EN
APC logo
Official user manual

APC Back-UPS

12 pages·490 KB·Uninterruptible Power Supply·PDF·ENDEFRITNLJA
APC Back-UPS
Table of Contents 26 sections Safety and General Information · Package Content · Connect the Battery · Connect Equipment · … ShowHide
Page 1 of the APC Back-UPS user manual — Package Content
Page 1 · click to enlarge
Page 1
APC Back-UPS — Safety and General Information diagram (page 1)
Fig. 1 · Safety and General Information

Safety and General Information

SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damages.

APC Back-UPS — Safety and General Information diagram (page 1)
Fig. 2 · Safety and General Information
  • This UPS is for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or high humidity.
  • Connect the UPS power cable directly to a wall outlet.
  • The socket outlet should be installed near the equipment and should be easily accessible.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. Failure to follow these instructions will result in death or serious injury.

Package Content

APC Back-UPS — Package Content diagram (page 1)
Fig. 3 · Package Content
Page 2 of the APC Back-UPS user manual — Connect the Battery
Page 2 · click to enlarge
Page 2

Connect the Battery

The Back-UPS is shipped with one battery cable disconnected.

APC Back-UPS — Connect the Battery diagram (page 2)
Fig. 4 · Connect the Battery

Remove the “Stop! Connect the Battery” label that covers the outlets

The battery connector is located on the underside of the unit.

APC Back-UPS — Connect the Battery diagram (page 2)
Fig. 5 · Connect the Battery

Pull up the battery connector handle. Turn the battery connector to a 90-degree upright position and push it into the unit. Specifications

ModelBVN650M1 BVN650M1-CABVN900M1 BVN900M1-CA InputVoltage120 Vac Nominal Frequency50/60 Hz ± 5Hz auto-sensing Brownout Transfer92 Vac Typical Over-voltage Transfer139 Vac Typical OutputUPS Capacity650 VA / 360 W900 VA / 480 W No. of Outlets79 Battery Backup/Surge Outlets5 / 26 / 3 Voltage – Normal Mode120 Vac Voltage – On Battery115 Vac ± 8% Frequency – On Battery50/60 Hz ± 1Hz Transfer Time6ms typical, 10ms max. USB Port*Charging Current2.1A Charger CompatibilityApple MFi 2.1A *Power output is dependent power drawn by the connected device. Check your device manufacturer to understand maximum charging current for a given USB spec. Protection and FilteringEMI/RFI FilterFull time AC Input Circuit Breaker7A, 125 Vac/250 Vac10A, 125 Vac/250 Vac

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 3 of the APC Back-UPS user manual — BVN900M1 BVN900M1-CA
Page 3 · click to enlarge
Page 3
ModelBVN650M1 BVN650M1-CABVN900M1 BVN900M1-CA BatteryType (maintenance-free)12V, 6AH lead acid12V, 9AH lead acid Average Life3 - 5 years, the number of discharge cycles, poor quality AC power, environmental temperature and humidity may shorten the battery lifetime Charging Time6~8 hours recover to 90% capacity PhysicalNet Weight6.8 lb (3.1 kg)8.4 lb (3.8 kg) Dimensions, LxWxH10.79 in x 4.13 in x 5.52 in 27.4 cm x 10.5 cm x 14.02 cm12.87 in x 4.13 in x 5.52 in 32.7 cm x 10.5 cm x 14.02 cm Shipping weight7.9 lb (3.6 kg)9.9 lb (4.53 kg) Shipping dimensions, LxWxH13.5 in x 5.67 in x 8.7 in 34.3 cm x 14.4 cm x 22.1 cm15.35 in x 6.18 in x 8.7 in 39 cm x 15.7 cm x 22.1 cm Operating Temperature32º F to 104º F (0º C to 40º C) Storage Temperature5º F to 113º F (–15º C to 45º C) Operating Relative Humidity0 to 90% non-condensing humidity Operating Elevation0 to 6,561.7 ft (0 to 2000 m) IP RatingIP20

