SINGLE-PACKAGED GAS HEATING/ELECTRIC COOLING UNITS
2 to 5 Nominal Tons Low NOx Models Available
EASY INSTALLATION—Factory-assembled package is a com- pact, fully self-contained, combination gas heating/electric cool- ing unit that is pre-wired, pre-piped, and pre-charged for minimum installation expense. These units are available in a variety of standard and optional heating/cooling size combinations with voltage options to meet residential and light commercial requirements. Units are light- weight and install easily on a rooftop or at ground level. The high tech composite unit base eliminates rust problems associated with ground level applications. CONVERTIBLE DUCT CONFIGURATION—Unit is designed for easy use in either downflow or horizontal applications. Each unit is easily converted from horizontal to downflow. EFFICIENT OPERATION High-efficiency design offers SEER (Seasonal Energy Effi- ciency Ratios) of 13.0 and AFUE (Annual Fuel Utilization Effi- ciency) ratings as high as 81%. Energy-saving, direct spark ignition saves gas by operating only when the room thermostat calls for heating. Standard units are furnished with natural gas controls. A low-cost field-installed kit for propane conversion is available for all units. 574B units with an “N” in the thirteenth position of model # are dedicated Low NOx units designed for California installa- tions. These models meet the California maximum oxides of ni- trogen (NOx) emissions requirement of 40 nanograms/joule or less as shipped from the factory and MUST be installed in Cali- fornia Air Quality Management Districts where a Low NOx rule exists. DURABLE, DEPENDABLE COMPONENTS Compressors are designed for high efficiency. Each compres- sor is hermetically sealed against contamination to help promote longer life and dependable operation. Each compressor also has vibration isolation to provide quieter operation. All compressors have internal high pressure and overcurrent protection. Monoport inshot burners produce precise air-to-gas mixture, which provides for clean and efficient combustion. The large monoport on the inshot (or injection type) burners seldom, if ever, requires cleaning. All gas furnace components are acces- sible in one compartment. Turbo-tubular™ heat exchangers are constructed of alumi- nized steel for corrosion resistance and optimum heat transfer for improved efficiency. The tubular design permits hot gases to make multiple passes across the path of the supply air. In addition, dimples located on the heat exchanger walls force the hot gases to stay in close contact with the walls, improving heat transfer. Direct-drive variable speed (ECM) blower motor is standard on all 574B models. Direct-drive, PSC condenser-fan motors are designed to help reduce energy consumption and provide for cooling operation down to 55°F outdoor temperature. Motormaster® II low ambient kit is available as a field-installed accessory.
FEATURES/BENEFITS One-piece heating and cooling units with low sound levels, easy installation, low maintenance, and dependable performance. Puron® Environmentally Sound Refrigerant is Bryant’s unique refrigerant designed to help protect the environment. Puron is an HFC refrigerant which does not contain chlorine that can harm the ozone layer. The most important advantage of Puron refrigerant is that it has not been banned in future air con- ditioning systems as the traditional refrigerant R-22 has been. Puron refrigerant is in service in thousands of systems proving highly reliable, environmentally sound performance. Perfect Heat, Perfect Humidity™ featuring Variable Speed Blower motors provides better comfort and energy efficiency. You can expect up to 30 times better dehumidification; economi- cal constant fan for less than $50 a year, which provides improved indoor air quality and more even temperatures from room to room; and reduced indoor noise due to lower air velocity. In addition, you’ll realize improved installation flexibility with 3 different airflow choices for best overall comfort.

