Engineer designed to satisfy your design requirements.
Cost Effectiveness


Dual Inlet Models MD628, MS628, and MU628 U.L. Classified Shown with 12” media modules DM120
Single Inlet Models MD524 and MS524 U.L. Classified Shown with 12” media modules DM080
Models UD980 and US980 U.L. Listed Shown with 12” media modules UM120
Models UD960 and US960 U.L. Listed Shown with 12” media modules UM080
AdobeAir, Inc. certifies that the evaporative air cooling products shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program.


MasterCool Evaporative Media MasterCool evaporative media is constructed of special cellulose material, impregnated with insoluble anti-rot salts and rigidifying saturants. The cross-fl uted design continually directs water to the air-entering side, inducing a highly turbulent mixing of air and water for optimum heat and moisture transfer.
Direct Evaporative Cooling Process Direct evaporative cooling exchanges sensible heat for latent heat, and follows upward along a constant wet-bulb temperature line on the Psychrometric Chart. The result is a dry-bulb temperature of the leaving air (B) approaching the wet-bulb temperature of the entering air (A).

Standard and Hi-Performance Models The fl exibility of modular components allows selection of CFM and saturation effi ciencies producing the sensible heat capacities needed to meet design requirements. For many applications, our standard 8” media continues to be an economical choice, with an 80% saturation effi ciency at 450 FPM. For more demanding design conditions, our 12” media offers 90% effi ciency at around 450 FPM.
Direct Evaporative Cooling Put simply, whenever water is evaporated, heat is absorbed. This basic principle underlies the design of the MasterCool direct evaporative cooler.
Comfort Levels Not only does evaporative cooling lower the temperature in the space to be cooled, it also lowers the temperature you feel. Rapid air movement produced by the MasterCool increases skin evaporation which causes you to feel 3-5° effectively cooler than the temperature read from a thermometer. Evaporative cooling can provide effective temperatures acceptable in most commercial/ industrial applications throughout the world.
High Quality Construction Hot-dipped galvanized steel, welded for maximum strength is combined with our exclusive POLYBOND® fi nish that protects the whole system – cabinet pans, distributor covers, louvers, and all other parts contacting water. The electrostatically applied polyester epoxy powder-based coating is cured at high temperature and is so durable that these models are backed by the best warranty in the industry.
Typical Applications The Industrial MasterCool is used for area cooling or spot cooling. In many areas it can replace or supplement mechanical refrigeration needs in agricultural, institutional, commercial, and industrial applications. Applications such as kitchens, laundries, gymnasiums, heat treating areas, and dry cleaning plants requiring large quantities of fresh air moving through the building are ideal candidates for evaporative cooling.
Energy Efficient... Environmentally Friendly With no compressors or condensors, MasterCool evaporative coolers offer signifi cant energy savings over mechanical refrigeration units; and, with no CFC’s, do not contribute to depletion of the ozone layer. Their air washing effect improves indoor air quality with fresh, fi ltered air constantly brought into the cooled space...forcing stale air out.


The Indirect Cooling Module Outside air is drawn into the ICM. A fan draws air through the inside of vertical fi ns (which have water running inside them). The air picks up heat and is expelled from the ICM while the fi ns are cooled by evaporation. Other outside air is drawn across the outside surfaces of the cooled fi ns, and is cooled without coming in contact with water. This cooled air, with no humidity added, then enters the direct evaporative section of the Industrial MasterCool for fi nal cooling.
Indirect/Direct Evaporative Cooling Process In the indirect cooling stage, entering air is cooled along a horizontal humidity ratio line on the Psychrometric Chart (A to B) without adding moisture. In the next cooling stage, this air is further cooled along a new wet-bulb line (B to C), resulting in a lower dry-bulb temperature of leaving air than can be achieved with single stage direct evaporative cooling alone.

Typical Confi gurations Many confi gurations of 2-Stage Industrial MasterCool are possible. Typical fi eld-assembled components include 2 or 3 Indirect Cooling Modules with Models MD/MS524 and 4 or 6 ICM’s with models MD/MS/
MU628 Contact your local MasterCool representative for assistance in sizing.

