COMMERCIAL SINGLE PACKAGE ROOFTOP UNITS GAS HEATING/ELECTRIC COOLING UNITS
Sizes 024-300
579F180-216 581A155,180 580F180,210
SIZES 090-151

Every compact one-piece unit arrives fully assembled, charged, tested, and ready to run. GAS HEAT MODELS — All ignition components are contained in the compact IGC (integrated gas controller) which is easily accessible for servicing. The IGC control board, designed and manufactured exclusively for Bryant rooftop units, provides built-in diagnostic capability. An LED (light-emitting diode) sim- plifies troubleshooting by providing visual fault notification and required system status confirmation. The IGC also contains an exclusive anti-cycle protection for gas heat operation. After 4 continuous cycles on the unit high- temperature limit switch, the gas heat operation is disabled, and an error code is issued. This feature greatly improves reli- ability of the rooftop unit. The IGC also contains burner control logic for accurate and dependable gas ignition. The LED is visible without removing the unit control box access panel. This LED fault-notification system reduces service person troubleshooting time and mini- mizes service costs. The IGC also maximizes heating effi- ciency by controlling evaporator-fan on and off delays. Tubular, dimpled gas heat exchangers optimize heat transfer for improved efficiency. The tubular design permits hot gases to make multiple passes across the path of the supply air. The dimpled design creates a turbulent gas flow to maximize heat- ing efficiency.

The California Air Quality Management Districts NOx require- ment of 40 nanograms/joule or less is met on 036-060 size Low NOx models. The extra thick Alumagard™ heat exchanger coating provides corrosion resistance and ensures long life (optional stainless steel heat exchangers are available). The unsightly appearance of flue stacks is eliminated and the effects of wind on heating operations are diminished by the induced draft combustion system. The inducer fan draws hot combustion gas through the heat exchanger at the optimum rate for the most effective heat transfer. The heat exchanger operates under negative pressure, preventing flue gas leakage into the indoor supply air. During the heating mode, the evaporator-fan relay automati- cally starts the evaporator fan after the heat exchanger warms up to a suitable temperature. The 30-second fan delay prevents cold air from entering the supply duct system when the condi- tioned space is calling for heat to maximize efficiency. The direct-spark ignition system saves operating expense when compared to pilot ignition systems. No crossover tube is required, therefore no sooting or pilot fouling problems can occur. All standard units are designed for natural gas, but an acces- sory propane conversion kit is available. All units have a flame rectification sensor to quickly sense the burner flame and ignite burners almost immediately. Fast shut- down is a certainty since the sensor reacts quickly to any flame outage or system failure. In the event of a shutdown, an error code is issued at the IGC board. Safety is also assured due to the heating safety controls which will shut down the unit if there is a problem. If excessive temper- atures develop, limit switches shut off the gas valve. After 4 continuous short cycles of the high-temperature limit switch, the IGC board locks out the gas heat cycle to prevent any fur- ther short cycles. This safety feature is provided exclusively on Bryant rooftop units. The rollout switch also deenergizes the gas valve in the event of a flame rollout. QUIET, EFFICIENT OPERATION AND DEPENDABLE PER- FORMANCE — Compressors have vibration isolators for quiet operation. Efficient fan and motor design permits operation at low sound levels. Unit sizes 090-300 offer lower utility costs through part-load operation using 2 or 3 stages of cooling. Quiet and efficient operation is provided by belt-driven evapora- tor fans (standard on all units over 5 tons). The belt-driven evaporator-fan is equipped with variable-pitch pulleys which allow adjustment within the rpm ranges of the factory-supplied pulleys. Increased operating efficiency is achieved through computer- designed coils featuring staggered internally enhanced copper tubes. Fins are ripple-edged for strength, lanced, and double waved for higher heat transfer. DURABLE, DEPENDABLE CONSTRUCTION — Designed for durability in any climate, the weather-resistant cabinets are con- structed of galvanized steel and bonderized, and all exterior panels are coated with a prepainted baked enamel finish. The paint finish is non-chalking, and is capable of withstanding ASTM (American Society for Testing and Materials) B117 500-hour Salt Spray Test. All internal cabinet panels are primed, permitting longer life and a more attractive appearance for the entire unit. In addition, all size 024-151 units are designed with a single, continuous top piece to eliminate any possible leaks at seams or gasketing. Totally enclosed condenser-fan motors and permanently lubricated bearings provide additional unit depend- ability.
Page Features/Benefits 1-4 Model Number Nomenclature 5-9 ARI Capacity Ratings 10-19 Options and Accessories 20-23 580F036-151 Physical Data 24-29 Base Unit Dimensions 30-33 Accessory Dimensions 34,35 Selection Procedure 36 Performance Data 37-78 Electrical Data 79-82 Typical Wiring Schematics 83-85 Typical Piping and Wiring 86 581B036-150 Physical Data 88-90 Base Unit Dimensions 91,92 Accessory Dimensions 93,94 Selection Procedure 95 Performance Data 96-136 Electrical Data 137,138 Typical Wiring Schematics 139-141 Typical Piping and Wiring 142 Guide Specifications (036-151 Size Units) 143-147 581C024-060 Physical Data 148,149 Base Unit Dimensions 150 Performance Data 151-166 Typical Wiring Schematics 167-168 Typical Piping and Wiring 169 Guide Specifications (024-160 Size Units) 170-174 579F180-300 Physical Data 175,176 Base Unit Dimensions 177,178 Accessory Dimensions 179-181 Selection Procedure 182 Performance Data 183-196 Electrical Data 197 Typical Wiring Schematics 198-201 Typical Piping and Wiring 202 580F180-300 Physical Data 203,204 Base Unit Dimensions 205-207 Accessory Dimensions 208-211 Selection Procedure 212 Performance Data 213-222 Electrical Data 223 Typical Wiring Schematics 224-226 Typical Piping and Wiring 227 581A155-300 Physical Data 228-231 Base Unit Dimensions 232,233 Accessory Dimensions 234-237 Selection Procedure 238 Performance Data 239-274 Electrical Data 275-277 Typical Wiring Schematics 278,279 Typical Piping and Wiring 280 Guide Specifications (155-300 Size Units) 281-288
Controls 289-292 Application Data 293-296
The efficient in-shot burners and all ignition components are contained in an easily removable, compact assembly.

EASY INSTALLATION AND CONVERSION All Units are Shipped in the Vertical Duct Configuration for fit-up to standard roof curbs. The contractor can order and install the roof curb early in the construction stage, before deci- sions on size requirements are made. All units feature a base rail design with forklift slots and rigging holes for easier maneuvering. Durable packaging protects all units during shipment and storage. The units can be easily converted from a vertical to a horizontal duct configuration by relocating the panels supplied with the unit (size 024-150 only). To Convert 024-151 Units from vertical to horizontal discharge, simply relocate 2 panels. The same basic unit can be used for a variety of applications and can be quickly modified at the job- site. To Convert 155-300 Units from vertical to horizontal discharge, use the optional horizontal supply/return adapter roof curb (581A155,180 and 579F/580F180-300) or accessory conversion kit (581A210-300). Please note that 581A210-300 units are available from the factory configured for horizontal supply/return. Convenient Duct Openings in the unit basepans permit side- by-side or concentric duct connections (see Application data section) without requiring internal unit modification. NOTE: On units using horizontal supply and return, the acces- sory barometric relief or power exhaust MUST be installed on the return ductwork. Thru-The-Bottom Service Connection Capability comes standard with the rooftop unit to allow power and control wiring and gas connections to be routed through the unit’s basepan, thereby minimizing roof penetrations (to prevent water leaks). (Thru-the-bottom gas connection requires thru-the-bottom accessory kit.) Power, gas and control connections are made on the same side of the unit to simplify installation. The Non-Corrosive Sloped Condensate Drain Pan (Size 024-150) permits either an external horizontal side con- densate drain (outside the roof curb) or an internal vertical bottom drain (inside the roof curb). Both options require an external, field-supplied P-trap. Standard 2-in. Throwaway Filters are easily accessed through a removable panel located above the air intake hood. No tools are required to change unit filters. Belt-Driven Evaporator-Fan Motors (optional on 580F units under 6 tons) allow maximum on-site flexibility without changing motors or drives. Low Voltage Wiring Connections are easily made thanks to the large terminal board which is located for quick, convenient access. In addition, color-coded wires permit easy tracing and diagnostics. PROVEN COMPRESSOR RELIABILITY — Design techniques feature computer-programmed balance between compressor, condenser, and evaporator. Bryant-specified hermetic compres- sors are equipped with compressor overcurrent and overtem- perature protection to ensure dependability. All units have Bryant’s exclusive Acutrol™ (024-151) or TXV (thermostatic expansion valve) metering device (155-300) which precisely controls refrigerant flow, preventing slugging and flood-back, while maintaining optimum unit performance. Refrigerant filter driers are standard. INTEGRATED ECONOMIZERS AND OUTDOOR-AIR DAMP- ERS — Available as options or accessories, economizers and manual outdoor-air dampers introduce outdoor air which mixes with the conditioned air, improving indoor-air quality and often reducing energy consumption. During a first stage call for cooling, if the outdoor-air tempera- ture is below the economizer control changeover set point, the

INDOOR-AIR QUALITY (IAQ) BEGINS WITH BRYANT ROOF- TOPS — Sloped condensate pans minimize biological growth in rooftop units in accordance with ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) Standard 62. Two-inch filters with optional dirty filter indicator switch provide for greater particle reduction in the return air. The face-split evaporator coils improve the dehumidification capability of standard units, maximize building humidity control. Optional proportional reacting CO2 sensor is available with the EconoMi$er IV outdoor air damper option/accessory to aid the IAQ benefits. PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM (581C036-060 and 581B036-150 only) — Bryant’s Perfect Humidity adaptive dehumidification system is an all- inclusive factory-installed option that can be ordered with any 581B rooftop unit to meet the demand for providing a flexible and high performing solution to accommodate all of these design related issues. This system expands the envelope of operation of 581B rooftop products to provide unprecedented flexibility to meet year-round comfort conditions. The Perfect Humidity adaptive dehumidification system has the industry’s only dual dehumidification mode setting. The Perfect Humidity system includes two new modes of operation. The 581B and 581C rooftop coupled with the Perfect Humidity system is capa- ble of operating in normal design cooling mode, subcooling mode, and hot gas reheat mode. Normal Design Cooling mode is when the unit will operate under its normal sequence of oper- ation by cycling compressors to maintain comfort conditions. Subcooling mode will operate to satisfy part load type condi- tions when the space requires combined sensible and a higher proportion of latent load control. Hot Gas Reheat mode will
operate when outdoor temperatures diminish and the need for latent capacity is required for sole humidity control. Hot Gas Reheat mode will provide neutral air for maximum dehumidifica- tion operation. EXCLUSIVE HOT GAS REHEAT DEHUMIDIFICATION PACK- AGE (581A181-300) — The hot gas reheat dehumidification package is a result of recent advances by Bryant in controlling comfort levels. This factory-installed option significantly improves the dehumidification capability of the rooftop unit and helps control humidity levels in the building. This option provides increased dehumidification by cooling the hot liquid refrigerant leaving the condenser coil. The hot gas reheat package consists of a subcooling coil located on the leaving-air side of the evaporator coil. The location of this coil in the indoor airstream enhances the latent capacity of the units by as much as 40%. Many buildings suffer from humidity dam- age or poor indoor air quality due to humid conditions. The improved latent capacity provided by the hot gas reheat option reduces the building’s humidity, eliminating potential property damage and making the space more comfortable. The hot gas reheat option is the ideal IAQ option for hot and humid regions. The operation of the hot gas reheat package can be controlled by a field-installed, wall mounted humidistat or Thermidistat™ device. The circuit activates only when needed (using the accessory humidistat) as opposed to some dehumidification systems that operate continuously. The humi- distat can be set for any humidity level between 20% and 80% relative humidity. The Thermidistat device can be set for any humidity level between 50% and 90% relative humidity.

580F036-151 3 to 12 1 / 2 Tons










MODEL NUMBER NOMENCLATURE 580F036-151 (Stainless Steel and Low NOx) 3 to 121/2 Tons





















MODEL NUMBER NOMENCLATURE 581B036-150 (Stainless Steel and Low NOx) — 3 to 121/2 Tons




















MODEL NUMBER NOMENCLATURE 581C024-060 (Stainless Steel and Low NOx) — 2 to 5 Tons










579F – Single-Package Standard-Efficiency Gas/Electric Unit
Fan Drive Option (Standard Motor) B – Standard Low-Medium
Fan Drive Static Capability D – Alternate High Fan
Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60
Factory-Installed Outdoor-Air and Other Upgrade Options C – EconoMi$er IV H – Manual Outdoor-Air Damper
Design Series Code
Nominal Tons 180 – 15 Tons 216 – 18 Tons 240 – 20 Tons 300 – 25 Tons
Gas Heat Input (Btuh) 230 – 230,000 275 – 275,000 300 – 300,000 360 – 360,000
580F – Single Package Medium-Efficiency Gas/Electric Unit
Fan Drive Static Capability D – Alternate High Fan
Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60
Factory-Installed Outdoor-Air and Other Upgrade Options C – EconoMi$er IV H – Manual Outdoor-Air Damper
Design Series Change
Nominal Tons 180 – 15 Tons 210 – 18 Tons 240 – 20 Tons 300 – 25 Tons
Gas Heat Input (Btuh) 275 – 275,000 300 – 300,000 360 – 360,000

581A155, 180, 181 — 13 to 15 Tons
581A – Single Package High Efficiency Gas/Electric Unit
Fan Drive Static Capability D – Alternate High Fan
Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60
Factory-Installed Outdoor-Air and Other Upgrade Options C – EconoMi$er IV H – Manual Outdoor-Air Damper
Design Series Change
Gas Heat Input (Btuh) 230 – 230,000 275 – 275,000 300 – 300,000 360 – 360,000
15 Tons 15 Tons with hot gas reheat*
*See pages 212 and 213 for cooling capacity tables for 581A181 unit. For all other data, contact application engineering. NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. The example model number: 581AEV180230--CB designates a 15 ton 460-3-60 high efficiency gas/electric rooftop unit with 230,000 Btuh natural gas input, EconoMi$er IV and standard, low-medium fan drive static capability.
581A210-300 — 18 to 25 Tons

Drive Static Capability · a48-8194


3. Ratings are based on: Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db air entering outdoor unit. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature. 4. All 580F036, 048, 060, 073, 091, 103, 121, 151 units are in com- pliance with ASHRAE 90.1-1999 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website: http://bcap-energy.org to determine if compliance with this standard pertains to a given geographical area of the United States.
dB — Sound Levels (decibels) db — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values SEER — Seasonal Energy Efficiency Ratio wb — Wet Bulb
*Air Conditioning and Refrigeration Institute. †Applies only to units with capacity of 65,000 Btuh or less. **The IPLV applies only to two-stage cooling units. NOTES:
208/230-1-60 — SINGLE-STAGE GAS HEAT



208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx
LEGEND AFUE — Annual Fuel Utilization Efficiency

EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Value SEER — Seasonal Energy Efficiency Ratio
*Air-Conditioning & Refrigeration Institute. †Applies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units.
NOTES: 1. Rated in accordance with ARI Standard 210/240 (036-120 units) or 360 (150 units) and 270 (036-150 units). 2. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db outdoor entering-air temperature. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.
208/230-1-60 — SINGLE-STAGE GAS HEAT

LEGEND AFUE — Annual Fuel Utilization Efficiency.

LEGEND AFUE — Annual Fuel Utilization Efficiency.

208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx
EFFICIENCY AFUE (%) Steady State (%) 036060N 60,000 50,000 20-50 930 80.2 81.2 036090N 90,000 74,000 30-60 1150 81.0 81.4 048060N 60,000 50,000 20-50 930 80.2 81.2 048090N 90,000 74,000 30-60 1150 81.0 81.4 048120N 120,000 101,000 40-70 1340 80.7 82.4 060060N 60,000 50,000 20-50 930 80.2 81.2 060090N 90,000 74,000 30-60 1150 81.0 81.4 060120N 120,000 101,000 40-70 1340 80.7 82.4
MINIMUM HEATING
RISE (°F)
AIRFLOW (CFM)
208/230/460-3-60 — 2-STAGE GAS HEAT
INPUT CAPACITY OUTPUT CAPACITY TEMPERATUR
MINIMUM HEATING AIRFLOW (CFM)
EFFICIENCY
UNIT 581B
E RISE (°F)
1st Stage 2nd Stage 1st Stage 2nd Stage AFUE (%) Steady State (%)
036072 50,000 72,000 41,000 59,040 25-55 1004 82.8 82.0 036115 82,000 115,000 65,600 93,150 55-85 1002 80.0 80.0 048072 50,000 72,000 41,000 59,040 25-55 1004 82.8 82.0 048115 82,000 115,000 66,420 93,150 35-65 1330 81.0 81.0 048150 120,000 150,000 96,000 120,000 50-80 1390 80.4 80.0 060072 50,000 72,000 41,000 59,040 25-55 1004 82.8 82.0 060115 82,000 115,000 66,420 93,150 35-65 1330 81.0 81.0 060150 120,000 150,000 96,000 120,000 50-80 1370 80.4 80.0 072072 50,000 72,000 41,000 59,040 25-55 1220 82.0 82.0 072115 82,000 115,000 66,420 93,150 35-65 1330 81.0 81.0 072150 120,000 150,000 96,000 120,000 50-80 1390 80.0 80.0 090125 90,000 125,000 73,800 102,500 20-50 1900 82.0 82.0 090180 120,000 180,000 98,400 147,600 35-65 1440 82.0 82.0 090224 180,000 224,000 147,600 183,680 45-75 2230 82.0 82.0 102125 90,000 125,000 73,800 102,500 20-50 1900 82.0 82.0 102180 120,000 180,000 98,400 147,600 35-65 1440 82.0 82.0 102224 180,000 224,000 147,600 183,680 45-75 2230 82.0 82.0 120180 120,000 180,000 98,400 147,600 35-65 1440 82.0 82.0 120224 180,000 224,000 147,600 183,680 35-65 2570 82.0 82.0 120250 200,000 250,000 160,000 200,000 40-70 2650 80.0 80.0 150224 180,000 224,000 147,600 183,680 35-65 2570 82.0 82.0 150250 200,000 250,000 160,000 200,000 40-70 2650 80.0 80.0
LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Capacities for stainless steel heat exchanger units are the same as standard units.

COOLING
TOTAL
kW SEER EER SOUND RATING
(decibels) 024 2 24,000 3.2 14.1 12.0** 76 036 3 36,200 4.1 14.0 11.8** 76 048 4 46,000 5.5 14.0 11.7** 76 060 5 59,000 6.7 14.0 11.9 80
(Btuh)
EER — Energy Efficiency Ratio SEER — Seasonal Energy Efficiency Ratio
*Air-Conditioning & Refrigeration Institute. **ARI does not require EER ratings for unit with capacity below 65,000 Btuh. For these units, the EER rating at ARI standard conditions is provided for informa- tion only.
208/230-1-60 — SINGLE-STAGE GAS HEAT
UNIT INPUT CAPACITY OUTPUT CAPACITY TEMPERATURE MINIMUM HEATING EFFICIENCY
581C 1st Stage 2nd Stage 1st Stage 2nd Stage RISE (°F) AIRFLOW (CFM) AFUE (%) Steady State
(%) 024050 50,000 — 40,500 — 25-65 575 81.00 81
036072 72,000 — 59,040 — 25-55 1004 82.80 82
036115 115,000 — 92,000 — 55-85 1002 80.00 80
048072 72,000 — 58,000 — 25-55 1004 82.80 82
048115 115,000 — 92,000 — 35-65 1320 81.00 81
048150 150,000 — 118,000 — 50-80 1396 80.40 80
060072 72,000 — 58,000 — 25-55 1004 82.80 82
060115 115,000 — 92,000 — 35-65 1327 81.00 81
060150 150,000 — 118,000 — 50-80 1314 80.40 80
UNIT INPUT CAPACITY OUTPUT CAPACITY TEMPERATURE MINIMUM HEATING EFFICIENCY
581C 1st Stage 2nd Stage 1st Stage 2nd Stage RISE (°F) AIRFLOW (CFM) AFUE (%) Steady State (%)
024050N 50,000 — 40,500 — 25-65 575 81.00 81
036060N 60,000 — 50,000 — 20-50 930 80.20 81
036090N 90,000 — 74,000 — 30-60 1150 81.00 81
048060N 60,000 — 50,000 — 20-50 930 80.20 81
048090N 90,000 — 74,000 — 30-60 1150 81.00 81
048120N 120,000 — 101,000 — 40-70 1340 80.70 82
060060N 60,000 — 50,000 — 20-50 930 80.20 81
060090N 90,000 — 74,000 — 30-60 1150 81.00 81
060120N 120,000 — 101,000 — 40-70 1340 80.70 82
AFUE — Annual Fuel Utilization Efficiency NOTE: Capacities for stainless steel heat exchanger units (S/R/T) are the same as standard units (D/E/F).

UNIT INPUT CAPACITY OUTPUT CAPACITY TEMPERATURE MINIMUM HEATING EFFICIENCY
581C 1st Stage 2nd Stage 1st Stage 2nd Stage RISE (°F) AIRFLOW (CFM) AFUE (%) Steady State (%)
036060N 60,000 — 50,000 — 20-50 930 80.20 81
036090N 90,000 — 74,000 — 30-60 1150 81.00 81
048060N 60,000 — 50,000 — 20-50 930 80.20 81
048090N 90,000 — 74,000 — 30-60 1150 81.00 81
048120N 120,000 — 101,000 — 40-70 1340 80.70 82
060060N 60,000 — 50,000 — 20-50 930 80.20 81
060090N 90,000 — 74,000 — 30-60 1150 81.00 81
060120N 120,000 — 101,000 — 40-70 1340 80.70 82
UNIT INPUT CAPACITY OUTPUT CAPACITY TEMPERATURE MINIMUM HEATING EFFICIENCY
581C 1st Stage 2nd Stage 1st Stage 2nd Stage RISE (°F) AIRFLOW (CFM) AFUE (%) Steady State (%)
036072 50,000 72,000 41,000 59,040 25-55 1004 82.80 82
036115 82,000 115,000 65,600 93,150 55-85 1002 80.00 80
048072 50,000 72,000 41,000 59,040 25-55 1094 82.80 82
048115 82,000 115,000 66,420 93,150 35-65 1330 81.00 81
048150 120,000 150,000 96,000 120,000 50-80 1390 80.40 80
060072 50,000 72,000 41,000 59,040 25-55 1004 82.80 82
060115 82,000 115,000 66,420 93,150 35-65 1330 81.00 81
060150 120,000 150,000 96,000 120,000 50-80 1370 80.40 80
AFUE — Annual Fuel Utilization Efficiency NOTE: Capacities for stainless steel heat exchanger units (S/R/T) are the same as standard units (D/E/F).


180 15 174,000 20,128 8.6 88 9.3 216 18 188,000 21,619 8.7 88 9.5 240 20 220,000 25,513 8.6 94 8.7 300 25 268,000 31,068 8.6 94 9.2

180 15 174,000 20,154 8.6 88 9.3 216 18 186,000 21,798 8.5 88 9.3 240 20 218,000 25,719 8.5 94 8.5 300 25 268,000 31,600 8.5 94 8.9
dB — Sound Levels (decibels) db — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values wb — Wet Bulb

180230 230,000/172,000 186,000 15-45 81.0 3830 180300 300,000/225,000 243,000 30-60 81.0 3750 216275 275,000/206,000 223,000 15-45 81.0 4580 216360 360,000/270,000 292,000 20-50 81.0 5400 240275 275,000/206,000 223,000 15-45 81.0 4580 240360 360,000/270,000 292,000 20-50 81.0 5400 300275 275,000/206,000 223,000 15-45 81.0 4580 300360 360,000/270,000 292,000 20-50 81.0 5400
*All units are 2-stage heat. NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating. For entering-air temperatures below 45 F both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation. Mixed air below 35 F optional stainless steel heat exchangers are recommended.
OPERATING LIMITS (F)
UNIT 579F MINIMUM CFM MAXIMUM CFM 180 4500 7,500 216 5400 9,000 240 6000 10,000 300 7000 11,250
UNITS TEMPERATURE All 40 180 and 216 with Low Ambient Kit 10 240 and 300 with Low Ambient Kit 25 All with Motormaster® Head Pressure Control –20


180 15 176,000 17,064 9.5 88 9.5 210 18 202,000 21,166 9.7 88 10.2 240 20 236,000 24,832 9.5 94 10.1 300 25 278,000 28,535 9.7 94 10.4
180 15 176,000 17,179 9.5 88 9.5 210 18 202,000 21,301 9.7 88 10.1 240 20 236,000 24,832 9.5 94 10.0 300 25 277,000 29,067 9.5 94 10.0
Bels — Sound Levels (1 bel = 10 decibels) db — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values wb — Wet Bulb
*Air Conditioning and Refrigeration Institute. NOTES:

180275 275,000/206,000 223,000 15-45 81.0 3750 180360 360,000/270,000 292,000 20-50 81.0 3830 210275 275,000/206,000 223,000 15-45 81.0 4580 210360 360,000/270,000 292,000 20-50 81.0 5400 240275 275,000/206,000 223,000 15-45 81.0 4580 240360 360,000/270,000 292,000 20-50 81.0 5400 300275 275,000/206,000 223,000 15-45 81.0 4580 300360 360,000/270,000 292,000 20-50 81.0 5400
*All units are 2-stage heat. NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating. For entering-air temperatures below 45 F both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation. Mixed air below 35 F optional stainless steel heat exchangers are recommended.
UNIT 580F MINIMUM CFM MAXIMUM CFM 180 4500 7,500 210 5400 9,000 240 6000 10,000 300 7000 11,250
UNITS TEMPERATURE All — Standard Unit 40 180 and 210 with Low Ambient Kit 10 240 and 300 with Low Ambient Kit 25 All with Motormaster® Head Pressure Control –20

UNIT 581A NOMINAL
NET COOLING
TOTAL WATTS EER
SOUND RATING
CAPACITY
IPLV
TONS
(Btuh)
(dB)
155230 13 134,000 12,209 10.60 88 11.4 180275 15 180,000 17,064 10.50 88 11.4
NET COOLING
SOUND RATING
UNIT 581A NOMINAL
CAPACITY
TOTAL WATTS EER
IPLV
TONS
(Btuh)
(dB)
155300 13 134,000 12,218 10.60 88 11.4 180360 15 180,000 17,179 10.50 88 11.1
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.
dB — Sound Levels (decibels) db — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values wb — Wet Bulb
*Air Conditioning and Refrigeration Institute. NOTES:
HEATING INPUT (Btuh) Stage 2/Stage 1*
OUTPUT CAPACITY
AGA STEADY
TEMPERATURE
MINIMUM HEATING
UNIT 581A
RISE (F)
STATE EFFICIENCY (%)
(Btuh)
155230 230,000/172,000 186,000 15-45 81.0 3750 155300 300,000/225,000 243,000 30-60 81.0 3830 180275 275,000/206,000 223,000 15-45 81.0 4580 180360 360,000/270,000 292,000 20-50 81.0 5400
*All units are 2-stage heat. †Minimum heating cfm must be maintained to ensure proper heating operation. NOTE: Minimum allowable temperature of mixed air entering the heat exchanger during first stage heating is 45 F. There is no minimum mixed-air limitation during second-stage heating. For entering air temperatures below 45 F, both stages of heat must be energized together to minimize conden- sation issues and ensure proper unit operation. Mixed air below 35 F optional stainless steel heat exchangers are recommended.
AIR QUANTITY LIMITS (Cooling)
COOLING OPERATION LIMITS
UNIT 581A MINIMUM CFM MAXIMUM CFM 155 3900 6500 180 4500 7500
UNIT SIZE
Standard
Unit With Low Ambient Kit
Unit With Motormaster®
581A
Control 155, 180 40 20 –20

TONS CFM NET COOLING CAPACITY (Btuh)
kW EER SOUND RATING
210 18 5,500 200,000 18.5 10.8 81.7 12.0 240 20 6,000 234,000 21.7 10.8 81.7 11.9 300** 25 7,500 278,000 27.8 10.0 84.6 10.9
3. Ratings are based on: Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature. 4. All 581A210-300 units are in compliance with ASHRAE 90.1 2001 Energy Standard for minimum EER requirements. Refer to state and local codes or visit the following website: http://bcap-energy.org to determine if compliance with this standard pertains to a given geographical area of the United States.
db — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values wb — Wet Bulb
*Air Conditioning and Refrigeration Institute. †IPLV values are calculated based on control configuration T.CTL = 2
(2 Stage Y1). **Size 300 unit is not listed with ARI, but is tested to ARI standards. NOTES:


MINIMUM HEATING CFM 210250 250,000/199,000 205,000 15-45 82% 4218 210365 365,000/281,000 296,000 25-55 81% 4977 210400 400,000/317,000 328,000 25-55 82% 5522 240250 250,000/199,000 205,000 15-45 82% 4218 240365 365,000/281,000 296,000 25-55 81% 4977 240400 400,000/317,000 328,000 25-55 82% 5522 300250 250,000/199,000 205,000 15-45 82% 4218 300365 365,000/281,000 296,000 25-55 81% 4977 300400 400,000/317,000 328,000 25-55 82% 5522

MINIMUM HEATING CFM 210250 250,000/199,000 205,000 15-45 82% 4218 210365 365,000/281,000 296,000 25-55 81% 4977 210400 400,000/317,000 328,000 25-55 82% 5522 240250 250,000/199,000 205,000 15-45 82% 4218 240365 365,000/281,000 296,000 25-55 81% 4977 240400 400,000/317,000 328,000 25-55 82% 5522 300250 250,000/199,000 205,000 15-45 82% 4218 300365 365,000/281,000 296,000 25-55 81% 4977* 300400 400,000/317,000 325,000 25-55 82% 5522*
*7000 cfm minimum recommended above 1.0 in. wg external static pressure.

MINIMUM HEATING CFM 210250 250,000/207,000 205,000 15-45 82% 4218 210365 365,000/291,000 296,000 25-55 81% 4480 210400 400,000/331,000 328,000 25-55 82% 5522 240250 250,000/207,000 205,000 15-45 82% 4218 240365 365,000/291,000 296,000 25-55 81% 4480 240400 400,000/331,000 328,000 25-55 82% 5522 300250 250,000/207,000 205,000 15-45 82% 4218 300365 365,000/291,000 296,000 25-55 81% 4480 300400 400,000/331,000 328,000 25-55 82% 5522

MINIMUM HEATING CFM 210250 225,000/207,000 185,000 15-45 82% 3807 210365 329,000/291,000 266,000 25-55 81% 4480 210400 356,000/331,000 292,000 25-55 82% 4916 240250 225,000/207,000 184,500 15-45 82% 3796 240365 329,000/291,000 266,000 25-55 81% 4480 240400 356,000/331,000 292,000 25-55 82% 4916 300250 225,000/207,000 185,000 15-45 82% 3807 300365 329,000/291,000 266,000 25-55 81% 4480* 300400 356,000/331,000 292,000 25-55 82% 4920*
*7000 cfm minimum recommended above 1.0 in. wg external static pressure. NOTE: All units are 2-stage gas heat.
(dB) IPLV†

ITEM OPTION* ACCESSORY† 100% OA Open Two-Position Damper X 25% OA Open Two-Position Damper X Condenser Coil Grille X Condenser Coil Hail Guard Assembly X Convenience Outlet (Load Side) X Copper Fins Indoor and Outdoor Coil X Copper Fins Outdoor Coil X E-Coat Outdoor Coil (Aluminum) X E-Coat Outdoor Coil (Copper) X EconoMi$er IV with Controller X X EconoMi$er2 (without controller) X X Electronic Programmable Thermostat X Enthalpy or Differential Enthalpy Sensor X Fan/Filter Status X Flue Discharge Deflector X Flue Shield X High-Static Motor and Drive X Hinged Access Panels (581C and 581B only) X Hinged Panel Kit for Economizer X Perfect Humidity™ Dehumidification Package (581C and 581B only) X Humidistat X Indoor Air Quality (CO2) Sensor X Light Commercial Thermidistat™ Device X Low NOX (036-060) X Louvered Hail Guard X X LP (Liquid Propane) Conversion Kit X Manual Outdoor-Air Damper X Motormaster® I, II, Head Pressure Control Low Ambient Kit) X Outdoor Air Enthalpy Sensor X Power Exhaust Transformer for 575 v X Power Exhaust with Barometric Relief X Pre-Coat Aluminum Fins on Outdoor Coil X Return Air CO2 Sensor (EconoMi$er IV) X Return Air Enthalpy Sensor X Return Air Temperature Sensor X Roof Curbs (Vertical and Horizontal Discharge) X Smoke Detectors, Supply/Return X Stainless Steel Heat Exchanger X Thermostats and Subbases X Thru-the-Bottom Utility Connections X Time Guard II (Compressor Cycle Delay) Control Circuit X Unit-Mounted Non-Fused Disconnect X UVC Lights X X
*Factory-installed. †Field-installed. NOTES: 1. Refer to unit price pages or contact your local representative for accessory and option package information. 2. Some options may increase product lead times.

ITEM OPTION* ACCESSORY† 25% Open Two-Position Damper X Barometric Relief Damper (not for use with Horizontal Adapter Curb) X Condenser Coil Hail Guard Assembly (180-240) X Convenience Outlet (Load Side) X Copper Fins Indoor and Outdoor Coil X Copper Fins Outdoor Coil X E-Coat Outdoor Coil (Aluminum) X E-Coat Outdoor Coil (Copper) X EconoMi$er IV with Controller X X EconoMi$er2 (without Controller) X Electronic Programmable Thermostat X Enthalpy or Differential Enthalpy Sensor X Fan/Filter Status X High-Static Motor and Drive X Hinged Access Panels X Horizontal Adapter Curb (180-240) X Humidistat X Indoor Air Quality (CO2) Sensor X Light Commercial Thermidistat™ Device X LP (Liquid Propane) Conversion Kit X Manual Outdoor-Air Damper X Motormaster® I, V Head Pressure Control (Low Ambient Kit) X Outdoor Air Enthalpy Sensor X Power Exhaust without Barometric Relief X Pre-coat Aluminum Fins on Outdoor Coil X Return Air CO2 Sensor X Return Air Enthalpy Sensor X Return Air Temperature Sensor X Roof Curbs (Vertical and Horizontal Discharge) X Thermostats and Subbases X Time Guard II (Compressor Cycle Delay) Control Circuit X Ultraviolet Germicidal Lamps X Unit-Mounted Non-Fused Disconnect X Winter Start Time Delay X
*Factory-installed. †Field-installed. NOTES: 1. Refer to unit price pages or contact your local representative for accessory and option package information. 2. Some options may increase product lead times. 3. No other options are available with hot gas reheat units.

ITEM OPTION* ACCESSORY† EconoMi$er IV X X Power Exhaust X X Barometric Relief X X Hail Guard X X Horizontal Kit X X Return Smoke Detector X X Supply Smoke Detector X Return and Supply Smoke Detector X Non-Fused Disconnect X Non-Powered Convenience Outlet X Outdoor Air Enthalpy Sensor X Return Air Enthalpy Sensor X Return Air Temperature Sensor X Return Air CO2 Sensor X Indoor Air Quality (CO2) Room Sensor X Hot Gas Reheat (181 (15t) model available only with HGRH) X Non-Powered Convenience Outlet X Pre-Coat Condenser X E-Coat Condenser Coil X Copper Condenser Coil X Copper Evaporator Coil X E-Coat Copper Evaporator Coil X Low Range Drive X Mid-Low Range Drive X Mid-High Range Drive X High Range Drive X Roof Curb (14 in.) X Roof Curb (24 in.) X Low Heat Gas X High Heat Gas X Medium Heat Gas X Stainless Steel Heat Exchangers X Propane Kit X Drip Edge X Two-Position Damper X X Phase Loss Detection X Manual Damper X X Thermostat and Subbase X Hinged Access Panels X
*Factory-installed. †Field-installed. NOTES: 1. Refer to unit price pages or contact your local representative for accessory and option package information. 2. Some options may increase product lead times.

Roof Curbs (Horizontal and Vertical) permit installation and securing of ductwork to curb prior to mounting unit on the curb. Both 14-in. and 24-in. roof curbs are available as field-installed accessories. EconoMi$er IV is available as a factory-installed option in vertical supply/return configuration only for unit sizes 036-151. Vertical or horizontal configuration is available for unit sizes 155-300. (The EconoMi$er IV is available as a field-installed accessory for horizontal and/or vertical supply return configura- tions.) The EconoMi$er IV is provided with an industry stan- dard, stand-alone, solid-state controller that is easy to configure and troubleshoot. The EconoMi$er IV is compatible with non- DDC applications. The EconoMi$er IV is equipped with a barometric relief damper capable of relieving up to 100% return air (for unit sizes 036-151 only). Dry bulb outdoor-air tempera- ture sensor is provided as standard. The return air sensor, indoor enthalpy sensor, and outdoor enthalpy sensor are pro- vided as field-installed accessories to provide enthalpy control, differential enthalpy control, and differential dry bulb tempera- ture control. EconoMi$er IV on 579F and 581A units is used for both vertical and horizontal return air configurations. EconoMi$er2 is available as a blanket quote control or as a field-installed accessory for horizontal and/or vertical supply return configurations. The EconoMi$er2 is provided without a controller for use with field-installed third-party controls. The EconoMi$er2 is equipped with a barometric relief damper capa- ble of relieving up to 100% return air. Dry bulb outdoor-air tem- perature sensor is provided as standard. The enthalpy, differential temperature (adjustable), and differential enthalpy control are provided as field-installed accessories. The EconoMi$er2 is capable of control from a 4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control (required for third party control interface). Manual Outdoor-Air Damper can be preset to admit up to 50% outdoor air for year round ventilation and is available as a field- installed accessory.
Two-Position Damper package is available as an accessory. Both 25% or 100% outdoor air dampers are available. Head Pressure Control (Motormaster) accessory package maintains condensing temperature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. Unit-Mounted, Non-Fused Disconnect Switch provides unit power shutoff. The switch is accessible from outside the unit, provides power off lockout capability and is available as a factory-installed option. Convenience Outlet is factory-installed and internally mounted with easily accessible 115-v female receptacle. Compressor Cycle Delay (Time Guard II) accessory prevents unit from restarting for minimum of 5 minutes after shutdown. Thru-The-Bottom Utility Connectors permit electrical connec- tions to be brought to the unit through the basepan. Con- nectors are available as field-installed accessories. Fan/Filter Status Switch accessory provides status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Power Exhaust accessory will provide system exhaust of up to 100% of return air (vertical only). The power exhaust is a field- installed accessory (separate vertical and horizontal design). Ultraviolet Germicidal Lamps eliminate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germicidal lamps are field installed in the evaporator section of the unit, aimed at the evaporator coil and condensate pan. Hinged Panel Option provides hinged access panels for the fil- ter, compressor, evaporator fan, and control box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is permanently attached to the rooftop unit. Hinged panels are a factory-installed option.

UNIT SIZE 580F 036 048 060 072 073 NOMINAL CAPACITY (tons) 3 4 5 6 6 OPERATING WEIGHT (lb)
Al/Cu* 465 476 497 576 626 COMPRESSOR
Type Reciprocating Scroll Quantity 1 No. Cylinders (per Circuit) 2 2 2 NA 2 Oil (oz) 50 50 50 54 60 REFRIGERANT TYPE R-22 Expansion Device Acutrol™ Metering Device Operating Charge (lb-oz)
Circuit 1 (first stage) 4-5 6-6 7-14 9-0 11-0 Circuit 2 (second stage) — CONDENSER FAN Propeller Type Nominal Cfm 3500 4000 4000 4000 4100 Quantity...Diameter (in.) 1...22.0 Motor Hp...Rpm 1/4...1100 Watts Input (Total) 325 320 CONDENSER COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins Rows...Fins/in. 1...17 2...17 Total Face Area (sq ft) 8.36 8.36 10.42 10.42 16.5 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10 Alt 1...10 x 10 1...10 x 10 1...10 x 10 — — High-Static 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 Type Drive Std Direct Direct Direct Belt Belt Alt Belt Belt Belt — — High-Static Belt Nominal Cfm 1200 1600 2000 2400 2100 Maximum Continuous Bhp Std.34 .75 1.20 2.40 2.40 Alt 1.20 1.20 1.30/2.40** — — High-Static 2.40 2.40 2.90 2.90 2.90 Motor Frame Size Std 48 48 48 56 56 Alt 48 48 56 — — High-Static 56 Nominal Rpm High/Low Std 860/800 1075/970 1075/1040 — — Alt 1620 1620 1725 — — High-Static 1725 Fan Rpm Range Std — — — 1070-1460 1070-1460 Alt 685-1045 770-1175 900-1300 — — High-Static 1075-1455 1075-1455 1300-1685 1300-1685 1300-1685 Motor Bearing Type Ball Maximum Allowable Rpm 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std — — — 2.8/3.8 2.8/3.8 Alt 1.9/2.9 1.9/2.9 2.8/3.8 — — High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4 3.4/4.4 Nominal Motor Shaft Diameter (in.) Std 1/2 1/2 1/2 5/8 5/8 Alt 1/2 1/2 5/8 — — High-Static 5/8 5/8 7/8 7/8 7/8 Fan Pulley Pitch Diameter (in.) Std — — — 4.5 4.5 Alt 4.5 4.0 5.5 — — High-Static 4.5 Belt, Quantity...Type...Length (in.) Std — — — 1...A...39 1...A...39 Alt 1...A...36 1...A...36 1...A...40 — — High-Static 1...A...39 1...A...39 1...A...40 1...A...40 1...A...40 Pulley Center Line Distance (in.) Std — — — 14.7-15.5 14.7-15.5 Alt 10.0-12.4 10.0-12.4 14.7-15.5 — — High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 14.7-15.5 Speed Change per Full Turn of Std — — — 80 80 Movable Pulley Flange (rpm) Alt 48 70 80 — — High-Static 65 65 60 60 60 Movable Pulley Maximum Full Turns Std — — — 5 5 From Closed Position Alt 5 5 5 — — High-Static 6 6 5 5 5 Factory Setting Std — — — 3 3 Alt 3 3 3 — — High-Static 31/2 Factory Speed Setting (rpm) Std — — — 1225 1226 Alt 829 932 1100 — — High-Static 1233 1233 1416 1396 1416 Fan Shaft Diameter at Pulley (in.) 5/8 EVAPORATOR COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins Rows...Fins/in. 2...15 2...15 3...15 4...15 4...15 Total Face Area (sq ft) 4.17 5.5
***Three-phase standard high heat models have heating input values as shown. Single-phase standard high heat models have one-stage heating with heating input values as follows:
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
580F036 — 115,000 Btuh 580F048,060 — 150,000 Btuh †††California SCAQMD compliant Low NOx models have combustion products
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins. †Weight of 14-in. roof curb. **Single phase/three-phase. ††Rollout switch lockout is manually reset by interrupting power to unit or reset-
that are controlled to 40 nanograms per joule or less. NOTES:
ting thermostat.
Unit

UNIT SIZE 580F 036 048 060 072 073 FURNACE SECTION
Rollout Switch Cutout Temp (F)†† 195 Burner Orifice Diameter (in drill size)
Natural Gas Std 074 — .113...33 115.113...33 150.113...33 .129...30 060N — .102...38 .102...38 — — 090N.102...38 .102...38 .102...38 — — 120N.102...38 .116...32 .116...32 — — Liquid Propane Alt 074 — .089...43 115.089...43 150.089...43 .104...37 .104...37 .102...38 .104...37 Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1.14 Stage 2.14 460 v Stage 1.14 Stage 2.14 Gas Input (Btuh) Standard Units 074 — —/74,000 (Stage 1/Stage 2) 115 —/74,000 —/115,000 150*** 82,000/115,000 120,000/150,000 Low NOx Units 060N††† — 60,000 60,000 — — 090N††† 60,000 90,000 90,000 — — 120N††† 90,000 120,000 120,000 — — Efficiency (Steady
State) (%) 80 Temperature Rise Range 074 — 15-45 115 15-45 35-65 150 55-85 50-80 060N — 20-50 20-50 — — 090N 20-50 30-60 30-60 — — 120N 30-60 40-70 40-70 — — Manifold Pressure (in. wg)
Natural Gas Std 3.5 Liquid Propane Alt 3.5 Gas Valve Quantity 1 Gas Valve Pressure Range (Min-Max Allowable)
Psig 0.180-0.470 in. wg 5.0-13.0 Field Gas Connection Size (in. FPT) 1/2 HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 500 ± 50 Internal Relief (Differential)
Cutout 428 428 428 Reset (Auto.) 320 320 320 LOW-PRESSURE SWITCH (psig)
Cutout 7 ± 3 Reset (Auto.) 22 ± 7 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) Varies by Option Selected RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 2...16 x 25 x 2
***Three-phase standard high heat models have heating input values as shown. Single-phase standard high heat models have one-stage heating with heating input values as follows:
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
580F036 — 115,000 Btuh 580F048,060 — 150,000 Btuh †††California SCAQMD compliant Low NOx models have combustion products
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins. †Weight of 14-in. roof curb. **Single phase/three-phase. ††Rollout switch lockout is manually reset by interrupting power to unit or reset-
that are controlled to 40 nanograms per joule or less. NOTES:
ting thermostat.

UNIT SIZE 580F 090 120 150 NOMINAL CAPACITY (tons) 71/2 10 121/2 OPERATING WEIGHT (lb)
Al/Cu* 881 1057 1077 COMPRESSOR
Type Reciprocating Reciprocating Scroll Quantity 2 2 2 No. Cylinders (per Circuit) 2 2 — Oil (oz) 42 ea 54 ea 54 ea REFRIGERANT TYPE R-22 Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 (first stage) 4-13 7- 3 8-10 Circuit 2 (second stage) 4-14 7-13 8- 6 CONDENSER COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins Rows...Fins/in. 1...17 2...17 2...17 Total Face Area (sq ft) 20.50 20.47 25.00 CONDENSER FAN Propeller Type Nominal Cfm 6400 7000 7000 Quantity...Diameter (in.) 2...22 2...22 2...22 Motor Hp...Rpm 1/4...1100 1/4...1100 1/4...1100 Watts Input (Total) 600 600 600 EVAPORATOR COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split Rows...Fins/in. 3...15 3...15 4...15 Total Face Area (sq ft) 8.0 10.0 11.1 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15 Alt 1...15 x 15 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 — Type Drive Std Belt Belt Belt Alt Belt Belt Belt High-Static Belt Belt — Nominal Cfm 3000 4000 5000 Maximum Continuous Bhp Std 2.40 2.40 3.70 Alt 2.40 2.90 5.25 High-Static 3.70 5.25 — Motor Frame Size Std 56 56 56 Alt 56 56 56 High-Static 56 56 — Fan Rpm Range Std 590-840 685-935 860-1080 Alt 685-935 835-1085 830-1130 High-Static 860-1080 830-1130 — Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 4.0/5.0 Alt 2.8/3.8 3.4/4.4 3.1/4.1 High-Static 4.0/5.0 2.8/3.8 — Nominal Motor Shaft Diameter (in.) Std 5/8 5/8 7/8 Alt 1/2 7/8 7/8 High-Static 7/8 7/8 — Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 8.0 Alt 7.0 7.0 5.9 High-Static 8.0 5.8 — Belt, Quantity...Type...Length (in.) Std 1...A...48 1...A...49 1...A...53 Alt 1...A...48 1...A...51 1...BX...48 High-Static 1...A...53 1...BX...48 — Pulley Center Line Distance (in.) Std 16.75-19.25 15.85-17.50 15.85-17.50 Alt 16.75-19.25 15.85-17.50 15.85-17.50 High-Static 16.75-19.25 15.85-17.50 — Speed Change per Full Turn of Std 50 50 44 Movable Pulley Flange (rpm) Alt 50 50 50 High-Static 60 60 — Movable Pulley Maximum Full Turns Std 5 5 5 From Closed Position Alt 5 5 6 High-Static 5 6 — Factory Setting Std 5 5 5 Alt 5 5 5 High-Static 5 5 — Factory Speed Setting (rpm) Std 590 685 860 Alt 685 835 960 High-Static 860 887 — Fan Shaft Diameter at Pulley (in.) 1 1 1
†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.
Unit

Rollout Switch Cutout Temp (F)** 195 195 195 Burner Orifice Diameter (in drill size)
Natural Gas Std 125.120...31 180.120...31 224.120...31 180.120...31 224.120...31 250.129...30 224.120...31 250.129...30 — — Liquid Propane Alt 125.096...41 180.096...41 224.096...41 180.096...41 224.096...41 200.102...38 224.096...41 250.102...38 — — Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1.14 .14 .14 Stage 2.20 .20 .20 460 v Stage 1.14 .14 .14 Stage 2.20 .20 .20 Gas Input (Btuh) Stage 1 125 125,000 180 120,000 224 180,000 180 120,000 224 180,000 250 200,000 224 180,000 250 200,000 — — Stage 2 125 — 180 180,000 224 224,000 180 180,000 224 224,000 200 250,000 224 224,000 250 250,000 — — Efficiency (Steady
State) (%) 80 80 80 Temperature Rise Range 125 20-50 180 35-65 224 35-65 180 35-65 224 35-65 250 40-70 224 45-75 250 40-70 — — Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5 Gas Valve Quantity 1 1 1 Gas Valve Pressure Range (Min-Max Allowable)
Psig 0.180-0.470 0.180-0.470 0.180-0.470 in. wg 5.0-13.0 5.0-13.0 5.0-13.0 Field Gas Connection Size (in. FPT) 1/2/3/4/3/4 3/4/3/4/3/4 3/4/3/4 HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320 LOSS-OF-CHARGE (LOW-PRESSURE)
SWITCH (psig) Cutout 7 ± 3 Reset (Auto.) 22 ± 7 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) Varies by Option Selected RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2
†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.

UNIT SIZE 580F 091 103 121 151 NOMINAL CAPACITY (tons) 71/2 81/2 10 121/2 OPERATING WEIGHT (lb)
Al/Cu* 881 896 1057 1077 COMPRESSOR
Type Reciprocating Scroll Scroll Scroll Quantity 2 No. Cylinders (per Circuit) 2 Oil (oz) (each compressor) 42 53 50 60 REFRIGERANT TYPE R-22 Expansion Device Acutrol™ Metering Device Operating Charge (lb-oz)
Circuit 1 (first stage) 7-10 7-14 8-10 9-8 Circuit 2 (second stage) 8-2 8-5 8-8 9-5 CONDENSER FAN Propeller Type Nominal Cfm 6500 6500 7000 7000 Quantity...Diameter (in.) 2...22 Motor Hp...Rpm 1/4...1100 Watts Input (Total) 650 CONDENSER COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins Rows...Fins/in. 2...17 Total Face Area (sq ft) 20.50 20.50 25.00 25.00 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15 1...15 x 15 Alt 1...15 x 15 — 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15 — Type Drive Std Belt Alt Belt — Belt Belt High-Static Belt Belt Belt — Nominal Cfm 2900 3000 3200 5000 Maximum Continuous Bhp Std 2.40 2.40 2.40 3.70 Alt 2.40 — 2.90 5.25 High-Static 3.70 3.70 5.25 — Motor Frame Size Std 56 Alt 56 — 56 56 High-Static 56 56 56 — Fan Rpm Range Std 590-840 685-935 685-935 860-1080 Alt 685-935 — 835-1085 830-1130 High-Static 860-1080 860-1080 830-1130 — Motor Bearing Type Ball Maximum Allowable Rpm 1500 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8 4.0/5.0 Alt 2.8/3.8 — 3.4/4.4 3.1/4.1 High-Static 4.0/5.0 4.0/5.0 2.8/3.8 — Nominal Motor Shaft Diameter (in.) Std 5/8 5/8 5/8 7/8 Alt 5/8 — 7/8 7/8 High-Static 7/8 7/8 7/8 — Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0 8.0 Alt 7.0 — 7.0 5.9 High-Static 8.0 8.0 5.8 — Belt, Quantity...Type...Length (in.) Std 1...A...48 1...A...48 1...A...49 1...A...53 Alt 1...A...48 — 1...A...51 1...BX...48 High-Static 1...A...53 1...A...53 1...BX...48 — Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50 15.85-17.50 Alt 16.75-19.25 — 15.85-17.50 15.85-17.50 High-Static 16.75-19.25 16.75-19.25 15.85-17.50 — Speed Change per Full Turn of Std 50 50 50 44 Movable Pulley Flange (rpm) Alt 50 — 50 50 High-Static 60 60 60 — Movable Pulley Maximum Full Turns Std 5 From Closed Position Alt 5 — 5 6 High-Static 5 5 6 — Factory Setting Std 5 Alt 5 — 5 5 High-Static 5 5 5 — Factory Speed Setting (rpm) Std 590 685 685 860 Alt 685 — 835 887 High-Static 860 860 887 — Fan Shaft Diameter at Pulley (in.) 1
EVAPORATOR COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split Rows...Fins/in. 3...15 3...15 3...15 4...15 Total Face Area (sq ft) 8.9 8.9 10.0 11.1
LEGEND *Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins. †Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or reset- ting thermostat.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
Unit

UNIT SIZE 580F 091 103 121 151 FURNACE SECTION
Rollout Switch Cutout Temp (F)** 195 Burner Orifice Diameter (in drill size)
Natural Gas Std 125.120...31 125.120...31 180.120...31 224.120...31 180.120...31 180.120...31 224.120...31 250.129...30 224.120...31 224.120...31 250.129...30 — — Liquid Propane Alt 125.096...41 125.096...41 180.096...41 224.096...41 180.096...41 180.096...41 224.096...41 250.102...38 224.096...41 224.096...41 250.102...38 — — Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1.14 Stage 2.20 460 v Stage 1.14 Stage 2.20 Gas Input (Btuh) Stage 1 125 125,000 125 125,000 180 120,000 224 180,000 180 120,000 180 120,000 224 180,000 250 200,000 224 180,000 224 180,000 250 200,000 — — Stage 2 125 — 125 — 180 180,000 224 224,000 180 180,000 180 180,000 224 224,000 250 250,000 224 224,000 224 224,000 250 250,000 — — Efficiency (Steady
State) (%) 80 Temperature Rise Range 125 20-50 125 20-50 180 35-65 224 35-65 180 35-65 180 35-65 224 35-65 250 40-70 224 45-75 224 45-75 250 40-70 — — Manifold Pressure (in. wg)
Natural Gas Std 3.5 Liquid Propane Alt 3.5 Gas Valve Quantity 1 Gas Valve Pressure Range (Min-Max Allowable)
Psig 0.180-0.470 in. wg 5.0-13.0 Field Gas Connection Size (in. FPT) 125 1/2 125 1/2 180 3/4 224 3/4 180 3/4 180 3/4 224 3/4 250 3/4 224 3/4 224 3/4 250 3/4 — — HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320 LOW-PRESSURE SWITCH (psig)
Cutout 7 ± 3 Reset (Auto.) 22 ± 7 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) Varies by Option Selected RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2
LEGEND *Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins. †Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or reset- ting thermostat.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
Option / Accessory 036 048 060 072, 073 090, 091 102, 103 120, 121 150, 151 lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg Power Exhaust -
vertical 50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34
horizontal 30 14 30 14 30 14 30 14 30 14 30 14 30 14 30 14
EconoMi$er ( IV or 2) 50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34 Two Position damper
(25%) 22 10 22 10 22 10 22 10 32 15 32 15 32 15 32 15
(100%) 39 18 39 18 39 18 39 18 58 26 58 26 58 26 58 26
Manual Dampers 12 5 12 5 12 5 18 8 18 8 18 8 18 8 18 8 Hail Guard (standard
hood assembly) 25 11 25 11 25 11 25 11 38 17 50 23 50 23 50 23
Cu/Cu Condenser Coil 6 3 13 6 13 6 15 7 12 5 23 10 23 10 23 10 Cu/Cu Condenser and
Evaporator Coils 12 5 19 9 21 10 26 12 25 11 49 22 49 22 49 22
Roof Curb (14-in. curb) 115 52 115 52 115 52 115 52 143 65 143 65 143 65 143 65 Roof Curb (24-in. curb) 197 89 197 89 197 89 197 89 245 111 245 111 245 111 245 111
Power Exhaust - · Two Position damper









D ALT DRAIN
ACCESSOR
CONNECTOR
Y POWER CRBTMPWR001A01
PKG. ACCY. B C
GAS POWER CONTROL
CRRFCURB001A01 1′-2″ [356] 580F 036-073 CRRFCURB002A01 2′-0″ [610]
3/4″ [19] NPT 3/4″ [19] NPT 1/2″ [12.7]
CRBTMPWR002A01 11/4″ [31.7] CRBTMPWR003A01 1/2″ [12.7] NPT 3/4″ [19] NPT CRBTMPWR004A01 3/4″ [19] NPT 11/4″ [31.7]
1′-911/16″ [551]
1′-4″ [406]
13/4″ [44.5]
1/2″ [12.7]
NPT
a48-7317


CRRFCURB003A01 1′-2″ [356] 580F 090-151 CRRFCURB004A01 2′-0″ [610]
3/4″ [19] NPT 11/4″ [31.7]

IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) 55,000 Btuh Sensible Heat Capacity (SHC) 40,000 Btuh Required Heating Capacity 60,000 Btuh Condenser Entering Air Temp 95 F (Summer) Evaporator Entering Air Temp 80 F edb,
MENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 75 find:
External static pressure 0.60 in. wg EconoMi$er IV static pressure 0.12 in. wg Total Static 0.72 in. wg Enter the standard motor Fan Performance table 580F060 Vertical Discharge (page 39) at 2,000 cfm and 0.72 in. wg external static pressure. The standard motor cannot provide 0.87 in. wg external static pressure. Enter the alternate motor Fan Performance table for 580F060, verti- cal discharge. At 2,000 cfm and 0.72 in. wg external static pressure, find that the rpm is 1219, the Bhp is 1.31, and the watts are 1168 (interpolation required). V DETERMINE NET COOLING CAPACITY.
67 F ewb Evaporator Air Quantity 2,000 cfm External Static Pressure 0.6 in. wg Electrical Characteristics (V-Ph-Hz) 230-3-60 Vertical discharge unit with optional EconoMi$er IV required.
edb — Entering dry-bulb ewb — Entering wet-bulb II SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY. Enter Cooling Capacities table for 580F060 (page 33) at condenser entering temperature 95 F, evaporator air entering at 2,000 cfm and 67 F wb. The 580F060 unit will provide a total cooling capacity of 60,900 Btuh and a sen- sible heating capacity of 45,300 Btuh. For air entering evaporator at temperatures other than 80 F edb, calculate sensible heat capacity correction as required using the for- mula in the notes following the Cooling Capacities tables. NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor heat. To calcu- late net capacities, see Step V. III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
Cooling capacities are gross capacities and do not include indoor (evaporator) fan motor (IFM) heat. Use the watts input power to the motor calculated in Section IV above. IFM Watts = 1168 Determine net cooling capacity using the following formula:
Net capacity = Gross capacity – IFM heat
= 60,900 Btuh – 1168 Watts
(3.412 Btuh Watts = 60,900 Btuh – 3985 Btuh = 56,915 Btuh
DESIGN CONDITION REQUIREMENTS. In the Heating Capacities and Efficiencies table (page 9) note that the 580F060 074 will provide an output capacity of 59,200 Btuh, which is adequate for the given application.
Net sensible capacity = 45,300 Btuh – 3985 Btuh
The calculations show that a 580F060 unit with the alter- nate motor and drive is the correct selection for the given conditions.
) · = 41,315 Btuh

580F036 (3 TONS)
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 900/0.11 1200/0.14 1500/0.17 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
75 TC 42.8 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2 SHC 20.0 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0 kW 2.91 2.81 2.70 2.99 2.88 2.78 3.02 2.92 2.82
85 TC 40.8 36.9 33.3 42.5 38.7 35.0 43.6 39.9 36.1 SHC 19.4 23.7 27.9 21.0 26.8 31.8 22.6 29.7 35.1 kW 3.14 3.01 2.90 3.20 3.08 2.97 3.24 3.14 3.02
95 TC 38.7 34.9 31.4 40.4 36.6 33.0 41.4 37.6 34.1 SHC 18.6 22.9 27.0 20.3 26.0 30.9 22.0 28.8 34.0 kW 3.35 3.21 3.09 3.42 3.29 3.16 3.47 3.35 3.22
105 TC 36.5 32.8 29.2 38.1 34.3 30.9 39.0 35.2 32.4 SHC 17.8 22.1 25.9 19.6 25.2 29.8 21.2 28.0 32.3 kW 3.55 3.41 3.27 3.63 3.49 3.35 3.68 3.54 3.43
115 TC 34.3 30.7 26.9 35.7 32.1 28.8 36.5 32.9 30.6 SHC 17.0 21.3 24.8 19.0 24.4 28.8 20.5 27.1 30.6 kW 3.76 3.60 3.45 3.84 3.68 3.54 3.88 3.74 3.64
Air Entering Evaporator — Cfm/BF 1200/0.12 1600/0.15 2000/0.18 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
Temp (F) Air Entering
75 TC 57.9 53.1 48.3 60.4 55.9 51.3 62.2 57.3 52.9 SHC 27.2 33.3 39.2 29.4 37.2 44.8 31.4 40.3 49.1 kW 4.07 3.93 3.79 4.17 4.03 3.90 4.24 4.08 3.96
85 TC 55.7 50.8 45.3 57.7 53.4 48.5 59.4 55.0 50.2 SHC 26.4 32.5 37.8 28.4 36.7 43.6 30.5 40.3 47.9 kW 4.40 4.24 4.08 4.47 4.35 4.20 4.54 4.42 4.25
95 TC 52.9 48.1 42.5 55.2 50.5 45.7 56.7 52.0 47.4 SHC 25.5 31.5 36.4 27.6 35.6 42.2 29.7 39.2 46.7 kW 4.70 4.54 4.36 4.78 4.63 4.47 4.87 4.70 4.56
105 TC 50.1 45.3 39.8 52.3 47.6 42.8 53.6 48.9 44.9 SHC 24.4 30.3 35.1 26.7 34.5 40.7 28.8 38.1 44.6 kW 5.00 4.81 4.62 5.10 4.91 4.73 5.17 4.99 4.84
115 TC 47.3 42.6 37.2 49.3 44.6 40.0 50.5 45.9 42.4 SHC 23.4 29.2 33.7 25.9 33.3 39.3 27.8 37.1 42.4 kW 5.30 5.07 4.88 5.42 5.19 4.99 5.48 5.28 5.12
Air Entering Evaporator — Cfm/BF 1500/0.07 2000/0.09 2500/0.12 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
Temp (F) Air Entering
75 TC 71.0 63.8 55.4 74.5 67.2 59.2 76.5 69.7 62.1 SHC 33.9 41.5 47.9 37.4 47.4 55.8 40.6 52.8 61.8 kW 5.04 4.82 4.62 5.20 4.97 4.76 5.29 5.06 4.87
85 TC 69.2 61.0 54.2 72.9 65.6 57.2 75.2 68.1 61.5 SHC 33.4 40.5 47.3 37.0 46.9 54.9 40.1 52.3 61.3 kW 5.50 5.27 5.02 5.66 5.41 5.18 5.75 5.50 5.29
95 TC 65.5 56.6 50.4 69.4 60.9 53.1 71.2 63.3 57.8 SHC 32.1 38.8 45.6 35.8 45.3 52.6 39.1 50.9 57.8 kW 5.88 5.62 5.37 6.01 5.76 5.53 6.12 5.87 5.67
105 TC 61.9 53.1 47.1 65.4 56.6 50.5 67.1 58.8 54.5 SHC 30.8 37.5 44.1 34.5 43.7 50.2 37.9 49.3 54.5 kW 6.25 5.99 5.72 6.38 6.13 5.91 6.50 6.23 6.06
115 TC 58.2 49.7 43.7 61.4 52.3 47.8 63.0 54.3 51.2 SHC 29.5 36.1 42.5 33.2 42.1 47.8 36.7 47.6 51.2 kW 6.63 6.35 6.08 6.75 6.49 6.29 6.88 6.59 6.46
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry-Bulb Lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil.

580F072 (6 TONS)
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 1800/0.06 2100/0.08 2400/0.09 3000/0.11 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 86.6 80.0 73.6 87.8 80.3 73.2 90.8 84.1 77.2 93.2 86.6 79.7 SHC 42.2 52.3 62.2 43.0 53.9 65.5 46.5 59.6 71.6 50.1 66.4 78.7 kW 5.48 5.33 5.21 5.69 5.50 5.32 5.59 5.44 5.29 5.66 5.51 5.35
85 TC 84.1 77.4 71.0 84.0 77.2 69.5 87.8 81.2 74.5 90.1 83.5 77.3 SHC 41.4 51.3 61.1 41.7 53.1 64.0 45.5 58.6 70.3 49.4 65.4 76.7 kW 6.17 6.00 5.85 6.21 6.04 5.83 6.27 6.11 5.94 6.35 6.19 6.02
95 TC 81.6 74.7 68.5 81.0 73.5 66.3 84.8 78.2 71.8 87.0 80.4 74.8 SHC 40.6 50.3 60.0 40.8 51.8 62.8 44.6 57.6 69.1 48.7 64.5 74.7 kW 6.86 6.67 6.49 6.78 6.54 6.33 6.95 6.77 6.59 7.03 6.86 6.69
105 TC 78.4 71.8 65.6 76.8 69.7 62.5 81.6 74.9 68.9 83.3 76.9 72.1 SHC 39.4 49.2 58.7 39.4 50.3 61.1 43.5 56.4 67.4 47.4 63.1 72.0 kW 7.60 7.39 7.20 7.30 7.05 6.80 7.72 7.50 7.31 7.77 7.59 7.41
115 TC 75.1 68.7 62.5 72.5 65.5 58.7 78.0 71.5 66.1 79.5 73.3 69.3 SHC 38.1 47.9 57.2 37.9 48.7 58.7 42.3 55.1 65.5 46.3 61.6 69.2 kW 8.36 8.14 7.93 7.81 7.53 7.27 8.49 8.25 8.06 8.55 8.33 8.18
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 1800/0.06 2100/0.07 2400/0.09 3000/0.11 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 81.3 77.8 71.3 82.7 78.7 72.9 84.2 79.7 74.6 85.3 82.5 76.7 SHC 38.2 51.3 61.6 40.2 54.2 65.9 42.3 57.1 70.2 43.7 64 76.4 kW 4.69 4.63 4.52 4.73 4.65 4.56 4.77 4.67 4.6 4.8 4.75 4.63
85 TC 78.8 75.6 69 81.1 77.1 70.7 83.3 78.6 72.3 85 80.5 75 SHC 37.7 50.4 60.5 40 53.9 64.9 42.2 57.5 69.2 44.3 63.6 74.9 kW 5.21 5.16 5.05 5.27 5.2 5.09 5.34 5.24 5.13 5.39 5.29 5.17
95 TC 77.1 73.3 66.9 79.2 74.8 68.5 81.3 76.2 70.1 82 78 73.3 SHC 37 49.9 59.7 39.4 53.3 64 41.8 56.8 68.3 43.5 63.4 73.2 kW 5.8 5.78 5.65 5.87 5.81 5.7 5.94 5.85 5.74 5.95 5.88 5.8
105 TC 75.4 70.7 62.9 76.6 72.1 64.8 77.9 73.4 66.7 79.7 74.9 70.9 SHC 36.7 48.7 58.2 38.6 52.3 62.2 40.6 55.9 66.3 43 62.4 70.9 kW 6.49 6.45 6.26 6.53 6.48 6.32 6.56 6.51 6.38 6.61 6.53 6.46
115 TC 72.1 67.9 59 73.6 69 61.1 75.2 70.1 63.3 76.7 71.9 68.1 SHC 35.3 47.5 57.2 37.6 51.2 60.2 39.9 54.8 63.3 42.2 61.5 68.1 kW 7.2 7.17 6.94 7.25 7.18 7.01 7.29 7.2 7.08 7.35 7.26 7.15
Air Entering Evaporator — Cfm/BF 2250/0.07 2800/0.09 3000/0.10 3750/0.12 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
Temp (F) Air Entering
75 TC 102.8 94.8 86.2 105.8 98.2 90.0 106.4 99.0 90.8 109.2 101.6 93.6 SHC 49.4 61.8 73.2 52.6 67.8 81.6 53.6 69.8 84.0 58.2 77.4 92.2 kW 7.14 6.82 6.50 7.28 6.98 6.68 7.32 7.04 6.72 7.46 7.18 6.86
85 TC 98.2 90.2 81.6 101.8 93.6 85.2 102.6 94.4 86.0 104.6 96.8 89.6 SHC 48.0 60.2 71.2 51.6 66.4 79.6 52.8 68.6 82.0 56.8 76.0 89.4 kW 7.66 7.34 7.00 7.82 7.50 7.18 7.86 7.54 7.22 7.98 7.68 7.40
95 TC 93.8 85.2 76.6 97.0 88.4 80.0 97.6 89.0 81.2 99.4 91.2 85.2 SHC 46.4 58.2 68.8 50.2 64.6 77.2 51.4 66.8 79.0 55.6 74.4 85.2 kW 8.18 7.84 7.48 8.36 8.00 7.64 8.40 8.04 7.70 8.50 8.16 7.92
105 TC 88.4 79.8 70.8 91.0 82.8 74.6 91.6 83.4 76.0 93.8 85.4 80.6 SHC 44.6 56.2 66.0 48.2 62.6 74.2 49.4 64.8 75.6 54.2 72.4 80.6 kW 8.68 8.30 7.98 8.80 8.46 8.14 8.86 8.50 8.20 8.98 8.64 8.42
115 TC 82.8 73.8 66.0 85.2 76.8 69.6 85.6 77.4 71.0 87.6 79.4 76.0 SHC 42.6 53.8 63.2 46.4 60.4 69.6 47.8 62.6 71.0 52.8 70.4 75.8 kW 9.16 8.78 8.42 9.30 8.92 8.64 9.34 8.96 8.72 9.48 9.10 8.94

580F091 (7 1 / 2 TONS)
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 2250/0.10 2800/0.11 3000/0.11 3750/0.14 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 105.8 97.6 88.7 108.9 101.1 92.6 109.5 101.9 93.5 112.4 104.6 96.4 SHC 50.9 63.6 75.4 54.1 69.8 84.0 55.2 71.9 86.5 59.9 79.7 94.9 kW 6.34 6.05 5.77 6.46 6.19 5.93 6.50 6.25 5.96 6.62 6.37 6.09
85 TC 101.1 92.9 84.0 104.8 96.4 87.7 105.6 97.2 88.5 107.7 99.6 92.2 SHC 49.4 62.0 73.3 53.1 68.4 81.9 54.4 70.6 84.4 58.5 78.2 92.0 kW 6.80 6.51 6.21 6.94 6.66 6.37 6.98 6.69 6.41 7.08 6.82 6.57
95 TC 96.6 87.7 78.9 99.9 91.0 82.4 100.5 91.6 83.6 102.3 93.9 87.7 SHC 47.8 59.9 70.8 51.7 66.5 79.5 52.9 68.8 81.3 57.2 76.6 87.7 kW 7.26 6.96 6.64 7.42 7.10 6.78 7.46 7.14 6.83 7.54 7.24 7.03
105 TC 91.0 82.1 72.9 93.7 85.2 76.8 94.3 85.9 78.2 96.6 87.9 83.0 SHC 45.9 57.9 67.9 49.6 64.4 76.4 50.9 66.7 77.8 55.8 74.5 83.0 kW 7.70 7.37 7.08 7.81 7.51 7.22 7.86 7.54 7.28 7.97 7.67 7.47
115 TC 85.2 76.0 67.9 87.7 79.1 71.6 88.1 79.7 73.1 90.2 81.7 78.2 SHC 43.9 55.4 65.1 47.8 62.2 71.6 49.2 64.4 73.1 54.4 72.5 78.0 kW 8.13 7.79 7.47 8.25 7.92 7.67 8.29 7.95 7.74 8.41 8.08 7.93
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 2550/0.08 3000/0.09 3400/0.11 4250/0.13 Air Entering Evaporator — Ewb 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 117.7 104.1 93.4 121.3 107.5 97.2 122.9 109.0 98.7 124.4 111.1 101.8 SHC 55.7 64.7 76.6 59.3 70.6 85.0 61.3 74.7 91.4 66.8 82.1 99.7 kW 6.42 6.34 6.26 6.46 6.38 6.30 6.47 6.39 6.33 6.50 6.41 6.35
85 TC 113.8 100.4 89.2 117.9 103.8 93.4 119.6 105.3 94.7 122.1 107.5 97.2 SHC 54.3 63.3 75.0 58.0 69.4 83.8 60.4 73.4 89.1 65.2 81.7 97.0 kW 7.35 7.26 7.17 7.41 7.31 7.24 7.43 7.33 7.24 7.46 7.37 7.28
95 TC 109.6 96.2 85.3 113.3 99.7 89.2 115.4 101.1 90.3 118.3 103.2 93.1 SHC 52.9 61.9 73.1 56.5 67.9 81.7 59.1 71.9 87.3 64.0 80.3 93.1 kW 8.37 8.27 8.16 8.42 8.33 8.24 8.46 8.34 8.22 8.51 8.40 8.31
105 TC 105.6 92.1 81.3 108.8 95.2 84.6 110.4 96.4 86.3 113.2 98.4 89.1 SHC 51.4 60.4 71.6 55.2 66.4 80.0 57.5 70.3 85.3 62.5 78.3 89.1 kW 9.49 9.37 9.27 9.55 9.44 9.34 9.57 9.45 9.35 9.61 9.49 9.41
115 TC 100.4 87.9 76.8 103.1 90.4 80.3 105.1 91.7 82.1 107.6 93.5 85.0 SHC 49.4 58.6 69.6 52.9 64.7 78.3 55.8 68.5 81.9 60.6 76.6 85.0 kW 10.63 10.56 10.46 10.70 10.62 10.55 10.74 10.62 10.54 10.80 10.68 10.58
125 TC 95.8 83.0 72.0 98.5 85.5 74.9 99.8 86.6 77.5 101.4 88.2 80.7 SHC 48.0 56.8 67.5 51.6 62.9 74.9 54.0 66.9 77.5 58.2 74.6 80.7 kW 11.97 11.83 11.61 12.02 11.89 11.73 12.05 11.92 11.80 12.09 11.97 11.86
Air Entering Evaporator — Cfm/BF 3000/0.095 4000/0.125 5000/0.15 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
Temp (F) Air Entering
75 TC 135.8 124.8 112.0 142.4 130.6 119.8 146.5 134.2 123.7 SHC 66.8 82.6 97.4 73.2 93.4 112.7 79.7 104.4 123.1 kW 9.76 9.41 9.10 10.00 9.61 9.27 10.17 9.75 9.41
85 TC 130.0 119.6 104.0 136.0 125.0 114.5 140.0 127.9 118.8 SHC 64.3 80.5 93.8 71.1 91.7 110.2 77.5 101.8 118.7 kW 10.41 10.07 9.74 10.67 10.28 9.94 10.84 10.41 10.09
95 TC 124.1 113.7 96.7 129.5 118.9 106.9 132.8 122.0 114.1 SHC 62.2 78.4 90.0 69.1 89.8 105.9 74.9 100.1 114.0 kW 11.13 10.78 10.40 11.38 10.99 10.63 11.52 11.14 10.83
105 TC 118.1 104.6 87.9 122.7 111.8 98.5 126.0 115.1 108.0 SHC 60.4 74.9 85.2 66.9 87.7 98.5 73.1 98.3 108.0 kW 11.93 11.52 11.10 12.13 11.74 11.41 12.27 11.89 11.65
115 TC 115.0 98.0 84.2 120.0 103.8 93.4 122.6 109.8 102.8 SHC 59.4 72.4 83.4 66.4 84.8 93.4 72.8 96.9 102.8 kW 12.26 11.82 11.40 12.48 12.06 11.78 12.60 12.20 12.00

580F121 (10 TONS)
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 3000/0.095 4000/0.125 5000/0.15 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
75 TC 138.2 127.0 114.0 145.0 132.9 122.0 149.1 136.6 125.9 SHC 68.0 84.1 99.1 74.5 95.1 114.7 81.1 106.3 125.3 kW 8.37 8.07 7.80 8.57 8.24 7.95 8.72 8.36 8.07
85 TC 132.3 121.7 105.9 138.4 127.2 116.6 142.5 130.2 120.9 SHC 65.5 81.9 95.5 72.4 93.3 112.2 78.9 103.6 120.8 kW 8.92 8.63 8.35 9.15 8.81 8.52 9.29 8.92 8.65
95 TC 126.3 115.7 98.4 131.8 121.0 108.8 135.2 124.2 116.1 SHC 63.3 79.8 91.6 70.3 91.4 107.8 76.2 101.9 116.0 kW 9.54 9.24 8.91 9.75 9.42 9.11 9.87 9.55 9.28
105 TC 120.2 106.5 89.5 124.9 113.8 100.3 128.3 117.2 109.9 SHC 61.5 76.2 86.7 68.1 89.3 100.3 74.4 100.1 109.9 kW 10.23 9.87 9.51 10.40 10.06 9.78 10.52 10.19 9.99
115 TC 117.1 99.8 85.7 122.2 105.7 95.1 124.8 111.8 104.6 SHC 60.5 73.7 84.9 67.6 86.3 95.1 74.1 98.6 104.6 kW 10.51 10.13 9.77 10.70 10.34 10.10 10.80 10.46 10.29
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 3750/0.08 4500/0.09 5000/0.10 6250/0.12 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 175.6 162.2 149.2 181.0 167.5 154.2 182.9 170.2 156.4 187.2 174.7 161.8 SHC 85.7 107.3 128.0 91.4 116.2 140.3 94.2 122.2 146.5 102.1 135.3 160.7 kW 11.16 10.85 10.57 11.32 11.00 10.69 11.37 11.07 10.73 11.49 11.19 10.87
85 TC 169.3 155.7 140.6 174.2 160.7 147.0 176.9 163.0 149.7 181.5 167.3 155.8 SHC 83.9 104.8 124.0 89.6 113.9 137.0 92.7 119.7 143.6 100.9 133.4 155.6 kW 12.15 11.78 11.42 12.31 11.94 11.58 12.39 12.01 11.63 12.53 12.14 11.82
95 TC 161.9 148.9 132.0 166.8 153.5 139.1 169.5 155.7 142.8 173.2 159.5 149.6 SHC 81.4 102.0 119.8 87.0 111.1 133.2 90.7 117.3 140.2 98.3 130.8 149.6 kW 13.12 12.72 12.28 13.30 12.89 12.46 13.40 12.97 12.56 13.54 13.11 12.78
105 TC 154.9 141.3 123.0 158.8 145.4 130.2 160.9 147.6 135.0 165.3 151.2 143.2 SHC 79.0 99.2 115.5 84.5 108.2 128.1 87.8 114.3 134.9 96.6 127.8 143.1 kW 14.16 13.66 13.17 14.31 13.82 13.35 14.38 13.91 13.48 14.58 14.07 13.77
115 TC 146.2 132.2 113.1 150.5 137.0 122.4 152.3 139.4 127.8 155.2 142.7 136.0 SHC 76.1 95.7 110.3 81.7 105.2 122.3 85.0 111.6 127.7 92.9 125.0 135.8 kW 15.09 14.57 14.07 15.30 14.76 14.25 15.37 14.87 14.43 15.49 15.02 14.73
Air Entering Evaporator — Cfm/BF 3750/0.08 4300/0.09 5000/0.11 6250/0.13 Air Entering Evaporator — Ewb 72 67 62 72 67 62 72 67 62 72 67 62
Temp (F) Air Entering
75 TC 164.6 152.0 139.9 167.3 155.3 142.6 170.9 158.2 146.2 173.9 162.0 151.0 SHC 81.3 101.9 121.7 84.5 108.1 130.0 88.9 115.9 139.8 96.7 128.7 150.8 kW 10.24 9.96 9.71 10.31 10.05 9.78 10.42 10.12 9.84 10.50 10.23 9.95
85 TC 159.9 147.1 133.6 162.6 150.2 137.4 166.3 153.0 141.3 169.5 156.8 147.1 SHC 79.7 99.9 119.1 83.1 106.3 128.0 88.3 114.1 137.7 96.1 127.4 146.9 kW 11.38 11.05 10.82 11.45 11.14 10.87 11.58 11.20 10.97 11.66 11.32 11.08
95 TC 154.2 141.5 124.4 157.2 144.6 129.3 159.9 147.6 134.5 164.0 150.9 142.3 SHC 77.9 98.0 114.8 81.8 104.5 124.1 86.3 112.5 133.8 94.4 125.8 142.2 kW 12.59 12.26 11.95 12.68 12.36 12.04 12.75 12.44 12.15 12.88 12.54 12.31
105 TC 147.8 134.2 114.0 150.7 137.2 119.1 153.3 140.4 136.4 156.4 143.7 136.7 SHC 75.4 95.2 109.5 79.6 101.9 118.2 84.4 110.6 126.5 92.2 124.0 136.6 kW 13.84 13.48 13.12 13.92 13.58 13.24 14.01 13.69 13.37 14.06 13.80 13.58
115 TC 139.7 120.4 102.8 142.1 124.2 109.1 145.5 127.5 117.1 148.4 133.2 128.1 SHC 72.5 89.8 102.6 76.7 97.0 109.1 82.1 105.7 116.6 90.4 120.1 128.0 kW 15.03 14.70 14.34 15.12 14.80 15.24 15.24 14.90 14.65 15.35 15.04 14.86
125 TC 130.5 107.0 92.5 132.8 109.7 135.5 135.5 112.7 105.0 138.2 121.1 118.3 SHC 69.8 84.4 92.4 73.7 91.5 99.2 79.0 99.9 104.9 87.7 114.6 118.3 kW 16.32 15.91 15.67 16.43 16.00 15.79 16.52 16.11 15.97 16.59 16.21 16.10
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry-Bulb Lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil.

