as follows:
Enter User Code*, then press the [1] key (* except “arm only” user). NOTE: During smoke detector reset, “FAULT x” is displayed (about 6 seconds) and should disappear if the detector is clear.

Manually
A key or key pair may have been assigned for manually initiating a FIRE alarm. See the Panic Keys section for key assignments. For convenience, indicate the key or key pair assigned for fire below. Individual Keys
A B C
Press the individual key assigned for fire for 2
seconds. OR Key Pairs
1 O F F and ∗ R E A D Y
∗ R E A D Y and #
Press the key pair assigned for fire at the same time.
3 S T A Y and #
AC
* - 6 ) ALARM FIRE
CUSTOM DISPLAY TOUCHPAD ENGLISH DISPLAY TOUCHPAD

1DWLRQDO)LUH3URWHFWLRQ$VVRFLDWLRQ 5HFRPPHQGDWLRQVRQ6PRNH'HWHFWRUV
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's National Fire Alarm Code (NFPA 72) noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics.
In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
DINING
BEDROOM
BEDROOM
TV ROOM KITCHEN
DINING
BDRM
LIVING ROOM
BDRM
LIVING ROOM
BEDROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
BEDROOM BEDROOM TO BR
KTCHN L
GARAGE L
. CLOSED DOOR
LVNG RM
BASEMENT

(PHUJHQF\(YDFXDWLRQ
Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association: 1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other may be a window, should your path be impassable. Station an escape ladder at such windows if there is a long drop to the ground. 3. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room. 4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape. 5. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in. 6. When smoke is present, crawl on the ground. Do not walk upright, since smoke rises and may overcome you. Clearer air is near the floor. 7. Escape quickly; don't panic. 8. Establish a common meeting place outdoors, away from your house, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the house — many die going back


Check Zones Press READY key. View faulted zones when system not ready.
Arm System Enter code. Press arming key desired: (AWAY, STAY, NIGHT-STAY, INSTANT)
Arms system in mode selected.
Quick Arm (if programmed)
Press #. Press arming key desired: (AWAY, STAY, INSTANT)
Arms system in mode selected, quickly and without use of a code.
Bypass Zone(s) Enter code. Press BYPASS key. Enter zone number(s) to be bypassed (use 2-digit entries).
Bypassed zones are unprotected and will not cause an alarm if violated.
Quick Bypass (if programmed)
Enter code. Press BYPASS key + [#]. Bypasses all faulted zones automatically.
Burglary:
Enter code. Press OFF key.
Also disarms system. Memory of alarm remains until cleared.
Press OFF key. Press any key.
Memory of Alarm remains until cleared. Determine cause.
Disarm System Enter code. Press OFF key. Also silences sounders. Memory of alarm remains until cleared.
After disarming, enter code again. Press OFF key again.
Touchpad beeps rapidly on entry if alarm has occurred while absent. Alarm display will remain upon disarming until cleared.
Duress (if active and connected to Customer Care Center)
Arm or disarm "normally", but use your 4-digit Duress code to do so.
Performs desired action and sends silent alarm to Customer Care Center.
Panic Alarms (as programmed)
Press key [A], [B], or [C] for at least 2 seconds.
See the Panic Keys section for emergency functions programmed for your system. Note: Keys “A”, “B”, and “C” may have been programmed for other functions.
Chime Mode To turn ON or OFF: Enter code. Press CHIME key.
The touchpad will sound if doors or windows are violated while system is disarmed and chime mode is ON.
Test Mode To turn ON: Enter code. Press TEST key. To turn OFF: Enter code. Press OFF key.
Tests alarm sounder and allows sensors to be tested.
Phone Access (Smartphone Module) if applicable
Consult Phone Access User's Guide that accompanies the Phone Module.
Permits system access remotely, via Touch-tone phone.
Silence Sounders · Clear Alarm Memory