Corporate thermostats include the Time Guard® II anti-short cycle protection circuitry. If a non-corporate thermostat without anti-short cycle protection is used the Time Guard II field in- stalled anti-short cycle kit is recommended.
holds are provided to manipulate the unit on the jobsite. A nesting feature ensures a positive unit base to roof curb seal when the unit is roof mounted. A convenient 3/4-in. wide perimeter flange makes frame mounting on a rooftop easy. Standard metal duct covers with insulation come with the unit and cover the horizontal duct openings. These can be left in place if the units are converted to downflow. Downflow operation is easily provided in the field to allow ver- tical ductwork connections. The basepan utilizes knockout style seals on the bottom openings to ensure a positive seal in the horizontal airflow mode. Integrated Gas Control (IGC) board provides safe and efficient control of heating and simplifies trouble-shooting through its built-in diagnostic function.
is designed to provide dependability. Liquid filter dryers are used to promote clean, unrestricted operation. Each unit leaves the factory with a full refrigerant charge. Refrig- erant service connections make checking operating pressures easier. HIGH AND LOW PRESSURE SWITCHES provide added reli- ability for the compressor. Evaporator and condenser coils are computer-designed for optimum heat transfer and cooling efficiency. The evaporator coil is fabricated from copper tube and aluminum fins and is lo- cated inside the unit for protection against damage. The con- denser coil is internally mounted on the top tier of the unit. Copper fin coils and pre-coated fin coils are available from the factory by special order. These coils are recommended in appli- cations where aluminum fins are likely to be damaged due to corrosion. They are ideal for seacoast applications. Low sound ratings ensure a quiet indoor and outdoor environ- ment with sound ratings as low as 72 dB. (See page 3.) Easy to service cabinets provide easy single-panel accessibility to serviceable components during maintenance and installation. The unit base with integrated drain pan provides easy ground lev- el installation with or without a mounting pad. Convenient rigging
are constructed of heavy-duty, phosphated, zinc- coated prepainted steel capable of withstanding 500 hours in salt spray. Interior surfaces of the evaporator/heat exchanger compartment are insulated with cleanable semi-rigid insulation board, which keeps the conditioned air from being affected by the outdoor ambient temperature and provides improved indoor air quality. (Conforms to American Society of Heating, Refriger- ation and Air Conditioning Engineers No. 62P.) The sloped drain pan minimizes standing water in the drain, which is provided with an external drain fitting. Louvered Grille provides hail and vandalism protection.
Options
Model Number 574B – Single Packaged Gas Heating/Electric Cooling
BT – AL evap, vinyl condens CC – AL evap, CU condens CU – CU evap & condens
TP – Base unit with tin plated indoor coil
hair pins TV – TP with vinyl coating on outdoor coil TC – TP with AL indoor coil and CU/CU
Electrical Supply N – 208/230-1-60 P – 208/230-3-60
outdoor coil Only used if ordering an option
Fuel W – Natural Gas P – Propane Gas
Low NOx Indicator N – Low NOx Unit Only used if ordering NOx units
Nominal Cooling Capacity 024 – 2 ton 030 – 2.5 ton (not yet available) 036 – 3 ton 042 – 3.5 ton (not yet available) 048 – 4 ton 060 – 5 ton
Heat Input Size 040 – 40,000 060 – 60,000 090 – 90,000 115 – 115,000 130 – 130,000
LEGEND CU — Copper AL — Aluminum





† Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air-
flow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg. * Based on altitude of 0 to 2000 ft.

† Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air-
flow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
** Based on altitude of 0 to 2000 ft.

Factory-installed options Coil options include Tin-Plated* indoor hairpins, copper/copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomenclature for coil options. *Tin-Plated indoor coils are built with special hairpins that are de- signed to resist both general pitting corrosion and excessive in- door corrosion (Formicary Corrosion).
Flat roof curbs in both 8 in. and 14 in. sizes are available for roof mounted applications. Square-to-round duct transition kit enables 024-048 size units to be fitted to 14 in. round ductwork. Compressor hard start kit assists compressor start-up by pro- viding additional starting torque on single phase units and pro- longs compressor motor life. Thermostats provide control for the system heating and cooling functions. Thermostat models are available in both programma- ble and non-programmable versions. Crankcase heater provides anti-floodback protection for low- load cooling applications. LP (liquid propane) conversion kit allows for conversion from natural gas to liquid propane fuel. Low-ambient kit (Motormaster® II control) allows the use of mechanical cooling down to outdoor temperatures as low as 0°F. Solid-state Time Guard® II device provides short-cycling pro- tection for the compressor. Not required with corporate electron- ic thermostats. Filter rack features easy installation, serviceability, and high- filtering performance for vertical applications. High altitude kit is for use at 2001 to 6000 ft above sea level. Kit consists of natural gas orifices that compensate for gas heat operation at high altitude. LP to natural gas conversion kit allows conversion back to natural gas. Lifting kit includes rigging brackets which are inserted into the unit base rigging holds to rig unit for rooftop applications.
Economizer with Solid-State Controls and Barometric Relief Dampers
Manual Air Damper (25% open)
Roof Curbs (8-in. and 14-in.)
Square-to-Round Duct Transition Kit
Compressor Hard Start Kit (for use on single-phase units only)
Low Ambient Kit (Motormaster® II Control)
Solid-State Time Guard® II Device
LP to Natural Conversion Kit
Economizer with solid-state controls and barometric relief dampers includes filter racks and provide outdoor air during cooling and reduce compressor operation.
Manual outside air damper includes hood and filter rack with adjustable damper blade for up to 25% outdoor air.


