Operation and installation instructions
an automatic gas heating basic unit
Type 60 – 81 / Model Vertico Type60 – 82 / Model Lithorond
ORANIER Heiz- und Kochtechnik GmbH · D-35075 Gladenbach · Telephone (0 64 62) 9 23-0 · Fax (0 6462) 9 22 3 49

ORANIER - Customer service services can only be used within Germany via our central customer service.
Switzerland: Gas Center Chur M. Honegger AG Sägenstr. 75 7000 Chur telephone 81-2 53 70 71 Faxes 81-2 53 73 31 Email [email protected]
Weidenhäuser Str. 1-7 35075 Gladenbach
Luxembourg: ENERGUS S.A. 40, rue Rangwee 2412 Luxembourg telephone 40 83 80 Faxes 40 83 81 Email [email protected]
Service for standing range telephone service 0 340 / 5 19-56-12 Telephone spare parts 0 330 / 519-56-14 Fax fax 0 3 40 / 5 19.
Email wrobel@Oranier.com ziemer@Oranier.com
Central kitchen technology telephone 0 64 62 / 9 23-355 Fax 0 6462 / 9 22 - 359 E-mail: customer service-kuechentechnik@Oranier.com
Please note In order for our customer service to carefully prepare repairs and provide the required spare parts, we need the following information:
Central heating technology Telephone 0 64 62 / 9 23-360 Fax 0 6462 / 9 22 369 Email: customer service-heating technology@Oranier.com
All services are available Monday to Thursday from 7.30 a.m. to 17.00 Fridays from 7.:30 a. m. to 15.00
Outside of service hours, please let us know your wishes by e-mail or fax.
Austria: TGK - Austria Technical equipment customer service Obachgasse 8 1220 Vienna telephone 01-259 80 18 Faxes 01-259 80 33 Email tgk@tgk.co.at or Neubauzeile 57 4030 Linz telephone 07 32-37 18 68 Faxes 07 32-37 18 35
Customer service / spare parts

Your contribution to environmental protection Directive 2002/96/EC (WEEE): Information for the end user The following information is only used by final consumers who have a product on which and. a. The symbol (FIG.) A) is indicated. This symbol is located on the glue plate with the technical device data (typeplate) attached to the device: this symbol means that the product has been classified as electrical or electronic equipment due to the prevailing regulations and complies with EU Directive 2002/96/EC (WEEE). Therefore, the appliance must not be disposed of in any case after its end with normal household waste. The device is free of charge either to a permanent collection point for electrical or electronic equipment, or to a reseller when buying a new product.
We as a manufacturer declare that the device described, with the CE-No. specified in the section “Technical data”, has been built according to the essential requirements of EC Gas Appliances Directive 90/396/EEC including modifications. The apparatus conforms to the type described in the related EC-type examination certificate.
FIG. A The end user is responsible for the transfer of the waste equipment to a suitable collection point. Otherwise, he will be punishable under the laws in force on waste disposal. Proper separate collection of waste for recycling and environmentally sound disposal avoids damage to the environment and health, allowing reuse of equipment components. For more information about the existing collections, please contact your municipality or the purchasing office where you purchased the device. Manufacturers and importers will live up to their responsibility for product recycling and environmentally sound disposal both directly and through participation in a collective scheme.
Disposal of packaging The package protects the device from transport damage. The packaging materials are selected according to environmentally compatible and disposal aspects, which makes them recyclable. The corrugated cardboard/paperboard is mainly made of waste paper. The styrofoam moldings are foamed CFC-free. The polyethylene film (PE) consists partly of secondary raw material. The strapping bands are made of polypropylene (PP). The return of the packaging to the material cycle saves raw materials and reduces waste generation. Your dealer will generally take back the packaging. If you dispose of the transport packaging yourself, please ask for the address of the nearest recyclables or recycling center.


