INSTALLATION, OPERATION &

QUICK START GUIDE

CompleteStat TM Controller

Models: CS9B-THOA CS9B-THOCA

CS9BE-THOA CS9BE-THOCA

Bard CompleteStat Controller — INSTALLATION, OPERATION & diagram (page 1)
Fig. 1
Bard CompleteStat Controller — INSTALLATION, OPERATION & diagram (page 1)
Fig. 2
Bard CompleteStat Controller — INSTALLATION, OPERATION & diagram (page 1)
Fig. 3

Bard Manufacturing Company, Inc. Bryan, Ohio 43506

Manual2100-684A Supersedes: 2100-684 Date: 11-10-20

www.bardhvac.com

Page 1 of 10

Page 2 of the Bard CompleteStat Controller user manual — INSTALLATION, OPERATION &
Page 2 · click to enlarge
Page 2
Page 2 of the Bard CompleteStat Controller user manual — INSTALLATION, OPERATION &
Page 3 of the Bard CompleteStat Controller user manual — B
Page 3 · click to enlarge
Page 3

INSTALLATION

3. Route control wiring through base plate.
4. With the embossed “UP” arrows of the base plate pointing in the appropriate direction, fasten the base plate to the desired wall location. A vertical/ horizontal 2x4 wall handybox can be used for the CO 2 -sensing CompleteStat and a vertical-only 2x4 wall handybox can be used for non-CO 2 -sensing CompleteStat.
5. Make appropriate control wire connections to terminal blocks. See low voltage wiring diagrams beginning on page 15.
1. It is recommended that18 AWG solid-conductor control wire is used for installation. See the low voltage wiring diagrams beginning on page 15 for exact number of conductors.
6. Replace controller over base plate, being careful not to pinch/dislodge connections.

where transient signals may accumulate and affect digital signal from control to unit.

7. Turn hex screws in bottom/top of controller counterclockwise (outward) to secure cover.
2. Turn the hex screws in the bottom and top of the controller clockwise (inward) until they clear the cover. Remove base plate from controller.

FIGURE 1 CompleteStat Dimensions

ModelsDimensions in Inches (mm) Height (A)Width (B)Depth CS9B(E)-THOA5.551 (141)4.192 (106)1.125 (29) CS9B(E)-THOCA5.192 (132)1.437 (36.5)

B

A

Mounting Controller

Page 4 of the Bard CompleteStat Controller user manual — NOTES _______________________________________________________________________________________
Page 4 · click to enlarge
Page 4

CompleteStat Setup at Time of Installation

Determine the following information prior to installation.

1. Degrees Scale: °F °C
2. Unit Type: A/C HP
3. Options: A/C – 1H/1C 2H/2C 1H/2C 2H/1C

HP – 1 Stage 2 Stage

4. Economizer: Yes No
5. Fan: Off Delay (seconds) Unoccupied: Auto On Occupied: Auto On
6. Humidity: Dehumidification Yes No
7. Humidity Setpoint:
8. Dehum Span:
9. Electric Strip Heat: Yes No
10. Reversing Valve: Active Htg Active Clg
11. System: Off Cool Heat Auto
12. Cool Setpoint:
13. Heat Setpoint:
14. Cool Setback:
15. Heat Setback:
16. Standby Time: Minutes
17. Motion Sensing: Daily Schedule
18. Date:
19. Time:
20. Occupied Minimum Cooling:
21. Occupied Maximum Cooling:
22. Unoccupied Minimum Cooling:
23. Unoccupied Maximum Cooling:
24. CO 2 Setpoint:
25. CO 2 Span :

NOTES

Show 4 more labels / short text on this page
______________________________________________________________________________________________ · ______________________________________________________________________________________________ · ______________________________________________________________________________________________ · ______________________________________________________________________________________________
Page 5 of the Bard CompleteStat Controller user manual — APPLICATION DEGREES: ºF UNIT_TYPE: HP OPT: 2 STAGES ADDITIONAL SETUP
Page 5 · click to enlarge
Page 5

BASIC OPERATION

BASIC SETUP

These instructions are intended to provide the basic settings to get the equipment started.

FIGURE 2 CompleteStat Buttons and Home, Overide and Configuration Screens

Bard CompleteStat Controller — BASIC SETUP diagram (page 5)
Fig. 4

MAIN MENU SYSTEM SETPOINTS DATE/TIME TECHNICIAN ABOUT

Navigate the menus and change settings by pressing a combination of the four arrow buttons and the ENTER button.

