Read the operating instructions and the enclosed brochure „Guarantee and additional notices“ completely. Follow the instructions they contain. Safely keep these documents for future reference. !
Function/Application Multimeter for taking measurements in the range of the overvoltage category CAT III up to max. 1000 V/CAT IV up to max 600 V. The meter can be used to measure DC and AC voltages, direct and alternating currents, resistances, capacitances, frequencies and duty factors within the speciÖ ed ranges; it can also be used for continuity and diode testing. In addition, the meter is Ö tted with a non-contact voltage detector and a vibration alarm.
Hazardous electrical voltage warning: Unprotected live components inside the device housing may pose a risk of electric shock.
Protection class II: The test device has reinforced or double insulation.
Overvoltage category III: Equipment in Ö xed installations and for applications where speciÖ c requirements with regard to the reliability and availability of equipment have to be met, e.g. circuit-breakers in Ö xed installations and devices used in industrial applications which are permanently connected to the Ö xed installation.
Overvoltage category IV: Devices such as electricity meters, overcurrent circuit breakers and ripple-control units, which are intended for use at or near the infeed into the electrical installation of buildings, and speciÖ cally from the main distribution to the supply system.

Safety instructions • Make sure that you always select the correct connections, the correct rotary switch position and the correct range for the measurement to be taken.


1 Rotary switch to set the measuring function
A Measured value display (4 segments, 4000 digits)

J Measurement units: mV, V, A, mA, Ohm, kOhm, MOhm, nF, F, Hz, kHz, MHz, %


V DC/V AC 1000 V DC, 1000 V AC
A DC/AC 10 A DC/AC (max. 30 seconds every 15 minutes)
Frequency, resistance, capacitance, duty factor, diode test, continuity test
AUTO OFF function In order to preserve the batteries, the meter switches off automatically if it is left idle for 15 minutes.

Attaching the test prods 2 In order to avoid the risk of injury, the test prods must always be kept in the holder on the rear of the meter when not in use and during transport.



The black test prod (–) must always be connected to the „COM socket“. When taking current measurements, the red test prod (+) must be connected to the „10 A socket“. For all other measuring functions, the red test prod must be connected to the „VąHZ socket“.
Please ensure that the test prods are connected correctly before each measurement. Taking a voltage measurement with 10 A current connections plugged in can cause the installed fuse to trip and result in damage to the measuring circuit. !
To take a current measurement, turn the rotary switch to position „10 A“ and press the „Mode“ button to set the voltage mode (AC, DC). Disconnect the circuit before connecting the meter. Then connect the measuring contacts to the object to be tested. The measured value acquired and the polarity appear on the display. Disconnect the circuit again before disconnecting the meter.
Do not measure currents above 10 A for longer than 30 seconds. This could damage the device or the test prods. !

To take a voltage measurement, turn the rotary switch to position „V“ and press the „Mode“ button to set the voltage mode (AC, DC). Then connect the measuring contacts to the object to be tested. The measured value acquired and the polarity appear on the display.
To measure the resistance, turn the rotary switch to position „ą“. Then connect the measuring contacts to the object to be tested. The measured value acquired appears on the display. If „O.L.“ appears on the display instead of a measured value, either the measuring range has been exceeded or the measuring circuit is not closed or has been interrupted. Resistances can only be measured correctly in isolation; therefore, the components might need to be disconnected from the remainder of the circuit.

When measuring resistance, to avoid the risk of the results of a measurement being distorted, there must be no traces of dirt, oil, solder spray or other contamination on the test prods. !


To test continuity, turn the rotary switch to position „ą“ and press the „Mode“ switch twice to activate the „Continuity test“ function. Then connect the measuring contacts to the object to be tested. A measured value of < 150 ohms is recognised as continuity; this is conÖ rmed by an audible signal. If „O.L.“ appears on the display instead of a measured value, either the measuring range has been exceeded or the measuring circuit is not closed or has been interrupted.

To test the diode, turn the rotary switch to position „ą“ and press the „Mode“ button once to activate the „Diode test“ function. Then connect the measuring contacts to the diode. The measured value acquired for the forward voltage appears on the display. If „O.L.“ appears on the display instead of a measured value, the diode has either been tested in the reverse direction or is faulty. If 0.0 V is measured, the diode is faulty or a short-circuit has occurred.
Reverse direction Forward direction
Forward direction


To take a capacitance measurement, turn the rotary switch to position „CAP“ and press the „Mode“ button three times to activate the „Capacitance measurement“ function. Then connect the measuring contacts to the object to be tested. In the case of poled capacitors, connect the positive pole to the red test prod.