580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 900 0.49 0.21 253 0.50 0.23 277 0.51 0.26 307 0.55 0.31 363 1000 0.42 0.23 270 0.43 0.25 292 0.43 0.27 321 0.51 0.32 374 1100 0.37 0.24 287 0.38 0.26 307 0.39 0.28 335 0.46 0.33 385 1200 0.33 0.26 304 0.33 0.27 323 0.34 0.29 349 0.40 0.34 397 1300 0.27 0.27 321 0.28 0.29 338 0.28 0.31 364 0.34 0.34 408 1400 0.20 0.29 338 0.23 0.30 354 0.25 0.32 378 — — — 1500 0.16 0.30 355 0.18 0.31 369 0.20 0.33 392 — — —
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
580F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 — — — 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 — 1400 1273 0.97 967 1337 1.09 1082 — 1500 1309 1.09 1082 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
580F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 1444 1.21 1200 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 1421 1.21 1199 1475 1.32 1316 1400 1273 0.97 967 1337 1.09 1082 1397 1.21 1200 1453 1.33 1320 1507 1.45 1443 1500 1309 1.09 1082 1371 1.21 1204 1430 1.33 1327 1486 1.46 1453 1540 1.59 1581
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1200 0.68 0.41 458 0.74 0.45 506 0.74 0.51 572 0.85 0.56 632 1300 0.61 0.42 471 0.67 0.46 521 0.66 0.52 589 0.78 0.58 651 1400 0.53 0.45 503 0.59 0.49 556 0.59 0.54 616 0.70 0.60 681 1500 0.45 0.47 536 0.51 0.52 593 0.52 0.56 631 0.63 0.62 698 1600 0.36 0.49 557 0.42 0.54 616 0.45 0.58 654 0.56 0.64 723 1700 0.26 0.52 584 0.32 0.57 646 0.37 0.60 678 0.48 0.66 750 1800 0.15 0.54 610 0.22 0.60 674 0.30 0.62 698 0.41 0.68 772 1900 0.04 0.56 629 0.11 0.62 696 0.23 0.64 720 0.34 0.70 796 2000 — 0.16 0.66 744 0.26 0.73 823
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 — — — 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 — 2000 962 0.85 847 1049 1.05 1043 —
580F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 — — — 1400 1147 0.98 972 1208 1.09 1086 — 1500 1175 1.09 1086 — 1600 — 1700 — 1800 — 1900 — 2000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1200 1.32 1316 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 1165 1.29 1283 1231 1.46 1453 2000 962 0.85 847 1049 1.05 1043 1127 1.24 1233 1198 1.42 1417 1263 1.61 1598
580F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572 1600 1204 1.21 1207 1263 1.35 1340 1320 1.48 1472 1373 1.61 1603 1424 1.74 1732 1700 1233 1.34 1336 1292 1.49 1480 1348 1.63 1622 1401 1.77 1762 1451 1.91 1901 1800 1262 1.48 1473 1321 1.64 1627 1376 1.79 1779 1428 1.94 1930 1479 2.09 2078 1900 1293 1.63 1620 1350 1.79 1784 1405 1.96 1946 1457 2.12 2106 1506 2.28 2265 2000 1323 1.79 1776 1380 1.96 1950 1434 2.13 2123 1486 2.31 2293 — — —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed Medium Speed High Speed 208 V 230,460,575 V 208 V 230,460,575 V 208 V 230,460,575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1500 0.69 0.67 750 1.01 0.71 791 1.00 0.70 782 1.20 0.76 845 1.22 0.79 875 1.28 0.85 949 1600 0.49 0.70 780 0.85 0.74 824 0.85 0.74 821 1.06 0.79 883 1.09 0.82 913 1.17 0.89 988 1700 0.29 0.73 810 0.70 0.77 857 0.70 0.77 861 0.93 0.83 921 0.97 0.85 950 1.06 0.92 1027 1800 0.09 0.75 839 0.54 0.80 891 0.55 0.81 900 0.80 0.86 959 0.84 0.89 988 0.95 0.96 1066 1900 — — — 0.39 0.83 924 0.40 0.84 940 0.67 0.90 997 0.72 0.92 1025 0.84 0.99 1105 2000 — — — 0.23 0.86 957 0.25 0.88 979 0.54 0.93 1035 0.59 0.95 1063 0.73 1.03 1144 2100 — — — 0.08 0.89 990 0.10 0.91 1018 0.41 0.96 1073 0.46 0.99 1101 0.62 1.06 1183 2200 — 0.28 1.00 1111 0.34 1.02 1138 0.51 1.10 1222 2300 — 0.15 1.03 1149 0.21 1.06 1176 0.40 1.13 1261 2400 — 0.02 1.07 1187 0.09 1.09 1213 0.29 1.17 1300 2500 — 0.18 1.20 1340
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 — — —
580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 — — — 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 — — — 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 — 2100 1415 1.95 1736 1476 2.18 1940 — 2200 1448 2.11 1875 1507 2.35 2083 — 2300 1480 2.28 2025 — 2400 — 2500 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require a field-supplied drive.

580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 1486 2.42 2149
580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 1552 2.50 2219 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 1580 2.63 2339 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 1557 2.52 2240 1609 2.78 2470 2100 1415 1.95 1736 1476 2.18 1940 1533 2.43 2155 1587 2.68 2378 — — — 2200 1448 2.11 1875 1507 2.35 2083 1563 2.59 2301 1617 2.85 2528 — — — 2300 1480 2.28 2025 1539 2.52 2237 1595 2.77 2459 — 2400 1513 2.46 2187 1571 2.71 2403 — 2500 1547 2.66 2360 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied drive.

580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 — — — 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 — — — 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 — 2800 1386 2.09 1860 1471 2.35 2085 — 2900 1429 2.31 2050 — 3000 —
580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 — — — 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 — 2200 1538 2.04 1816 1602 2.23 1984 — 2300 1572 2.23 1978 — 2400 — 2500 — 2600 — 2700 — 2800 — 2900 — 3000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 1576 2.41 2142 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 1613 2.62 2329 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 1581 2.61 2320 1649 2.85 2527 2800 1386 2.09 1860 1471 2.35 2085 1548 2.60 2305 1619 2.84 2522 — — — 2900 1429 2.31 2050 1512 2.57 2283 1588 2.83 2512 — 3000 1473 2.54 2252 1553 2.81 2494 —
580F072,073 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 1713 2.41 2142 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 1688 2.42 2149 1744 2.60 2312 2200 1538 2.04 1816 1602 2.23 1984 1663 2.42 2152 1720 2.61 2321 1775 2.81 2491 2300 1572 2.23 1978 1635 2.42 2153 1695 2.62 2328 1753 2.82 2504 — — — 2400 1607 2.42 2150 1669 2.63 2332 1729 2.83 2515 — 2500 1642 2.63 2333 1704 2.84 2523 — 2600 1677 2.85 2527 — 2700 — 2800 — 2900 — 3000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied drive.

580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 —
580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 — 2300 844 1.90 1773 893 2.22 2073 — 2400 854 1.99 1855 903 2.32 2159 — 2500 865 2.08 1940 — 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field-supplied drive.

580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 —
580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 — 2300 844 1.90 1773 893 2.22 2073 — 2400 854 1.99 1855 903 2.32 2159 — 2500 865 2.08 1940 — 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100
580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 935 2.52 2345 980 2.87 2673 1022 3.23 3015 2300 844 1.90 1773 893 2.22 2073 940 2.56 2389 984 2.91 2718 1027 3.28 3062 2400 854 1.99 1855 903 2.32 2159 950 2.66 2478 993 3.02 2812 1035 3.39 3159 2500 865 2.08 1940 913 2.41 2249 959 2.76 2573 1003 3.12 2911 1044 3.50 3261 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 — — — 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 — — — 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 — — — 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 — 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 — 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 — 3300 955 3.01 2810 1000 3.39 3159 — 3400 967 3.16 2945 1012 3.54 3299 — 3500 980 3.31 3084 1024 3.69 3445 — 3600 992 3.46 3230 — 3700 1005 3.63 3383 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 — 3800 761 1.98 1842 820 2.31 2156 — 3900 777 2.12 1974 — 4000 794 2.27 2113 — 4100 — 4200 — 4250 —
580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100 3800 761 1.98 1842 820 2.31 2156 874 2.66 2484 925 3.03 2824 973 3.41 3177 3900 777 2.12 1974 835 2.46 2296 889 2.82 2630 939 3.19 2977 986 3.58 3336 4000 794 2.27 2113 851 2.62 2442 904 2.99 2784 953 3.36 3137 — — — 4100 811 2.42 2259 867 2.78 2595 919 3.16 2944 968 3.54 3304 — — — 4200 828 2.59 2412 883 2.95 2755 934 3.34 3110 — 4250 837 2.67 2490 891 3.04 2838 942 3.43 3197 —
580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 — — — 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 — — — 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 — — — 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 — 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 — 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 — 3300 955 3.01 2810 1000 3.39 3159 — 3400 967 3.16 2945 1012 3.54 3299 — 3500 980 3.31 3084 1024 3.69 3445 — 3600 992 3.46 3230 — 3700 1005 3.63 3383 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 — — — 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 — — — 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 — 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 — 4300 989 1.93 1694 1039 2.19 1920 — 4400 1009 2.06 1804 1058 2.32 2034 — 4500 1030 2.19 1919 — 4600 1051 2.32 2039 — 4700 — 4800 — 4900 — 5000 —
580F120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 — 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 — 3200 1041 1.97 1732 1088 2.22 1947 — 3300 1056 2.07 1817 1102 2.32 2036 — 3400 1071 2.17 1905 — 3500 1087 2.28 1998 — 3600 1102 2.39 2094 — 3700 — 3800 — 3900 — 4000 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F120 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 — — — 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 — — — 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 — 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 — 4700 1071 2.47 2165 1118 2.75 2409 — 4800 1092 2.62 2295 1138 2.90 2545 — 4900 1113 2.77 2431 — 5000 —
580F120 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 — — — 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 — — — 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 — 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 — 3600 1102 2.39 2094 1146 2.65 2326 — 3700 1118 2.50 2195 1162 2.77 2430 — 3800 1134 2.62 2300 1177 2.89 2539 — 3900 1150 2.75 2410 — 4000 1167 2.88 2524 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field-supplied drive.

580F120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 1175 3.01 2640 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 1192 3.15 2768 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 1168 3.01 2646 1210 3.31 2901 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 1186 3.17 2780 1228 3.46 3040 4700 1071 2.47 2165 1118 2.75 2409 1162 3.03 2661 1205 3.33 2919 1245 3.63 3184 4800 1092 2.62 2295 1138 2.90 2545 1181 3.19 2801 1223 3.49 3064 1264 3.80 3333 4900 1113 2.77 2431 1158 3.06 2685 1201 3.36 2947 1242 3.66 3214 1282 3.97 3487 5000 1134 2.93 2572 1178 3.23 2832 1220 3.53 3097 1261 3.84 3369 1300 4.16 3647
580F120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 1215 3.00 2636 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 1228 3.12 2735 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 1201 2.96 2595 1241 3.23 2839 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 1215 3.08 2699 1255 3.36 2946 3600 1102 2.39 2094 1146 2.65 2326 1188 2.92 2563 1229 3.20 2808 1268 3.48 3058 3700 1118 2.50 2195 1162 2.77 2430 1203 3.04 2672 1243 3.33 2920 1282 3.62 3174 3800 1134 2.62 2300 1177 2.89 2539 1218 3.17 2785 1258 3.46 3036 1296 3.75 3295 3900 1150 2.75 2410 1193 3.02 2653 1233 3.31 2902 1273 3.60 3158 1311 3.90 3420 4000 1167 2.88 2524 1208 3.16 2770 1249 3.45 3024 1287 3.74 3284 1325 4.04 3549 4100 1183 3.01 2642 1224 3.30 2893 1264 3.59 3151 1302 3.89 3414 1340 4.20 3683 4200 1200 3.15 2765 1240 3.44 3020 1280 3.74 3282 1318 4.04 3549 1355 4.36 3823 4300 1216 3.30 2893 1257 3.59 3152 1295 3.89 3418 1333 4.20 3690 1370 4.52 3967 4400 1233 3.45 3025 1273 3.75 3289 1311 4.05 3559 1349 4.37 3834 1385 4.69 4116 4500 1250 3.60 3163 1290 3.91 3431 1328 4.22 3705 1364 4.54 3985 — — — 4600 1268 3.77 3306 1306 4.08 3578 1344 4.39 3856 1380 4.72 4140 — — — 4700 1285 3.94 3454 1323 4.25 3730 1360 4.57 4013 1396 4.90 4300 — — — 4800 1303 4.11 3608 1340 4.43 3888 1377 4.76 4175 — 4900 1320 4.29 3766 1357 4.62 4051 1394 4.95 4342 — 5000 1338 4.48 3930 1375 4.81 4219 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

580F121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 592 0.77 672 658 0.93 817 719 1.10 961 775 1.26 1105 828 1.42 1249 3100 607 0.83 731 672 1.00 881 731 1.17 1030 787 1.34 1179 839 1.51 1328 3200 623 0.90 794 686 1.08 949 744 1.26 1103 798 1.43 1257 850 1.61 1410 3300 638 0.98 860 700 1.16 1020 757 1.34 1179 810 1.52 1338 861 1.71 1496 3400 653 1.06 931 714 1.25 1095 770 1.44 1260 822 1.62 1423 872 1.81 1586 3500 669 1.15 1005 728 1.34 1175 783 1.53 1344 835 1.72 1512 884 1.91 1680 3600 685 1.23 1084 742 1.43 1258 796 1.63 1432 847 1.83 1606 895 2.03 1778 3700 700 1.33 1167 757 1.53 1346 810 1.74 1524 860 1.94 1703 907 2.14 1881 3800 716 1.43 1254 771 1.64 1438 823 1.85 1621 873 2.06 1805 919 2.26 1987 3900 732 1.53 1345 786 1.75 1534 837 1.96 1722 886 2.18 1911 932 2.39 2099 4000 748 1.64 1441 801 1.86 1635 851 2.08 1828 899 2.30 2022 — — — 4100 764 1.76 1542 816 1.98 1741 865 2.21 1939 — 4200 780 1.88 1648 831 2.11 1851 879 2.34 2054 — 4300 796 2.00 1758 846 2.24 1966 — 4400 812 2.13 1874 861 2.38 2087 — 4500 828 2.27 1994 — 4600 — 4700 — 4800 — 4900 — 5000 —
580F121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 878 1.59 1391 925 1.75 1534 970 1.91 1676 1014 2.07 1817 1055 2.23 1958 3100 888 1.68 1475 935 1.85 1623 979 2.02 1769 1022 2.18 1916 1063 2.35 2062 3200 898 1.78 1563 944 1.95 1715 988 2.13 1867 1031 2.30 2018 — — — 3300 909 1.88 1654 954 2.06 1811 998 2.24 1968 — 3400 919 1.99 1749 964 2.18 1911 1007 2.36 2073 — 3500 930 2.11 1848 975 2.30 2015 — 3600 941 2.22 1951 — 3700 952 2.35 2058 — 3800 — 3900 — 4000 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Refer to page 74 for general Fan Performance Data notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 592 0.77 672 658 0.93 817 719 1.10 961 775 1.26 1105 828 1.42 1249 3100 607 0.83 731 672 1.00 881 731 1.17 1030 787 1.34 1179 839 1.51 1328 3200 623 0.90 794 686 1.08 949 744 1.26 1103 798 1.43 1257 850 1.61 1410 3300 638 0.98 860 700 1.16 1020 757 1.34 1179 810 1.52 1338 861 1.71 1496 3400 653 1.06 931 714 1.25 1095 770 1.44 1260 822 1.62 1423 872 1.81 1586 3500 669 1.15 1005 728 1.34 1175 783 1.53 1344 835 1.72 1512 884 1.91 1680 3600 685 1.23 1084 742 1.43 1258 796 1.63 1432 847 1.83 1606 895 2.03 1778 3700 700 1.33 1167 757 1.53 1346 810 1.74 1524 860 1.94 1703 907 2.14 1881 3800 716 1.43 1254 771 1.64 1438 823 1.85 1621 873 2.06 1805 919 2.26 1987 3900 732 1.53 1345 786 1.75 1534 837 1.96 1722 886 2.18 1911 932 2.39 2099 4000 748 1.64 1441 801 1.86 1635 851 2.08 1828 899 2.30 2022 944 2.52 2214 4100 764 1.76 1542 816 1.98 1741 865 2.21 1939 912 2.43 2137 957 2.66 2334 4200 780 1.88 1648 831 2.11 1851 879 2.34 2054 925 2.57 2257 969 2.80 2460 4300 796 2.00 1758 846 2.24 1966 894 2.48 2175 939 2.71 2382 — — — 4400 812 2.13 1874 861 2.38 2087 908 2.62 2299 952 2.86 2512 — — — 4500 828 2.27 1994 877 2.52 2212 922 2.77 2430 — 4600 845 2.42 2120 892 2.67 2343 — 4700 861 2.57 2251 907 2.82 2479 — 4800 877 2.72 2388 — 4900 894 2.88 2531 — 5000 —
580F121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 878 1.59 1391 925 1.75 1534 970 1.91 1676 1014 2.07 1817 1055 2.23 1958 3100 888 1.68 1475 935 1.85 1623 979 2.02 1769 1022 2.18 1916 1063 2.35 2062 3200 898 1.78 1563 944 1.95 1715 988 2.13 1867 1031 2.30 2018 1072 2.47 2169 3300 909 1.88 1654 954 2.06 1811 998 2.24 1968 1040 2.42 2124 1080 2.60 2280 3400 919 1.99 1749 964 2.18 1911 1007 2.36 2073 1049 2.55 2234 1089 2.73 2395 3500 930 2.11 1848 975 2.30 2015 1017 2.49 2182 1058 2.68 2348 1098 2.86 2514 3600 941 2.22 1951 985 2.42 2123 1027 2.61 2295 1068 2.81 2466 — — — 3700 952 2.35 2058 996 2.55 2236 1038 2.75 2412 — 3800 964 2.47 2170 1007 2.68 2352 1048 2.89 2534 — 3900 976 2.60 2286 1018 2.82 2473 — 4000 987 2.74 2407 — 4100 999 2.88 2532 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Refer to page 74 for general Fan Performance Data notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field-supplied drive.

580F121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 592 0.77 672 658 0.93 817 719 1.10 961 775 1.26 1105 828 1.42 1249 3100 607 0.83 731 672 1.00 881 731 1.17 1030 787 1.34 1179 839 1.51 1328 3200 623 0.90 794 686 1.08 949 744 1.26 1103 798 1.43 1257 850 1.61 1410 3300 638 0.98 860 700 1.16 1020 757 1.34 1179 810 1.52 1338 861 1.71 1496 3400 653 1.06 931 714 1.25 1095 770 1.44 1260 822 1.62 1423 872 1.81 1586 3500 669 1.15 1005 728 1.34 1175 783 1.53 1344 835 1.72 1512 884 1.91 1680 3600 685 1.23 1084 742 1.43 1258 796 1.63 1432 847 1.83 1606 895 2.03 1778 3700 700 1.33 1167 757 1.53 1346 810 1.74 1524 860 1.94 1703 907 2.14 1881 3800 716 1.43 1254 771 1.64 1438 823 1.85 1621 873 2.06 1805 919 2.26 1987 3900 732 1.53 1345 786 1.75 1534 837 1.96 1722 886 2.18 1911 932 2.39 2099 4000 748 1.64 1441 801 1.86 1635 851 2.08 1828 899 2.30 2022 944 2.52 2214 4100 764 1.76 1542 816 1.98 1741 865 2.21 1939 912 2.43 2137 957 2.66 2334 4200 780 1.88 1648 831 2.11 1851 879 2.34 2054 925 2.57 2257 969 2.80 2460 4300 796 2.00 1758 846 2.24 1966 894 2.48 2175 939 2.71 2382 982 2.95 2589 4400 812 2.13 1874 861 2.38 2087 908 2.62 2299 952 2.86 2512 995 3.10 2725 4500 828 2.27 1994 877 2.52 2212 922 2.77 2430 966 3.02 2648 1008 3.26 2865 4600 845 2.42 2120 892 2.67 2343 937 2.92 2566 980 3.18 2788 1022 3.43 3010 4700 861 2.57 2251 907 2.82 2479 952 3.08 2706 994 3.34 2934 1035 3.60 3161 4800 877 2.72 2388 923 2.99 2621 966 3.25 2853 1008 3.52 3086 1049 3.78 3317 4900 894 2.88 2531 938 3.15 2768 981 3.42 3005 1022 3.69 3242 1062 3.96 3479 5000 910 3.05 2679 954 3.33 2921 996 3.60 3163 1037 3.88 3405 1076 4.15 3647
580F121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 878 1.59 1391 925 1.75 1534 970 1.91 1676 1014 2.07 1817 1055 2.23 1958 3100 888 1.68 1475 935 1.85 1623 979 2.02 1769 1022 2.18 1916 1063 2.35 2062 3200 898 1.78 1563 944 1.95 1715 988 2.13 1867 1031 2.30 2018 1072 2.47 2169 3300 909 1.88 1654 954 2.06 1811 998 2.24 1968 1040 2.42 2124 1080 2.60 2280 3400 919 1.99 1749 964 2.18 1911 1007 2.36 2073 1049 2.55 2234 1089 2.73 2395 3500 930 2.11 1848 975 2.30 2015 1017 2.49 2182 1058 2.68 2348 1098 2.86 2514 3600 941 2.22 1951 985 2.42 2123 1027 2.61 2295 1068 2.81 2466 1107 3.00 2637 3700 952 2.35 2058 996 2.55 2236 1038 2.75 2412 1078 2.95 2588 1117 3.15 2764 3800 964 2.47 2170 1007 2.68 2352 1048 2.89 2534 1088 3.09 2715 1126 3.30 2895 3900 976 2.60 2286 1018 2.82 2473 1059 3.03 2660 1098 3.24 2846 1136 3.45 3031 4000 987 2.74 2407 1029 2.96 2598 1069 3.18 2790 1108 3.40 2981 1146 3.61 3171 4100 999 2.88 2532 1041 3.11 2729 1080 3.33 2925 1119 3.56 3121 1156 3.78 3316 4200 1012 3.03 2662 1052 3.26 2863 1092 3.49 3065 1130 3.72 3266 1167 3.95 3466 4300 1024 3.19 2796 1064 3.42 3003 1103 3.66 3210 1141 3.89 3415 1177 4.13 3621 4400 1036 3.35 2937 1076 3.59 3148 1114 3.83 3359 1152 4.07 3570 1188 4.31 3781 4500 1049 3.51 3082 1088 3.76 3298 1126 4.00 3514 1163 4.25 3730 1199 4.50 3945 4600 1062 3.68 3232 1100 3.94 3454 1138 4.19 3675 1174 4.44 3895 1210 4.69 4116 4700 1075 3.86 3387 1113 4.12 3614 1150 4.38 3840 1186 4.63 4065 1221 4.89 4291 4800 1088 4.04 3549 1125 4.31 3780 1162 4.57 4011 1198 4.83 4241 — — — 4900 1101 4.23 3716 1138 4.50 3951 1174 4.77 4188 — 5000 1114 4.43 3888 1151 4.70 4129 1187 4.98 4370 —
Refer to page 74 for general Fan Performance Data notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 — — — 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 — — — 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 — 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 — 5100 961 3.29 3068 1007 3.59 3345 — 5200 978 3.48 3241 — 5300 995 3.67 3420 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 — — — 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 — — — 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 — 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 — 4200 1066 3.22 3004 1112 3.50 3264 — 4300 1078 3.38 3148 1123 3.66 3413 — 4400 1090 3.54 3297 — 4500 1103 3.70 3451 — 4600 — 4700 — 4800 — 4900 — 5000 — 5100 — 5200 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 1084 3.75 3500 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 1098 3.93 3668 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 1067 3.82 3558 1111 4.12 3841 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 1082 4.00 3733 1125 4.31 4021 5100 961 3.29 3068 1007 3.59 3345 1053 3.89 3627 1096 4.20 3915 1139 4.51 4208 5200 978 3.48 3241 1024 3.78 3523 1068 4.09 3811 1111 4.40 4103 1153 4.72 4400 5300 995 3.67 3420 1040 3.98 3707 1084 4.29 4000 1126 4.61 4298 1168 4.93 4600 5400 1012 3.87 3606 1056 4.18 3899 1099 4.50 4196 1141 4.82 4499 1182 5.15 4806 5500 1029 4.07 3799 1073 4.39 4097 1115 4.72 4400 1156 5.05 4707 — — — 5600 1046 4.29 3999 1089 4.61 4302 1131 4.94 4610 — 5700 1063 4.51 4207 1105 4.84 4515 1146 5.18 4827 — 5800 1080 4.74 4420 1122 5.08 4734 — 5900 1098 4.98 4642 — 6000 1115 5.22 4872 — 6100 — 6200 — 6300 —
580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 1243 4.37 4077 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 1210 4.24 3958 1252 4.54 4238 4400 1090 3.54 3297 1135 3.82 3566 1179 4.12 3841 1221 4.42 4121 1262 4.72 4405 4500 1103 3.70 3451 1147 4.00 3726 1190 4.29 4005 1232 4.60 4289 1273 4.91 4578 4600 1115 3.87 3612 1159 4.17 3891 1201 4.48 4175 1243 4.79 4464 1283 5.10 4757 4700 1128 4.05 3778 1171 4.36 4062 1213 4.67 4350 1254 4.98 4644 — — — 4800 1141 4.24 3951 1183 4.55 4239 1225 4.86 4532 1265 5.18 4830 — — — 4900 1154 4.43 4130 1196 4.74 4422 1237 5.06 4720 — 5000 1167 4.63 4314 1209 4.95 4611 — 5100 1181 4.83 4505 1221 5.16 4808 — 5200 1194 5.04 4703 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 900 0.54 0.21 253 0.57 0.23 277 0.55 0.26 307 0.60 0.31 363 1000 0.49 0.23 270 0.51 0.25 292 0.52 0.27 321 0.53 0.32 374 1100 0.43 0.24 287 0.45 0.26 307 0.46 0.28 335 0.49 0.33 385 1200 0.39 0.26 304 0.40 0.27 323 0.38 0.29 349 0.43 0.34 397 1300 0.33 0.27 321 0.35 0.29 338 0.35 0.31 364 0.36 0.34 408 1400 0.26 0.29 338 0.28 0.30 354 0.29 0.32 378 — — — 1500 0.21 0.30 355 0.23 0.31 369 0.24 0.33 392 — — —
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
580F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 — — — 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 — 1400 1246 0.99 980 1315 1.12 1111 — 1500 1274 1.09 1083 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
580F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 1448 1.30 1293 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 1414 1.28 1270 1473 1.41 1404 1400 1246 0.99 980 1315 1.12 1111 1379 1.25 1246 1440 1.39 1383 1499 1.53 1523 1500 1274 1.09 1083 1342 1.23 1221 1406 1.37 1362 1467 1.51 1505 1525 1.66 1652
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1200 0.75 0.41 458 0.81 0.45 506 0.87 0.51 572 0.92 0.56 632 1300 0.68 0.42 471 0.74 0.46 521 0.79 0.52 589 0.85 0.58 651 1400 0.60 0.45 503 0.66 0.49 556 0.71 0.54 616 0.77 0.60 681 1500 0.51 0.47 536 0.58 0.52 593 0.64 0.56 631 0.70 0.62 698 1600 0.42 0.49 557 0.49 0.54 616 0.56 0.58 654 0.63 0.64 723 1700 0.32 0.52 584 0.39 0.57 646 0.48 0.60 678 0.55 0.66 750 1800 0.21 0.54 610 0.29 0.60 674 0.41 0.62 698 0.48 0.68 772 1900 0.09 0.56 629 0.18 0.62 696 0.33 0.64 720 0.41 0.70 796 2000 — — — 0.06 0.65 731 0.26 0.66 744 0.33 0.73 823
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 — — — 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 — — — 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 —
580F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 — 1300 1113 0.92 915 1177 1.06 1058 — 1400 1138 1.01 1000 1201 1.15 1149 — 1500 1163 1.10 1092 — 1600 1189 1.20 1191 — 1700 — 1800 — 1900 — 2000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1177 1.25 1242 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 1205 1.37 1360 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 1165 1.31 1302 1234 1.49 1485
580F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740 1600 1189 1.20 1191 1252 1.36 1353 1310 1.53 1520 1365 1.70 1690 1418 1.87 1865 1700 1216 1.31 1299 1277 1.48 1468 1335 1.65 1640 1390 1.83 1817 1442 2.01 1998 1800 1242 1.42 1414 1303 1.60 1590 1361 1.78 1770 1415 1.96 1953 1467 2.15 2140 1900 1270 1.55 1538 1330 1.73 1721 1387 1.92 1908 1441 2.11 2098 1493 2.30 2292 2000 1297 1.68 1672 1357 1.87 1862 1414 2.07 2055 1467 2.26 2252 — — —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed Medium Speed High Speed 208V 230, 460, 575 V 208 V 230, 460, 575 V 208 V 230, 460, 575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1500 0.74 0.67 750 1.06 0.71 791 1.07 0.70 782 1.27 0.76 845 1.26 0.79 875 1.33 0.85 949 1600 0.54 0.70 780 0.90 0.74 824 0.92 0.74 821 1.13 0.79 883 1.14 0.82 913 1.22 0.89 988 1700 0.34 0.73 810 0.75 0.77 857 0.77 0.77 861 1.00 0.83 921 1.01 0.85 950 1.11 0.92 1027 1800 0.14 0.75 839 0.59 0.80 891 0.62 0.81 900 0.87 0.86 959 0.89 0.88 988 1.00 0.96 1066 1900 — — — 0.44 0.83 924 0.47 0.84 940 0.74 0.90 997 0.77 0.92 1025 0.89 0.99 1105 2000 — — — 0.28 0.86 957 0.32 0.88 979 0.61 0.93 1035 0.64 0.95 1063 0.78 1.03 1144 2100 — — — 0.13 0.89 990 0.17 0.91 1018 0.48 0.96 1073 0.51 0.99 1101 0.67 1.06 1183 2200 — 0.02 0.95 1058 0.35 1.00 1111 0.39 1.02 1138 0.56 1.10 1222 2300 — 0.22 1.03 1149 0.26 1.06 1176 0.45 1.13 1261 2400 — 0.09 1.07 1187 0.14 1.09 1213 0.34 1.17 1300 2500 — 0.23 1.20 1340
LEGEND See page 74 for general fan performance notes.
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
580F060 (5 TONS) — THREE-PHASE, ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 — — — 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 — — — 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 — 2200 1424 2.03 1801 1484 2.25 1997 — 2300 1455 2.19 1946 — 2400 1487 2.37 2103 — 2500 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require a field-supplied drive.

580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 1570 2.48 2200 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 1596 2.63 2333 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 1568 2.55 2262 1622 2.79 2475 2200 1424 2.03 1801 1484 2.25 1997 1541 2.48 2200 1596 2.71 2411 — — — 2300 1455 2.19 1946 1514 2.42 2147 1571 2.65 2355 1625 2.89 2570 — — — 2400 1487 2.37 2103 1545 2.60 2308 1601 2.84 2521 — 2500 1520 2.56 2269 1577 2.79 2480 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied drive.

580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 — 2800 1341 2.14 1899 1404 2.31 2048 — 2900 1384 2.36 2099 — 3000 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 — — — 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 — 2400 1500 2.17 1928 1559 2.35 2083 — 2500 1533 2.36 2098 — 2600 — 2700 — 2800 — 2900 — 3000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 1485 2.43 2158 1544 2.61 2315 2800 1341 2.14 1899 1404 2.31 2048 1464 2.48 2201 1523 2.66 2358 1580 2.84 2520 2900 1384 2.36 2099 1445 2.54 2253 1504 2.71 2410 1561 2.90 2572 — — — 3000 1428 2.60 2313 1487 2.78 2471 —
580F072,073 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 1673 2.53 2246 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 1644 2.52 2239 1699 2.71 2406 2400 1500 2.17 1928 1559 2.35 2083 1616 2.53 2243 1672 2.71 2408 1726 2.90 2579 2500 1533 2.36 2098 1591 2.54 2257 1647 2.73 2421 — 2600 1566 2.57 2281 1623 2.75 2444 — 2700 1600 2.79 2477 — 2800 — 2900 — 3000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied drive.

580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 —
580F090,091 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 — 2300 842 1.84 1719 895 2.17 2019 — 2400 851 1.92 1793 903 2.25 2097 — 2500 860 2.01 1873 911 2.34 2180 — 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field-supplied drive.

580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 —
580F090,091 (71/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 — 2300 842 1.84 1719 895 2.17 2019 — 2400 851 1.92 1793 903 2.25 2097 — 2500 860 2.01 1873 911 2.34 2180 — 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962
580F090,091 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 941 2.46 2297 988 2.82 2629 1033 3.19 2976 2300 842 1.84 1719 895 2.17 2019 944 2.51 2336 992 2.86 2669 1037 3.24 3018 2400 851 1.92 1793 903 2.25 2097 952 2.59 2416 999 2.95 2752 1043 3.33 3104 2500 860 2.01 1873 911 2.34 2180 960 2.68 2502 1006 3.05 2842 1051 3.43 3196 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 — — — 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 — — — 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 — — — 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 — 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 — 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 — 3400 954 3.02 2816 1000 3.39 3159 — 3500 966 3.16 2950 1011 3.54 3297 — 3600 978 3.31 3088 1022 3.69 3442 — 3700 990 3.47 3233 — 3750 996 3.55 3308 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 — 3800 753 1.91 1783 808 2.22 2074 — 3900 770 2.05 1912 824 2.37 2209 — 4000 787 2.20 2047 — 4100 804 2.35 2189 — 4200 — 4250 —
580F103 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.

580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962 3800 753 1.91 1783 808 2.22 2074 861 2.55 2380 910 2.90 2701 957 3.26 3036 3900 770 2.05 1912 824 2.37 2209 875 2.70 2522 924 3.05 2848 970 3.42 3189 4000 787 2.20 2047 840 2.52 2351 890 2.86 2669 938 3.22 3002 984 3.59 3348 4100 804 2.35 2189 856 2.68 2499 905 3.03 2824 952 3.39 3162 — — — 4200 821 2.51 2338 872 2.85 2655 920 3.20 2986 967 3.57 3331 — — — 4250 829 2.59 2415 880 2.93 2735 928 3.29 3069 974 3.66 3417 — — —
580F103 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 — — — 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 — — — 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 — — — 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 — 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 — 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 — 3400 954 3.02 2816 1000 3.39 3159 — 3500 966 3.16 2950 1011 3.54 3297 — 3600 978 3.31 3088 1022 3.69 3442 — 3700 990 3.47 3233 — 3750 996 3.55 3308 — 3800 1002 3.63 3385 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F120,121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 — — — 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 — 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 — 4400 750 2.01 1764 806 2.23 1958 — 4500 764 2.14 1879 819 2.37 2077 — 4600 779 2.28 1998 — 4700 — 4800 — 4900 — 5000 —
580F120,121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 — — — 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 — — — 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 — — — 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 — 3500 911 2.01 1760 959 2.21 1937 — 3600 920 2.11 1854 967 2.32 2033 — 3700 929 2.22 1951 — 3800 939 2.34 2053 — 3900 — 4000 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

580F120,121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 — — — 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 — — — 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 — 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 — 4800 808 2.56 2251 860 2.81 2462 — 4900 822 2.72 2385 — 5000 837 2.88 2525 —
580F120,121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 — — — 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 — — — 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 — 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 — 4000 959 2.59 2269 1004 2.81 2462 — 4100 969 2.72 2384 — 4200 979 2.85 2504 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field-supplied drive.

580F120,121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 955 2.91 2553 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 966 3.06 2684 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 932 2.97 2611 978 3.21 2820 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 944 3.13 2747 989 3.37 2960 4800 808 2.56 2251 860 2.81 2462 909 3.05 2674 956 3.29 2889 1001 3.54 3106 4900 822 2.72 2385 873 2.96 2601 922 3.21 2818 968 3.46 3037 1013 3.71 3258 5000 837 2.88 2525 887 3.13 2745 935 3.38 2966 981 3.63 3189 1024 3.89 3414
580F120,121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 1098 2.96 2600 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 1106 3.09 2710 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 1073 2.99 2625 1114 3.22 2824 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 1081 3.12 2741 1122 3.35 2943 4000 959 2.59 2269 1004 2.81 2462 1048 3.03 2660 1090 3.26 2861 1130 3.49 3067 4100 969 2.72 2384 1014 2.94 2581 1057 3.17 2782 1098 3.40 2987 1139 3.64 3195 4200 979 2.85 2504 1024 3.08 2705 1066 3.31 2909 1107 3.55 3117 1147 3.79 3329 4300 990 3.00 2629 1034 3.23 2833 1076 3.46 3040 1117 3.71 3252 1156 3.95 3467 4400 1000 3.14 2758 1044 3.38 2966 1085 3.62 3177 1126 3.87 3392 1165 4.11 3611 4500 1011 3.30 2892 1054 3.54 3104 1095 3.78 3319 1135 4.03 3537 1174 4.28 3759 4600 1022 3.45 3032 1064 3.70 3247 1105 3.95 3466 1145 4.20 3688 1183 4.46 3913 4700 1033 3.62 3176 1075 3.87 3395 1115 4.12 3618 1155 4.38 3843 1193 4.64 4072 4800 1044 3.79 3326 1085 4.04 3549 1126 4.30 3775 1164 4.56 4004 1202 4.83 4237 4900 1055 3.97 3482 1096 4.22 3708 1136 4.49 3938 1174 4.75 4171 1212 5.02 4406 5000 1066 4.15 3642 1107 4.41 3873 1146 4.68 4106 1184 4.95 4342 1221 5.22 4582
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 — — — 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 — — — 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 — 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 — 5300 912 3.13 2917 966 3.47 3233 — 5400 927 3.30 3073 980 3.64 3395 — 5500 943 3.47 3234 — 5600 958 3.65 3402 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
580F150,151 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 — — — 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 — 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 — 4300 1042 3.16 2951 1089 3.45 3218 — 4400 1053 3.31 3085 1100 3.60 3357 — 4500 1064 3.46 3224 — 4600 1075 3.61 3367 — 4700 — 4800 — 4900 — 5000 — 5100 — 5200 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 1062 3.78 3528 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 1074 3.95 3685 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 1039 3.80 3540 1086 4.13 3849 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 1052 3.97 3702 1099 4.31 4017 5300 912 3.13 2917 966 3.47 3233 1016 3.81 3551 1065 4.15 3870 1111 4.49 4191 5400 927 3.30 3073 980 3.64 3395 1030 3.99 3719 1078 4.34 4044 1123 4.69 4370 5500 943 3.47 3234 994 3.82 3563 1044 4.17 3892 1091 4.53 4223 1136 4.88 4555 5600 958 3.65 3402 1009 4.01 3736 1057 4.37 4071 1104 4.73 4408 1149 5.09 4746 5700 973 3.83 3575 1023 4.20 3915 1071 4.56 4256 1117 4.93 4599 — — — 5800 988 4.03 3754 1038 4.40 4100 1085 4.77 4447 1130 5.14 4796 — — — 5900 1004 4.22 3939 1052 4.60 4292 1099 4.98 4645 — 6000 1019 4.43 4131 1067 4.81 4489 1113 5.20 4848 — 6100 1034 4.64 4329 1082 5.03 4693 — 6200 1050 4.86 4533 — 6300 1065 5.09 4744 —
580F150,151 (121/2 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 1221 4.32 4031 4400 1053 3.31 3085 1100 3.60 3357 1145 3.90 3632 1188 4.19 3909 1230 4.49 4187 4500 1064 3.46 3224 1110 3.76 3502 1155 4.06 3782 1198 4.36 4064 1239 4.66 4348 4600 1075 3.61 3367 1121 3.91 3650 1165 4.22 3937 1208 4.53 4224 1249 4.84 4514 4700 1086 3.77 3515 1131 4.08 3805 1175 4.39 4096 1217 4.71 4389 1258 5.02 4684 4800 1097 3.93 3668 1142 4.25 3963 1186 4.57 4260 1228 4.89 4559 1268 5.21 4860 4900 1109 4.10 3826 1153 4.43 4128 1196 4.75 4430 1238 5.08 4734 — — — 5000 1120 4.28 3990 1164 4.61 4296 1207 4.94 4604 — 5100 1132 4.46 4159 1175 4.79 4471 1218 5.13 4784 — 5200 1144 4.65 4333 1187 4.99 4651 — 5300 1155 4.84 4512 1198 5.19 4836 — 5400 1167 5.04 4697 — 5500 1179 5.24 4889 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES 1. Values include losses for filters, unit casing, and wet coils. See this page for accessory/FIOP static pressure information. 2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 79 for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate. (Belt drive units only.)
SOUND RATING 60 Hz (dB)
A-WEIGHTED
OCTAVE BANDS
UNIT 580F
(dB)
63 125 250 500 1000 2000 4000 8000
036-072 81 80.5 56.8 75.8 72.4 72.9 74.8 75.4 71.3 69.1 073 80 80.0 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0 090 87 86.4 83.2 87.4 83.5 82.8 83.0 77.7 71.8 67.0 091, 103 82 82.0 62.2 69.3 71.5 74.7 76.2 72.9 68.7 61.5 120 88 87.6 97.6 90.4 85.7 84.8 83.9 77.5 71.3 65.8 121 84 84.0 64.6 71.7 73.3 76.9 77.6 73.7 70.6 63.7 150 87 86.4 83.7 87.2 83.4 82.8 83.0 77.7 71.8 67.0 151 86 86.0 63.7 69.9 72.5 78.2 81.1 77.3 73.3 66.8
COMPONENT CFM 1250 1500 1750 2000 2250 2500 2750 3000 Vertical EconoMi$er IV and EconoMi$er2 0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255 Horizontal EconoMi$er IV and EconoMi$er2 — — 0.1 0.125 0.15 0.18 0.225 0.275
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
FIOP — Factory-Installed Option
COMPONENT CFM 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250 Vertical EconoMi$er IV and EconoMi$er2 0.06 0.075 0.09 0.115 0.13 0.15 0.17 0.195 0.22 0.25 0.285 0.325 0.36 —
Horizontal EconoMi$er IV and EconoMi$er2 — 0.1 0.125 0.15 0.18 0.21 0.25 0.275 0.3 0.34 0.388 — — —
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in con- junction with the Fan Performance tables to determine blower rpm and watts.
FIOP — Factory-Installed Option

UNIT 580F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 036† 1045 1009 973 937 901 865 829 793 757 721 685 — — 036** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048† 1175 1135 1094 1054 1013 973 932 892 851 811 770 — — 048** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060† 1300 1266 1233 1200 1166 1133 1100 1066 1033 1000 966 933 900 060** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 — — 072,073†† 1460 1421 1382 1343 1304 1265 1226 1187 1148 1109 1070 — — 072,073** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1399 1300 — —
*Approximate fan rpm shown. †Indicates alternate motor and drive package.
**Indicates high-static motor and drive package. ††Indicates standard motor and drive package.
UNIT 580F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 090,091† 840 815 790 765 740 715 690 665 635 615 590 — — 090,091** 935 910 885 860 835 810 785 760 735 710 685 — — 090,091†† 1080 1025 1007 988 970 952 933 915 897 878 860 — — 103† 935 910 885 860 835 810 785 760 735 710 685 — — 103†† 1080 1025 1007 988 970 952 933 915 897 878 860 — — 120,121† 935 910 885 860 835 810 785 760 735 710 685 — — 120,121*** 1085 1060 1035 1010 985 960 935 910 885 860 835 — — 120,121†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830 150,151† 1080 1060 1035 1015 990 970 950 925 905 880 860 — — 150,151*** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
*Approximate fan rpm shown. †Indicates standard motor and drive package. **Indicates alternate drive package only.
††Indicates high-static motor and drive package. ***Indicates alternate motor and drive package.
ALTITUDE COMPENSATION* — 580F090-151
STANDARD UNITS


Orifice Size† 0-2,000 31 41 30 38 2,000 32 42 30 39 3,000 32 42 31 40 4,000 32 42 32 41 5,000 33 43 33 42 6,000 34 43 34 43 7,000 35 44 35 43 8,000 36 44 36 44 9,000 37 45 37 44 10,000 38 46 38 45 11,000 39 47 39 45 12,000 40 47 40 46 13,000 41 48 41 47 14,000 42 48 42 47
Orifice Size† 0-2,000 33 43 30 37 2,000 36 44 31 39 3,000 36 45 31 40 4,000 37 45 32 41 5,000 38 46 32 42 6,000 40 47 34 43 7,000 41 48 35 43 8,000 42 49 36 44 9,000 43 50 37 45 10,000 44 50 39 46 11,000 45 51 41 47 12,000 46 52 42 48 13,000 47 52 43 49 14,000 48 53 44 50
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your local Bryant distributor.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your local Bryant distributor.
ALTITUDE COMPENSATION* — 580F036-073
LOW NOx UNITS

(Btu/ft3) 0-2,000 1,100 2,001-3,000 1,050 3,001-4,000 1,000 4,001-5,000 950 5,001-6,000 900

120,000 BTUH NOMINAL INPUT Natural Gas Orifice Size† Natural Gas Orifice Size 0-2,000 38 32 2,000 40 33 3,000 41 35 4,000 42 36 5,000 43 37 6,000 43 38 7,000 44 39 8,000 45 41 9,000 46 42 10,000 47 43 11,000 48 44 12,000 49 44 13,000 50 46 14,000 51 47
*Derating of the unit is not required unless the heating value of the gas exceeds the val- ues listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code. IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor.

7.5-12.5 Ton
0 0.1 0.2 0.3 0.4 0.5
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
7 1/2 - 12 1/2 Ton
0.05 0.15 0.25
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
3-6 Ton 7 1/2-12 1/2 Ton
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
Vertical EconoMi$er IV and EconoMi$er2
Performance Data (580F036-151)
POWER EXHAUST OPTIONS
VERTICAL — MOUNTED IN ECONOMIZER HOOD POWER EXHAUST
NO. FANS CRPWREXH030A01 Power Exhaust System (208/230-1-60) 036-073 0.23 2 CRPWREXH021A01 Power Exhaust System (460-3-60) 036-073 0.24 2 CRPWREXH022A01 Power Exhaust System (208/230-1-60) 090-151 0.47 2 CRPWREXH023A01 Power Exhaust System (460-3-60) 090-151 0.37 2
POWER OUTPUT
USAGE
(Hp per fan)
HORIZONTAL — MOUNTED IN RETURN DUCTWORK POWER EXHAUST
NO. FANS CRPWREXH028A01 Horizontal Power Exhaust (208/230-1-60) All 0.48 1 CRPWREXH029A01 Horizontal Power Exhaust (460-3-60) All 0.48 1
POWER OUTPUT
USAGE
(Hp per fan)

0 0.1 0.2 0.3 0.4 0.5
STATIC PRESSURE (in. wg)
Flow in cubic feet per minute (cfm)
7 1/2 - 12 1/2 Ton
0.05" 0.15" 0.25"
Static Pressure (in. wg)
Flow in cubic feet per minute (cfm)
7 1/2 - 12 1/2 Ton
0.1" 0.2" 0.3" 0.4" 0.5"
Static Pressure (in. wg)
Horizontal EconoMi$er IV and EconoMi$er2
Performance Data (580F036-151)
OPTIONAL POWER EXHAUST
EVAPORATOR-FAN MOTOR EFFICIENCY
POWER REQUIREMENTS
UNIT 580F MOTOR EFFICIENCY (%) 036,048 75 060 74/84* 072, 073 84 090-121 80 150, 151 87
MOCP
UNIT SIZE
230 V (2 Fans Running)
230 VAC 460 VAC 575 VAC
580F036-073 1.40 Amps at 60 Hz 15.0 amps 15.0 amps 15.0 amps 580F090-151 3.04 Amps at 60 Hz
*Single phase/three-phase. NOTE: The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance requirements. Therefore, the indoor-fan motors for these units are exempt from these requirements.
MOCP — Maximum Overcurrent Protection

UNIT 580F EVAPORATOR-FAN
UNIT VOLTAGE
MAXIMUM ACCEPTABLE
MAXIMUM ACCEPTABLE
MAXIMUM AMP DRAW
MOTOR
CONTINUOUS BHP*
OPERATING WATTS
208/230 0.34 440 2.8 460 1.3 575 1.3
208/230 1.20 1000 4.9 460 2.1 575 2.1
208/230 2.40 2120 6.0 460 3.0 575 3.0
208/230 0.75 850 3.5 460 1.8 575 1.8
208/230 1.20 1000 4.9 460 2.1 575 2.1
208/230 2.40 2120 6.0 460 3.0 575 3.0
208/230 1.20 1340 5.9 460 3.2 575 3.2
208/230 1.30/2.40† 2120 6.6/5.2† 460 2.6 575 3.0
208/230 2.90 2562 8.6 460 3.9 575 3.9
208/230 2.40 2120 5.2 460 3.0 575 3.0
208/230 2.90 2562 8.6 460 3.9 575 3.9
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 2.90 2615 8.6 460 3.9 575 3.9
208/230 5.25 4400 17.3 460 8.5 575 8.5
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 5.25 4400 17.3 460 8.5 575 8.5
LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase. NOTE: High-static motor not available on single-phase units.

580F NOMINAL
IFM TYPE
CONV OUTLET
FAN MOTOR POWER SUPPLY MINIMUM UNIT DISCONNECT SIZE* Min Max Qty RLA LRA Qty FLA FLA MCA MOCP† FLA LRA
RANGE COMPRESSOR (each) OFM (each) IFM FLA
STD NO
17.7 25 17 85 YES 23.7 25 23 90
ALT NO 4.9 19.1 25 19 90 YES 25.1 30 25 95
187 254 1 10.2 75 1 1.4
HIGH NO 5.2 19.4 25 19 109 YES 25.4 30 25 114
7.6 15 7 44 YES 10.3 15 10 47
ALT NO 2.1 8.4 15 8 48 YES 11.1 15 11 50
414 508 1 4.4 40 1 0.8
HIGH NO 2.6 8.9 15 9 57 YES 11.6 15 11 59
7.1 15 7 37 YES 9.3 15 9 39
518 632 1 3.7 31 1 0.6 1.9 0.3
HIGH NO 2.0 7.2 15 8 44 YES 9.4 15 10 45
24.2 30 23 101 YES 30.2 35 29 106
ALT NO 4.9 25.6 30 25 105 YES 31.6 35 30 110
187 254 1 15.4 90 1 1.4
HIGH NO 5.2 25.9 30 25 124 YES 31.9 35 31 129
13.0 20 13 51 YES 15.7 20 15 53
ALT NO 2.1 13.3 20 13 53 YES 16.0 20 15 55
414 508 1 8.3 45 1 0.8
HIGH NO 2.6 13.8 20 13 62 YES 16.5 20 16 64
10.5 15 10 42 YES 12.7 15 12 43
518 632 1 6.4 36 1 0.6 1.9 0.3
HIGH NO 2.0 10.6 15 10 49 YES 12.8 15 12 50
Determine percent of voltage imbalance.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
% Voltage Imbalance = 100 x 7 457
= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
= 100 x max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
MOCP (separate power source
APPLICATION
MCA (230 V)
MCA (460 V)
MCA (575 V)
PART NO.
only) CRPWREXH030A01 036-073* 1.6 N/A 0.64 15 CRPWREXH021A01 036-073 N/A 0.68 N/A 15 CRPWREXH022A01 090-151* 3.4 N/A 1.32 15 CRPWREXH023A01 090-151 N/A 1.4 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
Average Voltage = 452 + 464 + 455 3
= 457 Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.
*Single or three phase.

580F NOMINAL
IFM TYPE
CONV OUTLET
FAN MOTOR POWER SUPPL MINIMUM UNIT DISCONNECT SIZE* Min Max Qty RLA LRA Qty FLA FLA MCA MOCP† FLA LRA
RANGE COMPRESSOR (each) OFM (each) IFM FLA
STD NO
27.3 35 27 128 YES 33.3 40 32 133
ALT NO 5.2 26.6 35 26 148 YES 32.6 35 32 153
187 254 1 16 114 1 1.4
HIGH NO 7.5 28.9 35 29 174 YES 34.9 40 34 179
13.2 20 13 71 YES 15.9 20 15 74
ALT NO 2.6 12.7 15 12 81 YES 15.4 20 15 84
414 508 1 7.4 64 1 0.8
HIGH NO 3.4 13.5 20 13 93 YES 16.2 20 16 96
10.4 15 11 65 YES 12.6 15 12 66
518 632 1 6.2 52 1 0.6 1.9 0.3
HIGH NO 2.0 11.2 15 11 74 YES 2.0 13.5 15 13 74
32.4 40 31 180 YES 38.4 45 37 184
187 254 1 20.6 146 1 1.4 5.2 0.6
HIGH NO 7.5 34.7 40 34 205 YES 40.7 45 39 210
15.3 20 15 90 YES 18.0 20 17 92
414 508 1 9.5 73 1 0.9 2.6 0.3
HIGH NO 3.4 16.1 20 16 103 YES 18.8 25 18 105
12.1 15 12 71 YES 13.3 20 13 72
518 632 1 7.6 58.4 1 0.6 2.0 0.3
HIGH NO 2.8 12.9 15 13 80 YES 14.1 20 15 81
32.4 40 31 180 YES 38.4 45 37 184
187 254 1 20.6 146 1 1.4 5.2 0.6
HIGH NO 7.5 34.7 40 34 205 YES 40.7 45 39 210
15.4 20 15 90 YES 18.0 20 17 92
414 508 1 9.5 73 1 0.9 2.6 0.3
HIGH NO 3.4 16.2 20 16 103 YES 18.8 25 18 105
12.3 15 13 75 YES 14.4 20 15 77
518 632 1 7.6 62 1 0.6 1.9 0.3
HIGH NO 2.0 13.1 20 14 84 YES 15.3 20 16 86
40.1 45 42 229 YES 46.1 50 48 233
ALT NO 5.8 40.1 45 42 229 YES 46.1 50 48 233
187 254 2 14 91 2 1.4
HIGH NO 10.6 44.9 50 48 273 YES 50.9 60 53 273
18.4 20 19 108 YES 24.4 25 22 110
ALT NO 2.6 18.4 20 19 108 YES 24.4 25 22 110
090 (71/2 Ton)
414 508 2 6.4 42 2 0.7
HIGH NO 4.8 20.6 25 22 130 YES 23.3 30 24 132
14.9 20 16 97 YES 20.9 25 18 99
ALT NO 2.0 14.9 20 16 97 YES 20.9 25 18 99
518 632 2 5.2 39 2 0.6
HIGH NO 2.8 16.7 20 18 114 YES 19.4 25 20 117
40.1 45 42 229 YES 44.9 50 48 234
ALT NO 5.8 40.1 45 42 229 YES 44.9 50 48 234
187 254 2 14 91 2 1.4
HIGH NO 10.6 44.9 50 48 273 YES 49.7 60 53 277
18.4 20 19 108 YES 20.6 25 22 110
ALT NO 2.6 18.4 20 19 108 YES 20.6 25 22 110
091 (71/2 Ton)
414 508 2 6.4 42 2 0.7
HIGH NO 4.8 20.6 25 22 130 YES 22.8 25 24 132
14.9 20 16 97 YES 16.6 20 18 99
ALT NO 2.0 14.9 20 16 97 YES 16.6 20 18 99
518 632 2 5.2 39 2 0.6
HIGH NO 2.8 16.7 20 18 114 YES 18.4 20 20 116

580F NOMINAL
IFM TYPE
CONV OUTLET
FAN MOTOR POWER SUPPLY MINIMUM UNIT DISCONNECT SIZE* Min Max Qty RLA LRA Qty FLA FLA MCA MOCP† FLA LRA
RANGE COMPRESSOR (each) OFM (each) IFM FLA
208/230-3-60 STD NO
44.3 50 46 272 YES 49.1 60 52 277
187 254 2 17.3 120.0 2 1.4 5.8 0.6
HIGH NO 10.6 49.1 60 52 316 YES 53.9 60 57 320
21.0 25 22 149 YES 23.2 30 24 151
414 508 2 7.9 70.0 2 0.7 2.6 0.3
103 (81/2 Ton)
HIGH NO 4.8 23.2 30 24 171 YES 25.4 30 27 173
16.7 20 17 109 YES 18.4 25 19 111
518 632 2 5.5 50.0 2 0.6 2.0 0.3
HIGH NO 2.8 18.5 25 19 126 YES 20.2 25 21 128
44.2 50 46 307 YES 50.2 60 52 311
ALT NO 7.5 45.9 50 48 326 YES 51.9 60 54 330
187 254 2 15.8 130 2 1.4
HIGH NO 15.0 53.4 60 57 374 YES 59.4 70 62 378
21.8 25 23 152 YES 27.8 30 25 154
ALT NO 3.4 22.6 25 24 191 YES 25.3 30 26 193
414 508 2 7.9 64 2 0.7
HIGH NO 7.4 26.6 30 28 185 YES 29.3 35 31 187
18.1 25 19 123 YES 24.1 25 21 109
ALT NO 2.0 18.7 25 20 155 YES 24.7 25 22 141
518 632 2 6.6 52 2 0.6
HIGH NO 2.8 21.9 30 23 150 YES 24.6 30 25 136
44.6 50 46 307 YES 49.4 60 52 312
ALT NO 7.5 46.3 60 48 326 YES 51.1 60 54 331
187 254 2 15.8 130 2 1.4
HIGH NO 15.0 53.8 60 57 374 YES 58.6 70 62 379
22.0 25 23 152 YES 24.2 30 25 154
ALT NO 3.4 22.8 25 24 191 YES 25.0 30 26 193
414 508 2 7.9 64 2 0.7
HIGH NO 7.4 26.8 30 28 185 YES 29.0 35 30 187
18.1 20 19 123 YES 19.8 25 21 125
ALT NO 2.8 18.7 20 20 150 YES 20.4 25 22 156
518 632 2 6.6 52 2 0.6
HIGH NO 3.3 21.9 25 23 155 YES 23.6 25 25 151
Determine percent of voltage imbalance.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
% Voltage Imbalance = 100 x 7 457
= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
= 100 x max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v
only) CRPWREXH030A01 036-073* 1.6 N/A 0.64 15 CRPWREXH021A01 036-073 N/A 0.68 N/A 15 CRPWREXH022A01 090-151* 3.4 N/A 1.32 15 CRPWREXH023A01 090-151 N/A 1.4 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
Average Voltage = 452 + 464 + 455 3
= 457 Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.
*Single or three phase.

580F NOMINAL
IFM TYPE
CONV OUTLET
FAN MOTOR POWER SUPPLY MINIMUM UNIT DISCONNECT SIZE* Min Max Qty RLA LRA Qty FLA FLA MCA MOCP† FLA LRA
RANGE COMPRESSOR (each) OFM (each) IFM FLA
208/230-3-60 STD NO
65.2 80 68 383 YES 71.2 80 74 387
187 254 2 23 146 2 1.4 10.6 0.6
HIGH NO 15.0 69.6 80 73 406 YES 75.6 80 79 410
29.6 35 31 192 YES 35.6 40 34 194
414 508 2 10.4 73 2 0.7 4.8 0.3
150 (121/2 Ton)
HIGH NO 7.4 32.2 35 34 203 YES 34.9 40 37 205
23.6 30 25 154 YES 29.6 35 27 156
518 632 2 8.3 58.4 2 0.6 2.0 0.3
HIGH NO 2.8 25.7 30 27 163 YES 31.7 35 29 165
56.2 70 59 359 YES 61.0 70 65 364
187 254 2 19 156 2 1.4 10.6 0.6
HIGH NO 15.0 60.6 70 64 378 YES 65.4 80 70 383
26.5 30 28 174 YES 28.7 35 30 176
414 508 2 9 75 2 0.7 4.8 0.3
151 (121/2 Ton)
HIGH NO 7.4 29.1 35 31 213 YES 31.3 35 33 215
21.6 25 23 127 YES 23.3 30 25 129
518 632 2 7.4 54 2 0.6 3.3 0.3
HIGH NO 5.6 23.7 25 25 159 YES 5.6 25.4 30 27 160
Determine percent of voltage imbalance.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
% Voltage Imbalance = 100 x 7 457
= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
= 100 x max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.
MOCP (separate power source
AB = 452 v BC = 464 v AC = 455 v
APPLICATION
MCA (230 V)
MCA (460 V)
MCA (575 V)
PART NO.
only) CRPWREXH030A01 036-073* 1.6 N/A 0.64 15 CRPWREXH021A01 036-073 N/A 0.68 N/A 15 CRPWREXH022A01 090-151* 3.4 N/A 1.32 15 CRPWREXH023A01 090-151 N/A 1.4 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
Average Voltage = 452 + 464 + 455 3
= 457 Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.
*Single or three phase.
V-PH-Hz · average voltage · = 1371 3

(580F090, 460-3-60 Shown)

AMPS
CB 24 V POTTER & BRUMFIELD 3.2 W2BX-1024-3.2
CB1 (150,151 Std) 460-3-60 Heinemann Airpax 8.5 CF3-Z228-41 219-3-2600-486
C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CLO — Compressor Lockout COMP — Compressor Motor EQUIP — Equipment FPT — Freeze Protection Thermostat GND — Ground HPS — High-Pressure Switch HS — Hall Effect Sensor I — Ignitor IDM — Induced Draft Motor IFC — Indoor Fan Contactor IFM — Indoor (Evaporator) Fan Motor IFMOVL — Indoor Fan Motor Overload Switch IGC — Integrated Gas Unit Controller LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve OFC — Outdoor Fan Contactor OFM — Outdoor Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal RAT — Return Air Temperature Sensor RS — Rollout Switch SAT — Mixed-Air Temperature Sensor SEN — Sensor TRAN — Transformer Field Splice
Splice (Marked) Factory Wiring
Accessory or Optional Wiring To indicate common potential only. Not to represent wiring.

LEGEND IAQ — Indoor Air Quality LA — Low Ambient Lockout Device POT — Potentiometer OAT — Outdoor-Air Temperature RAT — Return-Air Temperature
BLACK
BLUE
500 OHM RESISTOR
VIOLET
NOTE 1
PINK
RUN
RED
NOTE 2
50HJ540573 ACTUATOR ASSEMBLY
YELLOW
OPTIONAL CO SENSOR 4 - 20 mA
DIRECT DRIVE
WHITE
ACTUATOR
ECONOMISER2 PLUG
a48-7910 · - + · a48-8209

RED YEL BLU GRA
LINE SIDE
H1 H3
H2 H4
21 BLU
GRA
RED
TRAN4
YEL
X4 X2 X3 X1
RED
YEL
BLU
GRA
H3 H2
208-230-1 ONLY
SECONDARY
H1
H4
TRAN4
GRA RED
X4 X2 X3 X1
H1
H2
WHT BLK
SECONDARY
120V GROUND FAULT
TRAN4
INTERRUPTER CONVENIENCE
OUTLET GFI - CO
X4 X2 X3 X1
GRN-YEL GRN-YEL
SECONDARY
TEST RESET SWITCH
WHT BLK FUSE
15 AMP
Convenience Outlet (Optional) — Sizes 580F036-151
UNIT DISCONNECT
FIELD
BLK
BLK
POWER
YEL
YEL
SUPPLY
BLU
BLU
TB
BLK
BLK
YEL
YEL
BLU
BLU
SINGLE POINT CONNECTION BOX
a48-7462 · a48-7463



UNIT SIZE 581B 036 048 060 072 NOMINAL CAPACITY 3 4 5 6 OPERATING WEIGHT (lb)
Unit 530 540 560 635 COMPRESSOR Scroll Quantity 1 Oil (oz) 42 53 50 60 REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Standard Unit 5-8 10-2 10- 0 12-8 Unit With Perfect Humidity Dehumidification Package 9-0 15-8 17-0 21-0 CONDENSER FAN Propeller Quantity...Diameter (in.) 1...22 Nominal Cfm 3500 3500 4100 4100 Motor Hp...Rpm 1/4...825 1/4...825 1/4...1100 1/4...1100 Watts Input (Total) 180 180 320 320 CONDENSER COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins Standard Unit
Rows...Fins/in. 1...17 2...17 2...17 2...17 Total Face Area (sq ft) 14.6 16.5 16.5 16.5 Unit with Perfect Humidity Dehumidification Package
Rows...Fins/in. 1...17 Total Face Area (sq ft) 3.9 EVAPORATOR COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device Rows...Fins/in. 2...15 2...15 4...15 4...15 Total Face Area (sq ft) 5.5 EVAPORATOR FAN Centrifugal Type, Belt Drive Quantity...Size (in.) 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 Nominal Cfm 1200 1600 2000 2400 Maximum Continuous Bhp Std 1.20 1.20 1.30/2.40* 2.40 Hi-Static 2.40 2.40 2.90 2.90 Motor Frame Size Std 48 48 48/56* 56 Hi-Static 56 Fan Rpm Range Std 680-1044 770-1185 1035-1460 1119-1585 Hi-Static 1075-1455 1075-1455 1300-1685 1300-1685 Motor Bearing Type Ball Maximum Fan Rpm 2100 Motor Pulley Pitch Diameter A/B (in.) Std 1.9/2.9 1.9/2.0 2.4/3.4 2.4/3.4 Hi-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/3.4 Nominal Motor Shaft Diameter (in.) Std 1/2 1/2 5/8 5/8 Hi-Static 5/8 5/8 5/8 7/8 Fan Pulley Pitch Diameter (in.) Std 4.5 4.0 4.0 3.7 Hi-Static 4.5 Belt — Type...Length (in.) Std 1...A...36 1...A...36 1 4...40 1...A...38 Hi-Static 1...A...39 1...A...39 1...A...40 1...A...40 Pulley Center Line Distance (in.) 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 Speed Change per Full Turn of
Std 65 70 75 95 Hi-Static 65 65 60 60 Movable Pulley Maximum Full
Movable Pulley Flange (rpm)
Std 5 5 6 5 Hi-Static 6 6 5 5 Factory Setting — Full Turns Open Std 3 Hi-Static 31/2 Factory Speed Setting (rpm) Std 826 936 1248 1305 Hi-Static 1233 1233 1396 1396 Fan Shaft Diameter at Pulley (in.) 5/8
Turns from Closed Position
||California compliant three-phase models. ***California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.
Bhp — Brake Horsepower
*Single phase/three phase. †Indicates automatic reset. **60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners. ††An LP kit is available as an accessory.

UNIT SIZE 581B 036 048 060 072 FURNACE SECTION
Rollout Switch Cutout Temp (F)† 195 Burner Orifice Diameter (in drill size)**
Natural Gas — Std 071/072.113...33 114/115.113...33 149/150 — .129...30 .129...30 .129...30 060N.102...38 .102...38 .102...38 — 090N.102...38 .102...38 .102...38 — 120N — .116...32 .116...32 — Liquid Propane — Alt†† 071/072.089...43 114115.089...43 149/150 — .102...38 .102...38 .102...38 Thermostat Heat Anticipator Setting (amps) 208/230/460 v First Stage.14 Second Stage.14 Gas Input (Btuh)
First Stage/Second Stage (3-phase units) 072 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000 115 82,000/115,000 150 — 120,000/150,000 120,000/150,000 120,000/150,000 071II —/ 72,000 —/ 72,000 —/ 72,000 — 114II —/115,000 —/115,000 —/115,000 — 149II — —/150,000 —/150,000 — 060N*** —/ 60,000 —/ 60,000 —/ 60,000 — 090N*** —/ 90,000 —/ 90,000 —/ 90,000 — 120N*** — —/120,000 —/120,000 — Efficiency (Steady State) (%) 072 82 115 80 81 81 81 150 — 80 80 80 071 82 82 82 — 114 80 81 81 — 149 — 80 80 — 060N 80 80 80 — 090N 80 80 80 — 120N — 80 80 — Temperature Rise Range 072 25-55 115 55-85 35-65 35-65 35-65 150 — 50-80 50-80 50-80 071 25-55 25-55 25-55 — 114 55-85 35-65 35-65 — 149 — 50-80 50-80 — 060N 20-50 20-50 20-50 — 090N 30-60 30-60 30-60 — 120N — 40-70 40-70 — Manifold Pressure (in. wg)
Natural Gas — Std 3.5 Liquid Propane — Alt† 3.5 Gas Valve Quantity 1 Gas Valve Pressure Range (Min-Max Allowable)
Psig 0.180-0.470 in. wg 5.0-13.0 Maximum Static Pressure (in. wg) 1.0 Field Gas Connection Size (in. FPT) 1/2 HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief 450 ± 50 Cutout 428 Reset (Auto.) 320 LOSS-OF-CHARGE SWITCH/LOW-PRESSURE
SWITCH (Liquid LIne) (psig) Cutout 7 ± 3 Reset (Auto.) 22 ± 5 FREEZE PROTECTION THERMOSTAT
Opens (F) 30 ± 5 Closes (F) 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) Varies By Option Selected RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 2...16 x 25 x 2 4...16 x 16 x 2
||California compliant three-phase models. ***California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.
*Single phase/three phase. †Indicates automatic reset. **60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners. ††An LP kit is available as an accessory. In order to convert a Low NOx unit to
LP gas, the baffle must be removed. Low NOx units converted to LP gas are no longer California SCAQMD compliant.
Bhp— Brake Horsepower

UNIT SIZE 581B 090 102 120 150 NOMINAL CAPACITY (tons) 71/2 81/2 10 121/2 OPERATING WEIGHT (lb)
Unit 870 1015 1035 1050 COMPRESSOR Scroll Quantity 2 Oil (oz) (each compressor) 53 50 50 60 REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Standard Unit
Circuit 1 (first stage) 7-10 9- 8 9-10 9-8 Circuit 2 (second stage) 8- 2 8-13 10-10 9-5 Unit With Perfect Humidity Dehumidification Package
Circuit 1 (first stage) 13-0 16-0 16-8 15-3 Circuit 2 (second stage) 13-6 16-8 17-8 16-6 CONDENSER FAN Propeller Quantity...Diameter (in.) 2...22 Nominal Cfm 6500 6500 7000 7000 Motor Hp...Rpm 1/4...1100 Watts Input (Total) 650 CONDENSER COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins Standard Unit
Rows...Fins/in. 2...17 Total Face Area (sq ft) 20.5 25.0 25.0 25.0 Unit with Perfect Humidity Dehumidification Package
Rows...Fins/in. 1...17 Total Face Area (sq ft) 6.3 8.4 8.4 8.4 EVAPORATOR FAN Centrifugal Size (in.) 15 x 15 15 x 15 15 x 15 15 x 15 Type Drive Belt Nominal Cfm 3000 3400 4000 5000 Maximum Continuous Bhp Std 2.90 2.90 3.70 5.25 Hi-Static 4.20 4.20 5.25 — Motor Frame 56 Fan Rpm Range Std 840-1085 840-1085 860-1080 830-1130 Hi-Static 860-1080 860-1080 830-1130 — Motor Bearing Type Ball Maximum Fan Rpm 2100 Motor Pulley Pitch Diameter
Std 3.4/4.4 3.4/4.4 4.0/5.0 2.8/3.8 Hi-Static 4.0/5.0 4.0/5.0 2.8/3.8 — Nominal Motor Shaft Diameter (in.) 7/8 Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 8.0 5.8 Hi-Static 8.0 8.0 5.8 — Belt — Type...Length (in.) Std A...48 A...51 A...53 BX...48 Hi-Static A...53 A...53 BX...45 — Pulley Center Line Distance (in.) 16.75-19.25 16.75-19.25 15.85-17.50 15.85-17.50 Speed Change per Full Turn of
A/B (in.)
Std 50 50 45 60 Hi-Static 60 60 60 — Movable Pulley Maximum Full
Movable Pulley Flange (rpm)
Std 5 5 5 6 Hi-Static 5 5 6 — Factory Setting — Full Turns Open Std 5 Hi-Static 5 5 5 — Factory Speed Setting (rpm) Std 840 840 860 887 Hi-Static 860 860 890 — Fan Shaft Diameter at Pulley (in.) 1 EVAPORATOR COIL 3/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins Rows...Fins/in. 3...15 4...15 4...15 4...15 Total Face Area (sq ft) 8.9 11.1 11.1 11.1
Turns from Closed Position
**72,000 Btuh heat input units have 2 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners. ††An LP kit is available as an accessory.
Bhp — Brake Horsepower
*Single phase/three phase. †Indicates automatic reset.

UNIT SIZE 581B 090 102 120 150 FURNACE SECTION
Rollout Switch Cutout Temp (F)† 195 Burner Orifice Diameter (in drill size)**
Natural Gas — Std 125.120...31 125.120...31 180.120...31 180.120...31 180.120...31 180.120...31 224.120...31 224.129...30 224.120...31 224.120...31 250.129...30 — — Liquid Propane — Alt†† 125.096...41 125.096...41 180.096...41 180.096...41 180.096...41 180.096...41 224.096...41 224.102...38 224.096...41 224.096...41 250.102...38 — — Thermostat Heat Anticipator Setting (amps)
Stage 1.14 Stage 2.14 .14 .20 Gas Input (Btuh) Stage 1 125 90,000 125 90,000 180 120,000 180 120,000 180 120,000 180 120,000 224 180,000 224 180,000 224 180,000 224 180,000 250 200,000 — — Stage 2 125 125,000 125 125,000 180 180,000 180 180,000 180 180,000 180 180,000 224 224,000 224 224,000 224 224,000 224 224,000 250 250,000 — — Efficiency (Steady State) (%) 82 80 82 82 80 Temperature Rise Range 125 20-50 125 20-50 180 35-65 180 35-65 180 35-65 180 35-65 224 35-65 224 40-70 224 45-75 224 45-75 250 40-70 — — Manifold Pressure (in. wg)
Natural Gas — Std 3.5 Liquid Propane — Alt†† 3.5 Gas Valve Quantity 1 Gas Valve Pressure Range (Min-Max Allowable)
Psig 0.180-0.470 in. wg 5.0-13.0 Field Gas Connection Size (in. FPT) 125.50 125.50 180.75 180.75 180.75 180.75 224.75 224.75 224.75 224.75 250.75 — — HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief 450 ± 50 Cutout 428 Reset (Auto.) 320 LOSS-OF-CHARGE SWITCH/LOW-PRESSURE
SWITCH (Liquid LIne) (psig) Cutout 7 ± 3 Reset (Auto.) 22 ± 7 FREEZE PROTECTION THERMOSTAT
Opens (F) 30 ± 5 Closes (F) 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 25 x 1 1...16 x 25 x 1 RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2
**180,000 Btuh heat input units have 2 burners. 224,000 Btuh heat input units and 250,000 Btuh Heat input units have 3 burners. ††An LP kit is available as an accessory.
Bhp — Brake Horsepower
*Single phase/three phase. †Indicates automatic reset.
036 048 060 072 090 102 120 150
Option / Accessory
lb kg lb k g lb kg lb kg lb kg lb kg lb kg lb kg
Perfect Humidity Dehumidification System 15 7 23 10 25 11 29 13 44 20 51 23 51 23 51 23
Power Exhaust - vertical 50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34 Power Exhaust - horizontal 30 14 30 14 30 14 30 14 30 14 30 14 30 14 30 14 EconoMi$er ( IV or 2) 50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34 Two Position damper
(25%) 22 10 22 10 22 10 22 10 32 15 32 15 32 15 32 15
(100%) 39 18 39 18 39 18 39 18 58 26 58 26 58 26 58 26
Manual Dampers 12 5 12 5 12 5 18 8 18 8 18 8 18 8 18 8 Hail Guard (louvered) 16 7 16 7 16 7 16 7 34 15 34 15 34 15 34 15 Hail Guard (standard hood
assembly) 25 11 25 11 25 11 25 11 38 17 50 23 50 23 50 23
Cu/Cu Condenser Coil 6 3 13 6 13 6 15 7 12 5 23 10 23 10 23 10 Cu/Cu Condenser and
Evaporator Coils 12 5 19 9 21 10 26 12 25 11 49 22 49 22 49 22
Roof Curb (14-in. curb) 115 52 115 52 115 52 115 52 143 65 143 65 143 65 143 65 Roof Curb (24-in. curb) 197 89 197 89 197 89 197 89 245 111 245 111 245 111 245 111



Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm ft-in. mm
090 870 395 75 34.1 145 65.9 189 86 161 73 239 109 280 127 2-07/8 632 3-55/16 1050 2-911/16 856 2- 27/16 672 102 1015 460 75 34.1 145 65.9 223 101 188 85 279 126 327 148 1-27/8 378 4-15/16 1253 3-03/8 924 2-107/16 875 120 1035 469 75 34.1 145 65.9 225 102 192 87 285 129 333 151 1-27/8 378 4-15/16 1253 3-03/8 924 2-107/16 875 150 1050 476 75 34.1 145 65.9 228 103 195 88 289 131 338 153 1-27/8 378 4-15/16 1253 3-03/8 924 2-107/16 875
581B036-150
CORNER WEIGHT (D)
CORNER WEIGHT (C)
CORNER WEIGHT (B)
W/P.E. WEIGHT (A)
WEIGHT VERT. ECON IV
WEIGHT ECONOMI$ER IV
STD UNIT
UNIT
581B
a48-8200





IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) 44,600 Btuh Sensible Heat Capacity (SHC) 32,000 Btuh Required Heating Capacity 85,000 Btuh Condenser Entering-Air Temperature 95 F Evaporator Entering-Air Temperature 82 F edb,
MENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Pressure Drop tables (page 133), find:
External static pressure .75 in. wg Total static pressure = .75 in. wg Enter the Fan Performance table for 581B--048115 verti- cal discharge unit on page 104. At 1600 cfm and 0.75 in. wg interpolation is required. The rpm is 1051. The bhp is 0.90. The watts are 897. The factory-installed standard motor and drive are sufficient for operation. V DETERMINE NET COOLING CAPACITY.
67 F ewb Evaporator Air Quantity 1600 cfm External Static Pressure (ESP) 0.75 in. wg Electrical Characteristics (V-Ph-Hz) 230-1-60 II SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY. Enter the Cooling Capacities table (page 92) at condenser entering temperature of 95 F, evaporator-air entering at 1600 cfm and 80 F db and 67 F wb. The 581B--048115 unit will provide cooling capacity of 48,900 Btuh and a sensible heat capacity of 34,700 Btuh. For evaporator-air temperature other than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in Note 3 following the Cooling Capacities tables. For this example: Correction factor = 1.10 x (1 – .21) x (82 – 80) = 1.738 Multiply the correction factor of 1.738 by 1600 cfm (a total of 2781). From the Gross Cooling Capacities tables find that the sensible heat capacity at 80 F is 34.7 MBtuh (equivalent to 34,700 Btuh). Add 34,700 and 2781 to get the corrected sensible heat capacity of 37,481. NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor heat. To calcu- late net capacities, see Step V. III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
Cooling capacities are gross and do not include indoor-fan motor (IFM) heat. Determine net capacity using the follow- ing formula: Net capacity = gross capacity – IFM heat
= 48,900 Btuh – 897 Watts
(3.413 Btuh ) Watts = 48,900 Btuh – 3061 Btuh
Net capacity = 45,839 Btuh
Net sensible capacity = 37,481 Btuh – 3061 Btuh = 34,420 Btuh
DESIGN CONDITION REQUIREMENTS. In the Heating Capacities and Efficiencies table (page 10) note that unit 581B--048115 will provide output capacity of 93,150 Btuh, which is adequate for the given application.

