Bryant 548D

40 pages·1.3 MB·Heat Pump·PDF·ENDEFRITNLJA
Bryant 548D
Table of Contents 80 sections 548D Sizes 090-120 7 1 / 2 to 10 Tons · CONTENTS · INSTALLATION · I. STEP 1 — PROVIDE UNIT SUPPORT · … ShowHide
548D Sizes 090-120 7 1 / 2 to 10 Tonsp.1CONTENTSp.1INSTALLATIONp.1I. STEP 1 — PROVIDE UNIT SUPPORTp.1SAFETY CONSIDERATIONSp.1Fig. 1 — Roof Curb Detailsp.2II. STEP 2 — FIELD FABRICATE DUCTWORKp.3DRAIN PLUGp.3Fig. 3 — Condensate Drain Connectionp.3III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAPp.3Fig. 4 — External Trap Condensate Drainp.3NOTES:p.4Fig. 5 — Rigging Detailsp.4Table 1 — Physical Datap.6V. STEP 5 — MAKE ELECTRICAL CONNECTIONSp.7Fig. 7 — Power Wiring Connectionsp.7Table 2A — Electrical Data (Units Without Electrical Convenience Outlet)p.8Table 2B — Electrical Data (Units With Electrical Convenience Outlet)p.9LEGEND AND NOTES FOR TABLES 2A AND 2Bp.10D. Heat Anticipator Settingsp.11VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONSp.11A. Disconnect Switchp.11Table 3 — Heat Anticipator Settingsp.12OAT (TERMINALS ARE UP)p.14TOPp.14Fig. 17 — Durablade Economizer Damperp.14Minimum Position Settingp.14UNITp.14OUTSIDE AIR SCREENp.14ENTHALPY CONTROLp.14REV. Bp.14MINIMUM POSITIONp.14OPENp.14S O Dp.14TRp.14P P1p.14HOODp.14T1p.141 98818Ap.14OR UNPOWERED STATEp.14CONTACTS SHOWN IN HIGH ENTHALPYp.14TR TR1 24VAC ENTHALPY CONTROLp.14DAMPERp.14D C B Ap.14CW–SETPOINTS–CCWp.14OUTDOOR TEMP. ° Fp.14DAMPER CLOSEDp.14REV. 97-3672p.14Fig. 19 — Outdoor-Air Thermostat/p.14Fig. 18 — Durablade Economizer Minimump.14Position Damper Settingp.14Enthalpy Control Installationp.14Fig. 20 — Wiring Connections forp.14Outdoor-Air Thermostatp.14Fig. 30 — EconoMi$er Wiringp.17ECONOMI$ER CONTROLLERp.17BROWNp.17TEMPp.17VIOLETp.17OUTDOOR AIR SENSORp.17OATp.17COM OUT PWRp.17COMp.17WHITEp.17OAHp.17REDp.17RATp.17BROWN TEMP TEMP COM OUT PWRp.17VIOLET WHITEp.17RETURN AIR SENSORp.17RAHp.17+15 Vp.17SENSOR CO 2 (+) COMp.17V+ 24p.17CO 2 CO 2p.17COM VACp.17DAT COM REM POTp.17SUPPLY AIR TEMPERATURE SENSORp.17PINK TEMPp.17LED COMp.17
Page 1 of the Bryant 548D user manual — Table of Contents
Page 1 · Contents
Contents

Contents

548D Sizes 090-120 7 1 / 2 to 10 Tonsp.1CONTENTSp.1INSTALLATIONp.1I. STEP 1 — PROVIDE UNIT SUPPORTp.1SAFETY CONSIDERATIONSp.1Fig. 1 — Roof Curb Detailsp.2II. STEP 2 — FIELD FABRICATE DUCTWORKp.3DRAIN PLUGp.3Fig. 3 — Condensate Drain Connectionp.3III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAPp.3Fig. 4 — External Trap Condensate Drainp.3NOTES:p.4Fig. 5 — Rigging Detailsp.4Table 1 — Physical Datap.6V. STEP 5 — MAKE ELECTRICAL CONNECTIONSp.7Fig. 7 — Power Wiring Connectionsp.7Table 2A — Electrical Data (Units Without Electrical Convenience Outlet)p.8Table 2B — Electrical Data (Units With Electrical Convenience Outlet)p.9LEGEND AND NOTES FOR TABLES 2A AND 2Bp.10D. Heat Anticipator Settingsp.11VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONSp.11A. Disconnect Switchp.11Table 3 — Heat Anticipator Settingsp.12OAT (TERMINALS ARE UP)p.14TOPp.14Fig. 17 — Durablade Economizer Damperp.14Minimum Position Settingp.14UNITp.14OUTSIDE AIR SCREENp.14ENTHALPY CONTROLp.14REV. Bp.14MINIMUM POSITIONp.14OPENp.14S O Dp.14TRp.14P P1p.14HOODp.14T1p.141 98818Ap.14OR UNPOWERED STATEp.14CONTACTS SHOWN IN HIGH ENTHALPYp.14TR TR1 24VAC ENTHALPY CONTROLp.14DAMPERp.14D C B Ap.14CW–SETPOINTS–CCWp.14OUTDOOR TEMP. ° Fp.14DAMPER CLOSEDp.14REV. 97-3672p.14Fig. 19 — Outdoor-Air Thermostat/p.14Fig. 18 — Durablade Economizer Minimump.14Position Damper Settingp.14Enthalpy Control Installationp.14Fig. 20 — Wiring Connections forp.14Outdoor-Air Thermostatp.14Fig. 30 — EconoMi$er Wiringp.17ECONOMI$ER CONTROLLERp.17BROWNp.17TEMPp.17VIOLETp.17OUTDOOR AIR SENSORp.17OATp.17COM OUT PWRp.17COMp.17WHITEp.17OAHp.17REDp.17RATp.17BROWN TEMP TEMP COM OUT PWRp.17VIOLET WHITEp.17RETURN AIR SENSORp.17RAHp.17+15 Vp.17SENSOR CO 2 (+) COMp.17V+ 24p.17CO 2 CO 2p.17COM VACp.17DAT COM REM POTp.17SUPPLY AIR TEMPERATURE SENSORp.17PINK TEMPp.17LED COMp.17
Page 2 of the Bryant 548D user manual — Fig. 1 — Roof Curb Details
Page 2 · click to enlarge
Page 2
UNIT SIZE “D” ALT “E” “F” 548D “B” “C” DRAIN GAS POWER HOLE 6] 0] 090-150 3/4″ 3/4″ [19] NPT [19] NPT 11/4″ [31.7] N 2′ [- 88 27 7/1 ]6″ 1′-1 [50 81 35/ ]16″ [1 43 4/ .4 5″ ] [12.1 7/ ]2 ″ NPT 3/4″ [19] NPT [193 ]/ 4 N″ 11/4″ [31.7] N PT CONNECTOR “G” PACKAGE CONTROL ACCESSORY 1/2″ [12.7] CRBTMPWR001A00 PT NPT CRBTMPWR002A00 CRBTMPWR003A00 1/2″ [12.7] NPT PT CRBTMPWR004A00 NOTES: 6. Service clearance 4 ft on each side. 1. Roof curb accessory is shipped unassembled. 7. Direction of airflow. 2. Insulated panels, 1 in. thick polyure3. t Dh ia mn ee n f so ia om ns, i1 n3 / [4 lb ] ad re en is nit y m. illimeters. 8. C 00o 2n An 0e 0ct or a rp ea ck foa rg e ts h rC uR -tB heT -M cuP rW b R c0 o0 n1 nA e0 c0 t 4. Roof curb: 16 gage steel. Packages CRBTMP003A00 and 004A00 5. Attach ductwork to curb (flanges of duct for thru-the-bottom connections. rest on curb). S CLOSE TO B AS POSSIBLE

Fig. 1 — Roof Curb Details

Page 3 of the Bryant 548D user manual — Fig. 4 — External Trap Condensate Drain
Page 3 · click to enlarge
Page 3
M A0.AXIMUM ALLOWABLE DIFFERENCE (in.) A-BB-CA-C 0.51.01.0 Fig. 2 — Unit Leveling Tolerances
Bryant 548D — II. STEP 2 — FIELD FABRICATE DUCTWORK diagram (page 3)
Fig. 1

Lifting holes are provided in base rails as shown in Fig. 5 and 6. Refer to rigging instructions on unit.

Positioning Maintain clearance around and above unit to provide proper airflow and service access. See Fig. 6. Position unit on roof curb so that the following clearances are maintained: 1/4-in. clearance between roof curb and base rails on each side and in duct end of unit; 35/16-in. clearance between roof curb and condenser end (see Fig. 1, section C-C). Do not install unit in an indoor location. Do not locate unit air inlet near exhaust vents or other sources of contami- nated air.

II. STEP 2 — FIELD FABRICATE DUCTWORK

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

On vertical discharge units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For hori- zontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external duct- work, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap- plicable fire codes.

After unit is in position, remove polyethylene shipping wrap- per and rigging skid.

A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal discharge units with electric heat, a minimum clearance of 1 in. is required for the first 12 in. of ductwork. Cabinet return-air static should not exceed –0.35 in. wg with Durablade econo- mizer, –0.30 in. wg with EconoMi$er, or –0.45 in. wg without economizer.

DRAIN PLUG

Fig. 3 — Condensate Drain Connection

III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAP

Condensate drain connections are located on the bottom and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.

When using the standard end drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit. To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug (Red) from the bot- tom connection to the end connection. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.

Bryant 548D — Fig. 3 — Condensate Drain Connection diagram (page 3)
Fig. 2 · Fig. 3 — Condensate Drain Connection

All units must have an external trap for condensate drain- age. Install a trap at least 4-in. deep and protect against freeze-up. See Fig. 4. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.).

IV. STEP 4 — RIG AND PLACE UNIT Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.

Fig. 4 — External Trap Condensate Drain

Page 4 of the Bryant 548D user manual — Fig. 5 — Rigging Details
Page 4 · click to enlarge
Page 4
Bryant 548D — NOTES: diagram (page 4)
Fig. 3

NOTES:

1. Dimension in ( ) is in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. 3. Unit weights do not include economizer. See Table 1 for economizer weights.
UNIT 548DMAX WEIGHTDIMENSIONS ‘‘A’’‘‘B’’‘‘C’’ lbkgin.mmin.mmin.mm 09094042677.421966.541.5105442.121070 10296543877.421966.541.5105442.121070 120101546077.421966.541.5105442.121070

Fig. 5 — Rigging Details

Page 5 of the Bryant 548D user manual — NOTES:
Page 5 · click to enlarge
Page 5
BO M O A T H E E H O L E C R N C R N C R N C R N S ECO O FT OT RO U S E I T H A C C E S, O R YS P A C K A G ER S —Q’D ED CU O N OB MI Z EE R WO E HE TR WO E HE TR WO E HE TR WO E HE TR “H” “J” “K” WT ED I GU HNI TT WN EI GM HI$ TER 1 WR EA I GL HA TD (I AG ) (I BG ) (I CG ) (I DG ) 2 4 ″ , ″) OE RS / 3/ C RP B TWW ME PR WC RH 00 1R AT 0S 0 ( 5U 4N 8IT D Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm 11/4″) CRBTMPWR002A00 (1/2″, 940 426 44 20 62 28 207 94 178 81 254 115 301 136 207/8 632 3-55/16 1050 2-911/16 856 090 T E E RE Q W CH OR N D UI TD S’ I Z E SOLE UI SR EE 77 55 31 SI ZA ED ( MD a xH .) 88 11 66 8/16 109 16 55 44 63 08 44 44 22 00 66 22 22 88 22 21 32 19 06 1 11 98 33 88 83 22 76 41 11 21 49 33 20 59 11 44 70 22 -- 1 00 // 86 83 52 43 -- 15 // 11 20 55 30 32 -- 09 /1 98 25 46 11 20 02 24 V 7/8″ [22.2] 1/2″ N O E S: CONNECTION SIZES Power* [28.4] 11/8″ 3/4″ 1 .T Di mensions in [ ] are in millimeters. Dia. [35] Field Power Supply Hole 13/8″ A Power* 13/4″ [44.4] 11/4″ FPT Cent e v y. D [ P w p K o *S e either 3/4″ or 11/4″ for power, depending on wire 31 42 ″″ 12 // Dii aa .. [6 44 4] ] Co ha re gr i nS gu Pp ol ry t Hn ol eckout CB si zl ee .ct 32 .. Di rr eo cf t ig or na oi ft airflow. Dia. [22] Field Control Wiring Hole 7/8″ D 4. Ductwork to be attached to accessory roof curb only. 3/4″ — 14 NPT Condensate Drain E 5. Minimum clearance (local codes or jurisdiction may prevail): 2″ Dia. [51] Power Supply Knockout F a. Bottom to combustible surfaces (when not using curb) 0 inches, on horizontal discharge units with electric heat 1 in. clearance to ductwork for 1 ft. b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clearance is optional. c. Overhead, 60 in. to assure proper condenser fan operation. d. Between units, control box side, 42 in. per NEC (National Electrical Code). e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC. f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per NEC. g. Horizontal supply and return end, 0 inches. 6. With the exception of the clearance for the condenser coil as stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance. 7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material. 8. The vertical center of gravity is 1′-71/2″ [495] for 090 and 102, 2′-0″ [610] for 120 up from the bottom of the base rail. Fig. 6 — Base Unit Dimensions C R N C R N C R N C R N N O WO E HE TR WO E HE TR WO E HE TR WO E HE TR “H” “ EI GM HI$ TER (I AG ) (I BG ) (I CG ) (I DG )Kg Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in.28 207 94 178 81 254 115 301 136 207/8 632 3-55/1628 212 96 183 83 261 119 309 140 207/8 632 3-55/1628 223 101 193 88 274 124 325 147 2-107/8 885 4-15/16 D ECO CU O N OB MI Z EE R W WR EA I GL HA TDLb Kg Lb44 20 6244 20 6244 20 62 S E WT ED I GU HNI TTLb Kg940 426965 4381015 460 UNIT 548D090102120
Page 6 of the Bryant 548D user manual — Table 1 — Physical Data
Page 6 · click to enlarge
Page 6

