DMP Access Control Module (734)

2 pages·95 KB·PDF·ENDEFRITNLJA
DMP Access Control Module (734)
Table of Contents 27 sections 734 Access Control Module Quick Start Guide · Full Installation and Programming Guide · Step 1: Mount the 734 · 2. Insert the included screws in the desired mounting hole locations · … ShowHide
Page 1 of the DMP Access Control Module (734) user manual — Figure 2: Typical Door Strike Wiring Step 3: Wire the 734
Page 1 · click to enlarge
Page 1

734 Access Control Module Quick Start Guide

This quick start guide walks you through installing the access control module.

Full Installation and Programming Guide

To view the full 734 Access Control Module Installation and Programming Guide, scan this QR code

or visit DMP.com.

DMP Access Control Module (734) — Full Installation and Programming Guide diagram (page 1)
Fig. 1 · Full Installation and Programming Guide

1 2 3 4 5 6 7 8 10 11 12 13 14 9

LC AS REDWHTGRN BLK Z1 Z2 Z3 Z4+ Z4– RA GND GND

To Panel Keypad Bus or AX-Bus

PROG RED KYPD OUT DATA XMT LED WIEGAND READ LED RELAY

Step 1: Mount the 734

The back and ends of the 734 housing have wire entrances. The back also contains multiple mounting holes that allow

you to mount the module on a single‑gang switch box. DMP recommends mounting the 734 near the protected door.

1. Remove the PCB from the plastic housing by loosening the clips on

one side and gently lifting it out of the housing base.

2. Insert the included screws in the desired mounting hole locations

and tighten them to secure the housing to the surface.

Model 333 Suppressor – +

12/24 VDC Power Supply

3. Reinstall the PCB in the housing base.

Mag lock negative to power supply negative Figure 1: Typical Magnetic Lock Wiring

Step 2: Wire the Access Control Lock

The Form C relay draws up to 35 mA of current and contacts are rated for

10 Amps (resistive) at 12/24 VDC. When connecting multiple locks to the

Form C relay, the total current for all locks cannot exceed 10 Amps. The

three relay terminals marked NO C NC allow you to connect the device

wiring to the relay for module control. Use an additional power supply to

Model 333 Suppressor – +

12/24 VDC Power Supply

power magnetic locks and door strikes.

Door strike negative to power supply negative

Figure 2: Typical Door Strike Wiring Step 3: Wire the 734

KYPD IN (Keypad In): Receives and transmits data to the panel Keypad bus/AX‑Bus.

KYPD OUT (Keypad Out)Receives and transmits data out to other keypad(s) or module(s). Install a dual‑connector

harness to allow connection to other devices up to the maximum number of devices supported.

Show 23 more labels / short text on this page
Status Indicator · Reader · Inputs · Outputs Zones · Address DIP · Switches · Door Relay · Terminal · Indicator · LEDs · Normally Closed · Power supply positive · Mag lock positive · to Terminal C · to Terminal NC · Magnetic Door · Lock · Normally Open · Power supply positive · to Terminal C · Door strike positive · to Terminal NO · DC Door Strike
Page 2 of the DMP Access Control Module (734) user manual — 2500 North Partnership Boulevard Springfield, Missouri 65803‑8877 Domestic: 800.641.4282 | International: 417.831.9362
Page 2 · click to enlarge
Page 2

Step 4: Isolation Relay (Optional)

The Form C relay can control a device that draws less than 10 Amps of current. If a device draws more than 10 Amps of

current, or the sum of all devices controlled by the Form C relay exceeds 10 Amps, an isolation relay must be used.

NO C NC

Step 5: Install the 333 Suppressor

Use the included 333 suppressor with the 734 to suppress any surges caused by

RED

YEL GRN

energizing a magnetic lock or door strike. Install the 333 across the module’s C

DATA XMT LED RELAY

ON

WIEGAND READ LED

(common) and NO (normally open) or NC (normally closed) terminals.

If the device being controlled by the relay is connected to the NO and C terminals,

install the suppressor on the NO and C terminals. Conversely, if the device is connected

to the NC and C terminals, install the 333 Suppressor on NC and C terminals.

Figure 3: 333 Suppressor

Step 6: Wire the Zone Terminals

Installation on the 734

Terminals 8 through 12 connect grounded zones 1 through 3. These zones have a grounded side and cannot be used for

fire‑initiating devices. Zones 2 and 3 can also be used for access control with zone 2 providing a bypass feature and zone

3 providing request to exit functionality. Terminals 13 and 14 connect to zone 4. Zone 4 provides a non‑powered Class B

ungrounded zone suitable for connection to fire devices such as heat detectors or pull stations.

zone 4. The panel does not drop power to the Keypad Bus or AX‑Bus when a Sensor Reset is performed.

Use the supplied 311 1k Ohm End‑of‑Line (EOL) resistors on each zone. Refer to the panel programming guide for

programming instructions

Step 7: Connect a Card Reader

The 734 provides direct 12/24 VDC output to the reader on the RED terminal connection.

Wiegand Card Reader

The green wire carries Data Zero (D0), and the white wire carries Data One (D1). The red wire connects 12/24 VDC and

the black wire is ground.

OSDP Card Reader

For data transmission, connect the A (485 –) wire to the GRN terminal and the B (485 +) wire to the WHT terminal. For

reader power, connect the red (DC +) wire to the RED terminal and the black (DC –) wire to the BLK terminal.

Step 8: Set the 734 Address

To set the 734 address, move the DIP switches on the PCB to the appropriate positions. For complete address

instructions, scan the QR code at the beginning of the document.

Step 9: Connect the Power Supply

Power for the 734 can be provided by a 12 or 24 VDC power supply. The 12 VDC power can be provided by the panel

keypad bus or from a separate power supply. The 24 VDC power supply can be connected directly to the relay terminal

block (J1).

to the module.

Step 10: Program the Panel and 734

For all programming instructions, scan the QR code at the beginning of the document or refer to the appropriate panel

guide.

Designed, engineered, and manufactured in Springfield, MO using U.S. and global components.

  • I N T R U S I O N
  • F I R E
  • A C C E S S
  • N E T W O R K S

2500 North Partnership Boulevard Springfield, Missouri 65803‑8877 Domestic: 800.641.4282 | International: 417.831.9362

LT-2612 22165

DMP.com

Model 333 Suppressor · © 2022

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the DMP Access Control Module (734)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the DMP Access Control Module (734)

Be the first to ask — other owners or our team will answer.

Original document

DMP Access Control Module (734) manual PDF

2 pages·95 KB·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…