Precautionary statements
The installation may only be carried out by a professional (contract installer of a gas supply company). This takes responsibility for the proper installation and for first commissioning.
6-99.03.12.000 - 002 5

They have become owners of a space heater in which the latest heating technology combines with the stimulation of a wood fire. The gas valve used has a regulation modulating between maximum and minimum power.
If the heat requirement is below the minimum heating power, the valve switches off the main burner completely except for the ignition burner. Regardless of the thermostatic control of the gas valve, you have the possibility to adjust the heating power manually. The thermostatic control is then out of operation.


Model Vertico, Type 60-81
Model Lithorond, type 60-82
– to start and decommission the device.
– with a built-in thermostat to achieve an even room temperature.
– with thermoelectric safety valve for protection against the outflow of unburned gas.
– with built-in pressure regulator for the exact adjustment of nominal thermal load.
A Operating button 1* and Pressure button for piezzo ignition 2* B All-gas valve with: Power slider 3*
* These designations and numbers are used on page 7 for the control panels.
6 6-99.03.12.000 - 002

Adjustments
Open the gas tap.
Thermostatic control The power slider 3 on the all-gas valve B in positions (standard setting). The thermostat installed in the all-gas valve automatically regulates the room temperature, which is controlled by means of the control button. 1 is set. The specified digits characterize the control range of the thermostat. After a short time, you will have determined which setting corresponds to your need for heat. Living location and construction of the house, the size of the room as well as its heat loss affect this. Therefore, only indicative values can be specified at the factory which may deviate downwards or upwards. For an average room temperature of 20°-22° C., the setting 3 to 4 of the operating button should be appropriate. Higher numbers correspond to higher temperatures, lower numbers correspond with lower temperatures. The power, i.e. The flame size of the burner is automatically increased or reduced, depending on heat requirements and sliding continuously between the small-fire position and full-burning position. If the heat supply of the small position exceeds the requirements of the room, the thermostat switches off the gas feed up to the ignition flame. When the heat demand is renewed, it opens up its small position in order to automatically adapt itself to requirements. It may therefore be the case that, in position 3 with throttled power, or in a small position, the space heater burns only because the desired temperature has already been reached in the room. On the other hand, it is possible for this to burn at full power in position 1, because the room has a temperature of only approx. 10 °C or less. This control reduces ignition and operating noise to a minimum compared with other heating systems. During the setting, only the ignition flame burns and the control is overridden. However, the heat of the ignition flame is retained in space as basic heat.
– Operating button 1 rotate and press in the ignition position.
– Pressure button 2 for the piezzo ignition to ignite the ignition flame, press in several times until the ionic flame burns. Operating button 1 Approximately Hold in for 10 seconds.
– Operating button 1 Let go. If the ignition flame is extinguished, the illusion process may be repeated only after a waiting time of 3 minutes.
– If the ignition flame burns, temperature selection can be made. For this purpose, the operating button 1 For example, turn to the number 4.
If the temperature attained does not correspond to your wishes, you can increase the temperature by setting it to a higher number or lower the temperature through setting it up to a smaller number. For the night, turn the control button 1 to a smaller number or, if only the ignition flame is intended to burn, to the symbol .
In case of ignition difficulties, see the chapter ‘Incident assistance’.
For a short time – Operating button 1 Turn to the right, beyond the ignition position until it stops.
For longer periods – In the event of a prolonged interruption in operation, additionally close the gas connection valve.
After the shutdown, the space heater cannot be immediately put back into operation (re-switching block). A waiting time of approx. 60 seconds to be taken.
Manual scheme The thermostatic control is set out of force when the power slider 3 on the all-gas valve B from the standard setting ( ). The further the power slider is shifted from the position, the greater the set line or output of the circuit breaker. Flame size. With the operating button 1 The device can now no longer be regulated, but still switched off. In order to restore thermostatic control, conductor slide 3 Bring it back into position.
In the event of faults which cannot be eliminated themselves (see chapter “Incident Assistance”), the device must be taken out of operation until a specialist has resolved the problem.
6-99.03.12.000 - 002 7