QUICK START PROGRAMMING

To select A/C or HP, stages of heating and cooling, and with/without economizer:

  • ENTER button to select and/or exit value editing
  • UP or DOWN button to move among entries
  • RIGHT or LEFT button to move among value fields
1. Press RIGHT button to access Main Menu screen.
  • LEFT button to return to the home screen
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
3. Controller will ask for password. Press UP and RIGHT buttons to enter ‘BARD’. Press ENTER button.

accessed by simply pressing the UP or DOWN buttons during normal operation, any changes made in this fashion will not be permanent but last only for a specific length of time as an “override” feature. See Setpoints on page 9 for further information.

4. Press ENTER button again to enter the APPLICATION menu (see Figure 3).

FIGURE 3 Application Menu

if inactive for “X” number of seconds (factory default is 120 seconds). See page 14 in the latest version of CompleteStat Controller Advanced Programming & Features 2100-685 for information on adjusting the inactivity setting.

APPLICATION DEGREES: ºF UNIT_TYPE: HP OPT: 2 STAGES ADDITIONAL SETUP

the upper corners (as shown in Figure 7 on page 7), additional choices can be found by continuing to press the UP or DOWN buttons.

5. Press ENTER button again to choose DEGREES.

CONFIGURED” before the controller will allow the scale to be changed (see step 7 on page 6).

System Selection

Page 6 of the Bard CompleteStat Controller user manual — ADDITIONAL SETUP VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING
Page 6 · click to enlarge
Page 6
6. Press UP or DOWN button to choose °F (Fahrenheit) or °C (Celsius). Press ENTER to save selection of scale.
3. Press ENTER button to select/save appropriate economizer option.
4. Press LEFT button to go back to ADDITIONAL SETUP.

on the home screen until the 24VAC power is cycled off and back on.

5. The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions. To access or change blower settings, press DOWN button to scroll to FAN. Press ENTER button to enter FAN SETUP (see Figure 5).
7. Press DOWN button to scroll to UNIT_TYPE. Press ENTER button.
8. Press UP or DOWN button to choose from the available system types (A/C, HP or Not Configured). Press ENTER button to select/save appropriate choice.

FIGURE 5 Fan Setup (Air Conditioner)

10. Press DOWN button to scroll to OPT. Press ENTER button.
FAN SETUP SPEEDSCONSTANT SPEED OFF DELAY (SECS): 0 UNOCC: AUTO OCC: AUTO
11. Press UP or DOWN button to choose from the following available system stages:
  • A/C – 1H/1C HP – 1 Stage
  • A/C – 2H/2C HP – 2 Stages
  • A/C – 1H/2C
  • A/C – 2H/1C
6. Press DOWN button to scroll through selections; adjust as necessary.
12. Press ENTER button to select/save appropriate model stage.
  • Speeds: Constant speed (nonadjustable)
13. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
  • Off Delay: “0” = System fan will run for specified time after call ends; 0-600 seconds in 30-second increments.

Air Conditioner Applications (see Figure 4)

  • Unocc: “ON” = System fan will run continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).

pump application information can be found in the following section.

FIGURE 4 Additional Setup (Air Conditioner)

  • Occ: “ON” = System fan will run continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).

ADDITIONAL SETUP VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING

7. Press ENTER button to save changes to FAN mode selections.
8. Press LEFT button to go back to ADDITIONAL SETUP.

Ventilation, Fan and Humidity Setup

9. Press DOWN button to scroll to HUMIDITY. Press ENTER button to enter HUMIDITY SETUP.
1. Press ENTER button to enter VENTILATION menu.
2. Press ENTER button to highlight ECON options. Press UP or DOWN button to choose from the available economizer options:
10. Press DOWN button to scroll to DEHUMIDIFICATION. Press ENTER button (see Figure 6).
  • NONE = No economizer, or standard vent package (ERV/CRV/MFAD)
11. Press ENTER button again to highlight current dehum choice (default is ENABLE).
  • EN/DIS = Economizer in system
Page 7 of the Bard CompleteStat Controller user manual — DEHUMIDIFICATION AUX HEAT: W/O LOCKOUT DELAY (MINS): 15
Page 7 · click to enlarge
Page 7

FIGURE 6 Dehumidification (Air Conditioner)