Connect Equipment

Battery Backup + Surge

APC Back-UPS — Connect Equipment diagram (page 3)
Fig. 6 · Connect Equipment

BVN650M1 BVN650M1-CA

POWER

Battery Backup + Surge

BVN900M1 BVN900M1-CA

POWER

FeatureFunctionSuggested Use Battery Backup + Surge Protection Outlets• Receive power from the battery for a limited period of time when a power outage, or brownout condition occurs. • Provide protection from power surges or spikes.Connect a computer, monitor and other critical peripheral devices that need to remain on during power outages or AC problems. Surge Protection Outlets• Provide protection from power surges or spikes.Connect non-critical peripheral devices (such as printer, scanner, etc.) that do not need to remain on during power outages or AC problems.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Show 16 more labels / short text on this page
Surge Protection · Outlets · Protection Outlets · Circuit Breaker · USB Charger Port · Surge Protection · Building · Button · Outlets · AC Power · Wiring · Protection Outlets · Inlet · Fault · USB Charger Port · Button
Page 4 of the APC Back-UPS user manual — Quick Mute
Page 4 · click to enlarge
Page 4

Turn On the Back-UPS

Press the POWER button. It will illuminate green and a single short beep indicating that the Back-UPS is on and providing protection for connected equipment. The Back-UPS battery will charge regardless of whether the Back-UPS is switched on or off as long as it is connected to AC power. The UPS will have full runtime capability after the initial 24-hour charging period, connected to AC power. If the red Building Wiring Fault indicator (located on the end near the power cord) is lit, your building wiring may present a shock hazard that should be corrected by a qualified electrician.

Quick Mute

The Back-UPS is able to temporarily mute user correctable alarms such as On Battery. During such alarms, a short press (less than 2 seconds) of the POWER button will temporarily mute the alarm until the condition has been reset. A short double beep will confirm that Quick Mute has been activated. Pressing the POWER button for more than 2 seconds will turn off the UPS. Other critical events such as Battery replacement and Charger notification can not be temporarily muted. The unit in these cases must be turned off. On Battery Indicator Modes

With the UPS turned on, configuring the On Battery Indicator modes below is done by holding down the POWER button and waiting for the third beep. At the third beep, the POWER button will cycle red / green. Release the POWER button and its color will indicate the mode the UPS is in. Press the POWER button to cycle through each mode. See the following table for the 3 mode selection colors. Once the mode has been selected, wait 5 seconds and the setting will be committed to the UPS.

ModeVisual IndicatorAudible IndicatorMode Selection Color Quiet Alarm (default)The POWER button is solid green and flashes twice every 2 seconds until Low Battery notification where it will flash green in rapid succession.No alarm until Low Battery notification where the alarm beeps twice every 30 secondsFlashing green No AlarmNo alarm while the UPS is On BatteryFlashing red Full AlarmAlarm sounds 4 beeps every 30 seconds until Low Battery notification where the alarm beeps every half second. As the UPS shuts down, it sounds one beep every 4 secondsFlashing amber

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 5 of the APC Back-UPS user manual — Voltage Sensitivity Adjustment
Page 5 · click to enlarge
Page 5

Voltage Sensitivity Adjustment

The Back-UPS detects and reacts to line voltage distortions by transferring to battery backup power to protect connected equipment. In situations where either the Back- UPS or the connected equipment is too sensitive for the input voltage level it is necessary to adjust the transfer voltage.

1. Turn off the UPS while connected to a wall outlet. 2. Press and hold the ON/OFF button for 10 seconds. The POWER button will alternate green- red to indicate that the Back-UPS is in Program mode. 3. The POWER button will flash either green, amber, or red to indicate the current sensitivity level. Refer to the table for an explanation of the transfer voltage sensitivity levels. 4. To exit Program mode wait five seconds and all LED indicators will extinguish. Program mode is no longer active.

LED FlashesSensitivity SettingInput Voltage Range (AC Operation)Recommended Use GreenLOW88 Vac to 142 VacUse this setting with equipment that is less sensitive to fluctuations in voltage or waveform distortions. RedMEDIUM92 Vac to 139 VacFactory default setting. Use this setting under normal conditions. AmberHIGH96 Vac to 136 VacUse this setting when connected equipment is sensitive to voltage and waveform fluctuations.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 6 of the APC Back-UPS user manual — Status Indicators
Page 6 · click to enlarge
Page 6

