TYPE: AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1 AUD-18HX4SUNL AUD-24HX4SZLH AUD-36HX6SAHH AUD-48HX6SPHH AUD-60HX6SPHH
Thank you for buying this air conditioner. Please read these instructions carefully before installing and using this device, save it for later use.

We warmly welcome you as a user of our product! We thank you for your trust in us. Read this manual carefully before installation. Keep this manual safe for later use after installation.
Little space for installation is needed. The interior unit can easily be installed in the ceiling space.
Silent operation. The excellent fan design ensures a quiet and even airflow with little noise.
Optional static pressure 18 k: optional 10 Pa / 30 Pa, 24 k and 36 k: 50 Pa / 80 Pa
Meets various installation requirements. Often the type with air intake at the rear is applied depending on the actual space for installation. The unit is also supplied with air inlet at the bottom, with sound rising to about 5-6 dB.
(for the high-efficiency type a free choice of 1~80 Pa), 48 k / 60 k: 80 Pa / 120 Pa static pressure. One unit with multiple optional installation methods.
Highly efficient and environmentally friendly new coolant R410A. R410A protects the environment and can not harm the ozone layer.
Self-recovering after power failure. If the power supply is restored after a malfunction, all settings are still active and the air conditioner works according to the original settings.
On and off 24-hour timer. This timer can be set to automatically switch on or off the unit per day.
Self-diagnostic function in case of malfunction. If there is something wrong with the air conditioner, the microprocessor will examine the malfunction and then it can be read on screen for convenience in maintenance. MODEL DEVICE
On/off integrated air conditioner
AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH
AUD-18HX4SUNL AUD-24HX4SZLH AUD-36HX6SAHH AUD-48HX6SPHH AUD-60HX6SPHH
New DC inverter integrated air conditioner (high-efficiency model)
AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1

Composition of the air conditioner
2.1 Stand-up function
2.2 Sleep function
10 10 10 3. Installate wired remote 11 11
2.3 Timer Function
4.1 Remote control H1
4.1.1 Operating status 14 14 14
4.1.2 Control of airflow 15 15 15
4.1.3 Smart stand 16 16 16
4.1.4 Clock setting 16 16 16
4.1.5 Timer stand 17 17 17
4.1.6 Sleep Mode 18 18 18
4.1.7 Super-stand 18 18 18
4.2 Remote control J1
4.2.1 Operating status
4.2.2 Airflow control
4.2.3 Smart Stand
4.2.4 Clock setting
4.2.5 Timer mode
4.2.6 Sleep Mode
4.2.7 Super-stand
4.3 Remote control E4-07
4.3.1 Operating status
4.3.2 Control of airflow
4.3.3 Smart stand
4.3.4 Clock setting
4.3.5 Timer mode
4.3.6 Sleep Mode
4.3.7 Super-stand

6. Electrical wiring
6.1 General control
6.2 Change static pressure
44 7.1 Installation sites
7.2 Installation of the external unit
8. Cooling lines
45 8.1 Make flare coupling
8.2 Connecting line between indoor and outdoor units
45 8.3 Insulation of cooling pipes
45 8.5 Installation finishing 45 8.4 Taping pipes
9. Ventilation and test run
9.5 General 46 9.3 Finishing of the guides 46 9.2 Leakage test 45 9.1 Vacuum pump ventilation
47 9.4 Trying
: This symbol refers to a risk that may lead to serious personal injury or death.
: This symbol refers to a risk or unsafe action that could lead to serious
personal injury or death.
: This symbol refers to a risk or unsafe action that may lead to
personal injury and damage to products and buildings. : This refers to comments and instructions on operation, maintenance and operation. WATCH THIS.

New model DC inverter integrated (high-efficiency model) DC inverters integrated model (18 k, 24 k, 36 k)
DC inverter integrated model (48 k, 60 k) On/off integrated model

