Smart-UPS
Uninterruptible Power Supply
500 VA Short-depth Rack-Mount with Lithium-ion batteries
120 Vac


This manual provides critical product, safety and installation information for the SCL500RM1UC and SCL500RM1UNC. The only difference between these two models is in their monitoring and manage- ment options. The SCL500RM1UC has the “SmartConnect” port, which allows the product to be mon- itored remotely. Learn more about the APC
TM SmartConnect feature on www.smartconnect.apc.com The SCL500RM1UNC can be managed via traditional methods and APC softwares, it has an embedded network management card, the AP9537SUM.

SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to either a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
18-32 kg 40-70 lb 32-55 kg 70-120 lb >55 kg >120 lb
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 1

Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains). Before installing or servicing the equipment check that the:
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 2

WARNING
RISK OF CHEMICAL HAZARD AND EXCESSIVE HEAT
Failure to follow these instructions can result in death or serious injury.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 3
•

SCL500RM1UC and SCL500RM1UNC Rack-Mount



Two-post rack-mounting: Utilize the bracket holes that are offset 6.25”.

Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 4

Secure clip nuts to the rack, and attach brackets with provided screws.





Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 5
su1073d




Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 6
su1083a

For additional specifications, refer to the APC Web site at www.apc.com

Operating 0° to 40° C (50° to 104° F) Storage -15° to 45° C (5° to 113° F) Transporting -20° to 60° C (-4° to 140° F) IP Rating Operating IP20
Transporting 50,000 ft. (15,240m) Humidity Operating 10% to 90%
The transporting conditions are for 2 weeks maximum.
SCL500RM1UC & SCL500RM1UNC Rack-Mount

Display (more information below)
Online / On Battery indicator
APC™ SmartConnect status indicator Network status indicator Event Detected indicator Battery Error indicator
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 7

APC™ SmartConnect port
UPS input power cord
Chassis ground connection screw
APC™ SmartConnect Control
Building Wiring Fault indicator

SCL RM UNC 500 1

SCL500RM1UC and SCL500RM1UNC Rack-Mount Models

Model Dimensions (in/mm) H x W x D Weight (lb / kg)
SCL500RM1UC SCL500RM1UNC 1.75 x 17 x 9.14 in (44.44 x 431.8 x 232.14 mm) 9.25 / 4.2
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 8

For UPS installation information, refer to the Installation Guide included with the UPS.
The UPS is intended for IT environments. Avoid placement where there is excessive dust and humidity. Note that temperature in excess of 25o C may have an adverse effect on battery and UPS life. All vents on the side or rear of the UPS should be free of obstructions. The UPS is heavy. The UPS should be placed near the bottom of the rack.

Failure to follow these instructions can result in injury or equipment damage.

Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 9

APCTM SmartConnect allows you to monitor the health and status of your UPS from any device connected to the Internet. Visit www.smartconnect.apc.com to learn more. Log onto www.smartconnect.apc.com or scan the QR code to launch the registration process. The website includes instructions to setup your online account, activate your warranty and begin monitoring your UPS remotely. By connecting this product to the Internet using the APCTM SmartConnect port, you are agreeing to APCTM SmartConnect Terms of Use, as found at smartconnect.apc.com. Schneider Electric Data Privacy Policy can also be found at smartconnect.apc.com.
The Device IP Configuration Utility can discover Network Management Cards (NMC 2) that do not have an IP address assigned. Once discovered, you can configure the IP address settings for the cards. You can also search for devices already on the network by entering an IP range to define the search. The Utility scans the IP addresses in the defined range and discovers cards that already have a DHCP-assigned IP address. For detailed information on the Utility, see the Knowledge Base on the support page of the www.apc.com website and search for FA156064 (the ID of the relevant article). Once IP address found, access the Web management interface by this IP address. Enter the user name and password to login (by default, use apc and apc to login as the administrator).
Smart-UPS is provided with PowerChute management software for unattended operating system shutdown, UPS monitoring, UPS control and energy reporting. The following diagram is a representation of a typical server installation.