Status Indicators

StatusPower Button illuminationAudible Indicator OnAudible Indicator Terminates Power On The Back-UPS is supplying AC power to connected equipment.Solid greenNoneN/A On Battery Back-UPS supplying battery power to battery backup outlets.Solid green and flashes twice every 2 seconds.The audible alarm depends on the On Battery Indicator mode setting. See the On Battery Indicator Modes section for full details.- Using Quick Mute. - Beeping stops when AC power is restored or the Back-UPS is turned off. Applies only to modes where the on battery alarm is audible. Low Battery notification The Back-UPS is supplying battery power to the battery backup outlets and the battery is near a total discharge state.Flashes green in rapid succession. Low Battery shutdown The battery has been completely discharged while the Back-UPS is on battery, the UPS will shut down.None- AC power is restored. - AC is not restored within 32 seconds - The Back-UPS is turned off. Sleep Mode The UPS has shut down and will “awaken” once AC power is restored.NoneNoneN/A Replace Battery • The battery is disconnected. • The battery needs to be charged, or replaced.• Alternates green-red• Constant tone- Back-UPS is turned off. - If battery is disconnected, unplug the Back-UPS from AC source and then turn it off. Refer to the section “Connect the Battery” on page 2. - If battery needs replacement, refer to the section “Battery Replacement” on page 8 for details. Detected Overload An overload condition has occurred in one or more of the battery backup outlets while operating on battery power.Green-red alternately flashingBeeping (every 0.5 second)N/A Overload Shutdown An overload condition has occurred in one or more of the battery backup outlets while the Back-UPS is operating on AC power.NoneConstant toneIf overload occurs in line mode, Back-UPS will enter fault mode. If overload occurs in battery mode, Back-UPS can be turned off.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 7 of the APC Back-UPS user manual — Troubleshooting
Page 7 · click to enlarge
Page 7

Troubleshooting

Problem and Possible Cause Solution The Back-UPS will not turn on. The Back-UPS is not connected to AC power, there is no AC power available at the wall outlet, or the AC power is experiencing a brownout or over voltage condition.

  • Make sure the power cord is securely connected to the wall outlet, and that there is AC power available from the wall outlet. Where applicable, check that the wall outlet is switched on. The Back-UPS is on, the POWER button alternated green-red and the unit emits a constant tone
  • The battery is disconnected.
  • The battery is near the end of useful life and should be replaced.
A Back-UPS overload condition has occurred.Remove all nonessential equipment connected to the outlets. One at a time reconnect equipment to the BackUPS. Charge the battery for 24 hours to make sure it is fully charged. If the overload condition still occurs, replace the battery. The Back-UPS battery is completely dischargedConnect the Back-UPS to AC power and allow the battery to recharge for eight hours. Connected equipment does not accept the stepapproximated sine waveform from the BackUPS.The output waveform is intended for computers and peripheral devices. It is not intended for use with motor driven equipment. The Back-UPS may require service.Contact SEIT Technical Support for more solutions.

The Back-UPS is operating normally on battery power. At this point the user should save all open files, and shutdown the computer. When AC power is restored the battery will recharge. The POWER button flashes green in rapid succession. The Back-UPS battery has approximately two minutes of remaining runtime.

The battery is near a total discharge state. The user should save all open files, and shutdown the computer. When AC power is restored the battery will recharge. The Building Wiring Fault LED is red The building wiring presents a shock hazard that must be corrected by a qualified electrical.

Do not operate the Back-UPS. Call a qualified electrician to correct the building wiring fault.

  • The Back-UPS has an inadequate battery runtime
  • The battery is not fully charged.
  • The battery is near the end of useful life and should be replaced.

Leave the Back-UPS connected to AC power for eight hours while the battery charges to full capacity. As a battery ages, the runtime capability decreases. See Troubleshooting to order replacement batteries. The alarm is on with a constant tone; outlets are normal but POWER button is not bright. The UPS is on AC power but the power of the connected equipment exceeds the rated power of the UPS. If a power disruption is to occur at any moment the UPS may not be able to power the connected equipment. Power to the outlets will be uninterrupted as long as AC power is present.

Disconnect devices from the UPS until the load is less than the rated output of the UPS.

The alarm is beeping (every 0.5 second) and POWER button is flashing. The UPS have over temperature on battery mode.

Save all open files, and shut down the computer. When AC power is restored, the battery will recharge. The alarm is on with a constant tone and the UPS is off. The UPS was on battery and the connected load exceeded the rated load of the UPS.