FILTER ACCESS DOOR (HORIZONTAL APPLICATION ONLY.) DO NOT REMOVE FROM DOWNFLOW DISCHARGE.
HOLE FOR ECONOMIZER WIRING HARDNESS
RAINHOOD
DOOR LATCH ANGLE
HINGED FILTER ACCESS DOOR INSTALL FILTER ACCESS DOOR STICKER
A99315
A99314
Filter Rack
Manual Outside Air Damper

MANUAL OUTSIDE AIR HOOD
DAMPER BLADE
A99317
A99316
17 13/32 (442mm) · 11 13/32” (290mm) · 16 1/4” (413mm)

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Evaporator coil access side 36 (914) Power entry side (except for NEC requirements) 36 (914) Unit top 48 (1219) Side opposite ducts 36 (914) Duct panel 12 (304.8)* *Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
Top of unit 14 (355.6) Duct side of unit 2 (50.8) Side opposite ducts 14 (355.6) Bottom of unit 0.50 (12.7) Flue panel 36 (914.4) NEC REQ’D CLEARANCES. in. (mm) Between units, power entry side 42 (1066.8) Unit and ungrounded surfaces, power entry side 36 (914) Unit and block or concrete walls and other grounded surfaces, control box side 42 (1066.8) LEGEND CG - Center of Gravity COND - Condenser EVAP - Evaporator NEC - National Electrical Code REQ'D - Required Note: Dimensions are in in. (mm)


REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
in. [mm] EVAP. COIL ACCESS SIDE 36.00 [914.0] POWER ENTRY SIDE 36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP 36.00 [914.0] SIDE OPPOSITE DUCTS 36.00 [914.0] DUCT PANEL 12.00 [304.8] *
in. [mm] TOP OF UNIT 14.00 [355.6] DUCT SIDE OF UNIT 2.00 [50.8] SIDE OPPOSITE DUCTS 14.00 [355.6] BOTTOM OF UNIT 0.50 [12.7] FLUE PANEL 36.00 [914.4]
NEC. REQUIRED CLEARANCES.
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
MILLIMETERS [IN.] BETWEEN UNITS, POWER ENTRY SIDE 42.00 [1066.8] UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY SIDE 42.00 [1066.8]



Notes: 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied as required to unit being installed. 3. Dimensions in [ ] are in millimeters. 4. Roof curb is made of 16 gage steel. 5. Table lists only the dimensions per part number that have changed. 6. Attach ductwork to curb (flanges of duct rest on curb). 7. Insulated panels: 1-in. thick fiberglass 1 lb. density. 8. Dimensions are in inches. 9. When unit mounting screw is used (Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl.

y
I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) 34,500 Btuh Sensible Heat Capacity (SHC) 26,000 Btuh Required Heating Capacity 60,000 Btuh Condenser Entering Air Temperature 95°F Indoor-Air Temperature 80°F edb 67°F ewb Evaporator Air Quantity 1200 CFM External Static Pressure 0.2 in. wg Electrical Characteristics 230-1-60
MENTS AT DESIGN CONDITIONS. Before entering the air delivery tables, calculate the total static pressure required. From the given example, the Wet Coil Pressure Drop Table, and the Filter Pressure Drop table on page 16, find at 1200 cfm:
Wet Coil Pressure Drop 0.032 in. ws External Static Pressure 0.2 in. wg Filter Pressure Drop 0.13 in. wg Total Static Pressure 0.362 in. wg
Enter the table for Dry Coil Air Delivery — Horizontal and Downflow Discharge. At 0.362 ESP (external static pressure), the fan will deliver 1235 cfm with the NOM Speed pin selected.
II SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Net Cooling Capacities table at condenser entering temperature of 95 F. Unit 036 at 1225 cfm and 67 F ewb (entering wet bulb) will provide a total capacity of 36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction, if required, using Note 4 under Cooling Capacities tables.
V SELECT UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE. The Electrical Data table shows that the unit is designed to operate at 208/230-1-60.
III SELECT HEATING CAPACITY OF UNIT TO PROVIDE DESIGN CONDITION REQUIREMENT. In the Heating Capacities and Efficiencies table on page 4, note that the unit 036090 will provide 70,000 Btuh with an input of 90,000 Btuh.