During regular cleaning of the apartment, dust should also be removed from the heater. This avoids unnatural contamination of the room, as can occur in rooms with upholstered clothing and carpets due to abrasion of wool and cellulose which enter into the heater's convection stream as floating bodies. Care for stone surfaces regularly with suitable, commercially available care agents.
Function The space heaters are equipped with an exhaust gas monitoring device. This ensures that, in the event of a malfunction in exhaust gas discharge, no large quantities of exhaust gases can pass through the flow control into the installation space. In the event that the exhaust gas cannot be discharged unhindered through the chimney, a temperature sensor is heated by the exhaust which exits from the flow control and the supply of gas is interrupted after a delay time. In full-load operation of the heater, the deceleration time is a few seconds.
Restart of operations In order to be able to restart the heater after exhaust gas monitoring, wait a few minutes for the temperature sensor to cool down. In addition, it shall be ensured that the exhaust duct (pipe, chimney) is not blocked or obstructed at any point. The start-up can then take place as described above.
If the exhaust gas monitoring device should respond, a person skilled in the art must be able to check the apparatus or control system. the exhaust gas dissipation system.
8 6-99.03.12.000 - 002

Regular maintenance of the space heater ensures its operational reliability. We therefore do not recommend that the function of the gas fitting and burner system, the leakage properties of the parts carrying gases, the adjustment to the gas and the correct discharge of exhaust gases be checked every one or two years by a known contract installer. For all maintenance work, only original parts of the manufacturer shall be used. Repairs to the gas fitting shall be limited to substitution of assemblies. The opening of the gas fitting shall not be permitted.
Maintenance of the exhaust flap The exhaust flap shall be subjected to a functional test during the maintenance work at the gas fireplace and, if necessary, cleansing of dirt. For this purpose, the complete exhaust gas flap is kept under flowing water. In the case of severe greasy turbidity, the exhaust flap should be placed in a water bath containing hot fat-dissolving alkali (dishwashing detergent) and subsequently washed off with clear water. In no case should the cleaning be carried out mechanically, since there is a risk of permanent deformation of the control elements.
If a viewing window which is possibly in the process of being broken or if it has cracks, the space heater must not be put into operation until the viewing opening is renewed and the combustion chamber closed again.
Before calling customer service, check if you can fix the fault yourself based on the following information.
6-99.03.12.000 - 002 9

Precautionary statements
Instructions for the establishment
Installation may be carried out only by a professional
(contract installer of a gas supply company). This takes responsibility for the proper installation and for first commissioning.
Example of ventilated protection against thermal radiation
It must be ensured that the surfaces of components located behind the ventilated protection cannot have temperatures higher than 80 °C.
Installation rules for Austria • When installing the device in Austria, ÖVGW guidelines G1 (TR-Gas) and G2 (TRF LPG) must be observed.
Installation regulations for Switzerland • SVGW gas guideline G1 (2005): Gas installation
10 6-99.03.12.000 - 002
for Germany · Non-combustible material



Distances from combustible articles
Model Lithorond, type 60-82
The distance from the device rear wall to the positioning-
The wall shall be at least 100 mm.