Turn off the UPS. Disconnect all devices. Turn on the UPS and reconnect the devices one at a time.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 8 of the APC Back-UPS user manual — Service
Page 8 · click to enlarge
Page 8

Wall Mount Installation

  • Horizontal installation, use 2 screws 7.63” (194 mm) apart for BVN650M1/ BVN650M1-CA and 9.45” (240 mm) apart for BVN900M1/BVN900M1-CA.
  • Allow 5/16” (8 mm), of the screw to protrude from the wall.
APC Back-UPS — Wall Mount Installation diagram (page 8)
Fig. 7 · Wall Mount Installation

Service

If the unit requires service, do not return it to the dealer. Follow these steps:

1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by Schneider Electric Web site, www.apc.com. a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models. b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric Web site for country specific instructions. 3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. 4. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department of Transportation (DOT), and the International Air Transport Association (IATA) regulations require that UPS batteries be disconnected before shipping. The internal batteries may remain in the UPS. 5. Write the RMA# provided by Customer Support on the outside of the package. 6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 9 of the APC Back-UPS user manual — HAZARD OF EXPLOSION
Page 9 · click to enlarge
Page 9

Battery Replacement

CAUTION

RISK OF HYDROGEN SULPHIDE GAS OR EXCESSIVE SMOKE

  • Replace the battery at least every 5 years.
  • Replace the battery immediately when the UPS indicates battery replacement is necessary.
  • Replace the battery at the end of its service life.
  • Replace batteries with the same number and type of batteries as originally installed in the equipment.
  • Replace the battery immediately when the UPS indicates a battery overtemperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced. Failure to follow these instructions can result in injury.

CAUTION

HAZARD OF EXPLOSION

  • Do not dispose of the batteries in a fire. The batteries may explode.
  • Do not open or mutilate the batteries. Release electrolyte maybe toxic and it is harmful to the skin and eyes.
  • Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. In this case battery is not user replaceable.
  • A battery can present a risk of electrical shock and high short-circuit current. Contact with any part of a grounded battery can result in electrical shock. The following precautions should be observed when working on batteries:

a) Remove watches, rings, or other metal objects. b) Use tools with insulated handles. c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries. e) Disconnect charging source and load prior to installing or maintaining the

battery. f) Remove battery grounds during installation and maintenance to reduce likelihood of shock. g) Remove the connection from ground if any part of the battery is

determined to be grounded.

Failure to follow these instructions can result in injury.

The battery in the Back-UPS is not user-replaceable. Contact SEIT Technical Support for a list of authorized service centers near you.

For the recycling battery information, please go to apc.com/us

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 10 of the APC Back-UPS user manual — Warranty
Page 10 · click to enlarge
Page 10

Warranty

Register your product on-line. http://warranty.apc.com The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA

Page 11 of the APC Back-UPS user manual — EN 990-6275
Page 11 · click to enlarge
Page 11

APC by Schneider Electric IT Customer Support Worldwide

For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com EMC Compliance

This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.

Select models are ENERGY STAR

® qualified. For more information on your specific model go to www.apc.com

Select models are compliant with California (CEC) Battery Charger regulations. For more information on your specific model go to www.apc.com © 2019 APC by Schneider Electric. APC, the APC logo are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-6275

11/2019

Page 12 of the APC Back-UPS user manual — EN 990-6155-024
Page 12 · click to enlarge
Page 12

Important UPS Safety Information SAVE THIS GUIDE

SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the Schneider Electric equipment and batteries.

General Safety Information

  • This UPS is intended for indoor use only.
  • For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
  • The UPS cord shall be connected to an earthed mains socket outlet for safety reasons.

Battery Safety

  • A battery can present a risk of electric shock and burns by high shortcircuit current.
  • Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
  • Before installing or replacing the batteries, disconnect the charging source prior to connecting or disconnecting battery terminals. Do not wear any metal objects including watches and rings. Do not lay tools or metal parts on top of batteries. Remove conductive jewelry such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
  • Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
  • When replacing batteries, replace with the same type and number of batteries or battery packs.
  • CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
  • CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes and may be toxic.

© 2019 APC by Schneider Electric. APC, the APC logo, and Back-UPS are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-6155-024

4/2019

Ask about the APC Back-UPS

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the APC Back-UPS

Be the first to ask — other owners or our team will answer.

Original document

APC Back-UPS manual PDF

12 pages·490 KB·Uninterruptible Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…