COOLING CAPACITIES
Evaporator Air — CFM / BF
Temp (F) Outdoor Air
800/0.026 900/0.032 1000/0.04
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75 TC SHC kW
24.0 24.5 26.5 29.1 24.6 25.1 27.1 29.8 25.1 25.5 27.4 30.4 21.9 21.3 18.7 15.4 23.5 22.8 19.8 16.1 25.0 24.2 20.8 16.7 1.7 1.7 1.8 1.9
22.9 23.3 25.3 27.9 23.5 23.9 25.8 28.5 23.9 24.3 26.2 28.9 21.4 20.7 18.1 14.9 22.9 22.2 19.2 15.6 24.3 23.6 20.3 16.2 1.9 1.9 2.0 2.1 2.1
85 TC SHC kW
95 TC SHC kW
21.8 22.2 24.0 26.5 22.3 22.6 24.5 27.0 22.7 23.0 24.8 27.4 20.8 20.2 17.6 14.3 22.3 21.6 18.7 15.0 23.6 22.9 19.7 15.6 2.2 2.3 2.3
105 TC SHC kW
20.5 20.9 22.6 25.0 21.0 21.3 23.0 25.4 21.6 21.7 23.3 25.7 20.2 19.5 16.9 13.7 21.6 20.9 18.0 14.3 22.5 22.2 19.0 14.9 2.4 2.5
115 TC SHC kW
19.2 19.5 21.1 23.3 19.8 19.9 21.5 23.7 20.7 20.4 21.7 23.6 19.4 18.8 16.3 13.0 20.6 20.2 17.3 13.7 21.5 21.2 18.3 14.1 2.7 2.8 2.8
125 TC SHC kW
17.8 18.0 19.4 21.4 18.5 18.5 19.5 21.7 19.0 19.0 19.9 21.9 18.5 18.1 15.5 12.3 19.2 19.2 16.5 12.9 19.8 19.7 17.6 13.5 2.9 2.9 3.0 3.1 3.1
Temp (F) Outdoor Air
875/0.08 1000/0.09 1125/0.10
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75 TC SHC kW
85 TC SHC kW
95 TC SHC kW
105 TC SHC kW
115 TC SHC kW
125 TC SHC kW
See Legend and Notes on page 15.
Entering Condenser · Evaporator Air—CFM/BF · Entering Condenser

COOLING CAPACITIES (cont)
Temp (F) Outdoor Air
1100/0.06 1225/0.07 1400/0.08
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75 TC SHC kW
36.2 36.8 39.7 43.8 36.9 37.4 40.3 44.4 37.9 38.1 41.0 45.1 33.2 26.7 27.8 22.3 34.7 27.9 29.0 23.1 36.9 29.6 30.9 24.2 2.7 2.8 2.9
85 TC SHC kW
34.6 35.1 37.9 41.8 35.3 35.6 38.4 42.4 36.4 36.3 39.1 43.1 32.4 26.0 27.1 21.6 34.0 27.1 28.3 22.4 35.6 28.9 30.2 23.6 2.9 2.9 3.0 3.1 3.1 3.1 3.2
95 TC SHC kW
33.0 33.4 36.0 39.7 33.7 33.8 36.5 40.2 34.8 34.4 37.0 40.8 31.6 25.3 26.4 20.9 32.9 26.4 27.6 21.7 34.4 28.1 29.4 22.8 3.2 3.2 3.3 3.4 3.5
105 TC SHC kW
31.3 31.5 34.0 37.5 32.1 31.9 34.3 37.9 33.1 32.4 34.9 38.4 30.6 24.5 25.6 20.1 31.5 25.7 26.8 20.9 32.8 27.3 28.6 22.0 3.6 3.7 3.7 3.8 3.7 3.8 3.8
115 TC SHC kW
29.6 29.4 31.8 35.0 30.4 29.8 32.1 35.4 31.3 30.3 32.6 35.8 29.3 23.7 24.8 19.3 30.0 24.8 26.0 20.0 31.0 26.4 27.7 21.1 4.0 4.1 4.1 4.1 4.2
125 TC SHC kW
27.8 27.2 29.4 32.4 28.4 27.5 29.7 32.7 29.3 28.0 30.1 33.0 27.5 22.8 23.9 18.4 28.2 23.8 25.0 19.1 29.0 25.4 26.7 20.2 4.4 4.3 4.4 4.5
Temp (F) Outdoor Air
1225/0.11 1400/0.12 1575/0.14
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75 TC SHC kW
85 TC SHC kW
95 TC SHC kW
105 TC SHC kW
115 TC SHC kW
125 TC SHC kW
See Legend and Notes on page 15.

