Thank you for purchasing Raritan's Smart Rack Controller (SRC). This product provides an ideal rack management solution which features the following functions for data centers and server rooms:
This Quick Setup Guide explains how to install and configure the SRC. For further details on using the SRC, access online help from the application, or download the user guide from Raritan's Support page (http://www.raritan.com/support/). For more detailed information on this release, see the latest release notes on the Support page.
The following lists the equipment shipped with SRC. If anything is missing or damaged, contact the local dealer or Raritan Technical Support for help.
There are two ways to mount an SRC device, using the same Raritan rackmount brackets.

Part or all of the following equipment is shipped on demand only.
The SRC is mounted like a 1U device in the rack.
The SRC is mounted like a 0U device in the rack.

QS Rule Before You Begin
Prepare the installation site. Make sure the installation area is clean and not exposed to extreme temperatures or humidity. Allow sufficient space around the SRC for cabling and equipment connections.
To mount SRC like a 1U device:
Package Contents · Rackmount

Connection Ports for Sensors, Door Handles, and Assets

If you purchase Optional Accessories (on page 1), make sure you connect them to the correct port on the SRC. Connecting to the wrong port may cause damage to SRC and/or connected accessories.


To mount SRC like a 0U device:

Raritan's DX or DX2 environmental sensor packages are required for SRC to detect the surrounding condition like the temperature, or to control a system like door handles.
SRC provides the SENSOR port for connecting Raritan DX or DX2 environmental sensor packages so that you can remotely monitor environmental factors, such as temperature and humidity, around the rack.

You need a SmartLock kit if your SRC does NOT include a built-in DX2-DH2C2, such as SRC-0100.
DX2-DH2C2 ports and terminals:

Raritan's door handles or SmartLock kits are required for SRC to control the access to a cabinet.
Depending on your SRC model, you may have to purchase either only door handles or a full SmartLock kit from Raritan.
Raritan's SmartLock kit contains one DX2-DH2C2 and a pair of door handles.
To detect the cabinet's door status, you need to connect third-party contact closure detectors, which are optional.
Read the restrictions below before connecting door handles or a SmartLock kit (that is, DX2-DH2C2 kit) to SRC.


SRC door handle ports and terminals:
Numbers in the following diagram (
) correspond to the numbers in the previous section's table.

Connection procedure:
You only need to purchase door handles if your SRC has a built-in DX2-DH2C2, such as SRC-0102.
Connection procedure:
Both asset management strips and asset tags are required for SRC's asset management feature.
Limitation: Do NOT connect door handles or SmartLock kit to SRC while asset strips are being connected to SRC.
Each tag port on the regular asset strips corresponds to a rack unit and can be used to locate IT devices in a specific rack (or cabinet).
and

For each rack, you can attach asset strips up to 64U long, consisting of one MASTER and multiple SLAVE asset strips.
The following diagram illustrates an asset tag. Note that there are two types of asset tags: non-programmable and programmable tags. The only difference is that programmable asset tags allow you to customize each tag's ID or barcode number while non-programmable ones have factory default ID or barcode numbers, which you cannot change.
The difference between the master and slave asset strips is that the master asset strip has an RJ-45 connector while the slave does not.
The following diagram illustrates some asset strips. Note that Raritan provides more types of asset strips than the diagram.


8U MASTER asset strip with 8 tag ports
Before connecting regular asset strips to the SRC, you must assemble them.
8U SLAVE asset strip with 8 tag ports
5U "ending" SLAVE asset strip with 5 tag ports
To assemble regular asset strips:

You need both asset strips and asset tags for tracking IT devices.
Asset tags provide an ID number for each IT device. The asset tags are adhered to an IT device at one end and plugged in to an asset strip at the other.
The asset strip is connected to the SRC, and the asset tag transmits the ID and positioning information to the asset strip.
a. The MASTER asset strip is installed as the first one in the
asset strip assembly.
b. All SLAVE asset strips are connected following the MASTER
asset strip.
c. The "ending" slave asset strip is installed as the final one.

The asset strips are automatically attracted to the rack because of magnetic stripes on the back.
SRC supports a cabling distance up to 10 meters for each connected asset strip assembly.

To connect regular asset strips to SRC:


QS Rule Connecting SRC to Power
SRC supports redundant power with two inlets. See Product Models.
You can connect only one or both inlets to proper power sources.
Raritan provides more types of asset strips than regular asset strips, such as composite asset strips or blade extension strips. For detailed information, refer to the user documentation accompanying Raritan asset strips.

The SRC supports common web browsers, including Microsoft Internet Explorer®, Mozilla Firefox®, and Google® Chrome.
QS Rule Connecting SRC to Your Network
SRC can be connected to a wired or wireless network.
To access the SRC web interface:
To make a wired connection:

10/100/1000" supports up to 1000 Mbps so it is highly recommended for network connection. If connecting both ports to the LAN, you must connect them to two "different" subnets. If you are not sure whether the device is connected to the same or different subnets, contact your IT department.
To make a wireless connection:
It is highly recommended to change the default password. Make sure the new password is noted down and kept in a secure place.
QS Rule Using a Web Browser
Initial configuration using a web browser involves these two steps.
After logging in to the SRC web interface, you can navigate the left menu and then:
After connecting to a DHCP IPv4 network, an IPv4 address is automatically assigned to your SRC. You can operate the front panel display to retrieve the IPv4 address. See Using the Front Panel Display (on page 7).
The SRC front panel display is similar to the diagram below.

An iOS or Android mobile device, such as a smartphone or tablet, can function as a local display of SRC. Note that the Android device must support USB "On-The-Go" (OTG), or this function does not work.
To retrieve the IP address:
to show the "Main Menu."
to select "Device Info," and press
Raritan's app "PDView" is required for the mobile device to function as a local display. It is a free app.
until the device's IP address is displayed.
or · or · or

To download PDView:

If they have been changed, the login screen displays instead and you must enter appropriate user credentials for login.
The SRC supports the following USB Wi-Fi LAN adapters.
The USB cable and USB port to connect are determined by your mobile operating system.
To connect your mobile device to SRC:

You can connect the wireless LAN adapter either to SRC or to a USB hub attached to SRC.
To make a wireless connection:
Do one of the following:
If wireless networking is preferred, ensure that the wireless LAN configuration of your SRC matches the access point. The following is the wireless LAN configuration that the SRC supports.
You can access the SRC web interface via PDView to view or change the settings.
To access the SRC web interface:

For more information about SRC and the entire Raritan product line, see Raritan's website (www.raritan.com). For technical issues, contact Raritan Technical Support. See the Contact Support page in the Support section on Raritan's website for technical support contact information worldwide. Raritan's products use code licensed under the GPL and LGPL. You can request a copy of the open source code. For details, see the Open Source Software Statement at (http://www.raritan.com/about/legal-statements/open-source-software-statement/) on Raritan's website.
SRC has a cap plugged into its EXPANSION port when shipping out of the factory. This port is reserved for future use and does NOT function. It is suggested to keep the cap plugged continuously.