N E T W OR K S H U T D OW N
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 10

This button is used to turn the UPS output power on and off.
The Online indicator illuminates green when UPS output is turned on and operating on AC power.
The On Battery indicator illuminates orange and the unit will continue to emit a series of short beeps indicating that the UPS is operating on battery power.
The indicator illuminates red when events occur.
These indicators illuminate green when APCTM SmartConnect connection is okay.
These indicators illuminate red when APCTM SmartConnect connection is cut-off
These indicators illuminate green or orange when Network connection is okay.
The Battery Error indicator illuminates red when the UPS battery does not pass self test.
Configuration settings may be changed at any time using the PowerChute software or SmartConnect Switch. This table provides a brief description of the general settings, for more detailed information on each of these parameters consult application note 80 at www.apc.com
Function Factory Default Options Description
High Transfer 120 V: 136 Vac 130 Vac - 142 Vac To avoid unnecessary battery usage, set the transfer point higher if the AC voltage is chronically high and the connected equipment is known to work under this condition. The Power Quality setting will automatically change this setting.
Low Transfer 120 V: 100 Vac 90 Vac - 106 Vac Set the transfer point lower if the AC voltage is chronically low and the connected equipment can tolerate this condition. This setting may also be adjusted using the power quality setting.
Select the level of sensitivity to power events that the UPS will tolerate.
Date of Last Battery Replacement
Date set at factory.
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 11
Main on/off · Quick status LEDs

Function Factory Default Options Description
Auto Self Test On start-up and every 14 days since the last test
The interval at which the UPS will execute a self-test.
Firmware update: this only appears when new firmware is available in the flash memory of the UPS and is ready to be installed
This will permit remote configuration changes.
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 12
SmartConnect Control Switch · Enable with control

The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off, turn on, shut down, or reboot connected equipment.
In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:
Function Factory Default Options Description
Name String Outlet Group
Outlet Groups 1 & 2
Edit these names using an external interface, such as the Network Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in seconds
The amount of time the UPS or the Outlet Group will wait between receiving the command to turn on and the actual startup.
Set the value in seconds
The amount of time the Outlet Group will wait between receiving the command to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in seconds
The amount of time that the Outlet Group must remain off before it will restart.
0 sec Set the value in seconds
The amount of battery runtime that must be available before the Outlet Group will turn on.
Load Shed On Battery
When the unit switches to battery power, the UPS can disconnect power to the Controlled Outlet Group to save runtime. To configure this delay time, use the LOAD SHED TIME WHEN ON BATTERY setting.
Load Shed Time when On Battery
Disabled Set the value in seconds
The amount of time the UPS will keep the Outlet Group on when operating on battery. When the battery runtime falls below the specified value, the Outlet Group will turn off. Configure this time using the LOAD SHED RUNTIME REMAINING setting.
Load Shed On Runtime
Load Shed On Runtime Remaining
Disabled Set the value in seconds
When the remaining runtime reaches this level, the Outlet Group will turn off.
Load Shed on Overload
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 13
Minimum Return Time

Problem and Possible Cause Solution
The UPS will not turn on or there is no output.
The unit has not been turned on. Press the ON key once to turn on the UPS.
The UPS is not connected to AC power. Be sure the power cable is securely connected to the unit and to the AC power
supply.
The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset the circuit breaker.
The unit shows very low or no input AC voltage.
Contact a qualified electrician to correct wiring issue.
The battery connector plug is not securely connected.
Be sure that all battery connections are secure.
There is an internal UPS error detected. Do not attempt to use the UPS. Turn off the UPS and unplug it from AC. Contact
APC Customer Care Center for assistance.
The unit cannot remotely turn on. When network cable is disconnected with the UPS turned off and AC power connected the UPS will, after a while, automatically enter power saving mode. Tap the power button to wake up the UPS and enable its remote control feature.
The UPS is operating on battery, while connected to input AC power.
The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset the circuit breaker.
There is very high, very low, or distorted input line voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage with the AC voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.
UPS is emitting intermittent beeps.
The UPS is operating normally. None. The UPS is protecting the connected equipment.
UPS does not provide expected backup time.
The UPS battery is weak due to a recent power outage or is near the end of its service life.
Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the entire UPS even if the Battery Error indicator has not illuminated.
The UPS is experiencing an overload condition.
Check the UPS load display. Unplug unnecessary equipment, such as printers.
Display interface LEDs flash sequentially.
The UPS has been shut down remotely through software or an optional accessory card.
None. The UPS will restart automatically when AC power is restored.
The Error LED is illuminated. The UPS displays an error message and emits a constant beeping sound.
Internal UPS error detected. Do not attempt to use the UPS. Turn the UPS off and contact the Customer Care Center immediately.
The Battery Error icon is illuminated and the UPS beeps for one minute every five hours.
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the entire UPS unit.
The Battery Error icon is flashing and the UPS beeps once every 2 seconds.
The battery is not properly connected. Be sure that the battery connector is securely connected.
The UPS displays a site wiring error message.
Wiring errors detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit.
If the UPS indicates a site wiring error, have a qualified electrician inspect the building wiring. (Applicable to 120 V units only.)
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 14

Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of five(5) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT’s recommendations or specifications. Further, SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 15

If the unit requires service, do not return it to the dealer. Follow these steps:
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit and are available through the LCD interface on select models.
b. Call APC Support and a technician will attempt to solve the problem over the phone. If this is not
possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, it will be repaired or replaced at no cost.
d. Service procedures and returns may vary internationally. Refer to the APC web site for country
specific instructions.
Smart-UPS SCL500RM1UC and SCL500RM1UNC 120 Vac Short-depth Rack-Mount 16



Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:
– www.apc.com (Corporate Headquarters)
Connect to localized APC by Schneider Electric web sites for specific countries, each of which provides customer support information.
Global support searching APC by Schneider Electric Knowledge Base and using e-support.
– Local, country specific centers: go to www.apc.com/support/contact for contact information.
– For information on how to obtain local customer support, contact the APC by Schneider Electric
representative or other distributor from whom you purchased your APC by Schneider Electric product.
Select models are compliant with California (CEC) Battery Charger regulations. For more information on your specific model go to www.apc.com
© 05/2020 APC by Schneider Electric. APC, the APC logo, Smart-UPS, SmartConnect and PowerChute are
owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are
property of their respective owners.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| The UPS will not turn on or there is no output. | p.16 | ||
| The unit has not been turned on. | Press the ON key once to turn on the UPS. | p.16 | |
| The UPS is not connected to AC power. | Be sure the power cable is securely connected to the unit and to the AC power supply. | p.16 | |
| The input circuit breaker has tripped. | Reduce the load on the UPS. Disconnect nonessential equipment and reset the circuit breaker. | p.16 | |
| The unit shows very low or no input AC voltage. | Contact a qualified electrician to correct wiring issue. | p.16 | |
| The battery connector plug is not securely connected. | Be sure that all battery connections are secure. | p.16 | |
| There is an internal UPS error detected. | Do not attempt to use the UPS. Turn off the UPS and unplug it from AC. Contact APC Customer Care Center for assistance. | p.16 | |
| The unit cannot remotely turn on. | When network cable is disconnected with the UPS turned off and AC power connected the UPS will, after a while, automatically enter power saving mode. Tap the power button to wake up the UPS and enable its remote control feature. | p.16 | |
| The UPS is operating on battery, while connected to input AC power. | p.16 | ||
| There is very high, very low, or distorted input line voltage. | Move the UPS to a different outlet on a different circuit. Test the input voltage with the AC voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity. | p.16 | |
| UPS is emitting intermittent beeps. | p.16 | ||
| The UPS is operating normally. | None. The UPS is protecting the connected equipment. | p.16 | |
| UPS does not provide expected backup time. | p.16 | ||
| The UPS battery is weak due to a recent power outage or is near the end of its service life. | Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the entire UPS even if the Battery Error indicator has not illuminated. | p.16 | |
| The UPS is experiencing an overload condition. | Check the UPS load display. Unplug unnecessary equipment, such as printers. | p.16 | |
| Display interface LEDs flash sequentially. | p.16 | ||
| The UPS has been shut down remotely through software or an optional accessory card. | None. The UPS will restart automatically when AC power is restored. | p.16 | |
| The Error LED is illuminated. The UPS displays an error message and emits a constant beeping sound. | p.16 | ||
| Internal UPS error detected. | Do not attempt to use the UPS. Turn the UPS off and contact the Customer Care Center immediately. | p.16 | |
| The Battery Error icon is illuminated and the UPS beeps for one minute every five hours. | p.16 | ||
| The battery has a weak charge. | Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the entire UPS unit. | p.16 | |
| The Battery Error icon is flashing and the UPS beeps once every 2 seconds. | p.16 | ||
| The battery is not properly connected. | Be sure that the battery connector is securely connected. | p.16 | |
| The UPS displays a site wiring error message. | p.16 | ||
| Wiring errors detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit. | If the UPS indicates a site wiring error, have a qualified electrician inspect the building wiring. (Applicable to 120 V units only.) | p.16 |