FIRE ALARM FIRE is displayed; zone number of zone in alarm is displayed. If a fire alarm is manually activated, zone number 95 will be displayed.
Touchpad & Ext.
LOUD, CONTINUOUS* Touchpad & Ext.
ALARM is displayed. Zone number of zone in alarm is also displayed.
ONE SHORT BEEP (not repeated) Touchpad only
a. SYSTEM DISARM b. SYSTEM ARMING ATTEMPT WITH AN OPEN ZONE.
a. READY indicator light comes on. b. Number of the open protection zone displayed.
c. BYPASS VERIFY
c. Zone numbers of the bypassed protection zones are displayed (one beep is heard for each zone displayed). Subsequently, BYPASS is displayed.
ONE SHORT BEEP (once every 40 secs) Touchpad only
a. SYSTEM IS IN TEST MODE b. LOW BATTERY AT A TRANSMITTER
a. Opened zone numbers will appear. b. BAT displayed with zone number of transmitter.
TWO SHORT BEEPS Touchpad only
ARM AWAY AWAY is displayed. Red ARMED indicator is lit.
THREE SHORT BEEPS Touchpad only
a. ARM STAY, NIGHT-STAY, OR
a. STAY or INSTANT is displayed. Red ARMED indicator is lit.
b. CHIME displayed; zone number of open protection zone will be displayed if the [,] key is pressed.
b. ZONE OPENED WITH
SYSTEM IN CHIME MODE.
RAPID BEEPING Touchpad only
a. TROUBLE
a. CHECK displayed. Zone number of troubled protection zone is displayed. b. FIRE or ALARM is displayed; zone number of zone in alarm is displayed
b. MEMORY OF ALARM
c. SYSTEM LOW BATTERY d. EXT. SOUNDER WIRING FAIL
c. BAT displayed with no zone ID number.
d. CHECK 70 is displayed.
SLOW BEEPING Touchpad only
a. EXIT DELAY WARNING
a. AWAY is displayed.
b. ENTRY DELAY WARNING
b. Exceeding the entry delay time without disarming causes alarm.
* If a bell is used as external sounder, fire alarm is pulsed ring; burglary/audible emergency is steady ring.

SOUND CAUSE DISPLAY LOUD, INTERRUPTED* Touchpad & Ext.
FIRE ALARM. FIRE is displayed; descriptor of zone in alarm is displayed. If a fire alarm is manually activated, zone number 95 will be displayed.
LOUD, CONTINUOUS* Touchpad & Ext.
BURGLARY/AUDIBLE EMERGENCY ALARM.
ALARM is displayed. If programmed, descriptor of zone in alarm is also displayed
ONE SHORT BEEP (not repeated) Touchpad only
a. SYSTEM DISARM.
a. DISARMED/READY TO ARM is displayed.
b. SYSTEM ARMING ATTEMPT WITH AN OPEN ZONE.
b. Number and descriptor of open protection zone is displayed.
c. BYPASS VERIFY.
c. Numbers and descriptors of the bypassed zones are displayed (One beep is heard for each zone displayed). Subsequently, the following is displayed: DISARMED BYPASS /Ready to Arm.
ONE SHORT BEEP (once every 40 secs) Touchpad only
a. SYSTEM IS IN TEST MODE. b, LOW BATTERY AT A TRANSMITTER.
a. Opened Zone identifications will appear. b. LO BAT displayed with description of transmitter.
TWO SHORT BEEPS Touchpad only
ARM AWAY. ARMED AWAY displayed. Red ARMED indicator lit.
THREE SHORT BEEPS Touchpad only
a. ARM STAY, NIGHT-STAY, OR INSTANT.
a. ARMED STAY or ARMED INSTANT displayed.
Red ARMED indicator lit.
b. CHIME displayed, descriptor of open protection zone will be displayed if the [,] key is pressed.
b. ZONE OPENED WHILE SYSTEM IS DISARMED.
RAPID BEEPING Touchpad only
a. TROUBLE.
a. CHECK displayed. Descriptor of troubled
protection zone is displayed. b. FIRE or ALARM is displayed; descriptor of zone
b. MEMORY OF ALARM.
in alarm is displayed. c. SYSTEM LO BAT displayed.
c. SYSTEM LOW BATTERY. d. EXT. SOUNDER WIRE FAIL.
d. BELL FAILURE is displayed.
SLOW BEEPING Touchpad only
a. EXIT DELAY WARNING (if programmed).
a. ARMED AWAY is displayed along with You May Exit Now.
b. ENTRY DELAY WARNING.
b. DISARM SYSTEM OR ALARM WILL OCCUR is displayed. Exceeding the delay time without disarming causes an alarm.
* If a bell is used as external sounder, fire alarm is pulsed ring; burglary/audible emergency is steady ring.

Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Industry Canada This Class B digital apparatus complies with Canadian ICES-003. Cet Appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC Part 68 This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This equipment is hearing-aid compatible.
Industry Canada NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Ringer Equivalence Number Notice: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.


The following chart identifies the special functions that yourinstaller may have programmed for certain keys.


User Setup The following chart will help keep track of system users. Copies should be distributed to the partition 1 and partition 2 masters for their records.
To program a user attribute: Enter system/partition master code + [8] + user no. + “#” command listed in column heading…
Pager on/off [#] [5] + 0/1 01 installer (all) installer (0) 02 master (all) master (0) 03 part. 1 master (1) (4) (0) 04 (1) (0) (0) 05 (1) (0) (1) 06 (1) (0) (1) 07 (1) (0) (1) 08 (1) (0) (1) 09 (1) (0) (1) 10 (1) (0) (1) 11 (1) (0) (1) 12 (1) (0) (1) 13 (1) (0) (1) 14 (1) (0) (1) 15 (1) (0) (1) 16 (1) (0) (1) 17 (1) (0) (1) 18 (1) (0) (1) 19 (1) (0) (1) 20 (1) (0) (1) 21 (1) (0) (1) 22 (1) (0) (1) 23 (1) (0) (1) 24 (1) (0) (1) 25 (1) (0) (1) 26 (1) (0) (1) 27 (1) (0) (1) 28 (1) (0) (1) 29 (1) (0) (1) 30 (1) (0) (1) 31 (1) (0) (1) 32 (1) (0) (1)
User’s Part(s). (system master only)
Auth. Level [#] [1] + level
No.
Code enter new code
Group [#] [2] + group
Number [#] [4] + zone no.
[#] [3] + part(s) + [#]

(Enter system/partition master code + [8] + user no. + “#” command listed in column heading…)

Pager on/off [#] [5] + 0/1 33 part. 2 master (2) (4) (1) 34 (2) (0) (1) 35 (2) (0) (1) 36 (2) (0) (1) 37 (2) (0) (1) 38 (2) (0) (1) 39 (2) (0) (1) 40 (2) (0) (1) 41 (2) (0) (1) 42 (2) (0) (1) 43 (2) (0) (1) 44 (2) (0) (1) 45 (2) (0) (1) 46 (2) (0) (1) 47 (2) (0) (1) 48 (2) (0) (1) 49 (2) (0) (1)
Authority Levels: 0 = standard user Partitions: 1 = partition 1 and common 1 = arm only 2 = partition 2 and common 2 = guest 3 = common partition only 3 = duress 4 = partition master Paging: 0 = no paging 1 = allow paging

Automatically Reports Upon… Sched. Func. Key open/close alarm/trouble zone list Pager
Pager Phone Number\ Prefix Characters p1 p2 p1 p2 p1 p2 1

Schedules (master code + [#] + [6] [4]) No. Event Device No. Group No. Partition Start Stop Repeat Random (see list below) for “01” events: for “02” events: for “04-06” events: Time/ Time/ (yes/no) (yes/no) enter 01-18 enter 1-8 enter 1, 2, or 3 Day Day

