MOUNT ENCLOSURE THIS END UP. DO NOT BLOCK PERFORATED VENT HOLES.

405 Barclay Boulevard Lincolnshire, Illinois 60069 Tel: +1 847 955 8200 Toll free: +1 800 538 0363 Fax: +1 847 955 8208 detectgas@honeywell.com 18394 VLF7LPA 07/2016 REV H
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 1


The Manning Systems VL-F7-LPA Vent Line Sensor has a solid-state sensor imbedded in a 2" forged steel bull plug. A NEMA 4, 16 gauge steel box is fastened to the bull plug and houses a terminal strip. This is then wired to the current pre-amp which transmits a linear 4/20 mA signal to the readout equipment.

The standard trip points are normally in the 5,000 ppm to 10,000 ppm range. Manning Systems highly recommends that trip points be in this range due to the fact that minute amounts of a refrigerant released in the very small volume of a relief header will cause very high gas concentrations, normally in the percent range. Trying to have lower setpoints almost always results in false trips.
The solid-state sensor used in this design must be considered “broad-spectrum,” i.e., it will detect many gases. Normally this is not a problem due to the higher setpoints commonly used.
2" N.P.T. pipe plug
7/8" diameter hole for 1/2" conduit electrical connection
The VL-F7-LPA Vent Line Sensor should only be used in non-hazardous locations. Explosion-proof designs are not available at this time.

The sensors normally exhibit long life (five to eight years) unless exposed to very high gas concentrations for long periods or immersed in liquid refrigerant.
MOUNT ENCLOSURE THIS END UP. DO NOT BLOCK PERFORATED VENT HOLES.
Proper location in mounting the vent line sensor is the key to long and trouble-free life. Carefully review the mounting instruction portion of this manual.
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 3

Range:
Output: Linear 4/20 mA – connects to all Manning Systems readouts or other devices capable of accepting a 4/20 mA signal
Power Requirements: Powered directly from Manning Systems readouts or, when used as 4/20 mA pre-amp and sensor only, requires 17/24 VDC at 200 mA
Enclosures:
Weight:
Dimensions:
Cable Requirements:
Specifications subject to change without notice.
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 4

A Locating the VL-F7-LPA
B Mounting the VL-F7-LPA
in a Vent Line System
in a Relief System Venting Directly into a Water Tank
Discharging to atmosphere, vent line sensors must be mounted within one or two feet from discharge into the air.
Due to numerous code requirements a common practice is to plumb vent line systems to discharge directly into a water tank. Even though this seems like a very simple and safe way to protect from atmospheric discharge, it presents some unique challenges to the refrigeration designer in assuring a safe relief system. It also presents challenges in where to mount the vent line sensor.
Over 95% of all problems experienced with the VL Vent Line Sensor have been due to mounting the sensor away from the discharge, usually lower into the system, below the roof line. In this lower area you will encounter residual oil from previous releases, bacterial action due to moisture and heat, pipe coating residuals and minute relief valve weeping. All this action is additive and is a sure cause for trouble.
The vent line sensor was developed over the years for monitoring atmospheric discharge of vent lines. When properly mounted as described in Section A, it is an extremely reliable method of detecting releases to the atmosphere.
See Figure 2 which shows where to mount the vent line sensor. Important mounting considerations:

Make sure discharge does not hit the vent line sensor housing
25' max between sensor and pre-amp Mount pre-amp for easy access
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 5

The advent of the water dump tank utilizing a standard water level covering the relief header discharge presents the vent line sensor with some unique challenges. There are several possible mounting locations as follows:
The purge air will cause a small pressure to build due to the water “head” of the tank. A water head of 15 feet to 20 feet will cause the sensor to be 30 to 40 percent less sensitive due to the higher air pressure. This is normally not a problem due to the high refrigerant concentrations needed for a trip condition (see Figure 4).
In summary, if at all possible mount the vent line sensor on the tank atmospheric vent and utilize a water monitoring method such as pH in the water tank.