Table 1 — Physical Data

UNIT SIZE 548D090102120 NOMINAL CAPACITY (tons)71/281/210 OPERATING WEIGHT (lb) Unit Al/Al* Economizer Durablade EconoMi$er Roof Curb†940 44 62 143965 44 62 1431015 44 62 143 COMPRESSOR Quantity Oil (oz)Hermetic Scroll 2 2 2 45 ea 62 ea 54 ea REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2R-22 5-14 86 7-14 5-13 8-13 83 OUTDOOR COIL Rows...Fins/in. Total Face Area (sq ft)Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device 1...17 2...17 2...17 20.50 18.00 18.30 OUTDOOR FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total)Propeller Type 6500 6500 6500 2...22 2...22 2...22 1/4...1100 1/4...1100 1/4...1100 600 600 600 INDOOR COIL Rows...Fins/in. Total Face Area (sq ft)Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Fixed Orifice Metering Feed Device 3...15 3...15 3...15 8.0 8.0 11.1 INDOOR FAN Quantity...Size (in.) Std Alt Type Drive Std Alt Nominal Cfm Maximum Continuous Bhp Std Alt Motor Frame Size Std Alt Nominal Rpm High/Low Std Alt Fan Rpm Range Std Alt Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Min/Max (in.) Std Alt Nominal Motor Shaft Diameter (in.) Std Alt Fan Pulley Pitch Diameter (in.) Std Alt Belt, Quantity...Type...Length (in.) Std Alt Pulley Center Line Distance (in.) Std Alt Speed Change per Full Turn of Movable Pulley Flange (rpm) Std Alt Movable Pulley Maximum Full Turns From Closed Position Std Alt Factory Setting Std Alt Factory Speed Setting (rpm) Std Alt Fan Shaft Diameter at Pulley (in.)Centrifugal Type 1...15 x 15 1...15 x 15 1...15 x 15 1...15 x 15 — 1...15 x 15 Belt — Belt 3000 3600 4000 2.40 2.40 2.40 — — 2.90 56 56 56 — — 56 — 590-840 685-935 685935 685-935 — 835-1085 Ball Ball Ball 2100 2100 2100 2.4/3.4 2.8/3.8 2.8/3.8 2.8/3.8 — 3.4/4.4 5/8 5/8 5/8 — — 7/8 7.0 — 7.0 1...A...48 — 1...A...48 16.75-19.25 16.75-19.25 15.85-17.50 15.75-19.25 — 15.85-17.50 — 50 5 — 5 — 5 590 685 685 685 — 835 1 1 1 HIGH-PRESSURE SWITCH (psig)** Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.)450 ± 50 428 320 LOSS-OF-CHARGE SWITCH (psig)** Cutout Reset (Auto.)7 ± 3 22 ± 5 FREEZE-PROTECTION THERMOSTAT (F)** Opens Closes30 ± 5 45 ± 5 OUTDOOR-AIR INLET SCREENS Quantity...Size (in.)Cleanable 1...20 x 25 x 1 1...16 x 25 x 1 RETURN-AIR FILTERS Quantity...Size (in.)Throwaway 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2

Al — Aluminum Bhp — Brake Horsepower

*Indoor coil fin material/outdoor coil fin material. †Weight of 14-in. roof curb. **Requires an accessory or optional controls upgrade kit.

Page 7 of the Bryant 548D user manual — Fig. 7 — Power Wiring Connections
Page 7 · click to enlarge
Page 7

V. STEP 5 — MAKE ELECTRICAL CONNECTIONS

When installing units, provide a disconnect per the NEC. All field wiring must comply with the NEC and local re- quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One. Install field wiring as follows:

WARNING: Unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute) / NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

1. Install conduit through side panel openings. For units without electric heat, install conduit between discon- nect and control box. 2. Install power lines to terminal connections as shown in Fig. 7. 3. For units with electric heat, refer to Accessory Instal- lation Instructions. 4. If thru-the-bottom control connections are used, refer to the accessory installation instructions for informa- tion on control wiring. Refer to Fig. 6 for drilling holes in basepan. During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be bal- anced within 2%, and the current within 10%. Use the for- mula shown in Tables 2A and 2B, Note 2 on page 10 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance consti- tutes abuse and may cause damage to electrical compo- nents. Such operation would invalidate any applicable warranty.

A. Field Power Supply All units except 208/230-v units are factory-wired for the voltage shown on the unit nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer. Refer to unit label diagram for additional information. Pig- tails are provided for field wire connections. Use factory- supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.

Bryant 548D — V. STEP 5 — MAKE ELECTRICAL CONNECTIONS diagram (page 7)
Fig. 4
Bryant 548D — V. STEP 5 — MAKE ELECTRICAL CONNECTIONS diagram (page 7)
Fig. 5

LEGEND C — Contactor COMP — Compressor IFC — Indoor Fan Contactor NEC — National Electrical Code TB — Terminal Block

Field Wiring Factory Wiring Splice Connection (Factory-Supplied)

Fig. 7 — Power Wiring Connections

208/230-3-60 460-3-60 575-3-60

Page 8 of the Bryant 548D user manual — Table 2A — Electrical Data (Units Without Electrical Convenience Outlet)
Page 8 · click to enlarge
Page 8

Table 2A — Electrical Data (Units Without Electrical Convenience Outlet)

UNIT 548DNOMINAL V-PH-HzIFM TYPEVOLTAGE RANGECOMPRESSOR (each)OFM FLAIFM FLAELECTRIC HEAT*POWER SUPPLYDISCONNECT SIZE† MinMaxRLALRANominal kW**FLAMCAMOCPFLALRA 090 (71/2 Tons)208/230-3-60STD18725413.491.01.45.8— 7.8/10.4 12.0/16.0 18.6/24.0 24.0/32.0 31.8/42.4— 21.7/ 25.0 33.3/ 38.5 50.0/ 57.7 66.6/ 77.0 88.3/102.038.8/ 38.8 65.9/ 70.0 80.4/ 86.9 103.3/113.4 122.0/135.0 149.1/166.340/ 40†† 70/ 80 90/ 90 110/125 125/150 150/17541/ 41 66/ 69 79/ 85 100/109 117/129 142/158229/229 251/254 262/268ll 281/289ll 296/306ll 317/331ll 460-3-60STD4145086.742.00.72.6— 13.9 16.5 27.8 33.0 41.7— 16.7 19.8 33.4 39.7 50.219.1 40.0 43.8 60.8 68.7 81.820†† 45†† 45†† 70 70 9020 39 43 58 66 78108 124 128 141 147 158 575-3-60STD5186325.439.00.72.6— 17.0 34.0— 17.1 34.115.4 36.7 68.020†† 40†† 60††16 36 5597 114 131 102 (81/2 Tons)208/230-3-60STD18725416.0137.01.45.8— 7.8/10.4 12.0/16.0 18.6/24.0 24.0/32.0 31.8/42.4— 21.7/ 25.0 33.3/ 38.5 50.0/ 57.7 66.6/ 77.0 88.3/102.044.6/ 44.6 71.7/ 75.9 86.2/ 92.7 109.1/119.2 127.9/140.9 155.0/172.045/ 45†† 80/ 80 90/100 110/125 150/150 175/17547/ 47 72/ 75 85/ 91 106/115 123/135 148/164321/321 343/346 354/360II 373/381II 388/398II 409/423II 460-3-60STD4145088.369.00.72.6— 13.9 16.5 27.8 33.0 41.7— 16.7 19.8 33.4 39.7 50.222.7 43.6 47.4 64.4 72.3 85.425†† 45†† 50†† 70 80 9024 43 46 62 69 81162 178 182 195 201 212II 575-3-60STD5186326.458.00.72.6— 17.0 34.0— 17.1 34.117.3 39.0 60.220†† 40†† 60††18 38 58135 152 169 120 (10 Tons)208/230-3-60STD18725417.2124.01.45.8— 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0— 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.347.3/ 47.3 74.4/ 78.6 88.9/ 95.4 130.6/143.6 157.7/174.8 177.8/167.650/ 50†† 80/ 80 90/100 150/150 175/175 200/17549/ 49 74/ 78 88/ 94 126/138 151/167 170/188295/295 317/320 328/334ll 362/372ll 383/397ll 399/415ll ALT18725417.2124.01.47.5— 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0— 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.349.0/ 49.0 76.1/ 80.8 90.6/ 97.1 132.3/145.3 159.4/176.5 179.5/169.350/ 50†† 80/ 90 100/100 150/150 175/200 200/17551/ 51 76/ 80 90/ 96 128/140 153/169 171/190314/314 336/389ll 347/353ll 381/391ll 402/416ll 418/434ll 460-3-60STD4145088.659.60.72.6— 16.5 27.8 33.0 41.7 50.0— 19.8 33.4 39.7 50.2 60.123.4 48.1 65.1 73.0 86.1 83.525†† 50†† 70 80 90 9024 47 63 70 82 93143 163 176 183 193ll 203ll ALT4145088.659.60.73.4— 16.5 27.8 33.0 41.7 50.0— 19.8 33.4 39.7 50.2 60.124.2 48.9 65.9 73.8 86.9 84.325†† 50†† 70 80 90 9025 48 64 71 83 94182 202 216 222 233ll 243ll 575-3-60STD5186326.949.40.72.6— 17.0 34.0 51.0— 17.1 34.1 51.218.7 40.1 61.4 69.920†† 50†† 70 7020 39 59 78118 135 152 159 ALT5186326.949.40.73.4— 17.0 34.0 51.0— 17.1 34.1 51.219.4 40.7 62.0 70.620†† 50†† 70 8020 40 60 79149 166 183 201
Page 9 of the Bryant 548D user manual — Table 2B — Electrical Data (Units With Electrical Convenience Outlet)
Page 9 · click to enlarge
Page 9

Table 2B — Electrical Data (Units With Electrical Convenience Outlet)

UNIT 548DNOMINAL V-PH-HzIFM TYPEVOLTAGE RANGECOMPRESSOR (each)OFM FLAIFM FLAELECTRIC HEAT*POWER SUPPLYDISCONNECT SIZE† MinMaxRLALRANominal kW**FLAMCAMOCPFLALRA 090 (71/2 Tons)208/230-3-60STD18725413.491.01.45.8— 7.8/10.4 12.0/16.0 18.6/24.0 24.0/32.0 31.8/42.4— 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.043.6/ 43.6 70.7/ 74.8 85.2/ 91.7 108.1/118.2 126.8/139.8 153.9/171.145/ 45†† 80/ 80 90/100 110/125 150/150 175/17546/ 46 71/ 75 85/ 91 106/115 123/135 148/164234/234 256/259 267/272ll 285/294ll 300/311ll 322/336ll 460-3-60STD4145086.742.00.72.6— 13.9 16.5 27.8 33.0 41.7— 16.7 19.8 33.4 39.7 50.221.3 42.1 46.0 63.0 70.9 84.025†† 45†† 50†† 70 80 9023 42 45 61 68 80110 127 130 143 150 160ll 575-3-60STD5186325.439.00.72.6— 17.0 34.0— 17.1 34.117.1 38.5 59.720†† 40†† 60††18 38 5799 116 133 102 (81/2 Tons)208/230-3-60STD18725414.4103.01.45.8— 7.8/10.4 12.0/16.0 18.6/24.0 24.0/32.0 31.8/42.4— 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.049.4/ 49.4 76.5/ 80.7 91.0/ 97.5 113.9/124.0 132.7/145.7 159.8/176.950/ 50†† 80/ 90 100/100 125/125 150/150 175/20052/ 52 77/ 81 91/ 96 112/121 129/141 154/170326/326 348/351ll 359/364ll 377/386ll 392/403ll 414/428ll 460-3-60STD4145087.252.50.72.6— 13.9 16.5 27.8 33.0 41.7— 16.7 19.8 33.4 39.7 50.224.9 45.7 49.6 66.6 74.5 187.625†† 50†† 50†† 70 80 9026 45 49 65 72 84164 181 184 197 204 214ll 575-3-60STD5186326.044.00.72.6— 17.0 34.0— 17.1 34.119.3 40.7 62.020†† 45†† 7020 40 60137 154 171 120 (10 Tons)208/230-3-60STD18725417.2124.01.45.8— 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0— 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.352.1/ 52.1 79.2/ 83.4 93.7/100.2 135.4/148.4 162.5/179.6 182.6/172.460/ 60†† 80/ 90 100/110 150/150 175/200 200/20055/ 55 80/ 84 93/ 99 132/144 157/172 175/193300/300 322/325ll 333/338ll 366/377ll 388/402ll 404/420ll ALT18725417.2124.01.47.5— 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0— 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.353.8/ 53.8 80.9/ 85.1 95.4/101.9 137.1/150.1 164.2/181.3 184.3/174.160/ 60†† 90/ 90 100/110 150/175 175/200 200/20057/ 57 82/ 86 93/101 134/145 158/174 177/195319/319 341/344ll 352/357ll 385/396ll 407/421ll 423/439ll 460-3-60STD4145088.659.60.72.6— 16.5 27.8 33.0 41.7 50.0— 19.8 33.4 39.7 50.2 60.125.5 50.3 67.3 75.2 88.3 85.630†† 60†† 80 80 90 9027 50 65 73 85 96145 165 178 185 195ll 205ll ALT4145088.659.60.73.4— 16.5 27.8 33.0 41.7 50.0— 19.8 33.4 39.7 50.2 60.126.3 51.1 68.1 76.0 89.1 86.430†† 60†† 70 80 90 9028 51 66 73 85 97185 204 218 224 235ll 245ll 575-3-60STD5186326.949.40.72.6— 17.0 34.0 51.0— 17.1 34.1 51.220.5 41.8 63.1 71.720†† 45†† 70 8022 41 61 80120 137 154 171ll ALT5186326.949.40.73.4— 17.0 34.0 51.0— 17.1 34.1 51.221.1 42.5 63.7 72.320†† 45†† 70 8022 42 62 81151 168 185 202ll
Page 10 of the Bryant 548D user manual — LEGEND AND NOTES FOR TABLES 2A AND 2B
Page 10 · click to enlarge
Page 10

LEGEND AND NOTES FOR TABLES 2A AND 2B

FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor-Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor-Fan Motor RLA — Rated Load Amps

= 100 x max voltage deviation from average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

= 457 Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.