COOLING CAPACITIES (cont)
Temp (F) Outdoor Air
1260/0.06 1400/0.06 1600/0.08
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52.5 57.8 39.3 32.0 33.4 27.2 42.6 34.3 35.8 28.9 45.8 36.8 38.4 30.6 3.4 3.5 3.4 3.4 3.4 3.5
75 TC SHC kW
85 TC SHC kW
42.8 43.6 47.2 52.1 44.3 44.9 48.6 53.5 45.6 46.1 49.9 54.8 38.2 30.9 32.3 26.2 41.3 33.2 34.7 27.7 44.3 35.5 37.3 29.4 3.7 3.7 3.8 3.8 3.7 3.7 3.8
95 TC SHC kW
40.6 41.3 44.7 49.4 41.8 42.4 46.0 50.7 44.2 43.7 47.0 51.8 36.9 29.8 31.2 25.2 39.9 32.0 33.6 26.7 43.0 34.6 36.1 28.3 4.1 4.1 4.2 4.2 4.1 4.1 4.2 4.2 4.2 4.1 4.2 4.2
105 TC SHC kW
38.2 38.9 42.1 46.4 39.6 39.8 43.1 47.6 41.5 40.8 44.0 48.5 35.7 28.7 30.1 24.0 38.3 30.7 32.3 25.5 40.0 33.2 34.8 27.0 4.6 4.7 4.6 4.6 4.6 4.7
115 TC SHC kW
35.7 36.3 39.3 43.3 38.2 37.1 40.1 44.2 38.7 37.9 40.8 45.0 34.4 27.5 28.9 22.9 35.7 29.5 31.0 24.3 38.2 31.8 33.5 25.8 5.0 5.0 5.1 5.1 5.1 5.0 5.1
125 TC SHC kW
33.4 33.4 36.2 39.4 34.6 34.1 36.9 40.5 36.1 34.8 37.5 41.2 32.1 26.2 27.6 21.5 33.8 28.2 29.7 22.9 35.6 30.2 31.9 24.4 5.6 5.6 5.6 5.7 5.6
Evaporator Air — CFM/BF
Temp (F) Outdoor Air
1500/0.004 1750/0.007 2000/0.01
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
57.2 58.2 62.4 68.1 58.8 59.7 64.0 69.8 60.0 60.8 64.9 70.8 49.4 47.9 41.6 33.8 53.6 51.8 44.5 35.4 57.6 55.4 47.1 36.8 4.1 4.1 4.2 4.2 4.2 4.3 4.3 4.4 4.4 4.4 4.5 4.6
54.7 55.6 59.7 65.2 56.2 57.0 61.1 66.6 57.4 58.1 61.9 67.4 48.2 46.7 40.4 32.6 52.4 50.5 43.2 34.2 56.3 54.2 45.8 35.6 4.5 4.5 4.6 4.7 4.7 4.7 4.8 4.9 4.8 4.9 5.0 5.0
52.2 53.0 56.9 62.0 53.5 54.3 58.0 63.2 55.0 55.3 58.7 64.1 47.0 45.4 39.2 31.4 51.1 49.2 41.9 32.9 55.0 52.9 44.5 34.4 5.0 5.0 5.1 5.2 5.1 5.2 5.3 5.3 5.2 5.3 5.5 5.5
49.4 50.2 53.8 58.7 50.7 51.4 54.8 59.6 52.5 52.4 55.4 60.2 45.7 44.1 37.9 30.1 49.8 47.9 40.6 31.6 52.5 51.6 43.2 33.0 5.5 5.6 5.6 5.7 5.7 5.7 5.8 5.9 5.8 5.8 6.0 6.1
46.5 47.2 50.5 55.0 48.1 48.3 51.3 56.8 49.7 49.7 51.8 57.0 44.3 42.7 36.4 28.7 48.1 46.6 39.2 30.6 49.7 49.7 41.8 31.7 6.1 6.2 6.2 6.3 6.2 6.3 6.4 6.6 6.6
43.3 43.9 46.7 52.2 45.2 45.1 47.4 52.5 46.4 46.4 47.9 52.2 42.8 41.2 34.9 27.8 45.2 45.1 37.6 28.9 46.4 46.4 40.2 29.7 6.7 6.8 6.9 7.0 7.2 7.2
LEGEND BF — Bypass Factor Ewb — Entering Wet-Bulb kW — Total Unit Power Input SHC — Sensible Heat Capacity (1000 Btuh) TC — Cooling Capacity (1000 Btuh) ECM — Electronic Computated Motor * — TVA Conditions (75°F entering dry bulb) NOTES: 1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat. 2. Direct interpolation is permissible. Do not extrapolate. 3. The following formulas may be used:
sensible capacity (Btuh) t = t ldb edb 1.10 x cfm
t = Wet-bulb temperature corresponding to enthalpy of air leaving lwb
evaporator coil (h ) lwb total capacity (Btuh) h = h lwb ewb 4.5 x cfm
Evaporator Air—CFM/BF · Entering Condenser

FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — 20 X 24 X 1 — 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — 24 X 30 X 1 — 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18

PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0
024 COOLING 745 675 — 835 750 690 940 880 815
COOLING DEHUMIDIFY 675 625 — 675 650 600 755 730 705
030 COOLING 940 860 785 1020 965 895 1185 1100 1010
COOLING DEHUMIDIFY 820 785 735 820 800 770 955 920 880
036 COOLING 1025 935 — 1145 1085 1005 1320 1260 1180
COOLING DEHUMIDIFY 925 885 — 925 900 870 1060 1040 1010
PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0
042 COOLING 1035 1095 1280
COOLING DEHUMIDIFY 880 880 1025
048 COOLING 1150 1285 1500
COOLING DEHUMIDIFY 1025 1025 1200
060 COOLING 1480 1630 1920
COOLING DEHUMIDIFY 1305 1305 1535
574B HEATING ECM AIRFLOW—SMALL CABINET
EASY SELECT™ BOARD SETTING (CFM) 700 800 1100 1250
UNIT SIZE
PRESSURE 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 GAS HEAT SIZE
024 040 — — — 855 770 710 —
030 040 — — — 880 840 805 —
060 — 1030 970 910 — — —
036 060 — 1035 995 955 — — —
090 — 1170 1110 1025
EASY SELECT™ BOARD SETTING (CFM) 1000 1250 1600 1750 1800
UNIT SIZE
PRESSURE 0.0–1.0 GAS HEAT SIZE
042 060 1000 —
090 — 1250 — — —
090 — 1250 — — —
115 — — 1600 — —
130 — — — 1750 —
090 — 1250 — — —
115 — — 1600 — —
130 — 1800

AIRFLOW SETTING
CALCULATED TEMPERATURE
MIN. TEMP
MAX TEMP
MAX DISCH.
EAST SELECT™
TEMP 574B 024 40 800 36.5 20 50 175 574B 030 40 800 36.5 20 50 175 574B 030 60 1100 40 35 65 165 574B 036 60 1100 40 25 55 165 574B 036 90 1200 54 45 75 175 574B 042 60 1000 44 20 50 165 574B 042 90 1250 53 35 65 170 574B 048 90 1250 53 25 55 165 574B 048 115 1600 53 35 65 170 574B 048 130 1750 54 40 70 175 574B 060 90 1600 41 25 55 155 574B 060 115 1600 53 35 65 170 574B 060 130 1800 53 40 70 175
(SCFM)
RISE
RISE
RISE
PERFORMANCE DATA (CONT)
ECONOMIZER/1-IN. FILTER PRESSURE DROP (in. wg)
UNIT 574B PRESSURE DROP 024-036 0.20 042-060 0.25
HIGH ALTITUDE COMPENSATION
LIQUID PROPANE ONLY ORIFICE CONVERSION — 3.5 in. wc
NATURAL GAS ONLY ORIFICE CONVERSION — 3.5 in. wc
MANIFOLD PRESSURE*
MANIFOLD PRESSURE*
ALTITUDE (ft) INPUT (Btuh)
OUTPUT
ORIFICE NUMBER†
ALTITUDE (ft) INPUT (Btuh)
OUTPUT
ORIFICE NUMBER†
(Btuh)
(Btuh)
40,000 31,000 #44 60,000 46,000 #38 90,000 70,000 #38 115,000 92,000 #33 130,000 103,000 #31
40,000 31,000 #50 57,000 43,720 #46 85,500 66,520 #46 115,000 92,000 #42 127,000 100,580 #41
32,075 24,858 #48 48,547 37,219 #42 72,820 56,638 #42 90,094 72,075 #37 102,630 81,315 #34
33,834 26,221 #52 49,238 37,766 #48 73,856 57,461 #48 94,571 75,657 #44 101,284 80,214 #43
2001-6000
* As the height above sea level increases, there is less oxygen per cubic ft of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your Bryant distributor.
UNIT SIZE
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
024 0.005 0.007 0.010 0.012 0.015 —
030 — 0.007 0.010 0.012 0.015 0.018 0.021 0.024 —
036 — — — 0.019 0.023 0.027 0.032 0.037 0.042 0.047 —
042 — 0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043 — — —
048 — 0.027 0.032 0.036 0.041 0.046 0.052 0.057 0.063 0.068 —
060 — 0.029 0.032 0.036 0.040 0.045 0.049 0.053