Suggest removing 3/4" plug to allow ventilation across sensor to minimize water condensation
Tie in at lowest point
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 6
Water purge tank

C Wiring
conduit and dripping into the sensor enclosure. Silicone should not be used near the sensor, because silicone can damage the sensor.
Figure 5 presents wiring information for the VL-F7-LPA.
Electrical wiring must comply with all applicable codes. Plant equipment that may be involved and operating conditions should be discussed with local operating personnel to determine if any special needs should be taken into account.
Make drip loops for cables going into sensor housings. Follow the mounting instructions on the Pre-Amp enclosure (…This End Up). See Figure 2.
Electrical Power: 24 VDC regulated, 300 mA.
Nearly all start-up problems are due to improper wiring or monitor configuration. Please follow these guidelines carefully.
Output: Linear 4/20 mA output corresponding to 0–1%. Monitoring equipment may have a maximum input impedance of 250 ohms.
Between the current pre-amp and monitoring equipment use three conductor, #18 AWG, insulated, stranded, shielded copper cable. Between the vent line sensor and current pre-amp use #16 AWG, four conductors, non- shielded.
Cable Recommendation, Pre-Amp to Monitoring Device: #18/3 shielded cable (Belden #8770 or equivalent). Length of cable to pre-amp should be no greater than 1,500 feet. Use only the existing punched holes for connections to the pre-amp.
Do not pull sensor wiring with AC power cables. This will cause electrical interference. Be sure there are no breaks or splices in sensor wiring runs. If cable runs cannot be made without a splice, all connections must be soldered. Soldering should be done using a rosin flux to tie the connecting ends of sensor wires to ensure a positive and long-lasting contact.
Cable Recommendation, Vent Line Sensor to Pre-Amp: #16 AWG, 4 conductors non-shielded. Length of cable from vent line sensor to pre-amp should be no greater than 25 feet. Use only the existing punched holes for connections to the pre-amp.
Monitoring: The VL-F7-LPA Sensor may be monitored by the Manning Systems GM-10, GM-4, GM-1, GM-JR or other appropriately configured system. Monitoring equipment must be configured to indicate a fault if the signal is below 1.5 mA.
Ground the shield at the main control panel. Tape all exposed shield wire at the sensor to insulate it from the enclosure.
All penetrations into a refrigerated room should be sealed to prevent condensate from forming in the
A signal above 20 mA must be considered a high gas concentration.

White— Connects to signal input of monitoring equipment
Junction box may be rotated 1/2 turn either direction relative to pipe plug to align conduit hole as required to facilitate electrical connection
Red— Connects to 24 VDC power supply positive side (300 mA)
Black— Connects to power supply ground side
7/8" Diameter hole for 1/2" conduit electrical connection. Conduit hole should always be mounted pointing down
O-Ring seal gasket for CEMA/NEMA 4 applications
Bare— Connects to case ground of monitoring equipment (earth ground)
1500' maximum— 3-conductor #18 AWG shielded (Belden #8770 or equivalent)
25' maximum— 16 AWG, 4 conductors, non-shielded
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 7
Existing sensor wires

A Start-Up Procedures
Zero Calibration: After the unit is installed and has been powered up for a minimum of 24 hours, the unit should be zero calibrated by the following:
Before applying power, make a final check of all wiring for continuity, shorts, grounds, etc. It is usually best to disconnect external alarms and other equipment from the sensor until the initial start-up procedures are completed.
After power-up, allow 24 hours for the system to stabilize before testing the sensors. Because sensors are normally located at a distance from the main unit, the test time required and accuracy of the response checks will be improved if two people perform the start-up procedures and use radio contact.
Span Calibration: The unit is factory calibrated and normally does not need to be spanned. Do not adjust the span pot without certified calibration gas! If span adjustment is required, the following procedure will span the unit:
Calibration kits are available from Manning Systems.
Calibration of vent line sensors is normally done in the field by using the simple method described under “Start- Up Procedures” where the sensor is challenged with a gas and the proper outputs and trips are observed. (The challenge gas must cause a proper alarm trip.)
In a vent line the recommended trip point level is approximately 17 mA. Lower setpoints can result in false trips. Never set alarm points higher than 20 mA.
Either of the above methods will work for the ammonia or halocarbon vent line sensor as they both use broad- spectrum sensors.
If certified gas samples are required, contact Manning Systems for gases available and to discuss techniques in calibration depending on how the vent line sensor is mounted.
Each Vent Line Sensor has been factory tested with a calibrated gas sample. Information is noted on the data sheet provided with each sensor.
Due to environmental differences and background gases, the installed clean air signal may be different than it was during factory calibration. This difference can be zeroed out.
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 8