*Heaters are field installed only. †Used to determine minimum disconnect per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker.

% Voltage Imbalance = 100 x 7 457

||Optional disconnect switch is unavailable. (Applies to units with an FLA greater

or equal to 80.) NOTES:

= 1.53%

1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

% Voltage Imbalance · average voltage · = 1371

Page 11 of the Bryant 548D user manual — VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
Page 11 · click to enlarge
Page 11

B. Field Control Wiring Install an approved accessory thermostat assembly accord- ing to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the condi- tioned space to sense average temperature in accordance with thermostat installation instructions.

each unit and record quantity of ventilation air needed for use in Step 8.

2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 11. Remove optional outdoor-air damper hood package from filter section. 3. Assemble outdoor-air hood top and side plates as shown in Fig. 12. Install seal strips on hoop top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 8) as described in Steps 1 through 4 below.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Bryant 548D — D. Heat Anticipator Settings diagram (page 11)
Fig. 6 · D. Heat Anticipator Settings
1. If unit is mounted on roof curb and accessory thruthe-curb service plate connection is used, route wire through connection plate.
2. Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 6).
3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clearance between the highand low-voltage wiring. 4. Connect thermostat wires to screw terminals of lowvoltage connector (see Fig. 8).

AHA — Adjustable Heat Anticipator CC — Cooling Compensator

C. Defrost Board The defrost board timer cycle is set to 30 minutes. To change the cycle time, remove the wire from defrost board connected to the 30-minute quick-connect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time.

D. Heat Anticipator Settings

For units with electric heat, set heat anticipator settings as shown in Table 3.

VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS

A. Disconnect Switch

The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes. (See Fig. 9.)

B. Optional Durablade Economizer The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical dis- charge application, discard this plate.

1. Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by

Assembly

Page 12 of the Bryant 548D user manual — Table 3 — Heat Anticipator Settings
Page 12 · click to enlarge
Page 12

Table 3 — Heat Anticipator Settings

UNITUNIT VOLTAGE 208/230460575 Heater kW*ConfigurationHeater kW*ConfigurationHeater kW* 2Configuration 1-Stage2-Stage1-Stage2-Stage1-Stage2-Stage Stage 1Stage 2Stage 1StageStage 1Stage 2 548D10.4, 16.00.3NANA13.9, 16.5 27.8, 33.00.3NANA17.0, 34.00.3NANA 24.8, 32.00.60.30.3 42.4, 50.00.90.60.341.7, 50.00.60.30.351.00.60.30.3
Bryant 548D — Table 3 — Heat Anticipator Settings diagram (page 12)
Fig. 7 · Table 3 — Heat Anticipator Settings

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Bryant 548D — Table 3 — Heat Anticipator Settings diagram (page 12)
Fig. 8 · Table 3 — Heat Anticipator Settings

Adjust minimum position setting by loosening the screws on the position setting bracket. See Fig. 18. Slide bracket until the top screw is in the position determined by Fig. 17. Tighten screws. 9. Remove tape and shipping screw from outdoor-air thermostat (OAT). Fas-ten OAT to inside of hood using screws and speed clips provided. See Fig. 19. Make sure OAT terminals are positioned up. 10. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged. 11. Fasten hood top and side plate assembly to outdoor- air opening panel with screws provided. 12. Place knob supplied with economizer on OAT. See Fig. 19. Set for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 19.

13. Connect OAT per Fig. 20. 14. Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided.
4. On size 120 units, install vertical discharge block-off plate over duct openings. See Fig. 13. 5. Economizer is factory-installed in unit and secured with screws. See Fig. 14. NOTE: Be sure rear economizer flange is engaged under tabs in vertical return-air opening.
Bryant 548D — Table 3 — Heat Anticipator Settings diagram (page 12)
Fig. 9 · Table 3 — Heat Anticipator Settings
6. To convert to horizontal discharge application: a. Rotate the economizer 90 degrees until the economizer motor faces the outdoor section (see Fig. 15). b. Remove shipping screw and tape from barometric damper and rotate the barometric relief damper hinge 90 degrees. Barometric relief damper should open vertically to operate properly. c. Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 16.
7. Remove existing 12-pin blue and yellow wire jumper plug and store. Insert 12-pin economizer plug into economizer harness. See Fig. 14. 8. If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum position setting for required airflow. See Fig. 17.
Page 13 of the Bryant 548D user manual — Table 3 — Heat Anticipator Settings
Page 13 · click to enlarge
Page 13
Bryant 548D — Table 3 — Heat Anticipator Settings diagram (page 13)
Fig. 10 · Table 3 — Heat Anticipator Settings
Page 14 of the Bryant 548D user manual — Fig. 20 — Wiring Connections for
Page 14 · click to enlarge
Page 14
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 14)
Fig. 11
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 14)
Fig. 12

Example:

OAT (TERMINALS ARE UP)

Negative Pressure 0.1 in. wg Outdoor Airflow 1100 cfm Determine —

TOP

Fig. 17 — Durablade Economizer Damper

Minimum Position Setting

UNIT

OUTSIDE AIR SCREEN

4 3 2 1 0

ENTHALPY CONTROL

B

REV. B

MINIMUM POSITION

OPEN

S

S O D

TR

T

P P1

HOOD

T1

5 6 7 8 9

% H U M I D I T Y

1 98818A

RUSH AT 24VAC 3 mA MIN. AT 11 VDC CONTACT RATINGS: 1.5A RUN, 3.5A IN

OR UNPOWERED STATE

CONTACTS SHOWN IN HIGH ENTHALPY

TR TR1 24VAC ENTHALPY CONTROL

DAMPER

D C B A

CW–SETPOINTS–CCW

OUTDOOR TEMP. ° F

OPEN

DAMPER CLOSED

REV. 97-3672

Fig. 19 — Outdoor-Air Thermostat/

Fig. 18 — Durablade Economizer Minimum

Position Damper Setting

Enthalpy Control Installation

Bryant 548D — OR UNPOWERED STATE diagram (page 14)
Fig. 13

Fig. 20 — Wiring Connections for

Outdoor-Air Thermostat

Show 4 more labels / short text on this page
Given — · Setting = 6 · 55 50 85 · 60 65 70
Page 15 of the Bryant 548D user manual — OAT (TERMINALS ARE UP)
Page 15 · click to enlarge
Page 15
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 15)
Fig. 14
8. Install the outdoor air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 27 and 29. 9. Remove and save the 12-pin blue and yellow wire jumper plug from the unit wiring harness located in the upper left corner and insert the EconoMi$er plug. Refer to wiring diagram Fig. 30 and 31. Also refer to Fig. 32 if installing an accessory power exhaust.
10. Remove shipping tape from barometric relief dampers and ensure dampers move freely.
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 15)
Fig. 15

C. Optional EconoMi$er See Fig. 22 for EconoMi$er component locations.

1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 23.

Controller should be mounted in vertical position as shown in Fig. 22.

2. Assemble the hood assembly as follows: Remove the EconoMi$er hood from its packaging. Locate the outdoor air opening panel. See Fig. 24. Remove hood assembly shipping brackets located on back (sloped) side of EconoMi$er assembly. These brackets are used to retain hood assembly during shipping only. 3. Install the 1/8 x 3/4 in. seal strip on the exhaust air hood side panels and the bottom bracket. Assemble the exhaust air hood to the outdoor air opening panel as shown in Fig. 24, using the screws provided. Do not attach hood assembly to unit at this time.

4. Install the 1/8 x 7/8 in. seal strip on the outdoor air hood top and side panels. Assemble the outdoor air hood to the outdoor air opening panel as shown in Fig. 25, using the screws provided. Do not attach hood assembly to the unit as this time. 5. Slide the outdoor air inlet screens into the screen track on the hood side panels. While holding the screens in place, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen. Do not attach completed (Fig. 26) hood assembly to unit at this time. 6. Install the return air block-off plate over the return air duct opening. See Fig. 27. 7. Slide the EconoMi$er assembly into the rooftop unit. See Fig. 28 and 29.

Page 16 of the Bryant 548D user manual — OAT (TERMINALS ARE UP)
Page 16 · click to enlarge
Page 16
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 16)
Fig. 16
Bryant 548D — OAT (TERMINALS ARE UP) diagram (page 16)
Fig. 17
11. Install the complete hood assembly on the unit and secure using the screws provided.
12. Remove the indoor fan motor access panel.
13. Mount the supply air temperature sensor to the lower left portion of the indoor blower housing with the two (2) screws provided (see Fig. 33). Connect the violet and pink wires to the corresponding connections on the supply air temperature sensor. Replace the indoor fan motor access panel.

CO2 Control Set Up If a CO2 sensor is not being used, proceed to the next section. If a CO2 sensor is being used, perform the following:

1. Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm. 2. Locate the CO 2 SP (PPM) potentiometer and adjust to the desired set point. See Fig. 34.
Page 17 of the Bryant 548D user manual — Fig. 30 — EconoMi$er Wiring
Page 17 · click to enlarge
Page 17
Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 17)
Fig. 18 · Fig. 30 — EconoMi$er Wiring

Fig. 30 — EconoMi$er Wiring

ECONOMI$ER CONTROLLER

BROWN

TEMP

VIOLET

TEMP

OUTDOOR AIR SENSOR

OAT

COM OUT PWR

COM

WHITE

OAH

RED

RAT

BROWN TEMP TEMP COM OUT PWR

COM

VIOLET WHITE

RETURN AIR SENSOR

RAH

RED

+15 V

SENSOR CO 2 (+) COM

V+ 24

CO 2 CO 2

COM VAC

DAT COM REM POT

SUPPLY AIR TEMPERATURE SENSOR

PINK TEMP

COM

LED COM

TEMP VIOLET

Fig. 31 — EconoMi$er Sensor Wiring

Page 18 of the Bryant 548D user manual — Fig. 32 — Wiring Diagram for Power Exhaust System
Page 18 · click to enlarge
Page 18
Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 18)
Fig. 19 · Fig. 30 — EconoMi$er Wiring

Fig. 32 — Wiring Diagram for Power Exhaust System

Page 19 of the Bryant 548D user manual — Outdoor Temp – Return Air Temp
Page 19 · click to enlarge
Page 19

Mechanical Cooling Lockout Determine the outdoor-air temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiome- ter counterclockwise (CCW) to the OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the outdoor-air temperature is below this value. See Fig. 34. Dry Bulb Changeover Set Up

See Fig. 35 for barometric relief damper characteristics.

Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 19)
Fig. 20 · Fig. 30 — EconoMi$er Wiring

Determine the dry bulb changeover set point from Table 4. The settings are A, B, C and D. Locate the ECON SP potenti- ometer and set the dry bulb changeover set point. See Fig. 34. When the OAT is above this set point, the damper is limited to minimum position setting.

Table 4 — Changeover Set Points

Bryant 548D — Table 4 — Changeover Set Points diagram (page 19)
Fig. 21 · Table 4 — Changeover Set Points

SETTINGS A B C D Dry Bulb (°F) 73 69 66 63 Single Enthalpy* (Btu/lb) 27 25 24 22 Differential Temperature* (°F, Not Adjustable) 2

Differential Enthalpy* (Btu/lb, Not Adjustable) 1

*Field-installed accessory.

If a potentiometer fails, its setting will default to the values in Table 5.

Table 5 — Default Potentiometer Settings

0 200 400 600 800 1000 1200 1400 1600

POTENTIOMETER DEFAULT SETTING CO2 SP (PPM) 1,000 MECH CLG LOCKOUT 47° ECON SP D MIN POS (%) 20

VII. STEP 7 — ADJUST INDOOR-FAN SPEED

Adjust indoor-fan speed to meet jobsite requirements. For units with electric heat, required minimum cfm is 2250 for 548D090, 2550 for 548D102 and 3000 for 548D120 with the following exceptions:

Ventilation Air (Minimum Position Set Up) If ventilation air is not required, proceed to Step 5. If ventila- tion air is required, perform the following:

1. The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board. 2. Locate the minimum position (MIN POS) potentiometer. Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 34.
Bryant 548D — VII. STEP 7 — ADJUST INDOOR-FAN SPEED diagram (page 19)
Fig. 22
3. Replace the filter access panel. See Fig. 11. Ensure the filter access panel slides along the tracks and is securely engaged. 4. Calculate the minimum airflow across the EconoMi$er.

Table 6 shows indoor-fan motor data. Table 7 shows fan rpm at motor pulley settings for standard and alternate motors. Refer to Tables 8-13 to determine fan rpm settings. Fan motor pulleys are factory set for speed shown in Table 1.

a. Calculate % of outside air using the following formula. % Outdoor air through EconoMi$er

To change fan speeds:

1. Shut off unit power supply and tag disconnect.

% Outdoor air = Mixture Temp – Return Air Temp

2. Loosen belt by loosening fan motor mounting nuts See Fig. 36 and 37.

Outdoor Temp – Return Air Temp

3. Loosen movable pulley flange setscrew (see Fig. 38). 4. Screw movable flange toward fixed flange to increase fan rpm or away from fixed flange to decrease speed. Increasing fan rpm increases load on motor. Do not exceed maximum speed specified in Table 1.

b. Divide total CFM by percentage outdoor air, this gives outdoor air volume in CFM.