581B036 (3 TONS)
Air Entering Evaporator — Cfm/BF 900/0.14 1200/0.17 1500/0.20 Air Entering Evaporator — Ewb 72 67 62 72 67 62 72 67 62
75 TC 41.9 38.7 35.7 43.5 40.8 37.7 44.8 41.8 39.0 SHC 20.4 25.2 29.7 21.8 28.2 33.8 23.3 30.7 37.0 kW 2.19 2.16 2.12 2.21 2.18 2.15 2.23 2.19 2.16
85 TC 40.7 37.5 34.5 42.1 39.3 36.4 43.5 40.4 37.6 SHC 19.9 24.7 29.2 21.5 27.7 33.2 23.2 30.3 36.4 kW 2.46 2.42 2.39 2.47 2.44 2.41 2.50 2.45 2.42
95 TC 39.3 36.1 33.1 40.8 37.8 34.9 42.0 38.9 36.1 SHC 19.5 24.1 28.4 21.1 27.2 32.5 22.8 29.9 35.6 kW 2.75 2.71 2.66 2.77 2.73 2.69 2.79 2.74 2.71
105 TC 37.7 34.6 31.7 39.3 36.2 33.4 40.1 37.2 34.7 SHC 18.8 23.5 27.8 20.7 26.6 31.8 22.1 29.3 34.7 kW 3.06 3.02 2.98 3.09 3.04 3.01 3.10 3.06 3.03
115 TC 36.0 33.0 29.7 37.4 34.5 31.5 38.1 35.5 33.2 SHC 18.3 22.9 26.7 19.9 26.1 30.9 21.3 28.7 33.2 kW 3.41 3.36 3.31 3.43 3.39 3.34 3.44 3.41 3.37
125 TC 34.2 31.3 27.8 35.6 32.7 29.4 36.3 33.6 31.9 SHC 17.6 22.2 25.8 19.4 25.4 29.4 20.8 28.0 31.8 kW 3.78 3.73 3.66 3.80 3.76 3.71 3.81 3.78 3.75
Air Entering Evaporator — Cfm/BF 1200/0.17 1450/0.19 1600/0.21 2000/0.24 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 54.0 50.7 44.2 55.9 52.2 47.7 56.4 52.8 49.1 58.1 54.5 50.6 SHC 26.1 32.7 37.5 27.6 35.1 41.8 28.2 36.2 43.8 30.2 39.5 47.5 kW 2.81 2.80 2.76 2.83 2.81 2.78 2.83 2.80 2.79 2.84 2.82 2.79
85 TC 52.2 48.9 41.9 54.1 50.4 45.9 54.5 51.0 47.2 55.3 52.3 48.7 SHC 25.4 32.0 36.4 26.9 34.5 40.8 27.5 35.7 42.8 28.6 38.5 46.6 kW 3.20 3.19 3.15 3.22 3.20 3.17 3.22 3.20 3.18 3.22 3.20 3.18
95 TC 50.7 46.9 39.5 51.9 48.4 43.5 52.5 48.9 45.2 53.9 50.1 46.7 SHC 24.9 31.1 35.0 26.1 33.6 39.6 26.8 34.7 41.8 28.8 37.5 45.6 kW 3.64 3.61 3.57 3.65 3.62 3.60 3.65 3.62 3.60 3.67 3.63 3.61
105 TC 48.8 44.5 36.7 49.8 46.2 40.7 50.2 46.7 42.1 51.5 48.2 44.7 SHC 24.3 30.2 33.6 25.3 32.8 38.2 26.0 33.9 40.3 27.9 37.4 44.4 kW 4.12 4.09 4.03 4.12 4.09 4.06 4.12 4.09 4.07 4.14 4.11 4.08
115 TC 46.5 41.1 34.3 47.7 43.3 37.0 48.0 44.4 38.5 48.9 45.7 42.0 SHC 23.4 28.9 32.4 24.9 31.8 36.3 25.4 33.4 38.3 27.1 36.9 42.0 kW 4.64 4.59 4.53 4.65 4.62 4.55 4.64 4.63 4.56 4.65 4.63 4.60
125 TC 43.8 37.5 32.4 45.1 39.0 33.8 45.3 40.1 35.4 46.3 42.6 38.8 SHC 22.5 27.4 31.5 24.1 30.2 33.7 24.7 31.9 35.4 26.5 35.9 38.8 kW 5.19 5.13 5.05 5.20 5.15 5.09 5.19 5.17 5.11 5.20 5.19 5.15
Air Entering Evaporator — Cfm/BF 1500/0.08 1750/0.09 2000/0.11 2500/0.13 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 70.8 65.4 58.5 72.5 67.3 61.1 73.0 68.4 62.8 74.8 70.3 64.8 SHC 34.1 42.7 49.9 35.7 45.5 54.2 36.8 48.0 57.8 39.6 53.0 63.4 kW 3.53 3.49 3.44 3.55 3.50 3.46 3.55 3.51 3.47 3.57 3.54 3.48
85 TC 68.9 63.2 55.3 70.5 65.1 57.9 72.2 66.4 60.2 73.2 68.1 62.9 SHC 33.5 41.8 48.4 35.0 44.8 52.8 37.0 47.6 56.8 39.3 52.5 62.4 kW 3.98 3.94 3.87 4.00 3.96 3.90 4.03 3.97 3.92 4.04 3.99 3.94
95 TC 66.8 60.6 52.4 68.3 62.5 54.3 69.3 63.8 56.6 71.2 65.6 60.6 SHC 32.8 40.7 47.0 34.5 43.8 51.1 36.0 46.7 55.0 39.1 51.8 60.5 kW 4.48 4.43 4.35 4.50 4.45 4.37 4.51 4.46 4.40 4.55 4.48 4.44
105 TC 64.3 57.7 49.9 65.9 59.8 51.7 66.9 61.1 54.1 68.4 62.8 58.4 SHC 32.0 39.6 45.8 33.7 42.8 49.7 35.3 45.7 53.5 38.4 51.0 58.4 kW 5.03 4.96 4.87 5.05 4.99 4.90 5.06 5.00 4.93 5.08 5.02 4.98
115 TC 61.5 54.8 47.3 62.8 56.7 49.1 64.0 58.2 51.6 65.4 59.9 56.1 SHC 31.0 38.4 44.5 32.5 41.6 48.2 34.4 44.6 51.6 37.4 50.0 56.1 kW 5.61 5.55 5.46 5.62 5.58 5.49 5.65 5.60 5.52 5.67 5.61 5.57
125 TC 58.7 51.6 44.5 59.9 53.4 46.2 60.8 54.9 49.0 62.2 56.8 53.5 SHC 30.0 37.2 43.1 31.7 40.4 46.2 33.3 43.4 48.9 36.4 48.9 53.4 kW 6.27 6.19 6.09 6.28 6.21 6.13 6.29 6.24 6.17 6.31 6.27 6.22
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B072 (6 TONS)
Air Entering Evaporator — Cfm/BF 1800/0.05 2100/0.06 2400/0.06 3000/0.08 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 86.7 80.7 74.4 88.8 82.7 76.6 90.5 84.4 78.2 92.6 86.3 81.0 SHC 43.0 53.7 63.8 45.0 57.4 68.9 47.2 61.2 73.6 51.2 67.4 80.7 kW 4.58 4.46 4.33 4.63 4.50 4.38 4.67 4.55 4.41 4.72 4.58 4.47
85 TC 84.1 78.2 72.0 86.4 80.3 74.1 88.2 81.7 75.7 90.2 84.0 78.8 SHC 42.0 52.6 62.7 44.5 56.6 68.0 46.8 60.2 72.5 50.6 67.4 78.7 kW 5.10 4.97 4.85 5.16 5.03 4.90 5.21 5.06 4.93 5.26 5.12 4.99
95 TC 81.3 75.3 69.2 83.4 77.3 71.3 85.1 78.9 72.9 87.2 80.6 76.2 SHC 41.0 51.4 61.4 43.4 55.3 66.6 45.8 59.2 71.2 50.2 65.8 76.2 kW 5.65 5.52 5.39 5.71 5.57 5.44 5.77 5.62 5.48 5.83 5.66 5.55
105 TC 77.9 72.0 66.1 80.0 73.8 68.0 81.6 75.3 69.6 83.4 77.1 73.2 SHC 39.7 50.2 60.0 42.2 54.0 65.2 44.6 57.8 69.3 49.0 64.5 73.2 kW 6.22 6.08 5.94 6.29 6.13 6.00 6.34 6.17 6.04 6.40 6.22 6.12
115 TC 74.7 68.4 61.8 75.9 70.0 64.1 77.6 71.3 66.5 78.7 73.0 70.1 SHC 38.7 48.8 58.1 40.8 52.6 63.2 43.3 56.4 66.4 46.9 63.2 70.0 kW 6.84 6.68 6.49 6.87 6.71 6.56 6.93 6.75 6.63 6.96 6.80 6.72
125 TC 70.3 63.6 57.2 71.8 65.5 59.1 72.9 66.8 61.9 74.0 68.6 66.4 SHC 37.2 47.0 55.8 39.5 51.0 59.1 41.7 55.0 61.9 45.4 61.8 66.3 kW 7.43 7.25 7.03 7.48 7.30 7.13 7.51 7.35 7.22 7.54 7.41 7.33
Air Entering Evaporator — Cfm/BF 2250/0.10 3000/0.11 3750/0.14 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
75 TC 105.5 96.9 87.6 107.3 99.6 90.7 110.3 101.9 93.8 SHC 50.6 63.6 75.7 53.3 69.2 83.7 58.0 76.6 92.2 kW 5.15 5.07 5.04 5.16 5.11 5.06 5.20 5.13 5.07
85 TC 102.5 93.6 83.6 105.1 96.5 87.5 107.7 99.0 90.6 SHC 49.7 62.4 73.9 52.8 68.4 82.2 57.3 75.9 90.0 kW 5.86 5.79 5.73 5.89 5.82 5.77 5.93 5.86 5.78
95 TC 98.9 90.1 79.3 101.6 92.9 83.5 103.8 95.3 87.4 SHC 48.5 61.2 71.9 51.9 67.2 80.2 56.2 74.9 87.3 kW 6.65 6.58 6.49 6.69 6.61 6.53 6.72 6.64 6.57
105 TC 95.3 86.2 75.7 97.6 88.8 79.6 100.0 91.0 84.1 SHC 47.3 59.6 70.2 50.7 65.9 78.0 55.3 73.6 84.1 kW 7.51 7.44 7.31 7.55 7.48 7.36 7.59 7.50 7.41
115 TC 91.0 82.0 71.6 93.2 84.5 75.4 95.6 86.6 80.7 SHC 45.9 58.0 68.1 49.3 64.2 75.3 54.2 72.1 80.7 kW 8.43 8.33 8.20 8.46 8.37 8.27 8.52 8.42 8.34
125 TC 86.2 77.8 68.1 88.3 80.0 71.9 90.0 81.9 77.2 SHC 44.1 56.4 66.3 47.5 62.6 71.8 52.1 70.1 77.2 kW 9.38 9.29 9.14 9.43 9.34 9.24 9.47 9.38 9.32
Air Entering Evaporator — Cfm/BF 2550/0.11 3000/0.12 3400/0.13 4250/0.17 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 57 62 67 72 57 62 67 72 57
75 TC 94.6 101.0 110.0 119.2 100.4 104.4 113.4 121.8 104.2 106.8 115.8 123.4 109.8 111.0 119.0 125.8 SHC 94.6 84.4 69.4 54.4 100.4 92.4 75.0 57.2 104.2 99.0 80.0 59.8 109.8 110.4 89.4 64.2 kW 5.72 5.76 5.76 5.82 5.74 5.76 5.80 5.86 5.74 5.76 5.82 5.88 5.76 5.78 5.84 5.90
85 TC 91.0 97.4 106.8 115.8 97.4 101.0 110.0 119.6 101.2 103.0 112.0 121.6 108.0 108.0 116.0 123.4 SHC 91.0 83.0 68.8 53.2 97.4 91.2 74.2 57.0 101.2 97.6 78.8 59.6 108.0 108.0 89.4 64.2 kW 6.46 6.5 6.52 6.58 6.50 6.52 6.54 6.60 6.50 6.52 6.54 6.64 6.54 6.54 6.60 6.64
95 TC 85.2 91.4 103.0 112.8 93.4 96.6 106.2 116.0 98.2 99.2 108.4 117.8 104.6 104.6 111.6 121.2 SHC 85.2 80.4 67.2 52.6 93.4 89.4 73.0 55.8 98.2 96.2 78.2 58.8 104.6 104.6 88.0 64.6 kW 7.24 7.28 7.36 7.42 7.30 7.32 7.38 7.44 7.34 7.36 7.4 7.46 7.36 7.36 7.42 7.50
105 TC 80.0 82.2 98.6 108.6 87.0 87.8 101.6 111.8 93.4 93.6 103.8 114.0 101.0 100.8 106.8 116.6 SHC 80.0 76.6 65.6 51.2 87.0 85.6 71.6 54.8 93.4 93.2 76.6 57.8 101.0 100.8 86.8 63.6 kW 8.08 8.12 8.26 8.32 8.16 8.16 8.28 8.36 8.20 8.20 8.3 8.38 8.28 8.28 8.30 8.40
115 TC 73.6 74.6 89.4 103.4 81.0 81.2 95.2 106.4 86.2 86.2 98.4 108.4 96.4 96.4 101.6 111.8 SHC 73.6 73.0 62.2 49.6 81.0 81.2 69.4 53.0 86.2 86.2 75.0 56.4 96.4 96.4 85.4 62.8 kW 9.00 9.00 9.16 9.28 9.08 9.08 9.22 9.30 9.14 9.14 9.26 9.34 9.22 9.22 9.30 9.38
125 TC 68.6 68.6 80.2 98.2 74.4 74.4 84.0 101.0 79.2 79.2 86.8 102.8 88.0 88.0 93.8 105.6 SHC 68.6 68.6 59.0 48.0 74.4 74.4 65.4 51.6 79.2 79.2 71.0 54.6 88.0 88.0 82.8 61.0 kW 9.98 9.98 10.14 10.32 10.06 10.06 10.18 10.36 10.14 10.14 10.22 10.38 10.24 10.24 10.28 10.42
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B120 (10 TONS)
Air Entering Evaporator — Cfm/BF 3000/0.03 3200/0.03 4000/0.04 5000/0.04 Air Entering Evaporator — Ewb 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 140.3 129.4 115.0 141.2 130.4 118.1 145.2 134.0 122.1 147.5 136.6 125.3 SHC 65.6 82.2 97.4 66.7 84.4 101.5 71.3 93.1 113.5 77.9 103.7 124.7 kW 7.35 7.21 7.12 7.37 7.23 7.13 7.46 7.31 7.17 7.51 7.37 7.22
85 TC 137.7 125.3 110.0 138.9 126.6 113.6 142.6 130.6 117.7 144.6 133.3 122.3 SHC 65.0 81.2 95.2 66.3 83.6 99.7 71.0 92.8 112.0 76.9 103.1 122.2 kW 8.29 8.13 8.02 8.32 8.16 8.03 8.40 8.24 8.09 8.45 8.31 8.16
95 TC 133.8 120.7 103.0 135.1 121.9 107.2 138.8 125.8 112.8 141.7 128.5 118.5 SHC 63.9 79.6 92.2 65.2 82.0 97.0 70.6 91.5 109.7 76.9 102.5 118.4 kW 9.33 9.16 8.98 9.35 9.18 9.00 9.44 9.27 9.07 9.51 9.33 9.19
105 TC 128.7 115.4 96.5 129.8 116.6 99.7 133.7 120.3 107.1 136.7 122.8 114.5 SHC 62.3 77.6 89.4 63.6 80.2 93.5 69.4 89.6 106.8 76.0 100.6 114.3 kW 10.46 10.28 10.00 10.47 10.30 10.07 10.57 10.38 10.21 10.66 10.43 10.31
115 TC 123.2 109.1 90.8 124.3 110.3 92.2 127.9 114.4 100.8 130.9 116.8 110.1 SHC 60.4 75.1 86.6 61.9 77.8 90.0 67.6 87.6 100.7 74.6 98.7 109.9 kW 11.66 11.47 11.20 11.68 11.51 11.25 11.77 11.60 11.41 11.89 11.66 11.58
125 TC 117.5 101.8 86.2 118.5 103.0 87.4 121.6 107.1 96.0 124.1 110.3 104.8 SHC 58.5 72.5 84.5 60.0 75.0 87.3 65.8 85.1 96.0 72.5 96.9 104.8 kW 12.99 12.77 12.50 13.02 12.81 12.55 13.10 12.92 12.74 13.19 13.01 12.91
Air Entering Evaporator — Cfm/BF 3750/0.08 4300/0.09 5000/0.11 6250/0.13 Air Entering Evaporator — Ewb 72 67 62 72 67 62 72 67 62 72 67 62
75 TC 167.1 154.3 142.0 169.8 157.7 144.8 173.5 160.6 148.4 176.5 164.5 153.3 SHC 82.5 103.5 123.6 85.8 109.7 132.0 90.3 117.7 141.9 98.2 130.7 153.1 kW 9.44 9.18 8.95 9.50 9.26 9.01 9.60 9.33 9.07 9.68 9.43 9.17
85 TC 162.3 149.3 135.6 165.1 152.5 139.5 168.8 155.3 143.5 172.1 159.2 149.3 SHC 80.9 101.4 120.9 84.4 107.9 129.9 89.6 115.8 139.8 97.6 129.3 149.1 kW 10.49 10.18 9.97 10.55 10.27 10.02 10.67 10.32 10.11 10.75 10.43 10.21
95 TC 156.5 143.7 126.3 159.6 146.8 131.3 162.3 149.8 136.5 166.5 153.2 144.5 SHC 79.1 99.5 116.5 83.0 106.1 126.0 87.6 114.2 135.8 95.8 127.7 144.4 kW 11.60 11.30 11.01 11.69 11.39 11.10 11.75 11.47 11.20 11.87 11.56 11.35
105 TC 150.0 136.2 115.7 153.0 139.3 120.9 155.6 142.5 138.5 158.8 145.9 138.8 SHC 76.5 96.7 111.2 80.8 103.5 120.0 85.7 112.3 128.4 93.6 125.9 138.7 kW 12.76 12.42 12.09 12.83 12.52 12.20 12.91 12.62 12.32 12.96 12.72 12.52
115 TC 141.8 122.2 104.4 144.3 126.1 110.8 147.7 129.4 118.9 150.7 135.2 130.1 SHC 73.6 91.2 104.2 77.9 98.5 110.8 83.4 107.3 118.4 91.8 121.9 129.9 kW 13.85 13.55 13.22 13.94 13.64 13.35 14.05 13.73 13.50 14.15 13.86 13.70
125 TC 132.5 108.6 93.9 134.8 111.4 100.7 137.6 114.4 106.6 140.3 122.9 120.1 SHC 70.9 85.7 93.8 74.8 92.9 100.7 80.2 101.4 106.5 89.0 116.3 120.1 kW 15.04 14.66 14.44 15.14 14.75 14.55 15.23 14.85 14.72 15.29 14.94 14.84
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B036 (3 TONS) — SUBCOOLING MODE
Air Entering Evaporator — Cfm/BF 900/0.14 1200/0.17 1500/0.20 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
Air Ent Condenser
(Edb)
75 TC 41.3 37.3 34.3 43.5 39.2 35.9 45.5 41.6 38.2 SHC 17.5 22.4 26.7 19.6 25.5 31.2 21.5 28.5 35.2 kW 2.19 2.14 2.10 2.21 2.16 2.14 2.24 2.19 2.16
85 TC 38.6 34.4 31.6 41.3 37.5 33.3 43.5 38.6 35.5 SHC 15.2 20.1 25.1 17.1 23.2 29.0 18.9 26.3 32.9 kW 2.46 2.40 2.37 2.47 2.43 2.40 2.51 2.45 2.42
95 TC 35.9 31.4 28.8 39.2 35.9 30.6 41.3 35.7 32.9 SHC 13.0 17.9 23.3 14.5 21.1 26.9 16.1 24.2 30.6 kW 2.74 2.68 2.63 2.76 2.74 2.67 2.80 2.75 2.71
105 TC 33.8 29.7 27.4 36.3 32.2 28.7 38.1 32.8 30.4 SHC 10.9 15.8 21.0 12.5 18.9 24.6 14.0 21.7 28.1 kW 3.05 3.00 2.97 3.09 3.04 2.99 3.12 3.07 3.03
115 TC 31.8 28.0 25.5 33.2 28.7 26.5 34.9 30.0 27.9 SHC 9.0 13.7 18.4 10.3 16.8 22.3 11.9 19.3 25.2 kW 3.40 3.36 3.31 3.45 3.38 3.32 3.48 3.41 3.37
125 TC 28.7 26.3 23.4 29.7 25.5 22.9 31.3 27.1 25.5 SHC 6.9 12.2 17.3 7.9 14.5 20.6 9.2 17.3 22.3 kW 3.78 3.73 3.66 3.84 3.77 3.71 3.87 3.79 3.75
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 900 1200 1500 900 1200 1500 900 1200 1500
Air Ent Condenser
(Edb)
80 TC 12.83 15.84 18.20 13.24 16.31 18.73 13.58 16.72 19.18 SHC 4.06 5.69 6.98 2.21 3.83 5.12 .59 2.20 3.50 kW 2.12 2.12 2.12 2.13 2.13 2.13 2.14 2.14 2.14
75 TC 13.61 16.44 18.67 14.03 16.93 19.20 14.39 17.34 19.67 SHC 4.62 6.16 7.37 2.89 4.43 5.65 1.40 2.93 4.15 kW 2.11 2.11 2.11 2.12 2.12 2.12 2.14 2.14 2.14
70 TC 14.39 17.05 19.14 14.82 17.54 19.68 15.19 17.96 20.15 SHC 5.17 6.62 7.77 3.58 5.03 6.18 2.20 3.65 4.80 kW 2.10 2.10 2.10 2.12 2.12 2.12 2.13 2.13 2.13
60 TC 15.95 18.26 20.08 16.40 18.77 20.63 16.79 19.21 21.11 SHC 6.27 7.55 8.56 4.95 6.23 7.24 3.81 5.09 6.10 kW 2.09 2.09 2.09 2.11 2.11 2.11 2.12 2.12 2.12
50 TC 17.50 19.48 21.02 17.98 20.00 21.58 18.40 20.45 22.07 SHC 7.37 8.47 9.35 6.32 7.43 8.30 5.42 6.52 7.39 kW 2.07 2.07 2.07 2.10 2.10 2.10 2.12 2.12 2.12
40 TC 19.06 20.69 21.07 19.56 21.23 22.54 20.00 21.70 23.03 SHC 8.47 9.40 10.13 7.71 8.63 9.36 7.02 7.95 8.69 kW 2.06 2.06 2.06 2.08 2.08 2.08 2.11 2.11 2.11
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B048 (4 TONS) — SUBCOOLING MODE
Air Entering Evaporator — Cfm/BF 1200/0.17 1450/0.19 1600/0.21 2000/0.24 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
Air Ent Condenser
(Edb)
75 TC 52.9 47.5 41.5 55.7 50.9 47.5 57.0 51.7 48.1 60.5 55.6 52.1 SHC 22.7 28.4 33.4 26.1 34.1 38.9 25.9 33.7 41.6 29.4 39.1 47.5 kW 2.87 2.86 2.82 2.89 2.87 2.84 2.89 2.86 2.85 2.90 2.88 2.85
85 TC 49.2 43.8 37.1 52.1 47.2 43.6 52.9 47.9 43.7 55.4 51.4 47.0 SHC 19.8 25.5 30.4 22.2 29.5 35.8 22.4 31.1 38.7 24.2 36.0 44.3 kW 3.26 3.25 3.21 3.28 3.26 3.23 3.28 3.26 3.24 3.28 3.26 3.24
95 TC 45.8 40.1 32.8 48.2 43.6 39.4 48.8 44.0 39.3 51.7 47.4 43.0 SHC 17.2 22.5 27.3 18.4 24.8 32.6 19.0 28.1 35.9 20.7 33.0 41.0 kW 3.71 3.68 3.64 3.72 3.69 3.67 3.72 3.69 3.67 3.74 3.70 3.68
105 TC 41.6 37.0 29.7 43.2 38.9 35.4 43.9 39.7 34.7 46.5 41.4 37.5 SHC 13.5 19.5 23.9 14.7 21.7 29.2 15.0 23.7 30.6 16.4 27.8 35.1 kW 4.20 4.17 4.11 4.20 4.17 4.14 4.20 4.17 4.15 4.22 4.19 4.16
115 TC 37.2 33.2 27.1 38.4 34.0 30.8 39.4 35.5 30.0 41.3 35.2 31.9 SHC 9.9 16.4 20.7 11.3 18.5 25.6 11.2 19.7 25.4 12.4 22.4 28.6 kW 4.73 4.68 4.62 4.74 4.71 4.64 4.73 4.72 4.65 4.74 4.72 4.69
125 TC 32.4 28.1 24.9 33.8 28.1 27.4 35.3 30.5 26.6 36.1 32.0 28.7 SHC 7.2 12.9 18.3 8.4 14.5 21.9 16.8 21.1 21.2 9.5 18.3 24.1 kW 5.29 5.23 5.15 5.30 5.25 5.19 5.29 5.27 5.21 5.30 5.29 5.25
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 1200 1450 1600 1200 1450 1600 1200 1450 1600
Air Ent Condenser
(Edb)
80 TC 12.13 14.30 15.43 14.98 17.20 18.36 17.44 19.71 20.90 SHC 1.01 1.60 1.90 –0.18 0.41 0.72 –1.20 –0.61 –0.30 kW 2.76 2.76 2.76 2.75 2.75 2.75 2.74 2.74 2.74
75 TC 13.25 15.28 16.34 15.96 18.05 19.14 18.31 20.44 21.56 SHC 1.60 2.14 2.43 0.50 1.05 1.34 –0.45 0.11 0.40 kW 7.54 7.54 7.57 7.61 7.64 7.66 7.66 7.70 7.71
70 TC 14.37 16.27 17.26 16.94 18.90 19.92 19.17 21.17 22.22 SHC 2.18 2.69 2.96 1.17 1.69 1.96 0.30 0.82 1.10 kW 2.70
60 TC 16.60 18.24 19.10 18.91 20.60 21.48 20.91 22.64 23.54 SHC 3.35 3.79 4.03 2.52 2.97 3.21 1.80 2.25 2.50 kW 2.64 2.64 2.64 2.65
50 TC 18.83 20.22 20.94 20.87 22.30 23.04 22.65 24.10 24.86 SHC 4.51 4.89 5.09 3.86 4.25 4.45 3.30 3.69 3.89 kW 2.59 2.59 2.59 2.60 2.60 2.60 2.61 2.61 2.61
40 TC 21.06 22.19 22.78 22.84 24.00 24.61 24.38 25.57 26.19 SHC 5.68 5.99 6.16 5.21 5.53 5.69 4.80 5.12 5.29 kW 2.53 2.53 2.53 2.55 2.55 2.55 2.57 2.57 2.57
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B060 (5 TONS) — SUBCOOLING MODE
Air Entering Evaporator — Cfm/BF 1500/0.08 1750/0.09 2000/0.11 2500/0.13 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
Air Ent Condenser
(Edb)
75 TC 69.9 62.7 56.2 74.7 67.3 61.0 78.5 71.2 64.8 81.7 75.5 69.3 SHC 29.0 36.9 43.9 31.7 40.5 51.2 34.5 44.2 55.4 37.8 52.0 62.8 kW 3.61 3.55 3.51 3.64 3.58 3.49 3.65 3.60 3.51 3.62 3.58 3.51
85 TC 65.9 59.1 51.7 70.6 63.2 56.3 75.5 66.8 60.7 78.1 70.8 65.1 SHC 25.3 34.0 41.9 27.5 37.6 48.0 30.7 41.6 52.0 33.8 47.4 58.0 kW 4.05 3.97 3.91 4.07 4.01 3.92 4.11 4.00 3.95 4.08 4.02 3.96
95 TC 61.9 55.2 47.7 66.5 58.8 51.3 70.4 61.9 55.7 74.2 65.9 60.6 SHC 21.6 31.1 40.0 23.5 34.5 44.6 26.0 38.6 47.9 30.0 42.8 52.6 kW 4.53 4.43 4.35 4.55 4.47 4.37 4.56 4.42 4.41 4.58 4.49 4.44
105 TC 57.7 51.1 44.9 61.8 54.5 47.7 65.1 57.2 50.8 68.4 60.3 56.1 SHC 18.1 27.8 35.7 20.0 31.2 40.1 22.1 34.3 43.5 26.1 38.9 48.5 kW 5.05 4.93 4.84 5.09 4.97 4.88 5.11 4.96 4.92 5.11 5.03 4.98
115 TC 53.4 47.2 42.0 56.6 50.0 44.2 59.6 52.5 46.2 62.6 54.9 51.6 SHC 14.7 24.6 31.5 16.5 27.8 35.7 18.2 30.0 39.0 22.1 34.9 44.3 kW 5.60 5.49 5.40 5.64 5.52 5.45 5.69 5.55 5.48 5.69 5.61 5.57
125 TC 48.7 42.0 36.9 51.3 45.0 39.0 54.1 46.8 40.9 56.9 49.2 45.9 SHC 10.9 19.6 28.0 12.5 22.2 31.5 13.5 24.0 34.0 16.5 28.0 38.8 kW 6.26 6.12 6.02 6.28 6.18 6.09 6.33 6.18 6.13 6.33 6.27 6.22
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 1500 1750 2000 1500 1750 2000 1500 1750 2000
Air Ent Condenser
(Edb)
80 TC 17.67 19.23 20.59 17.51 19.09 20.48 17.37 18.98 20.39 SHC –0.39 0.07 0.46 –1.61 –1.15 –0.75 –2.67 –2.21 –1.80 kW 3.45 3.45 3.45 3.48 3.48 3.48 3.50 3.50 3.50
75 TC 18.55 20.03 21.32 18.45 19.95 21.27 18.36 19.89 21.23 SHC 0.28 0.71 1.09 –0.85 –0.42 –0.04 –1.83 –1.39 –1.01 kW 3.43 3.43 3.43 3.46 3.46 3.46 3.49 3.49 3.49
70 TC 19.44 20.83 22.06 19.39 20.81 22.06 19.35 20.80 22.07 SHC 0.95 1.36 1.71 –0.09 0.32 0.68 –0.99 –0.58 –0.22 kW 3.42 3.42 3.42 3.45 3.45 3.45 3.48 3.48 3.48
60 TC 21.20 22.44 23.53 21.27 22.54 23.65 21.33 22.62 23.75 SHC 2.30 2.65 2.95 1.44 1.80 2.11 0.70 1.06 1.37 kW 3.38 3.38 3.38 3.42 3.42 3.42 3.46 3.46 3.46
50 TC 22.96 24.05 25.00 23.15 24.26 25.23 23.31 24.43 25.42 SHC 3.64 3.94 4.20 2.97 3.27 3.53 2.39 2.69 2.96 kW 3.35 3.35 3.35 3.40 3.40 3.40 3.43 3.43 3.43
40 TC 24.73 25.66 26.48 25.03 25.98 26.81 25.28 26.25 27.10 SHC 4.99 5.23 5.45 4.50 4.75 4.96 4.07 4.32 4.54 kW 3.32 3.32 3.32 3.37 3.37 3.37 3.41 3.41 3.41
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B072 (6 TONS) — SUBCOOLING MODE
Air Entering Evaporator — Cfm/BF 1800/0.05 2100/0.06 2400/0.06 3000/0.08 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
Air Ent Condenser
(Edb)
75 TC 82.6 75.6 68.5 84.9 78.0 70.9 85.9 79.5 73.5 89.1 82.7 77.0 SHC 36.0 44.8 55.4 37.5 49.1 59.7 38.8 51.1 64.0 41.8 58.1 70.2 kW 4.60 4.52 4.36 4.67 4.57 4.46 4.70 4.57 4.45 4.77 4.61 4.51
85 TC 78.2 71.6 64.5 80.9 73.4 65.8 82.0 74.4 67.9 85.8 78.2 72.3 SHC 31.4 41.2 51.7 33.0 44.7 55.8 34.7 47.4 60.1 37.6 54.3 66.7 kW 5.16 5.03 4.89 5.22 5.11 4.96 5.26 5.09 4.97 5.32 5.17 5.04
95 TC 73.8 67.4 60.2 76.3 68.3 60.5 77.5 69.3 62.3 82.0 72.8 67.5 SHC 27.0 37.6 47.9 28.2 40.0 51.6 30.2 43.7 56.2 33.6 49.2 62.9 kW 5.75 5.60 5.44 5.80 5.66 5.48 5.84 5.68 5.53 5.90 5.73 5.60
105 TC 68.4 62.6 55.9 71.4 64.3 56.2 72.1 64.6 58.3 75.7 67.0 62.4 SHC 22.3 33.5 43.5 23.4 36.5 48.0 25.4 38.4 50.2 29.1 45.2 56.2 kW 6.37 6.22 6.06 6.45 6.27 6.10 6.46 6.29 6.16 6.53 6.36 6.24
115 TC 63.4 57.8 50.7 66.0 60.1 51.5 66.4 59.6 54.5 68.8 60.8 57.5 SHC 18.1 29.5 38.9 18.8 32.9 44.1 20.7 33.3 43.8 24.3 41.4 49.7 kW 7.04 6.89 6.68 7.10 6.91 6.74 7.12 6.95 6.83 7.16 7.01 6.92
125 TC 55.5 49.6 45.8 58.4 52.4 46.1 57.6 52.1 49.5 59.2 52.8 53.1 SHC 15.3 24.0 35.2 15.7 27.5 39.0 17.5 27.5 38.4 20.9 34.6 44.4 kW 7.80 7.61 7.38 7.83 7.67 7.49 7.89 7.72 7.58 7.92 7.78 7.70
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 1800 2100 2400 1800 2100 2400 1800 2100 2400
Air Ent Condenser
(Edb)
80 TC 27.41 28.12 28.75 27.25 27.98 28.62 27.12 27.86 28.51 SHC 5.74 7.61 9.25 1.68 3.52 5.14 –1.85 –0.03 1.58 kW 4.40 4.39 4.39 4.44 4.44 4.44 4.49 4.49 4.49
75 TC 27.98 28.66 29.24 27.89 28.58 29.18 27.81 28.52 29.13 SHC 5.73 7.48 9.02 1.92 3.65 5.18 –1.38 0.34 1.85 kW 4.45 4.45 4.45 4.50 4.50 4.50 4.55 4.55 4.55
70 TC 28.55 29.19 29.74 28.53 29.18 29.74 28.51 29.17 29.74 SHC 5.71 7.35 8.79 2.17 3.79 5.22 –0.91 0.70 2.12 kW 4.51 4.51 4.51 4.57 4.57 4.57 4.62 4.62 4.62
60 TC 29.70 30.25 30.74 29.80 30.37 30.86 29.89 30.47 30.97 SHC 5.67 7.09 8.34 2.65 4.06 5.29 0.04 1.43 2.65 kW 4.62 4.62 4.62 4.69 4.69 4.69 4.75 4.75 4.75
50 TC 30.84 31.32 31.73 31.07 31.56 31.98 31.27 31.77 32.20 SHC 5.63 6.83 7.89 3.14 4.33 5.37 0.98 2.15 3.19 kW 4.74 4.74 4.74 4.82 4.82 4.82 4.89 4.89 4.89
40 TC 31.99 32.38 32.73 32.35 32.75 33.12 32.66 33.07 33.43 SHC 5.60 6.57 7.43 3.63 4.59 5.44 1.92 2.88 3.72 kW 4.86 4.86 4.86 4.95 4.95 4.95 5.02 5.02 5.02
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B090 (7 1 / 2 TONS) — SUBCOOLING MODE
TEMP (F)
AIR ENTERING EVAPORATOR — Cfm/BF 2250/0.10 3000/0.11 3750/0.14 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62
(Edb)
75 TC 98.4 91.1 81.1 103.7 97.9 91.8 105.8 101.3 94.1 SHC 44.5 55.4 67.0 50.4 65.4 80.5 54.5 72.4 89.5 kW 5.05 4.96 4.87 5.09 5.04 4.97 5.16 5.04 4.99
85 TC 94.2 85.8 76.9 100.3 92.4 85.2 103.5 96.8 89.0 SHC 39.7 51.3 62.7 46.2 58.3 75.7 50.6 68.2 84.3 kW 5.74 5.65 5.55 5.81 5.75 5.64 5.89 5.74 5.70
95 TC 89.9 80.5 72.6 96.9 86.8 78.6 101.1 92.2 83.8 SHC 34.8 47.2 58.3 41.9 51.2 71.0 46.6 63.9 79.1 kW 6.42 6.33 6.22 6.52 6.45 6.31 6.62 6.43 6.40
105 TC 84.6 75.3 68.0 91.6 81.3 73.4 94.5 86.3 78.4 SHC 30.0 42.5 53.9 36.9 49.3 66.4 41.4 59.2 73.8 kW 7.26 7.16 7.05 7.36 7.25 7.15 7.46 7.29 7.23
115 TC 79.2 70.1 63.3 86.2 75.8 68.1 87.9 80.3 72.9 SHC 25.2 37.8 49.4 31.9 47.4 61.9 36.1 54.4 68.5 kW 8.10 7.99 7.87 8.20 8.05 7.98 8.30 8.14 8.05
125 TC 72.8 64.5 57.2 78.0 69.8 62.3 81.6 73.2 69.2 SHC 20.1 33.4 44.1 25.4 42.5 56.5 31.1 48.9 64.7 kW 9.10 8.94 8.83 9.23 9.05 8.95 9.26 9.10 8.99
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 2250 3000 3750 2250 3000 3750 2250 3000 3750
Air Ent Condenser
(Edb)
80 TC 37.74 40.54 42.68 38.48 41.35 43.55 39.12 42.05 44.29 SHC 10.67 15.63 19.63 5.01 9.84 13.74 0.10 4.82 8.63 kW 4.92 4.92 4.92 4.97 4.97 4.97 5.01 5.01 5.01
75 TC 37.34 39.95 41.95 38.08 40.75 42.81 38.72 41.45 43.55 SHC 9.83 14.48 18.24 4.52 9.05 12.70 –0.09 4.34 7.91 kW 5.19 5.19 5.19 5.25 5.25 5.25 5.30 5.30 5.30
70 TC 36.93 39.36 41.22 37.67 40.16 42.07 38.31 40.85 42.80 SHC 8.99 13.33 16.84 4.02 8.26 11.67 –0.28 3.86 7.19 kW 5.46 5.46 5.46 5.52 5.52 5.52 5.58 5.58 5.58
60 TC 36.13 38.18 39.75 36.87 38.97 40.58 37.51 39.66 41.31 SHC 7.31 11.04 14.04 3.04 6.67 9.60 –0.66 2.89 5.75 kW 5.99 5.99 5.99 6.08 6.08 6.08 6.15 6.15 6.15
50 TC 35.32 37.00 38.29 36.06 37.78 39.10 36.75 38.46 39.81 SHC 5.63 8.74 11.25 2.06 5.09 7.53 –1.03 1.93 4.32 kW 6.52 6.52 6.52 6.63 6.63 6.63 6.73 6.73 6.73
40 TC 34.52 35.82 36.82 35.26 36.60 37.62 35.90 37.27 38.32 SHC 3.94 6.44 8.45 1.08 3.51 5.47 –1.41 0.97 2.88 kW 7.05 7.05 7.05 7.18 7.18 7.18 7.30 7.30 7.30
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B102 (8 1 / 2 TONS) — SUBCOOLING MODE
Temp (F)
Air Entering Evaporator — Cfm/BF 2550/0.08 3000/0.09 3400/0.11 4250/0.13 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
(Edb)
75 TC 114.1 104.1 97.8 116.3 108.5 103.4 117.6 111.9 108.0 122.2 118.9 111.4 SHC 49.8 64.2 81.2 52.6 70.8 89.0 55.4 76.9 95.4 62.0 87.0 107.2 kW 5.57 5.46 5.44 5.59 5.50 5.44 5.60 5.51 5.44 5.62 5.62 5.69
85 TC 107.3 98.4 92.6 111.0 101.8 98.0 113.0 104.2 102.0 117.1 111.4 106.1 SHC 42.2 58.3 76.0 47.1 64.5 83.5 51.2 70.2 89.2 57.3 81.2 101.2 kW 6.32 6.30 6.15 6.32 6.27 6.18 6.34 6.22 6.20 6.30 6.31 6.45
95 TC 101.9 92.4 86.8 105.3 95.5 92.8 107.4 97.7 96.5 112.1 103.7 100.3 SHC 35.4 51.9 70.3 40.1 58.5 77.9 44.9 64.9 83.7 52.1 74.0 94.8 kW 7.06 7.13 6.93 7.06 7.06 6.95 7.06 6.99 6.98 7.01 7.04 7.17
105 TC 94.5 85.4 77.0 97.6 88.3 82.4 99.9 90.6 88.0 104.1 96.1 94.0 SHC 29.7 45.7 63.2 33.9 52.2 70.1 38.0 58.3 75.7 44.4 67.6 88.5 kW 7.99 8.00 7.81 8.01 7.97 7.85 8.02 7.94 7.89 7.96 7.96 8.08
115 TC 86.4 75.0 68.3 89.3 80.2 74.1 91.4 83.2 78.4 96.5 88.4 87.1 SHC 24.0 38.7 56.4 27.4 45.6 62.9 31.1 51.9 67.0 37.0 60.8 81.8 kW 8.91 8.83 8.66 8.93 8.86 8.76 8.97 8.86 8.84 8.91 8.93 8.90
125 TC 78.6 65.5 60.2 81.3 68.9 64.7 83.3 71.6 68.2 88.5 78.8 78.9 SHC 18.3 32.0 48.8 21.2 38.0 53.5 24.1 44.1 57.5 29.4 53.3 73.8 kW 9.81 9.65 9.53 9.86 9.68 9.64 9.89 9.71 9.75 9.90 9.72 9.88
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 2550 3000 3400 4250 2550 3000 3400 4250 2550 3000 3400 4250
Air Ent Condenser
(Edb)
80 TC 43.44 46.26 48.45 52.38 45.26 48.15 50.39 54.43 46.84 49.79 52.08 56.20 SHC 12.34 16.78 20.29 26.74 5.79 10.15 13.60 19.93 0.11 4.40 7.80 14.03 kW 6.31 6.05 5.83
75 TC 44.33 47.00 49.06 52.78 46.12 48.85 50.97 54.78 47.67 50.46 52.63 56.52 SHC 12.92 17.12 20.44 26.54 6.81 10.94 14.20 20.20 1.51 5.58 8.79 14.70 kW 6.38 6.38 6.8 6.38 6.15 5.95
70 TC 45.22 47.73 49.68 53.18 46.98 49.55 51.55 55.14 48.51 51.14 53.18 56.84 SHC 13.50 17.47 20.59 26.34 7.83 11.73 14.81 20.46 2.92 6.76 9.79 15.36 kW 6.46 6.25 6.07
60 TC 46.99 49.19 50.90 53.97 48.70 50.96 52.71 55.86 50.18 52.49 54.27 57.49 SHC 14.67 18.15 20.90 25.95 9.88 13.31 16.01 20.99 5.73 9.11 11.78 16.68 kW 6.60 6.45 6.32
50 TC 48.77 50.66 52.13 54.77 50.42 52.36 53.87 56.57 51.85 53.83 55.37 58.14 SHC 15.83 18.83 21.20 25.56 11.93 14.89 17.22 21.51 8.55 11.47 13.77 18.01 kW 6.74 6.64 6.56
40 TC 50.54 52.13 53.35 55.56 52.14 53.76 55.02 57.29 53.53 55.18 56.47 58.78 SHC 17.00 19.52 21.51 25.16 13.98 16.47 18.43 22.04 11.36 13.82 15.76 19.33 kW 6.88 6.84 6.81
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B120 (10 TONS) — SUBCOOLING MODE
Air Entering Evaporator — Cfm/BF 3000/0.03 3200/0.03 4000/0.04 5000/0.04 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
Air Ent Condenser
(Edb)
75 TC 134.3 122.5 111.4 135.8 124.3 113.0 138.4 129.5 123.5 143.3 136.5 130.2 SHC 60.0 76.1 93.7 61.3 79.1 97.4 68.0 89.5 109.4 75.2 100.9 123.3 kW 7.03 6.84 6.72 7.01 6.89 6.77 7.10 6.92 6.77 7.15 7.03 6.88
85 TC 127.6 115.4 104.6 128.9 118.1 107.0 132.5 121.5 116.6 137.2 128.0 122.9 SHC 51.5 68.8 87.2 53.9 72.0 91.2 61.0 82.7 102.4 68.6 93.6 115.9 kW 7.96 7.86 7.59 7.94 7.78 7.51 8.02 7.84 7.69 8.02 7.94 7.79
95 TC 120.9 108.3 97.8 121.9 111.8 101.0 126.5 113.4 109.7 131.1 119.4 115.5 SHC 43.0 61.5 80.6 46.5 64.8 84.9 53.9 75.9 95.4 62.0 86.2 108.4 kW 8.88 8.87 8.46 8.86 8.66 8.26 8.94 8.76 8.60 8.89 8.85 8.69
105 TC 112.0 99.9 90.4 113.1 103.2 93.4 117.2 105.0 100.7 122.1 110.5 105.9 SHC 36.1 54.1 73.8 38.8 57.8 78.9 45.6 68.2 86.8 53.0 78.3 99.7 kW 10.0 10.0 9.6 10.0 9.8 9.5 10.1 9.9 9.8 10.1 10.0 9.9
115 TC 103.0 91.5 83.1 104.3 94.6 85.9 107.8 96.7 91.7 113.0 101.6 96.4 SHC 29.2 46.7 66.9 31.2 50.7 72.9 37.3 60.6 78.3 44.0 70.3 90.9 kW 11.2 11.1 10.8 11.2 11.0 10.7 11.3 11.1 11.0 11.3 11.2 11.1
125 TC 94.1 83.1 75.7 95.5 86.0 78.3 98.5 88.3 82.7 104.0 92.7 86.8 SHC 22.3 39.3 60.1 23.5 43.7 66.8 29.0 52.9 69.7 35.0 62.4 82.2 kW 12.35 12.15 11.94 12.38 12.13 11.92 12.48 12.27 12.25 12.53 12.30 12.28
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 3000 3200 4000 5000 3000 3200 4000 5000 3000 3200 4000 5000
75 Dry Bulb 64 Wet Bulb (55% Relative)
(Edb)
80 TC 49.15 50.16 53.80 57.72 51.04 52.08 55.86 59.94 52.67 53.74 57.65 61.86 SHC 9.58 12.02 20.74 29.89 2.88 5.29 13.88 22.89 –2.92 -0.55 7.93 16.83 kW 7.39 7.38 7.38 7.37 7.45 7.45 7.44 7.43 7.50 7.50 7.49 7.49
75 TC 49.60 50.61 54.30 58.28 51.45 52.50 56.33 60.45 53.05 54.14 58.09 62.34 SHC 10.07 12.38 20.60 29.23 3.82 6.09 14.20 22.70 –1.60 0.64 8.65 17.05 kW 7.56 7.56 7.55 7.55 7.63 7.63 7.62 7.62 7.69 7.69 7.69 7.68
70 TC 50.04 51.07 54.81 58.83 51.86 52.92 56.80 60.96 53.43 54.53 58.52 62.82 SHC 10.56 12.73 20.47 28.58 4.75 6.89 14.52 22.52 –0.28 1.83 9.36 17.26 kW 7.73 7.73 7.72 7.72 7.81 7.81 7.81 7.80 7.89 7.88 7.88 7.87
60 TC 50.93 51.98 55.81 59.93 52.68 53.77 57.73 61.99 54.20 55.32 59.39 63.77 SHC 11.54 13.44 20.19 27.28 6.62 8.49 15.16 22.15 2.36 4.21 10.79 17.70 kW 8.07 8.07 8.07 8.06 8.18 8.18 8.17 8.17 8.27 8.27 8.26 8.26
50 TC 51.82 52.90 56.81 61.03 53.50 54.62 58.66 63.01 54.96 56.10 60.26 64.73 SHC 12.53 14.14 19.92 25.98 8.50 10.09 15.80 21.78 5.00 6.58 12.22 18.14 kW 8.42 8.42 8.41 8.41 8.54 8.66 8.65 8.65 8.65
40 TC 52.71 53.81 57.82 62.13 54.32 55.46 59.59 64.04 55.72 56.89 61.13 65.69 SHC 13.51 14.85 19.64 24.67 10.37 11.70 16.43 21.41 7.64 8.96 13.65 18.58 kW 8.76 8.76 8.76 8.75 8.91 8.91 8.91 8.90 9.04 9.04 9.04 9.03
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B150 (12 1 / 2 TONS) — SUBCOOLING MODE
Temp (F)
Air Entering Evaporator — Cfm/BF 3750/0.08 4300/0.09 5000/0.11 6250/0.13 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62
(Edb)
75 TC 156.3 144.2 132.3 160.0 148.4 136.2 162.8 150.6 138.2 169.0 157.5 145.6 SHC 66.6 87.6 112.1 72.5 94.8 121.3 76.9 99.6 127.5 87.0 115.5 142.7 kW 9.28 8.98 8.59 9.35 9.08 8.80 9.40 9.18 8.9 9.43 9.18 8.93
85 TC 147.6 136.2 123.7 150.7 140.1 127.2 154.1 140.8 127.9 161.1 148.0 135.4 SHC 58.7 80.0 103.8 63.5 86.5 112.2 68.7 91.0 118.1 77.7 107.8 133.2 kW 10.29 9.93 9.58 10.36 10.08 9.77 10.40 10.34 10.03 10.45 10.18 9.88
95 TC 138.9 128.2 115.1 141.4 131.8 118.3 145.3 131.0 117.6 153.1 138.4 125.1 SHC 50.8 72.3 95.5 54.4 78.1 103.2 60.5 82.3 108.7 68.5 100.0 123.7 kW 11.29 10.87 10.57 11.37 11.08 10.74 11.40 11.50 11.1 11.46 11.17 10.83
105 TC 129.1 117.8 105.8 131.7 121.0 108.7 134.8 119.9 107.7 140.9 126.9 115.9 SHC 42.1 63.5 86.5 45.4 69.0 93.9 51.2 74.2 101.3 57.7 90.2 113.6 kW 12.59 12.14 11.82 12.67 12.34 11.96 12.70 12.67 12.28 12.79 12.46 12.08
115 TC 119.2 107.3 96.4 122.1 110.2 99.0 124.2 108.8 97.8 128.7 115.3 106.7 SHC 33.5 54.8 77.5 36.4 59.8 84.7 41.9 66.1 93.8 46.8 80.5 103.5 kW 13.90 13.40 13.08 13.98 13.59 13.18 14.00 13.83 13.41 14.11 13.75 13.33
125 TC 109.4 96.9 87.1 112.4 99.4 89.3 113.7 97.7 87.8 116.5 103.8 97.5 SHC 24.8 46.0 68.5 27.4 50.7 75.5 32.6 58.0 86.4 36.0 70.7 93.5 kW 15.20 14.67 14.33 15.28 14.85 14.40 15.30 15.00 14.54 15.44 15.04 14.58
Air Entering Evaporator — Ewb (F) 75 Dry Bulb 62.5 Wet Bulb (50% Relative)
75 Dry Bulb 65.3 Wet Bulb (60% Relative) Air Entering Evaporator — Cfm 3750 4300 5000 6250 3750 4300 5000 6250 3750 4300 5000 6250
Air Ent Condenser
(Edb)
80 TC 43.54 45.21 47.05 49.78 45.46 47.16 49.05 51.85 47.11 48.86 50.78 53.64 SHC –4.36 0.76 6.50 15.20 –9.51 –4.35 1.45 10.22 –13.97 –8.77 –2.93 5.90 kW 8.70 8.82 8.92
75 TC 44.45 46.02 47.75 50.32 46.33 47.94 49.71 52.34 47.96 49.60 51.41 54.10 SHC –3.84 0.96 6.36 14.53 –8.66 –3.81 1.63 9.86 –12.84 –7.96 –2.48 5.82 kW 8.90 9.03 9.14
70 TC 45.36 46.82 48.45 50.86 47.20 48.71 50.37 52.84 48.80 50.34 52.04 54.55 SHC –3.32 1.17 6.21 13.85 –7.81 –3.28 1.80 9.50 –11.71 –7.14 –2.02 5.74 kW 9.10 9.24 9.36
60 TC 47.17 48.44 49.84 51.93 48.95 50.25 51.69 53.83 50.49 51.82 53.29 55.47 SHC –2.28 1.59 5.93 12.50 –6.12 –2.22 2.16 8.79 –9.45 –5.52 –1.11 5.57 kW 9.51 9.66 9.80
50 TC 48.98 50.05 51.24 53.00 50.70 51.80 53.01 54.82 52.18 53.31 54.55 56.39 SHC –1.24 2.00 5.64 11.15 –4.43 –1.15 2.52 8.07 –7.18 –3.89 –0.19 5.41 kW 9.91 10.09 10.24
40 TC 50.79 51.67 52.64 54.07 52.44 53.34 54.33 55.80 53.87 54.79 55.80 57.30 SHC –0.20 2.41 5.35 9.80 –2.73 –.019 2.87 7.36 –4.92 –2.26 0.72 5.24 kW 10.31 10.51 10.68
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
*Negative SHC value indicates that the air entering the coil is being heated. NOTES:
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 567 0.15 145 688 0.22 222 786 0.30 296 871 0.37 368 947 0.44 437 1000 599 0.18 177 717 0.27 265 814 0.35 349 897 0.43 430 972 0.51 509 1100 632 0.22 215 747 0.31 313 842 0.41 407 925 0.50 498 999 0.59 587 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960
581B036-150
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1016 0.51 505 1080 0.57 572 1139 0.64 637 1195 0.71 702 1249 0.77 765 1000 1041 0.59 587 1104 0.67 662 1163 0.74 737 1219 0.81 811 1272 0.89 883 1100 1066 0.68 674 1129 0.76 759 1188 0.85 843 1243 0.93 925 1296 1.01 1007 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 — — — 1400 1147 0.98 972 1208 1.09 1086 — 1500 1175 1.09 1086 —
Refer to this page for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 567 0.15 145 688 0.22 222 786 0.30 296 871 0.37 368 947 0.44 437 1000 599 0.18 177 717 0.27 265 814 0.35 349 897 0.43 430 972 0.51 509 1100 632 0.22 215 747 0.31 313 842 0.41 407 925 0.50 498 999 0.59 587 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1016 0.51 505 1080 0.57 572 1139 0.64 637 1195 0.71 702 1249 0.77 765 1000 1041 0.59 587 1104 0.67 662 1163 0.74 737 1219 0.81 811 1272 0.89 883 1100 1066 0.68 674 1129 0.76 759 1188 0.85 843 1243 0.93 925 1296 1.01 1007 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572
Refer to this page for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES 1. Static pressure losses (i.e., EconoMi$er IV) must be added to external static pressure before entering Fan Performance table. 2. Interpolation is permissible. Do not extrapolate. 3. Fan performance is based on wet coils, clean filters, and casing losses. See Accessory/FIOP Static Pressure table on page 133. 4. Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with
confidence. Using the fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire size. Contact your Bryant representative for details.

581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 — — — 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 — 2000 962 0.85 847 1049 1.05 1043 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 — — — 1400 1147 0.98 972 1208 1.09 1086 — 1500 1175 1.09 1086 — 1600 — 1700 — 1800 — 1900 — 2000 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1200 1.32 1316 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 1165 1.29 1283 1231 1.46 1453 2000 962 0.85 847 1049 1.05 1043 1127 1.24 1233 1198 1.42 1417 1263 1.61 1598
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572 1600 1204 1.21 1207 1263 1.35 1340 1320 1.48 1472 1373 1.61 1603 1424 1.74 1732 1700 1233 1.34 1336 1292 1.49 1480 1348 1.63 1622 1401 1.77 1762 1451 1.91 1901 1800 1262 1.48 1473 1321 1.64 1627 1376 1.79 1779 1428 1.94 1930 1479 2.09 2078 1900 1293 1.63 1620 1350 1.79 1784 1405 1.96 1946 1457 2.12 2106 1506 2.28 2265 2000 1323 1.79 1776 1380 1.96 1950 1434 2.13 2123 1486 2.31 2293 — — —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.

581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 — — — 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 — 2100 1090 0.97 859 1191 1.15 1023 — 2200 1131 1.09 970 1230 1.29 1143 — 2300 1173 1.23 1091 — 2400 — 2500 —
581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 — 1600 1342 1.18 1047 — 1700 1374 1.30 1153 — 1800 — 1900 — 2000 — 2100 — 2200 — 2300 — 2400 — 2500 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.
581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 — — —
581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 1445 1.34 1189 1506 1.48 1312 1564 1.62 1437 1600 1342 1.18 1047 1411 1.32 1173 1474 1.46 1300 1535 1.61 1429 1593 1.76 1560 1700 1374 1.30 1153 1441 1.45 1286 1505 1.60 1420 1565 1.75 1555 1622 1.91 1692 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 — — — 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 — 2200 1538 2.04 1816 1602 2.23 1984 — 2300 1572 2.23 1978 — 2400 — 2500 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.

581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 1576 2.41 2142
581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 1445 1.34 1189 1506 1.48 1312 1564 1.62 1437 1600 1342 1.18 1047 1411 1.32 1173 1474 1.46 1300 1535 1.61 1429 1593 1.76 1560 1700 1374 1.30 1153 1441 1.45 1286 1505 1.60 1420 1565 1.75 1555 1622 1.91 1692 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 1713 2.41 2142 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 1688 2.42 2149 1744 2.60 2312 2200 1538 2.04 1816 1602 2.23 1984 1663 2.42 2152 1720 2.61 2321 1775 2.81 2491 2300 1572 2.23 1978 1635 2.42 2153 1695 2.62 2328 1753 2.82 2504 — — — 2400 1607 2.42 2150 1669 2.63 2332 1729 2.83 2515 — 2500 1642 2.63 2333 1704 2.84 2523 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 967 0.63 563 1075 0.80 715 1170 0.97 861 1255 1.13 1002 1333 1.28 1139 1900 1008 0.72 643 1112 0.91 805 1205 1.08 960 1289 1.25 1111 1366 1.42 1258 2000 1049 0.82 731 1151 1.02 903 1241 1.20 1068 1323 1.38 1228 1399 1.56 1384 2100 1091 0.93 827 1189 1.14 1008 1278 1.33 1183 1358 1.52 1353 1433 1.71 1519 2200 1133 1.05 933 1229 1.26 1123 1315 1.47 1308 1393 1.67 1487 1467 1.87 1662 2300 1176 1.18 1047 1268 1.40 1247 1352 1.62 1441 1429 1.84 1630 1501 2.04 1815 2400 1218 1.32 1170 1308 1.55 1380 1390 1.78 1584 1466 2.01 1782 1537 2.23 1977 2500 1261 1.47 1304 1349 1.72 1523 1429 1.96 1736 1503 2.19 1945 — — — 2600 1305 1.63 1448 1390 1.89 1677 1468 2.14 1900 1540 2.38 2117 — — — 2700 1348 1.80 1602 1431 2.07 1841 1507 2.33 2073 — 2800 1392 1.99 1768 1472 2.27 2016 — 2900 1435 2.19 1945 — 3000 1479 2.40 2135 —
581B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1406 1.43 1273 1475 1.58 1403 1540 1.72 1531 1601 1.87 1657 1660 2.00 1780 1900 1438 1.58 1401 1505 1.73 1541 1569 1.89 1678 1630 2.04 1813 1689 2.19 1945 2000 1470 1.73 1537 1537 1.90 1686 1600 2.06 1833 1660 2.23 1977 1718 2.38 2118 2100 1502 1.89 1681 1568 2.07 1840 1631 2.25 1996 — 2200 1535 2.06 1834 1600 2.25 2002 — 2300 1569 2.25 1996 — 2400 — 2500 — 2600 — 2700 — 2800 — 2900 — 3000 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-supplied drive.

581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 967 0.63 563 1075 0.80 715 1170 0.97 861 1255 1.13 1002 1333 1.28 1139 1900 1008 0.72 643 1112 0.91 805 1205 1.08 960 1289 1.25 1111 1366 1.42 1258 2000 1049 0.82 731 1151 1.02 903 1241 1.20 1068 1323 1.38 1228 1399 1.56 1384 2100 1091 0.93 827 1189 1.14 1008 1278 1.33 1183 1358 1.52 1353 1433 1.71 1519 2200 1133 1.05 933 1229 1.26 1123 1315 1.47 1308 1393 1.67 1487 1467 1.87 1662 2300 1176 1.18 1047 1268 1.40 1247 1352 1.62 1441 1429 1.84 1630 1501 2.04 1815 2400 1218 1.32 1170 1308 1.55 1380 1390 1.78 1584 1466 2.01 1782 1537 2.23 1977 2500 1261 1.47 1304 1349 1.72 1523 1429 1.96 1736 1503 2.19 1945 1572 2.42 2149 2600 1305 1.63 1448 1390 1.89 1677 1468 2.14 1900 1540 2.38 2117 1608 2.62 2331 2700 1348 1.80 1602 1431 2.07 1841 1507 2.33 2073 1578 2.59 2301 1645 2.84 2524 2800 1392 1.99 1768 1472 2.27 2016 1547 2.54 2258 1616 2.81 2495 — — — 2900 1435 2.19 1945 1514 2.48 2203 1587 2.76 2455 — 3000 1479 2.40 2135 1556 2.70 2402 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1406 1.43 1273 1475 1.58 1403 1540 1.72 1531 1601 1.87 1657 1660 2.00 1780 1900 1438 1.58 1401 1505 1.73 1541 1569 1.89 1678 1630 2.04 1813 1689 2.19 1945 2000 1470 1.73 1537 1537 1.90 1686 1600 2.06 1833 1660 2.23 1977 1718 2.38 2118 2100 1502 1.89 1681 1568 2.07 1840 1631 2.25 1996 1690 2.42 2149 1747 2.59 2300 2200 1535 2.06 1834 1600 2.25 2002 1662 2.44 2167 1721 2.62 2330 1778 2.80 2490 2300 1569 2.25 1996 1633 2.45 2174 1694 2.64 2348 1752 2.84 2520 — — — 2400 1603 2.44 2167 1666 2.65 2355 1727 2.86 2539 — 2500 1638 2.64 2349 1700 2.87 2546 — 2600 1673 2.86 2541 — 2700 — 2800 — 2900 — 3000 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field- supplied drive.

581B090 (7 1 / 2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 — — — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 — — — 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 — — — 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 935 2.52 2345 980 2.87 2673 — — — 2300 844 1.90 1773 893 2.22 2073 940 2.56 2389 — 2400 854 1.99 1855 903 2.32 2159 950 2.66 2478 — 2500 865 2.08 1940 913 2.41 2249 959 2.76 2573 — 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 — 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 — 2700 886 2.28 2126 934 2.62 2445 — 2800 897 2.39 2227 944 2.73 2550 — 2900 908 2.50 2333 955 2.85 2661 — 3000 920 2.62 2443 — 3100 931 2.75 2560 — 3200 943 2.88 2682 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field- sup- plied drive.

581B090 (7 1 / 2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 935 2.52 2345 980 2.87 2673 1022 3.23 3015 2300 844 1.90 1773 893 2.22 2073 940 2.56 2389 984 2.91 2718 1027 3.28 3062 2400 854 1.99 1855 903 2.32 2159 950 2.66 2478 993 3.02 2812 1035 3.39 3159 2500 865 2.08 1940 913 2.41 2249 959 2.76 2573 1003 3.12 2911 1044 3.50 3261 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 1063 3.74 3483 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 1073 3.86 3601 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 1083 4.00 3725 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 1052 3.74 3484 1093 4.14 3856 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 1063 3.88 3615 — — — 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 1074 4.02 3752 — — — 3300 955 3.01 2810 1000 3.39 3159 1043 3.78 3521 1084 4.18 3896 — — — 3400 967 3.16 2945 1012 3.54 3299 1055 3.93 3667 — 3500 980 3.31 3084 1024 3.69 3445 1066 4.09 3817 — 3600 992 3.46 3230 1036 3.86 3596 — 3700 1005 3.63 3383 1048 4.03 3755 — 3750 1011 3.71 3462 1054 4.11 3836 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- sup- plied drive.

581B102 (8 1 / 2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 541 0.50 467 624 0.66 614 701 0.83 771 771 1.00 936 837 1.19 1109 2600 556 0.55 513 637 0.71 665 711 0.89 827 781 1.07 996 845 1.26 1173 2700 571 0.60 562 650 0.77 720 722 0.95 885 790 1.14 1059 854 1.33 1241 2800 586 0.66 615 663 0.83 777 734 1.02 948 800 1.21 1126 863 1.41 1312 2900 601 0.72 672 676 0.90 839 745 1.09 1014 811 1.28 1197 872 1.49 1387 3000 616 0.79 732 689 0.97 904 757 1.16 1083 821 1.36 1271 882 1.57 1465 3100 632 0.85 796 703 1.04 972 769 1.24 1157 832 1.45 1349 892 1.66 1548 3200 648 0.93 864 717 1.12 1045 782 1.32 1235 843 1.53 1431 902 1.75 1635 3300 663 1.00 936 731 1.20 1122 795 1.41 1316 855 1.63 1517 912 1.85 1725 3400 679 1.09 1012 745 1.29 1203 808 1.50 1402 867 1.72 1608 923 1.95 1820 3500 695 1.17 1092 760 1.38 1288 821 1.60 1492 879 1.83 1703 934 2.06 1920 3600 711 1.26 1177 774 1.48 1379 834 1.70 1587 891 1.93 1802 945 2.17 2024 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 — — — 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 — — —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 900 1.38 1289 959 1.58 1476 1015 1.79 1669 1069 2.00 1868 1121 2.22 2073 2600 907 1.46 1357 965 1.66 1548 1021 1.87 1745 1074 2.09 1948 1125 2.31 2158 2700 914 1.53 1429 972 1.74 1624 1027 1.96 1825 1079 2.18 2032 1130 2.41 2245 2800 922 1.61 1505 979 1.83 1704 1033 2.05 1909 1085 2.27 2120 1135 2.51 2337 2900 931 1.70 1584 986 1.92 1787 1040 2.14 1996 1091 2.37 2211 1141 2.61 2432 3000 939 1.79 1667 994 2.01 1874 1047 2.24 2087 1098 2.47 2307 1147 2.71 2532 3100 948 1.88 1753 1002 2.11 1965 1054 2.34 2183 1105 2.58 2406 1153 2.83 2635 3200 957 1.98 1844 1011 2.21 2060 1062 2.45 2283 1112 2.69 2510 — — — 3300 967 2.08 1939 1020 2.32 2160 1070 2.56 2386 1119 2.81 2618 — — — 3400 977 2.19 2039 1029 2.43 2264 1079 2.67 2494 — 3500 987 2.30 2143 1038 2.54 2372 1088 2.80 2607 — 3600 998 2.41 2251 1048 2.66 2485 — 3700 1008 2.54 2364 1058 2.79 2602 — 3800 1019 2.66 2482 — 3900 1031 2.79 2605 — 4000 — 4100 — 4200 — 4300 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field- sup- plied drive.

581B102 (8 1 / 2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 541 0.50 467 624 0.66 614 701 0.83 771 771 1.00 936 837 1.19 1109 2600 556 0.55 513 637 0.71 665 711 0.89 827 781 1.07 996 845 1.26 1173 2700 571 0.60 562 650 0.77 720 722 0.95 885 790 1.14 1059 854 1.33 1241 2800 586 0.66 615 663 0.83 777 734 1.02 948 800 1.21 1126 863 1.41 1312 2900 601 0.72 672 676 0.90 839 745 1.09 1014 811 1.28 1197 872 1.49 1387 3000 616 0.79 732 689 0.97 904 757 1.16 1083 821 1.36 1271 882 1.57 1465 3100 632 0.85 796 703 1.04 972 769 1.24 1157 832 1.45 1349 892 1.66 1548 3200 648 0.93 864 717 1.12 1045 782 1.32 1235 843 1.53 1431 902 1.75 1635 3300 663 1.00 936 731 1.20 1122 795 1.41 1316 855 1.63 1517 912 1.85 1725 3400 679 1.09 1012 745 1.29 1203 808 1.50 1402 867 1.72 1608 923 1.95 1820 3500 695 1.17 1092 760 1.38 1288 821 1.60 1492 879 1.83 1703 934 2.06 1920 3600 711 1.26 1177 774 1.48 1379 834 1.70 1587 891 1.93 1802 945 2.17 2024 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 900 1.38 1289 959 1.58 1476 1015 1.79 1669 1069 2.00 1868 1121 2.22 2073 2600 907 1.46 1357 965 1.66 1548 1021 1.87 1745 1074 2.09 1948 1125 2.31 2158 2700 914 1.53 1429 972 1.74 1624 1027 1.96 1825 1079 2.18 2032 1130 2.41 2245 2800 922 1.61 1505 979 1.83 1704 1033 2.05 1909 1085 2.27 2120 1135 2.51 2337 2900 931 1.70 1584 986 1.92 1787 1040 2.14 1996 1091 2.37 2211 1141 2.61 2432 3000 939 1.79 1667 994 2.01 1874 1047 2.24 2087 1098 2.47 2307 1147 2.71 2532 3100 948 1.88 1753 1002 2.11 1965 1054 2.34 2183 1105 2.58 2406 1153 2.83 2635 3200 957 1.98 1844 1011 2.21 2060 1062 2.45 2283 1112 2.69 2510 1160 2.94 2743 3300 967 2.08 1939 1020 2.32 2160 1070 2.56 2386 1119 2.81 2618 1167 3.06 2855 3400 977 2.19 2039 1029 2.43 2264 1079 2.67 2494 1127 2.93 2730 1174 3.19 2971 3500 987 2.30 2143 1038 2.54 2372 1088 2.80 2607 1135 3.05 2847 1181 3.32 3092 3600 998 2.41 2251 1048 2.66 2485 1097 2.92 2724 1144 3.18 2968 1189 3.45 3218 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 — — — 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- sup- plied drive.

581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 616 0.79 732 689 0.97 904 757 1.16 1083 821 1.36 1271 882 1.57 1465 3100 632 0.85 796 703 1.04 972 769 1.24 1157 832 1.45 1349 892 1.66 1548 3200 648 0.93 864 717 1.12 1045 782 1.32 1235 843 1.53 1431 902 1.75 1635 3300 663 1.00 936 731 1.20 1122 795 1.41 1316 855 1.63 1517 912 1.85 1725 3400 679 1.09 1012 745 1.29 1203 808 1.50 1402 867 1.72 1608 923 1.95 1820 3500 695 1.17 1092 760 1.38 1288 821 1.60 1492 879 1.83 1703 934 2.06 1920 3600 711 1.26 1177 774 1.48 1379 834 1.70 1587 891 1.93 1802 945 2.17 2024 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 — — — 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 — — — 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 — 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 939 1.79 1667 994 2.01 1874 1047 2.24 2087 1098 2.47 2307 1147 2.71 2532 3100 948 1.88 1753 1002 2.11 1965 1054 2.34 2183 1105 2.58 2406 1153 2.83 2635 3200 957 1.98 1844 1011 2.21 2060 1062 2.45 2283 1112 2.69 2510 1160 2.94 2743 3300 967 2.08 1939 1020 2.32 2160 1070 2.56 2386 1119 2.81 2618 1167 3.06 2855 3400 977 2.19 2039 1029 2.43 2264 1079 2.67 2494 1127 2.93 2730 1174 3.19 2971 3500 987 2.30 2143 1038 2.54 2372 1088 2.80 2607 1135 3.05 2847 1181 3.32 3092 3600 998 2.41 2251 1048 2.66 2485 1097 2.92 2724 1144 3.18 2968 1189 3.45 3218 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 — — — 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 — — — 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 — 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 — 4200 1066 3.22 3004 1112 3.50 3264 — 4300 1078 3.38 3148 1123 3.66 3413 — 4400 1090 3.54 3297 — 4500 1103 3.70 3451 — 4600 — 4700 — 4800 — 4900 — 5000 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- sup- plied drive.

581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 616 0.79 732 689 0.97 904 757 1.16 1083 821 1.36 1271 882 1.57 1465 3100 632 0.85 796 703 1.04 972 769 1.24 1157 832 1.45 1349 892 1.66 1548 3200 648 0.93 864 717 1.12 1045 782 1.32 1235 843 1.53 1431 902 1.75 1635 3300 663 1.00 936 731 1.20 1122 795 1.41 1316 855 1.63 1517 912 1.85 1725 3400 679 1.09 1012 745 1.29 1203 808 1.50 1402 867 1.72 1608 923 1.95 1820 3500 695 1.17 1092 760 1.38 1288 821 1.60 1492 879 1.83 1703 934 2.06 1920 3600 711 1.26 1177 774 1.48 1379 834 1.70 1587 891 1.93 1802 945 2.17 2024 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 1084 3.75 3500 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 1098 3.93 3668 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 1067 3.82 3558 1111 4.12 3841 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 1082 4.00 3733 1125 4.31 4021
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 939 1.79 1667 994 2.01 1874 1047 2.24 2087 1098 2.47 2307 1147 2.71 2532 3100 948 1.88 1753 1002 2.11 1965 1054 2.34 2183 1105 2.58 2406 1153 2.83 2635 3200 957 1.98 1844 1011 2.21 2060 1062 2.45 2283 1112 2.69 2510 1160 2.94 2743 3300 967 2.08 1939 1020 2.32 2160 1070 2.56 2386 1119 2.81 2618 1167 3.06 2855 3400 977 2.19 2039 1029 2.43 2264 1079 2.67 2494 1127 2.93 2730 1174 3.19 2971 3500 987 2.30 2143 1038 2.54 2372 1088 2.80 2607 1135 3.05 2847 1181 3.32 3092 3600 998 2.41 2251 1048 2.66 2485 1097 2.92 2724 1144 3.18 2968 1189 3.45 3218 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 1243 4.37 4077 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 1210 4.24 3958 1252 4.54 4238 4400 1090 3.54 3297 1135 3.82 3566 1179 4.12 3841 1221 4.42 4121 1262 4.72 4405 4500 1103 3.70 3451 1147 4.00 3726 1190 4.29 4005 1232 4.60 4289 1273 4.91 4578 4600 1115 3.87 3612 1159 4.17 3891 1201 4.48 4175 1243 4.79 4464 1283 5.10 4757 4700 1128 4.05 3778 1171 4.36 4062 1213 4.67 4350 1254 4.98 4644 — — — 4800 1141 4.24 3951 1183 4.55 4239 1225 4.86 4532 1265 5.18 4830 — — — 4900 1154 4.43 4130 1196 4.74 4422 1237 5.06 4720 — 5000 1167 4.63 4314 1209 4.95 4611 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- sup- plied drive.

581B150 (12 1 / 2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 1084 3.75 3500 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 1098 3.93 3668 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 1067 3.82 3558 1111 4.12 3841 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 1082 4.00 3733 1125 4.31 4021 5100 961 3.29 3068 1007 3.59 3345 1053 3.89 3627 1096 4.20 3915 1139 4.51 4208 5200 978 3.48 3241 1024 3.78 3523 1068 4.09 3811 1111 4.40 4103 1153 4.72 4400 5300 995 3.67 3420 1040 3.98 3707 1084 4.29 4000 1126 4.61 4298 1168 4.93 4600 5400 1012 3.87 3606 1056 4.18 3899 1099 4.50 4196 1141 4.82 4499 1182 5.15 4806 5500 1029 4.07 3799 1073 4.39 4097 1115 4.72 4400 1156 5.05 4707 — — — 5600 1046 4.29 3999 1089 4.61 4302 1131 4.94 4610 — 5700 1063 4.51 4207 1105 4.84 4515 1146 5.18 4827 — 5800 1080 4.74 4420 1122 5.08 4734 — 5900 1098 4.98 4642 — 6000 1115 5.22 4872 — 6100 — 6200 — 6300 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 1243 4.37 4077 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 1210 4.24 3958 1252 4.54 4238 4400 1090 3.54 3297 1135 3.82 3566 1179 4.12 3841 1221 4.42 4121 1262 4.72 4405 4500 1103 3.70 3451 1147 4.00 3726 1190 4.29 4005 1232 4.60 4289 1273 4.91 4578 4600 1115 3.87 3612 1159 4.17 3891 1201 4.48 4175 1243 4.79 4464 1283 5.10 4757 4700 1128 4.05 3778 1171 4.36 4062 1213 4.67 4350 1254 4.98 4644 — — — 4800 1141 4.24 3951 1183 4.55 4239 1225 4.86 4532 1265 5.18 4830 — — — 4900 1154 4.43 4130 1196 4.74 4422 1237 5.06 4720 — 5000 1167 4.63 4314 1209 4.95 4611 — 5100 1181 4.83 4505 1221 5.16 4808 — 5200 1194 5.04 4703 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- sup- plied drive.

581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 553 0.14 134 681 0.22 221 782 0.32 316 870 0.42 417 948 0.53 526 1000 582 0.16 163 707 0.26 257 807 0.36 358 894 0.47 466 971 0.58 580 1100 612 0.20 196 734 0.30 297 833 0.41 405 919 0.52 519 995 0.64 639 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941
581B036-150
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1019 0.64 640 1084 0.76 760 1146 0.89 885 1203 1.02 1016 1258 1.16 1152 1000 1042 0.70 700 1107 0.83 825 1168 0.96 956 1225 1.10 1091 — — — 1100 1065 0.77 765 1130 0.90 896 1190 1.04 1032 1247 1.18 1173 — — — 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 — 1300 1113 0.92 915 1177 1.06 1058 — 1400 1138 1.01 1000 1201 1.15 1149 — 1500 1163 1.10 1092 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- sup- plied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 553 0.14 134 681 0.22 221 782 0.32 316 870 0.42 417 948 0.53 526 1000 582 0.16 163 707 0.26 257 807 0.36 358 894 0.47 466 971 0.58 580 1100 612 0.20 196 734 0.30 297 833 0.41 405 919 0.52 519 995 0.64 639 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1019 0.64 640 1084 0.76 760 1146 0.89 885 1203 1.02 1016 1258 1.16 1152 1000 1042 0.70 700 1107 0.83 825 1168 0.96 956 1225 1.10 1091 1279 1.24 1232 1100 1065 0.77 765 1130 0.90 896 1190 1.04 1032 1247 1.18 1173 1301 1.33 1319 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.

581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 — — — 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 — — — 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 — 1300 1113 0.92 915 1177 1.06 1058 — 1400 1138 1.01 1000 1201 1.15 1149 — 1500 1163 1.10 1092 — 1600 1189 1.20 1191 — 1700 — 1800 — 1900 — 2000 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1177 1.25 1242 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 1205 1.37 1360 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 1165 1.31 1302 1234 1.49 1485
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740 1600 1189 1.20 1191 1252 1.36 1353 1310 1.53 1520 1365 1.70 1690 1418 1.87 1865 1700 1216 1.31 1299 1277 1.48 1468 1335 1.65 1640 1390 1.83 1817 1442 2.01 1998 1800 1242 1.42 1414 1303 1.60 1590 1361 1.78 1770 1415 1.96 1953 1467 2.15 2140 1900 1270 1.55 1538 1330 1.73 1721 1387 1.92 1908 1441 2.11 2098 1493 2.30 2292 2000 1297 1.68 1672 1357 1.87 1862 1414 2.07 2055 1467 2.26 2252 — — —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.

581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 — — — 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 — 2200 1085 1.09 966 1162 1.22 1086 — 2300 1127 1.23 1092 — 2400 — 2500 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 — 1600 1270 1.07 952 1342 1.22 1083 — 1700 1295 1.17 1040 — 1800 1321 1.28 1137 — 1900 — 2000 — 2100 — 2200 — 2300 — 2400 — 2500 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 1457 1.44 1280 1522 1.61 1430 1600 1270 1.07 952 1342 1.22 1083 1411 1.37 1221 1476 1.54 1365 1540 1.71 1517 1700 1295 1.17 1040 1365 1.32 1173 1432 1.48 1313 1497 1.64 1459 1559 1.82 1612 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 — — — 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 — 2400 1500 2.17 1928 1559 2.35 2083 — 2500 1533 2.36 2098 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field- supplied drive.

581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945
581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 1457 1.44 1280 1522 1.61 1430 1600 1270 1.07 952 1342 1.22 1083 1411 1.37 1221 1476 1.54 1365 1540 1.71 1517 1700 1295 1.17 1040 1365 1.32 1173 1432 1.48 1313 1497 1.64 1459 1559 1.82 1612 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 1673 2.53 2246 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 1644 2.52 2239 1699 2.71 2406 2400 1500 2.17 1928 1559 2.35 2083 1616 2.53 2243 1672 2.71 2408 1726 2.90 2579 2500 1533 2.36 2098 1591 2.54 2257 1647 2.73 2421 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 913 0.64 569 1010 0.80 715 1098 0.98 869 1178 1.16 1032 1252 1.35 1203 1900 952 0.73 652 1046 0.91 805 1131 1.09 965 1210 1.28 1134 1282 1.48 1311 2000 992 0.84 744 1083 1.02 903 1166 1.21 1070 1242 1.40 1245 1313 1.61 1427 2100 1032 0.95 844 1120 1.14 1010 1200 1.33 1184 1275 1.54 1365 1345 1.75 1553 2200 1073 1.07 954 1158 1.27 1127 1236 1.47 1307 1308 1.68 1495 1377 1.90 1689 2300 1114 1.21 1074 1196 1.41 1254 1272 1.62 1440 1343 1.84 1634 1409 2.07 1834 2400 1155 1.36 1204 1234 1.57 1391 1308 1.78 1584 1377 2.01 1784 1443 2.24 1990 2500 1196 1.51 1345 1273 1.73 1538 1345 1.96 1738 1412 2.19 1945 — — — 2600 1238 1.69 1497 1312 1.91 1697 1382 2.14 1904 1448 2.38 2117 — — — 2700 1280 1.87 1660 1352 2.10 1867 1420 2.34 2081 — 2800 1322 2.07 1835 1392 2.31 2050 — 2900 1364 2.28 2023 — 3000 —
581B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1322 1.56 1382 1388 1.77 1568 1451 1.98 1762 1510 2.21 1962 — — — 1900 1351 1.68 1495 1416 1.90 1686 1477 2.12 1885 1536 2.35 2090 — — — 2000 1380 1.82 1617 1444 2.04 1814 1505 2.27 2017 — 2100 1411 1.97 1748 1473 2.20 1950 — 2200 1441 2.13 1890 1503 2.36 2097 — 2300 1473 2.30 2041 — 2400 — 2500 — 2600 — 2700 — 2800 — 2900 — 3000 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-supplied drive.

581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 913 0.64 569 1010 0.80 715 1098 0.98 869 1178 1.16 1032 1252 1.35 1203 1900 952 0.73 652 1046 0.91 805 1131 1.09 965 1210 1.28 1134 1282 1.48 1311 2000 992 0.84 744 1083 1.02 903 1166 1.21 1070 1242 1.40 1245 1313 1.61 1427 2100 1032 0.95 844 1120 1.14 1010 1200 1.33 1184 1275 1.54 1365 1345 1.75 1553 2200 1073 1.07 954 1158 1.27 1127 1236 1.47 1307 1308 1.68 1495 1377 1.90 1689 2300 1114 1.21 1074 1196 1.41 1254 1272 1.62 1440 1343 1.84 1634 1409 2.07 1834 2400 1155 1.36 1204 1234 1.57 1391 1308 1.78 1584 1377 2.01 1784 1443 2.24 1990 2500 1196 1.51 1345 1273 1.73 1538 1345 1.96 1738 1412 2.19 1945 1477 2.43 2157 2600 1238 1.69 1497 1312 1.91 1697 1382 2.14 1904 1448 2.38 2117 1511 2.63 2335 2700 1280 1.87 1660 1352 2.10 1867 1420 2.34 2081 1484 2.59 2300 1546 2.84 2526 2800 1322 2.07 1835 1392 2.31 2050 1458 2.56 2270 1521 2.81 2496 — — — 2900 1364 2.28 2023 1432 2.53 2245 1496 2.78 2472 — 3000 1406 2.50 2224 1472 2.76 2452 —
581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1322 1.56 1382 1388 1.77 1568 1451 1.98 1762 1510 2.21 1962 1568 2.44 2169 1900 1351 1.68 1495 1416 1.90 1686 1477 2.12 1885 1536 2.35 2090 1593 2.59 2302 2000 1380 1.82 1617 1444 2.04 1814 1505 2.27 2017 1563 2.51 2227 1619 2.75 2443 2100 1411 1.97 1748 1473 2.20 1950 1533 2.43 2159 1590 2.67 2374 — — — 2200 1441 2.13 1890 1503 2.36 2097 1562 2.60 2311 1618 2.85 2532 — — — 2300 1473 2.30 2041 1533 2.54 2254 1591 2.79 2474 — 2400 1505 2.48 2203 1564 2.73 2422 — 2500 1537 2.68 2376 — 2600 1571 2.88 2560 — 2700 — 2800 — 2900 — 3000 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1686 rpm. All other rpms require field- supplied drive.

581B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 — — — 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 — — — 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 — — —
581B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 941 2.46 2297 988 2.82 2629 — — — 2300 842 1.84 1719 895 2.17 2019 944 2.51 2336 992 2.86 2669 — — — 2400 851 1.92 1793 903 2.25 2097 952 2.59 2416 — 2500 860 2.01 1873 911 2.34 2180 960 2.68 2502 — 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 — 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 — 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 — 2800 889 2.29 2140 938 2.64 2458 — 2900 899 2.40 2239 948 2.75 2561 — 3000 910 2.51 2343 958 2.86 2670 — 3100 921 2.63 2453 — 3200 932 2.75 2569 — 3300 943 2.88 2690 — 3400 — 3500 — 3600 — 3700 — 3750 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-supplied drive.

581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962
581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 941 2.46 2297 988 2.82 2629 1033 3.19 2976 2300 842 1.84 1719 895 2.17 2019 944 2.51 2336 992 2.86 2669 1037 3.24 3018 2400 851 1.92 1793 903 2.25 2097 952 2.59 2416 999 2.95 2752 1043 3.33 3104 2500 860 2.01 1873 911 2.34 2180 960 2.68 2502 1006 3.05 2842 1051 3.43 3196 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 1073 3.76 3503 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 1082 3.88 3616 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 1090 4.01 3736 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 1057 3.74 3488 1099 4.14 3861 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 1066 3.88 3616 — — — 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 1076 4.02 3749 — — — 3400 954 3.02 2816 1000 3.39 3159 1044 3.77 3518 1086 4.17 3889 — — — 3500 966 3.16 2950 1011 3.54 3297 1054 3.92 3660 — 3600 978 3.31 3088 1022 3.69 3442 1065 4.08 3808 — 3700 990 3.47 3233 1034 3.85 3591 — 3750 996 3.55 3308 1040 3.93 3669 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

581B102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 513 0.45 423 603 0.62 576 682 0.78 732 753 0.96 892 817 1.13 1055 2600 526 0.50 463 614 0.67 621 692 0.84 783 761 1.02 948 825 1.20 1117 2700 539 0.54 505 625 0.72 670 702 0.90 837 770 1.08 1008 834 1.27 1182 2800 552 0.59 551 637 0.77 721 712 0.96 894 780 1.15 1070 842 1.34 1250 2900 565 0.64 599 648 0.83 775 722 1.02 954 789 1.22 1136 851 1.42 1321 3000 579 0.70 651 660 0.89 832 732 1.09 1017 799 1.29 1204 860 1.50 1395 3100 592 0.76 706 672 0.96 893 743 1.16 1083 808 1.37 1276 869 1.58 1471 3200 606 0.82 764 684 1.03 957 754 1.24 1153 818 1.45 1351 878 1.66 1552 3300 620 0.88 825 696 1.10 1024 765 1.31 1225 829 1.53 1429 888 1.75 1636 3400 634 0.95 890 709 1.17 1095 777 1.40 1302 839 1.62 1511 897 1.85 1723 3500 648 1.03 958 721 1.25 1169 788 1.48 1381 850 1.71 1597 907 1.95 1815 3600 662 1.10 1030 734 1.34 1246 800 1.57 1465 860 1.81 1686 917 2.05 1909 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686
581B102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 877 1.31 1222 933 1.49 1392 986 1.68 1565 1037 1.87 1742 1085 2.06 1921 2600 885 1.38 1289 940 1.57 1464 993 1.76 1643 1043 1.96 1824 1091 2.15 2008 2700 892 1.46 1359 948 1.65 1540 1000 1.85 1723 1049 2.05 1909 1097 2.25 2099 2800 900 1.54 1432 955 1.74 1618 1007 1.94 1807 1056 2.14 1998 1103 2.35 2192 2900 908 1.62 1508 963 1.82 1699 1014 2.03 1893 1063 2.24 2089 1110 2.45 2289 3000 917 1.70 1587 970 1.91 1784 1021 2.13 1983 1070 2.34 2185 1117 2.56 2389 3100 925 1.79 1670 979 2.01 1872 1029 2.23 2076 1077 2.45 2283 1123 2.67 2492 3200 934 1.88 1756 987 2.10 1963 1037 2.33 2172 1085 2.56 2384 1131 2.79 2599 3300 943 1.98 1845 995 2.21 2057 1045 2.44 2272 1092 2.67 2490 — — — 3400 952 2.08 1939 1004 2.31 2156 1053 2.55 2376 1100 2.79 2599 — — — 3500 961 2.18 2035 1013 2.42 2258 1062 2.66 2483 — 3600 971 2.29 2135 1022 2.53 2364 1070 2.78 2595 — 3700 981 2.40 2240 1031 2.65 2473 — 3800 990 2.52 2348 1040 2.77 2587 — 3900 1000 2.64 2459 1050 2.90 2705 — 4000 1011 2.76 2576 — 4100 1021 2.89 2697 — 4200 — 4300 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-supplied drive.

