1158 WIRELESS EIGHT-ZONE INPUT MODULE Installation Guide

PROGRAM THE PANEL

The 1158 can be programmed with up to eight zones. When programming the 1158 in the panel, refer to the panel programming guide as needed.

Program the serial number associated with contacts 1 through 4 first. Then, start by programming contact 1.

When you enter the serial number associated with contacts 5 through 8, contact 1 displays again indicating that you are programming the first contact associated with that serial number.

Figure 11158
DMP Wireless Eight-zone Input Module (1158) — 1158 WIRELESS EIGHT-ZONE INPUT MODULE Installation Guide diagram (page 1)
Fig. 1 · 1158 WIRELESS EIGHT-ZONE INPUT MODULE Installation G…
1. In ZONE INFORMATION , enter the zone number, and then press CMD .

When a DMP panel is installed in a location with an existing non-DMP

2. Enter the ZONE NAME and press CMD .
3. Once ZONE TYPE appears, select the appropriate zone type, and then press CMD .

panel, the 1158 Wireless Eight- Zone Input Module can be used

to convert up to eight existing normally closed, hardwired zones into wireless zones. This allows the

4. At the NEXT ZONE prompt, select NO . If you see the WIRELESS ZONE prompt, select YES .

The 1158 uses two serial numbers to accommodate up to eight zones and can be powered by transferring

5. Enter the eight-digit SERIAL NUMBER and press CMD .
6. Enter the CONTACT number being used.
7. Enter the SUPERVSN TIME and press CMD .
8. At the NEXT ZONE prompt, select YES and continue to program up to seven more zones.
DMP Wireless Eight-zone Input Module (1158) — 1158 WIRELESS EIGHT-ZONE INPUT MODULE Installation Guide diagram (page 1)
Fig. 2 · 1158 WIRELESS EIGHT-ZONE INPUT MODULE Installation G…
PANELZONES XT30/XT50, XTLplus, & XTLtouchThe zone numbers begin with the 1158 address and are followed by the particular zone from the 1158. For example, an 1158 at keypad address 4 would provide zones 41, 42, 43, and 44. XR150Zone numbers are valid from 500599. Zones must still be programmed sequentially (i.e. 551, 552, 553, and 554). XR550Zone numbers are valid from 500999. Zones must still be programmed sequentially (i.e. 551, 552, 553, and 554).
  • All DMP 1100 Series Wireless Receivers and burglary panels
Page 2 of the DMP Wireless Eight-zone Input Module (1158) user manual — 2 1158 INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS
Page 2 · click to enlarge
Page 2

MOUNT THE 1158

Place the 1158 close to the existing non-DMP panel.

With the housing cover removed, use the supplied screws to secure the 1158 to a wall or other flat surface. Use the built-in holes on the PCB to screw the housing base onto a surface without removing the PCB. See Figure 2.

DMP Wireless Eight-zone Input Module (1158) — MOUNT THE 1158 diagram (page 2)
Fig. 3
Figure 21158 Mounting Hole Locations

WIRE THE 1158 ZONES

Wire the contacts and connect the receiver before connecting power to the 1158.

1. Locate the existing normally closed contacts you would like to connect to the 1158. These contacts should be within 2,500 feet of the 1158.
2. Use the existing wire to connect a contact to a zone terminal and a ground (GND) terminal. See Figure 2.
3. Repeat step 2 for the remaining contacts, as needed.
4. Connect the positive and negative DC OUTPUT terminals on the 1158 to any devices that require separate power, if necessary.

2 1158 INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS

Show 4 more labels / short text on this page
Mounting Hole · Mounting · Mounting Hole · Hole
Page 3 of the DMP Wireless Eight-zone Input Module (1158) user manual — 1158 INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS 3
Page 3 · click to enlarge
Page 3

POWER THE 1158

The 1158 can be powered by either AC or DC power sources. Follow the instructions below to transfer AC power from an existing panel or connect an AC transformer, DC transformer, or backup battery to the 1158.

Option AConnect AC Power

To power the 1158, you can transfer AC power from the existing panel to the 1158. You can also use a DMP Model 321 40 VA, 16.5 VAC Plug-In Transformer to power to 1158. If a backup battery is attached to the existing panel, it can be transfered to the 1158 as well. Use 18-22 gauge wire for all wiring connections.

1. Connect the 1158’s AC power terminals to the existing panel’s 16.5 VAC power supply. See Figure 3.
2. Ensuring that polarity is correct, connect the positive and negative BAT terminals on the 1158 to the existing panel’s backup battery, if necessary. The battery charging circuit supplies up to 50 mA.
3. Snap the housing cover into place.
Option BConnect DC Power

You can also use a 376L 12 VDC 600 mA Plug-in Power Supply or other 12 VDC power source with the 1158.

1. Connect the 376L flying leads to the BAT terminals on the 1158. See Figure 3.
2. Plug the 376L into a standard electrical outlet.
DMP Wireless Eight-zone Input Module (1158) — POWER THE 1158 diagram (page 3)
Fig. 4

tery or 12 VDC

Figure 31158 Zone and Power Wiring

1158 INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS 3

To Backup Bat- · To Zones · Power

Page 4 of the DMP Wireless Eight-zone Input Module (1158) user manual — POWER THE 1158
Page 4 · click to enlarge
Page 4

FCC INFORMATION This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

1. This device may not cause harmful interference, and 2. this device must accept any interference received, including interference that may cause undesired operation.

The antenna used for this transmitter must be installed to provide a separation distance of at least 20 cm (7.874 in.) from all persons. It must not be located or operated in conjunction with any other antenna or transmitter.

Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

1. Reorient or relocate the receiving antenna. 2. Increase the separation between the equipment and receiver. 3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. 4. Consult the dealer or an experienced radio/TV technician for help. INDUSTRY CANADA INFORMATION

This device complies with Industry Canada Licence-exempt RSS standards. Operation is subject to the following two conditions:

1. This device may not cause interference, and 2. this device must accept any interference, including interference that may cause undesired operation of the device.

This system has been evaluated for RF Exposure per RSS-102 and is in compliance with the limits specified by Health Canada Safety Code 6. The system must be installed at a minimum separation distance from the antenna to a general bystander of 7.87 inches (20 cm) to maintain compliance with the General Population limits.

Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:

1. l’appareil ne doit pas produire de brouillage, et 2. l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.

L’exposition aux radiofréquences de ce système a été évaluée selon la norme RSS-102 et est jugée conforme aux limites établies par le Code de sécurité 6 de Santé Canada. Le système doit être installé à une distance minimale de 7.87 pouces (20 cm) séparant l’antenne d’une personne présente en conformité avec les limites permises d’exposition du grand public.

DMP Wireless Eight-zone Input Module (1158) — POWER THE 1158 diagram (page 4)
Fig. 5

XT30 panels with 1100D Series Wireless Receiver with Version

XT50 panels with integrated wireless receiver or 1100D Series

Dimensions 4.65” L x 3.10” W x 1.40” H 11.81 L x 7.87 W x 3.56 H cm

Designed, engineered, and manufactured in Springfield, MO using U.S. and global components.

  • I N T R U S I O N
  • F I R E
  • A C C E S S
  • N E T W O R K S

Ask about the DMP Wireless Eight-zone Input Module (1158)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the DMP Wireless Eight-zone Input Module (1158)

Be the first to ask — other owners or our team will answer.

Original document

DMP Wireless Eight-zone Input Module (1158) manual PDF

4 pages·129 KB·Communications·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…