5. Turn on base unit power.
Page 20 of the Bryant 548D user manual — Fig. 30 — EconoMi$er Wiring
Page 20 · click to enlarge
Page 20
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange). To align fan and motor pulleys:
Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 20)
Fig. 23 · Fig. 30 — EconoMi$er Wiring
1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.

To adjust belt tension:

1. Loosen fan motor mounting plate nuts. 2. Units 090,102 — Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection with 5 to 10 lbs of force) and tighten mounting nuts with 10 lbs torque (see Fig. 36). Unit 120 — Slide motor mounting plate downward to tighten belt tension (1/2-in. deflection with 5 to 10 lbs of force). Secure motor mounting plate nuts with 10 lbs of torque. See Fig. 37. 3. Adjust bolt and nut on mounting plate to secure motor in fixed position. Realign fan and motor pulleys:

1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mounting plate.
Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 20)
Fig. 24 · Fig. 30 — EconoMi$er Wiring
Page 21 of the Bryant 548D user manual — Table 7 — Fan Rpm at Motor Pulley Settings*
Page 21 · click to enlarge
Page 21

Table 6 — indoor-Fan Motor Performance

UNIT 548D INDOOR-FAN

UNIT VOLTAGE

MAXIMUM ACCEPTABLE

MAXIMUM ACCEPTABLE

MAXIMUM AMP DRAW

MOTOR

CONTINUOUS BHP*

OPERATING WATTS

208/230 2.40 2120 6.1 460 2.7 575 2.7

208/230 2.40 2120 6.1 460 2.7 575 2.7

208/230 2.40 2120 6.1 460 2.7 575 2.7

208/230 2.90 2615 7.9 460 3.6 575 3.6

LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 7 — Fan Rpm at Motor Pulley Settings*

UNIT 548D MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5

090† 840 815 790 765 740 715 690 665 635 615 590 090** 935 910 885 860 835 810 785 760 735 710 685 102† 935 910 885 860 835 810 785 760 735 710 685 120† 935 910 885 860 835 810 785 760 735 710 685 120†† 1085 1060 1035 1010 985 960 935 910 885 860 835

*Approximate fan rpm shown. †Indicates standard motor and drive package. ** Indicates alternate drive package only. ††Indicates alternate motor and drive package.

Show 4 more labels / short text on this page
090 Standard · 102 Standard · Standard · Alternate
Page 22 of the Bryant 548D user manual — NOTES:
Page 22 · click to enlarge
Page 22

Table 8 — Fan Performance 548D090 — Vertical Discharge Units

STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 511 0.52 539 592 0.74 708 659 0.95 875 722 1.19 1072 778 1.43 1275 829 1.68 1491 2300 518 0.55 562 599 0.77 731 665 0.98 899 727 1.22 1097 783 1.47 1310 834 1.72 1526 2400 534 0.61 607 613 0.84 787 677 1.06 965 738 1.30 1165 794 1.55 1378 844 1.81 1604 2500 549 0.67 653 627 0.90 835 690 1.14 1031 750 1.38 1233 805 1.64 1456 855 1.91 1691 2550 557 0.71 684 633 0.94 867 697 1.18 1064 756 1.42 1267 811 1.69 1499 861 1.96 1735 2600 565 0.74 708 639 0.97 891 703 1.22 1097 761 1.46 1301 816 1.74 1543 866 2.01 1779 2700 581 0.81 763 652 1.04 948 717 1.31 1173 773 1.55 1378 827 1.83 1621 878 2.12 1875 2800 597 0.89 827 665 1.12 1014 733 1.40 1250 786 1.66 1473 839 1.93 1709 889 2.23 1971 2900 613 0.97 891 679 1.20 1081 745 1.50 1335 799 1.76 1560 850 2.04 1805 900 2.34 2067 3000 629 1.06 965 694 1.29 1156 759 1.59 1413 812 1.88 1665 862 2.15 1901 911 2.46 2171 3100 646 1.15 1039 709 1.39 1241 772 1.70 1508 825 1.99 1761 875 2.28 2015 923 2.58 2275 3200 662 1.25 1123 724 1.50 1335 785 1.80 1595 840 2.11 1866 887 2.41 2128 934 2.71 2386 3300 679 1.35 1207 740 1.61 1430 798 1.91 1691 854 2.24 1980 900 2.54 2240 946 2.85 2504 3400 696 1.46 1301 756 1.73 1534 811 2.02 1788 868 2.37 2093 914 2.69 2369 959 3.00 2629 3500 712 1.57 1396 771 1.85 1639 824 2.14 1892 881 2.50 2206 928 2.84 2495 971 3.16 2759 3600 729 1.69 1499 787 1.98 1753 839 2.21 2006 894 2.64 2326 942 2.99 2620 984 3.22 2886 3700 746 1.85 1613 803 2.12 1875 854 2.42 2136 907 2.78 2445 956 3.15 2751 997 3.49 3017 3750 755 1.89 1674 811 2.20 1945 862 2.49 2197 914 2.85 2504 963 3.23 2815 — — —

STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 884 1.97 1744 937 2.33 2058 947 2.66 2343 1022 3.10 2710 2300 885 2.00 1770 939 2.36 2084 979 2.69 2369 1025 3.12 2727 2400 892 2.08 1840 944 2.40 2119 987 2.76 2428 1039 3.20 2791 2500 902 2.18 1927 949 2.48 2188 1002 2.84 2495 1041 3.25 2831 2550 908 2.24 1980 953 2.53 2232 1003 2.87 2521 1045 3.28 2854 2600 913 2.29 2023 957 2.58 2275 1004 2.91 2554 1050 3.31 2878 2700 924 2.40 2120 967 2.70 2377 1010 3.01 2637 1056 3.37 2925 2800 935 2.52 2223 978 2.62 2479 1019 3.13 2735 1061 3.47 3002 2900 946 2.65 2335 989 2.96 2595 1030 3.27 2847 — — — 3000 957 2.78 2445 1000 3.09 2702 1040 3.41 2956 — — — 3100 968 2.91 2554 1011 3.24 2832 — 3200 980 3.04 2661 1022 3.38 2933 — 3300 991 3.18 2775 — 3400 1003 3.32 2886 — 3500 1014 3.48 3009 — 3600 — 3700 — 3750 —

ensures that the full range of the motor can be utilized with confi- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. 5. Values include losses for filters, unit casing, and wet coils. 6. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 7. Standard motor drive range: 590 to 840 rpm. Alternate motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. 8. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied drive is required. (See Note 7.)
2. indicates alternate drive is required.
3. indicates field-supplied motor and drive are required. 4. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 23 of the Bryant 548D user manual — NOTES:
Page 23 · click to enlarge
Page 23

Table 9 — Fan Performance 548D102 — Vertical Discharge Units

STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 557 0.71 684 633 0.94 867 697 1.18 1064 756 1.42 1267 811 1.69 1499 861 1.96 1735 2600 565 0.74 708 639 0.97 891 703 1.22 1097 761 1.46 1301 816 1.74 1543 866 2.01 1779 2700 581 0.81 763 652 1.04 948 717 1.31 1173 773 1.55 1378 827 1.83 1621 878 2.12 1875 2800 597 0.89 827 665 1.12 1014 733 1.40 1250 786 1.66 1473 839 1.93 1709 889 2.23 1971 2900 613 0.97 891 679 1.20 1081 745 1.50 1335 799 1.76 1560 850 2.04 1805 900 2.34 2067 3000 629 1.06 965 694 1.29 1156 759 1.59 1413 812 1.88 1665 862 2.15 1901 911 2.46 2171 3100 646 1.15 1039 709 1.39 1241 772 1.70 1508 825 1.99 1761 875 2.28 2015 923 2.58 2275 3200 662 1.25 1123 724 1.50 1335 785 1.80 1595 840 2.11 1866 887 2.41 2128 934 2.71 2386 3300 679 1.35 1207 740 1.61 1430 798 1.91 1691 854 2.24 1980 900 2.54 2240 946 2.85 2504 3400 696 1.46 1301 756 1.73 1534 811 2.02 1788 868 2.37 2093 914 2.69 2369 959 3.00 2629 3500 712 1.57 1396 771 1.85 1639 824 2.14 1892 881 2.50 2206 928 2.84 2495 971 3.16 2759 3600 729 1.69 1499 787 1.98 1753 839 2.27 2006 894 2.64 2326 942 2.99 2620 984 3.32 2886 3700 746 1.82 1613 803 2.12 1875 854 2.42 2136 907 2.78 2445 956 3.15 2751 997 3.49 3017 3750 755 1.89 1674 811 2.20 1945 862 2.49 2197 914 2.85 2504 963 3.23 2815 — — — 3800 763 1.95 1726 819 2.27 2006 869 2.56 2257 920 2.92 2562 970 3.31 2878 — — — 3900 780 2.09 1849 835 2.42 2136 884 2.72 2394 933 3.07 2686 983 3.48 3009 — — — 4000 796 2.23 1971 851 2.56 2257 900 2.89 2537 946 3.23 2815 — 4100 813 2.39 2110 867 2.74 2411 915 3.06 2678 960 3.40 2948 — 4200 830 2.55 2249 883 2.91 2554 931 3.24 2823 — 4250 839 2.63 2317 892 3.00 2629 939 3.34 2902 —

STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 908 2.24 1980 953 2.53 2232 1003 2.87 2521 1045 3.28 2854 2600 913 2.29 2023 957 2.58 2275 1004 2.91 2554 1050 3.31 2878 2700 924 2.40 2120 967 2.70 2377 1010 3.01 2637 1056 3.37 2925 2800 935 2.52 2223 978 2.62 2479 1019 3.13 2735 1061 3.41 3002 2900 946 2.65 2335 989 2.96 2595 1030 3.27 2847 — — — 3000 957 2.78 2445 1000 3.09 2702 1040 3.41 2956 — — — 3100 968 2.91 2554 1011 3.24 2832 — 3200 980 3.04 2661 1022 3.38 2933 — 3300 991 3.18 2775 — 3400 1003 3.52 2886 — 3500 1014 3.48 3009 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —

confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 6. Standard motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied drive is required. (See Note 6.)
2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 24 of the Bryant 548D user manual — NOTES:
Page 24 · click to enlarge
Page 24

Table 10 — Fan Performance 548D120 — Vertical Discharge Units

548D120 (10 TONS) — STANDARD AND ALTERNATE MOTORS (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 532 0.64 630 605 0.81 763 670 0.97 891 725 1.12 1014 778 1.28 1148 825 1.43 1275 3100 544 0.70 677 616 0.86 803 680 1.03 940 735 1.20 1081 787 1.36 1216 835 1.52 1353 3200 557 0.75 716 628 0.93 859 690 1.10 998 746 1.28 1148 796 1.44 1284 844 1.61 1430 3300 570 0.81 763 639 0.99 907 700 1.18 1064 757 1.36 1216 805 1.52 1353 854 1.70 1508 3400 583 0.88 818 651 1.06 965 711 1.25 1123 767 1.44 1284 815 1.61 1430 863 1.79 1587 3500 596 0.94 867 663 1.14 1031 721 1.33 1190 777 1.52 1353 826 1.71 1517 871 1.88 1665 3600 609 1.01 924 674 1.22 1097 732 1.42 1267 787 1.61 1430 836 1.80 1595 880 1.98 1753 3700 622 1.09 989 686 1.30 1165 744 1.50 1335 797 1.70 1508 847 1.91 1691 890 2.09 1849 3800 635 1.16 1047 698 1.39 1241 755 1.59 1413 808 1.80 1595 857 2.01 1779 901 2.20 1945 3900 649 1.25 1123 713 1.48 1318 767 1.68 1491 818 1.90 1683 867 2.11 1866 912 2.32 2050 4000 662 1.33 1190 722 1.57 1396 778 1.78 1578 829 2.01 1779 878 2.22 1962 922 2.44 2203 4100 675 1.42 1267 734 1.67 1482 790 1.89 1674 839 2.12 1875 888 2.33 2058 933 2.56 2309 4200 689 1.52 1353 746 1.77 1569 801 1.99 1761 851 2.23 1971 898 2.45 2212 943 2.69 2424 4300 702 1.61 1430 759 1.88 1665 813 2.11 1866 862 2.34 2067 908 2.58 2326 953 2.81 2533 4400 715 1.72 1526 772 1.99 1761 825 2.22 1962 873 2.46 2221 919 2.71 2442 963 2.94 2651 4500 729 1.83 1621 785 2.10 1858 837 2.35 2076 885 2.59 2335 929 2.85 2569 973 3.08 2782 4600 742 1.94 1718 797 2.22 1962 848 2.48 2238 896 2.72 2451 940 2.98 2688 984 3.22 2914 4700 756 2.06 1823 810 2.34 2067 860 2.61 2353 908 2.86 2578 951 3.12 2727 994 3.38 3068 4800 770 2.18 1927 823 2.46 2221 872 2.75 2505 919 3.00 2707 963 3.27 2847 1003 3.43 3202 4900 783 2.31 2041 836 2.60 2344 884 2.89 2605 931 3.14 2838 974 3.41 2956 1013 3.59 3349 5000 797 2.44 2203 849 2.73 2460 897 3.04 2661 943 3.30 2870 984 3.44 3211 1023 3.75 3501