581B102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 513 0.45 423 603 0.62 576 682 0.78 732 753 0.96 892 817 1.13 1055 2600 526 0.50 463 614 0.67 621 692 0.84 783 761 1.02 948 825 1.20 1117 2700 539 0.54 505 625 0.72 670 702 0.90 837 770 1.08 1008 834 1.27 1182 2800 552 0.59 551 637 0.77 721 712 0.96 894 780 1.15 1070 842 1.34 1250 2900 565 0.64 599 648 0.83 775 722 1.02 954 789 1.22 1136 851 1.42 1321 3000 579 0.70 651 660 0.89 832 732 1.09 1017 799 1.29 1204 860 1.50 1395 3100 592 0.76 706 672 0.96 893 743 1.16 1083 808 1.37 1276 869 1.58 1471 3200 606 0.82 764 684 1.03 957 754 1.24 1153 818 1.45 1351 878 1.66 1552 3300 620 0.88 825 696 1.10 1024 765 1.31 1225 829 1.53 1429 888 1.75 1636 3400 634 0.95 890 709 1.17 1095 777 1.40 1302 839 1.62 1511 897 1.85 1723 3500 648 1.03 958 721 1.25 1169 788 1.48 1381 850 1.71 1597 907 1.95 1815 3600 662 1.10 1030 734 1.34 1246 800 1.57 1465 860 1.81 1686 917 2.05 1909 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686
581B102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 877 1.31 1222 933 1.49 1392 986 1.68 1565 1037 1.87 1742 1085 2.06 1921 2600 885 1.38 1289 940 1.57 1464 993 1.76 1643 1043 1.96 1824 1091 2.15 2008 2700 892 1.46 1359 948 1.65 1540 1000 1.85 1723 1049 2.05 1909 1097 2.25 2099 2800 900 1.54 1432 955 1.74 1618 1007 1.94 1807 1056 2.14 1998 1103 2.35 2192 2900 908 1.62 1508 963 1.82 1699 1014 2.03 1893 1063 2.24 2089 1110 2.45 2289 3000 917 1.70 1587 970 1.91 1784 1021 2.13 1983 1070 2.34 2185 1117 2.56 2389 3100 925 1.79 1670 979 2.01 1872 1029 2.23 2076 1077 2.45 2283 1123 2.67 2492 3200 934 1.88 1756 987 2.10 1963 1037 2.33 2172 1085 2.56 2384 1131 2.79 2599 3300 943 1.98 1845 995 2.21 2057 1045 2.44 2272 1092 2.67 2490 1138 2.91 2710 3400 952 2.08 1939 1004 2.31 2156 1053 2.55 2376 1100 2.79 2599 1145 3.03 2824 3500 961 2.18 2035 1013 2.42 2258 1062 2.66 2483 1108 2.91 2711 1153 3.15 2942 3600 971 2.29 2135 1022 2.53 2364 1070 2.78 2595 1116 3.03 2827 1161 3.29 3063 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 — — —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 579 0.70 651 660 0.89 832 732 1.09 1017 799 1.29 1204 860 1.50 1395 3100 592 0.76 706 672 0.96 893 743 1.16 1083 808 1.37 1276 869 1.58 1471 3200 606 0.82 764 684 1.03 957 754 1.24 1153 818 1.45 1351 878 1.66 1552 3300 620 0.88 825 696 1.10 1024 765 1.31 1225 829 1.53 1429 888 1.75 1636 3400 634 0.95 890 709 1.17 1095 777 1.40 1302 839 1.62 1511 897 1.85 1723 3500 648 1.03 958 721 1.25 1169 788 1.48 1381 850 1.71 1597 907 1.95 1815 3600 662 1.10 1030 734 1.34 1246 800 1.57 1465 860 1.81 1686 917 2.05 1909 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 — — — 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 — — —
581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 917 1.70 1587 970 1.91 1784 1021 2.13 1983 1070 2.34 2185 1117 2.56 2389 3100 925 1.79 1670 979 2.01 1872 1029 2.23 2076 1077 2.45 2283 1123 2.67 2492 3200 934 1.88 1756 987 2.10 1963 1037 2.33 2172 1085 2.56 2384 1131 2.79 2599 3300 943 1.98 1845 995 2.21 2057 1045 2.44 2272 1092 2.67 2490 1138 2.91 2710 3400 952 2.08 1939 1004 2.31 2156 1053 2.55 2376 1100 2.79 2599 1145 3.03 2824 3500 961 2.18 2035 1013 2.42 2258 1062 2.66 2483 1108 2.91 2711 1153 3.15 2942 3600 971 2.29 2135 1022 2.53 2364 1070 2.78 2595 1116 3.03 2827 1161 3.29 3063 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 — — — 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 — 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 — 4300 1042 3.16 2951 1089 3.45 3218 — 4400 1053 3.31 3085 1100 3.60 3357 — 4500 1064 3.46 3224 — 4600 1075 3.61 3367 — 4700 — 4800 — 4900 — 5000 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.

581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 579 0.70 651 660 0.89 832 732 1.09 1017 799 1.29 1204 860 1.50 1395 3100 592 0.76 706 672 0.96 893 743 1.16 1083 808 1.37 1276 869 1.58 1471 3200 606 0.82 764 684 1.03 957 754 1.24 1153 818 1.45 1351 878 1.66 1552 3300 620 0.88 825 696 1.10 1024 765 1.31 1225 829 1.53 1429 888 1.75 1636 3400 634 0.95 890 709 1.17 1095 777 1.40 1302 839 1.62 1511 897 1.85 1723 3500 648 1.03 958 721 1.25 1169 788 1.48 1381 850 1.71 1597 907 1.95 1815 3600 662 1.10 1030 734 1.34 1246 800 1.57 1465 860 1.81 1686 917 2.05 1909 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 1062 3.78 3528 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 1074 3.95 3685
581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 917 1.70 1587 970 1.91 1784 1021 2.13 1983 1070 2.34 2185 1117 2.56 2389 3100 925 1.79 1670 979 2.01 1872 1029 2.23 2076 1077 2.45 2283 1123 2.67 2492 3200 934 1.88 1756 987 2.10 1963 1037 2.33 2172 1085 2.56 2384 1131 2.79 2599 3300 943 1.98 1845 995 2.21 2057 1045 2.44 2272 1092 2.67 2490 1138 2.91 2710 3400 952 2.08 1939 1004 2.31 2156 1053 2.55 2376 1100 2.79 2599 1145 3.03 2824 3500 961 2.18 2035 1013 2.42 2258 1062 2.66 2483 1108 2.91 2711 1153 3.15 2942 3600 971 2.29 2135 1022 2.53 2364 1070 2.78 2595 1116 3.03 2827 1161 3.29 3063 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 1221 4.32 4031 4400 1053 3.31 3085 1100 3.60 3357 1145 3.90 3632 1188 4.19 3909 1230 4.49 4187 4500 1064 3.46 3224 1110 3.76 3502 1155 4.06 3782 1198 4.36 4064 1239 4.66 4348 4600 1075 3.61 3367 1121 3.91 3650 1165 4.22 3937 1208 4.53 4224 1249 4.84 4514 4700 1086 3.77 3515 1131 4.08 3805 1175 4.39 4096 1217 4.71 4389 1258 5.02 4684 4800 1097 3.93 3668 1142 4.25 3963 1186 4.57 4260 1228 4.89 4559 1268 5.21 4860 4900 1109 4.10 3826 1153 4.43 4128 1196 4.75 4430 1238 5.08 4734 — — — 5000 1120 4.28 3990 1164 4.61 4296 1207 4.94 4604 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

581B150 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 1062 3.78 3528 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 1074 3.95 3685 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 1039 3.80 3540 1086 4.13 3849 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 1052 3.97 3702 1099 4.31 4017 5300 912 3.13 2917 966 3.47 3233 1016 3.81 3551 1065 4.15 3870 1111 4.49 4191 5400 927 3.30 3073 980 3.64 3395 1030 3.99 3719 1078 4.34 4044 1123 4.69 4370 5500 943 3.47 3234 994 3.82 3563 1044 4.17 3892 1091 4.53 4223 1136 4.88 4555 5600 958 3.65 3402 1009 4.01 3736 1057 4.37 4071 1104 4.73 4408 1149 5.09 4746 5700 973 3.83 3575 1023 4.20 3915 1071 4.56 4256 1117 4.93 4599 — — — 5800 988 4.03 3754 1038 4.40 4100 1085 4.77 4447 1130 5.14 4796 — — — 5900 1004 4.22 3939 1052 4.60 4292 1099 4.98 4645 — 6000 1019 4.43 4131 1067 4.81 4489 1113 5.20 4848 — 6100 1034 4.64 4329 1082 5.03 4693 — 6200 1050 4.86 4533 — 6300 1065 5.09 4744 —
581B150 (121/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 1221 4.32 4031 4400 1053 3.31 3085 1100 3.60 3357 1145 3.90 3632 1188 4.19 3909 1230 4.49 4187 4500 1064 3.46 3224 1110 3.76 3502 1155 4.06 3782 1198 4.36 4064 1239 4.66 4348 4600 1075 3.61 3367 1121 3.91 3650 1165 4.22 3937 1208 4.53 4224 1249 4.84 4514 4700 1086 3.77 3515 1131 4.08 3805 1175 4.39 4096 1217 4.71 4389 1258 5.02 4684 4800 1097 3.93 3668 1142 4.25 3963 1186 4.57 4260 1228 4.89 4559 1268 5.21 4860 4900 1109 4.10 3826 1153 4.43 4128 1196 4.75 4430 1238 5.08 4734 — — — 5000 1120 4.28 3990 1164 4.61 4296 1207 4.94 4604 — 5100 1132 4.46 4159 1175 4.79 4471 1218 5.13 4784 — 5200 1144 4.65 4333 1187 4.99 4651 — 5300 1155 4.84 4512 1198 5.19 4836 — 5400 1167 5.04 4697 — 5500 1179 5.24 4889 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
See page 107 for general fan performance notes. NOTES:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive.

UNIT 581B MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
036 1044 1008 971 935 898 862 826 789 753 716 680 — — 048 1185 1144 1102 1061 1019 978 936 895 853 812 770 — — 060 1460 1425 1389 1354 1318 1283 1248 1212 1177 1141 1106 1070 1035 072 1585 1538 1492 1445 1399 1352 1305 1259 1212 1166 1119 — — 090,102 1085 1060 1035 1010 985 960 935 910 890 865 840 — — 120 1080 1060 1035 1015 990 970 950 925 905 880 860 — — 150 1130 1112 1087 1062 1037 1212 987 962 937 912 887 962 830
*Approximate fan rpm shown (standard motor/drive).
581B036-150
UNIT 581B MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
036 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — — 072 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — — 090 1080 1025 1007 988 970 952 933 915 897 878 860 — — 102 1080 1025 1007 988 970 952 933 915 897 878 860 — — 120 1130 1112 1087 1062 1037 1212 987 962 937 912 887 962 830
*Approximate fan rpm shown (high-static motor/drive).
ALTITUDE COMPENSATION* — 581B090-150
72,000 AND 115,000/ 60,000 and 90,000 BTUH NOMINAL INPUT
125,000, 180,000, AND 224,000 BTUH NOMINAL INPUT
250,000 BTUH NOMINAL INPUT
ELEVATION
ELEVATION
Liquid Propane Orifice Size† 0-2,000 33/38 43 30/32 38 2,000 34/39 43 30/33 39 3,000 35/40 44 31/34 40 4,000 36/41 44 32/35 41 5,000 36/41 44 33/35 42 6,000 37/42 45 34/36 43 7,000 37/42 45 35/37 43 8,000 38/43 46 36/37 44 9,000 39/43 47 37/38 44 10,000 41/44 48 38/40 45 11,000 43/45 48 39/41 45 12,000 44/45 49 40/42 46 13,000 44/46 49 41/43 47 14,000 45/47 50 42/43 47
Natural Gas Orifice Size†
Liquid Propane Orifice Size†
Liquid Propane Orifice Size† 0-2,000 31 41 30 38 2,000 32 42 30 39 3,000 32 42 31 40 4,000 32 42 32 41 5,000 33 43 33 42 6,000 34 43 34 43 7,000 35 44 35 43 8,000 36 44 36 44 9,000 37 45 37 44 10,000 38 46 38 45 11,000 39 47 39 45 12,000 40 47 40 46 13,000 41 48 41 47 14,000 42 48 42 47
Liquid Propane Orifice Size†
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor.
ELEVATION MAXIMUM HEATING VALUE (Btu/ft3) 0-2000 1100 2001-3000 1050 3001-4000 1000 4001-5000 950 5001-6000 900
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

UNIT 581B
SOUND RATING
OCTAVE BANDS
63 125 250 500 1000 2000 4000 8000
036,048 76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3 060,072 80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0 090,102 82 62.2 69.3 71.5 74.7 76.2 72.9 68.7 61.5 120 84 64.6 71.1 73.3 76.9 77.6 73.7 70.6 63.7 150 86 63.7 69.9 72.5 78.2 81.1 77.3 73.3 66.8
LEGEND NOTE: The indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters.
dB — Sound Levels (decibels)
581B036-150
UNIT SIZE 581B EFFICIENCY% 036,048 75 060 74/84* 072 84 090,102 80 120 85 150 87
watts = bhp (746) motor efficiency
2. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance require- ments. Therefore, the indoor fan motors for Bryant 581B036-150 units are exempt from these requirements.
COMPONENT CFM
600 800 1000 1250 1500 1750 2000 2250 2500 2750 3000
Vertical EconoMi$er IV and EconoMi$er2 0.10 0.20 0.35 0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255
Horizontal EconoMi$er IV and EconoMi$er2 — 0.1 0.125 0.15 0.18 0.225 0.275
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Perfor- mance tables to determine indoor blower rpm and watts.
FIOP — Factory-Installed Option
COMPONENT CFM 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250 Vertical EconoMi$er IV and EconoMi$er2 0.06 0.075 0.09 0.115 0.13 0.15 0.17 0.195 0.22 0.25 0.285 0.325 0.36 — Horizontal EconoMi$er IV and EconoMi$er2 — 0.1 0.125 0.15 0.18 0.21 0.25 0.275 0.3 0.34 0.388 — — —
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Perfor- mance tables to determine indoor blower rpm and watts.
FIOP — Factory-Installed Option
(dB)


4 & 5 ton 6 ton 7.5 ton 8.5, 10 & 12.5 ton 3 ton
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50

0 0.1 0.2 0.3 0.4 0.5
STATIC PRESSURE (in. wg)
Flow in cubic feet per minute (cfm)
7 1/2 - 12 1/2 Ton
0.05" 0.15" 0.25"
Static Pressure (in. wg)
Flow in cubic feet per minute (cfm)
7 1/2 - 12 1/2 Ton
0.1" 0.2" 0.3" 0.4" 0.5"
Static Pressure (in. wg)
Horizontal EconoMi$er IV and EconoMi$er2
Performance Data (581B036-150)

UNIT 581B UNIT VOLTAGE
UNIT PHASE
MAXIMUM CONTINUOUS BHP*
MAXIMUM OPERATING WATTS*
MAXIMUM AMP DRAW
208/230 Single 1.20 1000 4.9 208/230 Three 1.20 1000 4.9 460 2.2 575 2.2
208/230 Single 1.20 1000 4.9 208/230 Three 1.20 1000 4.9 460 2.2 575 2.2
208/230 Single 1.30 1650 10.1 208/230 Three 2.40 2120 6.7 460 3.0 575 3.0
072 208/230 Three 2.40 2120 6.7 460 3.0 575 3.0
090,102 208/230 Three 2.90 2615 8.6 460 3.9 575 3.9
120 208/230 Three 3.70 3775 12.2 460 5.5 575 5.5
150 208/230 Three 5.25 4400 17.3 460 8.5 575 8.5
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT 581B UNIT VOLTAGE
UNIT PHASE
MAXIMUM CONTINUOUS BHP*
MAXIMUM OPERATING WATTS*
MAXIMUM AMP DRAW
036 208/230 Three 2.40 2120 6.7 460 3.0 575 3.0
048 208/230 Three 2.40 2120 6.7 460 3.0 575 3.0
060 208/230 Three 2.90 2615 8.6 460 3.9 575 3.9
072 208/230 Three 2.90 2615 8.6 460 3.9 575 3.9
090,102 208/230 Three 4.20 3775 12.2 460 5.5 575 5.5
120 208/230 Three 5.25 4400 17.3 460 8.5 575 8.5
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

VERTICAL — MOUNTED IN ECONOMIZER HOOD POWER EXHAUST
NO. FANS CRPWREXH030A01 Power Exhaust System (208/230-1-60) 036-072* 0.23 2 CRPWREXH021A01 Power Exhaust System (460-3-60) 036-072 0.24 2 CRPWREXH022A01 Power Exhaust System (208/230-1-60) 090-150* 0.47 2 CRPWREXH023A01 Power Exhaust System (460-3-60) 090-150 0.37 2
POWER OUTPUT
USAGE
(Hp per fan)
HORIZONTAL — MOUNTED IN RETURN DUCTWORK POWER EXHAUST|
NO. FANS CRPWREXH028A01 Horizontal Power Exhaust (208/230-1-60) All* 0.48 1 CRPWREXH029A01 Horizontal Power Exhaust (460-3-60) All 0.48 1
POWER OUTPUT
USAGE
(Hp per fan)
581B036-150
*Single or three phase rooftop unit.
MOCP 230 VAC 460 VAC 575 VAC
POWER EXHAUST
AMPS AT 230 V (2 FANS RUNNING)
SIZE
3 to 6 Ton 1.40 amps at 60 Hz 15.0 amps
15.0 amps 71/2 to 121/2 Ton 3.04 amps at 60 Hz
15.0 amps
LEGEND MOCP — Maximum Overcurrent Protection

FAN MOTOR POWER SUPPLY* MINIMUM UNIT DISCONNECT SIZE† Min Max Qty RLA LRA Qty FLA FLA MCA MOCP** FLA LRA
COMBUSTION
UNIT SIZE
581B NOMINAL
IFM TYPE
CONV OUTLET
RANGE COMPRESSOR (each) OFM (each) IFM FLA
208/230-1-60 STD NO 187 254 1 16 88 1 0.7 4.9 0.6 25.6 30 25 101 YES 31.6 35 30 106
18.5 25 18 90 YES 24.5 30 24 95
187 254 1 10.3 77 1 0.7 4.9 0.6
HIGH NO 5.2 19.4 25 19 120 YES 25.4 30 25 124
9.0 15 9 46 YES 11.7 15 11 48
414 508 1 5.1 39 1 0.4 2.2 0.3
HIGH NO 2.6 9.4 15 9 60 YES 12.1 15 12 63
7.6 10 7 36 YES 9.7 15 9 38
518 632 1 4.2 31 1 0.4 1.9 0.3
HIGH NO 2.0 7.7 10 8 43 YES 9.8 15 10 44
PH NO 1 0.4 2.6 0.9 8.3 10 8 52 YES 10.4 15 10 54
208/230-1-60 STD NO 187 254 1 23.7 126 1 0.7 4.9 0.6 35.2 45 34 139 YES 41.2 50 39 144
22.5 30 22 106 YES 28.5 35 27 111
187 254 1 13.5 93 1 0.7 4.9 0.6
HIGH NO 5.8 23.4 30 23 136 YES 29.4 35 29 140
10.6 15 10 54 YES 13.3 15 13 56
414 508 1 6.4 46.5 1 0.4 2.2 0.3
HIGH NO 2.6 11.0 15 11 68 YES 13.7 15 13 70
10.3 15 10 45 YES 12.5 15 12 47
518 632 1 6.4 40 1 0.4 1.9 0.3
HIGH NO 2.0 10.4 15 10 52 YES 12.6 15 12 53
PH NO 1 0.4 2.6 0.9 11.0 15 11 61 YES 13.2 15 13 63
208/230-1-60 STD NO 187 254 1 28.8 169 1 1.5 6.6 0.6 44.1 60 42 206 YES 50.1 60 48 210
28.9 35 28 168 YES 34.9 40 34 173
187 254 1 17.3 123 1 1.5 5.8 0.6
HIGH NO 7.5 30.6 35 30 187 YES 36.6 40 36 192
14.7 20 14 84 YES 17.4 20 17 87
414 508 1 9 62 1 0.8 2.6 0.3
HIGH NO 3.4 15.5 20 15 94 YES 18.2 20 18 96
11.5 15 11 63 YES 13.6 15 13 64
518 632 1 7.1 50 1 0.6 2.0 0.3
HIGH NO 2.8 12.3 15 12 72 YES 14.4 20 14 73
PH NO 1 0.8 3.4 0.3 12.2 15 12 76 YES 14.4 20 14 77
187 254 1 20.5 156 1 1.4 5.8 0.6 32.8 40 32 200 YES 38.8 45 37 205
HIGH NO 7.5 0.6 34.5 40 34 219 YES 40.5 45 39 224
414 508 1 9.6 75 1 0.6 2.6 0.3 15.2 20 15 97 YES 17.9 20 17 99
HIGH NO 3.4 0.3 16.0 20 16 107 YES 18.7 25 18 109
12.4 15 12 69 YES 14.6 20 14 70
518 632 1 7.7 56 1 0.8 2.0 0.3
HIGH NO 2.8 13.2 20 13 79 YES 15.4 20 15 80
PH NO 1 0.6 3.4 0.3 12.8 15 13 81 YES 15.0 20 15 83
38.2 45 40 242 YES 44.2 50 46 247
187 254 2 12.4 88 2 1.4 7.5 0.6
HIGH NO 10.6 41.3 45 44 267 YES 47.3 50 49 271
19.2 25 20 121 YES 21.9 25 23 123
414 508 2 6.4 44 2 0.7 3.4 0.3
090 (71/2 Tons)
HIGH NO 4.8 20.6 25 22 134 YES 23.3 25 24 136
14.6 20 15 95 YES 16.8 20 17 95
518 632 2 4.8 34 2 0.6 2.8 0.3
HIGH NO 3.3 15.3 20 17 104 YES 17.5 20 19 104
PH NO 2 0.7 4.8 0.3 15.8 20 17 104 YES 17.9 20 19 104

FAN MOTOR POWER SUPPLY* MINIMUM UNIT DISCONNECT SIZE† Min Max Qty RLA LRA Qty FLA FLA MCA MOCP** FLA LRA
COMBUSTION
UNIT SIZE
581B NOMINAL
V-PH-Hz IFM TYPE CONV OUTLET
RANGE COMPRESSOR (each) OFM (each) IFM FLA
40.2 45 42 276 YES 46.2 50 48 281
187 254 2 13.1 105 2 1.4 7.5 0.6
HIGH NO 10.6 43.3 50 46 301 YES 49.3 60 51 305
21.5 25 23 143 YES 24.2 30 25 145
414 508 2 7.4 55 2 0.7 3.4 0.3
102 (81/2 Tons)
HIGH NO 4.8 22.9 25 24 156 YES 25.6 30 27 158
18.2 20 19 115 YES 20.4 25 21 116
518 632 2 6.4 44 2 0.6 2.8 0.3
HIGH NO 3.3 18.9 25 20 124 YES 21.1 25 22 126
PH NO 0.7 4.8 0.3 19.4 25 20 124 YES 21.5 25 22 126
187 254 2 17.6 125 2 1.4 10.6 0.6 53.0 60 56 341 YES 59.0 70 61 345
HIGH NO 15.0 0.6 57.4 70 61 364 YES 63.4 70 66 369
24.9 30 26 171 YES 27.6 30 29 173
414 508 2 8.3 62.5 2 0.7 4.8 0.3
HIGH NO 7.4 27.5 30 29 182 YES 30.2 35 32 184
518 632 2 6.3 50 2 0.6 3.3 0.3 19.1 25 20 136 YES 21.3 25 22 138
HIGH NO 5.6 0.3 21.0 25 23 146 YES 23.1 25 25 148
PH NO 2 0.7 7.4 0.3 21.2 25 23 146 YES 23.4 25 25 148
208/230-3-60 STD NO 187 254 2 19 156 2 1.4 15.0 0.6 60.6 70 64 426 YES 66.6 70 70 431
460-3-60 STD NO 414 508 2 9 75 2 0.7 7.4 0.3 29.1 35 31 207 YES 31.8 35 33 209
150 (121/2 Tons)
518 632 2 7.4 54 2 0.6 5.6 0.3 23.5 30 25 154 YES 25.6 30 27 156
PH NO 2 0.7 7.4 0.3 23.7 30 25 154 YES 25.9 30 27 156
Determine percent of voltage imbalance.
CONV — Convenience Outlet FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor PH — Perfect Humidity™ Dehumidification System RLA — Rated Load Amps UL — Underwriters’ Laboratories
% Voltage Imbalance = 100 x 7 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
*The values listed in this table do not include power exhaust. See table at right for power exhaust requirements. †Used to determine minimum disconnect per NEC. **Fuse or HACR circuit breaker.
MOCP (separate power source
APPLICATION
MCA (230 V)
MCA (460 V)
MCA (575 V)
PART NO.
only) CRPWREXH030A01 036-072* 1.6 N/A 0.64 15 CRPWREXH021A01 036-072 N/A 0.68 N/A 15 CRPWREXH022A01 090-150* 3.4 N/A 1.32 15 CRPWREXH023A01 090-150 N/A 1.4 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker. 2. Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.
= 100 x max voltage deviation from average voltage
N/A — Not Available *Single or three phase. NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 581B060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps and the MCA New is below 35; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
452 + 464 + 455 3
= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.



581B036-150
LEGEND IAQ — Indoor Air Quality LA — Low Ambient Lockout Device POT — Potentiometer OAT — Outdoor-Air Temperature RAT — Return-Air Temperature
BLACK
BLUE
500 OHM RESISTOR
VIOLET
NOTE 1
PINK
RUN
RED
NOTE 2
50HJ540573 ACTUATOR ASSEMBLY
YELLOW
OPTIONAL CO SENSOR 4 - 20 mA
DIRECT DRIVE
WHITE
ACTUATOR
EconoMi$er2 Wiring — 581B036-150 Units
a48-7910 · - + · a48-8209

RED YEL BLU GRA
LINE SIDE
H1 H3
H2 H4
21 BLU
GRA
RED
TRAN4
YEL
X4 X2 X3 X1
RED
YEL
BLU
GRA
H3 H2
208-230-1 ONLY
SECONDARY
H1
H4
580F036-151 AND 581B036-150
TRAN4
GRA RED
X4 X2 X3 X1
H1
H2
WHT BLK
SECONDARY
120V GROUND FAULT
TRAN4
INTERRUPTER CONVENIENCE
OUTLET GFI - CO
X4 X2 X3 X1
GRN-YEL GRN-YEL
SECONDARY
TEST RESET SWITCH
WHT BLK FUSE
15 AMP
Convenience Outlet (Optional) — Sizes 581B036-150
UNIT DISCONNECT
FIELD
BLK
BLK
POWER
YEL
YEL
SUPPLY
BLU
BLU
TB
BLK
BLK
YEL
YEL
BLU
BLU
SINGLE POINT CONNECTION BOX
a48-7462 · a48-7463



PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 3 TO 121/2 TONS, NOMINAL (COOLING) 60,000 TO 250,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBERS: 580F, 581B
Color: American Sterling, this gray color is to match federal standard 595a, #26231. Gloss (per ASTM 0523, 60 deg. F): 60. Hardness of paint film: H-2H pencil hardness. 2. Evaporator fan compartment interior cabinet sur- faces shall be insulated with a minimum 1/2-in. thick, 1 lb density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil-faced fiber- glass insulation shall be used in the gas heat compartment. 3. Cabinet panels shall be easily removable for servicing. 4. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging. 5. Unit shall have a factory-installed, sloped conden- sate drain pan made of a non-corrosive material, pro- viding a minimum 3/4-in.-14 NPT connection with both vertical and horizontal drains, and shall comply with ASHRAE Standard 62. 6. Unit shall have a factory-installed filter access panel to provide filter access with tool-less removal. 7. Unit shall have standard thru-the-bottom gas and power connection capability (accessory kit is required). C. Fans:
PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing a hermetic compressor(s) for cooling duty and gas combustion for heating duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings. 1.02 QUALITY ASSURANCE A. Unit well exceeds ASHRAE 90.1-2001 Energy Standards.
Units 581B036-120 are Energy Star qualified. B. Unit shall be rated in accordance with ARI Standards 210
or 360. Designed in accordance with UL Standard 1995. C. Unit shall be designed to conform to ASHRAE 15, latest
revision. D. Unit shall be UL-tested and certified in accordance with
equipment drawings. Belt drive shall include an adjustable-pitch motor pulley. b. Fan wheel shall be double-inlet type with forward-
ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements. E. Roof curb shall be designed to conform to NRCA
curved blades. c. Bearings shall be sealed, permanently lubricated
Standards. F. Insulation and adhesive shall meet NFPA 90A require-
ball-bearing type for longer life and lower maintenance. 2. Evaporator fan shall be made from steel with a corro- sion-resistant finish and shall be dynamically balanced. 3. Bryant rooftop evaporator fan motors smaller than 5 hp are specifically designed for Bryant and are rated in maximum continuous Bhp or maximum con- tinuous watts. The motors do not have a horsepower rating on the nameplate. 4. Condenser fan shall be of the direct-driven (with totally enclosed motors) propeller type and shall dis- charge air vertically. 5. Condenser fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynamically balanced. 6. Induced-draft blower shall be of the direct-driven, sin- gle inlet, forward-curved centrifugal type, made from steel with a corrosion-resistant finish and shall be dynamically balanced. D. Compressor(s):
ments for flame spread and smoke generation. G. Unit casing shall be capable of withstanding 500-hour salt
spray exposure per ASTM B117 (scribed specimen). H. Unit shall be designed in accordance with ISO
9001:2000, and shall be manufactured in a facility regis- tered to ISO 9001:2000. I. Each unit shall be subjected to a completely automated
run testing on the assembly line. A factory-supplied print- out indicating tested pressures, amperages, data, and inspectors; providing certification of the unit status at the time of manufacture, shall be available upon request. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recommendations. PART 2 — PRODUCTS 2.01 EQUIPMENT (STANDARD) A. General:
Factory assembled, single-piece heating and cooling unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:

coil pan to maintain coating integrity and minimize corrosion potential between coil and pan. F. Heating Section:
to UL 1995 burst test at 2,200 psi. b. Evaporator and condenser coils shall be leak
tested to 150 psig and pressure tested to 400 psig. 4. Optional Coils: a. Optional pre-coated aluminum-fin coils shall have
tubular-section type constructed of a minimum of 20-gage steel coated with a nominal 1.2 mil aluminum-silicone alloy for corrosion resistance. b. The optional stainless steel heat exchanger shall
a durable epoxy-phenolic coating to provide pro- tection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize gal- vanic action between dissimilar metals. b. Copper-fin coils shall be constructed of copper
be of the tubular-section type, constructed of a minimum of 20-gage type 409 stainless steel. 3. Burners shall be of the in-shot type constructed of aluminum-coated steel. 4. All gas piping shall enter the unit cabinet at a single location on side of unit (horizontal plane). 5. The integrated gas controller (IGC) board shall include gas heat operation fault notification using an LED (light-emitting diode). 6. Unit shall be equipped with anti-cycle protection with one short cycle on unit flame rollout switch or 4 con- tinuous short cycles on the high-temperature limit switch. Fault indication shall be made using an LED. 7. The IGC board shall contain algorithms that modify evaporator-fan operation to prevent future cycling on high-temperature limit switch. 8. The LED shall be visible without removal of control box access panel. G. Refrigerant Components:
fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper con- struction shall provide protection in moderate coastal environments. c. E-Coated aluminum-fin coils shall have a flexible
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be alumi- num fins mechanically bonded to copper tubes. d. E-Coated copper-fin coils shall have a flexible
Refrigerant circuit components shall include:
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting sheet metal
protector which provides anti-cycle reset capabil- ity at the space thermostat, should any of the fol- lowing standard safety devices trip and shut off compressor. 1) Compressor overtemperature, overcurrent. 2) Loss-of-charge/low-pressure switch. 3) Freeze-protection thermostat, evaporator coil. 4) High-pressure switch. 5) Automatic reset motor thermal overload protector.

The lockout protection shall be easily discon- nected at the control board, if necessary. b. Heating section shall be provided with the follow-
f. EconoMi$er IV and EconoMi$er2 shall be
equipped with a barometric relief damper capable of relieving up to 100% return air. g. Designed to close damper(s) during loss-of-
ing minimum protections: 1) High-temperature limit switches. 2) Induced draft motor speed sensor. 3) Flame rollout switch. 4) Flame proving controls. J. Operating Characteristics:
power situations with spring return built into motor. h. Dry bulb outdoor-air temperature sensor shall be
provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F. For the EconoMi$er IV, the return air sen- sor, indoor enthalpy sensor, and outdoor enthalpy sensor shall be provided as field-installed acces- sories to provide enthalpy control, differential enthalpy control, and differential dry bulb temper- ature control. For the EconoMi$er2, the enthalpy, differential temperature (adjustable), and differen- tial enthalpy control shall be provided as field- installed accessories. i. EconoMi$er IV controller shall use a mixed air
All unit power wiring shall enter unit cabinet at a single factory-predrilled location. L. Motors:
thermistor mounted on the evaporator fan hous- ing to control EconoMi$er IV operation to a sup- ply air temperature of 55 F. j. The EconoMi$er IV and EconoMi$er2 shall have
1. Compressor motors shall be cooled by refrigerant gas passing through motor windings and shall have line break thermal and current overload protection. 2. Evaporator-fan motor shall have permanently lubri- cated bearings and inherent automatic-reset thermal overload protection. Evaporator motors are designed specifically for Bryant and do not have conventional horsepower (HP) ratings listed on the motor name- plate. Motors are designed and qualified in the “air- over” location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors” above that rating may be applied. 3. Totally enclosed condenser-fan motor shall have permanently lubricated bearings, and inherent auto- matic-reset thermal overload protection. 4. Induced-draft motor shall have permanently lubri- cated sealed bearings and inherent automatic-reset thermal overload protection. M. Special Features:
a gear-driven parallel blade design. k. EconoMi$er IV controller shall provide control of
internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%. l. EconoMi$er2 shall be capable of control from a
4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control (required for PremierLink™ or third party control interface). m. EconoMi$er IV controller Occupied Minimum
Damper Position Setting maintains the minimum airflow into the building during occupied period providing design ventilation rate for full occu- pancy (damper position during heating). A remote potentiometer may be used to override the set point. n. EconoMi$er IV controller Unoccupied Minimum
Damper Position Setting — The EconoMi$er IV dampers shall be closed when the unit is in the occupied mode. o. EconoMi$er IV controller IAQ/DCV Maximum
Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office.
Damper Position Setting — Setting the maximum position of the damper prevents the introduction of large amounts of hot or cold air into the space. This position is intended to satisfy the base mini- mum ventilation rate. p. EconoMi$er IV controller IAQ/DCV control modu-
and shall be capable of supporting entire unit weight. b. Permits installation and securing of ductwork to
curb prior to mounting unit on the curb. * 2. Integrated Economizers: a. Integrated integral modulating type capable of
lates the outdoor-air damper to provide ventilation based on the optional 2 to 10 vdc CO2 sensor input. q. Compressor lockout sensor (opens at 35 F,
simultaneous economizer and compressor opera- tion. During economizer operation, up to two compressors on sizes 090-150 will operate. b. Available as a factory-installed option in vertical
closes at 50 F). r. Actuator shall be direct coupled to economizer
gear, eliminating linkage arms and rods. s. Control LEDs:
supply/return configuration only. (Available as a field-installed accessory for dedicated horizontal and/or vertical supply return configurations.) c. Includes all hardware and controls to provide
cooling with outdoor air. d. Equipped with low-leakage dampers, not to exceed 2% leakage at 1 in. wg pressure differential. e. Capable of introducing up to 100% outdoor air.

t. Remote Minimum Position Control — A field-
provide unit power shutoff. Switch shall be accessi- ble from outside the unit and shall provide power off lockout capability. 14. Convenience Outlet: Outlet shall be factory-installed and internally mounted with easily accessible 115-v female recep- tacle. Shall include 15 amp GFI receptacle with inde- pendent fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed step-down transformer powered from the LOAD (RTU) side of the unit power supply. Shall be accessible from outside the unit. 15. High-Static Indoor Fan Motor(s) and Drive(s) (036-120):
installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation. 3. Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year round ventilation. * 4. 100% Two-Position Damper: a. Two-position damper package shall include single
blade damper and motor. Admits up to 100% out- door air. b. Damper shall close upon indoor (evaporator) fan
High-static motor(s) and drive(s) shall be factory- installed to provide additional performance range. 16. Flue Discharge Deflector: Flue discharge deflector directs unit exhaust verti- cally instead of horizontally. 17. Condenser Coil Grille: The grille protects the condenser coil from damage by large objects without increasing unit clearances. 18. Compressor Cycle Delay: Unit shall be prevented from restarting for minimum of 5 minutes after shutdown. 19. Thru-the-Bottom Utility Connectors: Kit shall provide connectors to permit gas and elec- trical connections to be brought to the unit through the basepan. 20. Fan/Filter Status Switch: Switch shall provide status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat. 21. Power Exhaust Accessory for EconoMi$er IV or EconoMi$er2:
shutoff. c. Designed to close damper during loss of power
situations. d. Equipped with 15% barometric relief damper. * 5. 25% Two-Position Damper: a. Two-position damper package shall include single
blade damper and motor. Admits up to 25% out- door air. b. Damper shall close upon indoor (evaporator) fan
shutoff. * 6. Head Pressure Control Package: Consists of solid-state control and condenser-coil temperature sensor to maintain condensing temper- ature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. 7. Propane Conversion Kit: Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane (valid up to 2000 ft elevation). * 8. Electronic Programmable Thermostat: Units shall be capable of using deluxe full-featured electronic thermostat. Thermostat shall use built-in compressor cycle delay control for both heating and cooling duty. Thermostat shall be capable of working with third party direct digital controls. 9. Light Commercial Thermidistat™ Device: Field-installed wall-mounted thermostat is used to control temperature and activation of the dehumidifi- cation package. The Thermidistat device can be set for humidity settings from 50% to 90% relative humidity. Automatic humidity control adjusts indoor humidity based on the outdoor temperature sensor. * 10. Flue Shield: Flue shield shall provide protection from the hot sides of the gas flue hood. * 11. Thermostat and Subbase: Thermostat and subbase shall provide staged cool- ing and heating automatic (or manual) changeover, fan control, and indicator light. * 12. Condenser Coil Hail Guard Assembly: Hail guard shall protect against damage from hail and flying debris. 13. Unit-Mounted, Non-Fused Disconnect Switch: Switch shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall
Power exhaust shall be used in conjunction with EconoMi$er IV or EconoMi$er2 to provide system exhaust of up to 100% of return air (vertical only). The power exhaust is a field-installed accessory (separate vertical and horizontal design). NOTE: Horizontal power exhaust is intended to mount in return ductwork. As the outdoor-air damper opens and closes, both propeller fans are energized and deenergized through the EconoMi$er IV controller. The set point is factory set at 100% of outdoor-air, and is adjust- able 0 to 100% to meet specific job requirements. Available in 208/230-1-60 v or 460-3-60 v. An LED light on the controller indicates when the power exhaust is operating. For the EconoMi$er2, the power exhaust shall be controlled by the third party controls. 22. Outdoor Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2):
The outdoor air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device to provide single enthalpy control. When used in conjunction with a return air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential enthalpy control. The sensor allows the EconoMi$er IV or EconoMi$er2 controller to determine if outside air is suitable for free cooling.

both temperature and humidity in the space are not satisfied. 2) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the compressor with the hot liquid refrigerant leaving the con- denser coil to create a two-phase heat transfer in the system, resulting in a neutral leaving-air temperature when only humidity in the space is not satisfied. b. The system shall consist of a subcooling/reheat
The return air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with an outdoor air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will pro- vide differential enthalpy control. 24. Return Air Temperature Sensor (EconoMi$er IV or EconoMi$er2):
The return air temperature sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with the standard outdoor air tem- perature sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential temperature control. 25. Indoor Air Quality (CO2) Sensor (EconoMi$er2): a. Shall have the ability to provide demand ventila-
dehumidification coil located downstream of the standard evaporator coil. This dehumidification coil is a two-row coil with the exception of the 036 unit, which has a one-row coil. c. The system shall include crankcase heater(s) for
the scroll compressor(s). d. The system shall include a low outdoor air tem-
tion indoor air quality (IAQ) control through the EconoMi$er2 with an IAQ sensor. b. The IAQ sensor shall be available in duct mount,
perature switch to lock out both subcooling and hot gas reheat mode when the outdoor-air tem- perature is below 40 F. e. The system shall include a Motormaster® low
wall mount, and wall mount with LED display. The set point shall have adjustment capability. c. Requires EconoMi$er2 control option. 26. Indoor Air Quality (CO2) Room Sensor (EconoMi$er IV):
ambient control to ensure the normal design cool- ing mode capable of down to 0° F low ambient operation. f. The system shall include a low-pressure switch
Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be wall mounted with an LED display in parts per million. The set point shall have adjustment capability. 27. Return Air CO2 Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be duct mounted. The set point shall have adjustment capability. 28. Gas Heat options (sizes 004-006): a. Single-stage gas heat shall be provided in lieu of
on the suction line to ensure low pressure start-up of hot gas reheat mode at lower outdoor tempera- ture condition. g. The system operation may be controlled by a
field-installed, wall-mounted humidistat. The dehumidification circuit will then operate only when needed. Field connections for the humidis- tat are made in the low-voltage compartment of the unit control box. The sensor can be set for any level between 55% and 80% relative humid- ity. h. The system shall include a thermostatic expan-
sion valve (TXV) to ensure a positive superheat condition and a balance of pressure drop. i. For units with two compressors (sizes 090-150),
two-stage heat. b. NOx reduction shall be provided to reduce nitrous
oxide emissions to meet the California Air Quality Management NOx requirement of 40 nanograms/ joule or less. c. Primary tubes on low NOx units shall be 409
depending on the conditions required to maintain the space set points, one or both compressors can operate in subcooling mode, one compressor could operate in subcooling mode while the other operates in hot gas reheat mode, or one or both compressors can operate in hot gas reheat mode. 31. Humidistat: Field-installed, wall-mounted humidistat is used to control activation of the dehumidification package. The humidistat can be set for humidity levels between 20% and 80% relative humidity. 32. Hinged Panel Option: Hinged panel option provides hinged access panels for the filter, compressor, evaporator fan, and control box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is perma- nently attached to the rooftop unit. 33. Louvered Hail Guard: The hail guard shall protect the entire outdoor coil surface from direct or indirect (from adjacent sur- faces) hail damage. Hail guard shall have a pressure drop of 2%.
stainless steel. Other components shall be alumi- nized steel. 29. Ultraviolet Germicidal Lamps: Ultraviolet germicidal lamps are designed to elimi- nate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germicidal lamps are field installed in the evaporator section of the unit, aimed at the evaporator coil and conden- sate pan. The short wavelength ultraviolet light inhib- its and kills mold, fungus and microbial growth. The lamps have an output rating at 45F in 400 fpm air- flow of 120 microwatts/cm2 at 1 meter. 30. Perfect Humidity™ Adaptive Dehumidification Sys- tem (581B only):
a. The Perfect Humidity dehumidification system
shall be factory-installed in the rooftop units, and shall provide greater dehumidification of the occupied space by two modes of dehumidification operations beside its normal design cooling mode: 1) Subcooling mode further subcools the hot liq- uid refrigerant leaving the condenser coil when

UNIT SIZE 581C 024 036 048 060 NOMINAL CAPACITY (tons) 2 3 4 5 OPERATING WEIGHT(lb) Base Unit** 530 540 560 635 COMPRESSOR Scroll Quantity 1 Oil (oz) 25 42 56 53 REFRIGERANT TYPE R-22 Expansion Device Operating Charge (lb-oz) Acutrol™ MeteringDevice Standard Unit 5---3 7---11 8---8 12---11 Unit With Perfect Humidity Adaptive Dehumidification System 10---2 14---0 14---13 21---0 CONDENSER FAN Propeller Quantity...Diameter (in.) 1...22 Nominal Cfm 3000 3500 3500 4100 Motor Hp...Rpm 1/8...825 1/8...825 1/8...825 1/4...1100 Watts Input (Total) 180 180 180 320 CONDENSER COIL Enhanced Copper Tubes, Aluminum LancedFins Rows...Fins/in. 1...17 1...17 2...17 2...17 Total Face Area (sq ft) 14.6 14.6 16.5 16.5 EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins Standard Unit Rows...Fins/in. 2...15 2...15 2...15 4...15 Total Face Area (sq ft) 4.2 5.5 5.5 5.5 Perfect Humidity Coil Adaptive Dehumidification System Rows...Fins/in. 1...17 1...17 2...17 2...17 Total Face Area (sq ft) 3.5 3.9 3.9 3.9 EVAPORATOR FAN Centrifugal Type, Belt Drive Quantity...Size (in.) 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 Nominal Cfm 800 1200 1600 2000 Maximum Continuous Bhp Std 0.58 1.20 1.20 1.30/2.40* Hi-Static 2.40 2.40 2.40 2.90
Motor Frame Size Std 48/56† Hi-Static 56 56 56 Motor Rpm Std 1620 1620 1620 1725 Hi-Static 1725 1725 1725 Fan Rpm Range Std 400-1000 680-1044 770-1185 1035-1460 Hi-Static 1075-1455 1075-1455 1300-1685 Motor Bearing Type Ball Maximum Fan Rpm 1620 2100 2100 2100 Motor Pulley Pitch Diameter A/B (in.) Std 2.4/3.2 1.9/2.9 1.9/2.0 2.4/3.4 Hi-Static 2.8/3.8 2.8/3.8 3.4/4.4 Nominal Motor Shaft Diameter (in.) Std 5/8 1/2 1/2 5/8 Hi-Static 7/8 5/8 5/8 5/8 Fan Pulley Pitch Diameter (in.) Std 4.0 4.5 4.0 4.0 Hi-Static 4.5 4.5 4.0 4.5 Belt — Type...Length (in.) Std 1...A...36 1...A...36 1 4...36 1...A...40 Hi-Static 1...A...39 1...A...39 1...A...39 1...A...40 Pulley Center Line Distance (in.) 10.0 -12.4 10.0-12.4 10.0-12.4 14.7-15.5 Speed Change per Full Turn of Movable Pulley Flange (rpm) Std 60 65 70 75 Hi-Static 65 65 60 Movable Pulley Maximum Full Turns from Closed Position Std 5 5 5 6 Hi-Static 6 6 5 Factory Setting — Full Turns Open Std 3 Hi-Static 31/2 31/2 31/2 Factory Speed Setting(rpm) Std 756 826 936 1248 Hi-Static 1233 1233 1396 Fan Shaft Diameter at Pulley (in.) 5/8
Bhp — Brake Horsepower
*Single/three phase. **Base unit weight does not include any options or accessories. See Options and Accessory weight tables for additional weight information. †Indicates automatic reset.

FURNACE SECTION Rollout Switch Cutout Temp(F)† 195 Burner Orifice Diameter (in drill size)** Natural Gas—Std* 071/072.113...33 .113...33 .113...33 114/115.089...43 .113...33 .113...33 .113...33 149/150 — .129...30 .129...30 060N — .113...33 .113...33 .113...33 090N — .113...33 .113...33 .113...33 120N — — .129...30 .129...30 .089...43 .102...38 .102...38 .102...38 — .102...38 .102...38 .102...38 — — .116...32 .116...32 Liquid Propane—Alt†† 071/072.073...49 .089...43 .089...43 .089...43 114/115.089...43 .089...43 .089...43 149/150 — .104...37 .104...37 — .089...43 .089...43 .089...43 — .089...43 .089...43 .089...43 — — .102...37 .104...37 — Thermostat Heat Anticipator Setting (amps) 208/230/460/575v First Stage 0.14 Second Stage 0.14 Gas Input (Btuh) First Stage/Second Stage 072 50,000/— || 50,000/72,000 || 50,000/72,000 || 50,000/72,000 115 || 82,000/115,000 || 82,000/115,000 || 82,000/115,000 150 — || 120,000/150,000 || 120,000/150,000 17111 — *** —/72,000 *** —/72,000 *** —/72,000 17211 — *** —/115,000 *** —/115,000 *** —/115,000 14911 — — *** —/150,000 *** —/150,000 060N*** — ††† —/60,000 ††† —/60,000 ††† —/60,000 0960N*** — ††† —/90,000 ††† —/90,000 ††† —/90,000 120N*** — — ††† —/120,000 ††† —/120,000 Efficiency (Steady State ) (%) 072 81 82.8 82.8 82.8 115 80 81 81 150 — 80.4 80.4 071 — 82 82 82 114 — 80 81 81 149 — — 80 80 060N — 80.2 80.2 80.2 090N 81 120N — — 80.7 80.7 Temperature Rise Range 072 25-55 25-25 25-55 115 25-65 55-85 35-65 35-65 150 — 50-80 50-80 071 — 25-55 25-55 25-55 114 — 55-85 35-65 35-65 149 — — 50-80 50-80 060N — 20-50 20-50 20-50 090N — 30-60 30-60 30-60 120N — — 40-70 40-70 Manifold Pressure (in.wg) Natural Gas—Std 3.5 Liquid Propane—Alt†† 3.5 Gas Valve Quanity 1 Gas Valve Pressure Range (Min-Max Allowable) psig 0.180-0.70 in wg 5.0-13.0 Field Gas Connection Size (in. FPT) 1/2 HIGH-PRESSURE SWITCH (psig) Standard CompressorInternal Relief 450±50 Cutout 428 Reset (Auto.) 320 LOSS-OF-CHARGE SWITCH (LiquidLIne) (psig) Cutout 7±3 22±5 Reset(Auto.) FREEZE PROTECTION THERMOSTAT Opens(F) 30±5 45±5 Closes(F) OUTDOOR-AIR INLET SCREENS Cleanable Screen quantity and size varies with option selected. RETURN-AIRFILTERS Throw away Quantity...Size (in.) 2...16x25x2
Bhp — Brake Horsepower IIThree-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating with heating input values as follows: 048-060, 036 — 72,000 Btuh 048-060, 036 — 115,000 Btuh 048-060 — 150,000 Btuh (shown in heating capacity tables) ***California compliant three-phase models. †††California SCAQMD compliant low NOx models have combustion products
*Single phase/three phase. Stainless steel models use the same orifices as equiva- lent standard heat exchangers. †Indicates automatic reset. **60,000 and
that are controlled to 40 nanograms per joule or less. NOTE: Capacities for stainless steel heat exchanger units (S/R/T) are the same as standard units (D/E/F).
Low NOx baffle must be removed and the units will no longer be classified as Low NOx units.

581C024-060

581C024 (2 Tons) Temp (F) Air Entering Evaporator -- CFM/BF Air Ent 600/0.12 800/0.14 1000/0.18 Condenser Air Entering Evaporator -- Ewb (F) (Edb) 57 62 67 72 57 62 67 72 57 62 67 72
75 TCG 22.6 24.3 26.7 29 25 25.7 28.1 30.2 26.6 26.8 29 30.9 SHG 21.7 19.5 16.4 13 24 22.9 18.6 14.1 25.6 25.4 20.6 15.1 CMP 1.18 1.19 1.2 1.21 1.19 1.19 1.2 1.21 1.19 1.2 1.21 1.22
85 TCG 21.3 23 25.7 28 24.2 24.7 27.2 29.6 25.9 25.9 27.9 30.2 SHG 20.5 19 16 12.7 23.3 22.4 18.4 14.1 24.9 24.9 20.3 15.1 CMP 1.36 1.37 1.38 1.39 1.38 1.38 1.39 1.4 1.38 1.38 1.39 1.4
95 TCG 19.9 21 24.7 27.2 23.1 23.3 26 28.6 25 24.9 26.9 29.3 SHG 19.1 18.2 15.7 12.4 22.2 21.9 18.1 13.9 24 24 20.2 15.1 CMP 1.56 1.57 1.59 1.6 1.58 1.58 1.59 1.61 1.59 1.59 1.6 1.61
105 TCG 18.4 18.8 23.2 26 21.3 21.3 24.8 27.4 23.9 23.9 25.6 28.2 SHG 17.7 17.3 15.1 12 20.5 20.5 17.7 13.5 23 23 19.9 14.8 CMP 1.78 1.78 1.81 1.82 1.8 1.8 1.82 1.83 1.81 1.81 1.82 1.84
115 TCG 16.6 16.5 20.5 24.7 19.7 19.7 22.4 26 22 22 24.1 26.7 SHG 16 15.9 14.1 11.6 19 19 16.9 13.1 21.1 21.1 19.5 14.5 CMP 2.01 2.01 2.05 2.08 2.05 2.05 2.06 2.08 2.06 2.06 2.07 2.09
125 TCG 15 15 17.7 22.2 17.7 17.7 19.6 24.4 19.7 19.8 20.5 25.2 SHG 14.5 14.5 13.2 10.8 17 17 16 12.7 19 19 18.3 14.1 CMP 2.27 2.27 2.3 2.34 2.3 2.3 2.32 2.35 2.32 2.32 2.33 2.36 581C036 (3 Tons) Temp (F) Air Entering Evaporator -- CFM/BF Air Ent 900/0.10 1200/0.13 1500/0.16 Condenser Air Entering Evaporator -- Ewb (F) (Edb) 57 62 67 72 57 62 67 72 57 62 67 72
75 TCG 32 34.5 38.9 42.8 35.1 37.1 40.9 44.9 38.1 38.5 42.2 45.9 SHG 32 28.9 25 20.4 35.1 33.6 28.3 22.3 38.1 37.4 31.2 23.9 CMP 1.94 1.96 1.98 2 1.96 1.97 1.99 2.01 1.98 1.98 2 2.02
85 TCG 30.9 33.2 37.5 41.4 33.8 34.9 39.4 43.3 36.9 37 40.5 44.3 SHG 30.9 28.3 24.5 19.8 33.8 32.5 27.8 21.8 36.9 36.7 30.7 23.3 CMP 2.19 2.21 2.24 2.26 2.22 2.23 2.25 2.27 2.24 2.24 2.26 2.28
95 TCG 29.5 31.4 35.4 39.7 31.8 32.3 37.7 41.5 35.1 35.2 38.8 42.5 SHG 29.5 27.3 23.6 19.2 31.8 31.2 27.2 21.2 35 35.2 30 22.8 CMP 2.47 2.49 2.52 2.54 2.5 2.51 2.54 2.56 2.53 2.53 2.54 2.56
105 TCG 28 29.5 33 38 29.5 29.5 34.7 39.7 32.3 32.2 36.8 40.8 SHG 28 26.4 22.6 18.6 29.4 29.4 26 20.7 32.3 32.2 29.5 22.5 CMP 2.78 2.79 2.83 2.86 2.81 2.81 2.85 2.87 2.84 2.84 2.86 2.88
115 TCG 26.3 27.1 30.7 35.2 27.6 27.6 31.1 37.6 29.6 29.5 32.9 38.5 SHG 26.3 25.3 21.7 17.7 27.6 27.6 24.5 20 29.6 29.5 27.8 21.9 CMP 3.1 3.11 3.16 3.2 3.15 3.15 3.18 3.22 3.17 3.17 3.2 3.23
125 TCG 24.4 24.7 28.1 32.1 25.5 25.5 27.5 33.7 27 27 28.5 35.8 SHG 24.4 24.1 20.7 16.6 25.5 25.4 22.9 18.8 27 27 26 21.2 CMP 3.45 3.46 3.51 3.56 3.51 3.51 3.53 3.59 3.53 3.53 3.55 3.6
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb COMP — Compressor Power kw SHG — Gross Sensible Capacity (1000 Btuh) TCG — Compressor Cooling Capicity (1000 Btuh)
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapora tor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80)

581C048 (4 Tons) Temp (F) Air Entering Evaporator -- CFM/BF Air Ent 1200/0.05 1600/0.07 2000/0.09 Condenser Air Entering Evaporator -- Ewb (F) (Edb) 62 67 72 62 67 72 62 67 72
75 TCG 46.3 51.1 55.7 48.8 53.5 58 50.7 54.9 59.1 SHG 39.9 33.8 27.1 46.3 38.6 29.8 50.6 42.7 32 CMP 2.36 2.37 2.38 2.37 2.38 2.39 2.37 2.38 2.39
85 TCG 42.9 49 54 46.2 51.5 56.4 49.2 52.8 57.4 SHG 38.5 33 26.6 45.2 37.9 29.4 49.1 42.2 31.7 CMP 2.69 2.71 2.72 2.71 2.72 2.74 2.72 2.72 2.74
95 TCG 38.7 45.8 51.9 42.6 48.8 54.2 46.8 50.4 55.5 SHG 36.5 31.8 25.9 42.5 37.1 28.9 46.8 41.6 31.4 CMP 3.05 3.08 3.11 3.07 3.1 3.12 3.1 3.11 3.12
105 TCG 34.4 41.1 49.1 39 43.8 51.5 43.3 46.3 52.8 SHG 34.3 30 24.9 39 35.3 28.2 43.3 40.4 30.9 CMP 3.42 3.48 3.53 3.47 3.5 3.54 3.5 3.52 3.54
115 TCG 31.4 36.3 44.7 35.8 38.4 47.3 39.2 40.6 49.5 SHG 31.4 28.1 23.5 35.8 33.3 26.9 39.2 38.1 30.1 CMP 3.85 3.9 3.96 3.9 3.92 3.98 3.93 3.94 4
125 TCG 28.2 31.1 39.8 31.9 33 41.6 35.3 35.4 43.9 SHG 28.1 26.2 21.8 31.9 31.1 25.1 35.3 35.4 28.4 CMP 4.31 4.35 4.42 4.36 4.37 4.44 4.4 4.4 4.46
581C060 (5 Tons) Temp (F) Indoor Entering Air -- CFM/BF Outdoor 1500/0.26 1750/.31 2000/.35 2500/.45 Air Ent Indoor Entering Air -- Ewb (F) (Edb) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
75 TCG 57 60.2 66.5 72 60.3 62.3 68.5 73.8 63.2 64.1 69.7 75.6 67.4 67.4 71.8 77.6 SHG 55.3 50.5 42.4 33.5 58.6 55.2 45.7 35.4 61.3 59.5 48.6 37.4 65.5 65.5 54.4 40.7 CMP 3.1 3.11 3.12 3.14 3.11 3.12 3.13 3.15 3.11 3.12 3.13 3.16 3.12 3.12 3.14 3.17
85 TCG 54.1 56.9 64 70.2 58.3 59.7 65.9 72 60.9 61.4 67.3 73.4 65.3 65.2 69.6 75.3 SHG 52.6 49.1 41.4 33 56.6 54.1 44.8 35 59.2 58.4 48 36.9 63.4 63.4 54.4 40.4 CMP 3.5 3.52 3.54 3.56 3.52 3.53 3.54 3.57 3.53 3.54 3.54 3.58 3.54 3.54 3.56 3.59
95 TCG 50.2 53 61.1 67.5 55 55.6 62.9 69.3 58.6 58.6 64.3 70.6 62.8 62.8 66.4 72.7 SHG 48.8 47.4 40.3 32.2 53.4 52.3 43.8 34.2 56.9 56.8 47.2 36.1 61 61 53.4 40 CMP 3.94 3.95 3.99 4.02 3.97 3.97 4.01 4.03 3.99 3.99 4.02 4.03 4.01 4.01 4.02 4.05
105 TCG 47.4 47.9 56.5 64.3 50.9 51 59.5 66.1 54.7 54.8 60.9 67.4 59.9 60 62.9 69 SHG 46 45.2 38.7 31.1 49.5 49.5 42.6 33.2 53.1 53.2 45.9 35.2 58.2 58.3 52.4 38.8 CMP 4.42 4.42 4.48 4.51 4.44 4.44 4.5 4.53 4.47 4.47 4.51 4.54 4.5 4.5 4.52 4.54
115 TCG 43.1 43.2 50.3 60.8 47.3 47.3 52.6 62.6 50.1 50.1 55.6 63.9 56 55.9 58.2 65.4 SHG 41.8 42 36.4 30 45.9 45.9 40.2 32.1 48.7 48.7 44.1 34.2 54.4 54.3 50.8 37.9 CMP 4.92 4.92 4.98 5.05 4.96 4.96 5 5.07 4.98 4.98 5.02 5.08 5.03 5.03 5.05 5.08
125 TCG 39 39 43.9 55.7 42.3 42.3 46.9 58.5 46.1 46.1 48.2 59.7 50.9 50.9 51.3 61.4 SHG 37.9 37.9 34.1 28.3 41.1 41 38.2 30.8 44.8 44.8 41.6 32.9 49.4 49.4 48.2 36.9 CMP 5.47 5.46 5.52 5.62 5.51 5.51 5.55 5.64 5.54 5.54 5.56 5.66 5.59 5.59 5.59 5.66
BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb COMP — Compressor Power kw SHG — Gross Sensible Capacity (1000 Btuh) TCG — Compressor Cooling Capicity (1000 Btuh)
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil. 3. The SHC is based on 80 F edb temperature of air entering evapo- rator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581C (2 Tons) - STANDARD MOTOR (BELT DRIVE)
EXTERNALSTATIC PRESSURE (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 600 500 0.08 531 0.08 607 0.14 713 0.21 788 0.29 878 0.37 700 529 0.09 567 0.09 633 0.16 739 0.24 816 0.32 902 0.41 800 547 0.1 592 0.12 660 0.19 761 0.27 845 0.37 937 0.47 900 570 0.13 620 0.14 691 0.22 793 0.32 870 0.42 957 0.53 1000 599 0.15 650 0.16 717 0.26 818 0.36 894 0.47 981 0.58
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
581C036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 567 0.15 145 688 0.22 222 786 0.30 296 871 0.37 368 947 0.44 437 1000 599 0.18 177 717 0.27 265 814 0.35 349 897 0.43 430 972 0.51 509 1100 632 0.22 215 747 0.31 313 842 0.41 407 925 0.50 498 999 0.59 587 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1016 0.51 505 1080 0.57 572 1139 0.64 637 1195 0.71 702 1249 0.77 765 1000 1041 0.59 587 1104 0.67 662 1163 0.74 737 1219 0.81 811 1272 0.89 883 1100 1066 0.68 674 1129 0.76 759 1188 0.85 843 1243 0.93 925 1296 1.01 1007 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 — — — 1400 1147 0.98 972 1208 1.09 1086 — 1500 1175 1.09 1086 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 567 0.15 145 688 0.22 222 786 0.30 296 871 0.37 368 947 0.44 437 1000 599 0.18 177 717 0.27 265 814 0.35 349 897 0.43 430 972 0.51 509 1100 632 0.22 215 747 0.31 313 842 0.41 407 925 0.50 498 999 0.59 587 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1016 0.51 505 1080 0.57 572 1139 0.64 637 1195 0.71 702 1249 0.77 765 1000 1041 0.59 587 1104 0.67 662 1163 0.74 737 1219 0.81 811 1272 0.89 883 1100 1066 0.68 674 1129 0.76 759 1188 0.85 843 1243 0.93 925 1296 1.01 1007 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.
581C048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 — — — 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 — 2000 962 0.85 847 1049 1.05 1043 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 — — — 1400 1147 0.98 972 1208 1.09 1086 — 1500 1175 1.09 1086 — 1600 — 1700 — 1800 — 1900 — 2000 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1200 1.32 1316 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 1165 1.29 1283 1231 1.46 1453 2000 962 0.85 847 1049 1.05 1043 1127 1.24 1233 1198 1.42 1417 1263 1.61 1598

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572 1600 1204 1.21 1207 1263 1.35 1340 1320 1.48 1472 1373 1.61 1603 1424 1.74 1732 1700 1233 1.34 1336 1292 1.49 1480 1348 1.63 1622 1401 1.77 1762 1451 1.91 1901 1800 1262 1.48 1473 1321 1.64 1627 1376 1.79 1779 1428 1.94 1930 1479 2.09 2078 1900 1293 1.63 1620 1350 1.79 1784 1405 1.96 1946 1457 2.12 2106 1506 2.28 2265 2000 1323 1.79 1776 1380 1.96 1950 1434 2.13 2123 1486 2.31 2293 — — —
LEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive. Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 — — — 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 — 2100 1090 0.97 859 1191 1.15 1023 — 2200 1131 1.09 970 1230 1.29 1143 — 2300 1173 1.23 1091 — 2400 — 2500 —
581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 — 1600 1342 1.18 1047 — 1700 1374 1.30 1153 — 1800 — 1900 — 2000 — 2100 — 2200 — 2300 — 2400 — 2500 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.
581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 — — —

581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 1445 1.34 1189 1506 1.48 1312 1564 1.62 1437 1600 1342 1.18 1047 1411 1.32 1173 1474 1.46 1300 1535 1.61 1429 1593 1.76 1560 1700 1374 1.30 1153 1441 1.45 1286 1505 1.60 1420 1565 1.75 1555 1622 1.91 1692 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 — — — 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 — 2200 1538 2.04 1816 1602 2.23 1984 — 2300 1572 2.23 1978 — 2400 — 2500 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.
581C060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 848 0.42 371 968 0.55 486 1069 0.68 600 1158 0.80 715 1238 0.94 831 1600 887 0.49 433 1004 0.63 556 1103 0.76 678 1190 0.90 800 1269 1.04 922 1700 927 0.57 502 1040 0.71 633 1137 0.86 763 1223 1.00 892 1302 1.15 1022 1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 1576 2.41 2142
581C060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1312 1.07 948 1380 1.20 1067 1445 1.34 1189 1506 1.48 1312 1564 1.62 1437 1600 1342 1.18 1047 1411 1.32 1173 1474 1.46 1300 1535 1.61 1429 1593 1.76 1560 1700 1374 1.30 1153 1441 1.45 1286 1505 1.60 1420 1565 1.75 1555 1622 1.91 1692 1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 1713 2.41 2142 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 1688 2.42 2149 1744 2.60 2312 2200 1538 2.04 1816 1602 2.23 1984 1663 2.42 2152 1720 2.61 2321 1775 2.81 2491 2300 1572 2.23 1978 1635 2.42 2153 1695 2.62 2328 1753 2.82 2504 — — — 2400 1607 2.42 2150 1669 2.63 2332 1729 2.83 2515 — 2500 1642 2.63 2333 1704 2.84 2523 —
Refer to page 107 for general Fan Performance Data notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.

581C024 (2Tons)
EXTERNALSTATIC PRESSURE (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 600 490 0.08 521 0.08 597 0.14 703 0.21 788 0.29 868 0.37 700 519 0.09 557 0.09 623 0.16 729 0.24 816 0.32 892 0.41 800 537 0.1 582 0.12 650 0.19 751 0.27 845 0.37 927 0.47 900 560 0.13 610 0.14 681 0.22 783 0.32 870 0.42 947 0.53 1000 589 0.15 640 0.16 707 0.26 808 0.36 894 0.47 971 0.58
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
581C036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 553 0.14 134 681 0.22 221 782 0.32 316 870 0.42 417 948 0.53 526 1000 582 0.16 163 707 0.26 257 807 0.36 358 894 0.47 466 971 0.58 580 1100 612 0.20 196 734 0.30 297 833 0.41 405 919 0.52 519 995 0.64 639 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1019 0.64 640 1084 0.76 760 1146 0.89 885 1203 1.02 1016 1258 1.16 1152 1000 1042 0.70 700 1107 0.83 825 1168 0.96 956 1225 1.10 1091 — — — 1100 1065 0.77 765 1130 0.90 896 1190 1.04 1032 1247 1.18 1173 — — — 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 — 1300 1113 0.92 915 1177 1.06 1058 — 1400 1138 1.01 1000 1201 1.15 1149 — 1500 1163 1.10 1092 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field- sup- plied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 553 0.14 134 681 0.22 221 782 0.32 316 870 0.42 417 948 0.53 526 1000 582 0.16 163 707 0.26 257 807 0.36 358 894 0.47 466 971 0.58 580 1100 612 0.20 196 734 0.30 297 833 0.41 405 919 0.52 519 995 0.64 639 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1019 0.64 640 1084 0.76 760 1146 0.89 885 1203 1.02 1016 1258 1.16 1152 1000 1042 0.70 700 1107 0.83 825 1168 0.96 956 1225 1.10 1091 1279 1.24 1232 1100 1065 0.77 765 1130 0.90 896 1190 1.04 1032 1247 1.18 1173 1301 1.33 1319 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740
LEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive. See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
581C048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 — — — 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 — — — 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 — 1300 1113 0.92 915 1177 1.06 1058 — 1400 1138 1.01 1000 1201 1.15 1149 — 1500 1163 1.10 1092 — 1600 1189 1.20 1191 — 1700 — 1800 — 1900 — 2000 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1177 1.25 1242 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 1205 1.37 1360 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 1165 1.31 1302 1234 1.49 1485

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740 1600 1189 1.20 1191 1252 1.36 1353 1310 1.53 1520 1365 1.70 1690 1418 1.87 1865 1700 1216 1.31 1299 1277 1.48 1468 1335 1.65 1640 1390 1.83 1817 1442 2.01 1998 1800 1242 1.42 1414 1303 1.60 1590 1361 1.78 1770 1415 1.96 1953 1467 2.15 2140 1900 1270 1.55 1538 1330 1.73 1721 1387 1.92 1908 1441 2.11 2098 1493 2.30 2292 2000 1297 1.68 1672 1357 1.87 1862 1414 2.07 2055 1467 2.26 2252 — — —
LEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive. See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 — — — 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 — 2200 1085 1.09 966 1162 1.22 1086 — 2300 1127 1.23 1092 — 2400 — 2500 —
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 — 1600 1270 1.07 952 1342 1.22 1083 — 1700 1295 1.17 1040 — 1800 1321 1.28 1137 — 1900 — 2000 — 2100 — 2200 — 2300 — 2400 — 2500 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field- supplied drive.
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 1457 1.44 1280 1522 1.61 1430 1600 1270 1.07 952 1342 1.22 1083 1411 1.37 1221 1476 1.54 1365 1540 1.71 1517 1700 1295 1.17 1040 1365 1.32 1173 1432 1.48 1313 1497 1.64 1459 1559 1.82 1612 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 — — — 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 — 2400 1500 2.17 1928 1559 2.35 2083 — 2500 1533 2.36 2098 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field- supplied drive.
581C060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753 1600 839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829 1700 879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914 1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1247 0.98 873 1320 1.13 1002 1390 1.28 1137 1457 1.44 1280 1522 1.61 1430 1600 1270 1.07 952 1342 1.22 1083 1411 1.37 1221 1476 1.54 1365 1540 1.71 1517 1700 1295 1.17 1040 1365 1.32 1173 1432 1.48 1313 1497 1.64 1459 1559 1.82 1612 1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 1673 2.53 2246 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 1644 2.52 2239 1699 2.71 2406 2400 1500 2.17 1928 1559 2.35 2083 1616 2.53 2243 1672 2.71 2408 1726 2.90 2579 2500 1533 2.36 2098 1591 2.54 2257 1647 2.73 2421 —
See page 107 for general fan performance notes.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.

UNIT 581C MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 024 936 906 876 846 816 786 756 726 696 656 639 — — 036 1044 1008 971 935 898 862 826 789 753 716 680 — — 048 1185 1144 1102 1061 1019 978 936 895 853 812 770 — — 060 1460 1425 1389 1354 1318 1283 1248 1212 1177 1141 1106 1070 1035
*Approximate fan rpm shown (standard motor/drive).
UNIT 581C MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 030 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — —
*Approximate fan rpm shown (high-static motor/drive).
UNIT 581C UNIT PHASE
MAXIMUM OPERATING WATTS* UNIT VOLTAGE MAXIMUM AMP DRAW 024 Single 0.58 580 208/230 2.0
Single 1.20 1000 208/230 4.9
Three 1.20 1000 208/230 4.9 460 2.2 575 2.2
Single 1.20 1000 208/230 4.9
Three 1.20 1000 208/230 4.9 460 2.2 575 2.2
Single 1.30 1650 208/230 9.2
Three 2.40 2120 208/230 6.7 460 3.0 575 3.0
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT 581C UNIT PHASE
MAXIMUM CONTINUOUS BHP*
MAXIMUM OPERATING WATTS* UNIT VOLTAGE MAXIMUM AMP DRAW
036 Three 2.40 2120 208/230 6.7 460 3.0 575 3.0
048 Three 2.40 2120 208/230 6.7 460 3.0 575 3.0
060 Three 2.90 2615 208/230 8.6 460 3.9 575 3.9
LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

2. The EPACT (Energy Policy Act of 1992) regulates energy require- ments for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance requirements. There- fore, the indoor fan motors for Bryant 581C024-060 units are exempt from these requirements.
UNIT SIZE
581C EFFICIENCY%
024, 036, 048 75 060 74/84*
*Single phase/3 phase. NOTES:
watts = bhp (746) motor efficiency
COMPONENT CFM
600 800 1000 1250 1500 1750 2000 2250 2500 2750 3000
Vertical EconoMi$er IV and EconoMi$er2 0.10 0.20 0.35 0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255
Horizontal EconoMi$er IV and EconoMi$er2 — 0.1 0.125 0.15 0.18 0.225 0.275
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
FIOP — Factory-Installed Option
581C - OPTION/ACCESSORY WEIGHTS
Option / Accessory 024 036 048 060 lb kg lb kg lb kg lb kg Perfect Humidity Dehumidification System 13 6 15 7 23 10 25 11 Power Exhaust - vertical 50 23 50 23 50 23 50 23 Power Exhaust - horizontal 30 14 30 14 30 14 30 14 EconoMi$er ( IV or 2) 50 23 50 23 50 23 50 23 Two Position damper (25%) 22 10 22 10 22 10 22 10 Two Position damper (100%) 39 18 39 18 39 18 39 18 Manual Dampers 12 5 12 5 12 5 12 5 Hail Guard (louvered) 16 7 16 7 16 7 16 7 Hail Guard (standard hood assembly) 25 11 25 11 25 11 25 11 Cu/Cu Condenser Coil 5 2 6 3 13 6 13 6 Cu/Cu Condenser and Evaporator Coils 10 5 12 5 19 9 21 10 Roof Curb (14-in. curb) 115 52 115 52 115 52 115 52 Roof Curb (24-in. curb) 197 89 197 89 197 89 197 89


ALTITUDE COMPENSATION* — 581C024-060
STANDARD UNIT
LOW NOx UNITS
50,000 BTUH NOMINAL INPUT Natural Gas Orifice Size†
ELEVATION
60,000 AND 90,000 BTUH NOMINAL INPUT
120,000 BTUH NOMINAL INPUT Natural Gas Orifice Size†
Orifice Size† 0-2,000 43 49 2,000 44 50 3,000 44 50 4,000 44 50 5,000 45 51 6,000 45 51 7,000 46 51 8,000 47 52 9,000 47 52 10,000 48 52 11,000 49 53 12,000 50 54 13,000 51 55 14,000 52 56
ELEVATION
Orifice Size 0-2,000 38 32 2,000 40 33 3,000 41 35 4,000 42 36 5,000 43 37 6,000 43 38 7,000 44 39 8,000 45 41 9,000 46 42 10,000 47 43 11,000 48 44 12,000 49 44 13,000 50 46 14,000 51 47
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your Bryant distributor.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your Bryant distributor.
ELEVATION MAXIMUM HEATING VALUE
AT SEA LEVEL (Btu/ft3) 0-2000 1100 2001-3000 1050 3001-4000 1000 4001-5000 950 5001-6000 900
*Derating of the gas heating equipment to compensate for the effects of alti- tude is always required. Orifice change is not required if the fuel heating value (at sea level) is below the limits listed in the table at left. Derating con- ditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.
(ft) · Natural Gas

HORIZONTAL ECONOMI$ER IV AND ECONOMI$ER2
PERFORMANCE DATA
PERFORMANCE DATA


Power Exhaust Part No. Power Exhaust Description Application
Power Output
Fans per
PE CRPWREXH021A01 Power Exhaust System (460-3-60) 036-060 0.24 2 CRPWREXH030A01 Power Exhaust System (208/230-1-60) 036-060 0.23 2
(Hp per fan)
Horizontal - Mounted in Return Ductwork
Power Exhaust Part No. Power Exhaust Description Application
Power Output
Fans per
PE CRPWREXH028A01 Power Exhaust System (208/230-1-60) ALL* 0.48 1 CRPWREXH029A01 Power Exhaust System (460-3-60) ALL 0.48 1
(Hp per fan)
* Single or three phase rooftop unit.

OCTAVE BANDS
UNIT 581C
A-WEIGHTED
(db)
63 125 250 500 1000 2000 4000 8000
024-048 76 76.0 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3 060 80 80.0 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
ARI — Air Conditioning and Refrigeration Institute
MINIMUM UNIT
VOLTAGE
COMBUSTION
POWER SUPPLY
DISCONNECT
UNIT SIZE
NOMINAL
RANGE COMPRESSOR OFM
FAN MOTOR IFM CONV OUTLET
SIZE
Min Max QTY RLA LRA QTY FLA FLA FLA MCA MOCP ** FLA LRA
208/ 230-1-60 STD 187 254 1 10.9 63 1 0.7 0.6 2.0 NO 16.3 20 15.6 69 YES 22.3 25 21.2 73
208/ 230-1-60 STD 187 254 1 16 88 1 0.7 0.6 4.9 NO 25.6 30 24.8 101 YES 31.6 35 30.4 106
187 254 1 10.3 77 1 0.7 0.6 4.9 NO 18.5 25 18.3 90 YES 24.5 30 23.8 95
HS 5.8 NO 19.4 25 19.3 120 YES 25.4 30 24.9 124
414 508 1 5.1 39 1 0.4 0.3 2.2 NO 9.0 15 8.9 46 YES 11.7 15 11.4 48
HS 2.6 NO 9.4 15 9.3 60 YES 12.1 15 11.8 63
1.9 NO 7.6 10 7.5 36 YES 9.7 15 9.5 38
518 632 1 4.2 31 1 0.4 0.3†
HS 2.0 NO 7.7 10 7.6 43 YES 9.8 15 9.6 44
Perfect Humidity 1 0.4† 2.6† NO 7.7 10 8.0 48 YES 9.8 15 9.6 50
Determine percent of voltage imbalance.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps UL — Underwriters’ Laboratories
% Voltage Imbalance = 100 x 7 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
*The values listed in this table do not include power exhaust. See table at right for power exhaust requirements. **Fuse or HACR circuit breaker. †460v motor NOTES:
MOCP
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker. 2. Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of volt- age imbalance.
PART NO.
power source) CRPWREXH030A01 036-072 1.6 N/A 0.64 15 CRPWREXH021A01 036-072 N/A 0.68 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
* — Single or three phase rooftop unit N/A — Not available NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 581B060—unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps and the MCA New is below 35; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
= 100 x max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455 3
= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

MINIMUM UNIT
UNIT SIZE
NOMINAL
V-PH-Hz IFM TYPE VOLTAGE
FAN MOTOR IFM CONV OUTLET POWER SUPPLY *
DISCONNECT
SIZE Min Max QTY RLA LRA QTY FLA FLA FLA MCA MOCP** FLA LRA
208/230-1-60 STD 197 254 1 21 115 1 1.5 0.6 4.9 NO 32.7 40 31.5 130 YES 38.7 45 37.0 135
187 254 1 14.1 95 1 1.5 0.6 4.9 NO 24.0 30 23.6 110 YES 30.0 35 29.1 115
HS 5.8 NO 24.9 30 24.6 140 YES 30.9 35 30.1 145
414 508 1 7.1 45 1 0.8 0.3 2.2 NO 11.9 15 11.6 53 YES 14.6 20 14.1 55
HS 2.6 NO 12.3 15 12.1 67 YES 15.0 20 14.6 70
1.9 NO 10.1 15 9.9 44 YES 12.3 15 11.9 46
518 632 1 6.1 38 1 0.6 0.3†
HS 2.0 NO 10.2 15 10.0 51 YES 12.4 15 12.0 52
Perfect Humidity 1 0.8† 2.6† NO 10.3 15 10.1 56 YES 12.5 15 12.1 58
208/230-1-60 STD 187 254 1 25 150 1 1.5 0.6 6.6 NO 39.4 50 38.1 187 YES 45.4 60 43.6 191
187 254 1 17.3 123 1 1.5 0.6 5.8 NO 28.9 35 28.3 168 YES 34.9 40 33.8 173
HS 7.5 NO 30.6 35 30.2 187 YES 36.6 40 35.8 192
414 508 1 8.4 70 1 0.8 0.3† 2.6 NO 13.9 20 13.6 92 YES 16.6 20 16.1 95
HS 3.4 NO 14.7 20 14.5 102 YES 17.4 20 17.0 104
2.0 NO 11.5 15 11.2 66 YES 13.6 15 13.2 67
518 632 1 7.1 53 1 0.6 0.3†
HS 2.8 NO 12.3 15 12.1 75 YES 14.4 20 14.1 76
Perfect Humidity 1 1.9† 3.4† NO 12.2 15 12.0 79 YES 14.4 20 14.0 80
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps UL — Underwriters’ Laboratories
MOCP
POWER EXHAUST
*The values listed in this table do not include power exhaust. See table at right for power exhaust requirements. **Fuse or HACR circuit breaker. †460v motor NOTES:
PART NO.
power source) CRPWREXH030A01 036-072 1.6 N/A 0.64 15 CRPWREXH021A01 036-072 N/A 0.68 N/A 15 CRPWREXH028A01 ALL* 1.7 N/A 0.68 15 CRPWREXH029A01 ALL N/A 0.7 N/A 15
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker. 2. Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of volt- age imbalance.
* — Single or three phase rooftop unit N/A — Not available NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 581B060—5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps and the MCA New is below 35; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
= 100 x max voltage deviation from average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455 3
= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7 457 = 1.53%

NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 2. Three phase motors are protected under primary single phasing conditions. 3. Use copper conductors only. 4. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap (ORN) and connect to 208 v tap (RED). Insulate end of 230 v tap.
C — Contactor, Compressor CAP — Capacitor CLO — Compressor Lockout COMP — Compressor Motor EQUIP — Equipment FPT — Freeze Up Protection Thermostat FU — Fuse GND — Ground HPS — High-Pressure Switch HS — Hall-Effect Sensor I — Ignitor IDM — Induced-Draft Motor IFC — Indoor Fan Contactor IFM — Indoor Fan Motor IGC — Integrated Gas Unit Controller LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve
OFM — Outdoor (Condenser) Fan Motor OLR — Overload Relay P — Plug PL — Plug Assembly QT — Quadruple Terminal RS — Rollout Switch SAT — Supply Air Temperature Sensor TRAN — Transformer
Accessory or Optional Wiring To indicate common potential only; not to represent wiring.

