Gallagher T15 Reader

Installation Note

T15 MIFARE® Reader, Black: C300470 T15 MIFARE® Reader, White: C300471 T15 Multi Tech Reader, Black: C300480 T15 Multi Tech Reader, White: C300481

T15 PIV Reader, Black: C305470 T15 PIV Reader, White: C305471 T15 PIV Reader - Multi Tech, Black: C305480 T15 PIV Reader - Multi Tech, White: C305481

Gallagher Access Control Reader (T15) — Installation Note diagram (page 1)
Fig. 2 · Installation Note

Page 1 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Page 2 of the Gallagher Access Control Reader (T15) user manual — Gallagher T15 Reader
Page 2 · click to enlarge
Page 2

This document gives certain information about products and/or services provided by Gallagher Group Limited or its related companies (referred to as "Gallagher Group").

The information is indicative only and is subject to change without notice meaning it may be out of date at any given time. Although every commercially reasonable effort has been taken to ensure the quality and accuracy of the information, Gallagher Group makes no representation as to its accuracy or completeness and it should not be relied on as such. To the extent permitted by law, all express or implied, or other representations or warranties in relation to the information are expressly excluded.

Neither Gallagher Group nor any of its directors, employees or other representatives shall be responsible for any loss that you may incur, either directly or indirectly, arising from any use or decisions based on the information provided.

Except where stated otherwise, the information is subject to copyright owned by Gallagher Group and you may not sell it without permission. Gallagher Group is the owner of all trademarks reproduced in this information. All trademarks which are not the property of Gallagher Group, are acknowledged.

Copyright © Gallagher Group Ltd 2022. All rights reserved.

Page 2 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Disclaimer

Page 4 of the Gallagher Access Control Reader (T15) user manual — 1 Introduction
Page 4 · click to enlarge
Page 4

1 Introduction

The Gallagher T15 Reader is a smart card and Bluetooth® low energy technology reader. It can be installed as either an entry reader or exit reader. The reader sends information to the Gallagher Controller and acts upon information sent from the Gallagher Controller. The reader itself does not make any access decisions.

The reader is available in ten variants. The supported technologies and compatibility for each variant is shown in the table below.

Reader VariantProduct CodesCard Technologies SupportedNFC Access for Android Supported FromBluetooth® Access Supported FromHBUS Comms Supported FromCardax IV Comms Supported From T15 MIFARE ReaderC300470 C300471ISO 14443A MIFARE® DESFire® EV1/EV2*, MIFARE Plus®, and MIFARE Classic® cardsvEL7.80 HBUS onlyNonevEL7.00vEL1.02 T15 Multi Tech ReaderC300480 C300481ISO 14443A MIFARE DESFire EV1/EV2*, MIFARE Plus, MIFARE Classic, and 125 KHz cardsvEL7.80 HBUS onlyvEL7.60 HBUS onlyvEL7.00vEL1.02** T15 PIV ReaderC305470 C305471ISO 14443A PIV, PIV-I, CAC, TWIC, MIFARE DESFire EV1/EV2*, MIFARE Plus, and MIFARE Classic cardsvEL7.80 HBUS onlyNonevEL7.10None T15 PIV Reader - Multi TechC305480 C305481ISO 14443A PIV, PIV-I, CAC, TWIC, MIFARE DESFire EV1/EV2*, MIFARE Plus, MIFARE Classic, and 125 KHz cardsvEL7.80 HBUS onlyNonevEL7.10None

* MIFARE DESFire EV2 is supported from vEL7.70.

** Gallagher strongly recommends against using dual technology 125/MIFARE cards with Multi Tech Readers for sites running pre-Command Centre v7.00 software. From Command Centre v7.00, a site may specify which technology a Multi Tech Reader should read off a dual technology card.