We recommend that the air conditioner be installed correctly by a qualified installer in accordance with the installation instructions provided for this unit. Before installation, check that the voltage of the power supply in your home or office corresponds to the voltage indicated on the label plate.
This product must not be changed in any way, otherwise this may have consequences such as water leakage, failure, short circuit, electric shocks, fire etc. Work such as welding pipes, etc. must be far removed from vessels with flammable and explosive materials, including air conditioner coolant, to ensure safety at work. To protect the air conditioner from severe corrosion, the outer unit must not be mounted in a place where seawater can splash directly on it or in sulphuric air at a spa. Do not install the air conditioner in a place where there are also devices that generate high heat.
If the power cable is damaged, it must be replaced by the factory or its service department in case of danger. A reliable grounding shall be provided at the location of installation to which the equipment can be connected. Do not connect the earthing of this product to various types of pipes, such as air lines, drains, lightning protection system etc. to avoid electric shocks or damage from other factors. The wiring must be carried out by a qualified electrician. All wiring must comply with local electrical standards. Before installation, check whether the electrical wiring, sockets and the kilowatt-hour meter are adequate. The electrical group to which this product is connected shall have a separate circuit breaker with overvoltage protection supplied for this product.
Please read this manual carefully before using the air conditioner. If you have any problems or difficulties after that, please consult your dealer for help. The air conditioner is designed to provide you with comfortable space conditions. Use the unit only for purpose as described in this instruction manual.
Never use petrol or other flammable substances near the air conditioner, as this presents a major hazard.
Do not turn the air conditioner on and off with the main circuit breaker. Use the ON/OFF button. Do not insert anything into the air intake or exhaust of both indoor and outdoor units. This is dangerous because the fan is running at high speed. Cool or heat the room not too much if there are babies or disabled.

Inside unit (24 k, 36 k, 48 k, 60 k)

The internal and external units are connected to copper pipes, which causes the coolant to flow.
External unit (18 k / 24 k / 36 k)

External unit (48 k, 60 k)
Please note: The images are based on the exterior view of a standard model. The shape of the air conditioner you have chosen may therefore vary.
Inner unit (18 k) · Air intake · Cooling lines



T IMER O FF S ET T IMER A
It is used for controlling current ON/OFF, setting operating condition, temperature, fan speed and other functions.
It is used for control of the wired remote control, setting operating condition, temperature, fan speed and other functions.
NOTE: The standard channel model air conditioner is not supplied with a wireless remote control. If you need one, buy it.
You can control the air conditioner with both wired and wireless remote control.
,

1. Introduction Wired Remote

1 Sensor room temperature: In the remote control, a temperature sensor is set to measure room temperature and this value is sent to the inner unit. If the inner unit does not connect to the remote control, the internal unit will switch to the temperature sensor incorporated into the interior unit.
2 Wireless receiver With this receiver you can use an additional wireless remote control to operate the inner unit. 3 ON/OFF button Press this button to turn the unit on or off. 4 Stand-chooser button Press this button for the selection of COOLS, UNSCHOOLS , VENTILATE, HEAT or AUTO-RUN.
In the COELEN position, the air conditioner will cool the room.
In the ONTV CHART mode, humidity in space is reduced.
In the VENTILEREN position, the air conditioner adjusts the temperature of the room with a gentle flow of air.
In the position WAITING, the air conditioner will warm up the room.
In the AUTO-RUN mode, the air conditioner shall operate according to room temperature.
Press this button to activate sleep mode and . . Press again to disable sleep mode. Press this button for 3 seconds to activate the Timer function. Press again 3 seconds to disable the Timer function. For the Timer functions, see chapter introduction Timer function.
6 FAN SPEED BUTTON: Press this button to change the current fan speed. You can choose between . . (automatic fan speed), .
7 TEMP selector: Press both buttons simultaneously to set the desired room temperature. If you have pressed both buttons, .TEMPERATURE .SET appears on the LCD screen, press . .to lower the set temperature and to increase the set temperatures.


Screen area for indicating the state in which the unit works.
Display fan speed.
Display direction of the valve (in channel type this function is not available).
Display area for the position in which the unit is currently operating.
Display Timer setting.



T IMER O FF


2.1 Stand-up function
2.1.1 Press the Stand-Selection button . . to select operating condition:
2.1.2 Press the ON/OFF . . button to switch on or off the unit. 2.1.3 Pressure on TEMPUS. INSTITUTION . . The temperature range can be set from 18 to 32 °C. 2.1.4 Press the VENTILATOR button . . to set the desired fan speed. Of course you can automatically set ventilation and the inner unit will automatically choose speed by the difference between room temperature and set temperature. 2.1.5 The unit can be turned off by pressing the ON/OFF button .
NOTE: The temperature setting is not available in the ventilation mode.

2.2 Sleep function

Press the timer/sleep button once to activate sleep mode and the sleeping sign . . Press the timer/sleep button again to break this position and the sleep sign will disappear on the LCD screen. NOTE: During the ventilation and car position, sleep function is not available.
2.3 Timer Function
2.3.1 The timer OF 1 You can turn off the timer when the inner unit is working. By holding the TIMER/SLAP button pressed for 3 seconds, the timer will appear on the LCD screen and the ACTIVE OFF symbol will flash. 2 You can adjust the time when the unit automatically switches off by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER OFF-Tip Stopping the flashing and the timers work. 4 If you want to turn off the ACTIVE TIMER OFF, press the TIMER/SLAP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER OFF'S automatically broken down.