Model Vertico, Type 60-81
6-99.03.12.000 - 002 11
Dimensions

Installation of the basic equipment At this point, only the setup of the basic device will be discussed. The assembly of the cladding is described separately. – Set up the basic device horizontally at its intended location, taking into account the specified fairing dimensions. Ground irregularities can be compensated by the screw feet.
Functional test of the exhaust flap After the exhaust flap has been installed in the gas control site, a functional test of the entire exhaust system shall be carried out as described in paragraph 8.3 of TRGI 1986/96. At each gas firing site, it shall be ascertained 5 minutes after operation with the windows and doors of the dwelling closed that no exhaust is leaking at the flow control. In the case of several fire stations installed in the dwelling, this test shall be carried out with all gas-firing points operating simultaneously both when the interior doors are closed and open. This test shall be carried out at the highest thermal output with which gas furnaces can operate, and also at the lowest heat load in the case of a gas furencing to be tested. If exhaust gas leaks during the test, no single-wall operation is ensured. The cause must be determined immediately, the defects are to be confirmed.
– Connect the space heater with the gas pipe and exhaust gas tube.
The space heater must be tilt-proof on the wall
are fixed:
– Screw the threaded rod accompanying the device into one of the screw holes present at the top in the rear wall of the device.
– A hexagon nut is first screwed onto the wall-side end of the threaded rod, and then the holding plate.
– Indicate the position of the holding plate on the wall.
Gas connection When connecting the gas line, it is absolutely essential to hold against the connection piece in a suitable manner. After installation, all connections shall be checked for leakage. The appliance connection faucet shall be mounted in a readily accessible position outside the equipment lining.
– Screw the holding plate with the attached fastening material on the wall. If the wall is of a special nature, the holding plate must be adjusted in another suitable manner.
– Finally, the threaded rod with the hexagon nut must be secured against rotation.
Insertion of the coal and wood imitation When the cladding is removed
In order to prevent the imitation arranged according to the specifications e.g. by moving the device, the construction of the imitation pieces must not take place until the space heater is connected on the gas side and off-gas side.
Remove the imitation material placed packed in the combustion chamber of the space heater. For this purpose, the viewing window must first be removed:
The mother accessible in the pictured opening X unscrew and remove the washer.
Connection of the exhaust pipe The connection of an all-gas space heater to a fireplace is in accordance with TRGI 1986/96 or TRF 1996 is increasing. In any case, the competent district chimney sweep master should be consulted.

– Tilt the viewing window with frame forward and lift it from lower locking
– Put aside windows with frame.
The packaging contains:
12 6-99.03.12.000 - 002







Closing the combustion chamber – Pick up the viewing window with frame and clean the inside of the window.
– Plug in frames at the bottom, press on top and with previously removed mother With washers underpinned screwed back onto the combustion chamber. In this case, make sure that the frame rests tightly on top.
6-99.03.12.000 - 002 13
Inserting the parts

Adjustment order All points strictly in the specified sequence.
The factory gas setting is specified on the type of gas adhesive.
At the installation site, it is essential to check whether local connection conditions, type of gas and pressure are in accordance with the device settings on the basis of information on the equipment labels.
Remove the sealing screw "1".
Connect the pressure gauge to the measuring nozzle "2".
If necessary, a changeover of equipment to this type of gas is required (see ‘changeover to another type of Gas’).
Open the appliance tap.
– put the device into operation and measure the flow pressure in full fire (if applicable). cool the heat sensor in the water bath. The flow pressure must lie within the specified range. If this is not the case, no setting or entry into service shall be carried out. The gas supply unit or the reservoir, i.e. the LPG supplier shall be corrected.
The verification and, if applicable, The correction of the gas input (rated heat load) is carried out either by nozzle pressure method or volumetric metering (for natural gas only). As a rule, the nozzle pressure method is preferred since it is sufficiently accurate and very time-saving.
– Take the device out of service and close the appliance tap.
Types of gas • With the natural gas setting E-G20 (H-G 20), gas appliances can be operated in the Wobbe index range from 11.3 to 15.2 kWh/m3 *.
– Remove the pressure gauge from the measuring nozzle “2” and seal the measuring tube “2“ gas-tight again with sealing screw “1”.


*relative to 15° C., 1013 mbar
Gasart and Wobbeindex are to be requested from the gas supply company.
A change of equipment to another gas-
Family is not allowed!
Open the appliance tap.
If the permissible subsequent flow pressure is exceeded,
or undershot, the device must not be put into operation! The gas supplier or The tail gas supplier shall be notified.
14 6-99.03.12.000 - 002
Connection conditions · Sit valve