BLACK
BLUE
500 OHM RESISTOR
VIOLET
NOTE 1
PINK
RUN
RED
NOTE 3
50HJ540573 ACTUATOR ASSEMBLY
YELLOW
OPTIONAL CO SENSOR 4 - 20 mA
DIRECT DRIVE
WHITE
ACTUATOR
ECONOMISER2 PLUG
LEGEND OAT — Outdoor Air Temperature Sensor NOTES:
- +



Packaged Rooftop Electric Cooling Unit with Gas Heat – Constant Volume Application HVAC Guide Specifications Size Range: 24,000 to 60,000 Btuh, Nominal (Input Heating) 2 to 5 Tons, Nominal (Cooling)
prepainted baked enamel finish on all externally exposed surfaces. The color of this pre-painted steel is referred to as “American Sterling,” a gray color. Bryant’s paint specification for this color is PH184. Color: American Sterling, this gray color is to match federal standard 595a, #26231. Gloss (per ASTM 0523, 60 deg. F): 60. Hardness of paint film: H-2H pencil hardness. 2. Evaporator fan compartment interior cabinet sur- faces shall be insulated with a minimum 1/2-in. thick, 1 lb density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil-faced fiber- glass insulation shall be used in the gas heat com- partment. 3. Cabinet panels shall be easily removable for servic- ing. 4. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging. 5. Unit shall have a factory-installed, sloped conden- sate drain pan made of a non-corrosive material, providing a minimum 3/4-in.-14 NPT. connection with both vertical and horizontal drains, and shall comply with ASHRAE Standard 62. 6. Unit shall have a factory-installed filter access panel to provide filter access with tool-less removal. 7. Unit shall have standard thru-the-bottom gas and power connection capability (accessory kit is required). C. Fans:
Bryant Model Number: 581C PART 1 — General 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing a hermetic compressor(s) for cooling duty and gas combustion for heating duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings. 1.02 QUALITY ASSURANCE A. Unit exceeds ASHRAE 90.1-2004 Energy Standards.
Units 003-006 are Energy Star qualified. B. Unit shall be rated in accordance with ARI Standards 210
or 360 as applicable. Designed in accordance with UL Standard 1995. C. Unit shall be designed to conform to ASHRAE 15, latest
revision. D. Unit shall be UL-tested and certified in accordance with
ment drawings. Belt drive shall include an adjustable-pitch motor pulley. b. Fan wheel shall be double-inlet type with for-
ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements. E. Roof curb shall be designed to conform to NRCA Stan-
ward-curved blades. c. Bearings shall be sealed, permanently lubri-
cated ball-bearing type for longer life and lower maintenance. 2. Evaporator fan shall be made from steel with a cor- rosion-resistant finish and shall be dynamically bal- anced. 3. Condenser fan shall be of the direct-driven (with totally enclosed motors) propeller type and shall discharge air vertically. 4. Condenser fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynamically balanced. 5. Induced-draft blower shall be of the direct-driven, single inlet, forward-curved centrifugal type, made from steel with a corrosion-resistant finish and shall be dynamically balanced. D. Compressor(s):
dards. F. Insulation and adhesive shall meet NFPA 90A require-
ments for flame spread and smoke generation. G. Unit casing shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen). H. Unit shall be designed in accordance with ISO
9001:2000, and shall be manufactured in a facility regis- tered to ISO 9001:2000. I. Each unit shall be subjected to a completely automated
run testing on the assembly line. A factory-supplied print- out indicating tested pressures, amperages, data, and inspectors; providing certification of the unit status at the time of manufacture; shall be available upon request. 0.01 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recom- mendations. PART 2 — Product 2.01 EQUIPMENT (STANDARD) A. General:
Factory assembled, single-piece heating and cooling unit. Contained within the unit enclosure shall be all fac- tory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:

to maintain coating integrity and minimize corro- sion potential between coil and pan. F. Heating Section:
fied to UL 1995 burst test at 2,200 psi. b. Evaporator and condenser coils shall be leak
tested to 150 psig and pressure tested to 400 psig. 3. Optional Coils: a. Optional pre-coated aluminum-fin coils shall
have a durable epoxy-phenolic coating to pro- vide protection in mildly corrosive coastal envi- ronments. Coating shall be applied to the aluminum fin stock prior to the fin stamping pro- cess to create an inert barrier between the alu- minum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b. Copper-fin coils shall be constructed of copper
tubular-section type constructed of a minimum of 20-gage steel coated with a nominal 1.2 mil aluminum-silicone alloy for corrosion resistance. b. The optional stainless steel heat exchanger
shall be of the tubular-section type, constructed of a minimum of 20-gage type 409 stainless steel. 3. Burners shall be of the in-shot type constructed of aluminum-coated steel. 4. All gas piping shall enter the unit cabinet at a single location on side of unit (horizontal plane). 5. The integrated gas controller (IGC) board shall include gas heat operation fault notification using an LED (light-emitting diode). 6. Unit shall be equipped with anti-cycle protection with one short cycle on unit flame rollout switch or 4 continuous short cycles on the high-temperature limit switch. Fault indication shall be made using an LED. 7. The IGC board shall contain algorithms that modify evaporator-fan operation to prevent future cycling on high-temperature limit switch. 8. The LED shall be visible without removal of control box access panel. G. Refrigerant Components:
fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper construction shall provide protection in moderate coastal environments. c. E-Coated aluminum-fin coils shall have a flexible
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resis- tance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corrosion durability shall be con- firmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil con- struction shall be aluminum fins mechanically bonded to copper tubes. d. E-Coated copper-fin coils shall have a flexible
Refrigerant circuit components shall include: 1. Fixed orifice metering system (AcutrolTM device). 2. Refrigerant filter drier. 3. Service gage connections on suction, discharge, and liquid lines. H. Filter Section:
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resis- tance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corrosion durability shall be con- firmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil con- struction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from contacting sheet metal coil pan
protector which provides anti-cycle reset capa- bility at the space thermostat, should any of the following standard safety devices trip and shut off compressor.

The lockout protection shall be easily discon- nected at the control board, if necessary. b. Heating section shall be provided with the fol-
f. EconoMi$er IV and EconoMi$er2 shall be equipped with a barometric relief damper capa- ble of relieving up to 100% return air. g. Designed to close damper(s) during loss-of-
lowing minimum protections:
power situations with spring return built into motor. h. Dry bulb outdoor-air temperature sensor shall be
provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F. For the EconoMi$er IV, the return air sen- sor, indoor enthalpy sensor, and outdoor enthalpy sensor shall be provided as field- installed accessories to provide enthalpy control, differential enthalpy control, and differential dry bulb temperature control. For the EconoMi$er2, the enthalpy, differential temperature (adjust- able), and differential enthalpy control shall be provided as field-installed accessories. i. The EconoMi$er IV and EconoMi$er2 shall have a gear-driven parallel blade design. j. EconoMi$er IV microprocessor control shall pro- vide control of internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%. k. EconoMi$er2 shall be capable of control from a
All unit power wiring shall enter unit cabinet at a single factory-predrilled location. L. Motors:
1. Compressor motors shall be cooled by refrigerant gas passing through motor windings and shall have line break thermal and current overload protection. 2. Evaporator-fan motor shall have permanently lubri- cated bearings and inherent automatic-reset ther- mal overload protection. Evaporator motors are designed specifically for Carrier and do not have conventional horsepower (HP) ratings listed on the motor nameplate. Motors are designed and quali- fied in the “air-over” location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors” above that rating may be applied. 3. Totally enclosed condenser-fan motor shall have permanently lubricated bearings, and inherent auto- matic-reset thermal overload protection. 4. Induced-draft motor shall have permanently lubri- cated sealed bearings and inherent automatic-reset thermal overload protection. M. Special Features:
4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control (required for PremierLink™ or third party control inter- face). l. EconoMi$er IV Microprocessor Occupied Mini- mum Damper Position Setting maintains the minimum airflow into the building during occu- pied period providing design ventilation rate for full occupancy (damper position during heating). A remote potentiometer may be used to override the set point. m. EconoMi$er IV Microprocessor Unoccupied Min-
imum Damper Position Setting — The EconoMi$er IV dampers shall be closed when the unit is in the occupied mode. n. EconoMi$er IV Microprocessor IAQ/DCV Maxi-
mum Damper Position Setting — Setting the maximum position of the damper prevents the introduction of large amounts of hot or cold air into the space. This position is intended to sat- isfy the base minimum ventilation rate. o. EconoMi$er IV Microprocessor IAQ/DCV control
Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office. 1. Roof Curbs (Horizontal and Vertical): a. Formed galvanized steel with wood nailer strip
modulates the outdoor-air damper to provide ventilation based on the optional 2 to 10 vdc CO2 sensor input. p. Compressor lockout sensor (opens at 35 F,
and shall be capable of supporting entire unit weight. b. Permits installation and securing of ductwork to
closes at 50 F). q. Actuator shall be direct coupled to economizer
curb prior to mounting unit on the curb. *2. Integrated Economizers:
gear, eliminating linkage arms and rods. r. Control LEDs:
a. Integrated integral modulating type capable of
simultaneous economizer and compressor oper- ation. b. Available as a factory-installed option in vertical
supply/return configuration only. (Available as a field-installed accessory for dedicated horizontal and/or vertical supply return configurations.) c. Includes all hardware and controls to provide
cooling with outdoor air. d. Equipped with low-leakage dampers, not to
installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation.
exceed 2% leakage at 1 in. wg pressure differ- ential. e. Capable of introducing up to 100% outdoor air.

independent fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed step-down transformer powered from the LOAD (RTU) side of the unit power supply. Shall be accessible from outside the unit. 15. High-Static Indoor Fan Motor(s) and Drive(s) (004- 012): High-static motor(s) and drive(s) shall be factory- installed to provide additional performance range. 16. Flue Discharge Deflector: Flue discharge deflector directs unit exhaust verti- cally instead of horizontally. 17. Condenser Coil Grille: The grille protects the condenser coil from damage by large objects without increasing unit clearances. 18. Compressor Cycle Delay: Unit shall be prevented from restarting for minimum of 5 minutes after shutdown. 19. Thru-the-Bottom Utility Connectors: Kit shall provide connectors to permit gas and elec- trical connections to be brought to the unit through the basepan. 20. Fan/Filter Status Switch: Switch shall provide status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat. 21. Energy$Recycler™ Energy Recovery System: The package shall be an outdoor rooftop, surface mounted, electronically controlled, air-to-air heat pump unit utilizing a hermetic compressor for cool- ing and heating duty. The Energy$Recycler system shall recover energy from building exhaust air and pre-condition ventila- tion air to allow higher ventilation requirements and minimizing energy cost. This option shall be available with the following: a. A mounting kit for the Energy$Recycler device
a. Two-position damper package shall include sin-
gle blade damper and motor. Admits up to 100% outdoor air. b. Damper shall close upon indoor (evaporator) fan
shutoff. c. Designed to close damper during loss of power
situations. d. Equipped with 15% barometric relief damper. 5. 25% Two-Position Damper: a. Two-position damper package shall include sin-
gle blade damper and motor. Admits up to 25% outdoor air. b. Damper shall close upon indoor (evaporator) fan
shutoff. *6. Head Pressure Control Package:
Consists of solid-state control and condenser-coil temperature sensor to maintain condensing temper- ature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. 7. LP (Liquid Propane) Conversion Kit: Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane (valid up to 2000 ft elevation). *8. Electronic Programmable Thermostat:
Units shall be capable of using deluxe full-featured electronic thermostat. Thermostat shall use built-in compressor cycle delay control for both heating and cooling duty. Thermostat shall be capable of work- ing with Carrier direct digital controls. 9. Light Commercial Thermidistat™ Device: Field-installed wall-mounted thermostat is used to control temperature and activation of the dehumidi- fication package. The Thermidistat device can be set for humidity settings from 50% to 90% relative humidity. Automatic humidity control adjusts indoor humidity based on the outdoor temperature sensor. *10. Flue Shield:
for cantilever mounting off of the rooftop unit with out the use of a slab or a roof curb. b. A field-installed 460-v to 208/230-v transformer
to provide power when the 208-230/1/60 or 100 size Energy$Recycler device is used with a 460- v rooftop unit. c. A field-installed 575-v to 208/230-v transformer
Flue shield shall provide protection from the hot sides of the gas flue hood. *11. Thermostat and Subbase:
to provide power when an Energy$Recycler device is used with a 575-v unit. 22. Power Exhaust Accessory for EconoMi$er IV or EconoMi$er2: Power exhaust shall be used in conjunction with EconoMi$er IV or EconoMi$er2 to provide system exhaust of up to 100% of return air (vertical only). The power exhaust is a field-installed accessory (separate vertical and horizontal design). NOTE: Horizontal power exhaust is intended to mount in return ductwork. As the outdoor-air damper opens and closes, both propeller fans are energized and deenergized through the EconoMi$er IV controller. The set point is factory set at 100% of outdoor-air, and is adjust- able 0 to 100% to meet specific job requirements. Available in 208/230-1-60 v or 460-3-60 v. An LED light on the controller indicates when the power exhaust is operating.
Thermostat and subbase shall provide staged cool- ing and heating automatic (or manual) changeover, fan control, and indicator light. *12. Condenser Coil Hail Guard Assembly:
Hail guard shall protect against damage from hail and flying debris. 13. Unit-Mounted, Non-Fused Disconnect Switch: Switch shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall pro- vide unit power shutoff. Switch shall be accessible from outside the unit and shall provide power off lockout capability. 14. Convenience Outlet: Outlet shall be factory-installed and internally mounted with easily accessible 115-v female recep- tacle. Shall include 15 amp GFI receptacle with

For the EconoMi$er2, the power exhaust shall be controlled by the or third party controls. 23. Outdoor Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2): The outdoor air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device to pro- vide single enthalpy control. When used in conjunc- tion with a return air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential enthalpy control. The sensor allows the EconoMi$er IV or EconoMi$er2 controller to deter- mine if outside air is suitable for free cooling. 24. Return Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2): The return air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with an outdoor air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential enthalpy control. 25. Return Air Temperature Sensor (EconoMi$er IV or EconoMi$er2): The return air temperature sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with the standard outdoor air temperature sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential temper- ature control. 26. Indoor Air Quality (CO2) Sensor (EconoMi$er2): a. Shall have the ability to provide demand ventila-
light inhibits and kills mold, fungus and microbial growth. The lamps have an output rating at 45F in 400 fpm airflow of 120 microwatts/cm2 at 1 meter. 31. Perfect Humidity™ Adaptive Dehumidification Sys- tem: a. The Perfect Humidity dehumidification system
shall be factory-installed in the rooftop unit, and shall provide greater dehumidification of the occupied space by two modes of dehumidifica- tion operations beside its normal design cooling mode:
1) Subcooling mode further subcools the hot liquid refrigerant leaving the condenser coil when both temperature and humidity in the space are not satisfied. 2) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the com- pressor with the hot liquid refrigerant leav- ing the condenser coil to create a two- phase heat transfer in the system, resulting in a neutral leaving-air temperature when only humidity in the space is not satisfied. b. The system shall consist of a subcooling/ reheat
dehumidification coil located downstream of the standard evaporator coil. This dehumidification coil is a two-row coil on the 005 and 006 units, and a one-row coil on 003 and 004 units. c. The system shall include crankcase heater(s) for
the scroll compressor(s). d. The system shall include a low outdoor air tem-
tion indoor air quality (IAQ) control through the EconoMi$er2 with an IAQ sensor. b. The IAQ sensor shall be available in duct mount,
perature switch to lock out both subcooling and hot gas reheat mode when the outdoor-air tem- perature is below 40 F. e. The system shall include a Motormaster® low
wall mount, and wall mount with LED display. The set point shall have adjustment capability. c. Requires EconoMi$er2, or Apollo control options. 27. Indoor Air Quality (CO2) Room Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ventilation control through the EconoMi$er IV. The IAQ sensor shall be wall mounted with an LED dis- play in parts per million. The set point shall have adjustment capability. 28. Return Air CO2 Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ventilation control through the EconoMi$er IV. The IAQ sensor shall be duct mounted. The set point shall have adjustment capability. 29. Gas Heat options (sizes 036-060): a. Single-stage gas heat shall be provided in lieu of
ambient control to ensure the normal design cooling mode capable of down to 0° F low ambi- ent operation. f. The system shall include a low-pressure switch on the suction line to ensure low pressure start- up of hot gas reheat mode at lower outdoor tem- perature condition. g. The system operation may be controlled by a
field-installed, wall-mounted humidistat. The dehumidification circuit will then operate only when needed. Field connections for the humidis- tat are made in the low-voltage compartment of the unit control box. The sensor can be set for any level between 55% and 80% relative humid- ity. h. The system shall include a Thermal Expansion
Valve (TXV) to ensure a positive superheat con- dition and a balance of pressure drop. 32. Humidistat: Field-installed, wall-mounted humidistat is used to control activation of the dehumidification package. The humidistat can be set for humidity levels between 20% and 80% relative humidity. 33. Hinged Panel Option: Hinged panel option provides hinged access panels for the filter, compressor, evaporator fan, and con- trol box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is per- manently attached to the rooftop unit.
two-stage heat. b. NOx reduction shall be provided to reduce
nitrous oxide emissions to meet the California Air Quality Management NOx requirement of 40 nanograms/joule or less. c. Primary tubes on low NOx units shall be 409
stainless steel. Other components shall be alu- minized steel. 30. Ultraviolet Germicidal Lamps: Ultraviolet germicidal lamps are designed to elimi- nate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germi- cidal lamps are field installed in the evaporator sec- tion of the unit, aimed at the evaporator coil and condensate pan. The short wavelength ultraviolet

UNIT 579F 180 216 240 300 208/230, 460 v 575 v NOMINAL CAPACITY (tons) 15 18 20 25 OPERATING WEIGHT (lb) 1650 1800 1850 2000 Economizer 90 Roof Curb 200 COMPRESSOR Scroll
1...SM120, 1...SR*782AE 1...SM120, 1...SM110 1...SM161, 1...SM120 Number of Refrigerant Circuits 2 2 2 Oil (oz) (Ckt 1, Ckt 2) 110, 72 110,110 112, 110 Stages of Capacity Control (%) 50/50 60/40 52/48 56/44 REFRIGERANT TYPE R-22 Expansion Device TXV Operating Charge (lb-oz) Circuit 1* 10-13 10-5 15-2 16-3 21-0 Circuit 2 11-5 14-8 15-4 CONDENSER COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced,
Quantity...Model (Ckt 1, Ckt 2) 2...SR*942AE 2 90, 90
Aluminum Pre-Coated, or Copper Plate Fins Rows...Fins/in. 2...17 21.7 3...15 3...15 4...15 Total Face Area (sq ft) 21.7 21.7 21.7 CONDENSER FAN Propeller Type Nominal Cfm 10,400 9300 13,700 12,500 Quantity...Diameter (in.) 3...22 3...22 2...30 2...30 Motor Hp...Rpm 1/2...1050 1/2...1050 1...1075 1...1075 Watts Input (Total) 1100 1100 3400 3400 EVAPORATOR COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split Rows...Fins/in. 2...17 3...15 3...15 4...15 Total Face Area (sq ft) 17.5 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2...10 x 10 2...10 x 10 2...12 x 12 2...12 x 12 2...12 x 12 Type Drive Belt Nominal Cfm 6000 6000 7200 8000 10,000 Motor Hp 3.7 3.0 5 7.5 10 Motor Nominal Rpm 1725 1725 1745 1745 1740
Maximum Continuous Bhp 4.25 3.45 5.90 8.7 [208/230, 575 v] 9.5 [460 v] 10.2 [208/230, 575 v] 11.8 [460 v] Motor Frame Size 56H 56H 184T 213T 215T Nominal Rpm High/Low — Fan r/s Range Low-Medium Static 891-1179 1159-1429 910-1095 1002-1225 1066-1283 High Static 1227-1550 — 1069-1287 1193-1458 1332-1550 Motor Bearing Type Ball Maximum Allowable Rpm 1550 Motor Pulley Pitch Diameter Low-Medium Static 3.1/4.1 4.3/5.3 4.9/5.9 5.4/6.6 4.9/5.9 Min/Max (in.) High Static 3.7/4.7 — 4.9/5.9 5.4/6.6 4.9/5.9 Nominal Motor Shaft Diameter (in.) 7/8 7/8 11/8 13/8 13/8 Fan Pulley Pitch Diameter (in.) Low-Medium Static 6.0 6.4 9.4 9.4 8.0 High Static 5.2 — 8.0 7.9 6.4 Nominal Fan Shaft Diameter (in.) 13/16 13/16 17/16 17/16 17/16 Belt, Quantity...Type...Length (in.) Low-Medium Static 1...BX...42 1...BX...45 1...BX...50 1...BX...54 2...BX...50 High Static 1...BX...42 — 1...BX...48 1...BX...50 2...BX...47 Pulley Center Line Distance (in.) 13.5-15.5 13.5-15.5 13.3-14.8 14.6-15.4 14.6-15.4 Speed Change per Full Turn of
Low-Medium Static 48 44 37 37 36 High Static 55 — 34 44 45 Movable Pulley Maximum Full Turns
Movable Pulley Flange (rpm)
From Closed Position 5 Factory Speed 3.5 Factory Speed Setting (rpm) Low-Medium Static 1035 1296 1002 1120 1182 High Static 1389 — 1178 1328 1470 Fan Shaft Diameter at Pulley (in.) 13/16 13/16 17/16 17/16 17/16
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora- tor coils; and Circuit 2 uses the upper portion of both coils. †Rollout switch is manual reset. **The 579F300 units requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). NOTE: The 579F units have a low-pressure switch (standard) located on the suc- tion side.

Rollout Switch Cutout Temp (F)† 190 Burner Orifice Diameter (in drill size)
Natural Gas 0.1285...30/0.136...29 Thermostat Heat Anticipator Setting (amps)
208/230, 575 Stage 1 0.98 Stage 2 0.44 460 v Stage 1 0.80 Stage 2 0.44 Gas Input Stage 1 172,000/225,000 206,000/270,000 206,000/270,000 206,000/270,000 Stage 2 230,000/300,000 275,000/360,000 275,000/360,000 275,000/360,000 Efficiency (Steady State) (%) 81 Temperature Rise Range 15-45/20-50 Manifold Pressure (in. wg)
Natural Gas 3.3 Gas Valve Quantity 1 Field Gas Connection Size (in.-FPT) 3/4 HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto) 320 LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto) 44 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 2...20 x 25 x 1 1...20 x 20 x 1 RETURN-AIR FILTERS Throwaway** Quantity...Size (in.) 4...20 x 20 x 2 4...16 x 20 x 2 POWER EXHAUST 1/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
†Rollout switch is manual reset. **The 579F300 units requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equiva- lent). NOTE: The 579F units have a low-pressure switch (standard) located on the suc- tion side.
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora- tor coils; and Circuit 2 uses the upper portion of both coils.
BASE UNIT OPERATING WEIGHTS* 180 216 240 300 lb kg lb kg lb kg lb kg 579F 1650 748 1800 816 1850 839 2000 907
*Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information.
(Weight Adders)
OPTION/ACCESSORY WEIGHTS 180 216 240 300 lb kg lb kg lb kg lb kg Barometric Relief Damper 50 23 50 23 50 23 50 23 Power Exhaust 85 39 85 39 85 39 85 39 EconoMi$er IV 90 41 90 41 90 41 90 41 Cu Condenser Coil 150 68 150 68 150 68 150 68 Cu Condenser and Evaporator Coils 280 127 280 127 280 127 280 127 Roof Curb (14-in. curb) 200 91 200 91 200 91 200 91 Horizontal Adapter Curb (Pre-Assembled) 250 113 250 113 250 113 250 113 Horizontal Adapter Curb (Field-Assembled) 343 156 343 156 343 156 343 156 Hail Guard 60 27 60 27 60 27 60 27
Cu — Copper

Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
180 1650 748 90 41 423 192 386 175 403 183 438 199 3-5 1041 3-5 1041 1-10 559 216 1800 816 90 41 432 196 410 186 461 209 472 214 3-3 991 3-7 1092 1-8 508
requires no clearance.
NOTES:
WEIGHT CORNER
WEIGHT ECONOMIZER
STD UNIT
UNIT
a48-7338

Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
240 1850 839 90 41 443 201 406 184 476 216 525 238 3-2 965 3-5 1041 1-8 508 300 2000 907 90 41 471 214 428 194 526 239 574 260 3-2 965 3-5 1041 1-8 508
requires no clearance.
NOTES:
WEIGHT CORNER
WEIGHT ECONOMIZER
STD UNIT
UNIT
a48-7339

CRRFCURB011A00 2′- 0″ (610) Standard Curb for Units Requiring High Installation
CRRFCURB012A00 2′- 0″ (610) Side Supply and Return Curb for High Installation
CRRFCURB010A00 1′−2″ (305) Standard Curb 14″ High
a48-7928



FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
ACCESSORY PACKAGE NO.
CRRFCURB013A00 1 ′ -11 ″ (584)
Horizontal Supply/Return Adapter Installation (579F180-300)
2'-2 1/16" 1'-6 5/16"
For horizontal return applications: The power exhaust relief must be installed in the return air duct.


LEGEND K.O. — Knockout

a48-4184 · a48-4185

IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity 170,000 Btuh Sensible Heat Capacity 111,000 Btuh Required Heating Capacity 200,000 Btuh Condenser Entering Air Temp 95 F (Summer) Evaporator Entering Air Temp 80 F edb,
MENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 164 find:
External static pressure 0.60 in. wg EconoMi$er IV static pressure 0.04 in. wg Total static pressure 0.64 in. wg
67 F ewb Evaporator Air Quantity 4,500 cfm External Static Pressure 0.6 in. wg Electrical Characteristics (V-Ph-Hz) 460-3-60 Vertical discharge unit with optional EconoMi$er IV required. edb — Entering dry-bulb ewb — Entering wet-bulb II SELECT UNIT BASED ON REQUIRED COOLING
Enter the Fan Performance table 579F180300 (page 161) at 4,500 cfm and 0.64 in. wg external static pressure. By interpolation, find that the rpm is 1017 and the watts are 1743. V DETERMINE NET COOLING CAPACITY.
Cooling capacities are gross capacities and do not include indoor (evaporator) fan motor (IFM) heat. Use the watts input power to the motor calculated in Section IV above. IFM Watts = 1743 Determine net cooling capacity using the following formula: Net capacity = Gross capacity – IFM heat
CAPACITY. Enter Cooling Capacities table for 579F180300 (page 152) at condenser entering temperature 95 F, evaporator air entering at 4,500 cfm and 67 F wb. The 579F180300 unit will provide a total cooling capacity of 179,000 Btuh and a sensible heating capacity of 117,000 Btuh. For air entering evaporator at temperatures other than 80 F edb, calculate sensible heat capacity correction as required using the for- mula in the notes following the Cooling Capacities tables. NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor heat. To calcu- late net capacities, see Step V. III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
= 179,000 Btuh – 1743 Watts
(3.412 Btuh ) Watts
= 179,000 Btuh – 5947 Btuh = 173,053 Btuh Net sensible capacity = 117,000 Btuh – 5947 Btuh
= 111,053 Btuh The calculations show that a 579F180300 unit with the standard motor and standard low-medium static drive is the correct selection for the given conditions.
DESIGN CONDITION REQUIREMENTS. In the ARI Heating Capacities and Efficiencies table (page 12) note that the 579F180300 will provide an output capacity of 243,000 Btuh, which is adequate for the given application.

Evaporator Air Quantity — Cfm 4500 5250 Evaporator Air — Ewb (F)/BF 54/0.48 58/0.32 62/0.22 67/0.20 72/0.19 76/0.24 80/0.04 54/0.54 58/0.39 62/0.25 67/0.23 72/0.21 76/0.23 80/0.04
Temp (F) Air Entering
75 TC — 168 177 192 209 225 240 171 171 182 197 214 229 246 SHC — 152 142 123 103 85 69 171 150 151 130 108 88 69 kW — 12.4 12.6 13.0 13.3 13.6 13.9 12.5 12.6 12.7 13.1 13.4 13.7 14.0
85 TC 159 164 171 186 202 219 233 166 172 175 190 207 222 237 SHC 159 148 139 120 100 83 66 166 151 148 127 105 86 67 kW 13.7 13.8 14.1 14.4 14.8 15.5 15.4 13.9 14.0 14.1 14.5 14.9 15.2 15.5
95 TC 154 159 165 179 195 210 226 161 164 169 183 199 214 229 SHC 154 142 136 117 98 80 64 161 155 145 124 102 83 64 kW 15.3 15.4 15.5 15.9 16.3 16.7 17.3 15.5 15.5 15.7 16.0 16.5 16.8 17.1
105 TC 149 154 158 172 187 201 216 156 156 162 176 191 205 222 SHC 149 137 133 114 95 78 61 156 156 142 121 99 81 62 kW 16.9 17.0 17.1 17.6 18.0 18.4 18.7 17.2 17.1 17.2 17.7 18.1 18.5 19.1
115 TC 144 145 152 165 179 193 207 150 151 156 168 183 196 210 SHC 144 142 130 111 92 75 58 150 151 137 118 96 78 58 kW 18.6 18.6 18.9 19.3 19.8 20.2 20.6 18.9 18.9 19.0 19.5 19.9 20.3 20.7
117 TC 143 143 150 163 178 191 205 149 149 154 167 181 194 208 SHC 143 142 129 110 91 74 57 149 149 136 117 96 77 58 kW 18.9 19.0 19.2 19.7 20.2 20.5 20.9 19.2 19.2 19.4 19.8 20.3 20.7 21.0
120 TC 141 141 148 161 175 — — 147 148 152 164 179 — — SHC 141 141 128 109 90 — — 147 148 135 116 95 — — kW 19.5 19.5 19.8 20.2 20.7 — — 19.8 19.8 19.9 20.4 20.8 — —
579F180 (15 Tons) (cont)
Temp (F) Air Entering
Evaporator Air Quantity — Cfm 6000 6750 Evaporator Air — Ewb (F)/BF 54/0.58 58/0.43 62/0.30 67/0.25 72/0.23 76/0.24 80/0.04 54/0.62 58/0.48 62/0.36 67/0.28 72/0.25 76/0.25 80/0.03
75 TC 178 174 185 200 218 233 250 183 179 183 203 221 236 253 SHC 178 171 159 136 112 91 70 183 179 161 142 116 93 70 kW 12.7 12.7 12.8 13.1 13.5 13.8 14.1 12.8 12.7 12.8 13.2 13.5 13.9 14.1
85 TC 173 173 179 193 210 227 244 178 178 183 196 213 228 247 SHC 173 172 156 133 109 89 68 178 178 161 139 113 91 68 kW 14.1 14.1 14.2 14.6 15.0 15.8 16.2 14.2 14.2 14.3 14.7 15.1 15.3 16.3
95 TC 167 167 173 186 203 217 232 173 173 177 189 205 220 235 SHC 167 167 152 130 106 86 64 173 173 157 137 111 88 65 kW 15.7 15.6 15.8 16.1 16.6 16.9 17.2 15.8 15.8 15.9 16.2 16.6 17.0 17.3
105 TC 162 162 167 179 194 208 223 168 167 171 181 197 211 225 SHC 162 162 147 127 104 83 61 168 167 152 133 108 85 62 kW 17.3 17.3 17.4 17.8 18.2 18.5 18.9 17.4 17.4 17.5 17.9 18.3 18.6 18.9
115 TC 156 156 160 171 186 199 213 160 160 165 173 188 201 215 SHC 156 156 143 124 101 80 59 160 160 145 130 104 82 59 kW 19.1 19.1 19.1 19.6 20.0 20.4 20.7 19.2 19.2 19.3 19.6 20.1 20.5 20.8
117 TC 154 155 159 169 184 197 211 159 159 163 171 186 199 — SHC 154 155 142 124 100 79 58 159 159 144 129 104 82 — kW 19.4 19.4 19.5 19.9 20.4 20.8 21.1 19.6 19.6 19.7 20.0 20.4 20.8 —
120 TC 153 153 157 167 181 — — 157 157 161 169 — — — SHC 153 153 140 122 99 — — 157 157 142 128 — — — kW 19.9 19.9 20.0 20.4 20.9 — — 20.1 20.1 20.2 20.5 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4.5 x cfm

579F180 (15 Tons) (cont)
Evaporator Air Quantity — Cfm
Temp (F) Air Entering
7500 Evaporator Air — Ewb (F)/BF 54/0.65 58/0.52 62/0.41 67/0.30 72/0.28 76/0.27 80/0.03
75 TC 188 183 193 206 223 239 256 SHC 188 183 170 148 120 95 70 kW 12.9 12.8 13.0 13.2 13.6 13.9 14.2
85 TC 183 183 187 199 215 233 249 SHC 183 183 167 145 117 94 68 kW 14.4 14.4 14.4 14.7 15.1 15.9 16.3
95 TC 177 177 181 191 207 222 237 SHC 177 177 161 142 114 90 65 kW 15.9 15.9 16.0 16.3 16.7 17.0 17.3
105 TC 171 171 175 183 199 213 228 SHC 171 171 154 138 111 87 62 kW 17.6 17.6 17.7 18.0 18.4 18.7 19.0
115 TC 164 164 169 175 190 203 217 SHC 164 164 146 135 108 84 59 kW 19.4 19.4 19.5 19.7 20.2 20.5 20.9
117 TC 163 163 167 173 188 201 — SHC 163 163 145 134 107 84 — kW 19.7 19.7 19.9 20.0 20.5 20.9 —
120 TC 161 161 165 170 — — — SHC 161 161 143 133 — — — kW 20.2 20.3 20.4 20.6 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4.5 x cfm
Condenser · (Edb)

Evaporator Air Quantity — Cfm 5400 6000 Evaporator Air — Ewb (F)/BF 54/0.49 58/0.31 62/0.20 67/0.18 72/0.16 76/0.19 80/0.05 54/0.53 58/0.35 62/0.23 67/0.19 72/0.17 76/0.19 80/0.05
Temp (F) Air Entering
75 TC 194 198 206 223 243 260 277 200 203 210 227 246 263 — SHC 194 178 169 146 121 99 79 200 191 177 152 125 102 — kW 13.6 13.7 13.9 14.2 14.6 15.0 15.2 13.7 13.8 14.0 14.4 14.7 15.1 —
85 TC 189 192 200 217 235 252 269 195 195 204 220 239 255 — SHC 189 176 166 143 118 97 76 195 195 174 149 123 100 — kW 15.1 15.2 15.4 15.9 16.3 16.6 16.9 15.3 15.3 15.7 16.0 16.4 16.8 —
95 TC 183 184 193 209 227 243 — 189 190 196 212 230 246 — SHC 183 181 162 140 115 94 — 189 190 170 146 120 97 — kW 16.8 16.8 17.1 17.6 18.0 18.4 — 17.0 17.0 17.2 17.6 18.1 18.5 —
105 TC 177 178 185 201 218 234 — 183 185 189 204 221 237 — SHC 177 178 159 137 112 91 — 183 185 166 143 116 94 — kW 18.6 18.6 18.8 19.3 19.8 20.2 — 18.8 18.6 18.9 19.4 19.9 20.3 —
115 TC 171 171 177 192 209 224 — 176 177 181 195 212 226 — SHC 171 171 154 133 109 88 — 176 177 161 139 113 90 — kW 20.5 20.5 20.7 21.2 21.8 22.1 — 20.7 20.7 20.8 21.3 21.8 22.2 —
117 TC 170 170 176 191 207 222 — 175 175 180 193 210 224 — SHC 170 170 154 132 108 87 — 175 175 160 138 112 90 — kW 20.9 20.9 21.1 21.6 22.1 22.5 — 21.1 21.1 21.2 21.7 22.2 22.6 —
120 TC 168 168 173 188 204 — — 173 173 177 191 207 — — SHC 168 168 152 131 107 — — 173 173 159 137 111 — — kW 21.5 21.5 21.7 22.2 22.7 — — 21.7 21.7 21.8 22.3 22.8 — —
579F216 (18 Tons) (cont)
Evaporator Air Quantity — Cfm 7000 8000 Evaporator Air — Ewb (F)/BF 54/0.58 58/0.42 62/0.29 67/0.21 72/0.20 76/0.20 80/0.05 54/0.62 58/0.48 62/0.36 67/0.23 72/0.22 76/0.21 80/0.04
Temp (F) Air Entering
75 TC 209 209 215 232 251 268 — 216 217 221 236 255 272 — SHC 209 209 189 162 132 106 — 216 217 198 171 138 109 — kW 13.9 13.9 14.1 14.5 14.9 15.2 — 14.1 14.1 14.2 14.5 15.0 15.3 —
85 TC 203 204 209 224 243 260 — 211 211 215 228 247 263 — SHC 203 204 185 159 129 103 — 211 211 192 168 135 107 — kW 15.5 15.5 15.7 16.1 16.5 16.9 — 15.7 15.7 15.8 16.2 16.6 17.0 —
95 TC 197 197 202 216 235 251 — 204 204 209 220 238 254 — SHC 197 197 180 156 126 100 — 204 204 185 165 132 104 — kW 17.2 17.2 17.4 17.8 18.2 18.7 — 17.4 17.4 17.6 17.9 18.3 18.7 —
105 TC 191 191 195 208 225 241 — 197 197 202 211 228 244 — SHC 191 191 175 152 123 97 — 197 197 177 161 128 100 — kW 19.0 19.0 19.2 19.5 20.0 20.5 — 19.2 19.2 19.3 19.6 20.1 20.6 —
115 TC 184 184 188 199 215 230 — 190 190 194 202 218 — — SHC 184 184 168 149 119 94 — 190 190 170 158 125 — — kW 21.0 21.0 21.1 21.5 22.0 22.4 — 21.1 21.1 21.2 21.6 22.1 — —
117 TC 183 183 187 197 214 228 — 188 188 192 200 216 — — SHC 183 183 166 148 118 93 — 188 188 171 157 124 — — kW 21.3 21.4 21.5 21.8 22.4 22.7 — 21.5 21.5 21.7 22.0 22.5 — —
120 TC 180 180 185 194 210 — — 186 186 190 197 — — — SHC 180 180 163 147 117 — — 186 186 172 156 — — — kW 21.9 22.0 22.1 22.4 23.0 — — 22.1 22.1 22.2 22.5 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F216 (18 Tons) (cont)
Evaporator Air Quantity — Cfm
Temp (F) Air Entering
9000 Evaporator Air — Ewb (F)/BF 54/0.65 58/0.53 62/0.40 67/0.25 72/0.23 76/0.23 80/0.05
75 TC 223 223 228 239 258 275 — SHC 223 223 202 181 144 113 — kW 14.3 14.3 14.4 14.6 15.0 15.4 —
85 TC 216 217 222 231 250 266 — SHC 216 217 194 177 141 110 — kW 15.8 15.9 16.0 16.3 16.7 17.1 —
95 TC 210 210 215 223 241 257 — SHC 210 210 187 174 138 107 — kW 17.6 17.6 17.7 18.0 18.4 18.8 —
105 TC 202 202 207 214 231 — — SHC 202 202 184 170 134 — — kW 19.4 19.4 19.5 19.7 20.2 — —
115 TC 195 195 196 204 221 — — SHC 195 195 192 166 131 — — kW 21.3 21.3 21.4 21.7 22.2 — —
117 TC 193 193 194 202 219 — — SHC 193 193 192 166 130 — — kW 21.7 21.7 21.7 22.0 22.6 — —
120 TC 191 191 191 199 — — — SHC 191 191 191 164 — — — kW 22.3 22.3 22.3 22.6 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4.5 x cfm
Condenser · (Edb)

Evaporator Air Quantity — Cfm 6,000 7,000 Evaporator Air — Ewb (F)/BF 54/0.48 58/0.31 62/0.21 67/0.19 72/0.17 76/0.22 80/0.05 54/0.54 58/0.37 62/0.25 67/0.21 72/0.19 76/0.21 80/0.04
Temp (F) Air Entering
75 TC 217 222 232 252 274 294 316 227 231 238 254 281 297 322 SHC 217 199 189 163 136 112 90 227 217 202 172 143 115 91 kW 15.1 15.2 15.4 15.8 16.2 16.6 17.0 15.3 15.4 15.5 15.9 16.4 16.5 17.2
85 TC 212 217 226 244 266 285 306 222 225 231 250 272 291 312 SHC 212 194 185 159 133 109 87 222 211 198 170 140 113 88 kW 16.9 17.2 17.3 17.6 18.0 18.4 18.8 17.1 17.3 17.3 17.7 18.2 18.6 19.0
95 TC 206 208 217 236 257 276 295 215 216 223 241 262 281 301 SHC 206 197 181 156 129 106 84 215 213 194 166 136 110 84 kW 18.9 18.8 19.0 19.5 20.0 20.4 20.8 19.0 19.0 19.2 19.6 20.1 20.5 21.0
105 TC 199 202 209 227 247 265 285 208 209 215 232 252 270 — SHC 199 190 177 152 126 103 80 208 209 189 163 132 107 — kW 20.8 20.9 21.1 21.6 22.0 22.5 22.9 21.0 21.0 21.2 21.7 22.2 22.6 —
115 TC 192 194 200 218 237 254 — 202 202 207 222 242 259 — SHC 192 192 173 149 122 99 — 202 202 183 159 129 103 — kW 23.0 22.9 23.3 23.8 24.3 24.8 — 23.2 23.2 23.5 23.9 24.5 24.9 —
117 TC 191 191 199 216 235 252 — 200 200 205 220 240 257 — SHC 191 191 172 148 121 99 — 200 200 182 158 128 102 — kW 23.5 23.5 23.7 24.2 24.8 25.2 — 23.8 23.8 23.9 24.4 24.9 25.3 —
120 TC 189 189 196 213 232 249 — 197 198 203 217 236 — — SHC 189 189 170 147 120 98 — 197 198 181 156 127 — — kW 24.2 24.2 24.4 25.0 25.5 25.9 — 24.5 24.5 24.6 25.1 25.6 — —
579F240 (20 Tons) (cont)
Evaporator Air Quantity — Cfm 8,000 9,000 Evaporator Air — Ewb (F)/BF 54/0.58 58/0.43 62/0.30 67/0.23 72/0.21 76/0.22 80/0.04 54/0.62 58/0.48 62/0.35 67/0.24 72/0.23 76/0.23 80/0.04
Temp (F) Air Entering
75 TC 236 238 241 259 286 302 328 244 244 250 267 290 307 — SHC 236 232 211 181 149 119 91 244 244 222 192 155 123 — kW 15.5 15.5 15.6 15.9 16.5 16.6 17.3 15.7 15.7 15.8 16.1 16.6 16.7 —
85 TC 231 230 237 254 276 296 — 237 238 243 258 281 300 — SHC 231 230 209 179 146 117 — 237 238 216 189 152 121 — kW 17.5 17.3 17.4 17.8 18.3 18.7 — 17.5 17.6 17.6 18.0 18.4 18.8 —
95 TC 223 223 229 245 267 285 — 231 230 235 249 270 289 — SHC 223 223 203 176 142 114 — 231 230 209 185 148 117 — kW 19.2 19.2 19.3 19.8 20.2 20.6 — 19.5 19.4 19.5 19.8 20.3 20.8 —
105 TC 216 216 221 236 256 274 — 222 223 228 239 260 278 — SHC 216 216 197 172 139 110 — 222 223 202 181 145 114 — kW 21.3 21.3 21.4 21.8 22.3 22.7 — 21.4 21.5 21.6 21.9 22.4 22.8 —
115 TC 208 209 213 226 246 263 — 214 214 220 229 249 266 — SHC 208 209 190 168 135 107 — 214 214 193 177 141 110 — kW 23.5 23.5 23.7 24.0 24.6 25.0 — 23.7 23.7 23.9 24.2 24.7 25.1 —
117 TC 207 207 212 224 243 260 — 213 213 219 227 246 263 — SHC 207 207 188 167 134 106 — 213 213 191 176 140 109 — kW 24.0 24.0 24.1 24.5 25.0 25.5 — 24.2 24.2 24.2 24.6 25.1 25.6 —
120 TC 204 205 209 221 240 — — 210 210 215 224 243 — — SHC 204 205 185 166 133 — — 210 210 193 175 139 — — kW 24.7 24.7 24.8 25.2 25.7 — — 24.9 24.9 25.0 25.3 25.8 — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F240 (20 Tons) (cont)
Evaporator Air Quantity — Cfm
Temp (F) Air Entering
10,000 Evaporator Air — Ewb (F)/BF 54/0.65 58/0.52 62/0.40 67/0.26 72/0.24 76/0.24 80/0.04
75 TC 250 250 256 267 294 314 — SHC 250 250 227 200 161 127 — kW 15.8 15.8 15.9 16.1 16.7 17.1 —
85 TC 243 244 249 262 284 303 — SHC 243 244 220 198 158 124 — kW 17.6 17.8 17.7 18.0 18.5 18.9 —
95 TC 236 236 241 252 274 292 — SHC 236 236 212 194 154 121 — kW 19.5 19.5 19.7 19.9 20.4 20.9 —
105 TC 228 228 234 242 263 281 — SHC 228 228 203 190 151 117 — kW 21.6 21.6 21.8 22.0 22.5 22.9 —
115 TC 220 220 223 232 251 268 — SHC 220 220 207 186 147 113 — kW 23.9 23.9 23.9 24.2 24.7 25.2 —
117 TC 218 218 221 230 249 266 — SHC 218 218 205 185 146 112 — kW 24.3 24.3 24.4 24.7 25.2 25.6 —
120 TC 215 215 218 226 245 — — SHC 215 215 203 183 145 — — kW 25.1 25.1 25.1 25.4 25.9 — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4.5 x cfm
Condenser · (Edb)

Evaporator Air Quantity — Cfm 7,000 8,000 Evaporator Air — Ewb (F)/BF 54/0.44 58/0.26 62/0.13 67/0.12 72/0.12 76/0.19 80/0.01 54/0.49 58/0.32 62/0.15 67/0.14 72/0.13 76/0.17 80/0.00
Temp (F) Air Entering
75 TC — 256 270 298 325 349 370 266 268 280 304 324 352 379 SHC — 243 229 198 164 133 106 266 251 246 209 168 137 107 kW — 19.3 20.0 20.3 21.0 21.6 22.2 19.5 19.6 19.9 20.5 20.9 21.8 22.4
85 TC 249 251 265 289 315 340 361 260 262 272 294 321 344 367 SHC 249 238 226 194 160 130 103 260 254 243 205 167 135 104 kW 21.3 21.3 21.7 22.4 23.1 24.3 24.4 21.6 21.6 22.0 22.5 23.3 23.9 24.6
95 TC 244 245 257 279 306 328 349 254 256 262 284 310 332 355 SHC 244 230 223 190 156 127 99 254 249 238 201 163 131 100 kW 23.6 23.5 24.1 24.6 25.6 26.2 26.7 23.8 23.9 24.1 24.8 25.5 26.2 26.9
105 TC 237 238 247 269 293 315 336 246 247 253 274 298 319 343 SHC 237 233 218 185 152 122 95 246 245 233 197 159 127 96 kW 25.9 25.9 26.3 27.0 27.8 28.5 29.2 26.3 26.3 26.5 27.2 28.0 28.7 29.5
115 TC 229 231 237 258 283 302 322 238 239 243 264 286 306 328 SHC 229 225 213 181 148 119 91 238 239 228 193 155 123 91 kW 28.6 28.6 28.9 29.6 30.3 31.2 31.9 28.9 28.9 29.1 29.7 30.6 31.4 32.1
117 TC 228 230 236 256 279 299 — 237 237 241 260 283 304 — SHC 228 225 212 180 147 118 — 237 237 227 192 154 122 — kW 29.1 29.1 29.4 30.2 31.0 31.7 — 29.4 29.5 29.6 30.4 31.2 31.9 —
120 TC 226 226 232 252 276 — — 234 234 238 257 280 — — SHC 226 225 211 179 145 — — 234 234 225 190 152 — — kW 30.0 30.0 30.3 30.9 31.8 — — 30.3 30.3 30.5 31.1 32.0 — —
579F300 (25 Tons) (cont)
Evaporator Air Quantity — Cfm 9,000 10,000 Evaporator Air — Ewb (F)/BF 54/0.53 58/0.37 62/0.18 67/0.15 72/0.14 76/0.17 80/0.00 54/0.57 58/0.41 62/0.23 67/0.16 72/0.15 76/0.17 80/0.00
Temp (F) Air Entering
75 TC 277 276 286 310 336 361 385 286 284 291 314 341 365 390 SHC 277 269 261 221 178 142 108 286 284 274 232 186 147 108 kW 19.8 19.5 20.0 20.6 21.3 22.0 22.6 20.0 20.2 20.2 20.8 21.5 22.1 22.7
85 TC 271 272 277 300 326 349 373 278 278 282 304 330 354 378 SHC 271 264 257 217 175 139 104 278 278 269 228 182 143 105 kW 22.2 21.9 22.1 22.7 23.4 24.1 24.8 22.1 22.1 22.2 22.8 23.6 24.2 24.9
95 TC 263 263 268 289 316 337 360 270 270 273 293 319 341 364 SHC 263 263 251 213 171 135 100 270 270 262 223 177 139 101 kW 24.1 24.1 24.3 24.9 25.9 26.4 27.1 24.4 24.4 24.4 25.1 25.8 26.5 27.2
105 TC 255 255 258 278 302 326 346 261 262 264 282 306 328 352 SHC 255 255 246 208 166 132 96 261 262 254 219 173 135 97 kW 26.5 26.5 26.6 27.3 28.1 29.0 29.6 26.8 26.8 26.9 27.5 28.3 29.0 29.8
115 TC 247 246 249 267 290 311 — 253 253 255 270 293 315 — SHC 247 246 239 204 162 127 — 253 253 245 214 168 131 — kW 29.1 29.2 29.3 30.0 30.8 31.5 — 29.3 29.3 29.6 30.1 30.9 31.7 —
117 TC 244 244 247 265 288 308 — 251 251 253 268 291 — — SHC 244 244 237 203 161 126 — 251 251 243 213 168 — — kW 29.7 29.7 29.8 30.4 31.3 32.1 — 30.0 30.0 30.0 30.6 31.4 — —
120 TC 241 242 244 261 — — — 248 248 250 264 — — — SHC 241 242 235 201 — — — 248 248 239 212 — — — kW 30.6 30.6 30.7 31.3 — — — 30.8 30.8 31.0 31.5 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F300 (25 Tons) (cont)
Evaporator Air Quantity — Cfm
Temp (F) Air Entering
11,250 Evaporator Air — Ewb (F)/BF 54/0.61 58/0.47 62/0.30 67/0.16 72/0.17 76/0.17 80/0.00
75 TC 295 295 298 319 342 367 392 SHC 295 295 285 245 193 151 108 kW 20.3 20.3 20.4 20.9 21.2 21.5 21.9
85 TC 288 287 289 310 334 359 384 SHC 288 287 278 241 190 148 106 kW 22.5 22.4 22.4 23.1 23.7 24.4 25.3
95 TC 278 278 280 318 323 346 — SHC 278 278 269 150 186 144 — kW 24.6 24.6 24.7 30.0 26.0 26.7 —
105 TC 269 269 272 285 310 332 — SHC 269 269 259 232 182 140 — kW 27.0 27.0 27.1 27.6 28.4 29.1 —
115 TC 259 260 262 273 297 318 — SHC 259 260 247 227 177 136 — kW 29.7 29.6 29.8 30.2 31.1 31.8 —
117 TC 257 257 261 271 294 — — SHC 257 257 245 226 176 — — kW 30.3 30.3 30.3 30.7 31.6 — —
120 TC 254 254 257 267 — — — SHC 254 254 242 224 — — — kW 31.1 31.1 31.3 31.6 — — —
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor 0.05 1.04 2.07 3.11 4.14 5.18
(BF)
NOTES:
0.10 0.98 1.96 2.94 3.92 4.91 0.20 0.87 1.74 2.62 3.49 4.36 0.30 0.76 1.53 2.29 3.05 3.82 0.40 0.65 1.31 1.96 2.62 3.27 0.50 0.55 1.09 1.64 2.18 2.73 0.60 0.44 0.87 1.31 1.74 2.18 0.70 0.33 0.65 0.98 1.31 1.64
tldb = tedb – sensible capacity (Btuh)
Use formula shown below.
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4.5 x cfm
Condenser · (Edb)

579F180230 (15 TONS) *
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4500 809 1.53 1317 906 1.74 1502 994 1.96 1690 1078 2.18 1882 1156 2.41 2077 1230 2.64 2275 4800 850 1.76 1516 942 1.98 1706 1027 2.20 1899 1107 2.43 2094 1183 2.66 2293 1255 2.89 2495 5100 892 2.01 1733 979 2.24 1928 1061 2.46 2125 1138 2.70 2325 1211 2.93 2528 1281 3.17 2733 5400 934 2.28 1970 1017 2.52 2169 1096 2.75 2371 1170 2.99 2575 1241 3.22 2781 1309 3.47 2990 5700 976 2.58 2225 1056 2.82 2429 1132 3.06 2635 1204 3.30 2843 1272 3.54 3053 1338 3.79 3266 6000 1019 2.90 2500 1096 3.14 2709 1168 3.38 2919 1238 3.63 3131 1304 3.88 3345 1368 4.13 3562 6300 1063 3.24 2795 1136 3.49 3008 1206 3.74 3223 1273 3.99 3439 1337 4.24 3657 — — — 6600 1106 3.61 3111 1177 3.86 3329 1244 4.11 3547 1309 4.37 3767 — 6900 1150 4.00 3448 1218 4.26 3670 — 7200 — 7500 —
579F180230 (15 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4500 1301 2.87 2477 1369 3.11 2683 1434 3.35 2891 1497 3.47 2997 1497 3.60 3103 4800 1324 3.13 2700 1390 3.37 2909 1454 3.62 3120 1515 3.74 3226 1515 3.87 3334 5100 1349 3.41 2942 1413 3.66 3153 1475 3.90 3367 1535 4.03 3475 1535 4.16 3584 5400 1374 3.71 3202 1437 3.96 3416 1498 4.21 3633 — 5700 1402 4.04 3481 1463 4.29 3699 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 194 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 4.25 (208/230 v and 460 v) or 3.45 (575 v) and the maximum continuous watts are 3775 (208/230 v and 460 v) or 3065 (575 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 891 to 1179 rpm (208/230 v and 460 v) or 1159 to 1429 (575 v). Alternate high-static drive range is 1227 to 1550 (208/230 v and 460 v only). Other rpms require a field-supplied drive.
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 755 2.27 1908 831 2.58 2171 901 2.91 2443 968 3.24 2723 1031 3.58 3009 1091 3.93 3302 6,000 810 2.72 2287 881 3.04 2556 947 3.37 2833 1010 3.71 3116 1070 4.05 3406 1127 4.40 3702 6,500 866 3.22 2710 932 3.55 2985 994 3.88 3266 1054 4.23 3554 1111 4.57 3847 1166 4.93 4146 7,000 923 3.78 3177 985 4.11 3458 1044 4.45 3744 1100 4.80 4036 1155 5.15 4333 1207 5.51 4635 7,500 980 4.39 3690 1038 4.73 3976 1094 5.07 4267 1148 5.43 4564 1200 5.78 4864 1250 6.15 5170 8,000 1038 5.06 4251 1093 5.40 4542 1146 5.75 4838 1197 6.11 5138 1246 6.47 5443 1294 6.84 5752 8,500 1096 5.78 4859 1148 6.13 5156 1198 6.49 5456 1247 6.85 5761 1294 7.22 6070 1340 7.59 6382 9,000 1154 6.56 5517 1204 6.92 5818 1251 7.28 6123 1298 7.65 6432 1343 8.02 6745 1388 8.40 7062 9,500 1213 7.40 6224 1260 7.77 6531 1306 8.13 6840 1350 8.51 7154 1394 8.88 7471 1436 9.26 7791 10,000 1272 8.30 6983 1317 8.67 7294 1360 9.05 7608 1403 9.43 7926 1445 9.81 8247 1486 10.19 8570
579F216275 AND 240275 (18 AND 20 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 1149 4.28 3602 1204 4.65 3907 1258 5.02 4217 1284 5.20 4375 1309 5.39 4533 6,000 1183 4.76 4003 1236 5.13 4310 1288 5.50 4622 1313 5.68 4780 1337 5.87 4939 6,500 1219 5.29 4450 1270 5.66 4759 1320 6.03 5073 1344 6.22 5232 1368 6.41 5391 7,000 1258 5.88 4942 1307 6.25 5253 1355 6.62 5569 1378 6.81 5729 1402 7.00 5890 7,500 1299 6.52 5480 1346 6.89 5794 1392 7.27 6113 1415 7.46 6273 1437 7.65 6435 8,000 1341 7.21 6065 1387 7.59 6383 1392 7.97 6704 1453 8.16 6866 1475 8.36 7300 8,500 1385 7.97 6699 1429 8.35 7019 1472 8.73 7343 1493 8.93 7506 1514 9.12 7670 9,000 1431 8.78 7382 1473 9.15 7705 1515 9.55 8032 1535 9.75 8196 — — — 9,500 1478 9.65 8114 1519 10.04 8441 — 10,000 —
Refer to page 194 for general Fan Performance Data notes. NOTE: Maximum continuous bhp for the 216 size is 5.90. Maximum continuous bhp for the 240 size is 8.70 (208/230 and 575 v) or 9.50 (460 v). The maximum continuous watts for the 216 size is 5180. The maximum continuous watts for the 240 size is 7915 (208/230 and 575 v) or 8640 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operat- ing cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range for the 216 size is 910 to 1095 rpm. Standard low-medium static drive range for the 240 size is 1002 to 1225 rpm. Alternate high-static drive range for the 216 size is 1069 to 1287. Alternate high- static drive range for the 240 size is 1193 to 1458 rpm. Other rpms require a field- supplied drive.

579F300275 (25 TONS) *
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 941 3.35 2,769 1002 3.80 3,140 1061 4.27 3528 1117 4.76 3,934 1171 5.27 4,356 1224 5.80 4,794 7,500 999 4.05 3,348 1057 4.53 3,742 1112 5.02 4152 1166 5.54 4,579 1218 6.07 5,216 1268 6.63 5,478 8,000 1058 4.85 4,007 1113 5.35 4,424 1165 5.87 4856 1216 6.41 5,304 1266 6.97 5,766 1314 7.55 6,243 8,500 1117 5.74 4,750 1169 6.28 5,190 1219 6.83 5645 1268 7.40 6,114 1315 7.98 6,597 1361 8.58 7,094 9,000 1177 6.75 5,583 1226 7.31 6,047 1274 7.89 6524 1320 8.48 7,015 1365 9.09 7,520 1410 9.72 8,037 9,500 1237 7.98 6,511 1284 8.46 6,999 1329 9.07 7499 1374 9.69 8,012 1417 10.33 8,538 1459 10.98 9,076 10,000 1297 9.12 7,450 1342 9.74 8,051 1385 10.37 8574 1428 11.02 9,110 1469 11.68 9,657 1510 12.36 10,217 10,500 1358 10.49 8,674 1400 11.14 9,209 1442 11.80 9755 1483 12.47 10,314 1523 13.16 10,883 — — — 11,000 1418 12.00 9,919 1459 12.67 10,478 — 11,250 1449 12.80 10,585 —
579F300275 (25 TONS) * (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 1274 6.35 5248 1323 6.92 5,718 1371 5.54 6204 7,500 1316 7.20 6960 1364 7.79 6,437 1410 6.41 6939 8,000 1360 8.14 6734 1406 8.76 7,239 1450 7.40 7759 8,500 1406 9.20 7605 1449 9.83 8,129 1492 8.48 8666 9,000 1453 10.36 8568 1495 11.02 9,111 1536 9.69 9667 9,500 1501 11.64 9627 1541 12.32 10,190 — — — 10,000 — 10,500 — 11,000 — 11,250 —
Refer to page 194 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4500 819 1.55 1335 914 1.76 1518 1001 1.98 1705 1083 2.20 1894 1160 2.42 2088 1234 2.65 2284 4800 861 1.78 1538 951 2.00 1726 1035 2.22 1916 1113 2.45 2110 1188 2.68 2307 1259 2.91 2507 5100 904 2.04 1759 989 2.26 1952 1069 2.49 2147 1145 2.72 2345 1218 2.95 2545 1287 3.17 2749 5400 947 2.32 1999 1300 2.55 2197 1105 2.78 2396 1179 3.01 2598 1248 3.25 2802 1315 3.49 3009 5700 990 2.62 2259 1068 2.85 2461 1142 3.09 2665 1213 3.33 2871 1280 3.57 3079 1345 3.81 3289 6000 1034 2.94 2539 1109 3.18 2745 1180 3.42 2953 1248 3.67 3163 1313 3.91 3375 1376 4.16 3589 6300 1078 3.29 2840 1150 3.54 3050 1218 3.78 3262 1284 4.03 3476 1348 4.28 3692 — — — 6600 1123 3.67 3161 1192 3.91 3376 1258 4.16 3592 — 6900 1167 4.06 3504 1234 4.32 3723 — 7200 — 7500 —
579F180300 (15 TONS) * (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4500 1304 2.88 2484 1371 3.12 2688 1435 3.36 2895 1467 3.48 2999 1497 3.60 3104 4800 1327 3.14 2711 1393 3.38 2917 1456 3.62 3126 1486 3.75 3232 1517 3.87 3338 5100 1353 3.43 2955 1417 3.67 3165 1478 3.92 3377 1508 4.04 3484 1537 4.16 3592 5400 1380 3.73 3219 1442 3.98 3432 1502 4.23 3646 1531 4.35 3755 — — — 5700 1408 4.06 3503 1468 4.31 3718 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 194 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 4.25 (208/230 v and 460 v) or 3.45 (575 v) and the maximum continuous watts are 3775 (208/230 v and 460 v) or 3065 (575 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 891 to 1179 rpm (208/230 v and 460 v) or 1159 to 1429 (575 v). Alternate high-static drive range is 1227 to 1550 (208/230 v and 460 v only). Other rpms require a field-supplied drive.

579F216360 and 240360 (18 AND 20 TONS) *
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 795 2.43 2043 866 2.74 2306 934 3.07 2578 998 3.40 2856 1059 3.74 3142 1117 4.08 3434 6,000 854 2.92 2452 921 3.24 2722 984 3.57 3998 1044 3.90 3281 1102 4.25 3570 1158 4.60 3865 6,500 914 3.46 2909 977 3.79 3184 1036 4.12 3465 1093 4.46 3752 1148 4.81 4045 1201 5.16 4343 7,000 975 4.06 3414 1034 4.39 3695 1090 4.73 3981 1144 5.08 4272 1196 5.43 4569 1246 5.79 4870 7,500 1037 4.72 3969 1092 5.06 4255 1145 5.41 4546 1196 5.76 4842 1256 6.12 5142 1294 6.48 5447 8,000 1099 5.44 4575 1150 5.79 4866 1201 6.14 5162 1249 6.50 5462 1297 6.86 5766 1343 7.22 6075 8,500 1161 6.22 5232 1210 6.57 5529 1258 6.93 5829 1304 7.29 6134 1349 7.66 6443 1393 8.03 6755 9,000 1223 7.07 5943 1270 7.43 6245 1315 7.79 6550 1360 8.16 6869 1403 8.53 7171 1445 8.90 7487 9,500 1286 7.98 6708 1331 8.34 7014 1374 8.71 7324 1416 9.08 7638 1457 9.46 7954 1498 9.84 8274 10,000 1349 8.95 7528 1392 9.32 7839 1433 9.70 8154 1473 10.07 8471 —
579F216360 and 240360 (18 AND 20 TONS) * (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 1173 4.44 3732 1227 4.80 4036 1279 5.17 4345 1304 5.35 4502 1329 5.54 4629 6,000 1211 4.95 4165 1263 5.32 4471 1313 5.69 4782 1337 5.87 4939 1361 6.06 5097 6,500 1252 5.53 4646 1302 5.89 4954 1350 6.26 5267 1373 6.56 5425 1396 6.64 5584 7,000 1295 6.16 5176 1343 6.52 5487 1389 6.90 5802 1412 7.09 5961 1434 7.28 6121 7,500 1340 6.85 5756 1386 7.22 6070 1431 7.60 6387 1452 7.79 6547 1474 7.98 6709 8,000 1388 7.60 6388 1431 7.97 6704 1474 8.35 7240 1495 8.54 7186 1516 8.74 7348 8,500 1436 8.41 7071 1478 8.79 7390 1520 9.17 7713 1540 9.37 7876 — — — 9,000 1486 9.28 7807 1527 9.67 8130 — 9,500 1538 10.22 8597 — 10,000 —
Refer to this page for general Fan Performance Data notes. NOTE: Maximum continuous bhp for the 216 size is 5.90. Maximum continuous bhp for the 240 size is 8.70 (208/230 and 575 v) or 9.50 (460 v). The maximum continuous watts for the 216 size is 5180. The maximum continuous watts for the 240 size is 7915 (208/230 and 575 v) or 8640 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operat- ing cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range for the 216 size is 910 to 1095 rpm. Standard low-medium static drive range for the 240 size is 1002 to 1225 rpm. Alternate high-static drive range for the 216 size is 1069 to 1287. Alternate high- static drive range for the 240 size is 1193 to 1458 rpm. Other rpms require a field- supplied drive.
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 992 4.05 3,348 1051 4.44 3,668 1106 4.83 3995 1160 5.24 4331 1212 5.65 4675 1262 6.08 5026 7,500 1055 4.77 3,947 1110 5.17 4,277 1162 5.58 4615 1214 6.00 4960 1263 6.43 5312 1311 6.86 5672 8,000 1118 5.58 4,610 1170 5.99 4,950 1220 6.41 5298 1268 6.84 5653 1315 7.27 6014 1361 7.72 6382 8,500 1182 6.46 5,339 1231 6.88 5,690 1278 7.31 6047 1324 7.75 6411 1369 8.20 6782 1413 8.66 7158 9,000 1246 7.42 6,136 1292 7.86 6,498 1337 8.30 6865 1381 8.75 7239 1424 9.21 7618 1466 9.68 8003 9,500 1310 8.47 7,005 1354 8.92 7,377 1397 9.38 7754 1439 9.84 8137 1480 10.31 8525 1520 10.79 8918 10,000 1374 9.61 7,947 1416 10.07 8,329 1457 10.54 8715 1497 11.02 9107 1537 11.50 9504 — — — 10,500 1439 10.84 8,964 1479 11.32 9,356 1518 11.79 9752 — 11,000 1503 12.17 10,059 1542 12.65 10,460 — 11,250 1536 12.86 10,636 —
579F300360 (25 TONS) * (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 1311 6.51 5385 1359 6.96 5751 1405 6.00 6124 7,500 1358 7.30 6039 1403 7.76 6412 1448 6.84 6792 8,000 1406 8.17 6767 1560 8.63 7137 1492 7.75 7524 8,500 1456 9.12 7541 1498 9.59 7929 1539 8.75 8323 9,000 1507 10.15 8393 1548 10.63 8790 — — — 9,500 — 10,000 — 10,500 — 11,000 — 11,250 —
Refer to this page for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.


ALTITUDE COMPENSATION* —
ALTITUDE DERATING FACTOR*
ELEVATION (ft) MAXIMUM HEATING VALUE
NATURAL GAS ORIFICE SIZE† Low Heat High Heat 0-3,000 30 29 3,000- 7,000 31 30 7,000- 9,000 32 31 9,000-10,000 33 31 above 10,000 35 32
(Btu/ft3) 0-2,000 1,100 2,001-3,000 1,050 3,001-4,000 1,000 4,001-5,000 950 5,001-6,000 900
(ft)
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For eleva- tions above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code. IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, then changing spuds may not be required.
*Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant distributor.
a50-4028

(LP Gas Units)
ELEVATION
LIQUID PROPANE ORIFICE SIZE
Low Heat and High Heat 0-2,000 36 2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42 10,000 43
OUTDOOR SOUND POWER
UNIT 579F
SOUND RATING
A-WEIGHTED
OCTAVE BANDS
(60 Hz)
(dB)
63 125 250 500 1000 2000 4000 8000
180 88 dB 87.8 90.8 88.7 86.4 84.3 83.5 78.4 75.6 66.8 216 88 dB 87.8 90.8 88.7 86.4 84.3 83.5 78.4 75.6 66.8 240 95 dB 94.1 98.7 92.3 93.8 90.9 89.6 85.9 80.3 74.3 300 95 dB 94.1 98.7 92.3 93.8 90.9 89.6 85.9 80.3 74.3
COMPONENT CFM 4500 5000 5400 6000 7200 7500 9000 10,000 11,250 EconoMi$er IV and EconoMi$er2 0.040 0.050 0.060 0.070 0.090 0.100 0.110 0.120 0.140
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
UNIT 579F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
180† (208/230 and 460-v) †† †† 1179 1150 1121 1093 1064 1035 1006 978 949 920 891 180** †† †† 1559 1522 1488 1455 1422 1389 1356 1323 1289 1256 1227 180† (575-v) †† †† 1429 1403 1376 1349 1323 1296 1269 1242 1215 1188 1159 216† †† †† 1095 1077 1058 1040 1021 1002 984 965 947 928 910 216** †† †† 1287 1265 1243 1222 1200 1178 1156 1134 1112 1091 1069 240† †† †† 1225 1209 1187 1165 1143 1120 1098 1076 1053 1031 1002 240** †† †† 1458 1434 1407 1381 1354 1328 1301 1275 1248 1222 1193 300† †† †† 1283 1269 1247 1225 1203 1182 1160 1138 1116 1095 1066 300** †† †† — — 1551 1524 1497 1470 1443 1415 1388 1361 1332
*Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package. ††Due to belt and pulley size, pulley cannot be set to this number of turns open.

MAXIMUM ACCEPTABLE CONTINUOUS
MAXIMUM ACCEPTABLE CONTINUOUS
MAXIMUM ACCEPTABLE
UNIT 579F UNIT VOLTAGE
MAXIMUM AMP DRAW
OPERATING
BHP*
BkW*
WATTS
180 208/230 4.25 3.17 3,775 10.5 460 4.25 3.17 3,775 4.8 575 3.45 2.59 3,065 3.9
216 208/230 5.90 4.40 5,180 15.8 460 7.9 575 6.0
240 208/230 8.70 6.49 7,915 22.0 460 9.50 7.08 8,640 13.0 575 8.70 6.49 7,915 10.0
300 208/230 10.20 7.61 9,510 28.0 460 11.80 8.80 11,000 14.6 575 10.20 7.61 9,510 13.0
BHP — Brake Horsepower BkW — Brake Kilowatts
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range of the motors can be utilized with confidence. Using fan motors up to the horsepower (brake kilowatt) ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
UNIT 579F MOTOR EFFICIENCY
(%) 180 (3.0 Hp) 81.7 180 (3.7 Hp) 85.8 216 (5 Hp) 87.5 240 (7.5 Hp) 88.5 300 (10 Hp) 89.5

NOMINAL VOLTAGE (3 Ph, 60 Hz)
POWER SUPPLY No. 1 No. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
COMBUSTION
UNIT 579F
RANGE
FAN MOTOR
208/230 187 253 28.8 195 28.8 195 3 0.5 1.7 3.7 10.5/11.0 — — 0.57 81/81 100/100 4.6 18.8 0.57 85/86 110/110
460 414 508 14.7 95 14.7 95 3 0.5 0.8 3.7 4.8 — — 0.30 40 50 2.3 6.0 0.30 43 50
575 518 633 10.8 80 10.8 80 3 0.5 0.8 3.0 3.9 — — 0.57 30 40 2.1 4.8 0.57 32 40
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8 — — 0.57 87/87 110/110 4.6 18.8 0.57 92/92 110/110
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9 — — 0.30 44 50 2.3 6.0 0.30 47 60
575 518 633 12.1 80 10.8 80 3 0.5 0.8 5.0 6.0 — — 0.57 34 40 2.1 4.8 0.57 36 40
208/230 187 253 37.8 239 30.1 225 2 1 6.6 7.5 25.0/25.0 — — 0.57 116/116 150/150 4.6 18.8 0.57 120/120 150/150
460 414 508 17.2 125 15.5 114 2 1 3.3 7.5 13.0 — — 0.30 57 70 2.3 6.0 0.30 59 70
575 518 633 12.4 80 12.1 80 2 1 3.4 7.5 10.0 — — 0.57 44 50 2.1 4.8 0.57 46 50
208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0 — — 0.57 130/130 150/150 4.6 18.8 0.57 135/135 175/175
460 414 508 21.8 158 17.2 125 2 1 3.3 10.0 14.6 — — 0.30 66 80 2.3 6.0 0.30 68 80
575 518 633 17.3 125 12.4 80 2 1 3.4 10.0 13.0 — — 0.57 54 70 2.1 4.8 0.57 56 70
EXAMPLE: Supply voltage is 460-3-60.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455
= 1371 3 = 457
*Fuse or HACR circuit breaker.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance.

% Voltage Imbalance = 100 x 7 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.
= 100 x max voltage deviation from average voltage

(579F240, 208/230 V Shown)
a48-7929

(579F240, 208/230 V Shown) (cont)
IFCB — Indoor-Fan Circuit Breaker IFM — Indoor-Fan Motor IGC — Integrated Gas Unit Controller L — Light LED — Light-Emitting Diode LOR — Lockout Relay LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve NEC — National Electrical Code OFC — Outdoor-Fan Contactor OFM — Outdoor-Fan Motor PL — Plug Assembly PRI — Primary RS — Rollout Switch SN — Sensor SR — Solenoid Relay SW — Switch TB — Terminal Block TC — Thermostat Cooling TH — Thermostat Heating
AHA — Adjustable Heat Anticipator BKR W/AT — Breaker with Amp Turns C — Contactor, Compressor CB — Circuit Breaker CC — Cooling Compensator CLO — Compressor Lockout COMP — Compressor Motor CR — Control Relay CT — Control Transformer DM — Damper Motor DU — Dummy Terminal EQUIP — Equipment FPT — Freeze Protection Thermostat FU — Fuse GND — Ground HPS — High-Pressure Switch HS — Hall Effect Sensor HV — High Voltage I — Ignitor IDM — Induced-Draft Motor IFC — Indoor-Fan Contactor
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only; not to represent wiring.
1. Compressor and fan motors thermally protected; 3-phase motors protected against primary single-phasing conditions. 2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 3. Jumpers are omitted when unit is equipped with economizer. 4. IFCB must trip amps is equal to or less than 140% full load amps. 5. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v power supply. If unit is to run on 208-v power supply, TRAN1 must be rewired. Disconnect the BLK wire on TRAN1 and connect wire to 208-v RED wire. Insulate 230-v ORN wire. 6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. 7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line) number signifies a normally open contact.

LEGEND AL —Ambient Limit OA — Outdoor Air ECB —Economizer Control Board OAS — Outdoor Air Sensor IA —Indoor Air RAS — Return Air Sensor IAQ —Indoor Air Quality SAT — Supply Air Temperature
RED
500 OHM RESISTOR
PINK
BLUE NOTE 1
RUN
OAT
BLACK
NOTE 2
50HJ540573 ACTUATOR ASSEMBLY
DIRECT DRIVE
WHITE
ACTUATOR
LEGEND OAT — Outdoor Air Temperature Sensor NOTES:
a48-7877 · a50-8058

a48-6005

(579F180 Shown)

LEGEND NEC — National Electrical Code b48-1258

UNIT 580F 180 210 240 300 NOMINAL CAPACITY (tons) 15 18 20 25 OPERATING WEIGHT
Unit 1800 1850 1900 2270 EconoMi$er IV 80 COMPRESSOR/MANUFACTURER Scroll, Copeland Quantity...Model (Ckt 1, Ckt 2) 1...ZR94KC, 1...ZR72KC 1...ZR108KC, 1...ZR94KC 1...ZR125KC, 1...ZR108KC 1...ZR4140KC, 2...ZR144KC Capacity Stages (%) 60, 40 55, 45 55, 45 60, 40 Number of Refrigerant Circuits 2 Oil (oz) (Ckt 1, Ckt 2) 85, 60 106, 81 106,106 136, 106 REFRIGERANT TYPE R-22 Expansion Device TXV Operating Charge (lb-oz)
Circuit 1* 19-8 19-8 19-11 26-13 Circuit 2 13-8 19-2 13-14 25-10 CONDENSER COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced,
Aluminum Pre-Coated, or Copper Plate Fins Rows...Fins/in. 4...15 4...15 4...15 3...15 (2 coils) Total Face Area (sq ft) 21.7 21.7 21.7 43.4 CONDENSER FAN Propeller Type Nominal Cfm 10,500 10,500 14,200 21,000 Quantity...Diameter (in.) 3...22 3...22 2...30 6...22 Motor Hp...Rpm 1/2...1050 1/2...1050 1...1075 1/2...1050 Watts Input (Total) 1100 1100 3400 2200 EVAPORATOR COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split Rows...Fins/in. 4...15 Total Face Area (sq ft) 17.5 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2...12 x 12 2...12 x 12 2...12 x 12 2...12 x 12 Type Drive Belt Nominal Cfm 6000 7200 8000 10,000 Motor Hp 5 5 7.5 10 Motor Nominal Rpm 1745 1745 1745 1740
Maximum Continuous Bhp 6.13 5.90 8.7 [208/230, 575 v] 9.5 [460 v] 10.2 [208/230, 575 v] 11.8 [460 v] Motor Frame Size 184T 184T 213T 215T Nominal Rpm High/Low — Fan Rpm Range Low-Medium Static 873-1021 910-1095 1002-1151 1066-1283 High Static 1025-1200 1069-1287 1193-1369 1332-1550 Motor Bearing Type Ball Maximum Allowable Rpm 1550 Motor Pulley Pitch Diameter Low-Medium Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9 Min/Max (in.) High Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9 Nominal Motor Shaft Diameter (in.) 11/8 11/8 13/8 13/8 Fan Pulley Pitch Diameter (in.) Low-Medium Static 9.4 9.4 9.4 8.0 High Static 8.0 8.0 7.9 6.4 Nominal Fan Shaft Diameter (in.) 17/16 Belt, Quantity...Type...Length (in.) Low-Medium Static 1...BX...50 1...BX...50 1...BX...53 2...BX...50 High Static 1...BX...48 1...BX...48 1...BX...50 2...BX...47 Pulley Center Line Distance (in.) 13.3-14.8 13.3-14.8 14.6-15.4 14.6-15.4 Speed Change per Full Turn of
Low-Medium Static 37 37 37 36 High Static 44 34 44 45 Movable Pulley Maximum Full Turns
From Closed Position 4 6 6 6 Factory Speed 3.5 Factory Speed Setting (rpm) Low-Medium Static 965 1002 1095 1182 High Static 1134 1178 1303 1470 Fan Shaft Diameter at Pulley (in.) 17/16
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils. †Rollout switch is manual reset. **The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). NOTE: The 580F180-300 units have a low-pressure switch (standard) located on the suction side.

Rollout Switch Cutout Temp (F)† 190 Burner Orifice Diameter (in drill size) Natural Gas 0.1285...30/0.136...29 Thermostat Heat Anticipator Setting (amps)
208/230, 575 v Stage 1 0.98 Stage 2 0.44 460 v Stage 1 0.80 Stage 2 0.44 Gas Input Stage 1 206,000/270,000 Stage 2 275,000/360,000 Efficiency (Steady-State) (%) 81 Temperature Rise Range 15-45/20-50 Manifold Pressure (in. wg) Natural Gas 3.3 Gas Valve Quantity 1 Gas Valve Pressure Range
in. wg 5.5-13.5 psig 0.235-0.487 Field Gas Connection Size (in.-FPT) 3/4 HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto) 320 LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto) 44 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 2...20 x 25 x 1 1...20 x 20 x 1 RETURN-AIR FILTERS Throwaway** Quantity...Size (in.) 4...20 x 20 x 2 4...16 x20 x 2 POWER EXHAUST 1/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils. †Rollout switch is manual reset. **The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). NOTE: The 580F180-300 units have a low-pressure switch (standard) located on the suction side.
BASE UNIT OPERATING WEIGHTS* 180 210 240 300 lb kg lb kg lb kg lb kg 580F 1800 816 1850 839 1900 862 2270 1030
*Base unit weight does not include copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 180 or 210 unit, add 75 lb (34 kg) for domestic crating. For 240 unit, add 135 lb (61 kg). For 300 unit, add 175 lb (79 kg) for domestic crating.
(Weight Adders)
OPTION/ACCESSORY WEIGHTS 180 210 240 300 lb kg lb kg lb kg lb kg Barometric Relief Damper 50 23 50 23 50 23 50 23 Power Exhaust 85 39 85 39 85 39 85 39 EconoMi$er IV 90 41 90 41 90 41 90 41 Cu Condenser Coil 150 68 150 68 150 68 150 68 Cu Condenser and Evaporator Coils 280 127 280 127 280 127 280 127 Roof Curb (14-in. curb) 200 91 200 91 200 91 200 91 Horizontal Adapter Curb (Pre-Assembled) 250 113 250 113 250 113 250 113 Horizontal Adapter Curb (Field-Assembled) 348 156 343 156 343 156 343 156 Hail Guard 60 27 60 27 60 27 60 27
Cu — Copper

$ · a48-8203

a48-8204

$ · a48-8205

CRRFCURB011A00 2′- 0″ (610) Standard Curb for Units Requiring High Installation
CRRFCURB012A00 2′- 0″ (610) Side Supply and Return Curb for High Installation
CRRFCURB010A00 1′−2″ (305) Standard Curb 14″ High
a48-6314

a48-7456

FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
ACCESSORY PACKAGE NO.
CRRFCURB013A00 1 ′ -11 ″ (584)
Horizontal Supply/Return Adapter Installation (580F180-240)
2'-2 1/16" 1'-6 5/16"
For horizontal return applications: The power exhaust relief must be installed in the return air duct.

LEGEND K.O. — Knockout
Factory-Installed Non-Fused Disconnect (180-300)
a48-4184 · a48-4185

IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity 230,000 Btuh Sensible Heat Capacity (SHC) 170,000 Btuh Required Heating Capacity 215,000 Btuh Condenser Entering Air Temp 95 F (Summer) Evaporator Entering Air Temp 80 F edb,
MENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 191 find: External static pressure 0.60 in. wg EconoMi$er IV static pressure 0.10 in. wg Total static pressure 0.70 in. wg Enter the Fan Performance table 580F240360 at 8,000 cfm and 0.70 in. wg external static pressure. By interpolation, find that the rpm is 1243 and the watts are 5368. V DETERMINE NET COOLING CAPACITY.
67 F ewb Evaporator Air Quantity 8,000 cfm External Static Pressure 0.6 in. wg Electrical Characteristics (V-Ph-Hz) 460-3-60 Vertical discharge unit with optional EconoMi$er IV required. edb — Entering dry-bulb ewb — Entering wet-bulb II SELECT UNIT BASED ON REQUIRED COOLING
Cooling capacities are gross capacities and do not include indoor (evaporator) fan motor (IFM) heat. Use the watts input power to the motor calculated in Section IV above. IFM Watts = 5368 Determine net cooling capacity using the following formula: Net capacity = Gross capacity – IFM heat = 249,000 Btuh – 5368 Watts
CAPACITY. Enter Cooling Capacities table for 580F240 (page 183) at condenser entering temperature 95 F, evaporator air entering at 8,000 cfm and 67 F wb. The unit will provide a total cooling capacity of 249,000 Btuh and a sensible heat- ing capacity (SHC) of 188,000 Btuh. For air entering evap- orator at temperatures other than 80 F edb, calculate SHC correction as required. NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor heat. To calcu- late net capacities, see Step V. III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
(3.412 Btuh ) Watts
= 249,000 Btuh – 18,316 Btuh = 230,684 Btuh Net sensible capacity = 188,000 Btuh – 18,316 Btuh = 169,684 Btuh The calculations show that a 580F240360 unit with the standard motor and standard low-medium static drive is the correct selection for the given conditions.
DESIGN CONDITION REQUIREMENTS. In the ARI Heating Capacities and Efficiencies table note that the 580F240360 will provide an output capacity of 292,000 Btuh, which is adequate for the given application.