Models shown with three ICM’s at each inlet location.
2-Stage Indirect/Direct Evaporative Cooling 2-Stage cooling allows you to use energy-saving evaporative cooling technology for design conditions where direct evaporative cooling alone is not adequate. A 2-stage cooler results in greater cooling power, less affected by higher ambient temperature and humidity.
KoolKalk... Computer Aided Sizing The sizing method described in this brochure can be used for general sizing of direct evaporative Industrial MasterCool units.
For more accurate sizing, and for sizing indirect/direct units, we recommend the use of KoolKalk... an IBM compatible computer program designed specifi cally for AdobeAir Evaporative Coolers. For more information please visit the AdobeAir, Inc. website at www.AdobeAir.com
In the indirect cooling stage, outside entering air is cooled sensibly reducing its total enthalpy. This “precooled” air is then evaporatively cooled in the direct cooling stage, approaching its new, lower wet-bulb temperature.
The end result is discharge temperatures near or even slightly below the wet-bulb temperature. More importantly, these lower discharge temperatures translate into customer comfort at a fraction of the cost of refrigerated air conditioning.
Applications With its substantial increase in cooling capacity, the indirect/direct 2-stage Industrial MasterCool can replace mechanical refrigeration in many applications.

Single Inlet Model Dimensions MD524 or UD960 (Down Discharge) and MS524 or US960 (Side Discharge)



Electrical Specifi cations HP Speed Phase Voltage Amperage NEMA Frame Shaft Diameter Motor Kit # ¾ 1 1 115/230 12.5/6.2 56 5/8 EJ006 ¾ 2 1 230 5.9 56 5/8 EJ020 ¾ 1 3 208-230/460 3.0/1.5 56 5/8 EJ883 115/230 15.1/7.5 56 5/8 EJ007 1 2 1 230 7.3 56 5/8 EJ021 1 1 3 208-230/460 3.6/1.7 143T 7/8 EJ665 1½ 1 1 115/230 14.5/6.3 143T 7/8 EJ212 1½ 1 3 208-230/460 4.6/2.2 143T 7/8 EJ666 2 1 1 115/230 19.0/8.5 143T 7/8 EJ213 2 1 3 208-230/460 7.1/3.3 143T 7/8 EJ667 3 1 3 208-230/460 8.7-8.4/4.2 182T 11/8 EJ668 5 1 3 208-230/460 14.2-13.0/6.5 184T 11/8 EJ659 7½ 1 3 208-230/460 20.9-19.2/9.6 213T 13/8 EJ675
Bleed Rates GPH per Media Module
Pump Volts Amps Watts GPH Model# At 4’ Head CP280 115 1.2 80 300 CP480 230 .6 80 300
Blower Model Blower Motor HP ¾ 1 1½ 2 3 5 7½ 524 or 960 7 8 9 10 10 – – 628 or 980 – 11 13 14 16 18 20

Dual Inlet Model Dimensions MD628 or UD980 (Down Discharge), MS628 or US980 (Side Discharge) and MU628 (Up Discharge)


Sizing Instructions Follow these steps to properly size the Industrial MasterCool. The performance or Sensible Heat Capacity of any cooler is a function of both the CFM and saturation effi ciency (which determines the delivered air discharge temperature). Sizing by only considering CFM may result in an improperly sized application.
Refer to the Electrical Specifi cations chart on facing page.
Refer to the Certifi ed Air Delivery CFM chart for the chosen cooler and selected motor HP.
Refer to the Sheave Selection charts on the next page. Find the selected motor HP, shaft size, and desired RPM (See Steps 2-4 above). You might need to look at more than one sheave before fi nding the correct RPM.
LAT = DB1 - [(DB1 - WB ) * EFF]
where EFF ‘ 0.80 for 8” media or 0.90 for 12” media
CFM = 0.925 * Sensible Heat Load
Complete systems consist of the following components, and are sold separately for application versatility.
Refer to the specifi cation / air fl ow charts on next page.
This will result in more accurate sizing. Motor Sheave Selection 1. Determine the external static pressure of the air delivery system.
Outdoor Dry-Bulb DB1 · Outdoor Wet-Bulb WB1 · Indoor Dry-Bulb T1

Certifi ed Air Delivery CFM at Various External Static Pressures Inches Water Gauge. AMCA Licensed Ratings.