1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
DEHUMIDIFICATION DEHUMENABLE ALLOW HEATING DEHUM: YES DEHUM SETPT: 60%RH DEHUM SPAN: 5%RH
3. Controller will ask for password. Press UP and RIGHT buttons to enter ‘BARD’. Press ENTER button.
4. In the TECHNICIAN menu screen, press ENTER button to enter the APPLICATION menu.
5. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
6. Press ENTER button again to choose AUX ELECTRIC HEAT.
12. Press UP or DOWN button to toggle ENABLE/ DISABLE. Press ENTER button to select/save choice.
7. Press ENTER button again to highlight current AUX HEAT choices (see Figure 8).
13. Press DOWN button to scroll through additional DEHUMIDIFICATION screen choices:
8. Press UP or DOWN button to scroll through AUX HEAT screen choices:
  • ALLOW HTG DEHUM = Allows dehumidification in heating: YES/NO (default is YES).
  • W/O LOCKOUT = Auxiliary heat will activate regardless of compressor operation or outdoor air temperature (factory default). If W/O LOCKOUT is chosen, proceed to set delay-on time (Step 9).
  • DEHUM SETPT = Relative Humidity (RH) setpoint: 45% RH to 80% RH, 1% increments (default is 60%RH).
  • DEHUM SPAN = Amount of RH% removal allowed past setpoint: 5% to 10%, 1% increments (default is 5%RH).
  • COMP LOCKOUT = Compressor locks out below the selected outdoor air temperature. Requires optional Bard 8403-061 Outdoor Air Temperature Sensor.
14. Press ENTER button to save changes.
  • NONE = No auxiliary strip heat; controller will not energize W2. If NONE is chosen, press LEFT button to return to the home screen.
15. Press LEFT button to return to the home screen. Proceed to System Enable on page 9 to continue the setup process.
9. Press DOWN button to highlight DELAY (MINS).

Heat Pump Applications (see Figure 7)

10. Press ENTER button to highlight default DELAY minutes.

A/C application information can be found in the previous section.

11. Press UP or DOWN button to select amount of minutes desired to delay the electric heat before activation: 10-120 minutes, in 10 minute increments (factory default 15 minutes). Press ENTER button to save choice.

FIGURE 7 Additional Setup (Heat Pump)

12. Press LEFT button to return to ADDITIONAL SETUP.

ADDITIONAL SETUP AUX ELECTRIC HEAT VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING

FIGURE 8 Aux Heat Setup

DEHUMIDIFICATION AUX HEAT: W/O LOCKOUT DELAY (MINS): 15

Auxiliary Electric Heat Setup

If the heat pump selection is chosen, electric heat must be configured. These steps do not apply to air conditioners or other types of conventional heating. To configure the auxiliary heat from the home screen:

Page 8 of the Bard CompleteStat Controller user manual — ADDITIONAL SETUP AUX ELECTRIC HEAT VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING
Page 8 · click to enlarge
Page 8

If COMP LOCKOUT was chosen during the heat strip configuration process, an optional outdoor air temperature sensor will have to be installed/ configured to specifically set the temperature at which the compressor will no longer be allowed to operate. Refer to the latest version of CompleteStat Controller Advanced Programming & Features 2100-685 to configure the outdoor air temperature sensor.

  • Off Delay: “0” = System fan will run for specified time after call ends; 0-600 seconds in 30-second increments.
  • Unocc: “ON” = System fan will run continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).

To install Bard 8403-061 Outdoor Air Temperature Sensor, attach the leads to terminals “OAT” and “GND”. To set the compressor outdoor air temperature limits from the home screen:

  • Occ: “ON” = System fan will run continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).
1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
9. Press ENTER button to save changes to FAN SETUP selections.
3. In the TECHNICIAN menu screen, press UP or DOWN button to scroll to LIMITS. Press ENTER button.

FIGURE 9 Fan Setup (Heat Pump)

4. Press DOWN button to scroll to COMP OAT CLG LOW. Press ENTER button.
FAN SETUP SPEEDSCONSTANT SPEED OFF DELAY (SECS): 0 UNOCC: AUTO OCC: AUTO
5. Press UP or DOWN button to select outdoor air temperature for compressor lockout (factory default 0ºF). Press ENTER to save choice.
6. Press LEFT button to return to TECHNICIAN menu.

Ventilation, Fan and Humidity Setup

1. In the TECHNICIAN menu screen, press ENTER button to enter the APPLICATION menu.
10. Press LEFT button to go back to ADDITIONAL SETUP.
2. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
11. Press DOWN button to scroll to HUMIDITY. Press ENTER button to enter HUMIDITY SETUP.
3. Press DOWN button to scroll to VENTILATION. Press ENTER button.
12. Press ENTER button again to choose DEHUMIDIFICATION (see Figure 10).
4. Press UP or DOWN button to choose from the available economizer options:
13. Press ENTER button again to highlight current dehum choice (default is ENABLE).
  • NONE = No economizer, or standard vent package (ERV/CRV/MFAD). This is the factory default.
14. Press UP or DOWN button to toggle ENABLE/ DISABLE. Press ENTER button to select/save choice.
  • EN/DIS = Economizer in system
5. Press ENTER button to select/save appropriate economizer option.
15. Press DOWN button to scroll through additional DEHUMIDIFICATION screen choices:
6. Press LEFT button to go back to ADDITIONAL SETUP.
  • ALLOW HTG DEHUM = Allows dehumidification in heating as well as cooling: YES/NO (default is YES).
7. The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions. To access or change blower settings, press DOWN button to scroll to FAN. Press ENTER button to enter FAN SETUP (see Figure 9).
  • DEHUM SETPT = Relative Humidity (RH) setpoint: 45% RH to 80% RH, 1% increments (default is 60%RH).
  • DEHUM SPAN = Amount of RH% removal allowed past setpoint: 5% to 10%, 1% increments (default is 5%RH).
8. Press DOWN button to scroll through selections; adjust as necessary.
  • Speeds: Constant speed (nonadjustable)
16. Press ENTER button to save changes.
Page 9 of the Bard CompleteStat Controller user manual — FIGURE 13
Page 9 · click to enlarge
Page 9