548D120 (10 TONS) — STANDARD AND ALTERNATE MOTORS (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 874 1.60 1422 926 1.82 1613 974 2.11 1920 1012 2.41 2134 3100 880 1.68 1491 933 1.87 1656 983 2.16 1963 1017 2.44 2177 3200 888 1.77 1569 934 1.94 1718 988 2.18 1980 1025 2.47 2230 3300 897 1.86 1648 940 2.03 1853 989 2.24 2031 1032 2.53 2282 3400 907 1.97 1744 947 2.14 1946 991 2.32 2099 1038 2.57 2318 3500 916 2.07 1831 956 2.25 2039 997 2.43 2195 1043 2.64 2380 3600 926 2.18 1927 966 2.41 2134 1004 2.54 2291 1045 2.74 2478 3700 934 2.28 2015 976 2.48 2238 1013 2.66 2397 1051 2.85 2569 3800 943 2.41 2160 985 2.60 2334 1023 2.79 2514 1059 2.98 2688 3900 952 2.51 2265 994 2.72 2451 1032 2.92 2633 1068 3.12 2819 4000 962 2.63 2371 1003 2.84 2560 1042 3.06 2763 1078 3.26 2952 4100 973 2.77 2496 1011 2.97 2679 1051 3.20 2895 1087 3.41 3097 4200 983 2.91 2624 1021 3.11 2810 1060 3.34 3029 1090 3.51 3276 4300 994 3.05 2754 1031 3.25 2943 1068 3.48 3166 1097 3.70 3453 4400 1004 3.19 2885 1042 3.41 3097 1080 3.63 3388 1105 3.91 3642 4500 1015 3.33 2020 1051 3.45 3218 1090 3.75 3493 1112 4.12 3843 4600 1025 3.48 3166 1060 3.61 3369 1100 3.92 3655 1119 4.35 4057 4700 1037 3.58 3335 1070 3.84 3325 1111 4.10 3822 1126 4.59 4284 4800 1048 3.75 3494 1080 3.95 3686 1121 4.28 3995 1133 4.85 4523 4900 1060 3.92 3659 1089 4.13 3854 1132 4.48 4174 1140 5.12 4775 5000 1072 4.11 3830 1099 4.32 4027 1144 4.67 4359 1147 5.40 5040

standard motor and 2.90 with alternate motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 5. Values include losses for filters, unit casing, and wet coils. 6. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 7. Standard motor drive range: 685 to 935 rpm. Alternate motor drive range: 835 to 1085 rpm. All other rpms require field-supplied drive. 8. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied or alternate (as appropriate) drive is required. (See Note 7.)
2. indicates alternate motor and drive are required.
3. indicates field-supplied motor and drive are required. 4. Maximum usable watts input is 2120 with standard motor and 2615 with alternate motor. Maximum continuous bhp is 2.40 with
Show 4 more labels / short text on this page
Airflow · (Cfm · Airflow · (Cfm)
Page 25 of the Bryant 548D user manual — NOTES:
Page 25 · click to enlarge
Page 25

Table 11 — Fan Performance 548D090 — Horizontal Discharge Units

STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 465 0.43 473 554 0.64 630 630 0.86 803 695 1.09 989 757 1.34 1199 2300 471 0.45 487 559 0.66 646 635 0.89 827 699 1.12 1014 760 1.37 1224 2400 482 0.50 524 569 0.71 684 645 0.95 875 708 1.18 1064 768 1.44 1284 2500 494 0.54 554 581 0.76 723 654 1.01 924 717 1.25 1123 776 1.51 1344 2550 501 0.57 577 587 0.79 747 659 1.05 956 722 1.29 1156 780 1.55 1378 2660 507 0.59 592 592 0.82 771 663 1.08 981 727 1.32 1182 784 1.58 1404 2700 520 0.65 638 604 0.89 827 672 1.14 1031 737 1.40 1250 793 1.66 1473 2800 533 0.71 684 615 0.95 875 683 1.20 1081 747 1.49 1327 802 1.75 1552 2900 546 0.77 731 626 1.02 932 693 1.27 1140 756 1.57 1396 813 1.84 1630 3000 559 0.83 779 637 1.09 989 704 1.35 1207 765 1.66 1473 823 1.94 1718 3100 572 0.90 835 648 1.17 1056 715 1.43 1275 775 1.74 1543 832 2.05 1814 3200 585 0.96 883 660 1.24 1114 727 1.52 1353 785 1.83 1321 841 2.15 1901 3300 598 1.03 940 671 1.32 1182 739 1.62 1439 795 1.91 1691 851 2.26 1997 3400 610 1.10 998 682 1.41 1258 750 1.72 1526 806 2.01 1779 860 2.36 2084 3500 623 1.17 1056 694 1.50 1335 761 1.82 1613 817 2.11 1866 870 2.47 2180 3600 636 1.25 1123 707 1.60 1422 772 1.93 1709 828 2.23 1971 880 2.57 2266 3700 649 1.33 1190 720 1.71 1517 783 2.03 1796 840 2.35 2076 890 2.69 2369 3750 655 1.37 1224 727 1.77 1569 789 2.09 1849 846 2.42 2136 896 2.75 2420

STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 810 1.62 1439 850 1.91 1691 873 2.20 1945 883 2.50 2206 895 2.78 2445 2300 816 1.65 1465 859 1.94 1718 888 2.24 1980 903 2.55 2249 911 2.85 2504 2400 824 1.72 1526 872 2.01 1779 909 2.32 2050 931 2.64 2326 935 2.96 2595 2500 832 1.79 1587 882 2.09 1849 925 2.40 2119 955 2.72 2394 972 3.06 2678 2550 836 1.83 1621 887 2.13 1884 931 2.45 2162 964 2.77 2436 986 3.11 2718 2660 839 1.87 1656 891 2.17 1919 936 2.49 2197 973 2.82 2479 999 3.16 2759 2700 846 1.95 1726 898 2.26 1997 946 2.58 2275 987 2.91 2554 1019 3.26 2839 2800 855 2.04 1805 906 2.35 2076 954 2.67 2352 997 3.01 2637 1034 3.36 2917 2900 863 2.13 1884 913 2.44 2154 961 2.77 2436 1006 3.12 2727 — — — 3000 872 2.22 1962 921 2.54 2240 969 2.88 2529 1014 3.22 2807 — — — 3100 882 2.33 2058 930 2.65 2335 976 2.99 2620 1021 3.34 2902 — — — 3200 892 2.45 2162 939 2.76 2428 984 3.10 2710 — 3300 902 2.57 2266 948 2.88 2529 993 3.21 2799 — 3400 912 2.69 2369 958 3.01 2637 1002 3.34 2902 — 3500 921 2.82 2479 968 3.15 2751 — 3600 930 2.95 2587 978 3.29 2862 — 3700 940 3.07 2686 — 3750 945 3.14 2743 —

ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 5. Values include losses for filters, unit casing, and wet coils. 6. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 7. Standard motor drive range: 590 to 840 rpm. Alternate motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. 8. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied drive is required. (See Note 7.)
2. indicates alternate drive is required.
3. indicates field-supplied motor and drive are required. 4. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 26 of the Bryant 548D user manual — NOTES:
Page 26 · click to enlarge
Page 26

Table 12 — Fan Performance 548D102 — Horizontal Discharge Units

STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 501 0.57 577 587 0.79 747 659 1.05 956 722 1.29 1156 780 1.55 1378 2660 507 0.59 592 592 0.82 771 663 1.08 981 727 1.32 1182 784 1.58 1404 2700 520 0.65 638 604 0.89 827 672 1.14 1031 737 1.40 1250 793 1.66 1473 2800 533 0.71 684 615 0.95 875 683 1.20 1081 747 1.49 1327 802 1.75 1552 2900 546 0.77 731 626 1.02 932 693 1.27 1140 756 1.57 1396 813 1.84 1630 3000 559 0.83 779 637 1.09 989 704 1.35 1207 765 1.66 1473 823 1.94 1718 3100 572 0.90 835 648 1.17 1056 715 1.43 1275 775 1.74 1543 832 2.05 1814 3200 585 0.96 883 660 1.24 1114 727 1.52 1353 785 1.83 1321 841 2.15 1901 3300 598 1.03 940 671 1.32 1182 739 1.62 1439 795 1.91 1691 851 2.26 1997 3400 610 1.10 998 682 1.41 1258 750 1.72 1526 806 2.01 1779 860 2.36 2084 3500 623 1.17 1056 694 1.50 1335 761 1.82 1613 817 2.11 1866 870 2.47 2180 3600 636 1.25 1123 707 1.60 1422 772 1.93 1709 828 2.23 1971 880 2.57 2266 3700 649 1.33 1190 720 1.71 1517 783 2.03 1796 840 2.35 2076 890 2.69 2369 3750 655 1.37 1224 727 1.77 1569 789 2.09 1849 846 2.42 2136 896 2.75 2420 3800 661 1.41 1258 733 1.82 1613 795 2.15 1901 852 2.48 2188 901 2.80 2462 3900 674 1.49 1327 746 1.93 1709 806 2.26 1997 863 2.61 2300 912 2.93 2571 4000 687 1.57 1396 759 2.05 1814 817 2.38 2102 874 2.75 2420 923 3.08 2694 4100 699 1.60 1473 772 2.17 1919 828 2.50 2206 885 2.88 2529 935 3.23 2815 4200 712 1.75 1552 785 2.30 2032 840 2.64 2326 897 3.03 2653 947 3.39 2940 4250 719 1.80 1595 792 2.37 2093 846 2.71 2386 903 3.10 2710 — — —

STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 836 1.83 1621 887 2.13 1884 931 2.45 2162 964 2.77 2436 986 3.11 2718 2660 839 1.87 1656 891 2.17 1919 936 2.49 2197 973 2.82 2479 999 3.16 2759 2700 846 1.95 1726 898 2.26 1997 946 2.58 2275 987 2.91 2554 1019 3.26 2839 2800 855 2.04 1805 906 2.35 2076 954 2.67 2352 997 3.01 2637 1034 3.36 2917 2900 863 2.13 1884 913 2.44 2154 961 2.77 2436 1006 3.12 2727 — — — 3000 872 2.22 1962 921 2.54 2240 969 2.88 2529 1014 3.22 2807 — — — 3100 882 2.33 2058 930 2.65 2335 976 2.99 2620 1021 3.34 2902 — — — 3200 892 2.45 2162 939 2.76 2428 984 3.10 2710 — 3300 902 2.57 2266 948 2.88 2529 993 3.21 2799 — 3400 912 2.69 2369 958 3.01 2637 1002 3.34 2902 — 3500 921 2.82 2479 968 3.15 2751 — 3600 930 2.95 2587 978 3.29 2862 — 3700 940 3.07 2686 — 3750 945 3.14 2743 — 3800 949 3.20 2781 — 3900 959 3.33 2894 — 4000 — 4100 — 4200 — 4250 —

confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 6. Standard motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied drive is required. (See Note 6.)
2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 27 of the Bryant 548D user manual — NOTES:
Page 27 · click to enlarge
Page 27

Table 13 — Fan Performance 548D120 — Horizontal Discharge Units

STANDARD AND ALTERNATE MOTORS (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 484 0.55 562 560 0.70 677 631 0.87 810 690 1.03 940 747 1.20 1081 3100 495 0.61 607 570 0.76 723 638 0.92 851 699 1.10 998 755 1.27 1140 3200 505 0.66 646 579 0.81 763 646 0.98 899 708 1.16 1047 761 1.34 1199 3300 516 0.72 692 589 0.87 810 655 1.05 956 717 1.23 1106 767 1.40 1250 3400 527 0.78 739 599 0.93 859 664 1.11 1006 724 1.30 1165 775 1.48 1318 3500 537 0.85 795 609 0.99 907 672 1.18 1064 731 1.36 1216 784 1.56 1387 3600 548 0.92 851 619 1.05 956 680 1.24 1114 738 1.43 1275 794 1.64 1456 3700 560 1.00 916 629 1.12 1014 688 1.31 1173 747 1.51 1344 802 1.73 1534 3800 571 1.08 981 639 1.19 1072 698 1.39 1241 756 1.60 1422 810 1.81 1604 3900 582 1.16 1047 649 1.27 1140 708 1.47 1310 764 1.69 1499 816 1.89 1674 4000 593 1.25 1123 659 1.35 1207 717 1.56 1387 773 1.78 1578 823 1.98 1753 4100 605 1.35 1207 670 1.44 1284 727 1.65 1465 781 1.86 1648 832 2.08 1840 4200 616 1.45 1292 680 1.53 1361 737 1.74 1543 789 1.95 1726 841 2.18 1927 4300 628 1.56 1387 690 1.63 1447 747 1.83 1621 798 2.05 1814 849 2.30 2032 4400 639 1.67 1482 701 1.73 1534 757 1.92 1700 807 2.16 1910 858 2.41 2177 4500 651 1.78 1578 712 1.84 1630 767 2.02 1788 817 2.27 2006 866 2.51 2265 4600 662 1.91 1691 722 1.95 1726 777 2.13 1884 827 2.38 2102 874 2.62 2362 4700 674 2.03 1796 733 2.07 1831 787 2.24 1980 836 2.50 2256 882 2.73 2460 4800 686 2.17 1919 744 2.20 1945 797 2.36 2084 846 2.62 2362 891 2.85 2569 4900 698 2.31 2041 755 2.33 2058 808 2.48 2238 856 2.73 2460 900 2.99 2698 5000 710 2.45 2212 766 2.47 2230 818 2.61 2353 866 2.86 2578 910 3.12 2819