Condensate trap — A 2-in. condensate trap must be field supplied.
covers to seal the horizontal discharge openings in the unit. Units installed in horizontal discharge orientation do not require duct covers. Maximum cooling airflow — To minimize the possibility of condensate blow-off from the evaporator, airflow through the units should not exceed 450 cfm per ton. Minimum cooling airflow — The minimum cooling airflow is 350 cfm per ton. Minimum cooling ambient operating temperature — All standard units have a minimum cooling ambient operating temperature of 55°F. With accessory low ambient temperature kit, units can operate at temperatures down to 0°F. Maximum operating outdoor air temperature — for cooling is 125°F.
1” MIN.
2” MIN.
Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges. To convert a unit to downflow discharge — Units are equipped with factory-installed inserts in the down-flow openings. Removal of the inserts is similar to removing an electrical knock-out. The unit is factory equipped with duct

RANGE COMPRESSOR OUTDOOR FAN
INDOOR FAN
UNIT SIZE 574B V-PH-Hz
MOTOR
MOTOR POWER SUPPLY
MAX FUSE
OR BKR 024 208/230–1–60 187 253 13.5 61.0 0.8 4.3 22.0/22.0 30/30 030 208/230–1–60 187 253 16.9 73.0 0.8 4.3 25.0/25.0 30/30
036 208/230–1–60 187 253 15.9 83.0 0.8 6.8 28.7/28.7 35/35 208/230–3–60 187 253 12.2 77.0 0.8 6.8 22.9/22.9 30/30
042 208/230–1–60 187 253 22.4 105.0 0.8 6.8 35.6/35.6 45/45 208/230–3–60 187 253 15.4 88.0 0.8 6.8 26.9/26.9 35/35
048 208/230–1–60 187 253 21.3 109.0 1.6 6.8 35.0/35.0 45/45 208/230–3–60 187 253 14.7 91.0 1.6 6.8 26.8/26.8 35/35
060 208/230–1–60 187 253 27.0 145.0 1.6 9.1 44.5/44.5 60/60 208/230–3–60 187 253 18.1 123.0 1.6 9.1 33.3/33.3 40/40
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
FLA — Full Load Amps LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps
452 + 464 + 455 Average Voltage =
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW will vary accordingly.
Determine maximum deviation from average voltage.
(AB) 457 (BC) 464 (AC) 457 Maximum deviation is 7 v.
452 = 5 v 457 = 7 v 455 = 2 v
NOTES: 1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker. 2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
Determine percent of voltage imbalance.
7 % Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
max voltage deviation from average voltage = 100 x average voltage





The indoor blower will cycle on and off with a call for cooling per the on/off delay profile selected on the easy select™ circuit board. NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains “on” until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat “breaks” the circuit between thermostat terminal R to terminals Y and G. These open circuits de-energize contactor coil C and relay coil BR. The condenser and compressor motors stop. After a 30-second de- lay, the blower motor stops. The unit is in a “standby” condition, waiting for the next “call for cooling” from the room thermostat. The indoor blower operation with a call for fan operation (G) in cooling mode will perform by the on/off delay profile selected on the Easy Select™ circuit board.
Heating — On a call for heating, terminal “W” of the thermostat is energized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC). The evaporator fan motor is energized 45 seconds after flame is es- tablished. When the thermostat is satisfied and “W” is de- energized, the burners stop firing and the evaporator fan motor shuts off after a 45-second time-off delay. Cooling — When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the ther- mostat connect contactor coil (C) (through unit wire Y) and blow- er relay coil (BR) (through unit wire G) across the 24-v secondary of transformer (TRAN). The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to con- denser (outdoor) fan motor (OFM). Both motors start instantly.