2.3.2 The TIMER ON 1 mode You can turn on the timer when the inner unit is not working. By holding the TIMER/SLAP button for 3 seconds, the timer will appear on the LCD screen and the . 2 You can adjust the time when the unit automatically switches on by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER ON-SHAKE indication stops blinking and the timers work. 4 If you want to turn off the ON-SHOT TERM, press the TIMER/SLEEP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER ON .She is automatically broken down.


3. Installation Wired Remote Control
Before installing the wired remote control, please note:


The wired remote control shall be installed by a qualified installer in accordance with the installation drawings. For installation, the power must be switched off. Do not install the wired remote control directly in the air current or at heating. The installation process is as follows. 1 Insert a flat screwdriver into the openings at the bottom (2 pieces). Be careful not to damage the circuit board by screwdriver. 2 Remove the back plate. 3 Use two screws (Ø 4x16) to mount the metal back plate in the right place and then connect the wiring for communication. 4 Click the top of the back plate. 5 Then click on the bottom of the back plate.


The remote control sends signals to the system.
ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.
SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode. DIMMER-KNOP (not available for this model) The brightness of the screen is reduced every time the button is pressed and after four pushes the image disappears.
I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control must be located in a location where the signal can easily be received through the inner unit.) TEMP SCHAKEL-KNOP (not available for this model) Specifies the set temperature flashing when the button is pressed. Indicates the indoor temperature when pressing the button again. The indication can be terminated by pressing the button again.
KNOP KLOCK To set the current time.
ON/OFF TIMER button To set or disable the timer.
SUPER-KNOP (not available for heating mode) To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)
ZACHT-KNOP (only works with DC inverter models) To limit the maximum power consumption, so that you can use the unit together with other electrical devices if there is not enough current.
DEMPEN-KNOP To set or disable the DEMPE mode.
SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right. *Not all remote control models have this button.
Symbols shown on the LCD display:
Autom. fan speed
Set view timer Display current time
Gem. fan speed
Aborting view I FEEL
NOTE: Each position with the relevant functions is explained in more detail on the following pages.


Battery application
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

S ET C LOCK S ET T IMER A
Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.
Remote control · Usage · Receiver signal


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
Range of available temperature setting
18 °C ~ 32 °C
NOTE: The heating mode is not available for models that can only cool.
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow (not available for this model)
Control of the direction of airflow

The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.
The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.
*HEAT ONLY VENT.

I FEEL SOFT 4
DIMMER SMART
SLEEP
MUTE TEP SWITCH
Control of vertical airflow (with remote control)

Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Control horizontal airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.
Operating condition and temperature are determined by the indoor temperature

Lower than T-3 °C
T
T-3 °C ≤ Interior ≤ T+3 °C
T
Higher than T+3 °C
T
Models for cooling only

DIMMER SMART
SLEEP
T+3 °C or less
T
MUTE TEP SWITCH
T Higher than T+3 °C
I FEEL SOFT

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.
What can you do in SLIMME mode?
Uncomfortable due to incorrect air flow
Fan speed changes between high, gem. and down, every time the button is pressed.
Uncomfortable due to incorrect direction of flow
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
Uncomfortable due to incorrect direction of flow
Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.
Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 5 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
(not available in heating mode)

The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.
The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.
NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.
SUPER mode · SUPER position


The remote control sends signals to the system.
ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time..
SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode. I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control shall be located in a location where the signal can easily be received through the internal unit.)
* Note: some remote control models do not have buttons in the square with dotted line.
KNOP KLOCK To set the current time.
DIMMER-KNOP (not available for this model) The brightness of the screen is reduced every time the button is pressed and after four pushes the image disappears.
ON/OFF TIMER button To set or disable the timer.
SUPER-KNOP For setting or turning off the fast cooling/heating. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C. Fast heating works with an automatic fan speed and a 32 °C temperature setting.)
SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right.
Symbols shown on the LCD display:
Autom. fan speed
Set view timer Display current time
Gem. fan speed
NOTE: Each position with the relevant functions is explained in more detail on the following pages.


Battery application
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.
S ET C LOCK S ET T IMER A
Remote control · Usage


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
NOTE: The heating mode is not available for models that can only cool.
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow (not available for this model)
Control of the direction of airflow
The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.