STANDARD AND ALTERNATE MOTORS (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 800 1.38 1233 850 1.52 1353 879 1.38 1233 925 1.81 1604 964 1.92 1761 3100 805 1.44 1284 857 1.63 1447 896 1.66 1473 935 1.93 1709 975 1.98 1811 3200 812 1.51 1344 862 1.71 1517 908 1.85 1639 944 2.01 1836 984 2.09 1903 3300 819 1.59 1413 867 1.78 1578 915 1.98 1753 952 2.11 1920 993 2.22 2014 3400 827 1.67 1482 873 1.85 1639 920 2.07 1831 963 2.21 2005 1001 2.31 2091 3500 833 1.75 1552 880 1.94 1718 926 2.15 1901 970 2.41 2134 1007 2.46 2221 3600 840 1.83 1621 888 2.04 1805 931 2.23 1971 976 2.47 2230 1017 2.62 2362 3700 847 1.92 1700 895 2.13 1884 938 2.33 2108 981 2.56 2309 1024 2.77 2496 3800 856 2.02 1788 901 2.23 1971 945 2.44 2203 986 2.65 2389 1029 2.89 2605 3900 865 2.12 1875 908 2.32 2050 953 2.55 2300 993 2.75 2478 1034 3.00 2707 4000 875 2.22 1962 915 2.42 2186 960 2.65 2389 1000 2.87 2587 1039 3.10 2800 4100 883 2.32 2050 924 2.54 2291 966 2.76 2487 1008 2.99 2698 1046 3.21 2904 4200 889 2.41 2177 934 2.65 2389 972 2.87 2587 1015 3.12 2819 1053 3.34 3029 4300 896 2.51 2265 943 2.77 2406 980 2.99 2698 1021 3.23 2923 1061 3.48 3166 4400 903 2.62 2362 951 2.89 2603 990 3.12 2819 1028 3.36 3049 1068 3.61 3241 4500 912 2.74 2469 958 3.00 2707 999 3.26 2982 1035 3.51 3161 1074 3.74 3346 4600 921 2.87 2587 965 3.11 2810 1008 3.39 3078 1041 3.68 3295 1081 3.90 3450 4700 930 3.00 2707 972 3.23 2923 1017 3.45 3224 1048 3.80 3436 1088 4.13 3552 4800 938 3.14 2838 980 3.37 3058 1025 3.55 3362 1055 3.85 3584 1095 4.30 3653 4900 946 3.27 2962 990 3.51 3149 1034 3.71 3505 1062 3.98 3741 1101 4.45 3753 5000 954 3.39 3078 998 3.62 3271 1042 3.85 3654 1068 4.08 3907 1108 4.59 3851

standard motor and 2.90 with alternate motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 5. Values include losses for filters, unit casing, and wet coils. 6. Use of a field-supplied motor may affect wire sizing. Contact your representative to verify. 7. Standard motor drive range: 685 to 935 rpm. Alternate motor drive range: 835 to 1085 rpm. All other rpms require field-supplied drive. 8. Interpolation is permissible. Do not extrapolate.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

NOTES:

1. Boldface indicates field-supplied or alternate (as appropriate) drive is required. (See Note 7.)
2. indicates alternate motor and drive are required.
3. indicates field-supplied motor and drive are required. 4. Maximum usable watts input is 2120 with standard motor and 2615 with alternate motor. Maximum continuous bhp is 2.40 with
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 28 of the Bryant 548D user manual — VII. HIGH FLOW VALVES
Page 28 · click to enlarge
Page 28

PRE-START-UP

b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled

with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed. e. Ensure belt and blower pulley are properly aligned and at correct tension.

1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.

START-UP

I. UNIT PREPARATION

3. Do not remove compressor terminal cover until all electrical sources are disconnected and tagged. 4. Relieve all pressure from system before touching or disturbing anything inside compressor terminal box if refrigerant leak is suspected around compressor terminals. Use accepted methods to recover refrigerant.

Make sure that unit has been installed in accordance with these installation instructions and applicable codes.

II. RETURN AIR FILTERS Make sure correct filters are installed in unit (see Table 1). Do not operate unit without return-air filters.

III. OUTDOOR-AIR INLET SCREEN

Outdoor-air inlet screen must be in place before operating unit.

5. Never attempt to repair soldered connection while refrigerant system is under pressure.

IV. COMPRESSOR MOUNTING Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.

6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:

V. INTERNAL WIRING

a. Shut off electrical power to unit and install lockout tag. b. Relieve all pressure from system using both high- and low-pressure ports. Use accepted methods to recover refrigerant. c. Cut component connection tubing with tub- ing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.

Check all electrical connections in unit control boxes; tighten as required. Ensure wiring does not come into direct contact with refrigerant tubing or sharp edges.

VI. REFRIGERANT SERVICE PORTS

Each refrigerant system has 4 Schrader-type service gage ports: One on the suction line, one on the cooling mode liquid line, and 2 on the compressor discharge line. Be sure that caps on the ports are tight.

VII. HIGH FLOW VALVES

Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.

Proceed as follows to inspect and prepare the unit for initial start-up:

1. Remove all access panels.

2. Read and follow instructions on all WARNING, CAU- TION, and INFORMATION labels attached to or shipped with unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires. b. Inspect for oil at all refrigerant tubing connec- tions and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrig- erant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. c. Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight. Ensure electrical wiring does not come into contact with refrigerant tubing or sharp edges. d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 4. Verify the following conditions: a. Make sure that outdoor-fan blades are correctly positioned in fan orifice. Refer to Outdoor Fan Adjustment section on page 32 for more details.

VIII. COMPRESSOR ROTATION It is important to be certain the scroll compressor is rotating in the proper direction. To determine whether or not com- pressor is rotating in the proper direction:

1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the indoor fan is probably also rotating in the wrong direction. 2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads. 4. Turn on power to the unit. Reenergize compressor.

The suction and discharge pressure levels should now move to their normal start-up levels.

Page 29 of the Bryant 548D user manual — XIV. OPERATING SEQUENCE
Page 29 · click to enlarge
Page 29

compressor contactor no. 1 (C1) are energized and the indoor-fan motor, compressor no. 1, outdoor-fan motors and outdoor fans start. The outdoor-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) and RVS2 are energized and compressor no. 2 starts.

IX. ADJUST GAS INPUT

The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Manifold pressure should be 3.5 in. wg.

B. Heating, Units Without Economizer Upon a call for heating through terminal W1, IFC, OFC, C1, and C2 are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC is energized through W2.

X. COOLING

To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO position. Adjust thermostat to a setting below room temperature. Compressor indoor and outdoor fans start on closure of contactors. Check unit charge. Refer to Refrigerant Charge section on page 32. Unit must operate for at least 15 minutes before adjusting charge.

C. Cooling, Units With Durablade Economizer When the outdoor-air temperature is above the OAT setting and the room thermostat calls for cooling, the compressor contactor no. 1 and outdoor fan contactor (OFC) are ener- gized to start compressor no. 1 and outdoor-fan motors. RVS1 (reversing valve solenoid) is energized). The indoor-fan motor (IFM) is energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor contactor no. 2 will be energized, starting com- pressor no. 2. RVS2 is energized. After the thermostat is sat- isfied and the IFM is deenergized, the damper moves to the fully closed position.

Reset thermostat at a position above room temperature. Compressor and outdoor fans will shut off.

To Shut Off Unit Set system selector switch at OFF position. Resetting ther- mostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then ON position.

When the outdoor-air temperature is below the OAT setting and the thermostat calls for Y1 and G, the economizer damper moves to the minimum position when the indoor fan starts. The first stage of cooling is provided by the econo- mizer. If the supply-air temperature is above 57 F, a switch on the supply-air thermostat is closed between the T2 ter- minal and the 24 vac terminal. This causes the damper to continue to modulate open until the supply-air temperature falls below 55 F or the damper reaches the fully open position.

XI. HEATING To start unit, turn on main power supply.

Set thermostat at HEAT position and a setting above room temperature, fan at AUTO position.

First stage of thermostat energizes the indoor fan motor, compressor, and outdoor fan; second stage energizes electric heater elements if installed. Check heating effects at air sup- ply grille(s).

When the supply-air temperature is between 55 F and 52 F, the supply-air thermostat has open switches between the T2 and 24 vac terminals and between the T1 and 24 vac termi- nals. This causes the economizer damper to remain in an intermediate open position. If the supply-air temperature falls below 52 F, a switch on the supply-air thermostat is closed between the T1 terminal and the 24 vac terminal. This causes the damper to modu- late closed until the supply-air temperature rises above 55 F or the damper reaches the minimum position.

If accessory electric heaters do not energize, reset limit switch (located on indoor-fan scroll) by depressing button located between terminals on the switch.

To Shut Unit Off Set system selector switch at OFF position. Resetting heat- ing selector lever below room temperature temporarily shuts unit off until space temperature falls below thermostat setting.

When the supply-air temperature is between 55 F and 57 F, the supply-air thermostat has open switches between the T2 and 24 vac terminals. This causes the economizer damper to remain in an intermediate open position.

XII. SAFETY RELIEF

A soft solder joint in the suction line at the loss-of-charge/ low-pressure switch fitting provides pressure relief under abnormal temperature and pressure conditions.

If the outdoor air alone cannot satisfy the cooling require- ments of the conditioned space, economizer cooling is in- tegrated with mechanical cooling, providing second stage cooling. Compressor no. 1 and outdoor fans will be ener- gized, and the position of the economizer damper will be determined by the supply-air temperature. Compressor no. 2 is locked out. When the second stage of cooling is satisfied, the compressor, RVS2, and outdoor fan motors will be deenergized. The damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied, the damper will move to fully closed position.

XIII. VENTILATION (CONTINUOUS FAN)

Set fan and system selector switches at ON and OFF posi- tions, respectively. Indoor fan operates continuously to pro- vide constant air circulation.

XIV. OPERATING SEQUENCE

A. Cooling, Units Without Economizer When the thermostat calls for cooling, terminals G and Y1 are energized. The indoor fan contactor (IFC), outdoor fan contactor (OFC), RVS1 (reversing valve solenoid), and

Page 30 of the Bryant 548D user manual — A. Indoor Coil
Page 30 · click to enlarge
Page 30

D. Cooling, Units With EconoMi$er When the Outdoor Air Temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan motor (IFM) is energized and the EconoMi$er damper modulates to mini- mum position. The compressor contactor and OFC are ener- gized starting the compressor and outdoor-fan motor (OFM). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized. When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cool- ing by modulating the return and outdoor-air dampers to maintain a 55 F supply air set point. If the supply-air tem- perature (SAT) is greater than 57 F, the EconoMi$er modu- lates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor-air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position. If outdoor air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.

energized through W2. The indoor-fan motor is energized, and the economizer damper moves to the minimum position. If the two-position damper is used, the outdoor-air damper opens to the minimum position whenever the indoor fan opens. When the thermostat is satisfied, the damper moves to the fully closed position.

F. Defrost When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fans. The electric heaters (if installed) will be energized.

The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F, or the duration of defrost cycle completes a 10-minute period. During the defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between heating and cooling modes until the defrost mode is complete.

At the end of the defrost cycle, the electric heaters (if in- stalled) will be deenergized; the reversing valves switch and the outdoor-fan motors will be energized. The unit will now operate in the heating mode.

If the space thermostat is satisfied during a defrost cycle, the unit will continue in the defrost mode until the time or tem- perature constraints are satisfied.

1. If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), the compressor number 1 and OFM are energized. The position of the EconoMi$er damper is maintained at its current value.

SERVICE

2. If Y1 is energized for more then 20 minutes, and Y2 is not energized (whether or not a 2-stage thermostat is used), compressor no. 1 and OFM are energized. The position of the EconoMi$er damper is maintained at its current value. 3. If Y1 is energized, and compressor no. 1 is already energized and the room thermostat calls for Y2, compressor no. 1 continues to operate. If Y2 remains energized for more than 20 minutes, compressor no. 2 is energized.

I. CLEANING

Inspect unit interior at the beginning of each heating and cooling season or more frequently as operating conditions require.

A. Indoor Coil

1. Turn unit power off and tag disconnect. Remove filter access panel and indoor coil access panel. 2. If economizer or accessory two-position damper is installed, remove economizer/two-position damper by disconnecting economizer plug and removing mounting screws (see Fig. 14, 15, or 22). Refer to Accessory Economizer or Two-Position Damper Installation Instructions for more details. 3. Slide filters out of unit.
4. If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressor no. 1 and 2 are deenergized. Re-asserting Y2 will start compressor no. 1 and (after a 20-minute interstage delay) compressor no. 2. 5. If compressor no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, backflush toward return-air section to remove foreign material. Caution should be taken as to not overflow the evaporator drain condensate pan. 5. Flush condensate pan after completion.

When the OAT is below the MECH CLG LOCKOUT set point, the compressors remain off.

E. Heating, Units With Economizer (If Accessory Heater is Installed) When the room thermostat calls for heat through terminal W1, the indoor-fan contactor outdoor fan contactor, C1, and C2 are energized. On units equipped for 2 stages of heat, when additional heat is needed, heater contactor is

6. Reinstall economizer/two-position damper and filters. 7. Reconnect wiring.
8. Replace access panels.
Page 31 of the Bryant 548D user manual — Fig. 41 — Separating Coil Sections
Page 31 · click to enlarge
Page 31

B. Outdoor Coils Inspect coils monthly. Clean condenser coils annually, and as required by location and outdoor-air conditions. Clean 2-row coils as follows:

Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 31)
Fig. 25 · Fig. 30 — EconoMi$er Wiring
1. Turn off unit power and tag disconnect. 2. Remove top panel screws on outdoor end of unit.

3. Remove outdoor coil corner post. See Fig. 39. To hold top panel open, place coil corner post between top panel and center post. See Fig. 40. 4. Remove device holding coil sections together at return end of outdoor coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 41. 5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 6. Secure the sections together. Reposition the coil sec- tions, and remove the coil corner post from between the top panel and center post. Install the coil corner post and coil center post, and replace all screws.

Fig. 39 — Cleaning Outdoor Coil

Bryant 548D — Fig. 39 — Cleaning Outdoor Coil diagram (page 31)
Fig. 26 · Fig. 39 — Cleaning Outdoor Coil

C. Condensate Drain

Check and clean each year at start of cooling season. In win- ter, keep drain dry or protect against freeze-up.

D. Filters Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.

Fig. 40 — Propping Up Top Panel

E. Outdoor-Air Inlet Screen

Clean screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screens.