580F180 (15 TONS)
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 4,500/0.010 5,250/0.120 6,000/0.140 6,750/0.150 7,500/0.160 Air Entering Evaporator — Ewb (F) 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
75 TC 175.7 191.8 210.9 180.5 196.4 214.9 183.3 201.0 218.9 187.1 203.0 222.9 189.2 205.0 224.9 SHC 145.5 123.0 99.9 156.2 131.5 104.9 167.8 139.1 110.6 175.3 146.3 115.0 183.7 155.8 119.4 kW 14.0 14.4 15.0 14.2 14.6 15.1 14.3 14.7 15.2 14.4 14.9 15.4 14.5 14.9 15.4
85 TC 168.8 185.1 203.0 173.3 189.2 207.0 177.1 192.8 210.9 179.7 196.0 214.9 182.3 198.0 216.9 SHC 141.7 119.8 97.1 151.6 128.6 101.9 162.4 135.9 106.7 171.1 143.1 111.0 179.1 150.2 116.4 kW 15.2 15.6 16.1 15.3 15.8 16.3 15.5 15.9 16.5 15.6 16.1 16.6 15.7 16.1 16.7
95 TC 161.8 177.5 194.4 166.4 181.5 199.0 169.0 184.7 203.0 171.7 187.7 205.0 174.5 189.4 207.0 SHC 138.7 116.8 93.9 147.5 125.2 99.1 157.6 132.7 103.3 167.2 139.9 108.3 173.9 146.5 112.2 kW 16.4 16.9 17.4 16.6 17.0 17.6 16.7 17.2 17.7 16.8 17.3 17.8 16.9 17.4 17.9
105 TC 154.6 169.3 185.3 158.6 173.1 189.2 161.2 175.9 192.0 164.0 178.1 194.6 167.4 179.7 196.2 SHC 133.9 113.6 90.7 143.7 121.4 95.7 154.2 129.0 100.3 161.8 136.1 104.7 167.2 142.7 108.7 kW 17.6 18.2 18.7 17.8 18.3 18.8 17.9 18.5 18.9 18.1 18.5 19.1 18.2 18.6 19.1
115 TC 147.1 160.8 175.5 150.4 164.2 179.1 152.4 166.4 181.9 155.8 168.6 184.3 159.6 169.7 185.7 SHC 130.1 110.2 87.4 139.7 117.8 92.1 149.3 125.4 96.7 155.6 131.9 101.1 159.2 139.1 105.3 kW 19.0 19.5 20.0 19.1 19.7 20.2 19.2 19.8 20.2 19.4 19.9 20.4 19.5 19.9 20.4
118 TC 144.7 158.0 172.5 147.7 161.2 175.9 150.0 163.4 178.3 153.4 165.4 180.7 157.0 166.8 182.1 SHC 129.0 109.1 86.4 138.5 116.6 91.1 147.7 124.2 95.5 153.4 130.7 99.9 156.8 137.7 104.1 kW 19.4 19.9 20.4 19.5 20.0 20.6 19.6 20.2 20.6 19.8 20.2 20.8 19.9 20.4 20.8
120 TC 142.9 156.2 170.5 145.9 159.2 — 148.3 161.2 — 151.8 163.2 — 155.4 164.8 — SHC 128 108 86 138 116 — 146 123 — 152 130 — 155 137 — kW 19.6 20.2 20.6 19.8 20.2 — 19.9 20.4 — 20.0 20.4 — 20.2 20.6 —
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 5,400/0.095 6,000/0.105 7,000/0.120 8,000/0.140 9,000/0.150 Air Entering Evaporator — Ewb (F) 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
75 TC 227 247 269 232 251 274 237 255 277 241 258 280 248 261 283 SHC 200 167 134 215 178 141 231 194 152 241 205 160 248 219 167 kW 15.9 16.5 17.2 16.1 16.7 17.3 16.3 16.8 17.5 16.5 16.9 17.6 16.7 17.0 17.7
85 TC 219 238 259 224 242 265 229 247 269 235 250 272 241 252 273 SHC 197 164 131 210 175 137 225 188 145 234 200 153 240 214 163 kW 17.2 17.8 18.5 17.4 17.9 18.6 17.6 18.1 18.8 17.8 18.3 19.0 18.0 18.3 19.0
95 TC 210 229 248 214 233 253 219 237 258 225 239 261 231 242 263 SHC 192 160 126 205 171 133 218 183 141 225 194 148 231 206 156 kW 18.5 19.2 19.9 18.7 19.3 20.0 19.0 19.5 20.2 19.2 19.6 20.3 19.4 19.7 20.4
105 TC 200 218 237 205 222 241 210 225 245 216 228 249 221 230 250 SHC 186 155 123 199 166 129 210 178 136 216 190 143 221 201 150 kW 19.9 20.5 21.2 20.1 20.7 21.3 20.4 20.8 21.5 20.6 21.0 21.7 20.8 21.0 21.8
115 TC 190 207 225 195 210 228 201 213 232 206 216 235 211 217 236 SHC 181 151 118 193 161 124 201 173 132 206 185 139 211 196 146 kW 21.3 21.9 22.6 21.5 22.1 22.8 21.8 22.2 22.9 22.0 22.4 23.1 22.2 22.4 23.1
120 TC 185 200 218 189 205 221 196 207 225 201 209 227 205 210 229 SHC 179 149 117 189 159 122 196 171 130 201 182 137 205 193 144 kW 22.1 22.6 — 22.3 22.8 — 22.5 22.9 — 22.7 — — 22.9 — —
BF — Bypass Factor kW — Compressor Power Edb — Entering Dry Bulb SHC — Gross Sensible Capacity (1000 Btuh) Ewb — Entering Wet Bulb TC — Gross Cooling Capacity (1000 Btuh)

580F240 (20 TONS)
Air Entering Evaporator — Cfm/BF 6,000/0.04 7,000/0.05 8,000/0.06 9,000/0.07 10,000/0.08 Air Entering Evaporator — Ewb (F) 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
Temp (F) Air Entering
75 TC 237 258 282 242 264 288 247 268 291 252 271 295 258 274 298 SHC 204 171 138 221 184 146 237 199 156 247 210 164 257 221 172 kW 16.7 17.4 18.1 16.9 17.6 18.3 17.1 17.8 18.5 17.3 17.9 18.6 17.5 18.0 18.7
85 TC 229 249 272 234 254 278 239 260 283 245 262 286 250 265 287 SHC 201 167 135 216 180 142 231 193 150 240 203 157 250 217 167 kW 18.1 18.7 19.5 18.3 18.9 19.7 18.5 19.1 19.9 18.7 19.3 20.1 18.8 19.4 20.1
95 TC 220 239 261 225 245 267 230 249 271 235 251 275 241 255 277 SHC 195 163 130 211 176 138 224 188 145 233 199 152 241 210 160 kW 19.4 20.2 20.9 19.7 20.4 21.2 19.9 20.6 21.3 20.1 20.6 21.4 20.3 20.8 21.6
105 TC 209 228 249 216 234 254 220 237 259 225 240 262 230 242 263 SHC 189 159 126 206 171 134 217 183 140 225 195 148 230 205 154 kW 20.9 21.5 22.3 21.2 21.8 22.5 21.4 22.0 22.7 21.6 22.1 22.9 21.8 22.2 23.0
115 TC 200 217 237 205 222 241 211 225 244 216 227 248 221 229 249 SHC 185 154 122 199 166 129 209 178 136 216 189 143 221 200 150 kW 22.5 23.1 23.8 22.7 23.3 24.0 22.9 23.4 24.2 23.2 23.6 24.4 23.4 23.7 24.4
120 TC 194 211 230 199 216 234 205 218 237 210 220 240 214 222 241 SHC 183 152 121 195 164 126 204 175 134 210 186 141 214 196 148 kW 23.2 23.8 24.6 23.5 24.0 — 23.7 24.2 — 23.9 24.4 — 24.1 24.4 —
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 7,000/0.05 8,000/0.06 9,000/0.07 10,000/0.08 11,250/0.09 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
75 TC 256 271 299 327 267 278 305 336 276 283 309 341 285 286 313 344 294 294 316 347 SHC 256 232 196 159 267 249 208 166 276 265 220 173 285 281 232 182 294 294 252 198 kW 18.0 18.3 18.9 19.6 18.3 18.5 19.1 19.8 18.5 18.7 19.2 19.9 18.7 18.8 19.4 20.1 19.0 19.0 19.5 20.2
85 TC 248 262 288 316 259 267 293 322 267 273 298 328 276 276 302 331 284 285 305 336 SHC 248 228 192 154 259 244 204 161 267 259 216 169 276 274 228 175 284 284 244 187 kW 20.0 20.4 20.9 21.5 20.3 20.4 21 21.7 20.6 20.6 21.2 21.9 20.8 20.8 21.3 22 21 21 21.5 22.1
95 TC 241 252 277 303 251 257 281 309 259 262 286 314 266 267 290 317 274 275 293 321 SHC 241 223 187 149 251 239 198 157 259 254 210 164 266 265 222 171 274 275 238 180 kW 22.4 22.6 23.1 23.7 22.6 22.7 23.3 23.9 22.8 22.9 23.4 24 23 23 23.5 24.2 23.2 23.2 23.6 24.2
105 TC 233 243 266 289 242 247 270 295 250 252 273 299 256 258 277 303 264 265 280 306 SHC 233 218 182 145 242 233 194 152 250 248 206 159 256 257 217 166 264 265 232 176 kW 24.9 25.1 25.6 26.2 25.2 25.3 25.8 26.3 25.4 25.4 25.9 26.5 25.6 25.6 26 26.6 25.8 25.8 26.1 26.7
115 TC 225 232 254 277 234 236 258 281 241 242 261 285 247 247 264 288 254 255 267 291 SHC 225 214 178 140 234 228 189 148 241 241 201 155 247 247 211 162 253 255 227 171 kW 27.9 27.9 28.5 29 28 28.1 28.6 29.2 28.2 28.2 28.7 29.2 28.4 28.4 28.8 29.3 28.7 28.7 28.9 29.5
125 TC 216 221 241 263 224 225 245 267 231 231 248 269 237 236 251 273 243 242 253 276 SHC 216 208 173 136 223 221 184 142 230 231 196 149 236 236 206 157 243 242 221 166 kW 30.9 31.1 31.6 32 31.2 31.2 31.7 32.2 31.4 31.4 31.7 32.3 31.6 31.6 31.9 32.3 31.7 31.7 31.9 32.5
BF — Bypass Factor kW — Compressor Power Edb — Entering Dry Bulb SHC — Gross Sensible Capacity (1000 Btuh) Ewb — Entering Wet Bulb TC — Gross Cooling Capacity (1000 Btuh)

Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 753 1307 1.53 761 1330 1.56 840 1572 1.84 912 1822 2.14 980 2080 2.44 4800 747 1384 1.62 790 1515 1.78 866 1765 2.07 936 2023 2.37 1002 2289 2.68 5100 741 1465 1.72 820 1718 2.01 893 1977 2.32 961 2243 2.63 1280 2516 2.95 5700 810 1911 2.24 882 2182 2.56 950 2459 2.88 1014 2741 3.21 1075 3029 3.55 6000 844 2164 2.54 914 2444 2.87 980 2730 3.20 1042 3021 3.54 1100 3317 3.89 6300 879 2439 2.86 947 2729 3.20 1010 3023 3.55 1070 3322 3.90 1127 3626 4.25 6600 915 2737 3.21 980 3035 3.56 1041 3338 3.91 1099 3645 4.28 1155 3957 4.64 6900 950 3057 3.59 1013 3364 3.95 1072 3675 4.31 1129 3991 4.68 1183 4311 5.06 7200 986 3401 3.99 1047 3717 4.36 1104 4037 4.74 1159 4361 5.11 1211 4689 5.50 7500 1022 3770 4.42 1081 4095 4.80 1136 4423 5.19 1189 4755 5.58 1241 5091 5.97
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1044 2345 2.75 1105 2619 3.07 1163 2899 3.40 1218 3187 3.74 1271 3481 4.08 4800 1065 2561 3.00 1124 2841 3.33 1180 3127 3.67 1235 3420 4.01 1287 3720 4.36 5100 1086 2795 3.28 1144 3082 3.61 1199 3375 3.96 1252 3674 4.31 1304 3979 4.67 5700 1132 3324 3.90 1187 3624 4.25 1240 3929 4.61 1291 4241 4.97 1341 4558 5.35 6000 1157 3619 4.24 1210 3925 4.60 1262 4239 4.97 1312 4557 5.34 1361 4880 5.72 6300 1182 3935 4.62 1234 4249 4.98 1285 4569 5.36 1334 4894 5.74 — — — 6600 1208 4274 5.01 1259 4595 5.39 1309 4922 5.77 — 6900 1235 4636 5.44 1285 4964 5.82 — 7200 1262 5021 5.89 — 7500 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1322 3781 4.43 1372 4088 4.79 1419 4400 5.16 1466 4719 5.53 1511 5042 5.91 4800 1337 4280 4.72 1386 4337 5.09 1433 4655 5.46 1479 4978 5.84 — — — 5100 1353 4290 5.03 1401 4607 5.40 1448 4930 5.78 — 5700 1388 4881 5.72 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 221 for general Fan Performance Data notes.
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms require a field- supplied drive.

Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 753 1307 1.53 786 1404 1.65 861 1644 1.93 932 1893 2.22 997 2150 2.52 4800 747 1384 1.62 818 1603 1.88 890 1852 2.17 958 2108 2.47 1022 2373 2.78 5100 775 1571 1.84 850 1822 2.14 920 2079 2.44 986 2344 2.75 1048 2616 3.07 5700 849 2054 2.41 918 2323 2.73 982 2598 3.05 1044 2879 3.38 1102 3166 3.71 6000 886 2329 2.73 952 2607 3.06 1015 2891 3.39 1074 3180 3.73 1130 3474 4.08 6300 924 2628 3.08 987 2915 3.42 1047 3207 3.76 1105 3504 4.11 1160 3807 4.46 6600 962 2951 3.46 1023 3246 3.81 1081 3547 4.16 1136 3853 4.52 1190 4163 4.88 6900 1000 3298 3.87 1059 3603 4.23 1115 3912 4.59 1168 4225 4.96 1220 4543 5.33 7200 1038 3672 4.31 1095 3986 4.67 1149 4303 5.05 1201 4625 5.42 1251 4950 5.81 7500 1077 4072 4.78 1131 4394 5.15 1184 4720 5.54 1234 5050 5.92 — — —
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1060 2414 2.83 1119 2685 3.15 1175 2964 3.48 1230 3250 3.81 1282 3542 4.15 4800 1082 2644 3.10 1140 2922 3.43 1195 3207 3.76 1248 3498 4.10 1299 3795 4.45 5100 1106 2894 3.39 1163 3178 3.73 1216 3470 4.07 1268 3767 4.42 1319 4071 4.77 5700 1157 3459 4.06 1211 3757 4.41 1262 4061 4.76 1312 4371 5.13 1360 4686 5.50 6000 1184 3774 4.43 1236 4080 4.79 1287 4391 5.15 1335 4707 5.52 1382 5029 5.90 6300 1212 4114 4.83 1263 4427 5.19 1312 4745 5.57 1359 5067 5.94 — — — 6600 1241 4478 5.25 1290 4798 5.63 1338 5122 6.01 — 6900 1270 4866 5.71 — 7200 — 7500 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1332 3841 4.50 1381 4145 4.86 1428 4456 5.23 1473 4772 5.60 1518 5095 5.98 4800 1349 4100 4.81 1397 4409 5.17 1443 4725 5.54 1488 5046 5.92 — — — 5100 1367 4380 5.14 1414 4695 5.51 1460 5180 5.88 — 5700 1407 5007 5.87 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 221 for general Fan Performance Data notes.
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms require a field- supplied drive.

580F210275 (18 TONS)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 755 2.27 1908 831 2.58 2171 901 2.91 2443 968 3.24 2723 1031 3.58 3009 1091 3.93 3302 6,000 810 2.72 2287 881 3.04 2556 947 3.37 2833 1010 3.71 3116 1070 4.05 3406 1127 4.40 3702 6,500 866 3.22 2710 932 3.55 2985 994 3.88 3266 1054 4.23 3554 1111 4.57 3847 1166 4.93 4146 7,000 923 3.78 3177 985 4.11 3458 1044 4.45 3744 1100 4.80 4036 1155 5.15 4333 1207 5.51 4635 7,500 980 4.39 3690 1038 4.73 3976 1094 5.07 4267 1148 5.43 4564 1200 5.78 4864 1250 6.15 5170 8,000 1038 5.06 4251 1093 5.40 4542 1146 5.75 4838 1197 6.11 5138 1246 6.47 5443 1294 6.84 5752 8,500 1096 5.78 4859 1148 6.13 5156 1198 6.49 5456 1247 6.85 5761 1294 7.22 6070 1340 7.59 6382 9,000 1154 6.56 5517 1204 6.92 5818 1251 7.28 6123 1298 7.65 6432 1343 8.02 6745 1388 8.40 7062 9,500 1213 7.40 6224 1260 7.77 6531 1306 8.13 6840 1350 8.51 7154 1394 8.88 7471 1436 9.26 7791 10,000 1272 8.30 6983 1317 8.67 7294 1360 9.05 7608 1403 9.43 7926 1445 9.81 8247 1486 10.19 8570
580F210275 (18 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 1149 4.28 3602 1204 4.65 3907 1258 5.02 4217 1284 5.20 4375 1309 5.39 4533 6,000 1183 4.76 4003 1236 5.13 4310 1288 5.50 4622 1313 5.68 4780 1337 5.87 4939 6,500 1219 5.29 4450 1270 5.66 4759 1320 6.03 5073 1344 6.22 5232 1368 6.41 5391 7,000 1258 5.88 4942 1307 6.25 5253 1355 6.62 5569 1378 6.81 5729 1402 7.00 5890 7,500 1299 6.52 5480 1346 6.89 5794 1392 7.27 6113 1415 7.46 6273 1437 7.65 6435 8,000 1341 7.21 6065 1387 7.59 6383 1392 7.97 6704 1453 8.16 6866 1475 8.36 7300 8,500 1385 7.97 6699 1429 8.35 7019 1472 8.73 7343 1493 8.93 7506 1514 9.12 7670 9,000 1431 8.78 7382 1473 9.15 7705 1515 9.55 8032 1535 9.75 8196 — — — 9,500 1478 9.65 8114 1519 10.04 8441 — 10,000 —
LEGEND *Standard low-medium static drive range is 910 to 1095 rpm. Alternate high-static drive range is 1069 to 1287. Other rpms require a field-supplied drive. Refer to page 221 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 5.90. The maximum continuous watts is 5180.
Bhp — Brake Horsepower Watts — Input Watts to Motor
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 795 2.43 2043 866 2.74 2306 934 3.07 2578 998 3.40 2856 1059 3.74 3142 1117 4.08 3434 6,000 854 2.92 2452 921 3.24 2722 984 3.57 3998 1044 3.90 3281 1102 4.25 3570 1158 4.60 3865 6,500 914 3.46 2909 977 3.79 3184 1036 4.12 3465 1093 4.46 3752 1148 4.81 4045 1201 5.16 4343 7,000 975 4.06 3414 1034 4.39 3695 1090 4.73 3981 1144 5.08 4272 1196 5.43 4569 1246 5.79 4870 7,500 1037 4.72 3969 1092 5.06 4255 1145 5.41 4546 1196 5.76 4842 1256 6.12 5142 1294 6.48 5447 8,000 1099 5.44 4575 1150 5.79 4866 1201 6.14 5162 1249 6.50 5462 1297 6.86 5766 1343 7.22 6075 8,500 1161 6.22 5232 1210 6.57 5529 1258 6.93 5829 1304 7.29 6134 1349 7.66 6443 1393 8.03 6755 9,000 1223 7.07 5943 1270 7.43 6245 1315 7.79 6550 1360 8.16 6869 1403 8.53 7171 1445 8.90 7487 9,500 1286 7.98 6708 1331 8.34 7014 1374 8.71 7324 1416 9.08 7638 1457 9.46 7954 1498 9.84 8274 10,000 1349 8.95 7528 1392 9.32 7839 1433 9.70 8154 1473 10.07 8471 —
580F210360 (18 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 1.9 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5,500 1173 4.44 3732 1227 4.80 4036 1279 5.17 4345 1304 5.35 4502 1329 5.54 4629 6,000 1211 4.95 4165 1263 5.32 4471 1313 5.69 4782 1337 5.87 4939 1361 6.06 5097 6,500 1252 5.53 4646 1302 5.89 4954 1350 6.26 5267 1373 6.56 5425 1396 6.64 5584 7,000 1295 6.16 5176 1343 6.52 5487 1389 6.90 5802 1412 7.09 5961 1434 7.28 6121 7,500 1340 6.85 5756 1386 7.22 6070 1431 7.60 6387 1452 7.79 6547 1474 7.98 6709 8,000 1388 7.60 6388 1431 7.97 6704 1474 8.35 7260 1495 8.54 7186 1516 8.74 7348 8,500 1436 8.41 7071 1478 8.79 7390 1520 9.17 7713 1540 9.37 7876 — — — 9,000 1486 9.28 7807 1527 9.67 8130 — 9,500 1538 10.22 8597 — 10,000 —
LEGEND *Standard low-medium static drive range is 910 to 1095 rpm. Alternate high-static drive range is 1069 to 1287. Other rpms require a field-supplied drive. Refer to page 221 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 5.90. The maximum continuous watts is 5180.
Bhp — Brake Horsepower Watts — Input Watts to Motor

580F240275 (20 TONS)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 824 2607 3.09 894 2844 3.37 961 3085 3.66 1023 3330 3.95 1083 3578 4.24 6,500 881 3030 3.59 947 3266 3.88 1009 3507 4.16 1069 3751 4.45 1126 3998 4.74 7,000 939 3488 4.14 1001 3725 4.42 1060 3965 4.70 1116 4208 4.99 1170 4454 5.28 7,500 998 3982 4.72 1055 4218 5.00 1111 4458 5.29 1165 4701 5.58 1217 4946 5.87 8,000 1056 4512 5.35 1111 4748 5.63 1164 4988 5.92 1215 5230 6.20 1264 5474 6.49 8,500 1116 5077 6.02 1167 5314 6.30 1218 5553 6.59 1266 5795 6.87 1314 6039 7.16 9,000 1175 5678 6.74 1224 5915 7.02 1272 6154 7.30 1319 6395 7.59 1364 6639 7.88 9,500 1235 6315 7.49 1282 6552 7.77 1327 6791 8.06 1372 7033 8.34 1415 7276 8.63 10,000 1295 6988 8.29 1340 7225 8.57 1383 7465 8.86 1426 7706 9.14 1468 7949 9.43
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 1141 3829 4.54 1196 4082 4.84 1249 4337 5.15 1301 4596 5.45 1351 4856 5.76 6,500 1181 4247 5.04 1234 4499 5.34 1285 4753 5.64 1334 5009 5.94 1383 5267 6.25 7,000 1223 4702 5.58 1274 4953 5.88 1323 5205 6.18 1371 5460 6.48 1417 5716 6.78 7,500 1267 5194 6.16 1316 5443 6.46 1363 5694 6.76 1409 5947 7.06 1454 6202 7.36 8,000 1313 5721 6.79 1359 5970 7.08 1405 6220 7.38 1449 6472 7.68 1493 6726 7.98 8,500 1360 6285 7.46 1405 6533 7.75 1449 6783 8.05 1491 7034 8.34 1533 7286 8.64 9,000 1408 6885 8.17 1451 7132 8.46 1494 7381 8.76 1535 7631 9.05 — — — 9,500 1458 7521 8.92 1499 7768 9.22 1540 8180 9.51 — 10,000 1508 8193 9.72 1549 8440 10.01 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 1399 5118 6.07 1446 5381 6.38 1492 5647 6.70 1537 5914 7.02 — — — 6,500 1429 5527 6.56 1475 5789 6.87 1520 6052 7.18 — 7,000 1462 5974 7.09 1507 6234 7.40 1550 6495 7.71 — 7,500 1498 6459 7.66 1540 6717 7.97 — 8,000 1535 6981 8.28 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 221 for general Fan Performance Data notes.
NOTE: Maximum continuous bhp for the standard motor is 8.70 (for 208/230 and 575-v units) and 9.50 (for 460-v units). The maximum con- tinuous watts is 7915 (for 208/230 and 575-v units) and 8640 (for 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Performance table for additional information.
*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms require a field- supplied drive.

580F240360 (20 TONS)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 868 2752 3.26 934 2987 3.54 997 3227 3.83 1058 3470 4.12 1115 3716 4.41 6,500 929 3201 3.80 991 3436 4.08 1051 3675 4.36 1108 3917 4.65 1162 4163 4.94 7,000 991 3687 4.37 1049 3923 4.65 1105 4161 4.94 1159 4403 5.22 1211 4647 5.51 7,500 1054 4211 5.00 1109 4447 5.28 1161 4686 5.56 1213 4926 5.84 1262 5170 6.13 8,000 1117 4773 5.66 1168 5009 5.94 1218 5247 6.22 1267 5488 6.51 1314 5731 6.80 8,500 1180 5373 6.37 1229 5609 6.65 1277 5847 6.94 1323 6088 7.22 1368 6331 7.51 9,000 1244 6011 7.13 1290 6247 7.41 1335 6485 7.69 1380 6726 7.98 1423 6968 8.27 9,500 1308 6687 7.93 1352 6924 8.21 1395 7162 8.50 1437 7402 8.78 1479 7644 9.07 10,000 1372 7401 8.78 1414 7638 9.06 1455 7876 9.34 1496 8117 9.63 1535 8358 9.92
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 1171 3965 4.70 1224 4216 5.00 1276 4469 5.30 1326 4726 5.61 1374 4983 5.91 6,500 1215 4410 5.23 1266 4659 5.53 1316 4911 5.83 1364 5165 6.13 1411 5421 6.43 7,000 1262 4894 5.81 1311 5142 6.10 1358 5392 6.40 1404 5645 6.70 1449 5899 7.00 7,500 1310 5415 6.42 1357 5663 6.72 1403 5912 7.01 1447 6164 7.31 1490 6416 7.61 8,000 1360 5976 7.09 1405 6222 7.38 1449 6471 7.68 1492 6721 7.97 1533 6973 8.27 8,500 1412 6575 7.80 1455 6821 8.09 1497 7068 8.39 1538 7318 8.68 — — — 9,000 1465 7212 8.56 1506 7457 8.85 1547 7705 9.14 — 9,500 1519 7888 9.36 — 10,000 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,000 1422 5243 6.22 1468 5505 6.53 1513 5768 6.84 — 6,500 1456 5679 6.74 1501 5938 7.04 1544 6199 7.35 — 7,000 1493 6155 7.30 1536 6412 7.61 — 7,500 1533 6670 7.91 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 221 for general Fan Performance Data notes.
NOTE: Maximum continuous bhp for the standard motor is 8.70 (for 208/230 and 575-v units) and 9.50 (for 460-v units). The maximum con- tinuous watts is 7915 (for 208/230 and 575-v units) and 8640 (for 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Performance table for more information.
*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms require a field- supplied drive.

580F300275 (25 TONS)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 941 3.35 2,769 1002 3.80 3,140 1061 4.27 3528 1117 4.76 3,934 1171 5.27 4,356 1224 5.80 4,794 7,500 999 4.05 3,348 1057 4.53 3,742 1112 5.02 4152 1166 5.54 4,579 1218 6.07 5,210 1268 6.63 5,478 8,000 1058 4.85 4,007 1113 5.35 4,424 1165 5.87 4856 1216 6.41 5,304 1266 6.97 5,766 1314 7.55 6,243 8,500 1117 5.74 4,750 1169 6.28 5,190 1219 6.83 5645 1268 7.40 6,114 1315 7.98 6,597 1361 8.58 7,094 9,000 1177 6.75 5,583 1226 7.31 6,047 1274 7.89 6524 1320 8.48 7,015 1365 9.09 7,520 1410 9.72 8,037 9,500 1237 7.98 6,511 1284 8.46 6,999 1329 9.07 7499 1374 9.69 8,012 1417 10.33 8,538 1459 10.98 9,076 10,000 1297 9.12 7,450 1342 9.74 8,051 1385 10.37 8574 1428 11.02 9,110 1469 11.68 9,657 1510 12.36 10,217 10,500 1358 10.49 8,674 1400 11.14 9,209 1442 11.80 9755 1483 12.47 10,314 1523 13.16 10,883 — — — 11,000 1418 12.00 9,919 1459 12.67 10,478 — 11,250 1449 12.80 10,585 —
580F300275 (25 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 1274 6.35 5248 1323 6.92 5,718 1371 5.54 6204 7,500 1316 7.20 6960 1364 7.79 6,437 1410 6.41 6939 8,000 1360 8.14 6734 1406 8.76 7,239 1450 7.40 7759 8,500 1406 9.20 7605 1449 9.83 8,129 1492 8.48 8666 9,000 1453 10.36 8568 1495 11.02 9,111 1536 9.69 9667 9,500 1501 11.64 9627 1541 12.32 10,190 — — — 10,000 — 10,500 — 11,000 — 11,250 —
Refer to this page for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Perfor- mance table for more information.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 992 4.05 3,348 1051 4.44 3,668 1106 4.83 3995 1160 5.24 4331 1212 5.65 4675 1262 6.08 5026 7,500 1055 4.77 3,947 1110 5.17 4,277 1162 5.58 4615 1214 6.00 4960 1263 6.43 5312 1311 6.86 5672 8,000 1118 5.58 4,610 1170 5.99 4,950 1220 6.41 5298 1268 6.84 5653 1315 7.27 6014 1361 7.72 6382 8,500 1182 6.46 5,339 1231 6.88 5,690 1278 7.31 6047 1324 7.75 6411 1369 8.20 6782 1413 8.66 7158 9,000 1246 7.42 6,136 1292 7.86 6,498 1337 8.30 6865 1381 8.75 7239 1424 9.21 7618 1466 9.68 8003 9,500 1310 8.47 7,005 1354 8.92 7,377 1397 9.38 7754 1439 9.84 8137 1480 10.31 8525 1520 10.79 8918 10,000 1374 9.61 7,947 1416 10.07 8,329 1457 10.54 8715 1497 11.02 9107 1537 11.50 9504 — — — 10,500 1439 10.84 8,964 1479 11.32 9,356 1518 11.79 9752 — 11,000 1503 12.17 10,059 1542 12.65 10,460 — 11,250 1536 12.86 10,636 —
580F300360 (25 TONS)* (cont)
Available External Static Pressure (in. wg) 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 7,000 1311 6.51 5385 1359 6.96 5751 1405 6.00 6124 7,500 1358 7.30 6039 1403 7.76 6412 1448 6.84 6792 8,000 1406 8.17 6767 1560 8.63 7137 1492 7.75 7524 8,500 1456 9.12 7541 1498 9.59 7929 1539 8.75 8323 9,000 1507 10.15 8393 1548 10.63 8790 — — — 9,500 — 10,000 — 10,500 — 11,000 — 11,250 —
Refer to this page for general Fan Performance Data notes. NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Perfor- mance table for more information.
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

ELEVATION
MAXIMUM HEATING VALUE
(Btu/ft3) 0-2,000 1,100 2,001-3,000 1,050 3,001-4,000 1,000 4,001-5,000 950 5,001-6,000 900
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For ele- vations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code. IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.
Power Exhaust (580F180-300)
ALTITUDE COMPENSATION — 580F180-300
(LP Gas Units)
ALTITUDE COMPENSATION* —
LIQUID PROPANE
ELEVATION
ORIFICE SIZE Low Heat and High Heat 0-2,000 36 2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42 10,000 43
NATURAL GAS ORIFICE SIZE† Low Heat High Heat 0-3,000 30 29 3,000- 7,000 31 30 7,000- 9,000 32 31 9,000-10,000 33 31 above 10,000 35 32
(ft)
*Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant dealer.
SOUND RATING
OCTAVE BANDS
UNIT 580F
A-WEIGHTED
63 125 250 500 1000 2000 4000 8000
180 88 dB 87.6 90.8 88.7 86.4 84.3 83.5 78.4 75.6 66.8 210 88 dB 87.8 90.8 88.7 86.4 84.3 83.5 78.4 75.6 66.8 240 94 dB 94.4 99.7 93.0 93.7 91.8 89.7 85.9 80.7 74.4 300 94 dB 94.1 98.7 92.3 93.8 90.9 89.6 85.9 80.3 74.3
Bels — Sound Levels (1 bel = 10 decibels)
a50-4028 · (dB) · (60 Hz)

COMPONENT CFM 4500 5000 5400 6000 7200 7500 9000 10,000 11,250 EconoMi$er IV and EconoMi$er2 0.040 0.050 0.060 0.070 0.090 0.100 0.110 0.120 0.140
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
UNIT 580F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
180† †† 1021 1002 984 965 947 928 910 891 873 180** †† 1200 1178 1156 1134 1112 1091 1069 1047 1025 210† †† †† 1095 1077 1058 1040 1021 1002 984 965 947 928 910 210** †† †† 1287 1265 1243 1222 1200 1178 1156 1134 1112 1091 1069 240† †† 1151 1132 1114 1095 1077 1058 1040 1021 1002 240** †† 1369 1347 1325 1303 1281 1259 1237 1215 1193 300† †† †† 1283 1269 1247 1225 1203 1182 1160 1138 1116 1095 1066 300** †† 1551 1524 1497 1470 1443 1415 1388 1361 1332
*Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package. ††Due to belt and pulley size, pulley cannot be set to this number of turns open.
MAXIMUM ACCEPTABLE CONTINUOUS
MAXIMUM ACCEPTABLE CONTINUOUS
MAXIMUM ACCEPTABLE
UNIT 580F UNIT VOLTAGE
MAXIMUM AMP DRAW
OPERATING
BHP*
WATTS
180 208/230 6.13 4.57 5,180 15.8 460 7.9 575 6.0
210 208/230 5.90 4.40 5,180 15.8 460 7.9 575 6.0
240 208/230 8.70 6.49 7,915 22.0 460 9.50 7.08 8,640 13.0 575 8.70 6.49 7,915 10.0
300 208/230 10.20 7.61 9,510 28.0 460 11.80 8.80 11,000 14.6 575 10.20 7.61 9,510 13.0
will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency require- ments as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
BHP — Brake Horsepower BkW — Brake Kilowatts
*Extensive motor and electrical testing on these units ensures that the full horse- power (brake kilowatt) range of the motors can be utilized with confidence. Using your fan motors up to the horsepower (brake kilowatt) ratings shown in this table
UNIT 580F MOTOR EFFICIENCY
(%) 5 Hp 87.5 7.5 Hp 88.5 10 Hp 89.5
NOTE: The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance requirements. Therefore, the indoor-fan motors for these units are exempt from these requirements.
BkW*

NOMINAL VOLTAGE (3 Ph, 60 Hz)
POWER SUPPLY No. 1 No. 1A No. 2 Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
COMPRESSOR OFM IFM POWER EXHAUST
COMBUSTION
UNIT 580F
RANGE
FAN MOTOR
208/230 187 253 32.1 195 — — 20.7 156 3 0.5 1.7 5.0 15.8/15.8 — — 0.57 82/82 110/110 4.6 18.8 0.57 86/86 110/110
460 414 508 16.4 95 — — 10 70 3 0.5 0.8 5.0 7.9 — — 0.30 41 50 2.3 6.0 0.30 43 50
575 518 633 12 80 — — 8.2 54 3 0.5 0.75 5.0 6.0 — — 0.57 31 40 2.1 4.8 0.57 34 40
208/230 187 253 30.1 225 — — 28.8 195 3 0.5 1.7 5.0 15.8/15.8 — — 0.57 87/87 110/110 4.6 18.8 0.57 92/92 110/110
460 414 508 15.5 114 — — 14.7 95 3 0.5 0.8 5.0 7.9 — — 0.30 44 50 2.3 6.0 0.30 47 60
575 518 632.5 12.1 80 — — 10.7 80 3 0.5 0.75 5.0 6.0 — — 0.57 34 40 2.1 4.8 0.57 36 40
208/230 187 253 42 239 — — 33.6 225 2 1 6.6 7.5 25.0/25.0 — — 0.57 124/124 150/150 4.6 18.8 0.57 129/129 150/150
460 414 508 19.2 125 — — 17.3 114 2 1 3.3 7.5 13.0 — — 0.30 61 80 2.3 6.0 0.30 63 80
575 518 633 13.8 80.0 — — 13.5 80.0 2 1.0 3.4 7.5 10.0 — — 0.57 48 60 2.1 4.8 0.57 50 60
208/230 187.2 253 20.7 156 20.7 156 47.1 245 6 0.5 1.7 10.0 28.0/28.0 — — 0.57 138/138 175/175 4.6 18.8 0.57 143/143 150/175
460 414 508 10 75 10 75 19.6 125 6 0.5 0.8 10.0 14.6 — — 0.30 64 80 2.3 6 0.30 66 80
575 517.5 632.5 8.2 54 8.2 54 15.8 100 6 0.5 0.8 10.0 13.0 — — 0.57 54 60 2.1 4.8 0.57 56 70
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
= 100 x max voltage deviation from average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455 3
*Fuse or HACR circuit breaker.

= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x 7 457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.
% Voltage Imbalance · average voltage

LEGEND AHA — Adjustable Heat Anticipator C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor CR — Control Relay DU — Dummy Terminal EQUIP — Equipment FPT — Freeze Protection
Thermostat FU — Fuse GND — Ground HPS — High-Pressure Switch HS — Hall Effect Sensor HV — High Voltage I — Ignitor IDM — Induced-Draft Motor IFC — Indoor-Fan Contactor IFCB — Indoor-Fan Circuit Breaker IFM — Indoor-Fan Motor IGC — Integrated Gas Unit
Controller L — Light LOR — Lockout Relay LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve OFC — Outdoor-Fan Contactor OFM — Outdoor-Fan Motor PL — Plug Assembly PRI — Primary QT — Quadruple Terminal R — Relay RS — Rollout Switch SEN — Sensor SW — Switch TB — Terminal Block TC — Thermostat, Cooling TH — Thermostat, Heating TRAN — Transformer
Splice Factory Wiring Field Wiring Option/Accessory Wiring To indicate common potential only, not to represent wiring.

LEGEND AL — Ambient Limit OA — Outdoor Air ECB — Economizer Control Board OAS— Outdoor Air Sensor IA — Indoor Air RAS— Return Air Sensor IAQ — Indoor Air Quality SAT — Supply Air Temperature
RED
500 OHM RESISTOR
PINK
BLUE NOTE 1
RUN
OAT
BLACK
NOTE 2
50HJ540573 ACTUATOR ASSEMBLY
DIRECT DRIVE
WHITE
ACTUATOR
ECONOMISER2 PLUG
LEGEND OAT — Outdoor Air Temperature Sensor NOTES:
a48-7877 · a50-8058

a48-6005

LEGEND NEC — National Electrical Code b48-1258

UNIT 581A 155 180 208/230 460 575 208/230 460 575 NOMINAL CAPACITY (tons) 12 15 OPERATING WEIGHT (lb)
Al/Al* 1725 1800 Al/Cu* 1875 1950 Cu/Cu* 2005 2080 EconoMi$er IV 90 90 EconoMi$er2 85 85 Roof Curb† 200 200 Hot Gas Reheat Dehumidification Package — 40 COMPRESSOR
Quantity...Model (Ckt 1, Ckt 2) 2...ZR72KC 1...ZR94KC, 1...ZR72KC Number of Refrigerant Circuits 2 2 Loading (% of full capacity) 0,53,100 0,60,100 Crankcase Heater Watts 70 70 Oil (oz) (Ckt 1, Ckt 2) 60,60 85,60 REFRIGERANT TYPE R-22 Expansion Device TXV Operating Charge (lb)
Circuit 1** 20.7 19.5 Circuit 2 13.4 13.45 CONDENSER FAN Propeller Type Nominal Cfm 10,500 10,500 Quantity...Diameter (in.) 3...22 3...22 Motor Hp...Rpm 1/2...1050 1/2...1050 Watts Input (Total) 1100 1100
CONDENSER COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced, Aluminum
Pre-Coated, or Copper Plate Fins Rows...Fins/in. 4...15 4...15 Total Face Area (sq ft) 21.7 21.7 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2...12 X 12 2...12 x 12 Type Drive Belt Belt Nominal Cfm 5200 6000 Std Motor Hp 2.9 3.0 5 Opt Motor Hp 3.7 N/A N/A Motor Nominal Rpm 1725 1745 Std Maximum Continuous Bhp 3.13 3.38 6.13 Opt Maximum Continuous Bhp 4.26 N/A Motor Frame Size 56H 184T Fan Rpm Range Low-Medium Static 895-1147 895-1147 873-1021 High Static 1040-1315 N/A 1025-1200 Motor Bearing Type Ball Ball Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Dia. Low-Medium Static 3.1/4.1 3.1/4.1 4.9/5.9 High Static 3.7/4.7 N/A 4.9/5.9 Nominal Motor Shaft Diameter (in.) 7/8 7/8 11/8 Fan Pulley Pitch Diameter (in.) Low-Medium Static 6.0 6.0 9.4 High Static 6.0 6.0 8.0 Nominal Fan Shaft Diameter (in.) 13/16 13/16 17/16 Belt, Quantity...Type... Length (in.) Low-Medium Static 1...BX...45 1...BX...45 1...BX...50 High Static 1...BX...45 1...BX...45 1...BX...48 Pulley Center Line Distance (in.) 14.5-16.0 14.5-16.0 13.3-14.8 Speed Change per Full Turn of Movable Pulley Flange (Rpm) Low-Medium Static 45 45 37 High Static 45 N/A 44 Movable Pulley Maximum Full Turns From Closed Position 6 6 4†† Factory Speed 3.5 3.5 3.5 Factory Speed Setting (Rpm) Low-Medium Static 987 987 965 High Static 1155 N/A 1134 EVAPORATOR COIL Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced or Copper Plate Fins, Face Split Rows...Fins/in. 4...15 4...15 Total Face Area (sq ft) 17.5 17.5 FURNACE SECTION
Rollout Switch Cutout Temp (F)*** 190 190 Burner Orifice Diameter (in...drill size) Natural Gas Std 0.1285...30/ 0.136...29 0.1285...30/ 0.136...29 Liquid Propane††† Alt 0.1065...36/0.1065...36 0.1065...36/0.1065...36 Thermostat Heat Anticipator Setting 208/230/460/575 v Stage 1 (amps) 0.98 0.8 0.98 0.98 0.8 0.98 Stage 2 (amps) 0.44 Gas Input (Btuh) Stage 1 172,000/230,000 206,000/270,000 Stage 2 225,000/300,000 275,000/360,000 Efficiency (Steady State) (%) 81 81 Temperature Rise Range 15-45/30-60 15-45/20-50 Manifold Pressure (in. wg)
Natural Gas Std 3.3 3.3 Liquid Propane††† Alt 3.3 3.3 Gas Valve Quantity 1 1 Gas Valve Pressure Range (Min-Max Allowable) (in. wg) 5.5-13.5 5.5-13.5 (psig).235-.487 .235-.487 Field Gas Connection Size (in.-FPT) 3/4 3/4 HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto.) 320 LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto.) 44 FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 2...20 x 25 x 1 1...20 x 20 x 1 RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...20 x 20 x 2 4...16 x 20 x 2
LEGEND *Evaporator coil fin material/condenser coil fin material. †Weight of 14-in. roof curb. **Circuit 1 uses the lower portion of condenser coil and lower portion of evaporator coils, and Circuit 2 uses the upper portion of both coils. ††Due to belt and pulley style, moveable pulley cannot be set to 0 to 1/2 turns open. ***Rollout switch is manual reset. †††A Liquid Propane kit is available as an accessory. Kit may be used at elevations as high as
Al — Aluminum Bhp — Brake Horsepower Cu — Copper TXV — Thermostatic Expansion Valve
2000 ft.
Unit

UNIT 581A 210 240 300 NOMINAL CAPACITY (tons) 18 20 25 OPERATING WEIGHT (lb)
Al/Al 2224 2272 2526 COMPRESSOR
Quantity 3 3 2 Number of Refrigerant Circuits 3 3 2 Oil (ounces) Ckt A...Ckt B...Ckt C 68...68...90 90...90...90 110...110...NA REFRIGERANT TYPE
Expansion Device TXV TXV TXV Operating Charge (lb) Circuit A 13.1 13.8 21.8 Circuit B 12.7 13.9 20.3 Circuit C 15.2 15.5 NA CONDENSER FAN
Nominal Cfm (Total, all fans) 14,000 14,000 21,000 Quantity...Diameter (in.) 4...22 4...22 6...22 Motor Hp...Rpm 1/4...1100 1/4...1100 1/4...1100 Watts Input (Total) 1400 1400 2100 CONDENSER COIL
Rows...Fins/in. 2...17 2...17 2...17 Total Face Area (sq ft) 57.78 57.78 66.67 EVAPORATOR FAN
Quantity...Size 2...15x11 2...15x11 2...15x11 Type Drive Belt Belt Belt Nominal Cfm 7000 8000 10,000 Motor Bearing Type Ball Ball Ball Maximum Allowable Fan Rpm 1400 1400 1400 EVAPORATOR COIL
Rows...Fins/in. 3...15 4...15 4...15 Total Face Area (sq ft) 23.33 23.33 27.22 FURNACE SECTION
Rollout Switch Cutout Temp (F) 225 225 225 Burner Orifice Diameter (in drill size) 0.136...29 0.136...29 0.136...29 Gas Natural Natural Natural Thermostat Heat Anticipator Setting Stage 1 (amps) 0.98 0.98 0.98 Stage 2 (amps) 0.44 0.44 0.44 Gas Input (Btuh) HIGH HEAT Stage 1 317,000 317,000 317,000 Stage 2 400,000 400,000 400,000 Efficiency (Steady State) % Vertical 82 82 82 Temperature Rise Range 25-55 25-55 25-55 Gas Input (Btuh) MEDIUM HEAT Stage 1 281,000 281,000 281,000 Stage 2 365,000 365,000 365,000 Efficiency (Steady State) % Vertical 81 81 81 Temperature Rise Range 25-55 25-55 25-55 Gas Input (Btuh) LOW HEAT Stage 1 199,000 199,000 199,000 Stage 2 250,000 250,000 250,000 Efficiency (Steady State) % Vertical 82 82 82 Temperature Rise Range (F) 15-45 15-45 15-45 Manifold Pressure
Natural Gas (in. wg) Vertical 3.00 3.00 3.00 Natural Gas (in. wg) Horizontal 2.95 2.95 2.95 Gas Valve Quantity 1 1 1 Gas Valve Pressure Range (in. wg) 5.5-13.0 5.5-13.0 5.5-13.0 Min-Max Allowable (psig).235-.469 .235-.469 .235-.469 Field Gas Connection Size (in. FPT) 3/4 3/4 3/4 HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 Reset (Auto) 320 320 320 OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.) 3...20x25 3...20x25 3...20x25 RETURN-AIR FILTERS
Quantity...Size (in.) 9...16x25 9...16x25 9...18x24
TXV — Thermostatic Expansion Valve

581A 210 240 300 203/230 and 460 V 575 V 203/230 and 460 V 575 V 203/230 and 460 V 575 V LOW RANGE
Motor Hp 3.7 3 5 Motor Nominal RPM 1725 1725 1745 Maximum Continuous Bhp 4.25 3.45 5.75 Maximum Continuous Watts 3698 3149 4900 Motor Frame Size 56HZ 56HZ S184T 184T S184T 184T Motor Shaft Diameter (in.) 7/8 7/8 11/8 Fan Rpm Range 647-886 810-1072 949-1206 949-1206 805-1007 805-1007 Motor Pulley Min. Pitch Diameter (in.) 2.7 3.1 3.7 3.7 4.8 4.8 Motor Pulley Max. Pitch Diameter (in.) 3.7 4.1 4.7 4.7 6.0 6.0 Blower Pulley Pitch Diameter (in.) 7.2 6.6 6.8 6.8 10.4 10.4 Blower Pulley Shaft Diameter (in.) 1.1875 Blower Pulley Type Fixed Pulley Center Line Distance (in.) 11.293-13.544 11.286-14.475 9.81-13.055 Belt, Quantity...Type...Length (in.) 1...BX...38 1...BX...45 1...BX...45 Speed Change Per Turn — Moveable Pulley (rpm) 48 52 51 51 40 40 Moveable Pulley Maximum Full Turns 6 Factory Speed Setting (rpm) 767 941 1078 1078 906 906 HIGH RANGE
Motor Hp 5 5 7.5 Motor Nominal Rpm 1745 Maximum Continuous Bhp 5.75 5.75 8.63 Maximum Continuous Watts 4900 4900 7267 Motor Frame Size S184T 184T S213T Motor Shaft Diameter (in.) 11/8 11/8 13/8 Fan Rpm Range 897-1139 873-1108 941-1176 Motor Pulley Min. Pitch Diameter (in.) 3.7 3.7 4.8 Motor Pulley Max. Pitch Diameter (in.) 4.7 4.7 6.0 Blower Pulley Pitch Diameter (in.) 7.2 7.4 8.9 Blower Pulley Shaft Diameter (in.) 1.1875 Blower Pulley Type Fixed Pulley Center Line Distance (in.) 9.81-13.055 9.81-13.055 9.025-12.179 Belt, Quantity...Type...Length (in.) 1...BX...38 1...BX...38 1...BX...42 Speed Change Per Turn — Moveable Pulley (rpm) 48 47 Moveable Pulley Maximum Full Turns 6 Factory Speed Setting (rpm) 1018 991 1059
Bhp — Brake Horsepower
581A 210 240 300 203/230 and 460 V 575 V 203/230 and 460 V 575 V 203/230 and 460 V 575 V LOW RANGE
Motor Hp 3.7 3 3.7 5 5 5 Motor Nominal Rpm 1725 1725 1725 1745 1745 1745 Maximum Continuous Bhp 4.25 3.45 4.25 5.75 5.75 5.75 Maximum Continuous Watts 3698 3149 3698 4900 4900 4900 Motor Frame Size 56HZ 56HZ 56HZ 184T S184T 184T Motor Shaft Diameter (in.) 7/8 7/8 7/8 11/8 11/8 11/8 Fan Rpm Range 896-1227 863-1141 896-1227 873-1108 805-1007 805-1007 Motor Pulley Min. Pitch Diameter (in.) 2.7 3.1 2.7 3.7 4.8 4.8 Motor Pulley Max. Pitch Diameter (in.) 3.7 4.1 3.7 4.7 6.0 6.0 Blower Pulley Pitch Diameter (in.) 5.2 6.2 5.2 7.4 10.4 10.4 Blower Pulley Shaft Diameter (in.) 1.1875 Blower Pulley Type Fixed Pulley Center Line Distance (in.) 11.293-13.544 11.286-14.475 11.293-13.544 9.81-13.055 9.81-13.055 9.81-13.055 Belt, Quantity...Type...Length (in.) 1...BX...35 1...BX...38 1...BX...35 1...BX...38 1...BX...45 1...BX...45 Speed Change Per Turn — Moveable Pulley (rpm) 66 56 66 47 40 40 Moveable Pulley Maximum Full Turns 6 Factory Speed Setting (rpm) 1062 1002 1062 991 906 906 HIGH RANGE
Motor Hp 5 7.5 7.5 Motor Nominal Rpm 1745 Maximum Continuous Bhp 5.75 8.63 8.63 Maximum Continuous Watts 4900 7267 7267 Motor Frame Size S184T 184T S184T 184T S213T S213T Motor Shaft Diameter (in.) 11/8 13/8 13/8 Fan Rpm Range 1113-1414 1042-1285 1113-1414 1113-1414 941-1176 941-1176 Motor Pulley Min. Pitch Diameter (in.) 3.7 4.3 3.7 3.7 4.8 4.8 Motor Pulley Max. Pitch Diameter (in.) 4.7 5.3 4.7 4.7 6.0 6.0 Blower Pulley Pitch Diameter (in.) 5.8 7.2 5.8 5.8 8.9 8.9 Blower Pulley Shaft Diameter (in.) 1.1875 Blower Pulley Type Fixed Pulley Center Line Distance (in.) 9.81-13.055 9.025-12.179 9.025-12.179 Belt, Quantity...Type...Length (in.) 1...BX...35 1...BX...38 1...BX...35 1...BX...35 1...BX...42 1...BX...42 Speed Change Per Turn — Moveable Pulley (rpm) 60 48 60 60 47 47 Moveable Pulley Maximum Full Turns 6 Factory Speed Setting (rpm) 1264 1164 1264 1264 1059 1059
Bhp — Brake Horsepower

BASE UNIT OPERATING WEIGHTS* 155 180 lb kg lb kg 581A 1725 782 1800 816
*Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 155 and 180 unit sizes add 75 lb (34 kg) for domestic crating. For export crating add 500 lb (227 kg).
OPTION/ACCESSORY WEIGHTS 48HJ015 48HJ017 lb kg lb kg Barometric Relief Damper 50 23 50 23 Power Exhaust 85 39 85 39 EconoMi$er IV 90 41 90 41 EconoMi$er2 85 39 85 39 Cu Condenser Coil 150 68 150 68 Cu Condenser and Evaporator Coils 280 127 280 127 Roof Curb (14-in. curb) 200 91 200 91 Horizontal Adapter Roof Curb (Preassembled) 250 113 250 113 Horizontal Adapter Roof Curb (Field-assembled) 343 156 343 156 Hail Guard 60 27 60 27 Hot Gas Reheat Dehumidification Package — — 40 18
OPTIONS AND ACCESSORIES — 581A210-300 (Weight Adders)
OPTION/ACCESSORY WEIGHTS 581A210 581A240 581A300 lb kg lb kg lb kg Barometric Relief Damper 50 23 50 23 50 23 Power Exhaust 125 57 125 57 125 57 Economizer 170 77 170 77 195 88 Cu Condenser Coil 162 73 162 73 202 92 Cu Condenser and Evaporator Coils 316 143 290 132 365 166 5-Cell Gas Heat Assembly 85 39 85 39 85 39 8-Cell Gas Heat Assembly 113 51 113 51 113 51 Roof Curb (14 inch) 210 95 210 95 210 95 Optional Indoor Motor 28 13 28 13 20 9 Two-Position Damper 45 20 45 20 45 20 Hail Guard 85 39 85 39 100 45 Horizontal Airflow 90 41 90 41 90 41 Hot Gas Reheat 70 32 70 32 85 39 CO2 Sensor 5 2 5 2 5 2 Return Smoke Detector 5 2 5 2 5 2 Supply Smoke Detector 5 2 5 2 5 2 Non-Fused Disconnect 15 7 15 7 15 7 Non-Powered Convenience Outlet 20 9 20 9 20 9 Enthalpy Sensor 2 1 2 1 2 1 Differential Enthalpy Sensor 3 1 3 1 3 1 Drip Edge 5 2 5 2 5 2 Manual Damper 25 11 25 11 25 11
Cu — Copper HACR — Heating, Air Conditioning and Refrigeration
Cu — Copper

Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
155 1725 782 90 41 407 185 375 170 383 174 410 186 3-3 991 3- 5 1051 1-10 559 180 1800 816 90 41 417 189 399 181 481 218 503 228 3- 2 961 3-6 1070 1-10 559
requires no clearance.
NOTES:
A CORNER
WEIGHT CORNER
WEIGHT ECONOMI$ER IV
STD UNIT
UNIT
581A
a48-8219



Deg. in. Deg. in.
DIMENSIONS* (degrees and inches)
581A155,180
PKG. NO. REF. CURB HEIGHT DESCRIPTION
CRRFCURB010A00 1′-2″ (305) Standard Curb 14″ High
CRRFCURB011A00 2′-0″ (610) Standard Curb for Units
CRRFCURB012A00 2′-0″ (610) Side Supply and Return
Curb for High Installation
Requiring High Installation · a50-5670

FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
ACCESSORY PACKAGE NO.
CRRFCURB013A00 1 ′ -11 ″ (584)
Horizontal Supply/Return Adapter Installation (581A155,180)
581A155, 180
2'-2 1/16" 1'-6 5/16"
For horizontal return applications: The power exhaust relief must be installed in the return air duct.


a48-4184 · a48-6126



Calculate pressure drop: Design External Static Pressure 1.40 EconoMi$er IV 0.07 1.47 in. wg (ESP) Enter Fan Performance tables for 581A180 (low heat units) at 6,000 cfm and 1.47 in. wg. The rpm is 1228 and the Bhp is 4.73. The factory-installed 5 hp motor and alter- nate high-static drive are sufficient for this operation. V DETERMINE NET COOLING CAPACITIES.
Capacity (TC) 168,000 Btuh Gross Sensible Heat
Capacity (SHC) 121,000 Btuh Required Heating Capacity 190,000 Btuh Condenser Entering Air
Temperature 95 F Summer Indoor Air Temperature 80 F edb, 67 F ewb Evaporator Air Quantity 6,000 cfm External Static Pressure 1.40 in. wg Electrical Characteristics (V-Ph-Hz) 230-3-60 II SELECT UNIT BASED ON REQUIRED COOLING
Cooling capacities are gross capacities and do not include indoor (evaporator) fan motor (IFM) heat. To determine input power to the motor, enter the Fan Performance tables for 581A180 (low heat units) at 6,000 cfm and 1.47 in. wg. Input watts to the motor are 4035. Determine net cooling capacity and net sensible cooling capacity using the following formulas: IFM Heat = Input Watts x 3.412 Btuh/Watt = 4035 x 3.412 = 13,767 Btuh Net Capacity = Gross Capacity – IFM Heat = 190,000 – 13,767 = 176,233 Btuh Net Sensible Cap. = Gross Sensible Cap. – IFM Heat = 136,000 – 13,767 = 122,233 Btuh The calculations show that a 581A180275 unit is the cor- rect selection for the given conditions. VI SELECT THE UNIT THAT CORRESPONDS TO POWER
CAPACITY. Enter Cooling Capacities table for 581A180 at condenser entering temperature of 95 F, evaporator air quantity of 6,000 cfm, and indoor air temperature of 67 F. The 581A180 unit will provide a total cooling capacity of 190,000 Btuh and a SHC of 136,000 Btuh. For evaporator air temperatures other than 80 F, calculate SHC correction using formula in notes under cooling capacity tables. Unit meets design conditions for TC and SHC. NOTE: Unit ratings are gross capacities and do not include the effect of indoor fan motor heat. To calculate net capacities, see Step V. III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENT. In Heating Capacities and Efficiencies table, note that 581A180275 unit will provide 223,000 Btuh with an input of 275,000 Btuh. IV DETERMINE FAN SPEED AND POWER REQUIRE-
SOURCE AVAILABLE. The electrical data table shows that the 230-3-60 unit is available.
MENTS AT DESIGN CONDITIONS. Before entering the Fan Performance tables, calculate the total static pressure required based on unit components. Tabulated fan performance includes filters and wet evapo- rator coil. Refer to Accessory/FIOP Static Pressure table for added pressure drops.

Evap Air — Cfm/BF 3600/0.01 4375/0.01 5000/0.01 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 152 156 161 174 189 201 213 161 164 167 180 195 207 218 169 171 172 184 199 211 222 SHC 152 144 135 114 92.9 75.4 57.5 161 156 150 125 99.6 78.7 57.5 169 166 162 134 105 81.3 57.4 kW 7.56 7.65 7.74 8.01 8.33 8.6 8.86 7.76 7.82 7.88 8.14 8.46 8.72 8.97 7.92 7.95 7.98 8.24 8.55 8.82 9.06
70 TC 148 152 156 169 183 195 206 157 160 162 174 189 200 211 165 166 167 179 193 204 214 SHC 148 141 133 112 90.6 73.2 55.4 157 153 148 123 97.3 76.5 55.3 165 162 160 132 103 79.1 55.3 kW 8.5 8.58 8.67 8.97 9.26 9.53 9.8 8.7 8.75 8.81 9.07 9.39 9.66 9.91 8.86 8.89 8.91 9.16 9.49 9.76 9.99
75 TC 146 150 154 166 181 192 204 155 158 160 172 186 197 208 163 164 164 176 189 201 212 SHC 146 139 132 111 89.7 72.2 54.6 155 151 146 122 96.2 75.5 54.6 163 161 158 131 101 78.1 54.5 kW 9.02 9.1 9.18 9.45 9.8 10.1 10.4 9.22 9.27 9.31 9.58 9.91 10.2 10.5 9.39 9.41 9.43 9.68 9.99 10.3 10.6
85 TC 142 145 149 161 175 186 196 151 153 154 166 179 190 200 158 159 159 170 183 194 203 SHC 142 136 129 109 87.4 70 52.4 151 147 144 119 93.9 73.2 52.3 158 157 155 128 99.1 75.8 52.2 kW 10.1 10.2 10.3 10.6 10.9 11.2 11.5 10.3 10.4 10.4 10.7 11 11.3 11.6 10.5 10.5 10.5 10.8 11.1 11.4 11.7
95 TC 138 141 143 155 168 179 189 147 148 149 160 173 183 192 153 153 154 164 177 187 195 SHC 138 133 127 106 85 67.7 50.1 147 144 141 117 91.6 70.9 50 153 153 152 126 96.9 73.5 49.9 kW 11.4 11.4 11.5 11.8 12.2 12.4 12.7 11.6 11.6 11.6 11.9 12.3 12.6 12.8 11.8 11.8 11.8 12 12.4 12.7 12.9
105 TC 134 136 138 149 162 172 181 141 142 143 153 166 176 184 148 148 148 157 169 179 186 SHC 134 129 124 104 82.4 65.3 47.7 141 139 137 114 89 68.4 47.5 148 148 148 123 94.3 70.9 47.4 kW 12.7 12.8 12.8 13.2 13.5 13.8 14.1 12.9 13 13 13.3 13.6 13.9 14.2 13.1 13.1 13.1 13.4 13.7 14 14.3
115 TC 129 130 132 143 155 164 172 136 137 138 146 158 168 175 142 142 142 149 161 171 177 SHC 129 125 121 101 79.8 62.7 45.1 136 135 133 111 86.3 65.9 45 142 142 142 120 91.6 68.4 45 kW 14.2 14.2 14.3 14.6 15 15.3 15.6 14.4 14.4 14.5 14.7 15.1 15.5 15.7 14.6 14.6 14.6 14.8 15.2 15.6 15.7
125 TC 124 125 126 136 147 156 163 131 131 132 140 150 159 165 136 136 136 142 153 162 167 SHC 124 121 118 98.2 77 60.1 42.5 131 130 128 109 83.5 63.2 42.5 136 136 136 117 88.7 65.7 42.4 kW 15.8 15.8 15.9 16.2 16.6 17 17.2 16.1 16.1 16.1 16.4 16.7 17.1 17.3 16.3 16.2 16.2 16.4 16.8 17.2 17.4
581A155 (12 Tons) (cont)
Evap Air — Cfm/BF 5625/0.02 6250/0.02 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 175 175 176 187 202 214 224 180 180 180 190 204 216 226 SHC 175 173 171 142 110 83.8 57.3 180 180 180 151 115 86.2 57.2 kW 8.03 8.05 8.07 8.3 8.61 8.87 9.1 8.14 8.15 8.16 8.36 8.66 8.93 9.14
70 TC 170 171 171 181 195 207 216 175 176 176 184 198 209 218 SHC 170 169 168 140 108 81.5 55.2 175 176 176 148 113 84 55.1 kW 8.98 8.99 9.01 9.23 9.55 9.81 10 9.09 9.1 9.11 9.3 9.61 9.87 10.1
75 TC 168 168 169 179 192 203 213 173 173 173 181 195 206 215 SHC 168 167 166 139 107 80.5 54.4 173 173 173 147 112 83 54.3 kW 9.5 9.51 9.52 9.75 10.1 10.3 10.6 9.62 9.62 9.62 9.81 10.1 10.4 10.6
85 TC 163 163 164 172 185 196 205 168 168 168 175 188 198 206 SHC 163 162 162 136 104 78.2 52.2 168 168 168 145 109 80.6 52.1 kW 10.6 10.6 10.6 10.9 11.2 11.5 11.7 10.7 10.7 10.8 10.9 11.2 11.5 11.8
95 TC 158 158 158 166 178 189 196 162 162 162 168 180 190 197 SHC 158 157 157 134 102 75.9 49.8 162 162 162 142 107 78.3 49.7 kW 11.9 11.9 11.9 12.1 12.4 12.7 12.9 12.1 12.5 12.8 13
105 TC 152 152 152 159 171 181 187 157 157 157 161 173 182 188 SHC 152 152 152 131 99.3 73.3 47.4 157 157 157 139 104 75.7 47.4 kW 13.2 13.2 13.2 13.4 13.8 14.1 14.3 13.4 13.4 13.4 13.5 13.9 14.2 14.4
115 TC 146 146 146 151 163 172 177 150 150 150 153 165 174 178 SHC 146 146 146 128 96.6 70.7 44.9 150 150 150 136 102 73.1 44.8 kW 14.7 14.7 14.7 14.9 15.3 15.6 15.8 14.9 15.4 15.7 15.8
125 TC 140 140 140 144 155 163 167 144 144 144 146 156 164 168 SHC 140 140 140 125 93.7 67.9 42.4 144 144 144 133 98.7 70.2 42.3 kW 16.4 16.4 16.4 16.5 16.9 17.2 17.4 16.5 16.5 16.5 16.6 17 17.3 17.4
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
581A155, 180
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80). 4. Use chart below for bypass factor.
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
ENTERING WET-BULB (F) 54 58 62 67 72 76 80 Bypass Factor 3600 0.355 0.158 0.054 0.038 0.049 0.000 0.000 4375 0.439 0.255 0.112 0.043 0.057 0.000 0.000 5000 0.486 0.314 0.126 0.054 0.037 0.000 0.000 5625 0.525 0.360 0.174 0.066 0.073 0.000 0.000 6250 0.551 0.410 0.202 0.080 0.079 0.000 0.000
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Evap Air — Cfm/BF 4500/0.01 5250/0.01 6000/0.01 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 180.5 184.6 188.7 203.5 219.9 233.7 247 189.3 191.7 194.2 208.7 224.1 238 251 198.1 198.8 199.6 212.9 229.3 242 255 SHC 180.5 172.4 159.4 132.3 104.7 87.9 65.7 189.3 183.2 173.2 142.8 110.4 91 65.5 198.1 195.1 185.1 153.1 116.7 94 65.4 kW 9.41 9.49 9.58 9.87 10.19 10.47 10.78 9.58 9.63 9.68 9.97 10.29 10.57 10.87 9.75 9.77 9.79 10.07 10.39 10.67 10.95
70 TC 176.7 180.5 184.4 199 215.1 227.8 242 185.3 187.5 189.8 203 219.2 231.8 245 193 194.5 195.1 208.1 224.3 237 248 SHC 176.7 169 155.8 129.4 102.4 86 63.9 185.3 179.7 169.3 138.9 108 89.1 63.8 193 191.4 181 149.7 114.2 92.2 63.7 kW 10.5 10.57 10.64 10.96 11.35 11.62 11.95 10.68 10.72 10.76 11.06 11.45 11.72 12.04 10.85 10.87 10.89 11.17 11.55 11.82 12.13
75 TC 174.7 177.5 181 196 213 224.2 238 182.3 184.4 186 201 217 229.2 242 190.9 191.3 189 204 219 233.1 246 SHC 174.7 167.2 147 124 99 84.9 62.9 182.3 177.9 160 133 105 88 62.8 190.9 189.5 173 143 113 91 62.7 kW 11.07 11.14 11.2 11.6 12 12.23 12.57 11.25 11.3 11.3 11.7 12.1 12.33 12.66 11.45 11.45 11.4 11.8 12.1 12.44 12.75
85 TC 169.6 172.2 175 190 205 218.1 230.8 177.2 179 180 194 209 221.9 233.3 185.6 185.9 183 198 212 225.7 237 SHC 169.6 163.3 145 121 97 82.5 60.7 177.2 174.1 157 130 102 85.6 60.5 185.6 184.7 168 139 106 88.6 60.4 kW 12.29 12.35 12.3 12.7 13.1 13.5 13.86 12.47 12.51 12.5 12.8 13.2 13.61 13.96 12.67 12.68 12.6 12.9 13.3 13.71 14.05
95 TC 164.3 166.5 168 182 197 209.8 221.2 171.7 172.6 172 187 201 213.4 224.6 179.1 179.3 176 190 203 217.1 228 SHC 164.3 158.9 142 118 93 79.8 57.9 171.7 168.8 154 127 98 82.8 57.9 179.1 178.7 164 136 102 86 57.8 kW 13.59 13.65 13.5 13.9 14.3 14.85 15.23 13.8 13.82 13.6 14 14.4 14.96 15.32 14 14 13.8 14.1 14.5 15.07 15.43
105 TC 158.1 159.8 161 174 188 200.3 212.4 165.2 166 165 178 191 203.8 214.6 172.3 172.3 169 181 193 207.3 216.8 SHC 158.1 154.2 138 115 91 76.8 55.2 165.2 163.1 150 124 95 79.9 55.1 172.3 172.2 158 132 98 83 54.9 kW 14.97 15.02 14.8 15.2 15.6 16.28 16.69 15.19 15.21 14.9 15.3 15.7 16.39 16.77 15.41 15.4 15.1 15.4 15.7 16.5 16.86
115 TC 151.8 152.8 152 165 179 190.6 201.3 158.4 158.8 157 168 180 194 204.5 165 164.9 161 171 181 197.3 206.6 SHC 151.8 149.1 134 111 87 73.7 52.1 158.4 157 145 120 91 76.7 52.1 165 164.9 151 128 94 79.8 51.9 kW 16.45 16.48 16.1 16.5 16.9 17.79 18.21 16.68 16.68 16.2 16.6 17 17.91 18.3 16.89 16.88 16.4 16.7 17 18.01 18.39
125 TC 144.7 145.4 146 157.1 170.5 180.7 191.1 150.8 151.1 151.5 160.2 172.9 183.9 192 156.8 156.9 157 163.2 175.4 186.2 193.9 SHC 144.7 143.5 123.4 102.2 81.16 70.4 48.9 150.8 150.2 135.2 109.6 85.15 73.4 48.8 156.8 156.9 145.6 117.4 89.3 76.4 48.7 kW 17.96 18.01 18.05 18.49 18.99 19.44 19.85 18.18 18.22 18.25 18.6 19.11 19.5 19.89 18.42 18.44 18.46 18.72 19.14 19.65 19.93
581A180 (15 Tons) (cont)
Evap Air — Cfm/BF 6750/0.01 7500/0.02 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 203.8 204.2 204.6 216.3 231.7 244 257 209.5 209.5 209.6 218.8 235 248 259 SHC 203.8 201.8 191.2 164.1 124.1 97 65.4 209.5 209.5 196.6 173.7 138.1 100 65.2 kW 9.88 9.88 9.89 10.13 10.45 10.72 11 9.99 9.99 9.99 10.19 10.51 10.78 11.05
70 TC 199.6 199.8 200.1 210.5 226.5 239 250 205.2 205.1 205.1 213.8 228.8 241 252 SHC 199.6 197.8 187 159.7 121.3 95.2 63.5 205.2 205.1 192.4 169.8 134.5 98.2 63.5 kW 10.99 10.99 11 11.24 11.6 11.88 12.18 11.12 11.11 11.11 11.31 11.65 11.94 12.22
75 TC 196.4 196.6 194 206 220 235 247 201.9 201.9 198 208 223 237 249 SHC 196.4 195.7 181 153 120 94 62.5 201.9 201.9 186 163 163 97.1 62.5 kW 11.58 11.58 11.6 11.9 12.2 12.5 12.8 11.71 11.7 11.7 11.9 11.9 12.56 12.84
85 TC 191 191.1 188 200 213 227.8 239 196.4 196.4 192 202 214 229.8 241 SHC 191 190.5 175 148 115 91.6 60.2 196.4 196.4 180 157 119 94.6 60.2 kW 12.81 12.81 12.7 13 13.3 13.77 14.1 12.96 12.95 12.8 13.1 13.4 13.84 14.13
95 TC 184.4 184.5 181 192 205 219.1 229.7 189.7 189.7 185 194 206 221.1 230.5 SHC 184.4 184.2 170 144 108 88.9 57.7 189.7 189.7 174 153 113 91.9 57.6 kW 14.15 14.15 13.9 14.2 14.6 15.14 15.47 14.29 14.29 14 14.3 14.6 15.2 15.51
105 TC 176.7 176.7 173 182 194 209.2 218.5 181.9 181.9 177 184 194 211.1 220.1 SHC 176.7 176.7 162 140 103 86 54.9 181.9 181.9 166 148 107 88.9 54.7 kW 15.55 15.55 15.2 15.5 15.8 16.57 16.9 15.7 15.7 15.3 15.5 15.8 16.64 16.94
115 TC 169.5 169.4 166 172 183 198.2 207.1 173.9 173.8 169 174 183 200 208.6 SHC 169.5 169.4 155 136 98 82.7 51.8 173.9 173.8 158 142 101 85.6 51.7 kW 17.05 17.04 16.6 16.8 17.1 18.08 18.42 17.2 17.2 16.7 16.9 17.1 18.15 18.45
125 TC 160.9 161.1 161.2 165.6 177.4 187.9 195.4 165.1 165.2 165.4 167.8 179.2 188.6 196 SHC 160.9 161.1 150.7 125.6 95.04 79.4 48.7 165.1 165.2 155.2 133.2 105.3 82.3 48.6 kW 18.57 18.59 18.62 18.81 19.18 19.68 20.06 18.72 18.75 18.78 18.91 19.33 19.71 20.09
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80). 4. Use chart below for bypass factor.
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
ENTERING WET-BULB (F) 54 58 62 67 72 76 80 Bypass Factor 4500 0.396 0.193 0.054 0.053 0.067 0.000 0.000 5250 0.455 0.272 0.077 0.065 0.077 0.000 0.000 6000 0.504 0.337 0.121 0.077 0.088 0.000 0.000 6750 0.544 0.390 0.193 0.094 0.100 0.000 0.000 7500 0.578 0.436 0.244 0.108 0.114 0.000 0.000
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Evap Air — Cfm/BF 5400/0.05 6300/0.06 7200/0.07 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 202 206 211 229 248 263 279 212 215 218 235 254 269 285 220 221 223 239 259 273 289 SHC 202 193 184 155 124 99.3 74.7 212 205 199 166 131 103 74.9 220 216 213 177 138 106 75 kW 10.2 10.3 10.4 10.6 10.8 11 11.2 10.4 10.4 10.4 10.7 10.9 11.1 11.3 10.5 10.5 10.5 10.7 11 11.2 11.4
70 TC 197 202 206 223 242 256 272 207 209 212 228 247 262 277 215 216 217 233 252 267 282 SHC 197 189 181 152 122 97 72.5 207 202 196 163 129 101 72.7 215 212 210 174 135 104 72.8 kW 11.4 11.5 11.5 11.8 12 12.2 12.5 11.6 11.6 11.6 11.9 12.1 12.3 12.6 11.7 11.7 11.7 11.9 12.2 12.4 12.6
75 TC 195 199 203 219 238 253 268 204 206 209 225 244 258 273 212 213 214 229 248 263 277 SHC 195 187 180 150 120 95.8 71.3 204 199 195 162 127 99.3 71.4 212 210 208 173 134 103 71.5 kW 12.1 12.2 12.2 12.5 12.7 13 13.2 12.3 12.3 12.3 12.6 12.8 13 13.3 12.4 12.4 12.4 12.6 12.9 13.1 13.3
85 TC 190 193 196 213 231 246 260 199 201 202 218 236 251 264 206 207 208 222 240 255 268 SHC 190 183 177 148 118 93.4 68.8 199 195 191 159 125 96.9 68.9 206 205 204 170 131 100 69 kW 13.5 13.5 13.6 13.8 14.1 14.4 14.6 13.6 13.7 13.7 13.9 14.2 14.5 14.7 13.7 13.8 13.8 14 14.3 14.5 14.8
95 TC 184 187 190 205 222 236 250 193 194 195 210 227 241 254 200 200 201 214 231 245 258 SHC 184 179 173 144 114 90.2 65.9 193 190 187 156 121 93.7 66.1 200 199 199 167 128 97.1 66.2 kW 15 15 15.1 15.4 15.7 15.9 16.2 15.1 15.2 15.2 15.5 15.8 16 16.3 15.3 15.3 15.3 15.5 15.8 16.1 16.3
105 TC 178 180 182 197 213 228 240 186 187 188 201 217 232 244 193 193 193 205 221 235 247 SHC 178 173 169 141 111 87.3 62.9 186 184 183 152 118 90.8 63.1 193 193 193 163 124 94.1 63.2 kW 16.6 16.7 16.7 17 17.3 17.7 17.9 16.8 16.8 16.8 17.1 17.4 17.8 18 16.9 16.9 16.9 17.2 17.5 17.8 18
115 TC 171 172 174 188 203 217 228 179 179 179 192 207 221 232 185 185 185 195 210 224 235 SHC 171 168 165 137 107 83.6 59.6 179 178 178 149 114 87.1 59.7 185 185 185 159 121 90.4 59.9 kW 18.4 18.4 18.4 18.8 19.1 19.4 19.7 18.6 18.6 18.6 18.9 19.2 19.5 19.8 18.7 18.7 18.7 19 19.3 19.6 19.9
125 TC 164 165 165 178 192 205 216 171 171 171 182 196 208 219 177 177 177 185 199 211 222 SHC 164 162 160 134 104 79.8 56.1 171 171 171 145 110 83.2 56.3 177 177 177 155 117 86.5 56.4 kW 20.2 20.3 20.3 20.6 21 21.3 21.6 20.4 20.4 20.4 20.8 21.1 21.4 21.7 20.6 20.6 20.6 20.8 21.2 21.5 21.8
581A210 (18 Tons) (cont)
Evap Air — Cfm/BF 8100/0.08 9000/0.09 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 227 227 228 243 262 277 293 233 233 233 246 265 280 295 SHC 227 226 224 187 144 109 75.1 233 233 233 198 151 113 75.1 kW 10.5 10.6 10.6 10.7 11 11.2 11.4 10.6 10.6 10.6 10.8 11 11.3 11.5
70 TC 222 222 222 236 255 271 284 228 228 227 239 258 272 287 SHC 222 221 221 185 142 107 72.8 228 228 227 195 148 110 72.9 kW 11.8 11.8 11.8 12 12.2 12.5 12.7 11.9 11.9 11.8 12 12.3 12.5 12.7
75 TC 219 219 219 232 251 266 280 225 224 224 235 254 268 282 SHC 219 218 218 183 140 106 71.6 225 224 224 193 147 109 71.7 kW 12.5 12.5 12.5 12.7 12.9 13.2 13.4 12.6 12.5 12.5 12.7 13 13.2 13.4
85 TC 213 213 213 225 243 258 271 218 218 218 228 245 260 273 SHC 213 213 213 180 138 103 69.1 218 218 218 190 144 107 69.2 kW 13.8 13.8 13.8 14.1 14.3 14.6 14.8 13.9 13.9 13.9 14.1 14.4 14.6 14.8
95 TC 206 206 206 217 234 248 260 211 211 211 220 236 250 262 SHC 206 206 206 177 134 100 66.3 211 211 211 187 141 103 66.4 kW 15.4 15.4 15.4 15.6 15.9 16.1 16.4 15.5 15.5 15.5 15.6 15.9 16.2 16.4
105 TC 199 199 199 208 224 238 249 203 203 204 210 226 240 251 SHC 199 199 199 173 131 97.2 63.2 203 203 204 183 137 100 63.4 kW 17 17.1 17.1 17.3 17.6 17.9 18.1 17.2 17.2 17.2 17.3 17.6 17.9 18.1
115 TC 191 191 191 198 213 226 237 195 195 195 201 215 228 238 SHC 191 191 191 169 127 93.5 60 195 195 195 179 133 96.6 60 kW 18.8 18.8 18.8 19 19.3 19.7 19.9 18.9 18.9 18.9 19.1 19.4 19.7 19.9
125 TC 182 182 182 188 201 213 224 186 186 186 190 203 215 225 SHC 182 182 182 165 123 89.6 56.5 186 186 186 174 129 92.6 56.6 kW 20.7 20.7 20.7 20.9 21.2 21.6 21.9 20.9 20.9 20.9 21 21.3 21.6 21.9
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
581A155, 180
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80). 4. Use chart below for bypass factor.
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
ENTERING WET-BULB (F) 54 58 62 67 72 76 80 Bypass Factor 5400 0.424 0.238 0.125 0.120 0.138 0.000 0.000 6300 0.478 0.304 0.153 0.132 0.145 0.000 0.000 7200 0.525 0.364 0.190 0.144 0.153 0.000 0.000 8100 0.562 0.414 0.231 0.156 0.162 0.000 0.000 9000 0.594 0.456 0.281 0.168 0.170 0.000 0.000
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Evap Air — Cfm/BF 6,000/0.04 7,000/0.05 8,000/0.05 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 235 242 248 267 288 306 323 247 251 256 274 296 312 330 257 259 262 279 300 317 333 SHC 235 224 212 178 143 115 86.6 247 238 230 191 151 119 87 257 251 246 204 159 123 86.7 kW 11.5 11.6 11.7 12 12.4 12.7 13 11.7 11.8 11.8 12.1 12.5 12.8 13.1 11.9 11.9 11.9 12.2 12.6 12.9 13.1
70 TC 231 237 242 261 282 300 316 242 246 250 268 289 305 323 252 254 256 273 293 310 326 SHC 231 220 209 175 141 113 84.5 242 234 227 189 149 117 84.9 252 247 243 201 156 120 84.6 kW 13.1 13.2 13.3 13.6 14 14.3 14.6 13.3 13.3 13.4 13.7 14.1 14.4 14.8 13.4 13.5 13.5 13.8 14.2 14.5 14.8
75 TC 228 234 239 257 278 295 311 239 243 246 264 285 301 318 249 250 252 269 290 305 322 SHC 228 218 208 174 139 112 83.1 239 232 225 187 147 115 83.6 249 245 241 199 155 119 83.5 kW 13.9 14 14.1 14.5 14.9 15.2 15.6 14.1 14.2 14.2 14.6 15 15.3 15.7 14.3 14.3 14.4 14.7 15.1 15.4 15.8
85 TC 223 227 231 250 270 287 303 234 236 238 256 277 292 310 243 244 245 261 282 296 314 SHC 223 213 204 171 136 109 80.5 234 227 221 184 144 112 80.9 243 240 236 196 152 116 81.3 kW 15.6 15.7 15.8 16.2 16.6 17.1 17.4 15.8 15.9 15.9 16.3 16.8 17.2 17.6 16 16.1 16.1 16.5 16.9 17.3 17.7
95 TC 216 219 223 241 260 277 292 226 228 230 247 267 282 298 235 235 236 251 272 285 303 SHC 216 208 200 167 132 105 77.2 226 221 217 180 141 109 77.7 235 233 231 192 148 112 78 kW 17.4 17.5 17.6 18.1 18.6 19 19.4 17.7 17.7 17.8 18.2 18.7 19.1 19.6 17.9 17.9 17.9 18.3 18.9 19.2 19.7
105 TC 208 211 214 231 249 265 279 218 219 220 236 256 270 285 226 226 226 241 260 273 290 SHC 208 202 195 163 129 101 73.6 218 215 212 176 137 105 74 226 226 225 188 145 108 74.4 kW 19.3 19.4 19.5 20 20.6 21 21.5 19.6 19.6 19.7 20.2 20.8 21.2 21.6 19.9 19.9 19.9 20.3 20.9 21.3 21.8
115 TC 200 202 204 220 237 253 266 209 210 210 225 243 257 271 217 217 217 229 248 260 275 SHC 200 195 190 158 124 97.2 69.5 209 207 206 171 132 101 70 217 217 217 183 140 104 70.4 kW 21.3 21.4 21.5 22 22.7 23.2 23.6 21.7 21.7 21.7 22.2 22.9 23.3 23.8 21.9 21.9 21.9 22.4 23 23.4 23.9
125 TC 191 192 193 208 224 239 251 199 199 200 212 230 243 255 207 207 206 216 232 245 257 SHC 191 188 185 153 120 92.8 65.3 199 199 199 166 128 96.4 65.7 207 207 206 178 135 99.8 65.5 kW 23.5 23.5 23.6 24.2 24.8 25.4 25.9 23.8 23.8 23.8 24.4 25 25.5 26 24.1 24.1 24.1 24.5 25.1 25.7 26.1
581A240 (20 Tons) (cont)
Evap Air — Cfm/BF 9,000/0.06 10,000/0.07 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 265 266 267 284 305 321 338 272 272 272 287 307 325 340 SHC 265 262 260 216 166 126 87 272 271 271 227 173 130 86.7 kW 12.3 12.7 12.9 13.2 12.1 12.1 12.1 12.4 12.7 13 13.3
70 TC 260 261 261 277 298 315 331 266 267 267 281 301 317 333 SHC 260 258 256 213 164 124 85 266 267 267 225 171 127 84.7 kW 13.6 13.6 13.6 13.9 14.3 14.6 14.9 13.7 13.7 13.7 14 14.3 14.6 15
75 TC 256 257 258 273 294 310 326 263 263 263 277 296 312 327 SHC 256 255 254 211 162 123 83.7 263 263 263 223 169 126 83.4 kW 14.5 14.5 14.5 14.8 15.2 15.5 15.8 14.6 14.6 14.6 14.9 15.2 15.6 15.9
85 TC 250 250 250 265 285 301 316 257 256 256 268 287 303 317 SHC 250 250 249 208 159 120 81 257 256 256 220 166 123 80.7 kW 16.2 16.2 16.2 16.5 17 17.4 17.7 16.4 16.4 16.4 16.6 17 17.4 17.7
95 TC 242 242 242 255 274 288 304 248 248 248 258 276 292 306 SHC 242 242 242 204 155 116 77.8 248 248 248 215 162 120 77.6 kW 18.1 18.1 18.1 18.4 18.9 19.3 19.7 18.3 18.3 18.2 18.5 19 19.4 19.7
105 TC 233 233 233 244 263 275 291 239 239 239 247 264 279 291 SHC 233 233 233 200 152 112 74.2 239 239 239 211 158 116 73.9 kW 20.1 20.1 20.1 20.4 21 21.4 21.8 20.3 20.2 20.2 20.5 21 21.5 21.8
115 TC 223 223 223 232 250 262 276 229 228 228 235 251 263 276 SHC 223 223 223 195 147 108 70.2 229 228 228 206 154 111 69.9 kW 22.2 22.1 22.1 22.5 23.1 23.5 24 22.3 22.3 22.3 22.6 23.1 23.6 24
125 TC 213 212 212 219 234 247 258 218 217 217 222 235 248 259 SHC 213 212 212 189 142 103 65.4 218 217 217 200 148 106 65.2 kW 24.3 24.3 24.3 24.6 25.2 25.7 26.2 24.5 24.5 24.5 24.7 25.3 25.8 26.2
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80). 4. Use chart below for bypass factor.
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
ENTERING WET-BULB (F) 54 58 62 67 72 76 80 Bypass Factor 6,000 0.386 0.197 0.108 0.109 0.134 0.000 0.000 7,000 0.444 0.260 0.131 0.121 0.138 0.000 0.000 8,000 0.492 0.321 0.163 0.133 0.145 0.000 0.000 9,000 0.532 0.375 0.205 0.146 0.154 0.000 0.000 10,000 0.566 0.420 0.245 0.158 0.164 0.000 0.000
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Evap Air — Cfm/BF 7,500/0.05 8,250/0.06 9,500/0.07 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 287 296 304 331 359 385 408 297 304 310 336 367 390 414 311 315 319 345 375 398 421 SHC 287 274 261 220 178 145 110 297 285 273 229 185 148 110 311 303 294 246 194 152 111 kW 15.5 15.7 15.9 16.5 17.3 17.9 18.6 15.7 15.9 16 16.7 17.4 18.1 18.7 16 16.1 16.2 16.9 17.6 18.3 19
70 TC 279 286 293 318 345 367 392 288 293 298 323 350 372 397 301 303 306 329 357 381 403 SHC 279 267 255 214 173 139 105 288 278 268 224 178 142 105 301 294 287 239 188 147 105 kW 17 17.2 17.3 18 18.7 19.3 20 17.2 17.3 17.5 18.1 18.8 19.4 20.1 17.5 17.6 17.7 18.3 19 19.7 20.3
75 TC 275 281 287 311 338 360 383 283 288 293 316 343 365 388 296 298 300 323 349 372 394 SHC 275 264 252 212 170 136 102 283 274 265 221 176 139 103 296 290 284 237 185 144 103 kW 17.9 18.1 18.2 18.8 19.5 20.1 20.8 18.1 18.2 18.4 18.9 19.7 20.3 20.9 18.4 18.5 18.5 19.1 19.8 20.5 21.1
85 TC 267 272 277 299 324 345 366 274 278 282 304 329 350 370 286 287 289 311 334 355 375 SHC 267 257 247 207 165 131 97.3 274 267 259 216 171 134 97.3 286 282 278 232 180 139 97.3 kW 19.8 19.9 20 20.6 21.2 21.8 22.4 20 20.1 20.1 20.7 21.4 22 22.6 20.2 20.3 20.3 20.9 21.5 22.1 22.7
95 TC 259 263 267 288 311 331 350 267 270 273 293 315 335 354 278 279 281 299 322 340 358 SHC 259 251 242 202 160 126 92.5 267 261 255 212 166 129 92.5 278 276 273 227 175 134 92.4 kW 22.1 22.2 22.3 22.8 23.4 23.9 24.5 22.3 22.4 22.5 22.9 23.5 24 24.6 22.6 22.6 22.6 23.1 23.6 24.2 24.7
105 TC 253 256 260 279 301 318 335 260 262 264 282 304 322 338 269 270 270 287 308 326 342 SHC 253 246 239 198 156 122 87.9 260 255 250 207 162 125 87.8 269 268 267 222 171 129 87.7 kW 24.9 25 25.1 25.4 25.9 26.4 26.9 25.1 25.1 25.1 25.5 26 26.5 26.9 25.2 25.2 25.2 25.6 26.1 26.6 27.1
115 TC 246 249 252 270 291 305 320 253 255 256 274 294 309 323 262 262 262 277 298 312 328 SHC 246 240 235 195 152 118 83.5 253 250 246 204 158 121 83.4 262 261 261 218 167 125 83.9 kW 28.1 28.2 28.3 28.6 29 29.3 29.6 28.3 28.3 28.3 28.6 29 29.4 29.7 28.4 28.4 28.4 28.7 29.1 29.4 29.9
125 TC 238 240 242 259 279 293 305 245 246 246 262 281 295 310 253 253 253 266 284 298 313 SHC 238 234 230 190 148 114 79.2 245 243 240 199 153 116 79.7 253 253 253 214 162 120 79.9 kW 31.6 31.7 31.7 32 32.4 32.6 32.9 31.8 31.8 31.8 32.1 32.4 32.7 33 31.9 31.9 31.9 32.1 32.5 32.7 33.1
581A300 (25 Tons) (cont)
Evap Air — Cfm/BF 10,750/0.08 12,000/0.09 Evap Air — Ewb (F) 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60 TC 322 324 327 351 380 404 429 332 333 334 357 386 410 432 SHC 322 317 313 260 203 157 111 332 330 329 276 212 162 111 kW 16.3 16.4 16.4 17 17.8 18.5 19.2 16.6 16.6 16.6 17.2 18 18.6 19.2
70 TC 311 312 314 336 364 386 408 320 320 321 341 368 392 414 SHC 311 308 305 255 198 151 105 320 320 319 269 206 156 106 kW 17.8 17.8 17.9 18.4 19.2 19.8 20.5 18.5 19.3 20 20.6
75 TC 306 307 308 329 356 378 398 315 315 315 333 360 383 404 SHC 306 304 302 252 195 149 103 315 314 314 266 203 153 103 kW 18.7 18.7 18.7 19.3 20 20.6 21.3 18.9 18.9 18.9 19.4 20.1 20.8 21.4
85 TC 295 296 297 315 340 362 379 303 303 303 319 344 365 385 SHC 295 295 294 246 189 144 97.3 303 303 303 260 198 148 97.9 kW 20.5 20.5 20.5 21 21.7 22.3 22.8 20.7 20.7 20.7 21.1 21.8 22.4 23
95 TC 286 286 286 303 327 344 364 293 293 294 307 330 347 366 SHC 286 286 286 241 185 138 93 293 293 294 255 193 142 92.8 kW 22.7 22.7 22.7 23.1 23.8 24.3 24.9 22.9 22.9 22.9 23.2 23.9 24.4 24.9
105 TC 277 277 277 290 312 329 347 284 284 285 295 314 331 352 SHC 277 277 277 236 179 133 88.3 284 284 285 250 188 137 88.7 kW 25.4 25.4 25.4 25.7 26.2 26.7 27.2 25.5 25.6 25.6 25.8 26.3 26.7 27.3
115 TC 268 269 269 281 300 315 332 274 274 275 283 303 317 333 SHC 268 269 269 232 176 129 84.4 274 274 275 245 184 133 84 kW 28.5 28.5 28.5 28.7 29.2 29.5 30 28.6 28.6 28.6 28.8 29.2 29.5 30
125 TC 260 259 259 269 287 300 316 265 265 264 271 289 302 318 SHC 260 259 259 227 171 125 80 265 265 264 240 179 129 80.1 kW 32.1 32.5 32.8 33.2 32.1 32.1 32.1 32.2 32.5 32.8 33.3
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
581A155, 180
NOTES:
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80). 4. Use chart below for bypass factor.
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
ENTERING WET-BULB (F) 54 58 62 67 72 76 80 Bypass Factor 7,500 0.407 0.208 0.097 0.104 0.123 0.000 0.000 8,250 0.443 0.256 0.110 0.112 0.128 0.000 0.000 9,500 0.494 0.324 0.138 0.123 0.136 0.000 0.000 10,750 0.536 0.380 0.181 0.134 0.145 0.000 0.000 12,000 0.571 0.427 0.232 0.145 0.154 0.000 0.000
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Air Entering Evaporator — Cfm/BF 4500/0.02 5250/0.03 6000/0.04 6750/0.04 7500/0.05 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
Temp (F) Air Entering
75 TC 166 179 193 214 175 186 202 221 183 191 208 227 190 195 212 232 197 199 216 236 SHC 165 152 129 108 175 166 140 115 183 178 150 121 190 189 159 127 197 196 168 133 kW 10.4 10.6 10.7 10.9 10.5 10.6 10.8 11.0 10.6 10.7 10.9 11.1 10.7 10.7 10.9 11.2 10.8 10.8 11.0 11.2
85 TC 162 174 189 209 171 180 195 216 179 185 200 222 186 189 205 226 192 194 208 230 SHC 162 150 127 106 171 163 137 113 179 175 147 119 186 185 156 125 192 192 164 131 kW 11.7 11.9 12.1 12.3 11.8 12.0 12.1 12.4 11.9 12.0 12.2 12.5 12.0 12.1 12.3 12.5 12.1 12.1 12.3 12.6
95 TC 158 169 182 202 166 174 187 209 174 179 194 214 181 183 198 218 187 188 201 221 SHC 158 148 126 104 166 160 134 110 174 172 145 116 181 180 154 122 187 187 163 128 kW 12.7 12.9 13.1 13.3 12.9 13.0 13.2 13.4 13.0 13.0 13.2 13.5 13.1 13.1 13.3 13.6 13.1 13.2 13.4 13.6
105 TC 153 163 178 195 162 168 181 201 169 172 188 206 175 177 191 209 181 181 194 213 SHC 153 145 123 101 162 157 133 107 169 167 142 113 175 175 151 119 181 181 160 125 kW 14.1 14.2 14.4 14.7 14.2 14.3 14.5 14.8 14.3 14.3 14.6 14.8 14.4 14.4 14.6 14.9 14.5 14.5 14.7 14.9
115 TC 148 156 171 188 157 161 176 193 163 165 180 197 169 170 183 201 174 175 185 203 SHC 148 141 120 98 157 153 130 104 163 162 139 110 169 169 148 116 174 174 156 122 kW 15.5 15.6 15.8 16.1 15.6 15.7 15.9 16.2 15.7 15.8 16.0 16.3 15.8 15.8 16.1 16.3 15.9 15.9 16.1 16.4
125 TC 143 149 163 179 151 153 168 184 157 158 171 188 163 163 174 190 167 167 176 192 SHC 143 138 117 95 151 149 126 101 157 156 136 107 163 163 144 112 167 167 153 118 kW 17.0 17.1 17.4 17.7 17.2 17.2 17.5 17.8 17.3 17.3 17.6 17.8 17.4 17.4 17.6 17.9 17.5 17.5 17.6 17.9
581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF
Evaporator Air Quantity — Cfm/BF 4500/0.12 5250/0.14 6000/.015 6750/0.18 7500/0.18 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
Temp (F) Air Entering
65 TC 55 57 59 56 58 59 56 58 60 57 59 60 57 59 61 SHC 34 32 30 36 34 32 37 35 33 38 36 35 40 38 36 kW 4.4 4.5 4.5 4.4 4.5 4.5 4.4 4.5 4.5 4.4 4.5 4.5 4.4 4.5 4.5
75 TC 42 44 45 43 44 46 43 45 46 43 45 46 44 45 47 SHC 22 19 17 23 21 18 25 22 20 26 24 21 28 25 23 kW 4.8
85 TC 29 30 31 29 31 32 30 31 32 30 32 33 31 32 33 SHC 9 6 3 11 8 5 13 10 7 14 11 8 16 12 9 kW 5.2 5.2 5.3 5.2 5.2 5.3 5.2 5.2 5.3 5.2 5.2 5.3 5.2 5.2 5.3
95 TC 15 16 17 16 17 18 16 18 18 17 18 19 17 18 19 SHC –3 –7 –11 –1 –5 –9 1 –3 –7 2 –2 –5 4 0 –4 kW 5.6
581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF
Evaporator Air Quantity — Cfm/BF 4500/0.12 5250/0.14 6000/.015 6750/0.18 7500/0.18 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
Temp (F) Air Entering
65 TC 81 84 86 82 85 87 83 86 88 84 87 89 85 87 90 SHC 34 32 30 36 33 31 37 35 33 39 36 34 40 38 36 kW 7.8 7.9 7.9 7.8 7.9 7.9 7.8 7.9 7.9 7.8 7.9 7.9 7.8 7.9 7.9
75 TC 62 64 66 62 65 67 63 66 68 64 66 68 64 67 69 SHC 22 19 16 24 21 18 25 22 20 27 24 21 28 25 22 kW 8.5
85 TC 42 44 46 43 45 46 43 45 47 44 46 48 44 46 48 SHC 10 6 2 12 8 4 14 10 6 15 11 8 16 13 9 kW 9.2 9.2 9.3 9.2 9.2 9.3 9.2 9.2 9.3 9.2 9.2 9.3 9.2 9.2 9.3
95 TC 23 24 26 23 25 26 24 25 27 24 26 27 24 26 27 SHC –2 –7 –11 0 –5 –9 2 –3 –7 3 –1 –6 5 0 –4 kW 9.9
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use for-
.10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 4500/0.12 5250/0.14 6000/.015 6750/0.18 7500/0.18 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 133 140 146 134 141 147 135 142 148 136 143 149 137 144 150 SHC 73 69 65 75 71 67 77 73 69 79 75 71 81 76 72 kW 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8
75 TC 116 123 128 117 123 129 117 124 130 118 125 131 118 126 132 SHC 61 55 50 63 57 52 65 59 54 66 61 56 68 62 57 kW 11.8
85 TC 98 105 111 99 106 112 99 106 112 100 107 113 100 107 113 SHC 48 41 35 50 43 37 52 45 39 54 46 40 55 48 42 kW 12.9 13.0 13.0 12.9 13.0 13.0 12.9 13.0 13.0 12.9 13.0 13.0 12.9 13.0 13.0
95 TC 81 88 94 81 88 94 81 88 95 81 89 95 81 89 95 SHC 36 28 21 38 29 22 39 31 24 41 32 25 42 34 26 kW 14.0 14.1 14.1 14.0 14.1 14.1 14.0 14.1 14.1 14.0 14.1 14.1 14.0 14.1 14.1
581A210 (18 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Air Entering Evaporator — Cfm/BF 5400/0.03 6300/0.04 7200/0.05 8100/0.06 9000/0.07 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
Temp (F) Air Entering
75 TC 183 198 215 236 192 206 224 245 201 212 230 252 210 216 235 257 217 222 240 262 SHC 182 169 143 120 192 184 156 127 201 197 166 134 210 209 177 141 217 218 186 147 kW 11.5 11.7 11.9 12.2 11.6 11.8 12.1 12.4 11.7 11.9 12.2 12.5 11.9 11.9 12.2 12.5 12.0 12.0 12.3 12.6
85 TC 179 192 210 231 188 200 217 239 197 205 223 244 205 210 227 249 212 215 232 254 SHC 179 166 142 117 188 181 153 125 197 194 163 131 205 206 173 138 212 213 183 145 kW 12.8 13.1 13.3 13.7 13.0 13.2 13.5 13.8 13.2 13.3 13.6 13.9 13.3 13.4 13.7 14.0 13.4 13.5 13.7 14.1
95 TC 175 186 202 223 184 193 209 229 193 198 215 236 200 203 219 241 206 208 223 245 SHC 175 163 142 114 184 177 151 121 193 191 160 128 200 200 170 135 206 207 180 142 kW 14.1 14.3 14.6 14.9 14.3 14.4 14.7 15.1 14.4 14.5 14.8 15.2 14.6 14.6 14.9 15.3 14.7 14.7 15.0 15.4
105 TC 170 180 197 215 179 186 201 222 187 192 208 226 194 197 212 230 200 202 215 235 SHC 170 160 136 111 179 174 147 118 187 186 158 125 194 195 168 131 200 201 178 138 kW 15.6 15.8 16.1 16.5 15.8 15.9 16.2 16.6 15.9 16.0 16.3 16.7 16.1 16.1 16.4 16.8 16.2 16.2 16.5 16.9
115 TC 165 173 189 208 173 179 195 214 181 184 199 218 187 189 203 222 193 194 205 225 SHC 165 157 133 109 173 170 144 116 181 181 154 122 187 188 164 128 193 194 173 134 kW 17.2 17.4 17.7 18.1 17.4 17.5 17.8 18.2 17.5 17.6 17.9 18.3 17.7 17.7 18.0 18.4 17.8 17.9 18.1 18.5
125 TC 159 166 181 199 167 171 186 203 174 177 190 207 180 182 193 210 186 187 196 213 SHC 159 154 130 105 167 166 140 112 174 175 151 118 180 181 160 124 186 187 170 130 kW 18.9 19.1 19.5 19.9 19.1 19.2 19.6 20.0 19.3 19.4 19.7 20.1 19.5 19.5 19.8 20.1 19.6 19.6 19.8 20.2
581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 5400/0.03 6300/0.04 7200/0.05 8100/0.06 9000/0.07 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 61 63 65 62 64 66 63 65 66 63 65 67 64 66 68 SHC 38 35 34 40 37 35 41 39 37 43 41 39 44 42 40 kW 5.0
75 TC 47 48 50 47 49 51 48 50 51 48 50 52 49 51 52 SHC 24 21 18 26 23 20 28 25 22 29 26 24 31 28 25 kW 5.4
85 TC 32 33 35 32 34 35 33 34 36 33 35 36 34 35 37 SHC 11 7 3 13 9 5 14 11 7 16 12 9 17 14 10 kW 5.9
95 TC 17 18 19 18 19 20 18 19 20 19 20 21 19 20 21 SHC –3 –8 –12 –1 –6 –10 1 –4 –8 3 –2 –6 4 0 –4 kW 6.3
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross
ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
(BF)
NOTES:
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm

581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 5400/0.03 6300/0.04 7200/0.05 8100/0.06 9000/0.07 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 90 93 95 91 94 97 92 95 98 93 96 99 94 97 100 SHC 38 35 33 40 37 35 41 39 37 43 40 38 44 42 40 kW 8.8
75 TC 68 71 73 69 72 74 70 73 75 71 74 76 72 74 77 SHC 24 21 18 26 23 20 28 25 22 30 26 23 31 28 25 kW 9.6
85 TC 47 49 51 47 50 52 48 50 52 49 51 53 49 51 53 SHC 11 7 3 13 9 5 15 11 7 17 12 9 18 14 10 kW 10.3
95 TC 25 27 29 26 27 29 26 28 29 26 28 30 27 29 30 SHC –2 –8 –12 0 –5 –10 2 –-3 –8 3 –2 –6 5 0 –5 kW 11.1
581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 5400/0.03 6300/0.04 7200/0.05 8100/0.06 9000/0.07 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 147 155 162 148 157 164 150 158 165 151 160 167 152 161 168 SHC 81 76 72 84 79 75 86 81 77 88 83 79 90 85 80 kW 11.9 12.0 12.0 11.9 12.0 12.0 11.9 12.0 12.0 11.9 12.0 12.0 11.9 12.0 12.0
75 TC 128 136 143 129 137 144 130 138 146 131 139 147 132 140 148 SHC 67 61 56 70 63 58 72 65 60 74 67 62 76 69 63 kW 13.2
85 TC 108 117 124 109 118 125 110 118 126 110 119 127 111 120 127 SHC 54 46 39 56 48 41 58 50 43 60 52 45 61 53 46 kW 14.5
95 TC 89 98 105 89 98 106 89 98 106 90 99 107 90 99 107 SHC 40 31 23 42 33 25 44 34 26 45 36 28 47 37 29 kW 15.8 15.7 15.7 15.8 15.7 15.7 15.8 15.7 15.7 15.8 15.7 15.7 15.8 15.7 15.7
581A240 (20 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Air Entering Evaporator — Cfm/BF 6000/0.04 7000/0.05 8000/0.06 9000/0.07 10,000/0.08 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
Temp (F) Air Entering
75 TC 216 234 255 279 226 243 265 290 237 251 273 298 247 256 279 305 256 263 284 310 SHC 213 199 171 141 225 217 185 151 237 232 198 159 247 241 211 168 256 251 223 176 kW 13.9 14.2 14.6 15.0 14.0 14.4 14.8 15.3 14.3 14.5 15.0 15.4 14.5 14.6 15.1 15.6 14.6 14.8 15.2 15.7
85 TC 211 227 249 272 221 237 258 282 232 243 265 287 242 250 270 293 250 255 275 300 SHC 209 194 168 141 221 214 182 148 232 228 195 155 242 237 206 163 250 244 220 173 kW 15.4 15.8 16.2 16.7 15.7 16.0 16.4 16.9 15.9 16.1 16.6 17.1 16.1 16.3 16.7 17.2 16.3 16.4 16.8 17.4
95 TC 207 220 240 262 217 228 250 269 228 235 254 278 236 241 259 286 243 247 264 290 SHC 205 192 164 134 217 209 179 142 228 222 190 152 236 230 202 161 243 236 214 169 kW 17.2 17.5 17.9 18.4 17.4 17.7 18.2 18.6 17.7 17.9 18.3 18.8 17.9 18.0 18.4 19.0 18.1 18.2 18.6 19.1
105 TC 201 214 232 253 211 221 238 261 221 228 247 266 229 234 251 271 236 239 255 278 SHC 197 190 161 131 211 206 172 140 221 216 188 146 229 223 200 155 236 229 212 165 kW 19.0 19.3 19.8 20.3 19.3 19.5 20.0 20.6 19.5 19.7 20.2 20.7 19.8 19.9 20.3 20.8 20.0 20.0 20.4 21.0
115 TC 195 206 224 245 205 213 230 252 214 219 236 258 221 225 240 262 228 231 243 265 SHC 191 185 158 129 205 201 171 137 214 209 183 145 221 215 194 152 228 221 207 160 kW 21.0 21.3 21.8 22.4 21.3 21.5 22.0 22.7 21.6 21.7 22.2 22.8 21.8 21.9 22.3 22.9 22.0 22.1 22.4 23.0
125 TC 189 198 215 235 198 204 221 239 207 210 225 244 214 216 229 248 220 222 232 251 SHC 184 179 154 125 198 194 167 132 207 201 179 139 214 207 191 147 220 212 202 154 kW 23.1 23.4 24.0 24.7 23.5 23.7 24.2 24.8 23.8 23.9 24.4 25.0 24.0 24.1 24.5 25.1 24.2 24.3 24.6 25.2
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm

581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 6000/0.04 7000/0.05 8000/0.06 9000/0.07 10,000/0.08 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 73 75 77 73 76 78 74 76 79 75 77 79 75 78 80 SHC 45 42 40 47 44 42 49 47 44 51 48 46 53 50 48 kW 6.1
75 TC 55 57 59 56 58 60 56 58 60 57 59 61 57 59 61 SHC 29 25 22 31 27 24 33 30 26 35 31 28 37 33 30 kW 6.6
85 TC 38 40 41 38 40 42 39 40 42 39 41 42 39 41 43 SHC 13 8 4 15 10 7 17 13 9 19 14 10 21 16 12 kW 7.2
95 TC 20 22 23 21 22 24 21 22 24 21 23 24 21 23 24 SHC –4 –9 –14 –1 –7 –11 1 –4 –9 3 –3 –7 5 –1 –6 kW 7.7
581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF
Evaporator Air Quantity — Cfm/BF 6000/0.04 7000/0.05 8000/0.06 9000/0.07 10,000/0.08 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
Temp (F) Air Entering
65 TC 106 110 113 108 111 114 109 113 116 110 114 117 111 115 118 SHC 45 42 39 47 44 41 49 46 44 51 48 46 53 50 47 kW 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8 10.7 10.7 10.8
75 TC 81 84 87 82 85 88 83 86 89 83 87 89 84 87 90 SHC 29 25 21 31 27 24 34 29 26 36 31 28 37 33 30 kW 11.6
85 TC 56 58 61 56 59 61 56 59 61 57 59 62 57 60 62 SHC 13 8 3 16 10 6 18 13 8 20 15 10 22 16 12 kW 12.6 12.7 12.7 12.6 12.7 12.7 12.6 12.7 12.7 12.6 12.7 12.7 12.6 12.7 12.7
95 TC 30 33 34 30 32 34 30 32 34 30 32 34 30 32 34 SHC –3 –9 –14 0 –6 –12 2 –4 –10 4 –2 –8 6 0 –6 kW 13.6
581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON
Evaporator Air Quantity — Cfm/BF 6000/0.04 7000/0.05 8000/0.06 9000/0.07 10,000/0.08 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
Temp (F) Air Entering
65 TC 177 185 191 177 185 192 178 186 192 178 186 193 178 186 193 SHC 98 92 86 100 94 88 101 95 90 103 97 92 104 98 93 kW 14.5 14.6 14.7 14.5 14.6 14.7 14.5 14.6 14.7 14.5 14.6 14.7 14.5 14.6 14.7
75 TC 154 161 168 154 162 169 155 162 169 155 163 169 155 163 170 SHC 81 73 66 83 75 69 85 78 71 87 80 73 89 81 75 kW 16.1
85 TC 131 138 145 131 139 145 131 139 146 132 139 146 132 140 146 SHC 63 54 46 66 57 49 69 60 52 71 62 54 73 64 56 kW 17.7 17.7 17.8 17.7 17.7 17.8 17.7 17.7 17.8 17.7 17.7 17.8 17.7 17.7 17.8
95 TC 107 115 122 108 115 122 108 116 122 108 116 123 109 116 123 SHC 46 35 25 50 39 29 53 42 32 55 45 35 58 47 38 kW 19.3
Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
rator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Temp (F) Air Entering
Air Entering Evaporator — Cfm/BF 7000/0.042 8250/0.052 9500/0.062 10,750/0.072 12,000/0.082 Air Entering Evaporator — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72 57 62 67 72
75 TC 245 268 293 318 259 282 303 333 274 291 314 340 289 301 322 348 305 309 332 356 SHC 245 229 197 162 259 254 213 173 274 271 230 183 289 287 247 195 305 298 267 203 kW 16.4 17.0 17.6 18.2 16.7 17.4 17.9 18.6 17.1 17.6 18.2 18.8 17.5 17.8 18.4 19.0 18.0 18.1 18.6 19.2
85 TC 233 259 278 309 256 273 293 324 271 282 305 330 285 290 312 337 298 303 321 343 SHC 233 228 186 158 256 252 211 171 271 264 229 180 285 276 246 191 298 295 261 201 kW 17.9 18.7 19.3 19.9 18.5 19.1 19.7 20.4 19.0 19.4 20.0 20.8 19.3 19.6 20.2 21.1 19.8 19.9 20.4 21.3
95 TC 230 252 276 303 251 265 284 314 269 274 290 326 274 282 300 332 283 293 308 334 SHC 230 225 191 156 251 249 202 166 269 269 220 181 274 274 238 190 283 280 259 197 kW 20.0 20.8 21.4 22.1 20.7 21.2 21.5 22.4 21.3 21.4 21.9 23.0 21.5 21.7 22.1 23.2 21.6 22.0 22.5 23.3
105 TC 226 245 268 292 242 253 277 301 255 264 284 308 266 275 290 314 278 281 294 319 SHC 226 223 188 153 242 241 205 163 255 255 221 171 265 265 240 185 278 278 253 194 kW 22.0 22.8 23.3 24.3 22.7 23.1 23.7 24.7 23.1 23.4 24.0 25.0 23.6 23.7 24.3 25.2 24.0 24.1 24.4 25.4
115 TC 221 233 258 281 232 242 267 290 247 253 274 297 253 260 275 302 267 269 279 306 SHC 221 217 183 149 232 230 200 160 247 246 217 170 253 254 233 179 267 267 248 189 kW 24.3 25.1 25.7 26.7 24.8 25.4 26.1 27.1 25.3 25.8 26.4 27.2 25.8 26.0 26.5 27.3 26.1 26.3 26.7 27.4
125 TC 216 223 247 268 225 230 253 275 237 240 256 280 247 248 260 285 254 255 263 288 SHC 216 212 181 145 225 223 196 155 237 236 211 163 247 247 228 174 254 254 242 184 kW 26.9 27.1 28.0 29.0 27.4 27.5 28.3 29.4 27.8 27.9 28.5 29.6 28.2 28.3 28.7 29.8 28.5 28.6 28.9 29.9
581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B OFF
Evaporator Air Quantity — Cfm/BF 7500/0.045 8250/0.055 9500/0.065 10,750/0.075 12,000/0.085 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
Temp (F) Air Entering
65 TC 79 83 87 80 84 88 81 85 89 82 86 90 83 87 91 SHC 39 33 28 41 35 30 43 37 32 45 39 34 47 41 36 kW 11
75 TC 56 61 65 57 62 66 59 63 67 60 64 68 61 65 69 SHC 18 11 5 20 12 6 22 15 8 24 16 10 26 18 12 kW 11
85 TC 34 38 42 35 39 43 37 41 45 38 42 46 39 43 47 SHC –2 –11 –19 –1 –10 –18 1 –8 –16 3 –7 –14 4 –5 –13 kW 11 11 12 11 12
95 TC 12 16 19 13 17 21 15 19 22 16 20 24 17 22 25 SHC –23 –33 –42 –22 –32 –41 –20 –31 –40 –19 –30 –39 –17 –28 –38 kW 12
581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B ON
Temp (F) Air Entering
Evaporator Air Quantity — Cfm/BF 7500/0.045 8250/0.055 9500/0.065 10,750/0.075 12,000/0.085 Evaporator Air — Relative Humidity (%) 50 55 60 50 55 60 50 55 60 50 55 60 50 55 60
65 TC 211 222 231 215 226 235 220 232 241 226 237 247 230 242 252 SHC 123 115 109 129 121 115 139 131 124 147 139 133 155 147 140 kW 19 19 20 19 19 20 19 19 20 19 20 20 19 20 20
75 TC 182 193 202 185 196 205 189 200 210 192 204 214 196 208 218 SHC 103 93 85 110 100 91 120 110 101 128 118 110 136 126 118 kW 20 21 21 20 21
85 TC 153 164 174 155 166 176 157 169 178 159 171 181 161 173 184 SHC 84 72 62 90 78 68 100 88 78 110 97 87 118 106 95 kW 22
95 TC 124 135 145 125 136 146 125 137 147 126 138 148 127 139 149 SHC 64 50 38 71 57 45 81 67 55 91 76 64 99 85 72 kW 23 24 23 23 24 23 24 24
BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82
tldb = tedb – sensible capacity (Btuh)
1.10 x cfm
Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm

581A155 (12 TONS) WITH STANDARD MOTOR (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 597 895 0.84 692 967 1.07 781 1150 1.33 858 1342 1.59 928 1527 1.85 4000 625 1014 0.98 714 1097 1.21 800 1292 1.48 876 1495 1.75 945 1689 2.03 4250 653 1141 1.13 737 1236 1.36 820 1442 1.64 895 1656 1.93 963 1859 2.22 4500 682 1274 1.29 761 1382 1.54 840 1599 1.82 914 1824 2.11 982 2037 2.42 4750 711 1415 1.48 786 1538 1.73 861 1765 2.01 934 2001 2.32 1001 2224 2.63 5000 740 1563 1.68 812 1702 1.94 884 1940 2.22 954 2188 2.53 1020 2419 2.86 5250 769 1719 1.89 839 1875 2.16 907 2125 2.45 974 2384 2.77 1039 2625 3.10 5500 799 1884 2.13 867 2060 2.41 931 2321 2.70 996 2592 3.02 1059 2841 3.36 5750 828 2058 2.38 894 2256 2.67 956 2528 2.97 1018 2810 3.29 1080 3069 3.64 6000 857 2243 2.64 923 2464 2.96 982 2748 3.26 1041 3042 3.59 1101 3308 3.94 6250 885 2438 2.93 951 2687 3.27 1008 2981 3.58 1065 3286 3.91 1122 3559 4.26
581A155 (12 TONS) WITH STANDARD MOTOR (Low Heat Units)* (cont)
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 992 1756 2.12 1053 1988 2.40 1112 2236 2.68 1169 2497 2.97 1224 2769 3.27 4000 1009 1931 2.31 1069 2173 2.59 1126 2431 2.88 1181 2702 3.18 1234 2984 3.48 4250 1026 2114 2.51 1085 2366 2.80 1141 2634 3.10 1194 2914 3.40 1246 3206 3.72 4500 1044 2304 2.72 1102 2566 3.02 1157 2844 3.33 1209 3133 3.65 1260 3433 3.97 4750 1062 2504 2.95 1120 2775 3.26 1174 3062 3.58 1226 3360 3.91 1275 3666 4.23 5000 1081 2712 3.19 1138 2993 3.52 1191 3288 3.85 1242 3592 4.18 1291 3905 4.52 5250 1100 2931 3.44 1156 3220 3.79 1209 3523 4.13 1260 3832 4.47 1308 4148 4.82 5500 1119 3160 3.72 1175 3457 4.07 1228 3765 4.43 1278 4077 4.78 1326 4395 5.14 5750 1138 3399 4.00 1194 3702 4.37 1246 4014 4.74 1296 4328 5.11 1343 4644 5.48 6000 1158 3649 4.31 1213 3957 4.69 1265 4270 5.07 1315 4581 5.45 — — — 6250 1179 3910 4.64 1233 4219 5.02 1284 4531 5.41 —
Bhp — Brake Horsepower Watts — Input Watts to Motor
1. Field-supplied motor required. 2. Maximum continuous bhp for the standard motor is 3.13 (for 208/230 and 460-v units) or 3.38 (for 575-v units). The maximum continuous watts is 2700 (for 208/230 and 460-v units) or 3065 (for 575-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Data tables for more information. 3. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb.
*Standard low-medium static drive range is 895 to 1147 rpm. Other rpms require a field-supplied drive. Refer to page 262 for general Fan Performance Data notes.
581A155 (12 TONS) WITH OPTIONAL MOTOR (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 597 895 0.84 692 967 1.07 781 1150 1.33 858 1342 1.59 928 1527 1.85 4000 625 1014 0.98 714 1097 1.21 800 1292 1.48 876 1495 1.75 945 1689 2.03 4250 653 1141 1.13 737 1236 1.36 820 1442 1.64 895 1656 1.93 963 1859 2.22 4500 682 1274 1.29 761 1382 1.54 840 1599 1.82 914 1824 2.11 982 2037 2.42 4750 711 1415 1.48 786 1538 1.73 861 1765 2.01 934 2001 2.32 1001 2224 2.63 5000 740 1563 1.68 812 1702 1.94 884 1940 2.22 954 2188 2.53 1020 2419 2.86 5250 769 1719 1.89 839 1875 2.16 907 2125 2.45 974 2384 2.77 1039 2625 3.10 5500 799 1884 2.13 867 2060 2.41 931 2321 2.70 996 2592 3.02 1059 2841 3.36 5750 828 2058 2.38 894 2256 2.67 956 2528 2.97 1018 2810 3.29 1080 3069 3.64 6000 857 2243 2.64 923 2464 2.96 982 2748 3.26 1041 3042 3.59 1101 3308 3.94 6250 885 2438 2.93 951 2687 3.27 1008 2981 3.58 1065 3286 3.91 1122 3559 4.26
581A155 (12 TONS) WITH OPTIONAL MOTOR (Low Heat Units)* (cont)
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 992 1756 2.12 1053 1988 2.40 1112 2236 2.68 1169 2497 2.97 1224 2769 3.27 4000 1009 1931 2.31 1069 2173 2.59 1126 2431 2.88 1181 2702 3.18 1234 2984 3.48 4250 1026 2114 2.51 1085 2366 2.80 1141 2634 3.10 1194 2914 3.40 1246 3206 3.72 4500 1044 2304 2.72 1102 2566 3.02 1157 2844 3.33 1209 3133 3.65 1260 3433 3.97 4750 1062 2504 2.95 1120 2775 3.26 1174 3062 3.58 1226 3360 3.91 1275 3666 4.23 5000 1081 2712 3.19 1138 2993 3.52 1191 3288 3.85 1242 3592 4.18 1291 3905 4.52 5250 1100 2931 3.44 1156 3220 3.79 1209 3523 4.13 1260 3832 4.47 1308 4148 4.82 5500 1119 3160 3.72 1175 3457 4.07 1228 3765 4.43 1278 4077 4.78 1326 4395 5.14 5750 1138 3399 4.00 1194 3702 4.37 1246 4014 4.74 1296 4328 5.11 1343 4644 5.48 6000 1158 3649 4.31 1213 3957 4.69 1265 4270 5.07 1315 4581 5.45 — — — 6250 1179 3910 4.64 1233 4219 5.02 1284 4531 5.41 —
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Alternate high-static drive range is 1040 to 1315 (for 208/230 and 460-v units). The alternate high-static drive is not available for 575-v units. Other rpms require a field-supplied drive. Refer to page 262 for general Fan Performance Data notes.

581A155 (12 TONS) WITH STANDARD MOTOR (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 622 888 0.89 713 1027 1.13 795 1234 1.37 869 1454 1.63 936 1584 1.89 4000 652 1015 1.04 738 1168 1.28 818 1388 1.54 890 1620 1.80 956 1756 2.07 4250 682 1151 1.20 763 1317 1.45 841 1550 1.72 911 1793 1.99 976 1937 2.27 4500 713 1295 1.38 790 1474 1.63 864 1719 1.91 934 1973 2.20 997 2126 2.49 4750 744 1448 1.58 817 1641 1.84 889 1896 2.12 956 2159 2.42 1019 2326 2.72 5000 776 1610 1.80 845 1817 2.06 914 2081 2.35 979 2353 2.66 1041 2536 2.97 5250 808 1783 2.04 874 2003 2.31 940 2277 2.60 1003 2556 2.91 1064 2757 3.24 5500 840 1967 2.29 903 2200 2.57 966 2482 2.87 1028 2768 3.19 1087 2991 3.52 5750 872 2163 2.57 933 2410 2.86 993 2699 3.16 1053 2990 3.49 1110 3237 3.83 6000 905 2373 2.87 963 2634 3.16 1021 2929 3.47 1078 3225 3.81 1134 3497 4.15 6250 937 2596 3.19 994 2872 3.49 1049 3172 3.81 1105 3473 4.15 1159 3769 4.50
581A155 (12 TONS) WITH STANDARD MOTOR (High Heat Units)* (cont)
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 999 1829 2.15 1059 2091 2.42 1117 2343 2.70 1174 2521 2.99 1228 2801 3.29 4000 1017 2010 2.35 1076 2279 2.63 1132 2540 2.91 1186 2738 3.21 1239 3023 3.51 4250 1036 2198 2.56 1093 2474 2.85 1148 2743 3.14 1201 2962 3.44 1253 3251 3.75 4500 1056 2395 2.78 1112 2675 3.08 1166 2951 3.39 1217 3194 3.70 1267 3487 4.01 4750 1077 2601 3.03 1132 2885 3.34 1184 3168 3.65 1235 3435 3.97 1284 3731 4.29 5000 1098 2816 3.29 1152 3104 3.61 1204 3392 3.93 1253 3683 4.26 1301 3981 4.59 5250 1120 3042 3.56 1173 3332 3.90 1224 3626 4.23 1273 3940 4.57 1320 4239 4.91 5500 1142 3279 3.86 1195 3570 4.20 1245 3870 4.55 1293 4203 4.89 1339 4501 5.24 5750 1165 3528 4.18 1217 3819 4.53 1266 4125 4.88 1313 4471 5.24 — — — 6000 1188 3789 4.51 1239 4080 4.88 1288 4389 5.24 — 6250 1212 4062 4.87 1262 4351 5.24 —
Bhp — Brake Horsepower Watts — Input Watts to Motor
1. Field-supplied motor required. 2. Maximum continuous bhp for the standard motor is 3.13 (for 208/230 and 460-v units) or 3.38 (for 575-v units). The maximum continuous watts is 2700 (for 208/230 and 460-v units) or 3065 (for 575-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Data tables for more information. 3. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb.
*Standard low-medium static drive range is 895 to 1147 rpm. Other rpms require a field-supplied drive. Refer to page 262 for general Fan Performance Data notes.
581A155 (12 TONS) WITH OPTIONAL MOTOR (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 622 888 0.89 713 1027 1.13 795 1234 1.37 869 1454 1.63 936 1584 1.89 4000 652 1015 1.04 738 1168 1.28 818 1388 1.54 890 1620 1.80 956 1756 2.07 4250 682 1151 1.20 763 1317 1.45 841 1550 1.72 911 1793 1.99 976 1937 2.27 4500 713 1295 1.38 790 1474 1.63 864 1719 1.91 934 1973 2.20 997 2126 2.49 4750 744 1448 1.58 817 1641 1.84 889 1896 2.12 956 2159 2.42 1019 2326 2.72 5000 776 1610 1.80 845 1817 2.06 914 2081 2.35 979 2353 2.66 1041 2536 2.97 5250 808 1783 2.04 874 2003 2.31 940 2277 2.60 1003 2556 2.91 1064 2757 3.24 5500 840 1967 2.29 903 2200 2.57 966 2482 2.87 1028 2768 3.19 1087 2991 3.52 5750 872 2163 2.57 933 2410 2.86 993 2699 3.16 1053 2990 3.49 1110 3237 3.83 6000 905 2373 2.87 963 2634 3.16 1021 2929 3.47 1078 3225 3.81 1134 3497 4.15 6250 937 2596 3.19 994 2872 3.49 1049 3172 3.81 1105 3473 4.15 1159 3769 4.50
581A155 (12 TONS) WITH OPTIONAL MOTOR (High Heat Units)* (cont)
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 999 1829 2.15 1059 2091 2.42 1117 2343 2.70 1174 2521 2.99 1228 2801 3.29 4000 1017 2010 2.35 1076 2279 2.63 1132 2540 2.91 1186 2738 3.21 1239 3023 3.51 4250 1036 2198 2.56 1093 2474 2.85 1148 2743 3.14 1201 2962 3.44 1253 3251 3.75 4500 1056 2395 2.78 1112 2675 3.08 1166 2951 3.39 1217 3194 3.70 1267 3487 4.01 4750 1077 2601 3.03 1132 2885 3.34 1184 3168 3.65 1235 3435 3.97 1284 3731 4.29 5000 1098 2816 3.29 1152 3104 3.61 1204 3392 3.93 1253 3683 4.26 1301 3981 4.59 5250 1120 3042 3.56 1173 3332 3.90 1224 3626 4.23 1273 3940 4.57 1320 4239 4.91 5500 1142 3279 3.86 1195 3570 4.20 1245 3870 4.55 1293 4203 4.89 1339 4501 5.24 5750 1165 3528 4.18 1217 3819 4.53 1266 4125 4.88 1313 4471 5.24 — — — 6000 1188 3789 4.51 1239 4080 4.88 1288 4389 5.24 — 6250 1212 4062 4.87 1262 4351 5.24 —
Bhp — Brake Horsepower Watts — Input Watts to Motor
*Alternate high-static drive range is 1040 to 1315. Other rpms require a field- supplied drive. Refer to page 262 for general Fan Performance Data notes.

581A180 (15 TONS) (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 753 1307 1.53 761 1330 1.56 840 1572 1.84 912 1822 2.14 980 2080 2.44 4800 747 1384 1.62 790 1515 1.78 866 1765 2.07 936 2023 2.37 1002 2289 2.68 5100 741 1465 1.72 820 1718 2.01 893 1977 2.32 961 2243 2.63 1025 2516 2.95 5700 810 1911 2.24 882 2182 2.56 950 2459 2.88 1014 2741 3.21 1075 3029 3.55 6000 844 2164 2.54 914 2444 2.87 980 2730 3.20 1042 3021 3.54 1100 3317 3.89 6300 879 2439 2.86 947 2729 3.20 1010 3023 3.55 1070 3322 3.90 1127 3626 4.25 6600 915 2737 3.21 980 3035 3.56 1041 3338 3.91 1099 3645 4.28 1155 3957 4.64 6900 950 3057 3.59 1013 3364 3.95 1072 3675 4.31 1129 3991 4.68 1183 4311 5.06 7200 986 3401 3.99 1047 3717 4.36 1104 4037 4.74 1159 4361 5.11 1211 4689 5.50 7500 1022 3770 4.42 1081 4095 4.80 1136 4423 5.19 1189 4755 5.58 1241 5091 5.97
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1044 2345 2.75 1105 2619 3.07 1163 2899 3.40 1218 3187 3.74 1271 3481 4.08 4800 1065 2561 3.00 1124 2841 3.33 1180 3127 3.67 1235 3420 4.01 1287 3720 4.36 5100 1086 2795 3.28 1144 3082 3.61 1199 3375 3.96 1252 3674 4.31 1304 3979 4.67 5700 1132 3324 3.90 1187 3624 4.25 1240 3929 4.61 1291 4241 4.97 1341 4558 5.35 6000 1157 3619 4.24 1210 3925 4.60 1262 4239 4.97 1312 4557 5.34 1361 4880 5.72 6300 1182 3935 4.62 1234 4249 4.98 1285 4569 5.36 1334 4894 5.74 — — — 6600 1208 4274 5.01 1259 4595 5.39 1309 4922 5.77 — 6900 1235 4636 5.44 1285 4964 5.82 — 7200 1262 5021 5.89 — 7500 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1322 3781 4.43 1372 4088 4.79 1419 4400 5.16 1466 4719 5.53 1511 5042 5.91 4800 1337 4025 4.72 1386 4337 5.09 1433 4655 5.46 1479 4978 5.84 — — — 5100 1353 4290 5.03 1401 4607 5.40 1448 4930 5.78 — 5700 1388 4881 5.72 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 262 for general Fan Performance Data notes. NOTES:
Bhp — Brake Horsepower FIOP — Factory-Installed Option Watts — Input Watts to Motor
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms require a field- supplied drive.

581A180 (15 TONS) (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 753 1307 1.53 786 1404 1.65 861 1644 1.93 932 1893 2.22 997 2150 2.52 4800 747 1384 1.62 818 1603 1.88 890 1852 2.17 958 2108 2.47 1022 2373 2.78 5100 775 1571 1.84 850 1822 2.14 920 2079 2.44 986 2344 2.75 1048 2616 3.07 5700 849 2054 2.41 918 2323 2.73 982 2598 3.05 1044 2879 3.38 1102 3166 3.71 6000 886 2329 2.73 952 2607 3.06 1015 2891 3.39 1074 3180 3.73 1130 3474 4.08 6300 924 2628 3.08 987 2915 3.42 1047 3207 3.76 1105 3504 4.11 1160 3807 4.46 6600 962 2951 3.46 1023 3246 3.81 1081 3547 4.16 1136 3853 4.52 1190 4163 4.88 6900 1000 3298 3.87 1059 3603 4.23 1115 3912 4.59 1168 4225 4.96 1220 4543 5.33 7200 1038 3672 4.31 1095 3986 4.67 1149 4303 5.05 1201 4625 5.42 1251 4950 5.81 7500 1077 4072 4.78 1131 4394 5.15 1184 4720 5.54 1234 5050 5.92 — — —
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1060 2414 2.83 1119 2685 3.15 1175 2964 3.48 1230 3250 3.81 1282 3542 4.15 4800 1082 2644 3.10 1140 2922 3.43 1195 3207 3.76 1248 3498 4.10 1299 3795 4.45 5100 1106 2894 3.39 1163 3178 3.73 1216 3470 4.07 1268 3767 4.42 1319 4071 4.77 5700 1157 3459 4.06 1211 3757 4.41 1262 4061 4.76 1312 4371 5.13 1360 4686 5.50 6000 1184 3774 4.43 1236 4080 4.79 1287 4391 5.15 1335 4707 5.52 1382 5029 5.90 6300 1212 4114 4.83 1263 4427 5.19 1312 4745 5.57 1359 5067 5.94 — — — 6600 1241 4478 5.25 1290 4798 5.63 1338 5122 6.01 — 6900 1270 4866 5.71 — 7200 — 7500 —
Available External Static Pressure (in. wg) 2.2 2.4 2.6 2.8 3.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1332 3841 4.50 1381 4145 4.86 1428 4456 5.23 1473 4772 5.60 1518 5095 5.98 4800 1349 4100 4.81 1397 4409 5.17 1443 4725 5.54 1488 5046 5.92 — — — 5100 1367 4380 5.14 1414 4695 5.51 1460 5016 5.88 — 5700 1407 5007 5.87 — 6000 — 6300 — 6600 — 6900 — 7200 — 7500 —
Refer to page 262 for general Fan Performance Data notes. NOTES:
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms require a field- supplied drive.

581A210 (18 TONS) (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 460 591 0.68 548 774 0.89 623 951 1.09 692 1126 1.29 755 1301 1.50 4000 499 774 0.89 581 976 1.12 653 1170 1.35 717 1361 1.56 777 1551 1.78 4500 538 990 1.14 617 1212 1.39 685 1423 1.64 746 1630 1.88 803 1835 2.11 5000 579 1243 1.43 654 1485 1.71 719 1715 1.97 778 1938 2.23 832 2158 2.48 5500 621 1536 1.77 693 1798 2.07 755 2045 2.35 811 2285 2.63 864 2520 2.90 6000 664 1871 2.15 732 2152 2.48 792 2417 2.78 846 2673 3.07 897 2925 3.36 6500 707 2250 2.59 772 2550 2.93 830 2834 3.26 883 3106 3.57 932 3373 3.88 7000 751 2676 3.08 813 2994 3.44 869 3295 3.79 920 3585 4.12 967 3868 4.45 7500 795 3150 3.62 855 3487 4.01 909 3805 4.38 958 4112 4.73 1004 4411 5.07 8000 839 3676 4.23 897 4029 4.63 949 4366 5.02 997 4689 5.39 1042 5004 5.75 8500 884 4253 4.89 940 4625 5.32 990 4978 5.73 1037 5318 6.12 1080 5649 6.50
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 814 1476 1.70 871 1650 1.90 924 1825 2.10 975 1999 2.30 1023 2173 2.50 4000 834 1740 2.00 888 1930 2.22 939 2119 2.44 988 2308 2.65 1035 2497 2.87 4500 857 2039 2.35 909 2243 2.58 958 2446 2.81 1005 2650 3.05 1051 2853 3.28 5000 884 2376 2.73 933 2594 2.98 980 2811 3.23 1026 3028 3.48 1070 3244 3.73 5500 913 2753 3.17 960 2984 3.43 1006 3215 3.70 1049 3445 3.96 1092 3674 4.23 6000 945 3172 3.65 990 3417 3.93 1034 3662 4.21 1076 3905 4.49 1117 4147 4.77 6500 978 3636 4.18 1022 3895 4.48 1064 4153 4.78 1104 4409 5.07 1144 4665 5.37 7000 1012 4145 4.77 1055 4419 5.08 1095 4691 5.39 1135 4960 5.70 1173 5229 6.01 7500 1047 4703 5.41 1089 4992 5.74 1128 5277 6.07 1167 5561 6.40 1204 5842 6.72 8000 1084 5311 6.11 1124 5615 6.46 1163 5915 6.80 1200 6211 7.14 1236 6506 7.48 8500 1121 5972 6.87 1160 6290 7.23 1198 6604 7.60 1234 6914 7.95 1269 7223 8.31
Refer to page 262 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v) High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v) All other rpms require field-supplied drive.

581A210 (18 TONS) (Medium Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 470 611 0.70 556 791 0.91 630 967 1.11 697 1141 1.31 760 1314 1.51 4000 511 802 0.92 591 1001 1.15 661 1194 1.37 725 1383 1.59 784 1572 1.81 4500 553 1029 1.18 629 1248 1.44 695 1458 1.68 756 1663 1.91 812 1866 2.15 5000 597 1297 1.49 669 1534 1.76 732 1761 2.03 789 1982 2.28 843 2201 2.53 5500 641 1606 1.85 709 1862 2.14 770 2106 2.42 825 2343 2.70 876 2577 2.96 6000 686 1961 2.26 751 2234 2.57 809 2495 2.87 862 2749 3.16 911 2997 3.45 6500 732 2363 2.72 794 2653 3.05 849 2931 3.37 900 3201 3.68 948 3465 3.99 7000 779 2815 3.24 837 3122 3.59 891 3416 3.93 940 3702 4.26 986 3981 4.58 7500 826 3320 3.82 882 3642 4.19 933 3953 4.55 980 4254 4.89 1025 4549 5.23 8000 873 3879 4.46 926 4217 4.85 975 4542 5.22 1021 4860 5.59 1065 5169 5.95 8500 921 4495 5.17 972 4847 5.57 1019 5189 5.97 1063 5521 6.35 1105 5846 6.72
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 818 1488 1.71 874 1661 1.91 927 1835 2.11 978 2008 2.31 1026 2182 2.51 4000 840 1760 2.02 893 1948 2.24 943 2136 2.46 992 2324 2.67 1039 2512 2.89 4500 865 2068 2.38 915 2270 2.61 964 2472 2.84 1011 2673 3.07 1056 2876 3.31 5000 893 2417 2.78 942 2632 3.03 988 2848 3.28 1033 3063 3.52 1076 3278 3.77 5500 925 2808 3.23 971 3037 3.49 1016 3266 3.76 1059 3494 4.02 1100 3721 4.28 6000 958 3243 3.73 1003 3486 4.01 1045 3728 4.29 1087 3970 4.57 1127 4210 4.84 6500 993 3725 4.28 1036 3982 4.58 1077 4238 4.87 1117 4492 5.17 1156 4745 5.46 7000 1029 4256 4.90 1071 4528 5.21 1111 4797 5.52 1150 5064 5.82 1187 5330 6.13 7500 1067 4838 5.56 1107 5124 5.89 1146 5407 6.22 1184 5688 6.54 1220 5967 6.86 8000 1106 5474 6.30 1145 5774 6.64 1182 6071 6.98 1219 6365 7.32 1254 6657 7.66 8500 1145 6165 7.09 1183 6479 7.45 1220 6790 7.81 1255 7098 8.16 1290 7403 8.51
Refer to page 262 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v) High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v) All other rpms require field-supplied drive.

581A210 (18 TONS) (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 470 611 0.70 556 791 0.91 630 967 1.11 697 1141 1.31 760 1314 1.51 4000 511 802 0.92 591 1001 1.15 661 1194 1.37 725 1383 1.59 784 1572 1.81 4500 553 1029 1.18 629 1248 1.44 695 1458 1.68 756 1663 1.91 812 1866 2.15 5000 597 1297 1.49 669 1534 1.76 732 1761 2.03 789 1982 2.28 843 2201 2.53 5500 641 1606 1.85 709 1862 2.14 770 2106 2.42 825 2343 2.70 876 2577 2.96 6000 686 1961 2.26 751 2234 2.57 809 2495 2.87 862 2749 3.16 911 2997 3.45 6500 732 2363 2.72 794 2653 3.05 849 2931 3.37 900 3201 3.68 948 3465 3.99 7000 779 2815 3.24 837 3122 3.59 891 3416 3.93 940 3702 4.26 986 3981 4.58 7500 826 3320 3.82 882 3642 4.19 933 3953 4.55 980 4254 4.89 1025 4549 5.23 8000 873 3879 4.46 926 4217 4.85 975 4542 5.22 1021 4860 5.59 1065 5169 5.95 8500 921 4495 5.17 972 4847 5.57 1019 5189 5.97 1063 5521 6.35 1105 5846 6.72
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3500 818 1488 1.71 874 1661 1.91 927 1835 2.11 978 2008 2.31 1026 2182 2.51 4000 840 1760 2.02 893 1948 2.24 943 2136 2.46 992 2324 2.67 1039 2512 2.89 4500 865 2068 2.38 915 2270 2.61 964 2472 2.84 1011 2673 3.07 1056 2876 3.31 5000 893 2417 2.78 942 2632 3.03 988 2848 3.28 1033 3063 3.52 1076 3278 3.77 5500 925 2808 3.23 971 3037 3.49 1016 3266 3.76 1059 3494 4.02 1100 3721 4.28 6000 958 3243 3.73 1003 3486 4.01 1045 3728 4.29 1087 3970 4.57 1127 4210 4.84 6500 993 3725 4.28 1036 3982 4.58 1077 4238 4.87 1117 4492 5.17 1156 4745 5.46 7000 1029 4256 4.90 1071 4528 5.21 1111 4797 5.52 1150 5064 5.82 1187 5330 6.13 7500 1067 4838 5.56 1107 5124 5.89 1146 5407 6.22 1184 5688 6.54 1220 5967 6.86 8000 1106 5474 6.30 1145 5774 6.64 1182 6071 6.98 1219 6365 7.32 1254 6657 7.66 8500 1145 6165 7.09 1183 6479 7.45 1220 6790 7.81 1255 7098 8.16 1290 7403 8.51
Refer to page 262 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v) High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v) All other rpms require field-supplied drive.

581A240 (20 TONS) (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 590 1276 1.47 663 1516 1.74 727 1745 2.01 786 1968 2.26 840 2189 2.52 5,500 633 1579 1.82 703 1838 2.11 764 2084 2.40 820 2324 2.67 872 2560 2.94 6,000 677 1925 2.21 744 2203 2.53 803 2467 2.84 857 2723 3.13 907 2974 3.42 6,500 722 2317 2.67 786 2614 3.01 842 2896 3.33 894 3167 3.64 942 3434 3.95 7,000 767 2758 3.17 828 3073 3.53 883 3371 3.88 933 3660 4.21 979 3942 4.53 7,500 813 3250 3.74 871 3582 4.12 924 3897 4.48 972 4202 4.83 1017 4500 5.18 8,000 859 3795 4.36 915 4143 4.77 966 4475 5.15 1012 4797 5.52 1056 5110 5.88 8,500 906 4394 5.05 959 4759 5.47 1008 5107 5.87 1053 5445 6.26 1096 5774 6.64 9,000 952 5051 5.81 1004 5432 6.25 1051 5797 6.67 1095 6150 7.07 1136 6494 7.47 9,500 999 5767 6.63 1049 6163 7.09 1094 6544 7.53 1137 6913 7.95 1177 7272 8.36 10,000 1047 6544 7.53 1094 6956 8.00 1138 7352 8.46 1180 7736 8.90 1219 8111 9.33
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 891 2408 2.77 940 2625 3.02 987 2843 3.27 1032 3060 3.52 1076 3277 3.77 5,500 921 2792 3.21 968 3024 3.48 1014 3255 3.74 1057 3485 4.01 1099 3716 4.27 6,000 954 3221 3.70 999 3467 3.99 1042 3711 4.27 1084 3955 4.55 1125 4198 4.83 6,500 988 3696 4.25 1032 3956 4.55 1073 4214 4.85 1114 4470 5.14 1153 4726 5.44 7,000 1024 4219 4.85 1066 4493 5.17 1106 4764 5.48 1145 5034 5.79 1183 5303 6.10 7,500 1060 4792 5.51 1101 5080 5.84 1140 5365 6.17 1178 5649 6.50 1215 5930 6.82 8,000 1098 5417 6.23 1138 5719 6.58 1176 6018 6.92 1213 6315 7.26 1249 6610 7.60 8,500 1137 6096 7.01 1175 6413 7.38 1212 6726 7.74 1248 7036 8.09 1283 7344 8.45 9,000 1176 6831 7.86 1214 7163 8.24 1250 7490 8.61 1285 7814 8.99 1319 8135 9.36 9,500 1216 7624 8.77 1253 7970 9.17 1288 8312 9.56 1322 8649 9.95 1355 8984 10.33 10,000 1256 8478 9.75 1292 8838 10.16 1327 9193 10.57 1360 9545 10.98 1393 9893 11.38
Refer to page 262 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 949-1206 High Range: 941-1176 All other rpms require field-supplied drive.

581A240 (20 TONS) (Medium Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 607 1329 1.53 677 1565 1.80 740 1791 2.06 797 2013 2.31 850 2231 2.57 5,500 652 1648 1.90 719 1902 2.19 779 2145 2.47 833 2382 2.74 884 2616 3.01 6,000 699 2013 2.32 763 2285 2.63 819 2545 2.93 872 2798 3.22 921 3046 3.50 6,500 746 2428 2.79 807 2716 3.12 861 2993 3.44 911 3262 3.75 958 3525 4.05 7,000 794 2895 3.33 851 3198 3.68 904 3491 4.02 952 3776 4.34 998 4055 4.66 7,500 842 3415 3.93 897 3735 4.30 947 4043 4.65 994 4343 5.00 1038 4637 5.33 8,000 891 3992 4.59 943 4327 4.98 991 4650 5.35 1036 4966 5.71 1079 5274 6.07 8,500 940 4628 5.32 990 4977 5.72 1036 5316 6.11 1080 5646 6.49 1121 5970 6.87 9,000 990 5325 6.12 1037 5688 6.54 1082 6042 6.95 1124 6386 7.35 1163 6724 7.73 9,500 1039 6085 7.00 1085 6462 7.43 1128 6829 7.85 1168 7188 8.27 1207 7541 8.67 10,000 1089 6911 7.95 1133 7301 8.40 1174 7682 8.83 1213 8055 9.26 1251 8421 9.69
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 900 2448 2.82 949 2664 3.06 995 2879 3.31 1040 3095 3.56 1083 3310 3.81 5,500 933 2847 3.27 979 3077 3.54 1023 3305 3.80 1066 3534 4.06 1108 3762 4.33 6,000 967 3292 3.79 1011 3535 4.07 1054 3778 4.35 1095 4019 4.62 1135 4260 4.90 6,500 1003 3785 4.35 1046 4043 4.65 1087 4298 4.94 1127 4553 5.24 1165 4806 5.53 7,000 1041 4330 4.98 1082 4601 5.29 1122 4870 5.60 1160 5138 5.91 1197 5404 6.22 7,500 1079 4926 5.67 1119 5212 5.99 1158 5495 6.32 1195 5776 6.64 1231 6055 6.96 8,000 1119 5578 6.42 1158 5878 6.76 1195 6174 7.10 1231 6468 7.44 1267 6761 7.78 8,500 1160 6288 7.23 1198 6601 7.59 1234 6912 7.95 1269 7219 8.30 1303 7524 8.65 9,000 1202 7056 8.12 1238 7384 8.49 1273 7708 8.87 1308 8029 9.23 1341 8347 9.60 9,500 1244 7887 9.07 1279 8228 9.46 1314 8566 9.85 1347 8900 10.24 1379 9231 10.62 10,000 1287 8781 10.10 1321 9137 10.51 1355 9488 10.91 1387 9836 11.31 — — —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 949-1206 High Range: 941-1176 All other rpms require field-supplied drive.

581A240 (20 TONS) (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 607 1329 1.53 677 1565 1.80 740 1791 2.06 797 2013 2.31 850 2231 2.57 5,500 652 1648 1.90 719 1902 2.19 779 2145 2.47 833 2382 2.74 884 2616 3.01 6,000 699 2013 2.32 763 2285 2.63 819 2545 2.93 872 2798 3.22 921 3046 3.50 6,500 746 2428 2.79 807 2716 3.12 861 2993 3.44 911 3262 3.75 958 3525 4.05 7,000 794 2895 3.33 851 3198 3.68 904 3491 4.02 952 3776 4.34 998 4055 4.66 7,500 842 3415 3.93 897 3735 4.30 947 4043 4.65 994 4343 5.00 1038 4637 5.33 8,000 891 3992 4.59 943 4327 4.98 991 4650 5.35 1036 4966 5.71 1079 5274 6.07 8,500 940 4628 5.32 990 4977 5.72 1036 5316 6.11 1080 5646 6.49 1121 5970 6.87 9,000 990 5325 6.12 1037 5688 6.54 1082 6042 6.95 1124 6386 7.35 1163 6724 7.73 9,500 1039 6085 7.00 1085 6462 7.43 1128 6829 7.85 1168 7188 8.27 1207 7541 8.67 10,000 1089 6911 7.95 1133 7301 8.40 1174 7682 8.83 1213 8055 9.26 1251 8421 9.69
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 5,000 900 2448 2.82 949 2664 3.06 995 2879 3.31 1040 3095 3.56 1083 3310 3.81 5,500 933 2847 3.27 979 3077 3.54 1023 3305 3.80 1066 3534 4.06 1108 3762 4.33 6,000 967 3292 3.79 1011 3535 4.07 1054 3778 4.35 1095 4019 4.62 1135 4260 4.90 6,500 1003 3785 4.35 1046 4043 4.65 1087 4298 4.94 1127 4553 5.24 1165 4806 5.53 7,000 1041 4330 4.98 1082 4601 5.29 1122 4870 5.60 1160 5138 5.91 1197 5404 6.22 7,500 1079 4926 5.67 1119 5212 5.99 1158 5495 6.32 1195 5776 6.64 1231 6055 6.96 8,000 1119 5578 6.42 1158 5878 6.76 1195 6174 7.10 1231 6468 7.44 1267 6761 7.78 8,500 1160 6288 7.23 1198 6601 7.59 1234 6912 7.95 1269 7219 8.30 1303 7524 8.65 9,000 1202 7056 8.12 1238 7384 8.49 1273 7708 8.87 1308 8029 9.23 1341 8347 9.60 9,500 1244 7887 9.07 1279 8228 9.46 1314 8566 9.85 1347 8900 10.24 1379 9231 10.62 10,000 1287 8781 10.10 1321 9137 10.51 1355 9488 10.91 1387 9836 11.31 — — —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 949-1206 High Range: 941-1176 All other rpms require field-supplied drive.

581A300 (25 TONS) (Low Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 750 2,468 2.84 806 2,767 3.18 854 3,031 3.49 898 3,298 3.79 943 3,584 4.12 7,000 797 2,942 3.38 853 3,276 3.77 899 3,557 4.09 941 3,832 4.41 982 4,118 4.74 7,500 845 3,468 3.99 900 3,840 4.42 945 4,142 4.76 985 4,430 5.09 1024 4,721 5.43 8,000 892 4,045 4.65 948 4,462 5.13 991 4,789 5.51 1030 5,092 5.86 1067 5,391 6.20 8,500 939 4,677 5.38 995 5,141 5.91 1038 5,497 6.32 1076 5,818 6.69 1112 6,129 7.05 9,000 986 5,364 6.17 1042 5,882 6.76 1085 6,269 7.21 1122 6,611 7.60 1157 6,936 7.98 9,500 1033 6,108 7.03 1090 6,684 7.69 1132 7,105 8.17 1169 7,470 8.59 1203 7,813 8.99 10,000 1079 6,911 7.95 1137 7,550 8.68 1180 8,007 9.21 1216 8,399 9.66 1249 8,761 10.08 10,500 1126 7,773 8.94 1184 8,480 9.75 1227 8,978 10.33 1263 9,399 10.81 1296 9,782 11.25 11,000 1172 8,696 10.00 1232 9,475 10.90 1274 10,017 11.52 1310 10,468 12.04 1342 10,876 12.51 11,500 1219 9,681 11.13 1279 10,539 12.12 1322 11,127 12.80 1357 11,611 13.35 — — — 12,000 1265 10,732 12.34 1326 11,669 13.42 — 12,500 1311 11,848 13.63 —
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 988 3,900 4.49 1035 4,250 4.89 1082 4,634 5.33 1130 5,053 5.81 1177 5,499 6.32 7,000 1024 4,426 5.09 1066 4,760 5.48 1109 5,126 5.90 1153 5,524 6.35 1197 5,953 6.85 7,500 1063 5,026 5.78 1101 5,351 6.15 1141 5,702 6.56 1181 6,081 6.99 1222 6,490 7.46 8,000 1104 5,698 6.55 1140 6,020 6.92 1176 6,361 7.32 1213 6,727 7.74 1251 7,118 8.19 8,500 1146 6,443 7.41 1180 6,765 7.78 1214 7,103 8.17 1249 7,459 8.58 1283 7,837 9.01 9,000 1190 7,259 8.35 1222 7,586 8.73 1255 7,925 9.11 1287 8,276 9.52 1319 8,645 9.94 9,500 1235 8,148 9.37 1266 8,483 9.76 1296 8,824 10.15 1327 9,176 10.55 1357 9,541 10.97 10,000 1280 9,111 10.48 1310 9,456 10.88 1340 9,804 11.28 1369 10,158 11.68 1398 10,522 12.10 10,500 1326 10,147 11.67 1355 10,505 12.08 1384 10,862 12.49 — 11,000 1372 11,259 12.95 — 11,500 — 12,000 — 12,500 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.

581A300 (25 TONS) (Medium Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 775 2,600 2.99 825 2,872 3.30 871 3,130 3.60 915 3,400 3.91 959 3,692 4.25 7,000 826 3,115 3.58 875 3,408 3.92 918 3,679 4.23 959 3,954 4.55 1000 4,245 4.88 7,500 878 3,690 4.24 925 4,006 4.61 966 4,292 4.94 1005 4,575 5.26 1043 4,868 5.60 8,000 929 4,326 4.98 975 4,667 5.37 1015 4,970 5.72 1052 5,265 6.06 1088 5,564 6.40 8,500 981 5,029 5.78 1026 5,395 6.20 1064 5,717 6.58 1100 6,025 6.93 1134 6,332 7.28 9,000 1033 5,799 6.67 1076 6,191 7.12 1114 6,533 7.51 1148 6,856 7.89 1181 7,173 8.25 9,500 1085 6,640 7.64 1128 7,058 8.12 1164 7,421 8.54 1198 7,761 8.93 1229 8,091 9.31 10,000 1137 7,553 8.69 1179 8,000 9.20 1214 8,385 9.64 1247 8,741 10.05 1278 9,086 10.45 10,500 1190 8,542 9.82 1230 9,016 10.37 1265 9,424 10.84 1297 9,799 11.27 1327 10,158 11.68 11,000 1242 9,609 11.05 1282 10,111 11.63 1316 10,542 12.12 1347 10,937 12.58 1376 11,311 13.01 11,500 1294 10,756 12.37 1333 11,287 12.98 1367 11,741 13.50 — 12,000 1347 11,985 13.78 — 12,500 —
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 1004 4,016 4.62 1050 4,374 5.03 1098 4,769 5.48 1145 5,195 5.97 1192 5646 6.49 7,000 1041 4,559 5.24 1083 4,902 5.64 1126 5,277 6.07 1170 5,685 6.54 1214 6122 7.04 7,500 1081 5,179 5.96 1120 5,512 6.34 1159 5,872 6.75 1199 6,261 7.20 1240 6680 7.68 8,000 1124 5,875 6.76 1160 6,203 7.13 1196 6,553 7.54 1233 6,928 7.97 1270 7329 8.43 8,500 1168 6,647 7.64 1202 6,974 8.02 1235 7,318 8.42 1269 7,684 8.84 1304 8071 9.28 9,000 1214 7,495 8.62 1245 7,825 9.00 1277 8,168 9.39 1309 8,527 9.81 1341 8905 10.24 9,500 1260 8,421 9.69 1290 8,756 10.07 1320 9,100 10.47 1351 9,457 10.88 1381 9830 11.31 10,000 1308 9,425 10.84 1337 9,768 11.23 1365 10,116 11.63 1394 10,474 12.05 — — — 10,500 1356 10,510 12.09 1384 10,862 12.49 — 11,000 — 11,500 — 12,000 — 12,500 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.

581A300 (25 TONS) (High Heat Units)*
Available External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 775 2,600 2.99 825 2,872 3.30 871 3,130 3.60 915 3,400 3.91 959 3,692 4.25 7,000 826 3,115 3.58 875 3,408 3.92 918 3,679 4.23 959 3,954 4.55 1000 4,245 4.88 7,500 878 3,690 4.24 925 4,006 4.61 966 4,292 4.94 1005 4,575 5.26 1043 4,868 5.60 8,000 929 4,326 4.98 975 4,667 5.37 1015 4,970 5.72 1052 5,265 6.06 1088 5,564 6.40 8,500 981 5,029 5.78 1026 5,395 6.20 1064 5,717 6.58 1100 6,025 6.93 1134 6,332 7.28 9,000 1033 5,799 6.67 1076 6,191 7.12 1114 6,533 7.51 1148 6,856 7.89 1181 7,173 8.25 9,500 1085 6,640 7.64 1128 7,058 8.12 1164 7,421 8.54 1198 7,761 8.93 1229 8,091 9.31 10,000 1137 7,553 8.69 1179 8,000 9.20 1214 8,385 9.64 1247 8,741 10.05 1278 9,086 10.45 10,500 1190 8,542 9.82 1230 9,016 10.37 1265 9,424 10.84 1297 9,799 11.27 1327 10,158 11.68 11,000 1242 9,609 11.05 1282 10,111 11.63 1316 10,542 12.12 1347 10,937 12.58 1376 11,311 13.01 11,500 1294 10,756 12.37 1333 11,287 12.98 1367 11,741 13.50 — 12,000 1347 11,985 13.78 — 12,500 —
Available External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6,500 1004 4,016 4.62 1050 4,374 5.03 1098 4,769 5.48 1145 5,195 5.97 1192 5646 6.49 7,000 1041 4,559 5.24 1083 4,902 5.64 1126 5,277 6.07 1170 5,685 6.54 1214 6122 7.04 7,500 1081 5,179 5.96 1120 5,512 6.34 1159 5,872 6.75 1199 6,261 7.20 1240 6680 7.68 8,000 1124 5,875 6.76 1160 6,203 7.13 1196 6,553 7.54 1233 6,928 7.97 1270 7329 8.43 8,500 1168 6,647 7.64 1202 6,974 8.02 1235 7,318 8.42 1269 7,684 8.84 1304 8071 9.28 9,000 1214 7,495 8.62 1245 7,825 9.00 1277 8,168 9.39 1309 8,527 9.81 1341 8905 10.24 9,500 1260 8,421 9.69 1290 8,756 10.07 1320 9,100 10.47 1351 9,457 10.88 1381 9830 11.31 10,000 1308 9,425 10.84 1337 9,768 11.23 1365 10,116 11.63 1394 10,474 12.05 — — — 10,500 1356 10,510 12.09 1384 10,862 12.49 — 11,000 — 11,500 — 12,000 — 12,500 —
Refer to this page for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES 1. Static pressure losses (i.e., EconoMi$er IV) must be added to external static pressure before entering Fan Performance table. 2. Interpolation is permissible. Do not extrapolate. 3. Fan performance is based on wet coils, clean filters, and casing losses. See Accessory/FIOP Static Pressure table on page 273. 4. Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confidence. Using the fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire size. Contact your Bryant representative for details. 6. Field-supplied drive requires changing belt and motor pulley to meet desired airflow. See application data or contact your local Bryant representative for details.

581A210 (18 TONS) (Low Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 635 1064 1.22 709 1278 1.47 776 1492 1.72 838 1708 1.96 896 1924 2.21 4,000 707 1402 1.61 773 1627 1.87 835 1853 2.13 892 2080 2.39 947 2307 2.65 4,500 780 1802 2.07 840 2037 2.34 897 2273 2.61 950 2510 2.89 1001 2465 2.84 5,000 853 2264 2.60 909 2510 2.89 961 2756 3.17 1011 2710 3.12 1059 3015 3.47 5,500 928 2794 3.21 979 3049 3.51 1028 3012 3.46 1075 3333 3.83 1120 3661 4.21 6,000 1003 3047 3.50 1051 3376 3.88 1096 3714 4.27 1140 4059 4.67 1182 4411 5.07 6,500 1079 3812 4.38 1123 4166 4.79 1166 4529 5.21 1207 4898 5.63 1247 5274 6.07 7,000 1155 4697 5.40 1196 5078 5.84 1236 5465 6.29 1275 5859 6.74 1313 6260 7.20 7,500 1231 5714 6.57 1270 6120 7.04 1308 6533 7.51 1345 6952 8.00 1381 7378 8.49 8,000 1308 6871 7.90 1344 7303 8.40 1380 7741 8.90 — 8,500 1385 8177 9.40 — 9,000 — 9,500 — 10,000 —
581A210 (18 TONS) (Low Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 951 2143 2.46 1003 2120 2.44 1052 2387 2.75 1100 2662 3.06 1146 2944 3.39 4,000 998 2535 2.92 1048 2548 2.93 1095 2835 3.26 1141 3129 3.60 1184 3432 3.95 4,500 1050 2756 3.17 1097 3055 3.51 1142 3363 3.87 1185 3678 4.23 1227 4001 4.60 5,000 1105 3329 3.83 1150 3651 4.20 1192 3979 4.58 1234 4315 4.96 1274 4658 5.36 5,500 1163 3997 4.60 1205 4342 4.99 1246 4692 5.40 1286 5051 5.81 1324 5415 6.23 6,000 1224 4771 5.49 1263 5138 5.91 1302 5511 6.34 1340 5892 6.78 1377 6278 7.22 6,500 1286 5658 6.51 1324 6048 6.96 1361 6445 7.41 1397 6847 7.87 — — — 7,000 1350 6668 7.67 1386 7081 8.14 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v) High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

581A210 (18 TONS) (Medium Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 645 1105 1.27 720 1329 1.53 788 1549 1.78 851 1767 2.03 910 1982 2.28 4,000 718 1454 1.67 785 1692 1.95 848 1926 2.22 906 2158 2.48 962 2388 2.75 4,500 792 1866 2.15 853 2117 2.43 911 2364 2.72 965 2609 3.00 1017 2583 2.97 5,000 867 2343 2.69 923 2605 3.00 977 2865 3.30 1027 2845 3.27 1076 3163 3.64 5,500 943 2889 3.32 995 3162 3.64 1044 3158 3.63 1092 3497 4.02 1138 3843 4.42 6,000 1019 3177 3.65 1067 3532 4.06 1113 3892 4.48 1158 4259 4.90 1201 4631 5.33 6,500 1096 3973 4.57 1141 4354 5.01 1184 4742 5.45 1226 5136 5.91 1267 5535 6.37 7,000 1173 4894 5.63 1215 5304 6.10 1256 5719 6.58 1295 6140 7.06 1334 6567 7.55 7,500 1250 5952 6.85 1290 6389 7.35 1328 6832 7.86 1366 7281 8.37 — — — 8,000 1328 7153 8.23 1365 7620 8.76 — 8,500 — 9,000 — 9,500 — 10,000 —
581A210 (18 TONS) (Medium Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 965 2195 2.53 1018 2181 2.51 1068 2442 2.81 1116 2708 3.11 1162 2979 3.43 4,000 1014 2364 2.72 1064 2644 3.04 1112 2930 3.37 1158 3221 3.70 1202 3517 4.05 4,500 1067 2882 3.31 1114 3187 3.67 1160 3498 4.02 1204 3814 4.39 1246 4135 4.76 5,000 1123 3489 4.01 1168 3820 4.39 1211 4156 4.78 1253 4497 5.17 1294 4844 5.57 5,500 1182 4194 4.82 1224 4551 5.23 1266 4913 5.65 1306 5280 6.07 1345 5652 6.50 6,000 1243 5008 5.76 1283 5391 6.20 1323 5779 6.65 1361 6172 7.10 1398 6569 7.56 6,500 1306 5939 6.83 1345 6349 7.30 1382 6763 7.78 — 7,000 1371 6997 8.05 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v) High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

581A210 (18 TONS) (High Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 645 1105 1.27 720 1329 1.53 788 1549 1.78 851 1767 2.03 910 1982 2.28 4,000 718 1454 1.67 785 1692 1.95 848 1926 2.22 906 2158 2.48 962 2388 2.75 4,500 792 1866 2.15 853 2117 2.43 911 2364 2.72 965 2609 3.00 1017 2583 2.97 5,000 867 2343 2.69 923 2605 3.00 977 2865 3.30 1027 2845 3.27 1076 3163 3.64 5,500 943 2889 3.32 995 3162 3.64 1044 3158 3.63 1092 3497 4.02 1138 3843 4.42 6,000 1019 3177 3.65 1067 3532 4.06 1113 3892 4.48 1158 4259 4.90 1201 4631 5.33 6,500 1096 3973 4.57 1141 4354 5.01 1184 4742 5.45 1226 5136 5.91 1267 5535 6.37 7,000 1173 4894 5.63 1215 5304 6.10 1256 5719 6.58 1295 6140 7.06 1334 6567 7.55 7,500 1250 5952 6.85 1290 6389 7.35 1328 6832 7.86 1366 7281 8.37 — — — 8,000 1328 7153 8.23 1365 7620 8.76 — 8,500 — 9,000 — 9,500 — 10,000 —
581A210 (18 TONS) (High Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 965 2195 2.53 1018 2181 2.51 1068 2442 2.81 1116 2708 3.11 1162 2979 3.43 4,000 1014 2364 2.72 1064 2644 3.04 1112 2930 3.37 1158 3221 3.70 1202 3517 4.05 4,500 1067 2882 3.31 1114 3187 3.67 1160 3498 4.02 1204 3814 4.39 1246 4135 4.76 5,000 1123 3489 4.01 1168 3820 4.39 1211 4156 4.78 1253 4497 5.17 1294 4844 5.57 5,500 1182 4194 4.82 1224 4551 5.23 1266 4913 5.65 1306 5280 6.07 1345 5652 6.50 6,000 1243 5008 5.76 1283 5391 6.20 1323 5779 6.65 1361 6172 7.10 1398 6569 7.56 6,500 1306 5939 6.83 1345 6349 7.30 1382 6763 7.78 — 7,000 1371 6997 8.05 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v) High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

581A240 (20 TONS) (Low Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 642 1082 1.24 714 1296 1.49 781 1510 1.74 843 1726 1.98 901 1943 2.23 4,000 714 1426 1.64 780 1651 1.90 841 1877 2.16 898 2103 2.42 952 2330 2.68 4,500 787 1831 2.11 847 2067 2.38 904 2303 2.65 957 2540 2.92 1008 2501 2.88 5,000 862 2301 2.65 917 2547 2.93 969 2793 3.21 1019 2755 3.17 1066 3062 3.52 5,500 937 2838 3.26 988 3094 3.56 1036 3067 3.53 1083 3390 3.90 1127 3719 4.28 6,000 1013 3113 3.58 1060 3445 3.96 1105 3783 4.35 1149 4130 4.75 1191 4484 5.16 6,500 1089 3893 4.48 1133 4250 4.89 1175 4615 5.31 1216 4986 5.73 1256 5364 6.17 7,000 1166 4798 5.52 1207 5181 5.96 1247 5570 6.41 1285 5965 6.86 1323 6369 7.32 7,500 1243 5837 6.71 1282 6244 7.18 1319 6658 7.66 1355 7080 8.14 1391 7507 8.63 8,000 1320 7017 8.07 1356 7450 8.57 1392 7890 9.08 — 8,500 1398 8350 9.60 — 9,000 — 9,500 — 10,000 —
581A240 (20 TONS) (Low Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 955 2160 2.48 1007 2142 2.46 1056 2409 2.77 1104 2684 3.09 1149 2968 3.41 4,000 1004 2299 2.64 1053 2578 2.96 1100 2865 3.29 1145 3160 3.63 1189 3463 3.98 4,500 1056 2793 3.21 1103 3093 3.56 1147 3402 3.91 1191 3718 4.28 1233 4041 4.65 5,000 1112 3376 3.88 1156 3699 4.25 1199 4029 4.63 1240 4366 5.02 1280 4710 5.42 5,500 1171 4057 4.67 1212 4402 5.06 1253 4754 5.47 1292 5114 5.88 1331 5480 6.30 6,000 1232 4845 5.57 1271 5213 6.00 1310 5588 6.43 1348 5970 6.87 1384 6358 7.31 6,500 1295 5749 6.61 1333 6141 7.06 1369 6538 7.52 — 7,000 1360 6778 7.80 1396 7193 8.27 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 873-1108 (575-v) High Range: 1113-1414 All other rpms require field-supplied drive.