sufficient heating in each operating position and to ensure a reliable over-ignition. The ignition flame load is determined by the ignition burner nozzle. If the heating of the thermocouple and a safe over-ignition are no longer ensured, cleaning or possibly also replacement of the ignition burner nozzle must be carried out. An excessively large ignition flame can be readjusted with the "7" setscrew. The adjusting screw shall be screwed in at least one thread (one revolution).
– Remove the sealing screw “3” and connect the pressure measuring device to the metering nozzle “4”.
Open the appliance tap.
– put space heater into operation according to the user’s instructions.
– Turn the operating button to its highest position (if applicable). Cool the heat sensor in a water bath.
– Adjust nozzle pressure according to the adjustment table with the control screw "5".
– Take the device out of service and close the appliance tap.
– Remove the pressure gauge from the measuring nozzle “4” and close the measuring tube “4“ again with a sealing screw “3” gas-tight.
Functional test All connections shall be checked for leakage.
Open the appliance tap.
- Mount the cladding.
– Ignition and main burners, checking combustion stability at large and small positions.
By volumetric method (only for natural gas) – put space heater into operation according to the user’s instructions.
– After completion of the work, this instruction must be handed over to the customer. The customer must be informed about the operation, correct handling and safety devices of the device.
– Take other gas consumers out of service.
– Turn the operating button to its highest position (if applicable). Cool the heat sensor in a water bath.
After an operating time of 10 minutes, determine the gas consumption over a period of 5 minutes (read on the gas clock).
– Compare actual gas consumption with the target value specified in section “Technical data”.
– If necessary, adjust the gas consumption with control screw "5" and check the gas use again.
– Now turn the control button slowly to the left until the burner flames are re-burning. The main burner now burns in the small position. It must be ensured that a satisfactory over-ignition is guaranteed in all cases. Using the nozzle size specified in the section “Technical data”, this is the case with a small adjustment screw that has been turned into an impact.
– If necessary, adjust the small position with the small adjustment screw "6" (left rotation increased, right-hand rotation reduced gas passage).
6-99.03.12.000 - 002 15

Switching the device to another gas family (natural gas to propane and vice versa) is not permitted.
Conversion to another natural gas category
The gas changeover shall be carried out only by an
can be carried out by a person skilled in the art.
Only customer service related
special nozzles are used.
rich, the heater may only be operated with natural gas H (= device setting Natural Gas E).
Nozzle sets The available nozzle sets and their order numbers can be found in the technical data.
– Close the gas tap.
- Take off the disguise. The removal of the cladding is effected in a change to the sequence contained in separate assembly instructions.
Remove shielding and holding plate "8". For this purpose, unscrew the two screws "9", suspend the holding plate if necessary at the rear and remove it by pulling forward.
Remove the window:
– For this, the mother accessible in the depicted opening X unscrew and remove the washer.
– Remove the pipe clamp “11” and pull the nozzle stick “12” downwards from the injector “10”.
– Change the main burner nozzle “13”, countering it in a friendly manner.
The jet stick again Up to the stop plug into the injector and secure it with a pipe clamp.
– Reassemble the holding plate “8” and cladding.
– Closing the combustion chamber:
– To do this, pick up the viewing window with a frame and clean the inside of the window.
– Move the viewing window with frame forward and lift it from lower locking
– Plug in frames at the bottom, press on top and with previously removed mother With washer underlay screwed back onto the combustion chamber. In this case, make sure that the frame rests tightly on top.
– Put aside windows with frame.
– Control nozzle pressure (rated thermal load) and adjust it if necessary (see “Technical data”).
The setting of the small position and that of the ignition burner remain unchanged!
– Stick attached stickers to the previous gas-art sticker.
– Perform leakage testing.
– Control the subsequent flow pressure.
- Mount the cladding.
16 6-99.03.12.000 - 002
Replacement of the main burner nozzle

(=device setting natural gas E) and liquefied petroleum gas 50 mbar.
Type series 60-8X Type Series 60-8x P
Natural gas thread R 1⁄2" 1⁄2, 8 mm
Exhaust connection Ø 80 mm
Exhaust gas temperature 190 °C 177 °C
Exhaust gas mass flow rate 5.83 g/s 5.1 g/ s
CO2 content 4.1 vol.% 4.3 vol. %
Exhaust flap, thermally controlled type HOS 80
Rated heat output Rated thermal load (relative to calorific value Hi)
5,0 kW 6,1 kW 4.2 kW 5.1 kW
Gasart Type Series 60-8X Typeseries 60-8X P
Main burner nozzle characteristic number * 215 / 16 mm long
Natural gas E 20 mbar (G 20) AT, CH: H 20 mbar Wobbe index range Ws = 11,3 – 15,2 kWh/m3
Small adjustment screw characteristic number * 170
Order number of nozzles 5-54.00.00.000
Main burner nozzle characteristic number * 235 / 22.5 mm long
Natural gas LL 20 mbar (G 25) only DE Wobbe index range Ws = 9.5 – 12.4 kWh/m3
Small adjustment screw characteristic number * 170
Order number of nozzles 5-54.00.01000
105 / 16 mm long
Small adjustment screw characteristic number * 90
Propane (G 31) 50 mbar
* nozzle diameter in hundredths of a millimeter (e.g. 240 = Ø 2,4 mm
6-99.03.12.000 - 002 17

