TX3-TOUCH-UPS-KIT Installation Instructions

A. Package contents

  • APC Back-UPS uninterruptible power supply (model: BE 550G, rating: 550VA 120V) including manufacturer’s documentation and USB A male to USB B male cable (shown on right)
  • 2 USB over Ethernet extender cables (shown on right). Use with an Ethernet cable (not included) if more distance is required. Maximum distances is 46 m (150 feet)

B. Connect the USB Cable

The USB connection between the uninterruptible power supply and the TX3 Touch (in conjunction with the APC software) ensures that the TX3 Touch will shut down properly during a power outage.

1. Connect the USB port on the uninterruptible power supply to the USB port on the TX3 Touch.
Mircom TX3 Touch UPS Kit — B. Connect the USB Cable diagram (page 1)
Fig. 1 · B. Connect the USB Cable

USB A male to USB B male (Connect to the USB port at the bottom of the Touch chassis, above the On/Off switch)

If the USB A male to B male cable is too short, use an Ethernet cable (not included) and the included USB over Ethernet extender cables as shown below. The maximum distance is 46 m (150 feet).

Mircom TX3 Touch UPS Kit — B. Connect the USB Cable diagram (page 1)
Fig. 2 · B. Connect the USB Cable

Ethernet to USB A female USB A male to Ethernet (Connect to the USB port at the bottom of the Touch chassis, above the On/Off switch)

2. Go to page 2.

LT-6714 Rev 0 http://www.mircom.com Page 1 of 3

Page 2 of the Mircom TX3 Touch UPS Kit user manual — C. Connect the Power Cable
Page 2 · click to enlarge
Page 2

C. Connect the Power Cable

1. Connect the power supply cable from the Line terminals on the TX3-PS24-5A power supply to one of the Battery Backup + Surge Protection receptacles on the uninterruptible power supply.

Power supply cable (included with TX3-PS24-5A

To AC outlet (follow manufacturer's instructions)

Battery Backup + Surge Protection

2. Follow the manufacturer’s documentation to power on the uninterruptible power supply.
3. Go to page 3.

LT-6714 Rev 0 http://www.mircom.com Page 2 of 3

TX3-PS24-5A power supply · Line · Back-UPS

Page 3 of the Mircom TX3 Touch UPS Kit user manual — 2. Install the APC PowerChute Personal Edition Software
Page 3 · click to enlarge
Page 3

D. Install the APC PowerChute Personal Edition Software (existing installations only)

The APC software (in conjunction with the USB cable) ensures that the TX3 Touch will shut down properly during a power outage.

1. Back up the Job to a USB Flash Drive

1. On the main touch screen display, enter 9999 .

The administrator access code window appears.

2. Enter the password to log in to the system and press OK (by default the there is no password).
3. Insert a USB flash drive into the USB port above the On/Off switch on the TX3 Touch.
4. Select File - Backup from the Menu Bar. The Backup Jobs window appears.
5. Select Backup current job only .
6. Click Browse and choose the USB flash drive as the location to store the backup files.
7. Click Backup Now .

2. Install the APC PowerChute Personal Edition Software

1. Read the manufacturer’s documentation for instructions on how to get the APC PowerChute Personal Edition software.
2. Transfer the APC software to a USB flash drive.
3. On the TX3 Touch, select File - Shut Down - Exit to Windows from the Menu Bar.
4. Click Yes .

The TX3 Touch software shuts down and the Windows Explorer appears.

5. Insert the USB flash drive into the USB port above the On/Off switch on the TX3 Touch.
6. In the Windows Explorer, double-click the icon for the USB flash drive.
7. Double-click the exe file for the APC software.
8. Follow the instructions on the screen to install the software.
9. During the installation, you may see a Hibernation Support Warning . This is normal. Click OK on this warning.
10. After the software has been installed, double-click the Desktop folder, then double-click the Restart icon to restart the TX3 Touch.

If you have questions, contact us at:

http://www.mircom.com Phone: 1-905-660-4655 Toll Free: 1-888-647-2665

LT-6714 Rev 0 http://www.mircom.com Page 3 of 3

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Mircom TX3 Touch UPS Kit

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mircom TX3 Touch UPS Kit

Be the first to ask — other owners or our team will answer.

Original document

Mircom TX3 Touch UPS Kit manual PDF

3 pages·680 KB·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…