Page 4 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Page 5 of the Gallagher Access Control Reader (T15) user manual — HBUS cabling topology
Page 5 · click to enlarge
Page 5

2 Before you begin

2.1 Shipment contents

Check the shipment contains the following items:

  • 1 x Gallagher T15 Reader facia assembly
  • 1 x Gallagher T15 Reader bezel
  • 1 x M3 Torx Post Security screw
  • 2 x 25 mm No.6 self tapping, pan head, Phillips drive fixing screws
  • 2 x 40 mm No.6 self tapping, pan head, Phillips drive fixing screws

2.2 Power supply

The Gallagher T15 Reader is designed to operate over a supply voltage of 13.6 Vdc measured at the reader terminals. The operating current draw is dependant on the supply voltage at the reader. The power source should be linear or a good quality switched-mode power supply. The performance of the reader may be affected by a low quality, noisy power supply.

2.3 Cabling

The Gallagher T15 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm2) stranded security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When using a single cable to carry both power supply and data, both the power supply voltage drop and data requirements must be considered.

HBUS cabling topology

The HBUS communications protocol is based on the RS485 standard and allows the reader to communicate over a distance of up to 500 m (1640 ft).

The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or "Star" topology should not be used between devices). Should "Star" or "Home-Run" wiring be required, the HBUS 4H/8H Modules and the HBUS Door Module allow multiple HBUS devices to be individually wired to the one physical location.

The end devices on the HBUS cable should be terminated using 120 ohms resistance. To terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers to the Controller. To terminate a reader, connect the orange (termination) wire to the green (HBUS A) wire. Termination is already included at the HBUS Module, (i.e. each HBUS port is permanently terminated at the module).

Page 5 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Page 6 of the Gallagher Access Control Reader (T15) user manual — H1 H4 H8 H5
Page 6 · click to enlarge
Page 6

"T" or "Star" circuits are

RS485 1

"T" or "Star" circuits are

RS485 1

HBUS Device Controller 6000

Terminate Remove the on-board

H1 H4 H8 H5

Page 6 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Show 31 more labels / short text on this page
HBUS Device · not permitted between · HBUS devices · HBUS Device · HBUS Device · HBUS Device · HBUS Device · Controller 6000 · Connect the on-board · Terminate · termination jumper · HBUS Device · not permitted between · HBUS devices · HBUS Device · HBUS Device · HBUS Device · Terminate · termination jumper · Controller 6000 · HBUS Device · HBUS Device · HBUS Device · HBUS Device · HBUS Module · Terminate · Terminate · HBUS Device · HBUS Device · Terminate · Terminate
Page 7 of the Gallagher Access Control Reader (T15) user manual — 3 Distance between readers
Page 7 · click to enlarge
Page 7

Cable distance

Cable typeCable format*HBUS single reader connected using data only in a single cableCardax IV single reader connected using data only in a single cable***HBUS/Cardax IV single reader connected using power and data in a single cable**** CAT 5e or betet r**4 twisted pair each 2 x 0.2 mm2 (24 AWG)500 m (1640 ft)200 m (650 ft)100 m (330 ft) BELDEN 9842** (shielded)2 twisted pair each 2 x 0.2 mm2 (24 AWG)500 m (1640 ft)200 m (650 ft)100 m (330 ft) SEC4724 x 0.2 mm2 Not twisted pairs (24 AWG)400 m (1310 ft)200 m (650 ft)100 m (330 ft) SEC41424 x 0.4 mm2 Not twisted pairs (21 AWG)400 m (1310 ft)200 m (650 ft)150 m (500 ft) C303900/ C303901 Gallagher HBUS Cable2 Twisted pair each 2 x 0.4 mm2 (21 AWG, Data) and 2 x 0.75 mm2 Not Twisted Pair (~18 AWG, Power)500 m (1640 ft)200 m (650 ft)450 m (1490 ft)

* The matching of wire sizes to equivalent wire gauges are only approximate. ** Recommended cable types for optimal HBUS RS485 performance. *** Not applicable for PIV or Bluetooth® enabled reader installations. **** Tested with 13.6V at start of cable. Notes:

  • Shielded cable may reduce the obtainable cable length. Shielded cable should be grounded at the Controller end only.
  • If other cable types are used, operating distances and performance may be reduced depending on the cable quality.
  • HBUS allows up to 20 readers to be connected to a single cable. Each reader requires 13.6 Vdc to function correctly. The cable length and the number of readers connected will have an impact on the voltage at each reader.