MD/MS/MU 628 or UD/US 980 Sheave Selection Motor HP Browning Bore Blower RPM / Sheave Turns Open MasterCool Part # 5 4 ½ 4 3 ½ 3 2 ½ 2 1 ½ 1 ½ 0 Package # Single Phase Motor Blower RPM @ 1725 Motor RPM / Sheave Turns Open 1 1VL40 5/8 230 240 249 259 268 278 288 297 307 316 326 EL110 1½, 2 1VL40 7/8 230 240 249 259 268 278 288 297 307 316 326 EL112 1 1VL44 5/8 268 278 288 297 307 316 326 335 345 355 364 ESH2411 1½, 2 1VL44 7/8 268 278 288 297 307 316 326 335 345 355 364 EL685 1 1VP50 5/8 326 335 345 355 364 374 383 393 403 412 422 693 1½, 2 1VP50 7/8 326 335 345 355 364 374 383 393 403 412 422 686 Three Phase Motor Blower RPM @ 1750 Motor RPM / Sheave Turns Open 1, 1½, 2 1VL34 7/8 185 194 204 214 224 233 243 253 263 272 282 EL116 1, 1½, 2 1VL40 7/8 233 243 253 263 272 282 292 301 311 321 331 EL112 1, 1½, 2 1VL44 7/8 272 282 292 301 311 321 331 340 350 360 369 EL685 1, 1½, 2 1VP50 7/8 331 340 350 360 369 379 389 399 408 418 428 686 3 2VP42 11/8 253 263 272 282 292 301 311 321 331 340 350 687 3, 5 2VP50 11/8 331 340 350 360 369 379 389 399 408 418 428 688 5 2VP60 11/8 408 418 428 438 447 457 467 476 486 496 506 689 7½ 2VP60 13/8 408 418 428 438 447 457 467 476 486 496 506 692

Project Submittal Sheet Models MD/MS 524, MD/MS/MU 628 — U.L. Classifi ed or UD/US 960, UD/US 980 — U.L. Listed
*Total design sensible heat load of project.
Blower Section Motor Specifi cations Kits Ref. No. Qty. Model No. Motor HP Volts Phase Amps Motor Sheave Belt
*NOTE: Each unit (ready to operate) consists of one blower section, one blower motor, one pulley-belt kit, one motor sheave. Wet Section – Pump
Wet Section Pump Ref. No. Qty. Model No. Quantity Volts Amps GPM
*NOTE: Each wet section (ready to operate) consists of one wet module and one pump.
Your local MasterCool Representative of AdobeAir, Inc., is ready to assist you in unit selection and application.
MasterCool evaporative coolers and components are designed and tested in accordance with one or more of the following standards or agencies: Air Delivery: Data published derived from tests conducted in accordance with A.M.C.A. (Air Move- ment and Control Assoc.) Standard 210. Sealant: Water Immersion: per ASTM D870. Flexibility: per ASTM D756. Corrosion Resistance: per ASTM B117. Cycle Freeze/Thaw: per ASTM C117. POLYBOND®: Corrosion Resistance: per ASTM B117. Pencil Hardness: per ASTM D3363. Adhesion: per ASTM D3359. Impact Resistance: per ASTM D2794. Flexibility: per ASTM D522. Specular Gloss: per ASTM D523. Surface Burning Characteristics of Building Materials (best rating) per U.L. 723 and ASTM E-84. Pumps: Recognized under the U.L. component recognition program for the application – construc- tion, thermal overload, running overload, and locked rotor protection. Blower Motors: U.L. Recognized general purpose drip-proof. Polymeric Materials: Tested in accordance with U.L. 94 and 746C. Covered by City of Los Angeles Research Reports (C.O.L.A.) RR930224 (for all single phase applications), or RR930190 (for 3 phase applications) Electrical, and RR8141 Mechanical.
The world leader in evaporative cooling technology, AdobeAir, Inc. is continually involved in the process of product improvement. AdobeAir, Inc. therefore reserves the right to change specifi cations and/or design without prior notice. To obtain the most current product information and/or specifi cations, visit the AdobeAir, Inc. web site at www.AdobeAir.com
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.