Gasart Type Series 60-8X Typeseries 60-8X P
Natural gas E 20 mbar (G 20)
0,645 m3/h
Calorific value Hi = 34,02 MJ/m3 Wobbeindex Ws = 50,72 MJ / m3
Natural gas LL 20 mbar (G 25) only DE calorific value Hi = 29.25 MJ/m3 Wobbeindex Ws = 41.52 MJ / m3
0,751 m3/h
Propane 50 mbar (G 31) calorific value Hi = 46.26 MJ/m3 Wobbeindex Ws = 76.84 MJ / m3
0,397 kg/h flow rate of gas
All figures for the calorific value Hi, Wobbeindex Ws and the connection value (flow rate) refer to 15 °C, 1013 mbar, dry gas.
Categories NOx mg/kWh
1 2 3 4 5
350 260 200 150 100
18 6-99.03.12.000 - 002

In order to claim guarantees, the presentation of proof of purchase is required in each case.
For our ORANIER devices, we provide a factory guarantee regardless of the obligations of the dealer under the purchase contract vis-à-vis the final customer under these conditions:
– External chemical or physical effects
during transport, storage, installation and use (e.g. Damage caused by quenching with water, overflowing foods, condensation and superheating. Hair cracking in enamelled or tile-glazed parts is not a quality defect.
The ORANIER guarantee covers the irrevocable repair of the device or of the parts covered. A claim for free replacement is only valid for those parts which have defects in the material and processing.
- Wrong size choice.
- Non-compliance with our installation and operation
instructions, the applicable building law general and local regulations of competent authorities, gas and electricity suppliers. This also includes elements on the exhaust pipes (furnace tube, inadequate or excessively heavy chimney draw) as well as improper maintenance work carried out, especially making changes to the equipment, its fittings and lines.
All direct labour and material costs incurred to eliminate this situation are taken over. Further claims are excluded.
– Use of unsuitable fuels in coal-fired
equipment fired and fuel oil; inappropriate gas quality and variations of gas pressure for appliances; unusual voltage fluctuations compared to the nominal voltage for electrical appliances.
– Incorrect operation and overload, and therefore
overheating of the equipment, improper treatment, insufficient care, inadequate cleaning of the machinery or its parts; use of unsuitable cleaners (see operating instructions).
– wear of the flames immediately
used parts of iron and fireclay (e.g. Steel, cast or fireclay liners.
We are not liable for indirect and immediate damage caused by the devices. This also includes room contamination caused by decomposition products of organic dust components and whose pyrolysis products can be deposited as a dark coating on wallpaper, furniture, textiles and furnace parts.
If the removal of a defect is not covered by our warranty, then the final customer must pay for the costs of the installation visit and repair.
ORANIER Heiz- und Kochtechnik GmbH Weidenhäuser Str. 1 – 7 35075 Gladenbach
6-99.03.12.000 - 002 19

3 x Competence and constantly new ideas

O Gas stoves with remote control
O Wood and coal permanent fire furnaces

O Installation stove gas or electric
O Installation cooking fields Gas and Electric
O Standing gas and electric

incl. heat exchanger;
6-99.03.12.000
ORANIER Heiz- und Kochtechnik GmbH. Weidenhäuser Str. 1-7. 35075 Gladenbach
Tel.: 06462-923-0 . Fax: 06462-923-349 . Email: info@Oranier.com
ww w . O r a n i e r c o m