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Events: 00 = clear event 03 = latch key report 06 = auto disarm 01 = device on/off 04 = forced STAY arm 07 = display “reminder” 02 = user access 05 = forced AWAY arm
List of Output Devices Device Description Schedule No. Function Key 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18







/LPLWHG :DUUDQW\
Any part of the system, including the wiring, installed under this Agreement which proves to be defective in material or workmanship within 90 days of the date of completion of installation will be repaired or replaced at ADT's option with a new functionally operative part. Labor and material required to repair or replace such defective components or to make mechanical adjustments to the system will be free of charge for a period of 90 days following the completion of the original installation.
This warranty is extended only to the original consumer purchaser of the system and may be enforced only by such person.
To obtain service under this warranty, call or write our local ADT Service Department at the telephone number or address found in your local yellow pages.
Service pursuant to the warranty will be furnished only during ADT's normal working hours 8:00A.M. to 4:30P.M., Monday through Friday, except holidays. Services rendered outside the normal working hours of ADT are not within the scope of this warranty and any services requested to be performed at such times shall be charged for at ADT's then applicable rates for labor and material.
This warranty does not apply to the conditions listed below, and in the event customer calls ADT for service under the warranty and upon inspection it is found that one of these conditions has led to the inoperability or apparent inoperability of the system, a charge will be made for the service call of the ADT representative, whether or not he actually works on the system. Should it actually be necessary to make repairs to the system due to one of the "conditions Not Covered By Warranty", a charge will be made for such work at ADT's then applicable rates for labor and material.
Conditions Not Covered By Warranty.
A. Damage from accidents, acts of God, alterations, misuse, tampering or abuse.
B. Failure of the customer to properly close or secure a door, window, or other point protected
by a burglar alarm device.
C. Failure of customer to properly follow operating instructions provided by ADT at time of
installation or at a later date.
D. Trouble in leased telephone.
E. Trouble due to interruption of commercial power.
F. Battery replacements.

This warranty is in lieu of all other express warranties. Any implied warranties of merchantability and fitness for a particular purpose are limited in duration to a period of 90 days from the date of completion of installation. The exclusive remedy of the customer hereunder shall be repair or replacement as stated above. Under no circumstances shall ADT be liable to the customer or any other person for incidental or consequential damages of any nature, including without limitation, damages for personal injury or damages to property, and, however occasioned, whether alleged as resulting from breach of warranty by ADT, the negligence of ADT, or otherwise, ADT's liability will in no event exceed the purchase price of the system. Some states may not allow limitations on how long an implied warranty lasts, or the exclusion or limitations of incidental or consequential damages, so the above limitations and exclusions may not apply to you, unless a longer period is required by applicable law. Any action against ADT in connection with a system must be commenced within one year after the cause of action has occurred. No agent, employee or representative of ADT nor any other person is authorized to modify this warranty in any respect. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
ADT agrees to install the equipment in a workmanlike manner in accordance with the following conditions: A. Customer will make premises available without interruption during ADT normal working
hours 8:00A.M. to 4:30P.M., Monday through Friday, except Holidays. B. Customer understands that the installation will necessitate drilling into various parts of the
premises: ADT intends, generally, to conceal wiring in the finished areas of the premises; however, there may be areas which, due to construction, decoration, or furnishing of the premises, ADT determines, in its sole discretion, that it would be impractical to conceal wiring and, in such cases, wiring will be exposed. C. Customer agrees to provide 110 VAC electrical outlets at designated locations for
equipment requiring AC power. D. Customer to provide for lifting and replacing carpeting, if required, for installation of floor
mats or wiring. ALL RIGHTS RESERVED No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form, or by any means – electronic, mechanical, photocopying, recording, or otherwise without the written permission of ADT Security Systems, Inc. The material in this publication is for information purposes and subject to change without notice. ADT Security Systems, Inc. assumes no responsibility for any errors which may appear in this publication.

ADT Security Services, Inc. One Town Center Rd. Boca Raton, FL 33486
Copyright © 2000