FIGURE 10 Dehumidification (Heat Pump)

  • EMER HT = HP mode only.
  • OFF = HVAC system is inactive.
DEHUMIDIFICATION DEHUMENABLE ALLOW HEATING DEHUM: YES DEHUM SETPT: 60%RH DEHUM SPAN: 5%RH
  • COOLING = System is in “Cooling-Only” mode. HVAC system will cycle cooling in reference to cooling setpoint only. Unit will not activate heating sequence.
  • HEATING = System is in “Heating-Only” mode. HVAC system will cycle heating in reference to heating setpoint only. Unit will not activate cooling sequence.
4. Press ENTER button to save choice.
5. Press LEFT button to return to the home screen.
1. Press LEFT button two (2) times to return to ADDITIONAL SETUP.

FIGURE 12 System Enable

2. Press UP or DOWN buttons to scroll to VALVE (see Figure 11). NOTE: VALVE does not show up on first screen . Continuing to press the UP or DOWN button will display VALVE.

SYSTEM SYSTEM ENABLE: AUTO OCCUPANCY: SCHEDULE OCC OVRIDE (MINS): 240 SCHEDULE

3. Press ENTER button to highlight choice of ACTIVE HTG or ACTIVE CLG. Press UP or DOWN button to toggle between the choices. Press ENTER button to save choice.
4. Press LEFT button to return to the home screen.

FIGURE 11 Additional Setup (Heat Pump)

To access setpoints from the home screen:

1. Press RIGHT button to access the Main Menu screen.

ADDITIONAL SETUP VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING VALVE

2. Press DOWN button to scroll to SETPOINTS. Press ENTER button (see Figure 13). Factory default values are shown in the figure.

FIGURE 13

SETPOINTS COOL SETPT: 74°F COOL SETBACK: 80°F HEAT SETPT: 70°F HEAT SETBACK: 64°F HUMIDITY CO2 SETPT (PPM): 1200 CO2 SPAN (PPM): 200

To enable heating or cooling from the home screen:

1. Press RIGHT button to access the Main Menu screen.
2. Press ENTER button to enter the SYSTEM menu (see Figure 12).
3. Press ENTER button to choose from available SYSTEM ENABLE options (use UP or DOWN buttons to scroll through choices):
3. Press ENTER button to select COOL SETPT.
4. Press UP or DOWN buttons to enter appropriate cooling setpoint. Press ENTER button to save new cooling setpoint.
  • AUTO (factory default) = System is in “AutoChangeover” mode. HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints.
5. Press DOWN button to scroll to HEAT SETPT. Press ENTER button.
Show 4 more labels / short text on this page
Reversing Valve Setup · Setpoints · Setpoints · System Enable
Page 10 of the Bard CompleteStat Controller user manual — SYSTEM SYSTEM ENABLE: AUTO OCCUPANCY: SCHEDULE OCC OVRIDE (MINS): 240 SCHEDULE
Page 10 · click to enlarge
Page 10
6. Press UP or DOWN buttons to enter appropriate heating setpoint. Press ENTER button to save new heating setpoint.
7. Follow the steps provided above to adjust cooling and heating setback temperatures, dehum setpoint and span, and CO 2 setpoint and span of control in parts per million (if available).
8. Press LEFT button to return to the home screen.

setpoints to contradict one another, or to be within a degree of conflicting operation.

temperatures lower than 56°F or above 86°F, or humidity higher than 65%, will experience an internal Low Temperature or High Temperature alarm. This will not affect normal operation and can be cleared easily.

Bard CompleteStat should be operational at this point. For further controller enhancement or operation detail, please consult the latest edition of CompleteStat Advanced Programming & Features 2100-685.

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Bard CompleteStat Controller

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bard CompleteStat Controller

Be the first to ask — other owners or our team will answer.

Original document

Bard CompleteStat Controller manual PDF

10 pages·112 KB·Controller·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…