3 Distance between readers

The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions. When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of the wall is not less than 200 mm (8 inches) away.

Gallagher Access Control Reader (T15) — 3 Distance between readers diagram (page 7)
Fig. 3 · 3 Distance between readers

Page 7 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

200 mm · 200 mm

Page 8 of the Gallagher Access Control Reader (T15) user manual — 4 Installation
Page 8 · click to enlarge
Page 8

4 Installation

The Gallagher T15 Reader is designed to be mounted on any solid flat surface. However installation on metal surfaces, particularly those with a large surface area will reduce read range. The extent to which the range is reduced will depend upon the type of metal surface.

The recommended mounting height for the reader is 1.1 m (3.6 ft) from the floor level to the centre of the reader device. However this may vary in some countries and you should check local regulations for variations to this height.

1. Use the reader bezel as a guide to drill all three holes. Drill the 13 mm (1/2 inch) diameter centre hole (this is the centre hole for which the building cable will exit the mounting surface) and the two fixing holes.
2. Run the building cabling out through the centre hole and through the reader bezel.
3. Secure the bezel to the mounting surface using the two fixing screws provided. It is important the bezel of the reader is flush with and tight against the mounting surface. Three screw locations have been provided. Gallagher recommend using the outer screw locations.

No. 6 pan head screw

No. 6 pan head screw

4. Connect the reader tail extending from the facia assembly to the building cable. Connect the wires for the appropriate reader you wish to interface, either an HBUS Reader or a Cardax IV Reader, as shown in the following diagrams.

Page 8 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Bezel · Building cable

Page 9 of the Gallagher Access Control Reader (T15) user manual — 4 Installation
Page 9 · click to enlarge
Page 9

An HBUS Reader connects to a Gallagher Controller 6000, Gallagher 4H/8H Module (attached to a Controller 6000) or a Gallagher HBUS Door Module (connected to a Controller 6000).

A Cardax IV Reader connects to a Gallagher Controller 6000, Gallagher 4R/8R Module (attached to a Controller 6000) or a Gallagher GBUS Universal Reader Interface (Gallagher GBUS URI).

HBUS Reader connectionHBUS Reader terminated:

Positive Red Negative Black HBUS Termination Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue

Positive Red Negative Black HBUS Termination Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue

Cardax IV Reader connection:

Positive Red Negative Black HBUS Termination Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue

5. Fit the facia assembly into the bezel by clipping the small lip, into the top of the bezel and holding the top, press the bottom of the facia assembly down into the bezel.
6. Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) through the hole at the bottom of the bezel to secure the facia assembly.

Fit screw to secure facia to bezel

7. Removal of the facia assembly is a simple reversal of these steps.

Page 9 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Show 7 more labels / short text on this page
HBUS Reader · HBUS Reader · Cardax IV Reader · Building cable · Reader tail · Facia · Connection
Page 10 of the Gallagher Access Control Reader (T15) user manual — 6 Accessories
Page 10 · click to enlarge
Page 10
8. Configure the reader in Command Centre. If the reader is connected as an HBUS Reader, refer to the topic "Configuring HBUS Devices" in the Command Centre Configuration Client Online Help. If the reader is connected as a Cardax IV Reader, refer to the topic "Creating Readers" in the Command Centre Configuration Client Online Help.

5 LED indications

LED (squiggle)HBUS indication 3 Flash (Amber)No communications with the Controller. 2 Flash (Amber)Communications with the Controller, but reader is not configured. 1 Flash (Amber)Configured to a Controller, but reader is not assigned to a door or elevator car. On (Green or Red)Fully configured and functioning normally. Green = Access mode is Free Red = Access mode is Secure Flashes GreenAccess has been granted. Flashes RedAccess has been denied. Flashes (Blue)Reading and validating a PIV card. Reading a Gallagher mobile credential.
LED (squiggle)Cardax IV indication 3 Flash (Amber)No communications with the Controller. On (Green or Red)Fully configured and functioning normally. Green = Access mode is Free Red = Access mode is Secure Flashes GreenAccess has been granted. Flashes RedAccess has been denied.