C Troubleshooting
A high signal can also be caused by lack of oxygen if the sensor is located more than two feet from the atmos- pheric discharge. See the mounting instructions for proper mounting techniques.
The greatest probability for trouble is reversed or incorrect wiring. Always be consistent with color codes and double-check terminal screw tightness.
Contact Manning Systems for more details if you cannot identify the problem.
If sensor output is 0.5 mA: The vent line pre-amp continuously monitors the status of the sensor and, if fault conditions arise, the red FLT LED in the pre-amp will light (see Figure 6). After a short time delay, the pre-amp will output a signal of 0.5 mA. Monitoring equipment must be configured to indicate a fault if the signal is less than 1.5 mA.
Manning Systems recommends that as a minimum each sensor be challenged with a gas sample once each six (6) months.
Also, the signal being sent by the sensor should be logged on a monthly basis.
First, check for proper color codes or loose wires to sensors labelled “O O R R” on both the pre-amp and vent line sensor.
During the gas challenge test, all alarm outputs should be confirmed and logged to insure system integrity.
Second, if the FLT LED is lit continuously, remove the Vent Line Sensor junction box cover (see Figure 5). With power off, measure the resistance across the “RR” (Red Red) terminals which should be approximately 30 ohms. If this is an open circuit, a replacement sensor is required. Contact Manning Systems. If the FLT LED is flashing, this indicates a faulty sensor. Contact Manning Systems for a replacement sensor.
For replacement parts, contact Manning Systems, Inc. Be sure to give serial number of unit.
If the sensor output is 0 mA: First, verify +24 VDC at the sensor terminal block (see Figure 6, Note 2).
MANNING SYSTEMS, INC.
REV 0
Second, check voltage between Test– and Test+ (see Figure 6, Note 1). Voltage should be in the range of 40 mV to 200 mV corresponding to an actual current flow of 4 to 20 mA. If this voltage is 0 mV, the signal has no path to ground. Check monitoring equipment connections and configuration. Input impedance must be 250 ohms or less.
SPAN
ZERO
Black - Red +
TEST +
If sensor output indicates a gas concentration when the vent line appears clean: Remove the 3/4" vent plug bushing carefully and you should observe a signal decrease. Weeping pressure relief valves could be the problem. Remove the full 2" plug for greater ventilation. Always do the testing at the sensor with special caution as all vent line systems could discharge at any time. Always be prepared and wear appropriate protective gear such as a face shield and gloves.
40 TO 200 MVDC SHD
TEST –
VDC
GND
SIG
O
O
R
R
12 TO 24 VDC
Black - Red +
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 02/2005 REVF Copyright © 2005 Manning Systems, Inc. All Rights Reserved. 9

1. Limited Warranty Honeywell Analytics, Inc. (”Honeywell”) warrants to the original purchaser and/or ultimate customer (”Purchaser”) of Honeywell’s products (”Product”) that if any part thereof proves to be defective in material or workmanship withing eighteen months of the date of shipment by Honeywell or twelve months from the date of first use by the purchaser, whichever comes first, such defective part will be repaired or replaced, free of charge, at Honeywell’s discretion if shipped prepaid to Honeywell Analytics at 405 Barclay Boulevard, Lincolnshire, Illinois 60069, in a package equal to or in the original container. The Product will be returned freight prepaid and repaired or replaced if it is determined by Honeywell that the part failed due to defective materials or workmanship. The repair or replacement of any such defective part shall be Honeywell’s sole and exclusive responsibility and liability under the limited warranty.
5. Limitation of Liability IT IS UNDERSTOOD AND AGREED THAT HONEYWELL’S LIABILITY, WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE PURCHASE PRICE PAID BY THE PURCHASER FOR THE PRODUCT AND UNDER NO CIRCUMSTANCES SHALL HONEYWELL BE LIABLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE PRODUCT IS A CONSIDERATION LIMITING HONEYWELL’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS UNDER THIS WARRANTY MAY BE BROUGHT BY THE PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS OCCURRED.
A. If gas sensors are part of the Product, the gas sensor is covered by a twelve month limited warranty of the manufacturer. B. If gas sensors are covered by this limited warranty, the gas sensor is subject to inspection by Honeywell for extended exposure to excessive gas concentrations if a claim by the Purchaser is made under this limited warranty. Should such inspection indicate that the gas sensor has been expended rather than failed prematurely, this limited warranty shall not apply to the Product. C. This limited warranty does not cover consumable items such as batteries or items subject to wear or periodic replacement including lamps, fuses, valves, vanes, sensor elements, cartridges, or filter elements.
Manning VL-F7-LPA Gas Sensor 18394 VLF7LPA 07/2016 REVH 10