581A240 (20 TONS) (Medium Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 652 1123 1.29 726 1347 1.55 793 1567 1.80 856 1784 2.05 914 2000 2.30 4,000 725 1479 1.70 792 1716 1.97 854 1950 2.24 912 2182 2.51 967 2412 2.77 4,500 800 1897 2.18 861 2148 2.47 918 2395 2.75 972 2639 3.04 1024 2620 3.01 5,000 875 2383 2.74 931 2645 3.04 984 2904 3.34 1035 2892 3.33 1083 3212 3.69 5,500 952 2937 3.38 1003 2883 3.32 1053 3217 3.70 1100 3558 4.09 1145 3905 4.49 6,000 1029 3249 3.74 1077 3605 4.15 1123 3966 4.56 1167 4334 4.98 1210 4707 5.41 6,500 1106 4061 4.67 1151 4445 5.11 1194 4834 5.56 1236 5229 6.01 1276 5629 6.47 7,000 1184 5003 5.75 1226 5414 6.23 1266 5831 6.71 1306 6253 7.19 1344 6681 7.68 7,500 1262 6083 7.00 1302 6522 7.50 1340 6967 8.01 1377 7417 8.53 — — — 8,000 1341 7312 8.41 1378 7779 8.95 — 8,500 — 9,000 — 9,500 — 10,000 —
581A240 (20 TONS) (Medium Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 970 2213 2.55 1022 2203 2.53 1072 2464 2.83 1120 2730 3.14 1166 3002 3.45 4,000 1019 2393 2.75 1069 2673 3.07 1117 2959 3.40 1163 3251 3.74 1207 3548 4.08 4,500 1073 2920 3.36 1120 3226 3.71 1165 3537 4.07 1209 3854 4.43 1252 4176 4.80 5,000 1130 3537 4.07 1174 3870 4.45 1218 4207 4.84 1259 4549 5.23 1300 4896 5.63 5,500 1189 4257 4.90 1232 4614 5.31 1273 4977 5.72 1313 5345 6.15 1352 5719 6.58 6,000 1251 5086 5.85 1292 5469 6.29 1331 5859 6.74 1369 6253 7.19 — — — 6,500 1315 6035 6.94 1354 6446 7.41 1391 6861 7.89 — 7,000 1381 7114 8.18 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 873-1108 (575-v) High Range: 1113-1414 All other rpms require field-supplied drive.

581A240 (20 TONS) (High Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 652 1123 1.29 726 1347 1.55 793 1567 1.80 856 1784 2.05 914 2000 2.30 4,000 725 1479 1.70 792 1716 1.97 854 1950 2.24 912 2182 2.51 967 2412 2.77 4,500 800 1897 2.18 861 2148 2.47 918 2395 2.75 972 2639 3.04 1024 2620 3.01 5,000 875 2383 2.74 931 2645 3.04 984 2904 3.34 1035 2892 3.33 1083 3212 3.69 5,500 952 2937 3.38 1003 2883 3.32 1053 3217 3.70 1100 3558 4.09 1145 3905 4.49 6,000 1029 3249 3.74 1077 3605 4.15 1123 3966 4.56 1167 4334 4.98 1210 4707 5.41 6,500 1106 4061 4.67 1151 4445 5.11 1194 4834 5.56 1236 5229 6.01 1276 5629 6.47 7,000 1184 5003 5.75 1226 5414 6.23 1266 5831 6.71 1306 6253 7.19 1344 6681 7.68 7,500 1262 6083 7.00 1302 6522 7.50 1340 6967 8.01 1377 7417 8.53 — — — 8,000 1341 7312 8.41 1378 7779 8.95 — 8,500 — 9,000 — 9,500 — 10,000 —
581A240 (20 TONS) (High Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3,500 970 2213 2.55 1022 2203 2.53 1072 2464 2.83 1120 2730 3.14 1166 3002 3.45 4,000 1019 2393 2.75 1069 2673 3.07 1117 2959 3.40 1163 3251 3.74 1207 3548 4.08 4,500 1073 2920 3.36 1120 3226 3.71 1165 3537 4.07 1209 3854 4.43 1252 4176 4.80 5,000 1130 3537 4.07 1174 3870 4.45 1218 4207 4.84 1259 4549 5.23 1300 4896 5.63 5,500 1189 4257 4.90 1232 4614 5.31 1273 4977 5.72 1313 5345 6.15 1352 5719 6.58 6,000 1251 5086 5.85 1292 5469 6.29 1331 5859 6.74 1369 6253 7.19 — — — 6,500 1315 6035 6.94 1354 6446 7.41 1391 6861 7.89 — 7,000 1381 7114 8.18 — 7,500 — 8,000 — 8,500 — 9,000 — 9,500 — 10,000 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 896-1227 (208/230 and 460-v), 873-1108 (575-v) High Range: 1113-1414 All other rpms require field-supplied drive.

581A300 (25 TONS) (Low Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 786 2,658 3.06 819 2,835 3.26 857 3,052 3.51 899 3,304 3.80 943 3,586 4.12 7,000 842 3,208 3.69 871 3,386 3.89 905 3,599 4.14 943 3,847 4.42 983 4,123 4.74 7,500 898 3,827 4.40 925 4,006 4.61 955 4,217 4.85 989 4,460 5.13 1026 4,733 5.44 8,000 955 4,518 5.20 979 4,699 5.40 1007 4,908 5.65 1037 5,148 5.92 1070 5,416 6.23 8,500 1012 5,284 6.08 1034 5,466 6.29 1059 5,675 6.53 1087 5,912 6.80 1117 6,176 7.10 9,000 1069 6,127 7.05 1090 6,312 7.26 1113 6,521 7.50 1138 6,757 7.77 1165 7,017 8.07 9,500 1127 7,050 8.11 1146 7,238 8.32 1167 7,448 8.57 1190 7,682 8.84 1215 7,940 9.13 10,000 1184 8,057 9.27 1202 8,247 9.49 1221 8,460 9.73 1243 8,693 10.00 1266 8,948 10.29 10,500 1242 9,149 10.52 1258 9,344 10.75 1276 9,557 10.99 1296 9,791 11.26 1318 10,046 11.55 11,000 1299 10,331 11.88 1315 10,529 12.11 1332 10,745 12.36 1350 10,979 12.63 1370 11,232 12.92 11,500 1357 11,604 13.35 1372 11,806 13.58 — 12,000 — 12,500 —
581A300 (25 TONS) (Low Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 988 3,900 4.49 1035 4,248 4.89 1082 4,632 5.33 1129 5,050 5.81 1177 5,499 6.32 7,000 1024 4,428 5.09 1066 4,760 5.48 1109 5,124 5.89 1153 5,521 6.35 1197 5,950 6.84 7,500 1063 5,031 5.79 1102 5,354 6.16 1141 5,703 6.56 1181 6,081 6.99 1221 6,487 7.46 8,000 1105 5,709 6.57 1140 6,025 6.93 1176 6,364 7.32 1213 6,729 7.74 1250 7,116 8.18 8,500 1149 6,465 7.44 1181 6,777 7.79 1215 7,109 8.18 1249 7,463 8.58 1283 7,838 9.02 9,000 1194 7,302 8.40 1225 7,608 8.75 1256 7,935 9.13 1287 8,282 9.53 1319 8,649 9.95 9,500 1242 8,222 9.46 1270 8,524 9.80 1298 8,847 10.17 1328 9,189 10.57 1358 9,548 10.98 10,000 1290 9,227 10.61 1316 9,525 10.96 1343 9,845 11.32 1370 10,181 11.71 1399 10,536 12.12 10,500 1340 10,321 11.87 1364 10,617 12.21 1389 10,932 12.57 — 11,000 1391 11,505 13.23 — 11,500 — 12,000 — 12,500 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.

581A300 (25 TONS) (Medium Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 799 2,730 3.14 833 2,914 3.35 872 3,135 3.61 914 3,392 3.90 958 3,687 4.24 7,000 856 3,294 3.79 887 3,481 4.00 921 3,699 4.25 958 3,950 4.54 999 4,235 4.87 7,500 913 3,929 4.52 941 4,118 4.74 972 4,335 4.99 1006 4,582 5.27 1042 4,860 5.59 8,000 971 4,637 5.33 996 4,829 5.55 1024 5,046 5.80 1055 5,290 6.08 1088 5,562 6.40 8,500 1029 5,421 6.24 1052 5,617 6.46 1078 5,835 6.71 1106 6,077 6.99 1136 6,345 7.30 9,000 1087 6,285 7.23 1108 6,484 7.46 1132 6,703 7.71 1158 6,946 7.99 1185 7,211 8.29 9,500 1145 7,231 8.32 1165 7,433 8.55 1187 7,655 8.80 1211 7,898 9.08 1236 8,161 9.39 10,000 1203 8,262 9.50 1222 8,468 9.74 1243 8,693 10.00 1265 8,936 10.28 1288 9,199 10.58 10,500 1261 9,381 10.79 1279 9,592 11.03 1299 9,820 11.29 1319 10,065 11.58 1341 10,327 11.88 11,000 1320 10,592 12.18 1337 10,807 12.43 1355 11,038 12.70 1374 11,284 12.98 1394 11,547 13.28 11,500 1378 11,896 13.68 — 12,000 — 12,500 —
581A300 (25 TONS) (Medium Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 1005 4,020 4.62 1052 4,390 5.05 1100 4,791 5.51 1148 5,221 6.00 1195 5673 6.52 7,000 1041 4,555 5.24 1084 4,908 5.64 1128 5,294 6.09 1172 5,710 6.57 1217 6153 7.08 7,500 1080 5,168 5.94 1119 5,508 6.33 1160 5,878 6.76 1201 6,279 7.22 1242 6708 7.71 8,000 1122 5,862 6.74 1158 6,190 7.12 1195 6,548 7.53 1233 6,934 7.97 1272 7347 8.45 8,500 1167 6,638 7.63 1200 6,959 8.00 1234 7,305 8.40 1269 7,677 8.83 1304 8076 9.29 9,000 1214 7,499 8.63 1244 7,813 8.99 1275 8,149 9.37 1308 8,511 9.79 1340 8896 10.23 9,500 1262 8,447 9.72 1290 8,754 10.07 1319 9,084 10.45 1349 9,437 10.85 1379 9812 11.28 10,000 1312 9,482 10.91 1338 9,785 11.25 1365 10,110 11.63 1392 10,454 12.02 — — — 10,500 1363 10,608 12.20 1387 10,909 12.55 — 11,000 — 11,500 — 12,000 — 12,500 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.

581A300 (25 TONS) (High Heat Units)*
External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 799 2,730 3.14 833 2,914 3.35 872 3,135 3.61 914 3,392 3.90 958 3,687 4.24 7,000 856 3,294 3.79 887 3,481 4.00 921 3,699 4.25 958 3,950 4.54 999 4,235 4.87 7,500 913 3,929 4.52 941 4,118 4.74 972 4,335 4.99 1006 4,582 5.27 1042 4,860 5.59 8,000 971 4,637 5.33 996 4,829 5.55 1024 5,046 5.80 1055 5,290 6.08 1088 5,562 6.40 8,500 1029 5,421 6.24 1052 5,617 6.46 1078 5,835 6.71 1106 6,077 6.99 1136 6,345 7.30 9,000 1087 6,285 7.23 1108 6,484 7.46 1132 6,703 7.71 1158 6,946 7.99 1185 7,211 8.29 9,500 1145 7,231 8.32 1165 7,433 8.55 1187 7,655 8.80 1211 7,898 9.08 1236 8,161 9.39 10,000 1203 8,262 9.50 1222 8,468 9.74 1243 8,693 10.00 1265 8,936 10.28 1288 9,199 10.58 10,500 1261 9,381 10.79 1279 9,592 11.03 1299 9,820 11.29 1319 10,065 11.58 1341 10,327 11.88 11,000 1320 10,592 12.18 1337 10,807 12.43 1355 11,038 12.70 1374 11,284 12.98 1394 11,547 13.28 11,500 1378 11,896 13.68 — 12,000 — 12,500 —
581A300 (25 TONS) (High Heat Units)* (cont)
External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 6,500 1005 4,020 4.62 1052 4,390 5.05 1100 4,791 5.51 1148 5,221 6.00 1195 5673 6.52 7,000 1041 4,555 5.24 1084 4,908 5.64 1128 5,294 6.09 1172 5,710 6.57 1217 6153 7.08 7,500 1080 5,168 5.94 1119 5,508 6.33 1160 5,878 6.76 1201 6,279 7.22 1242 6708 7.71 8,000 1122 5,862 6.74 1158 6,190 7.12 1195 6,548 7.53 1233 6,934 7.97 1272 7347 8.45 8,500 1167 6,638 7.63 1200 6,959 8.00 1234 7,305 8.40 1269 7,677 8.83 1304 8076 9.29 9,000 1214 7,499 8.63 1244 7,813 8.99 1275 8,149 9.37 1308 8,511 9.79 1340 8896 10.23 9,500 1262 8,447 9.72 1290 8,754 10.07 1319 9,084 10.45 1349 9,437 10.85 1379 9812 11.28 10,000 1312 9,482 10.91 1338 9,785 11.25 1365 10,110 11.63 1392 10,454 12.02 — — — 10,500 1363 10,608 12.20 1387 10,909 12.55 — 11,000 — 11,500 — 12,000 — 12,500 —
Refer to page 261 for general Fan Performance Data notes. NOTE: Maximum continuous bhp is:
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive ranges: Low Range: 805-1007 High Range: 941-1176 All other rpms require field-supplied drive.



(8 Cell) 0-2,000 29 30 29 29 2,000 29 30 29 29 3,000 30 31 30 30 4,000 30 31 30 30 5,000 30 31 30 30 6,000 30 31 30 30 7,000 31 32 31 31 8,000 31 32 31 31 9,000 31 32 31 31 above 10,000 32 33 32 32
(LP Gas)

(8 Cell) 0-2,000 35 38 35 35 2,000 36 39 36 36 3,000 36 39 36 36 4,000 37 40 37 37 5,000 37 40 37 37 6,000 38 41 38 38 7,000 39 42 39 39 8,000 40 43 40 40 9,000 41 44 41 41 above 10,000 42 45 42 42

Low Speed 208 V Med Speed 208 V High Speed 208 V
Low Speed 230,460,575V Med Speed 230,460,575V High Speed 230,460,575V
3250 3350 3450 3550 3650 3750 3850 3950 4050 4250 4450 4650 4850

(Btu/ft3) 0-2,000 1,100 2,001-3,000 1,050 3,001-4,000 1,000 4,001-5,000 950 5,001-6,000 900
(Natural Gas Units)

NATURAL GAS ORIFICE SIZE† Low Heat High Heat 0-3,000 30 29 3,000- 7,000 31 30 7,000- 9,000 32 31 9,000-10,000 33 31 above 10,000 35 32
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For eleva- tions above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code. IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.
*Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant dealer.
(LP Gas Units)


Low Heat and High Heat 0-2,000 36 2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42 10,000 43

COMPONENT CFM 4500 5000 5400 6000 7200 7500 9000 10,000 11,250 EconoMi$er IV 0.040 0.050 0.060 0.070 0.090 0.100 0.110 0.120 0.140
LEGEND *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
FIOP — Factory-Installed Option
A-WEIGHTED
UNIT 581A
Octave Bands 63 125 250 500 1000 2000 4000 8000 155 87 87.3 87.1 89.9 86.4 84.0 82.7 79.0 73.9 68.6 180 88 88.0 95.7 88.9 87.2 85.2 91.9 79.5 72.7 66.0
UNIT 581A NOMINAL HP VOLTAGE MAX WATTS EFF. % MAX BHP MAX BkW MAX AMPS
2.9 208 2700 85.8 3.13 2.34 9.46 2.9 230 2700 85.8 3.13 2.34 8.6 2.9 460 2700 85.8 3.13 2.34 4.3 3 575 3065 81.7 3.38 2.53 3.9
3.7 208 3610 85.8 4.38 3.27 10.5 3.7 230 3610 85.8 4.38 3.27 10.5 3.7 460 3610 85.8 4.38 3.27 4.8
180 5 208 5180 87.5 6.13 4.57 15.8 5 230 5180 87.5 6.13 4.57 15.8 5 460 5180 87.5 6.13 4.57 7.9 5 575 5180 87.5 6.13 4.57 6.0
BHP — Brake Horsepower BkW — Brake Kilowatts
UNIT 581A MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
155† 1147 1124 1101 1078 1055 1032 1010 987 964 941 918 895 †† 155** 1315 1292 1269 1246 1223 1200 1178 1155 1132 1109 1086 1063 1040 180† †† 1021 1002 984 965 947 928 910 891 873 180** †† 1200 1178 1156 1134 1112 1091 1069 1047 1025
*Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package. ††Due to belt and pulley style, pulley cannot be set to this number of turns open.

UNIT 581A
ARI RATING (decibels)
A-WEIGHTED
OCTAVE BANDS
(db)
63 125 250 500 1000 2000 4000 8000
155,180 88 87.6 90.8 88.7 86.4 84.3 83.5 78.4 75.6 66.8 210, 240 82 81.7 90.2 84.8 80.7 79.0 77.6 71.4 66.7 60.7 300 85 84.9 90.0 86.3 83.6 82.9 80.3 74.9 71.4 66.5
ARI — Air Conditioning and Refrigeration Institute
MOTOR PULLEY TURNS OPEN
581A DRIVE
0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6
Low Range Vertical 647 667 687 707 727 747 767 786 806 826 846 866 886
High Range Vertical 897 917 937 958 978 998 1018 1038 1058 1079 1099 1119 1139
Low Range Horizontal 896 924 951 979 1006 1034 1062 1089 1117 1144 1172 1199 1227
High Range Horizontal 1113 1138 1163 1188 1213 1238 1264 1289 1314 1339 1364 1389 1414
Low Range Vertical 810 832 854 876 897 919 941 963 985 1007 1028 1050 1072
High Range Vertical 873 893 912 932 951 971 991 1010 1030 1049 1069 1088 1108
Low Range Horizontal 863 886 909 933 956 979 1002 1025 1048 1072 1095 1118 1141
High Range Horizontal 1042 1062 1083 1103 1123 1143 1164 1184 1204 1224 1245 1265 1285
Low Range Vertical 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206
High Range Vertical 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176
Low Range Horizontal 896 924 951 979 1006 1034 1062 1089 1117 1144 1172 1199 1227
High Range Horizontal 1113 1138 1163 1188 1213 1238 1264 1289 1314 1339 1364 1389 1414
Low Range Vertical 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206
High Range Vertical 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176
Low Range Horizontal 873 893 912 932 951 971 991 1010 1030 1049 1069 1088 1108
High Range Horizontal 1113 1138 1163 1188 1213 1238 1264 1289 1314 1339 1364 1389 1414
Low Range Vertical 805 822 839 856 872 889 906 923 940 957 973 990 1007
High Range Vertical 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176
Low Range Horizontal 805 822 839 856 872 889 906 923 940 957 973 990 1007
High Range Horizontal 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176
*Approximate fan rpm shown.

UNIT 581A DRIVE ORIENTATION MOTOR
NOMINAL
HP VOLTAGE MAX WATTS
EFFICIENCY
MAX BHP
MAX AMPS
P/N
HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD58DL575 3 575 3149 81.7 3.45 2.57 3.9
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD58DL575 3 575 3149 81.7 3.45 2.57 3.9
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9
HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9
HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1
HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9
BHP — Brake Horsepower BkW — Brake Kilowatts
COMPONENT CFM 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 Economizer 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.15 0.16 0.17 0.19 0.20
LEGEND *The static pressure must be added to the external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
FIOP — Factory-Installed Option

NOMINAL VOLTAGE (3 Ph, 60 Hz)
POWER SUPPLY No. 1 No. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
COMPRESSOR OFM IFM POWER EXHAUST
COMBUSTION
UNIT 581A
RANGE
FAN MOTOR
208/230 187 253 20.7 156 20.7 156 3 0.5 1.70 2.9 8.8/ 8.4 — — 0.57 60/60 80/80 4.6 18.8 0.57 65/65 80/80
460 414 506 10.0 75 10.0 75 3 0.5 0.80 2.9 4.2 — — 0.30 29 35 2.3 6.0 0.30 31 40
575 518 633 8.2 54 8.2 54 3 0.5 0.75 3.0 3.9 — — 0.57 25 30 2.1 4.8 0.57 27 30
208/230 187 253 20.7 156 20.7 156 3 0.5 1.70 3.7 10.5/11.0 — — 0.57 62/63 80/80 4.6 18.8 0.57 67/67 80/80
460 414 506 10.0 75 10.0 75 3 0.5 0.80 3.7 4.8 — — 0.30 30 35 2.3 6.0 0.30 32 40
208/230 187 253 32.1 195 20.7 156 3 0.5 1.70 5.0 15.8/15.8 — — 0.57 82/82 110/110 4.6 18.8 0.57 86/86 110/110
460 414 506 16.4 95 10.0 75 3 0.5 0.80 5.0 7.9 — — 0.30 41 50 2.3 6.0 0.30 43 50
575 518 633 12.0 80 8.2 54 3 0.5 0.75 5.0 6.0 — — 0.57 31 40 2.1 4.8 0.57 34 45
Example: Supply voltage is 460-3-60.
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455
*Fuse or HACR circuit breaker.
= 457 Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.
= 100 x max voltage deviation from average voltage

VOLTAGE
COMPRESSOR OFM IFM POWER EXHAUST
COMBUSTION
FAN MOTOR POWER SUPPLY DISCONNECT
NOMINAL VOLTAGE
RANGE
SIZE No. 1 No. 2 No. 3
(3 Ph, 60 Hz)
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA Qty Hp FLA (ea) FLA MCA MOCP* FLA
3.7 10.6/ 9.6 — — —
78/ 77 100/ 90 83/ 82 2 1 5.9 90/ 89 100/100 97/ 96
208/230 187 253 16.7 130 16.7 130 22.4 184 4 0.25 1.5
5 16.7/15.2 — — — 84/ 83 100/100 90/ 89 2 1 5.9 96/ 94 100/100 104/102
7.5 24.2/22 — — — 92/ 89 100/100 99/ 96 2 1 5.9 104/101 125/110 112/110
3.7 4.8 — — —
39 45 42 2 1 3.1 45 50 49
5 7.6 — — — 42 50 45 2 1 3.1 48 50 52
460 414 506 9 70 9 70 10.7 90 4 0.25 0.7
7.5 11 — — — 45 50 49 2 1 3.1 51 60 56
3 3.9 — — —
32 40 35 2 1 2.4 37 45 40
575 518 633 7 55 7 55 9.3 73 4 0.25 0.7
5 6.1 — — — 35 40 37 2 1 2.4 39 45 43
7.5 9 — — — 37 45 40 2 1 2.4 42 50 46
3.7 10.6/ 9.6 — — —
89/ 88 100/100 96/ 95 2 1 5.9 101/100 110/110 110/109
5 16.7/15.2 — — — 96/ 94 100/100 103/102 2 1 5.9 107/106 125/125 117/115
208/230 187 253 22.4 184 22.4 184 22.4 184 4 0.25 1.5
7.5 24.2/22 — — — 103/101 125/110 112/109 2 1 5.9 115/113 125/125 126/123
10 30.8/28 — — — 112/108 125/125 120/116 2 1 5.9 124/120 150/125 133/130
3.7 4.8 — — —
42 50 46 2 1 3.1 49 50 53
5 7.6 — — — 45 50 49 2 1 3.1 51 60 56
460 414 506 10.7 90 10.7 90 10.7 90 4 0.25 0.7
7.5 11 — — — 49 50 53 2 1 3.1 55 60 60
10 14 — — — 52 60 56 2 1 3.1 59 60 63
5 6.1 — — —
39 45 42 2 1 2.4 44 50 48
7.5 9 — — — 42 50 46 2 1 2.4 47 50 51
575 518 633 9.3 73 9.3 73 9.3 73 4 0.25 0.7
10 11 — — — 44 50 48 2 1 2.4 49 60 53
5 16.7/15.2 — — —
132/130 175/175 138/136 2 1 5.9 143/142 175/175 151/150
208/230 187 253 47.1 245 47.1 245 — — 6 0.25 1.5
7.5 24.2/22 — — — 139/137 175/175 147/144 2 1 5.9 151/149 175/175 160/158
10 30.8/28 — — — 146/143 175/175 154/151 2 1 5.9 158/155 200/200 168/164
5 7.6 — — —
56 60 59 2 1 3.1 62 80 66
7.5 11 — — — 59 60 63 2 1 3.1 66 80 70
460 414 506 19.6 125 19.6 125 — — 6 0.25 0.7
10 14 — — — 62 80 66 2 1 3.1 69 80 73
5 6.1 — — —
46 60 48 2 1 2.4 51 60 54
575 518 633 15.8 100 15.8 100 — — 6 0.25 0.7
7.5 9 — — — 49 60 52 2 1 2.4 54 60 57
10 11 — — — 51 60 54 2 1 2.4 56 60 59
Example: Supply voltage is 460-3-60.
FLA — Full Load Amps MCA — Minimum Circuit Amps HACR — Heating, Air Conditioning and MOCP— Maximum Overcurrent Protection Refrigeration NEC — National Electrical Code IFM — Indoor (Evaporator) Fan Motor OFM — Outdoor (Condenser) Fan Motor LRA — Locked Rotor Amps RLA — Rated Load Amps MCA — Minimum Circuit Amps
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455 3
*Fuse or HACR circuit breaker.
= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 100 x max voltage deviation from average voltage
average voltage

VOLTAGE
COMPRESSOR OFM IFM POWER EXHAUST
COMBUSTION
FAN MOTOR POWER SUPPLY DISCONNECT
NOMINAL VOLTAGE
RANGE
SIZE No. 1 No. 2 No. 3
(3 Ph, 60 Hz)
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA Qty Hp FLA (ea) FLA MCA MOCP* FLA
3.7 10.6/ 9.6 — — —
83/ 82 100/100 89/ 88 2 1 5.9 95/ 94 100/100 103/101
208/230 187 253 16.7 130 16.7 130 22.4 184 4 0.25 1.5
5 16.7/15.2 — — — 89/ 88 100/100 96/ 94 2 1 5.9 101/ 99 110/100 110/108
7.5 24.2/22 — — — 97/ 94 100/100 105/102 2 1 5.9 109/106 125/125 118/116
3.7 4.8 — — —
42 50 45 2 1 3.1 48 50 52
5 7.6 — — — 45 50 48 2 1 3.1 51 60 56
460 414 506 9 70 9 70 10.7 90 4 0.25 0.7
7.5 11 — — — 48 50 52 2 1 3.1 54 60 59
3 3.9 — — —
35 40 38 2 1 2.4 40 45 43
575 518 633 7 55 7 55 9.3 73 4 0.25 0.7
5 6.1 — — — 38 45 40 2 1 2.4 42 50 46
7.5 9 — — — 40 45 44 2 1 2.4 45 50 49
3.7 10.6/ 9.6 — — —
94/ 93 100/100 102/101 2 1 5.9 106/105 125/125 116/115
5 16.7/15.2 — — — 101/ 99 110/100 109/107 2 1 5.9 112/111 125/125 123/121
208/230 187 253 22.4 184 22.4 184 22.4 184 4 0.25 1.5
7.5 24.2/22 — — — 108/106 125/125 118/115 2 1 5.9 120/118 125/125 131/129
10 30.8/28 — — — 117/113 125/125 125/122 2 1 5.9 129/125 150/150 139/136
3.7 4.8 — — —
45 50 49 2 1 3.1 52 60 56
5 7.6 — — — 48 50 52 2 1 3.1 54 60 59
460 414 506 10.7 90 10.7 90 10.7 90 4 0.25 0.7
7.5 11 — — — 52 60 56 2 1 3.1 58 60 63
10 14 — — — 55 60 60 2 1 3.1 62 70 67
5 6.1 — — —
42 50 46 2 1 2.4 47 50 51
7.5 9 — — — 45 50 49 2 1 2.4 50 50 55
575 518 633 9.3 73 9.3 73 9.3 73 4 0.25 0.7
10 11 — — — 47 50 51 2 1 2.4 52 60 57
5 16.7/15.2 — — —
137/135 175/175 144/142 2 1 5.9 148/147 175/175 157/155
208/230 187 253 47.1 245 47.1 245 — — 6 0.25 1.5
7.5 24.2/22 — — — 144/142 175/175 152/150 2 1 5.9 156/154 200/200 166/163
10 30.8/28 — — — 151/148 175/175 160/157 2 1 5.9 163/160 200/200 173/170
5 7.6 — — —
59 60 62 2 1 3.1 65 80 69
7.5 11 — — — 62 80 66 2 1 3.1 69 80 73
460 414 506 19.6 125 19.6 125 — — 6 0.25 0.7
10 14 — — — 65 80 69 2 1 3.1 72 90 77
5 6.1 — — —
49 60 52 2 1 2.4 54 60 57
575 518 633 15.8 100 15.8 100 - - 6 0.25 0.7
7.5 9 — — — 52 60 55 2 1 2.4 57 60 60
10 11 — — — 54 60 57 2 1 2.4 59 60 63
Example: Supply voltage is 460-3-60.
FLA — Full Load Amps MCA — Minimum Circuit Amps HACR — Heating, Air Conditioning and MOCP— Maximum Overcurrent Protection Refrigeration NEC — National Electrical Code IFM — Indoor (Evaporator) Fan Motor OFM — Outdoor (Condenser) Fan Motor LRA — Locked Rotor Amps RLA — Rated Load Amps MCA — Minimum Circuit Amps
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455 3
*Fuse or HACR circuit breaker.
= 1371 3 = 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 100 x max voltage deviation from average voltage
average voltage

AHA — Adjustable Heat Anticipator C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor CR — Control Relay DM — Damper Motor DU — Dummy Terminal EQUIP — Equipment FPT — Freeze Protection Thermostat FU — Fuse GND — Ground HPS — High-Pressure Switch HS — Hall Effect Sensor HV — High Voltage I — Ignitor IDM — Induced Draft Motor IFC — Indoor Fan Contactor IFM — Indoor (Evaporator) Fan Motor IGC — Integrated Gas Unit Controller L — Light LOR — Lockout Relay LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve OFC — Outdoor Fan Contactor OFM — Outdoor Fan Motor PL — Plug Assembly PRI — Primary QT — Quadruple Terminal RS — Rollout Switch SW — Switch TB — Terminal Block TC — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer Terminal (Marked)
Option/Accessory Wiring To indicate common potential only. Not to represent wiring.

LEGEND AL — Ambient Limit OA — Outdoor Air ECB — Economizer Control Board OAS— Outdoor Air Sensor IA — Indoor Air RAS— Return Air Sensor IAQ — Indoor Air Quality SAT — Supply Air Temperature
RED
500 OHM RESISTOR
PINK
BLUE NOTE 1
RUN
OAT
BLACK
NOTE 2
50HJ540573 ACTUATOR ASSEMBLY
581A155-300
DIRECT DRIVE
WHITE
ACTUATOR
ECONOMISER2 PLUG
LEGEND OAT — Outdoor Air Temperature Sensor NOTES:
a48-7877 · a50-8058

LEGEND NEC — National Electrical Code b48-1258

PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 13 AND 15 TONS (581A), 15 TO 25 TONS
the NFPA 90 flame retardance requirements and has an ‘‘R’’ Value of 3.70. Aluminum foil-faced fiber- glass insulation shall be used in the gas heat compartment. 3. Cabinet panels shall be easily removable for servic- ing. Cabinet panels are minimum 20 gage. Panels shall have 1/2-in. thick, 1.5-lb. density insulation. 4. Filters shall be accessible through an access panel. 5. Holes shall be provided in the base rails (minimum 12 gage) for rigging shackles to facilitate overhead rigging. 6. Unit shall contain a sloped drain pan, to prevent standing water from accumulating. Pan shall be fabri- cated of hot dipped zinc coated minimum spangle steel. Zinc coating shall be G90 designation accord- ing to ASTM Standard A653. Unit shall contain a factory-installed nonferrous main condensate drain connection. C. Fans:
(579F, 580F), NOMINAL (COOLING) 230,000 TO 360,000 BTUH, NOMINAL (INPUT HEATING) (GAS UNITS) BRYANT MODEL NUMBERS: 580F, 579F, 581A PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Unit is an outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing scroll hermetic compres- sors for cooling duty and gas combustion for heating duty. Supply air shall be discharged downward or horizontally (with horizontal supply/return curb adapter assembly), as shown on contract drawings. Standard unit shall include a manual outdoor-air inlet. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standards 270
and 360 and all units shall be designed in accordance with UL Standard 1995. NOTE: Size 300 units are beyond the scope of ARI certifi- cation guidelines. B. Unit shall be designed to conform to ASHRAE 15. C. Unit shall be ETL and ETL, Canada tested and certified in
an adjustable pulley. The standard fan drive shall have a factory-installed low-medium external static pressure capable fan drive. The alternate fan drive option shall have a factory-installed external high static pressure capable fan drive. b. Fan wheel shall be made from steel with a
accordance with ANSI Z21.47 Standards as a total package. D. Roof curb shall be designed to conform to NRCA
corrosion-resistant finish. It shall be a dynamically balanced, double-inlet type with forward-curved blades. 2. Condenser fans shall be of the direct-driven propeller type, with corrosion-resistant blades riveted to corrosion-resistant steel supports. They shall be dynamically balanced and discharge air upwards. 3. Induced-draft blower shall be of the direct-driven, single inlet, forward-curved, centrifugal type. It shall be made from steel with a corrosion-resistant finish and shall be dynamically balanced. D. Compressor(s):
Standards. E. Insulation and adhesive shall meet NFPA 90A require-
ments for flame spread and smoke generation. F. Unit casing shall be capable of withstanding 500-hour salt
spray exposure per ASTM B117 (scribed specimen). G. Unit shall be manufactured in a facility registered to
ISO 9001:2000. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recommendations. PART 2 — PRODUCTS 2.01 EQUIPMENT (STANDARD) A. General:
Each unit shall be a factory assembled, single-piece heat- ing and cooling unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:
1. Constructed of galvanized steel (G90 — 1.8 oz. of zinc per square foot of sheet metal), bonderized and primer-coated on both sides and coated with a baked polyester thermosetting powdercoating finish on the outer surface. The color of this pre-painted steel is referred to as “American Sterling,” a gray color. Bryant’s paint specification for this color is PH184. Color: American Sterling, this gray color is to match federal standard 595a, #26231. Gloss (per ASTM 0523, 60 deg. F): 60. Hardness of paint film: H-2H pencil hardness. 2. Indoor blower compartment interior surfaces shall be insulated with a minimum 1/2-in. thick, 1 lb density fiberglass insulation. Fiberglass insulation shall be bonded with a thermosetting resin (8 to 12% by weight nominal, phenol formaldehyde typical), and coated with an acrylic or other material that meets
be tubular-section design and shall be constructed of a minimum 20 gage, 409 stainless steel.

Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office.
Refrigerant circuit components shall include:
a durable epoxy-phenolic coating to provide pro- tection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize gal- vanic action between dissimilar metals. b. Optional copper-fin coils shall be constructed of
Standard filter section shall consist of 2 sizes of factory- installed 2-in. thick throwaway fiberglass filters of com- mercially available sizes. Filters shall be approximately 10% efficient with an airside pressure drop of approxi- mately 0.07 in. wg (clean). I. Controls and Safeties:
copper fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for gal- vanic corrosion between coil and pan. All copper construction shall provide protection in moderate coastal environments. c. E-Coated aluminum-fin coils shall have a flexible
voltage control circuit. J. Safeties:
a. Unit shall incorporate a solid-state compressor
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be alumi- num fins mechanically bonded to copper tubes. d. E-Coated copper-fin coils shall have a flexible
lockout which provides reset capability at the space thermostat, should any of the following safety devices trip and shut off compressor: 1) Compressor lockout protection provided for either internal or external overload. 2) Low-pressure switch. 3) Dual freezestats (evaporator coil). 4) High-pressure switch. b. Supply-air thermostat shall be located in the unit. c. Heating section shall be provided with the follow-
ing minimum protections: 1) High-temperature limit switch. 2) Induced-draft motor speed sensor. 3) Flame rollout switch. 4) Flame proving controls. 5) Redundant gas valve. K. Operating Characteristics:
epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting sheet metal coil pan to maintain coating integrity and minimize corrosion potential between coil and pan.
All unit power wiring shall enter unit cabinet at a single location. M. Motors:

n. EconoMi$er IV controller Unoccupied Minimum
Damper Position Setting — The EconoMi$er IV dampers shall be completely closed when the unit is in the occupied mode. o. EconoMi$er IV controller IAQ/DCV Maximum
nailer strip and shall be capable of supporting entire unit weight. b. Permits installing and securing ductwork to curb
Damper Position Setting — Setting the maximum position of the damper prevents the introduction of large amounts of hot or cold air into the space. This position is intended to satisfy the base mini- mum ventilation rate. p. EconoMi$er IV controller IAQ/DCV control modu-
prior to mounting unit on the curb. 3. Horizontal Adapter Roof Curb: Includes factory-assembled adapter and internal duct and substantially improves evaporator fan static performance (static regain). NOTE: Power exhaust or barometric relief must be mounted in the return ductwork when used in con- junction with this accessory. * 4. Integrated Economizers: a. Integrated integral modulating type capable of
lates the outdoor-air damper to provide ventilation based on the optional 2 to 10 vdc CO2 sensor input. q. Compressor lockout sensor (opens at 35 F,
closes at 50 F). r. Actuator shall be direct coupled to economizer
simultaneous economizer and compressor operation. b. Available as a factory-installed option in vertical
gear, eliminating linkage arms and rods. s. Control LEDs:
supply/return configuration only. (Available as a field-installed accessory for horizontal and/or ver- tical supply return configurations.) c. Includes all hardware and controls to provide
cooling with outdoor air. d. Equipped with low-leakage dampers, not to
exceed 2% leakage at 1 in. wg pressure differential. e. Capable of introducing up to 100% outdoor air.
installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation. 5. Two-Position Damper: Two-position damper package shall include single blade damper and 24-v motor. Admits up to 25% outdoor air, and shall close upon unit shutoff. Damper shall cover 3.8-in. high by 17.75-in. wide (117.8 sq. in.) opening in return air upper panel. 6. Accessory Compressor Cycle Delay: Compressor shall be prevented from restarting for a minimum of 5 minutes after shutdown. * 7. Thermostats and Subbases: To provide staged heating and cooling in addition to automatic (or manual) changeover and fan control. * 8. Barometric Relief Damper Package: a. Package shall include damper, seals, hardware,
f. EconoMi$er IV and EconoMi$er2 shall be
equipped with a barometric relief damper. g. Designed to close damper(s) during loss-of-
power situations with spring return built into motor. h. Dry bulb outdoor-air temperature sensor shall be
provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F. For the EconoMi$er IV, the return air sensor, indoor enthalpy sensor, and outdoor enthalpy sensor shall be provided as field- installed accessories to provide enthalpy control, differential enthalpy control, and differential dry bulb temperature control. For the EconoMi$er2, the enthalpy, differential temperature (adjustable), and differential enthalpy control shall be provided as field-installed accessories. i. EconoMi$er IV controller shall use a mixed air
thermistor mounted on the evaporator fan hous- ing to control EconoMi$er IV operation to a sup- ply air temperature of 55 F. j. The EconoMi$er IV and EconoMi$er2 shall have
and hoods to relieve excess internal pressure. b. Damper shall close due to gravity upon unit
shutdown. c. Damper package must be field-installed in return-
a gear-driven parallel blade design. k. EconoMi$er IV controller shall provide control of
air ductwork when used with optional side return connections. * 9. Power Exhaust: Package shall include an exhaust (propeller style) fan, 1/2 Hp 208-230, 460 v (factory-wired for 460 v) direct drive motor, and damper for vertical flow units with economizer to control over-pressurization of building. Power Exhaust package must be field- installed in return-air ductwork when used with optional side return connections. * 10. Head Pressure Control Package: Consists of an accessory outdoor-air package and a solid-state control with condenser coil temperature sensor for controlling condenser-fan motor speed to maintain condensing temperature between 90 F and 100 F at outdoor ambient temperature down to –20 F.
internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%. l. EconoMi$er2 shall be capable of control from a
4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control (required for third party control interface). m. EconoMi$er IV controller Occupied Minimum
Damper Position Setting maintains the minimum airflow into the building during occupied period providing design ventilation rate for full occu- pancy (damper position during heating). A remote potentiometer may be used to override the set point.

lamps have an output rating at 45 F in 400 fpm air- flow of 120 microwatts/cm2 at 1 meter. 22. Stainless Steel Condensate Pan: Stainless steel condensate pans shall be available for condensate collection. 23. Light Commercial Thermidistat™ Device: Shall regulate temperature and humidity from one location. Automatic humidity control adjusts indoor humidity level between 50 and 90% RH (relative humidity) based on the outdoor temperature sensor. 24. Fan/Filter Status Switch: Provides status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat. 25. Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year-round ventilation. 26. High-Static Motor(s) and Drive(s): High-static motor(s) and drive(s) shall be factory- installed to provide additional performance range. 27. Indoor Air Quality (CO2) Sensor: a. Shall have the ability to provide demand ventila-
and humidity) of outdoor air and indoor air and controlling economizer cut-in point at the most economical level. NOTE: Two accessory enthalpy sensors are required for differential enthalpy control. * 13. Electronic Programmable Thermostat: Capable of using deluxe full-featured electronic thermostat. 14. Winter Start Time-Delay Relay: Used in conjunction with the accessory low-ambient kit or head pressure control device, permits opera- tion in cooling at lower outdoor ambient tempera- tures. See price pages for more information. 15. Liquid Propane Conversion Kit: Kit shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane gas. 16. Hinged Access Panels for the Filter, Compressors, Evaporator Fan, and Control Box Areas:
tion indoor air quality (IAQ) control through the economizer with an IAQ sensor. b. The IAQ sensor shall be available in duct mount,
Filter hinged access panels permit tool-less entry for changing filters. Evaporator fan hinged access panel shall be field-convertible to a tool-less entry by removing and discarding screws. Each external hinged access panel shall be permanently attached to the rooftop unit. 17. Convenience Outlet: Shall be factory-installed and internally mounted with an externally accessible 115-v, 15 amp. GFI, female receptacle with hinged cover. Voltage required to operate convenience outlet shall be provided by a field-installed separate branch circuit. 18. Non-Fused Disconnect Switch: Shall be factory-installed, internally mounted, NEC and UL approved non-fused switch shall provide unit power shutoff. The control access door shall be interlocked with the non-fused disconnect. The dis- connect switch must be in the OFF position to open the control box access door. Shall be accessible from outside the unit and shall provide power off lockout capability. 19. Alternate Drive: Shall provide higher static drive capability to en- hance evaporator-fan performance rpm range. 20. Hail Guard, Condenser Coil Grille: Shall protect the condenser coil from hail, flying debris, and damage by large objects without increas- ing unit clearances. 21. Ultraviolet Germicidal Lamps: Ultraviolet germicidal lamps are designed to elimi- nate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germicidal lamps are field installed in the evaporator section of the unit, aimed at the evaporator coil and conden- sate pan. The short wavelength ultraviolet light inhib- its and kills mold, fungus and microbial growth. The
wall mount, and wall mount with LED display. The set point shall have adjustment capability. 28. Return Air CO2 Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be duct mounted. The set point shall have adjustment capability. 29. Outdoor Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2):
The outdoor air enthalpy sensor shall be used to pro- vide single enthalpy control. When used in conjunc- tion with a return air enthalpy sensor, the controller will provide differential enthalpy control. The sensor allows the controller to determine if outside air is suitable for free cooling. 30. Return Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2):
The return air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with an outdoor air enthalpy sensor, the controller will provide differential enthalpy control. 31. Return Air Temperature Sensor (EconoMi$er IV or EconoMi$er2):
The return air temperature sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with the standard outdoor air tem- perature sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential temperature control. 32. Indoor Air Quality (CO2) Room Sensor (EconoMi$er IV):
Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be wall mounted with an LED display in parts per million. The set point shall have adjustment capability.

2. Indoor blower compartment interior surfaces shall be insulated with a minimum 1/2-in. thick, 1 lb density fiberglass insulation. Fiberglass insulation shall be bonded with a thermosetting resin (8 to 12% by weight nominal, phenol formaldehyde typical), and coated with an acrylic or other material that meets the NFPA 90 flame retardance requirements and has an ‘‘R’’ Value of 3.70. Aluminum foil-faced fiber- glass insulation shall be used in the gas heat compartment. 3. Cabinet panels shall have minimum 1/2-in. thick, 1.5-lb. density insulation. Each external access panel shall be permanently attached to the rooftop unit. Panels shall also include tiebacks. 4. Filters shall be accessible through an access panel. 5. Holes shall be provided in the base rails (minimum 14 gage) for rigging shackles and level travel and movement during overhead rigging operations. 6. Fork lift slots shall be available from two sides of the unit (end and side). 7. Unit shall contain a sloped drain pan, to prevent standing water from accumulating. Pan shall be fabri- cated of epoxy powder coated steel. C. Fans:
250,000 TO 400,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBERS: 581A
PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Unit is an outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing scroll hermetic compres- sors with crankcase heaters for cooling duty and gas com- bustion heat for heating duty. Supply air shall be discharged downward or horizontally, as shown on con- tract drawings. 1.02 QUALITY ASSURANCE A. Unit shall well exceed the energy efficiency requirements
of ASHRAE standard 90.1-2001. Unit shall be Energy Star qualified. B. Unit shall be rated in accordance with ARI Standards 270
block ball bearings and adjustable belt drive. Blower assembly shall slide out of unit for servicing. b. Fan wheel shall be made from steel with a corro-
and 360 and all units shall be designed in accordance with UL Standard 1995. C. Unit shall be designed to conform to ASHRAE 15. D. Unit shall be UL and UL, Canada, tested and certified in
sion resistant finish. It shall be a dynamically bal- anced, double-inlet type with forward-curved blades. c. The indoor fan system (blower wheels, motors,
accordance with ANSI Z21.47 Standards as a total package. E. Roof curb shall be designed to conform to NRCA
belts, and both bearings) shall slide out for easy access. 2. Condenser fans shall be of the direct-driven propeller type, with corrosion-resistant blades riveted to corro- sion-resistant steel supports. They shall be dynami- cally balanced and discharge air upwards. Condenser fan motors shall be totally enclosed and be of a shaft down design. 3. Induced-draft blower shall be of the direct-driven, sin- gle inlet, forward-curved, centrifugal type. It shall be made from steel with a corrosion-resistant finish and shall be dynamically balanced. D. Compressor(s):
Standards. F. Insulation and adhesive shall meet NFPA 90A require-
ments for flame spread and smoke generation. G. Unit casing shall be capable of withstanding 500-hour salt
spray exposure per ASTM B117 (scribed specimen). H. Unit shall be manufactured in a facility registered to
ISO 9001:2000. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recommendations. PART 2 — PRODUCTS 2.01 EQUIPMENT (STANDARD) A. General:
The 581A unit shall be a factory assembled, single-piece heating and cooling unit. Contained within the unit enclo- sure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:
1. Constructed of galvanized steel (G90 — 1.8 oz. of zinc per square foot of sheet metal), bonderized and primer-coated on both sides and coated with a baked polyester thermosetting powdercoating finish on the outer surface. The color of this pre-painted steel is referred to as “American Sterling,” a gray color. Bry- ant’s paint specification for this color is PH184. Color: American Sterling, this gray color is to match federal standard 595a, #26231. Gloss (per ASTM 0523, 60 deg. F): 60. Hardness of paint film: H-2H pencil hardness.

3. Optional pre-coated aluminum-fin coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy- phenolic barrier shall minimize galvanic action between dissimilar metals. 4. Copper-fin coils shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper construction shall provide protection in moderate coastal environments. 5. E-Coated aluminum-fin coils shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsu- lation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteris- tics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794- 93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be aluminum fins mechani- cally bonded to copper tubes. 6. E-Coated copper-fin coils shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteris- tics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794- 93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be accept- able. A polymer strip shall prevent coil assembly from contacting sheet metal coil pan to maintain coating integrity and minimize corrosion potential between coil and pan. F. Heating Section:
Each refrigerant circuit shall include:
Standard filter section shall consist of factory-installed 2-in. thick throwaway fiberglass filters. I. Controls and Safeties:
lockout which provides optional reset capability at the space thermostat, should any of the following safety devices trip and shut off compressor: 1) Compressor lockout protection provided for either internal or external overload. 2) Low-pressure protection. 3) Freeze protection (evaporator coil). 4) High-pressure protection (high pressure switch or internal). b. Induced draft heating section shall be provided
with the following minimum protections: 1) High-temperature limit switch. 2) Induced-draft motor speed sensor. 3) Flame rollout switch. 4) Flame proving controls. 5) Redundant gas valve. J. Operating Characteristics:
All unit power wiring shall enter unit cabinet at a single location. L. Motors:

M. Special Features:
q. Control LEDs:
Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office.
nailer strip and shall be capable of supporting entire unit weight. b. Permits installing and securing ductwork to curb
prior to mounting unit on the curb. c. Retrofit roof curb kit shall be available for fit up to
installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation. * 3. Barometric Relief Damper Package: a. Package shall include damper, seals, hardware,
existing Bryant roof curbs. * 2. Integrated Economizer: a. Integrated integral modulating type capable
of simultaneous economizer and compressor operation. b. Available as a factory-installed option in vertical
and hoods to relieve excess internal pressure. b. Damper shall close due to gravity upon unit
shutdown. * 4. Power Exhaust: Package shall include an exhaust (centrifugal style) fan, 1 Hp 208-230, 460 v (factory-wired for 460 v) direct-drive motor, and damper for vertical flow units with economizer to control over-pressurization of building. * 5. Thermostats and Subbases: Units shall provide staged heating and cooling in addition to automatic (or manual) changeover and fan control. 6. Hot Gas Bypass Dehumidification Package: The dehumidification package is a factory-installed option that provides increased dehumidification by diverting hot gas from the compressor to the HGRH coil to provide approximately 75 F leaving air tem- perature dehumidifying the air but NOT overcooling the space. The package consists of a single row, 12.25 sq ft subcooling coil located on the leaving air- side of the evaporator coil. The location of this coil in the indoor airstream greatly enhances the latent capacity of the unit. The package shall be equipped with low pressure switch(es) and TXVs. Low pressure switch(es) pre- vents evaporator coil freeze-up and TXVs assure a positive superheat condition. If the operation of the Hot Gas Reheat (HGRH) coil is controlled by a field- installed wall-mounted humidistat, the dehumidifica- tion circuit will then operate only when needed. Optional field connections for the humidistat are made in the low voltage compartment of the unit control box. 7. Humidistat: Field-installed, wall-mounted humidistat is used to control activation of the dehumidification package. The humidistat can be set for humidity levels between 20% and 80% relative humidity. * 8. Electronic Programmable Thermostat: Thermostat shall be capable of using deluxe full- featured electronic thermostat. 9. Liquefied Propane Conversion Kit: Kit shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane gas. 10. Convenience Outlet: Outlet shall be factory-installed and internally mounted with an externally accessible 115-v, 15 amp GFI, female receptacle with hinged cover. A step down transformer shall be included so no additional wiring is necessary.
supply/return configuration only. (Available as a field-installed accessory for dedicated horizontal and/or vertical supply return configurations.) c. Includes all hardware and controls to provide
cooling with outdoor air. d. Equipped with low-leakage dampers, not to
exceed 2% leakage at 1 in. wg pressure differential. e. Capable of introducing up to 100% outdoor air.
f. EconoMi$er IV shall be equipped with a baromet-
ric relief damper. g. Designed to close damper(s) during loss-of-
power situations with spring return built into motor. h. Dry bulb outdoor-air temperature sensor shall be
provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F. For the EconoMi$er IV, the return air sensor, indoor enthalpy sensor, and outdoor enthalpy sensor shall be provided as field-installed accessories to pro- vide enthalpy control, differential enthalpy control, and differential dry bulb temperature control. i. EconoMi$er IV controller shall use a mixed air
thermistor mounted on the evaporator fan hous- ing to control EconoMi$er IV operation to a sup- ply air temperature of 55 F. j. The EconoMi$er IV shall have a gear-driven par-
allel blade design. k. EconoMi$er IV controller shall provide control of
internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%. l. EconoMi$er IV controller Occupied Minimum
Damper Position Setting maintains the minimum airflow into the building during occupied period providing design ventilation rate for full occupancy (damper position during heating). A remote poten- tiometer may be used to override the set point. m. EconoMi$er IV controller Unoccupied Minimum
Damper Position Setting — The EconoMi$er IV dampers shall be completely closed when the unit is in the occupied mode. n. EconoMi$er IV controller IAQ/DCV control modu-
lates the outdoor-air damper to provide ventilation based on the optional 2 to 10 vdc CO2 sensor input. o. Compressor lockout sensor (opens at 35 F,
closes at 50 F). p. Actuator shall be direct coupled to economizer
gear, eliminating linkage arms and rods.

11. Non-Fused Disconnect Switch: Switch shall be factory-installed, internally mounted, NEC and UL approved. Non-fused switch shall pro- vide unit power shutoff. Shall be accessible from out- side the unit and shall provide power off lockout capability. 12. Hail Guard, Condenser Coil Grille: Grille shall protect the condenser coil from hail, flying debris, and damage by large objects without increas- ing unit clearances. 13. Horizontal Kit: Horizontal kit shall contain all the necessary hard- ware to convert a vertical airflow unit to a horizontal airflow unit. The unit shall also be available as a horizontal air- flow unit directly from the factory. 14. Return Air Smoke Detector: The smoke detector shall send input to the controller to shut down the unit in case smoke is detected. The smoke detector shall be factory installed in the return air section or shall be available as a field-installed accessory. 15. Two-Position Damper: The damper shall admit up to 25% outdoor air and shall close upon shutdown. The package shall include a single-blade damper and motor. 16. Manual Damper: The damper shall have a manually adjustable out- side air intake for up to 33% outside air. 17. 30% Filters: The filters shall be 30% efficient. The filters shall be 2-in., pleated filters. 18. Standard Motor with Alternate Drive: The alternate drive shall provide high-static drive capability to enhance evaporator fan performance. 19. Alternate Motor with Standard Drive: The alternate motor shall provide high-static motor capability to enhance evaporator fan performance. 20. Alternate Motor with Optional Drive: The alternate motor and optional drive shall provide high-static motor and drive capability to enhance evaporator fan performance. 21. Four-in. Filter Capability: The unit shall be capable of accepting 4-in. filters by removal of the factory-supplied 2-in. filters and filter rack and installation of a specially designed filter bracket. 22. Supply Air Smoke Detector: The smoke detector shall send input to the controller to shut down the unit in case smoke is detected. The smoke detector shall be factory installed in the sup- ply air section or shall be available as a field- installed accessory. 23. Supply and Return Air Smoke Detector: The smoke detector shall send input to the controller to shut down the unit in case smoke is detected. The smoke detector shall be factory installed in the sup- ply and return air sections or shall be available as a field-installed accessory.
24. HACR Breaker: The HACR circuit breaker shall be factory installed. 25. Thru-the-Curb Utility Connectors: Kit shall provide connectors to permit gas and elec- trical connections to be brought to the unit through the roof curb. 26. Condensate Overflow Switch: The condensate overflow switch shall close when the condensate level in the pan rises above switch. 27. Outdoor Air Enthalpy Sensor (EconoMi$er IV): The outdoor air enthalpy sensor is used to sense outdoor air enthalpy for the EconoMi$er IV device. The outdoor air humidity sensor, in conjunction with the standard outdoor air temperature sensor, shall be used with the EconoMi$er IV device to provide outdoor enthalpy. Outdoor air enthalpy shall be cal- culated by the EconoMi$er IV device from the out- door air temperature and enthalpy readings. When the outdoor air enthalpy sensor is installed, the EconoMi$er IV can perform Outdoor Air Enthalpy control. With the additional installation of an acces- sory return air temperature sensor and return air enthalpy sensor, differential enthalpy control can also be performed. 28. Return Air Enthalpy Sensor (EconoMi$er IV): The return air enthalpy sensor is used to sense return air enthalpy for the EconoMi$er IV device. The return air enthalpy sensor, in conjunction with the accessory return air temperature sensor, shall be used with the EconoMi$er IV device to provide return air enthalpy. Return air enthalpy shall be cal- culated by the EconoMi$er IV device from the return air temperature and humidity readings. With the additional installation of an accessory return air tem- perature sensor and outdoor air enthalpy sensor, dif- ferential enthalpy control can also be performed. 29. Return Air Temperature Sensor (EconoMi$er IV): The return air temperature sensor is used to sense return air temperature for the EconoMi$er IV device. When the return air temperature sensor is installed, the EconoMi$er IV can perform Differential Tempera- ture control. The return air temperature sensor, in conjunction with the accessory return air humidity sensor, shall be used with the EconoMi$er IV device to provide return air enthalpy. Return air enthalpy shall be calculated by the EconoMi$er IV device from the return air temperature and humidity read- ings. With the additional installation of an accessory return air enthalpy sensor and outdoor air humidity sensor, differential enthalpy control can also be per- formed. 30. Indoor Air Quality (CO2) Room Sensor (EconoMi$er IV:
Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be wall mounted with an LED display in parts per million. The set point shall have adjustment capability. 31. Return Air CO2 Sensor (EconoMi$er IV): Sensor shall have the ability to provide demand ven- tilation control through the EconoMi$er IV. The IAQ sensor shall be duct mounted. The set point shall have adjustment capability.

OPERATING SEQUENCE, SIZE 024-151 UNITS Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor-fan motor runs continuously while unit is cooling. For units with 2 stages of cooling, if the thermostat calls for a second stage of cooling by energizing Y2, compressor contac- tor no. 2 (C2) is energized and compressor no. 2 starts. Heating, Units Without Economizer — When the thermostat calls for heating, terminal W1 is energized. To prevent thermo- stat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. Cooling, Units With EconoMi$er IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F mixed-air temperature into the zone. As the mixed-air temperature fluctuates above 55 or below 50 F, the dampers will be modulated (open or close) to bring the mixed-air temper- ature back within control. If mechanical cooling is utilized with free cooling, the outdoor-air damper will maintain its current position at the time the com- pressor is started. If the increase in cooling capacity causes the mixed-air temperature to drop below 45 F, then the outdoor-air damper position will be decreased to the minimum position. If the mixed-air temperature continues to fall, the outdoor-air damper will close. Control returns to normal once the mixed-air temperature rises above 48 F. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. For EconoMi$er IV operation, there must be a thermostat call for the fan (G). If the unit is occupied and the fan is on, the damper will operate at minimum position. Otherwise, the damper will be closed when the thermostat is satisfied. When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV damper to the minimum position. On the initial power to the EconoMi$er IV control, it will take the damper up to 21/2 minutes before it begins to position itself. Any change in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes. If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differ- ential dry bulb, or differential enthalpy), then the control will modulate the dampers open to maintain the mixed-air tempera- ture set point at 50 to 55 F.
If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature set point. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor. Heating, Units With Economizer NOTE: The units have 2 stages of heat. When the thermostat calls for heating, power is sent to W1 on the IGC (integrated gas unit controller) board. An LED (light- emitting diode) on the IGC board will be on during normal oper- ation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition acti- vation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be energized (and the outdoor- air dampers will open to their minimum position). If for some reason the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, inter- rupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop (and the outdoor-air dampers will close). If the overtemper- ature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 min- utes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. When the thermostat is satisfied and W1 and W2 are deener- gized, the IFM continues to run and the economizer damper then moves to the minimum position. OPERATING SEQUENCE, 580F180-300, 579F150-300 AND 581A155,180 Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motor (IFM), com- pressor no. 1 and condenser fan(s) start. The condenser-fan motor(s) runs continuously while unit is cooling. When the ther- mostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.

Heating, Units Without Economizer — When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition acti- vation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be energized. If for some reason the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, inter- rupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop. If the overtemperature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. An LED indicator is provided on the IGC to monitor operation. The IGC is located by removing the side panel and viewing the IGC through the view port located in the control box access panel. During normal operation, the LED is continuously on. Cooling, Units With EconoMi$er IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F mixed-air temperature into the zone. As the mixed-air temperature fluctuates above 55 or below 50 F, the dampers will be modulated (open or close) to bring the mixed-air temper- ature back within control. If mechanical cooling is utilized with free cooling, the outdoor-air damper will maintain its current position at the time the com- pressor is started. If the increase in cooling capacity causes the mixed-air temperature to drop below 45 F, then the outdoor-air damper position will be decreased to the minimum position. If the mixed-air temperature continues to fall, the outdoor-air damper will close. Control returns to normal once the mixed-air temperature rises above 48 F. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). If the unit is occupied and the fan is on, the damper will operate at minimum position. Otherwise, the damper will be closed. When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV damper to the minimum position. On the initial power to the EconoMi$er IV control, it will take the damper up to 21/2 minutes before it begins to position itself. Any change in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes. If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differ- ential dry bulb, or differential enthalpy), then the control will modulate the dampers open to maintain the mixed-air tempera- ture set point at 50 to 55 F. If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature set point. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor. Heating, Units With Economizer NOTE: The units have 2 stages of heat. When the thermostat calls for heating, power is sent to W1 on the IGC (integrated gas unit controller) board. An LED (light- emitting diode) on the IGC board will be on during normal oper- ation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition acti- vation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be energized (and the outdoor- air dampers will open to their minimum position). If for some reason the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, inter- rupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop (and the outdoor-air dampers will close). If the overtemper- ature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 min- utes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control.

When the thermostat is satisfied and W1 and W2 are deener- gized, the IFM continues to run and the economizer damper then moves to the minimum position. Units With Hot Gas Bypass Dehumidification Package — When thermostat calls for cooling, terminals G and Y1 and Y2 and the compressor contactors C1 and C2 are energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. As shipped from the factory, hot gas bypass dehumidification circuit is always energized. If hot gas bypass circuit modulation is desired, a field-installed, wall- mounted humidistat is required. If the hot gas bypass humidistat is installed and calls for the hot gas bypass subcooler coil to operate, the humidistat internal switch closes. This energizes and closes the liquid line solenoid valve coil (LLSV) of the hot gas bypass circuit, forcing the hot liquid refrigerant of the liquid line to enter the subcooler coil. As the hot liquid passes through the subcooler coil, it is exposed to the cold supply airflow coming off from the evaporator coil and the liquid is further cooled to a temperature approaching the evaporator coil leaving-air temperature. The state of the refrig- erant leaving the subcooler coil is a highly subcooled liquid refrigerant. The liquid then enters a thermostatic expansion valve (TXV) where the liquid is dropped to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid. The TXV can throttle the pressure drop of the liquid refrigerant and maintain proper con- ditions at the compressor suction valve over a wide range of operating conditions. The liquid then enters a second fixed restrictor expansion device for a second pressure drop to a 2-phase fluid. The liquid proceeds to the evaporator coil at a temperature lower than normal cooling operation. This lower temperature is what increases the latent capacity of the rooftop. The 2-phase refrigerant passes through the evaporator and is changed into a vapor. The air passing over the evaporator coil will become colder than during normal operation as a result of the colder refrigerant temperatures. However, as it passes over the subcooler coil, the air will be warmed slightly. As the refrigerant leaves the evaporator, the refrigerant passes a low-pressure switch in the suction line. This low-pressure switch will de-activate the hot gas bypass package when the suction pressure reaches 60 psig. The low-pressure switch is an added safety device to protect against evaporator coil freeze-up. The low-pressure switch will only de-activate and open the liquid line solenoid valve in the hot gas bypass circuit. The compressors will continue to run as long as there is a call for cooling, regardless of the position of the low-pressure switch. The solenoid valve and the hot gas bypass package will be re-activated only when the call for cooling has been satis- fied, the low-pressure switch has closed, and a new call for cooling exists. The crankcase heaters on the scroll compressor provide additional protection for the compressor due to the additional refrigerant charge in the subcooler. When the humidistat is satisfied, the humidistat internal switch opens cutting power to and opening the LLSV. The refrigerant is routed back through the evaporator and the subcooler coil is removed from the refrigerant loop. When the thermostat is satisfied, C1 and C2 are deenergized and the compressor and OFM shut off. After a 30-second delay, the IFM shuts off. If the thermostat fan selector switch is in the ON position, the IFM will run continuously. OPERATING SEQUENCE, 581A210-300 Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC) and compressor contactors A1 and B1 (except 300 units) are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor fan motor runs continuously while unit is cooling. If further cooling is required, the Y2 output
from the thermostat energizes compressor contactor C1 (B1 on 300 units). Heating, Units Without Economizer NOTE: The 581A210-300 units have 2 stages of heat. When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (light- emitting diode) on the IGC board will be on during normal oper- ation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition acti- vation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat. When ignition occurs the IGC board will continue to monitor the condi- tion of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be energized (and the outdoor-air dampers will open to their minimum position). If for some rea- son the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, inter- rupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop (and the outdoor-air dampers will close). If the overtemperature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. A LED indicator is provided on the IGC to monitor operation. The IGC is located by removing the side panel and viewing the IGC through the view port located in the control box access panel. During normal operation, the LED is continuously on. Cooling, Units With EconoMi$er IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F mixed-air temperature into the zone. As the mixed-air temperature fluctuates above 55 or below 50 F, the dampers will be modulated (open or close) to bring the mixed-air temper- ature back within control. If mechanical cooling is utilized with free cooling, the outdoor-air damper will maintain its current position at the time the com- pressor is started. If the increase in cooling capacity causes the mixed-air temperature to drop below 45 F, then the outdoor-air damper position will be decreased to the minimum position. If the mixed-air temperature continues to fall, the outdoor-air damper will close. Control returns to normal once the mixed-air temperature rises above 48 F. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.

If field-installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. For EconoMi$er IV operation, there must be a thermostat call for the fan (G). If the unit is occupied and the fan is on, the damper will operate at minimum position. Otherwise, the damper will be closed. When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV damper to the minimum position. On the initial power to the EconoMi$er IV control, it will take the damper up to 21/2 minutes before it begins to position itself. Any change in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes. If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differ- ential dry bulb, or differential enthalpy), then the control will modulate the dampers open to maintain the mixed-air tempera- ture set point at 50 to 55 F. If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature set point. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor. Heating, Units With Economizer NOTE: The units have 2 stages of heat. When the thermostat calls for heating, power is sent to W1 on the IGC (integrated gas unit controller) board. An LED (light- emitting diode) on the IGC board will be on during normal oper- ation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The
induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition acti- vation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be energized (and the outdoor- air dampers will open to their minimum position). If for some reason the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, inter- rupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop (and the outdoor-air dampers will close). If the overtemper- ature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 min- utes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. When the thermostat is satisfied and W1 and W2 are deener- gized, the IFM continues to run and the economizer damper then moves to the minimum position.

1. CONDENSATE DRAIN PAN — A sloped condensate drain pan is supplied on all units. The condensate pan must be externally trapped. Condensate drains are located on both the bottom and end of the unit. 2. DUCTWORK — All ductwork must be attached to flanges. If no flanges are present, they must be field supplied. Secure vertical discharge ductwork to roof curb. For hori- zontal discharge applications, attach ductwork to flanges. Field-supplied flanges can be attached to horizontal dis- charge openings and all ductwork attached to flanges. 3. THERMOSTAT — Use of 2-stage cooling thermostat is rec- ommended for all units equipped with economizer. A 2-stage cooling thermostat is required for size 090-300 units with integrated economizer. 4. HEATING-TO-COOLING CHANGEOVER — All units are automatic changeover from heating to cooling when auto- matic changeover thermostat and subbase are used. 5. AIRFLOW — Units are draw-thru on cooling and blow-thru on heating. 6. MAXIMUM AIRFLOW — To minimize possibility of conden- sate blow-off from evaporator, airflow through units should not exceed 500 cfm/ton (sizes 024-240) and 11,250 cfm (size 300). 7. MINIMUM AIRFLOW — Minimum airflow for cooling is 300 cfm/ton (sizes 036-240) and 280 cfm/ton (300 units). Refer to Heating Capacities and Efficiencies table for mini- mum heating airflow. 8. MINIMUM AMBIENT OPERATING TEMPERATURE — Minimum ambient operating temperature for size 036-150 standard units is 25 F. With accessory Motormaster® I, II, or IV units can operate at outdoor temperatures down to –20 F. Unit sizes 155-300 are designed to operate at outdoor tem- peratures down to 40 F. With accessory Motormaster I or Motormaster V control, units can operate at outdoor tem- peratures down to –20 F. NOTE: Under most application circumstances, if the roof- top unit is equipped with an economizer, low ambient con- trols are not required. Unless the outdoor air is unsatisfactory for free cooling due to high temperature, excessive humidity, or poor air quality, outdoor air should be used. 9. MAXIMUM OPERATING OUTDOOR-AIR TEMPERA- TURE — Maximum outdoor operating temperature for cooling is shown below (60 Hz):
45 F for aluminum heat exchangers. This temperature set- ting will bring on the second stage of heat whenever the ambient temperature is below the thermostat set point. Indoor comfort may be compromised when heating is initi- ated using low entering air temperatures with insufficient heating temperature rise.
FIELD-INSTALLED OUTDOOR-AIR THERMOSTAT
W2
TO UNIT THERMOSTAT CONNECTIONS
Wiring of Outdoor-Air Thermostat
12. MOTOR DATA — Due to Bryant’s internal unit design (draw-thru over the motor), air path, and specially designed motors, the full horsepower (maximum continuous bhp) listed in the Physical Data tables and the notes following each Fan Performance table can be utilized with extreme confidence. Using Bryant motors to the values listed in the Physical Data, Fan Performance, and Evaporator-Fan Motor Data tables will not result in nuisance tripping or premature motor failure. In addition, the unit warranty will not be affected. 13. THRU-THE-BOTTOM CONNECTIONS — The accessory thru-the-bottom connections are needed to ensure proper connections when routing wiring and piping through the basepan and roof curb. This accessory is used for electric and control power only or electric, control power, and gas piping depending on which accessory is selected. 14. FIELD-SUPPLIED FAN DRIVES — If the factory drive sets must be changed to obtain other wheel speeds, consult the nearest Browning Manufacturing Co. sales office with the required new wheel speed and the data from Physical Data tables (center distances, motor and fan shaft diameters, motor horsepower) for a modified drive set selection. For minor speed changes, the fan sheave size should be changed. (Do not reduce the size of the motor sheave; this will result in reduced belt horse-power ratings and reduced belt life.) All indoor fan pulleys are adjustable. See physical data tables for rpm adjustment ranges. 15. CONDENSER COIL PROTECTION a. PRE-COATED ALUMINUM FIN COILS have a durable
581B,C024-150 125 F 580F036-151 115 F 579F/580F180-240 120 F 579F/580F300 125 F 581A036-155 125 F 581A180 120 F 581A210 125 F 581A240 125 F 581A300 125 F 10. HIGH ALTITUDES — These may require a change to the gas orifice. Refer to Altitude Compensation tables. 11. MINIMUM HEATING ENTERING AIR TEMPERATURE — The minimum temperature of air entering the dimpled heat exchanger is 50 F continuous and 45 F intermittent for alu- minum heat exchangers and 40 F continuous and 35 F intermittent for stainless steel heat exchangers. To operate at lower mixed-air temperatures, a field-supplied outdoor- air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required tem- perature to ensure full fire operation. Wire the outdoor-air thermostat (part no. HH22AG106) in series with the second stage gas valve as shown below. Set the outdoor-air thermostat at 35 F for stainless steel heat exchangers or
epoxy-phenolic coating applied to the fin prior to the fin stamping process to provide protection in mildly corro- sive coastal environments. Pre-coated coils have an inert barrier between the aluminum fin and copper tube. This barrier electrically disconnects the dissimilar metals to minimize the potential for galvanic corrosion. This economical option provides substantial corrosion protec- tion beyond the standard uncoated coil construction. b. COPPER-FIN COILS provide increased corrosion resis-
tance in moderate coastal environments where industrial air pollution is not present. All copper coils eliminate bi- metallic construction to eliminate the potential for gal- vanic corrosion. Application in industrial environments is not recommended due to potential attack from sulfur, sulfur oxide, nitrogen oxides, carbon and several other industrial airborne contaminants. In moderate seacoast environments, copper-fin coils have extended life com- pared to standard or pre-coated aluminum-fin coils.
a48-7481


1'-10 11/16'' MAX.
6'-2 3/8'' MAX. 5'-9 3/16'' MAX.
4'-6 13/16''1'-0 3/16''
B 24'' MIN.
A
BAFFLE
Shaded area indicates block-off panels.
c. E-COATED ALUMINUM FIN coils undergo a precisely
and enhances rooftop operation through reduced energy consumption, optimal zone comfort, and efficient equip- ment cycling. This is accomplished by operating the com- pressors when the outdoor air temperature is too warm, integrating the compressors with outdoor air when free cooling is available, and locking out the compressor when outdoor air temperature is too cold. The detailed sequence of operation is described in the Controls section with a brief description of selected application items here. a. THERMOSTAT INTERFACE — The EconoMi$er IV con-
controlled scientific process that bonds an impermeable epoxy coating to the specially prepared fin coil surface. E-Coating produces a smooth, consistent coating that is less brittle, more resilient and more durable than previ- ous postcoating processes. E-Coated aluminum-fin coils offer economical protection and improved coil life in many contaminated environments. d. E-COATED COPPER-FIN COILS provide maximum
protection in virtually all environments, this option com- bines the continuous, impenetrable barrier of the E- Coating process with the natural resistance of an all-cop- per construction. E-Coated copper-fin coil assemblies ensure long life, even in environments that combine harsh coastal conditions with industrial contamination. 16. ECONOMI$ER IV — The EconoMi$er IV factory-installed economizer package includes a gear-driven damper sys- tem that modulates the return air and outdoor air supply to the rooftop unit in order to take advantage of “free cooling” with outdoor air when conditions are suitable. The system utilizes industry proven technology available for integrating the use of outdoor air for cooling with mechanical cooling for 3 through 25-ton rooftop units. The intuitive EconoMi$er IV microprocessor-based controller optimizes
trol was designed to work with conventional thermostats that have Y1 (cooling stage 1), Y2 (cooling stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). In addi- tion, the EconoMi$er IV will support an occupied/ unoccupied switch (typically integrated into the thermo- stat or Thermidistat™ device). When the switch is closed, it provides a 24-vac signal to the unit for occu- pied mode, and provides no signal to indicate unoccu- pied mode. The EconoMi$er IV control can be configured to allow different minimum economizer damper positions and to allow the use of mechanical cooling in the occupied mode.
ENVIRONMENT
DESCRIPTION (Dura-Shield Option)
Standard, Non-Corrosive Mild Coastal Severe Coastal Industrial Combined Coastal
and Industrial Standard, Al/Cu X Pre-Coated Al/Cu X Cu/Cu X E-Coated Al/Cu X X E-Coated Cu/Cu X
Al/Cu — Aluminum Fin with Copper Tube Coil E-Coated — Extremely Flexible and Durable Epoxy Coating Uniformly Cu/Cu — Copper Fin with Copper Tube Coil Applied to the Coil Surfaces Dura-Shield — Family of Coil Protection Options Pre-Coated — Epoxy Coating Applied to Fin Stock Material

b. CONTROL FEATURES — The EconoMi$er IV controller
Compressor Staging — The EconoMi$er IV is an inte- grated economizer and has the ability to utilize simulta- neous outdoor air and compressors. The EconoMi$er IV can be configured to support economizer and compres- sor operation. Only one or two compressor operation is available with 3 to 121/2 ton units. c. CHANGEOVER STRATEGIES — The EconoMi$er IV
provides superior functionality for rooftop unit operation. EconoMi$er IV control features are included as follows: Remote Minimum Position — The EconoMi$er IV con- troller can be used with a field-supplied and field- installed remote minimum position control switch that will enable and disable the EconoMi$er IV to open or close the damper beyond the minimum position for modified ventilation, providing 2 to 10 vdc output. NOTE: Minimum position signal takes priority over the DCV (demand control ventilation) maximum position signal. Demand Control Ventilation (DCV) — The EconoMi$er IV has DCV capability when using an IAQ sensor. This sensor is typically installed in the return duct or occupied space. When implementing a DCV control scheme with the EconoMi$er IV, the control algorithm will modulate the position of the damper between two user-configured damper positions, Maximum DCV Position and Minimum Occupied position. Design airflow rates for these two damper positions should be such that when the damper is at the Maximum DCV position, enough fresh ventila- tion air will be brought in to remove contaminants and CO2 generated by sources other than people (i.e., since in unoccupied mode). The Maximum DCV position is intended to satisfy the IAQ “Base Ventilation Rate.” The Minimum Occupied position design airflow rate should be sufficient to satisfy ventilation requirements for removing CO2 from all sources including people at the maximum occupancy. IAQ Sensors — EconoMi$er IV can be utilized with any IAQ (CO2) sensor that provides a 2 to 10 vdc output. The controller will modulate the outdoor air damper to pro- vide ventilation based on the sensor output and the IAQ setting of the controller. When used, an IAQ sensor will modulate the damper from the minimum position (base ventilation rate based on CO2 levels) to maximum posi- tion (full occupancy ventilation rate). Damper Operation — The EconoMi$er IV allows the damper to be configured for two adjustable damper posi- tions including maximum position and occupied mini- mum positions. The two (2) position damper capability is a unique feature of EconoMi$er IV and includes opera- tion flexibility as follows: 1. Minimum Occupied Position: This adjustable position allows a minimum ventilation (base ventilation rate) airflow rate through the unit during occupied periods. 2. Demand Control Ventilation (DCV) Maximum Posi- tion: A DCV maximum occupied position is provided when using an IAQ sensor for DCV. See DCV and Control sections for sequence. The DCV Maximum Position limits outdoor airflow into the rooftop when the DCV routine overrides the mixed air sensor. Set- ting the DCV Maximum Position of the outdoor air damper prevents large amounts of hot or cold air into the space. IMPORTANT: When the DCV Maximum Position is set below the minimum position, the minimum position overrides the maximum position, negating most DCV functions. Power Exhaust — The EconoMi$er IV has the capability to control one stage of power exhaust for maintaining air balance and pressurization. Control is activated based on outdoor air damper position (adjustable); factory-set at the “middle” position (dampers halfway open).
controller can be configured to accommodate all avail- able economizer control strategies that place the rooftop unit in economizer mode including: Remote Minimum Position — Used when a remote sig- nal from a remote minimum position control will enable and disable the EconoMi$er IV (remote enable control). Outdoor Dry Bulb — EconoMi$er IV will be enabled based on the outdoor-air temperature. This is provided standard with the EconoMi$er IV. Differential Dry Bulb — EconoMi$er IV will be enabled whenever the outdoor-air temperature is lower than the return-air temperature. Outside Air Enthalpy — EconoMi$er IV will be enabled based on the outside air enthalpy curves as shown in the EconoMi$er IV Changeover diagram below. The A, B, C, and D curves shown have been in use for many years and have been included as part of the latest ASHRAE 90.1 energy efficiency code. The curves are designed to take into consideration both outdoor temper- ature and humidity. These curves are used to set up the EconoMi$er IV controller to use the EconoMi$er IV for free cooling when the conditions to the left of the curve exist. When the conditions are to the right of the curve, then outdoor air cooling will not be used and the outdoor air damper position will be set at the minimum position. Deciding which curve is used is a function of the outdoor climate and the type of economizer utilized. Since EconoMi$er IV is a fully integrated economizer, the range where outdoor air can be utilized for free cooling is expanded and the A and B curves may be used. The control point table in the EconoMi$er IV Changeover dia- gram below provides assistance for whether the A and B curves will be suitable. In general terms, a hot and humid climate may be a reason not to use the A curve, while a cooler climate might be more applicable for using the A or B curve. The EconoMi$er IV has expanded outdoor air capability. For a changeover economizer which cannot utilize simultaneous economizer and compression, both A and B curves would potentially be undesirable since the tem- perature and humidity levels are too high without com- pression assistance to provide effective cooling. Therefore, most changeover economizers utilize the D curve. Differential Enthalpy — The EconoMi$er IV will be enabled based on the comparison of the enthalpy of the return air and outside air. When the outside air enthalpy is lower than he return side, the unit will be in econo- mizer mode. Using the EconoMi$er IV controller for implementing different control changeover strategies requires the use of different combinations of dry bulb and humidity sensors as outlined in the EconoMi$er IV Sensor Usage table.

12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
CONTROL POINT
CURVE
APPROX. °F (°C)
AT 50% RH
A B C D
73 (23) 70 (21) 67 (19) 63 (17)
RELATIVE HUMIDITY (%)
A
B
D
A
B
D
HIGH LIMIT CURVE
110 (43) 45 (7)
Economizer Changeover Curves
ECONOMI$ER IV SENSOR USAGE CHART
ECONOMI$ERIV WITH OUTDOOR AIR
ECONOMI$ERIV WITH SINGLE
ENTHALPY SENSOR Accessories Required Accessories Required Outdoor Air Dry Bulb None. The outdoor air dry bulb sensor is factory installed. CRTEMPSN002A00* Differential Dry Bulb CRTEMPSN002A00* (2) CRTEMPSN002A00* Single Enthalpy HH57AC078 None. The single enthalpy sensor is factory installed.
APPLICATION
HH57AC078
CRENTDIF004A00*
CO2 for DCV Control using a
Wall-Mounted CO2 Sensor CGCDXSEN004A00
CO2 for DCV Control using a
Duct-Mounted CO2 Sensor
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. †CGCDXSEN004A00 is an accessory CO2 sensor. **CGCDXASP001A00 is an accessory aspirator box required for duct-mounted applications.



UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Copyright 2007 Bryant Heating & Cooling Systems Printed in U.S.A. 3/07 Catalog No. PDS580F-36-4