Bryant 548D — Fig. 40 — Propping Up Top Panel diagram (page 31)
Fig. 27 · Fig. 40 — Propping Up Top Panel

F. Belts Adjust belt tension and pulley alignment at least twice a year or more frequently as operating conditions require.

II. LUBRICATION

A. Compressors Each compressor is charged with correct amount of oil at the factory.

B. Fan Motor Bearings

Fan motor bearings are permanently lubricated. No further lubrication of outdoor- or indoor-fan motors is required.

Fig. 41 — Separating Coil Sections

Page 32 of the Bryant 548D user manual — Fig. 43 — Cooling Charging Chart, 548D090
Page 32 · click to enlarge
Page 32

III. OUTDOOR FAN ADJUSTMENT (Fig. 42)

c. Suction-tube temperature (F) at low-side service

1. Shut off unit power supply.

fitting. d. Suction (low-side) pressure (psig). 5. Using “Cooling Charging Charts” compare outdoor- air temperature (F db) with the suction line pressure (psig) to determine desired system operating suction line temperature. See Fig. 43-45. 6. Compare actual suction-tube temperature with desired suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if actual temperature is more than 3° F higher than proper suction-tube tem- perature, or remove refrigerant if actual temperature is more than 3° F lower than required suction-tube temperature.

2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 42. 4. Tighten setscrews and replace outdoor-fan assembly.
Bryant 548D — III. OUTDOOR FAN ADJUSTMENT (Fig. 42) diagram (page 32)
Fig. 28 · III. OUTDOOR FAN ADJUSTMENT (Fig. 42)

B. To Use Cooling Charging Charts Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted. EXAMPLE: (Fig. 43)

UNIT VOLTAGE

‘‘A’’

in. 208/230 V 2.75 460 V and 575 V 3.50

Fig. 42 — Outdoor Fan Adjustment

IV. ECONOMIZER ADJUSTMENT

Refer to Optional Economizer sections on pages 11 and 15. IMPORTANT: Refer to Troubleshooting Tables 14-16 for addi- tional information.

Outdoor Temperature 85 F Suction Pressure 70 psig Suction Temperature should be 49 F (Suction Temperature may vary ±5° F.)

V. REFRIGERANT CHARGE

C. Heating Mode Charge Do not attempt to adjust charge by cooling methods while in Heating mode. When charging is necessary in Heating mode, recover refrigerant and weigh in according to unit data plate refrigerant data.

A. Checking and Adjustment Refrigerant Charge The refrigerant system is fully charged with R-22 refriger- ant, tested, and factory-sealed. Unit must operate in cooling mode a minimum of 10 minutes before checking charge.

NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge. A superheat charging chart is attached to the outside of the service access panel. The chart includes the required suction line temperature at given suction line pressures and outdoor ambient temperatures. An accurate superheat, thermocouple- or thermistor-type thermometer and a gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.

Bryant 548D — V. REFRIGERANT CHARGE diagram (page 32)
Fig. 29

Proceed as follows:

1. Remove caps from lowand high-pressure service fittings.
2. Using hoses with valve core depressors, attach lowand high-pressure gage hoses to lowand highpressure service fittings, respectively. 3. Start unit in Cooling mode and let unit run until system pressures stabilize. 4. Measure and record the following: a. Outdoor ambient-air temperature (F db). b. Evaporator inlet-air temperature (F wb).

Fig. 43 — Cooling Charging Chart, 548D090

Page 33 of the Bryant 548D user manual — Fig. 45 — Cooling Charging Chart; 548D120
Page 33 · click to enlarge
Page 33

Fig. 44 — Cooling Charging Chart; 548D102

Bryant 548D — Fig. 44 — Cooling Charging Chart; 548D102 diagram (page 33)
Fig. 30 · Fig. 44 — Cooling Charging Chart; 548D102

Fig. 45 — Cooling Charging Chart; 548D120

Page 34 of the Bryant 548D user manual — Table 14 — Heating and Cooling Troubleshooting
Page 34 · click to enlarge
Page 34

TROUBLESHOOTING

Refer to Tables 14-16 and Fig. 46 for troubleshooting information.

Table 14 — Heating and Cooling Troubleshooting

PROBLEM CAUSE REMEDY Compressor and outdoor fan will not start.

Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control relay. Replace component. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. High-pressure switch tripped. See problem ‘‘Excessive head pressure.’’ Low-pressure switch tripped. Check for leaks, repair, and recharge. Freeze-up protection thermostat tripped. See problem ‘‘Suction pressure too low.’’ Compressor will not start but outdoor fan runs.

Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace. Compressor motor burned out, seized, or internal overload open.

Determine cause. Replace compressor.

Defective overload. Determine cause and replace. One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Compressor cycles (other than normally satisfying thermostat).

Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge to nameplate. Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked outdoor coil or dirty air filter. Determine cause and correct. Defective overload. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or capacitor.

Replace.

Restriction in refrigerant system. Locate restriction and remove. Compressor operates continuously.

Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Outdoor coil dirty or restricted. Clean coil or remove restriction. Scroll compressor makes excessive noise.

Compressor rotating in the wrong direction. Reverse the 3-phase power leads as described in Start-Up, page 28. Excessive head pressure

Dirty air filter. Replace filter. Dirty outdoor coil. Clean coil. Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condensing air restricted or air short-cycling. Determine cause and correct. Head pressure too low.

Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction. Excessive suction pressure.

High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Suction pressure too low.

Dirty air filter (cooling) or dirty outdoor coil (heating). Replace filter or clean coil. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted Remove source of restriction. Insufficient indoor airflow (cooling mode). Increase air quantity. Check filter and replace if necessary. Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace. Outdoor ambient temperature below 25 F. Install low-ambient kit. Compressor no. 2 will not run.

Unit in economizer mode. Proper operation; no remedy necessary.

Page 35 of the Bryant 548D user manual — Table 15 — Durablade Economizer Troubleshooting
Page 35 · click to enlarge
Page 35

Table 15 — Durablade Economizer Troubleshooting

PROBLEM CAUSE REMEDY Damper does not open.

Indoor fan is off. 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Check proper thermostat connection to G on the connection board. No power to economizer motor.

1. Check that SW3 is properly making contact with the damper blade. Check that SW1 is in the NC (normally closed) position. 2. Check diode D18. If diode is not functioning properly, replace economizer control board. 3. Confirm that the economizer control board is grounded properly at PL6-4 (brown wire) and at brown terminal of the economizer control board (brown wire). The economizer motor must also be grounded properly at the negative motor terminal (brown wire). 4. Verify SW1 and SW3 are working and wired properly (see unit label diagram). 5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If 24 vac not present, check unit wiring (see unit label diagram). If 24 vac is found in both places, check for 24 vac at the yellow terminal of the economizer control board (yellow wire). If 24 vac power is not present, replace the economizer control board. Economizer motor failure. If the indoor fan and economizer motor are energized, verify that there is a minimum of 18 vdc at the positive motor terminal. If the motor is not operating, replace the motor. Economizer operation limited to minimum position.

OAT or EC set too high. 1. Set at correct temperature (3 F below indoor space temperature). 2. Check OAT or EC by setting above outdoor temperature or humidity level. If the OAT or EC switches do not close, replace OAT or EC. Economizer control board incorrectly wired or not functioning.

1. Perform the following tests when OAT or EC is closed. Y1 is called for, and damper is at minimum position. Confirm 24 vac on gray terminal of the economizer control board (gray wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Verify that SW1 and SW3 are wired correctly and working properly (see unit label diagram). 3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not present, check wiring (see unit wiring label diagram). 4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace economizer control board. Incorrect SAT wiring or inoperative SAT.

1. After verifying that the OAT and EC settings and the economizer control board wir- ing are correct, check to ensure that the 24 vac terminal of the SAT has 24 vac (white wire). If OAT, EC, and control board are functioning and wired properly and no 24 vac exists, check wiring (see unit label diagram). 2. If supply-air temperature is greater than 57 F, 24 vac should be found at terminal T2 on the SAT (pink wire). If 24 vac is not present, replace SAT. Damper does not close.

Incorrect economizer wiring.

1. Verify that SW2 and SW4 are wired and working properly (see unit label diagram). 2. Check diode D19. If diode is not functioning properly, replace economizer control board. Incorrect damper actuator wiring or inoperative economizer circuit board.

1. After verifying that the wiring is correct, modulate the damper to the minimum posi- tion. Remove the calls for G. 2. If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac is not present, check wiring (see unit label diagram). 3. If damper still does not move, check for 24 vac at blue terminal of economizer con- trol board (blue wire). If 24 vac is not present, replace the economizer control board. Incorrect SAT wiring or inoperative SAT.

1. After verifying that the wiring is correct and the economizer control board is func- tioning properly, place the OAT or EC switch in the closed position. Place a call for Y1 and open the damper to the fully open position. Confirm that the 24 vac terminal of the SAT has 24 vac (white wire). If 24 vac is not present, check wiring (see unit label diagram). 2. If supply-air temperature is less than 52 F, 24 vac should be found at terminal T1 on the SAT (violet wire). If 24 vac not found, replace SAT. Economizer motor failure. If economizer control board and SAT are functioning properly, verify that there is a minimum of 18 vdc at the positive motor terminal. If a minimum of 18 vdc is present and the motor is still not operating, replace the motor. Economizer damper does not close on power loss.

Insufficient battery power, inoperative economizer control board.

1. Check voltage potential across batteries. If lower than 14 vdc, replace close-onpower-loss power supply (9-v alkaline batteries). Check this emergency power supply on a regular basis or whenever the filters are changed. 2. If the close-on-power-loss and economizer control board are functioning properly, check for 14 vdc or higher at the blue terminal of the economizer control board (blue wire) when power is disconnected from unit. If 14 vdc is not present, replace the control board.

C1 — Common Power EC — Enthalpy Control IFC — Indoor Fan Contactor IFO — Indoor Fan On OAT — Outdoor-Air Thermostat PL — Plug SAT — Supply-Air Thermostat SW — Economizer Position Switch

Page 36 of the Bryant 548D user manual — Table 16 — EconoMi$er Troubleshooting
Page 36 · click to enlarge
Page 36

Table 16 — EconoMi$er Troubleshooting

PROBLEM CAUSE REMEDY Damper does not open. Indoor Fan is Off. Check to ensure that 24 vac is present at Terminal C1 (Common Power) on the IFC (Indoor Fan contactor) or that 24 vac is present at the IFO (Indoor Fan On) terminal. Check whether 24 vac is present at PL (Plug) 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). Check proper thermostat connection to G on the connection board. No power to EconoMi$er controller.

Check to ensure that 24 vac is present across Terminals 24 VAC and 24V COM on the EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram). If 24 vac is present, STATUS light should be on constantly. No power to G Terminal. If IFM is on, check to ensure 24 vac is present on G Terminal of the EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram). Controller fault. If STATUS light is flashing one flash, the EconoMi$er controller is experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller. Thermostat fault. If STATUS light is flashing two flashes, the EconoMi$er controller senses the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1. Actuator Fault. Check the wiring between the EconoMi$er controller and the actuator. Hold CONFIG button between three and ten seconds to verify the actuator’s operation. (This process takes three minutes to complete.) EconoMi$er operation limited to minimum position.

Minimum position set incorrectly.

Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting. EconoMi$er changeover set point set too high or too low.

Set at correct value. See Table 4.

Supply air temperature sensor faulty.

If STATUS light is flashing 4 flashes, the supply air temperature sensor is faulty. Check wiring or replace sensor. Outdoor air temperature sen- sor faulty.

If STATUS light is flashing 5 flashes, the outdoor-air temperature sensor is faulty. Check wiring or replace sensor. Damper position less than minimum position set point.

The supply air temperature is less than 45 F, causing the minimum position to decrease. Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct, EconoMi$er is operating correctly. Damper does not return to minimum position.

Supply air low limit strategy controlling.

If a CO2 sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to the Start-Up instructions. EconoMi$er is operating correctly. Damper does not close on power loss

CO2 ventilation strategy controlling.

Damper travel is restricted.

Check to ensure the damper is not blocked.

IFM — Indoor-Fan Motor OAT — Outdoor-Air Temperature

Page 37 of the Bryant 548D user manual — Fig. 30 — EconoMi$er Wiring
Page 37 · click to enlarge
Page 37
Bryant 548D — Fig. 30 — EconoMi$er Wiring diagram (page 37)
Fig. 31 · Fig. 30 — EconoMi$er Wiring
Page 38 of the Bryant 548D user manual — Fig. 46 — Typical Wiring Diagram (cont)
Page 38 · click to enlarge
Page 38

NOTES:

1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent. 2. Three-phase motors are protected under primary single-phasing conditions. 3. Thermostat: HH07AT172 and P272-2783 Subbase: HH93AZ176, 178 and P272-1882, 1883 4. Set Heat anticipator at .8 amp for 1st stage and .3 amp for 2nd stage. 5. Use copper conductors only. 6. Use copper, copper clad aluminum or aluminum conductors. 7.

CB

VOLTAGE

Mfg. Pt. No.

MUST

TRIP AMPS

RATING

Potter & Brumfield 24 V W28X-1024-3.2 3.2

AHA — Adjustable Heat Anticipator AWG — American Wire Gage C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Capacitor CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor D — Diode DB — Defrost Board DFT — Defrost Thermostat EC — Enthalpy Control ECON — Economizer EPS — Emergency Power Supply

R — Relay RVS — Reversing Valve Solenoid SAT — Supply Air Thermostat SW1 — Switch Fully Open SW2 — Switch Fully Closed SW3 — Switch Minimum Vent Position SW4 — Switch Maximum Vent Position TB — Terminal Block TC — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer

(nine volt battery) EQUIP — Equipment ER — Economizer Relay FPT — Freeze-Up Protection Thermostat FU — Fuse GND — Ground HC — Heater Contactor (Strip Heat) HPS — High-Pressure Switch HR — Heater Relay IFC — Indoor Fan Contactor IFM — Indoor Fan Motor IFMOVL — Indoor Fan Motor Overload Switch LPS — Low-Pressure Switch LSM — Limit Switch (Manual Reset) MCA — Minimum Circuit Amps MTR — Motor OAT — Outdoor Air Thermostat OFC — Outdoor Fan Contactor OFM — Outdoor Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal

Accessory or Optional Wiring

To indicate common potential only, not to represent wiring.