6 Accessories

AccessoryProduct code T15 Bezel, Black, Pk 10C300296 T15 Bezel, White, Pk 10C300297 T15 Bezel, Silver, Pk 10C300298 T15 Bezel, Gold, Pk 10C300299 T15 Dress Plate, Black, Pk 10C300324

Page 10 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Page 11 of the Gallagher Access Control Reader (T15) user manual — 7 Technical specifications
Page 11 · click to enlarge
Page 11

7 Technical specifications

Routine maintenance:Not applicable for this reader Cleaning:This reader should only be cleaned with a clean, lint free, damp cloth Voltage:13.6 Vdc Current3:MIFARE ReaderMulti Tech Reader Idle1Maximum2Idle1Maximum2 50 mA77 mA81 mA136 mA Temperature range:-35 °C to +70 °C4 Note: Direct sunlight may increase the internal reader temperature above the ambient temperature level Humidity:0 - 95% non-condensing5 Environmental protection:IP686 Impact rating:IK076 Unit dimensions:Height 139 mm (5.47 inches) Width 44 mm (1.73 inches) Depth 23 mm (0.9 inches) Maximum number of readers on one HBUS cable:20

1 The reader is idle. 2 Maximum reader current during credential read. 3 The current values stated above have been reported using the default configuration for a reader in Command Centre. Changing the configuration may vary the current value. Reader currents verified by UL are provided in the document "3E2793 Gallagher Command Centre UL Configuration Requirements". 4 Gallagher T Series readers are UL temperature tested and certified for operation in 0oC - 49oC (indoor) and -35oC - +66oC (outdoor). 5 Gallagher T Series readers are UL humidity tested and certified to 85% and have been independently verified to 95%. 6 Environmental protection and impact ratings are independently verified.

Page 11 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Page 12 of the Gallagher Access Control Reader (T15) user manual — 8 Approvals and Compliance Standards
Page 12 · click to enlarge
Page 12

8 Approvals and Compliance Standards

This symbol on the product or its packaging indicates that this product must not be disposed of with other waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment. The separate collection and recycling of your waste equipment at the time of disposal will help conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. For more information about where you can drop off your waste equipment for recycling, please contact your local city recycling office or the dealer from whom you purchased the product.

This product complies with the environmental regulations for the Restriction of Hazardous Substances in electrical and electronic equipment (RoHS). The RoHS directive prohibits the use of electronic equipment containing certain hazardous substances in the European Union. FCC

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

  • Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.

Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Please refer to the document "3E2793 Gallagher Command Centre UL Configuration Requirements" for a guide to configuring the Gallagher system to the appropriate UL Standard. Installers must ensure these instructions are followed to ensure the installed system is UL compliant.

AS/NZS IEC 60839.11.1:2019 Grade 4, Class II

C300480 only The C300480 variant of the T15 Readers is the only variant that complies with BIS.

US - Equipmentcom, burg and acc reader CA - Equipment: com, burg reader

Page 12 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Industry Canada · Industrie Canada · UL Installations

Page 13 of the Gallagher Access Control Reader (T15) user manual — 9 Mounting dimensions
Page 13 · click to enlarge
Page 13

9 Mounting dimensions

16 mm (0.63") 67 mm (2.64")

139 mm (5.47")

44 mm (1.73")

13 mm (1/2") diameter hole for cable

44 mm (1.73")

Page 13 3E4237 Gallagher T15 Reader | Edition 11 | February 2022 Copyright © Gallagher Group Limited

Ask about the Gallagher Access Control Reader (T15)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Gallagher Access Control Reader (T15)

Be the first to ask — other owners or our team will answer.

Original document

Gallagher Access Control Reader (T15) manual PDF

13 pages·287 KB·Security·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…