To take a frequency measurement, turn the rotary switch to position „Hz“. Then connect the measuring contacts to the object to be tested. Press the „Mode“ button to switch from Hz to % (duty factor).

The „Auto range“ function is activated automatically when the meter is switched on. Auto range searches for the best possible range for each measurement in the corresponding measuring functions. Press the „Range“ button to activate manual range selection, then press the „RANGE“ button several times until you reach the desired range. Pay attention to changes in decimal places or units. To return to the „Auto range“ range, press the „RANGE“ button and hold it down for 2 seconds. „AUTO“ reappears on the display. The „Range“ function can only be used for voltage, current and resistance measurements.


The comparative measurement function takes a measurement relative to a reference value that has been saved previously. This enables the difference between the current measured value and the saved reference value to be displayed. Press the „REL“ button whilst a reference measurement is being taken in the corresponding measuring function. The display now shows the difference between the current measurement and the set reference value. Press the „REL“ button again to deactivate the function. The „Rel“ function can only be used for voltage, current and capacitance measurements, as well as continuity tests.
The „Hold“ function enables you to keep the current measured value on the display. Press the „HOLD“ button to activate and deactivate the function.

The non-contact voltage detector integrated in the meter is able to detect AC voltages from 100 V to 600 V, thus enabling live cables or cable breaks, for example, to be identiÖ ed. Turn the rotary switch to position „V“ and run the voltage sensor along the object to be tested (5 - 10 mm). The display lights up and the device starts to vibrate if AC voltage is detected.



Non-contact voltage detection is no substitute for conventional voltage testing. As the device detects an electrical Ö eld, it will react even to static charge. !
Voltage detection, single-pole phase test For reasons of safety, you must disconnect the black measuring lead from the COM socket on the device to take this measurement. Turn the rotary switch to position „V“. Connect the red test prod to the phase or neutral conductor. The red LED only lights up if the phase conductor is live. When the single-pole phase test is carried out on the outer conductor, the indicator function may be adversely affected under certain conditions (e.g. when insulating personnel protective equipment is used or at insulated locations).

The single-pole phase test is not suitable for checking for zero voltage. To do this, you need to carry out a two-pole phase test. !
To replace the fuse, Ö rst disconnect the test prods from their voltage source and then from the device. Remove all screws from the rear of the meter and then remove the battery. Open the housing and replace the fuse with one of the same type and speciÖ cation (10 A/600 V). Close the housing and carefully screw the meter back together.



The meter needs to be calibrated and tested on a regular basis to ensure it produces accurate measurement results. We recommend carrying out calibration once a year.
4.000 V 40.00 V 400.0 V ± (1.2% rdg ± 2 digits)
40.00 V 400.0 V ± (1.5% rdg ± 3 digits)
DC current 10 A ± (2.5% rdg ± 5 digits)
AC current 10 A ± (3.0% rdg ± 7 digits)
4.000 ką ± (1.0% rdg ± 2 digits)
40.00 ką 400.0 ką 4.000 Mą ± (1.2% rdg ± 2 digits)
40.00 Mą ± (2.0% rdg ± 3 digits)
± (3.0% rdg ± 5 digits) 4.000 F
100.0 F ± (5.0% rdg ± 5 digits)
9.999 Hz ± (1.5% rdg ± 5 digits) 99.99 Hz

Duty factor 0.1%…99.9% ± (1.2% rdg ± 2 digits)
Diode test 0.3 mA ± (10% rdg ± 5 digits)
Polarity Sign for negative polarity
Fuse 10 A/600 V quick-acting, 240 A2/s (6.35 x 31.8 mm)
Protection class II, double insulation
Overvoltage CAT III - 1000 V, CAT IV - 600 V
Test standards EN 61326, EN 61010-1, EN 61010-2-031
Max. rel. humidity 80% non-condensing
Operating temperature 0°C to 55°C
Power supply 1 x 9 V battery (NEDA 1604, IEC 6F22)
Dimensions 150 x 70 x 48 mm
Subject to technical alterations. 06.2010
This device complies with all necessary standards for the free movement of goods within the EU.
This product is an electric device and must be collected separately for disposal according to the European Directive on waste electrical and electronic equipment.
Further safety and supplementary notices at: www.laserliner.com/info
Pollution degree 2 · Weight 255 g