PACKAGED GAS HEATING/ELECTRIC COOLING UNITS CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING
C. Fans:
BRYANT MODEL NUMBER: 574B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a scroll compressor for cooling duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings. Condenser fan/coil section shall have a draw-thru design with vertical discharge for minimum sound levels. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standards
plate fins mechanically bonded to seamless copper tubes with all joints brazed. (Copper/copper and vinyl- coated construction available as option). Tube sheet openings shall be belled to prevent tube wear. F. Heating Section: 1. Induced-draft combustion type with energy saving direct spark ignition system and redundant main gas valve. 2. Induced-draft motors shall be provided with solid- state hall-effect sensor to ensure adequate airflow for combustion. 3. The heat exchangers shall be constructed of aluminized steel for corrosion resistance. 4. Burners shall be of the in-shot type constructed of aluminum coated steel. 5. All gas piping and electric power shall enter the unit cabinet at a single location. G. Refrigerant Components:
210/240-94 and 270-95 (Sound ratings for 270-95 are not listed with ARI). B. Unit shall be designed in accordance with UL Standard
1995. C. Unit shall be manufactured in a facility registered to
ISO 9001 manufacturing quality standard. D. Unit shall be UL listed and certified under Canadian
Standards as a total package for safety requirements. E. Roof curb shall be designed to conform to NRCA
Standards. F. Insulation and adhesives shall meet NFPA 90A requirements for flame spread and smoke generation. G. Cabinet insulation shall meet ASHRAE Standard 62P. 1.03 DELIVERY, STORAGE AND HANDLING Unit shall be stored and handled per manufacturer’s
recommendations. PART 2 — PRODUCTS 2.01 EQUIPMENT A. General:
Refrigerant expansion shall be of the fixed orifice type. H. Filters:
Factory-assembled, single-piece, heating and cooling unit. Contained within the enclosure shall be all factory wiring, piping, controls, refrigerant charge with R-410A refrigerant, and special features required prior to field start-up. B. Unit Cabinet:
Filter section shall consist of field-installed, throwaway, 1-in. thick fiberglass filters of commercially available sizes. I. Controls and Safeties: 1. Unit controls shall be complete with a self- contained low voltage control circuit. 2. Compressors shall incorporate a solid-state compressor protector that provides reset capability. 3. Unit shall provide high and loss-of-charge/low pressure safety protection. J. Operating Characteristics:
1. Unit Cabinet shall be constructed of phosphated, zinc-coated, pre-painted steel capable of with- standing 500 hours in salt spray. 2. Normal service shall be through a single removable cabinet panel. 3. The unit shall be constructed on a rust proof unit base that has an externally trapped, integrated sloped drain pan. 4. Evaporator fan compartment top surface shall be insulated with a minimum 1/2-in. thick, flexible fiberglass insulation, coated on the air side and retained by adhesive and mechanical means. The evaporator wall sections will be insulated with a minimum semi-rigid foil-faced board capable of being wiped clean. Aluminum foil-faced fiberglass insulation shall be used in the entire indoor air cavity section. 5. Unit shall have a field-supplied condensate trap.

K. Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single
location. L. Motors:
manual or automatic changeover and indoor fan control. 6. Natural-to-Propane Conversion Kit: Shall be complete with all required hardware to convert
to liquid propane (LP) operation. 7. Low Ambient Package: Shall consist of a solid-state control and condenser coil temperature sensor for controlling condenser-fan mo- tor operation, which shall allow unit to operate down to 0° F outdoor ambient temperature. 8. Filter Rack Kit: Shall provide filter mounting for downflow applications. 9. Square-To-Round Duct Transitions 024-048: Shall have the ability to convert the supply and return
guard and vandalism protection. N. Duct Conversion:
openings from rectangular to round. 10. Compressor Protection (Time Guard® II Kit) Solid-state control shall protect compressor by prevent-
Shall be available with the use of included duct covers. O. Special Features Available:
ing “short cycling.” 11. Crankcase Heater: Shall provide anti-floodback protection for low-load
door, copper/copper and vinyl-coated refrigerant coils. 2. Economizer: a. Economizer controls capable of providing free cool-
cooling applications. 12. High Altitude Kit: Shall consist of natural gas orifices to compensate for
gas heat operation at 2001 to 6000 ft above sea level. 13. Low NOx (Natural Gas only) option: Shall provide NOx reduction to values below 40 nano-
ing using outside air. b. Equipped with low leakage dampers not to exceed
3% leakage, at 1.0 in. wg pressure differential. c. Spring return motor shuts off outdoor damper on
grams/joule to meet California emission requirements. 14. Compressor Hard Start Kit: Shall provide additional starting torque for single-phase
power failure. 3. Flat Roof Curb: Curbs shall have seal strip and a wood nailer for flash-
compressors. (Single phase only). 15. Rigging kit includes rigging brackets which are inserted into the unit base rigging holds to rig unit for rooftop ap- plications.
ing and shall be installed per manufacturer’s instruc- tions. 4. Manual Outdoor Air Damper: Package shall consist of damper, birdscreen, and rain-
hood which can be preset to admit outdoor air for year- round ventilation.