Fig. 46 — Typical Wiring Diagram (cont)

Copyright 2000 Bryant Heating & Cooling Systems CATALOG NO. 5354-805

Show 10 more labels / short text on this page
Field Splice · Marked Wire · Terminal (Marked) · Terminal (Unmarked) · Terminal Block · Splice · Spliced (Marked) · Factory Wiring · Field Control Wiring · Field Power Wiring
Page 39 of the Bryant 548D user manual — Fig. 30 — EconoMi$er Wiring
Page 39 · click to enlarge
Page 39
Page 39 of the Bryant 548D user manual — Fig. 30 — EconoMi$er Wiring
Page 40 of the Bryant 548D user manual — COOLING SUPPLY AIR DB WB
Page 40 · click to enlarge
Page 40

START-UP CHECKLIST (Remove and Store in Job File)

I. PRELIMINARY INFORMATION

MODEL NO.:_______________________________________

SERIAL NO. ___________________________________________

DATE: _____________________________________________

TECHNICIAN: _________________________________________

UNIT NO.: _________________________________________

JOB LOCATION: _______________________________________

JOB NAME:____________________________________________

II. PRE-START-UP (insert checkmark in box as each item is completed)

VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS

CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS

CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE

CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE

VERIFY THAT UNIT INSTALLATION IS LEVEL

CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS

CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS

ENSURE BELT TENSION AND BLOWER PULLEYS ARE PROPERLY ALIGNED

III. START-UP

ELECTRICAL

SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1

CIRCUIT NO. 1 COMPRESSOR AMPS L1 L2 L3

CIRCUIT NO. 2 COMPRESSOR AMPS L1 L2 L3

INDOOR FAN AMPS L1 L2 L3

TEMPERATURES

OUTDOOR-AIR TEMPERATURE DB (dry bulb)

RETURN-AIR TEMPERATURE DB WB (wet bulb)

COOLING SUPPLY AIR DB WB

PRESSURES (Cooling Mode)

REFRIGERANT SUCTION, CIRCUIT 1 PSIG ° F

REFRIGERANT SUCTION, CIRCUIT 2 PSIG ° F

REFRIGERANT DISCHARGE, CIRCUIT 1 PSIG ° F

REFRIGERANT DISCHARGE, CIRCUIT 2 PSIG ° F

VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION.

VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 32 AND 33.

Copyright 2000 Bryant Heating & Cooling Systems CL-1 CATALOG NO. 5354-805

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Compressor and outdoor fan will not start.Power failure.Call power company. p.34
Compressor and outdoor fan will not start.Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker. p.34
Compressor and outdoor fan will not start.Defective thermostat, contactor, transformer, or control relay.Replace component. p.34
Compressor and outdoor fan will not start.Insufficient line voltage.Determine cause and correct. p.34
Compressor and outdoor fan will not start.Incorrect or faulty wiring.Check wiring diagram and rewire correctly. p.34
Compressor and outdoor fan will not start.Thermostat setting too high.Lower thermostat setting below room temperature. p.34
Compressor and outdoor fan will not start.High-pressure switch tripped.See problem ‘‘Excessive head pressure.’’ p.34
Compressor and outdoor fan will not start.Low-pressure switch tripped.Check for leaks, repair, and recharge. p.34
Compressor and outdoor fan will not start.Freeze-up protection thermostat tripped.See problem ‘‘Suction pressure too low.’’ p.34
Compressor will not start but outdoor fan runs.Faulty wiring or loose connections in compressor circuit.Check wiring and repair or replace. p.34
Compressor will not start but outdoor fan runs.Compressor motor burned out, seized, or internal overload open.Determine cause. Replace compressor. p.34
Compressor will not start but outdoor fan runs.Defective overload.Determine cause and replace. p.34
Compressor will not start but outdoor fan runs.One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine cause. p.34
Compressor cycles (other than normally satisfying thermostat).Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and recharge to nameplate. p.34
Compressor cycles (other than normally satisfying thermostat).Defective compressor.Replace and determine cause. p.34
Compressor cycles (other than normally satisfying thermostat).Insufficient line voltage.Determine cause and correct. p.34
Compressor cycles (other than normally satisfying thermostat).Blocked outdoor coil or dirty air filter.Determine cause and correct. p.34
Compressor cycles (other than normally satisfying thermostat).Defective overload.Determine cause and replace. p.34
Compressor cycles (other than normally satisfying thermostat).Defective thermostat.Replace thermostat. p.34
Compressor cycles (other than normally satisfying thermostat).Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or capacitor.Replace. p.34
Compressor cycles (other than normally satisfying thermostat).Restriction in refrigerant system.Locate restriction and remove. p.34
Compressor operates continuously.Dirty air filter.Replace filter. p.34
Compressor operates continuously.Unit undersized for load.Decrease load or increase unit size. p.34
Compressor operates continuously.Thermostat set too low.Reset thermostat. p.34
Compressor operates continuously.Low refrigerant charge.Locate leak, repair, and recharge. p.34
Compressor operates continuously.Leaking valves in compressor.Replace compressor. p.34
Compressor operates continuously.Air in system.Recover refrigerant, evacuate system, and recharge. p.34
Compressor operates continuously.Outdoor coil dirty or restricted.Clean coil or remove restriction. p.34
Scroll compressor makes excessive noise.Compressor rotating in the wrong direction.Reverse the 3-phase power leads as described in Start-Up, page 28. p.34
Excessive head pressureDirty air filter.Replace filter. p.34
Excessive head pressureDirty outdoor coil.Clean coil. p.34
Excessive head pressureRefrigerant overcharged.Remove excess refrigerant. p.34
Excessive head pressureAir in system.Recover refrigerant, evacuate system, and recharge. p.34
Excessive head pressureCondensing air restricted or air short-cycling.Determine cause and correct. p.34
Head pressure too low.Low refrigerant charge.Check for leaks, repair, and recharge. p.34
Head pressure too low.Compressor valves leaking.Replace compressor. p.34
Head pressure too low.Restriction in liquid tube.Remove restriction. p.34
Excessive suction pressure.High heat load.Check for source and eliminate. p.34
Excessive suction pressure.Compressor valves leaking.Replace compressor. p.34
Excessive suction pressure.Refrigerant overcharged.Recover excess refrigerant. p.34
Suction pressure too low.Dirty air filter (cooling) or dirty outdoor coil (heating).Replace filter or clean coil. p.34
Suction pressure too low.Low refrigerant charge.Check for leaks, repair, and recharge. p.34
Suction pressure too low.Metering device or low side restrictedRemove source of restriction. p.34
Suction pressure too low.Insufficient indoor airflow (cooling mode).Increase air quantity. Check filter and replace if necessary. p.34
Suction pressure too low.Temperature too low in conditioned area.Reset thermostat. p.34
Suction pressure too low.Field-installed filter drier restricted.Replace. p.34
Suction pressure too low.Outdoor ambient temperature below 25 F.Install low-ambient kit. p.34
Compressor no. 2 will not run.Unit in economizer mode.Proper operation; no remedy necessary. p.34
Damper does not open.Indoor fan is off.1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Check proper thermostat connection to G on the connection board. p.35
Damper does not open.No power to economizer motor.1. Check that SW3 is properly making contact with the damper blade. Check that SW1 is in the NC (normally closed) position. 2. Check diode D18. If diode is not functioning properly, replace economizer control board. 3. Confirm that the economizer control board is grounded properly at PL6-4 (brown wire) and at brown terminal of the economizer control board (brown wire). The economizer motor must also be grounded properly at the negative motor terminal (brown wire). 4. Verify SW1 and SW3 are working and wired properly (see unit label diagram). 5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If 24 vac not present, check unit wiring (see unit label diagram). If 24 vac is found in both places, check for 24 vac at the yellow terminal of the economizer control board (yellow wire). If 24 vac power is not present, replace the economizer control board. p.35
Damper does not open.Economizer motor failure.If the indoor fan and economizer motor are energized, verify that there is a minimum of 18 vdc at the positive motor terminal. If the motor is not operating, replace the motor. p.35
Economizer operation limited to minimum position.OAT or EC set too high.1. Set at correct temperature (3 F below indoor space temperature). 2. Check OAT or EC by setting above outdoor temperature or humidity level. If the OAT or EC switches do not close, replace OAT or EC. p.35
Economizer operation limited to minimum position.Economizer control board incorrectly wired or not functioning.1. Perform the following tests when OAT or EC is closed. Y1 is called for, and damper is at minimum position. Confirm 24 vac on gray terminal of the economizer control board (gray wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Verify that SW1 and SW3 are wired correctly and working properly (see unit label diagram). 3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not present, check wiring (see unit wiring label diagram). 4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace economizer control board. p.35
Economizer operation limited to minimum position.Incorrect SAT wiring or inoperative SAT.1. After verifying that the OAT and EC settings and the economizer control board wir- ing are correct, check to ensure that the 24 vac terminal of the SAT has 24 vac (white wire). If OAT, EC, and control board are functioning and wired properly and no 24 vac exists, check wiring (see unit label diagram). 2. If supply-air temperature is greater than 57 F, 24 vac should be found at terminal T2 on the SAT (pink wire). If 24 vac is not present, replace SAT. p.35
Damper does not close.Incorrect economizer wiring.1. Verify that SW2 and SW4 are wired and working properly (see unit label diagram). 2. Check diode D19. If diode is not functioning properly, replace economizer control board. p.35
Damper does not close.Incorrect damper actuator wiring or inoperative economizer circuit board.1. After verifying that the wiring is correct, modulate the damper to the minimum posi- tion. Remove the calls for G. 2. If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac is not present, check wiring (see unit label diagram). 3. If damper still does not move, check for 24 vac at blue terminal of economizer con- trol board (blue wire). If 24 vac is not present, replace the economizer control board. p.35
Damper does not close.Incorrect SAT wiring or inoperative SAT.1. After verifying that the wiring is correct and the economizer control board is func- tioning properly, place the OAT or EC switch in the closed position. Place a call for Y1 and open the damper to the fully open position. Confirm that the 24 vac terminal of the SAT has 24 vac (white wire). If 24 vac is not present, check wiring (see unit label diagram). 2. If supply-air temperature is less than 52 F, 24 vac should be found at terminal T1 on the SAT (violet wire). If 24 vac not found, replace SAT. p.35
Damper does not close.Economizer motor failure.If economizer control board and SAT are functioning properly, verify that there is a minimum of 18 vdc at the positive motor terminal. If a minimum of 18 vdc is present and the motor is still not operating, replace the motor. p.35
Economizer damper does not close on power loss.Insufficient battery power, inoperative economizer control board.1. Check voltage potential across batteries. If lower than 14 vdc, replace close-on- power-loss power supply (9-v alkaline batteries). Check this emergency power sup- ply on a regular basis or whenever the filters are changed. 2. If the close-on-power-loss and economizer control board are functioning properly, check for 14 vdc or higher at the blue terminal of the economizer control board (blue wire) when power is disconnected from unit. If 14 vdc is not present, replace the control board. p.35
Damper does not open.Indoor Fan is Off.Check to ensure that 24 vac is present at Terminal C1 (Common Power) on the IFC (Indoor Fan contactor) or that 24 vac is present at the IFO (Indoor Fan On) terminal. Check whether 24 vac is present at PL (Plug) 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). Check proper thermostat connection to G on the connection board. p.36
Damper does not open.No power to EconoMi$er controller.Check to ensure that 24 vac is present across Terminals 24 VAC and 24V COM on the EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram). If 24 vac is present, STATUS light should be on constantly. p.36
Damper does not open.No power to G Terminal.If IFM is on, check to ensure 24 vac is present on G Terminal of the EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram). p.36
Damper does not open.Controller fault.If STATUS light is flashing one flash, the EconoMi$er controller is experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller. p.36
Damper does not open.Thermostat fault.If STATUS light is flashing two flashes, the EconoMi$er controller senses the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1. p.36
Damper does not open.Actuator Fault.Check the wiring between the EconoMi$er controller and the actuator. Hold CONFIG button between three and ten seconds to verify the actuator’s operation. (This process takes three minutes to complete.) p.36
EconoMi$er operation limited to minimum position.Minimum position set incorrectly.Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting. p.36
EconoMi$er operation limited to minimum position.EconoMi$er changeover set point set too high or too low.Set at correct value. See Table 4. p.36
EconoMi$er operation limited to minimum position.Supply air temperature sensor faulty.If STATUS light is flashing 4 flashes, the supply air temperature sensor is faulty. Check wiring or replace sensor. p.36
EconoMi$er operation limited to minimum position.Outdoor air temperature sen- sor faulty.If STATUS light is flashing 5 flashes, the outdoor-air temperature sensor is faulty. Check wiring or replace sensor. p.36
Damper position less than minimum position set point.Supply air low limit strategy controlling.The supply air temperature is less than 45 F, causing the minimum position to decrease. Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct, EconoMi$er is operating correctly. p.36
Damper does not return to minimum position.CO2 ventilation strategy controlling.If a CO2 sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to the Start-Up instructions. EconoMi$er is operating correctly. p.36
Damper does not close on power lossDamper travel is restricted.Check to ensure the damper is not blocked. p.36

Ask about the Bryant 548D

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 548D

Be the first to ask — other owners or our team will answer.

Original document

Bryant 548D manual PDF

40 pages·1.3 MB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…