The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.
OFF
COOLING, DRYING
*HEAT ONLY VENT.
MODE FAN
Control of vertical airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
TIMER ON TIMER OFF CLOCK
Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Control horizontal airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.



Operating condition and temperature are determined by the indoor temperature



Lower than T-3 °C
T
T-3 °C ≤ Interior ≤ T+3 °C
T
ON/OFF
Higher than T+3 °C
T
Models for cooling only
SLEEP SUPER
T+3 °C or less
T
SMART FAELE DIMMER
T Higher than T+3 °C
TIMER ON TIMER OFF CLOCK
The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.
What can you do in SLIMME mode?
Uncomfortable due to incorrect air flow
Fan speed changes between high, gem. and down, every time the button is pressed.
Uncomfortable due to incorrect direction of flow
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
Uncomfortable due to incorrect direction of flow
Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.

Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C. Fast heating works with an automatic fan speed, automatically changing the set temperature to 32 °C.
The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. To disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF, SLEEP or TEMPERATURE INSTITUTION.
NOTE: The SLIM button is not available in SUPER mode. The device will continue to work in SUPER mode if you do not break it down by pressing one of the buttons specified above.

The remote control sends signals to the system.

ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.
SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode.
I FEEL-Button To set or disable the I FEel mode.
10 SUPER-KNOP To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)
KNOP KLOCK To set the current time.
ON/OFF TIMER button To set or disable the timer.
Symbols shown on the LCD display:
Shipping signal Display cooling
Autom. fan speed
Set view timer Display current time
Gem. fan speed
Display heating display temperature set
NOTE: When you put the batteries in your remote control for the first time, all indications appear on the LCD screen for a few seconds and then the "Cow" and "warming" indications are displayed sequentially, allowing you to choose "Heating" models and "Coulding" only for cooling models. Each position with the relevant functions is explained on the following pages.


Battery application
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Point the remote to the wired remote control to control the air conditioner. The remote control can operate the wired remote up to 8 m distance, if it is directed towards the receiver of the wire-wired remote.
S ET C LOCK S ET T IMER A
Remote control · Usage


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, the fan speed is automatically on Autom. set, the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
NOTE: The heating mode is not available for models that can only cool.

Press the button, once the signal is received by the device, the display that the inner unit works will light up. (This model has no display for operation.)
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, SLEEP, KLOCK and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow (not available for this model)
Control of the direction of airflow

The vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.

The direction of the airflow can also be adjusted to your own requirements by pressing the SWING button on the remote control.
COOLING, DRYING
SUPER
SMART
*HEAT ONLY VENT.
TIMER ON
TIMER OFF
SLEEP
CLOCK
I FEEL
*The heating mode is only available for heat pump models.
Control of vertical airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
By pressing the SWING button, the horizontal air valve will automatically swivel up and down.
By pressing the SWING button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal valve manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.

Fan speed changes between high, gem. and down, every time the button is pressed.
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.
SLIMME mode

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.
Press the button once to increase or decrease time by 1 minute. Press the or button for one and a half seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR, DROGEN or SLIM. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.


The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.
SMART
FAN MODE
TIMER ON
TIMER OFF
SLEEP
CLOCK
I FEEL
NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.
SLEEP mode · SUPER mode ·Super mode

3 minutes of protection after a stop from the compressor. To protect the compressor, after a stop the compressor cannot be switched on for at least 3 minutes.
Five minutes of protection. The compressor must operate at least 5 minutes after it is switched on. In these 5 minutes, the compressor will not stop even if the room temperature has reached its set value unless you switch off the unit using the remote control (all units disabled by the user).
Cooling function. In the cooling mode, temperature can be set between 18-32 °C. The fan of the inner unit will never stop working. It's gonna keep working even if the compressor stops.
Heating function. Because the air conditioner heats through outdoor heating (with the heat pump), it can reduce its heating capacity if the outside temperature is too low. If the effect of heating is not sufficient, an additional heater shall be used.
Anti-freeze function in cooling. If the temperature of the air outlet in the inner unit is too low, it will work with only the fan for some time to prevent freezing or ice forming inside the heat exchanger.
Prevention of cold air. The fan of the internal unit will not rotate for a few minutes after heating is switched on until the heat exchanger of the inner unit has reached an adequate temperature. The system to prevent a cold air flow is then in operation.
De-shooting. If the outside temperature is too low, freezing or ice formation can occur in the heat exchanger outside which reduces heating performance. The air conditioner defrosting system will then enter into force. At the same time, the fan of the indoor unit (or in some cases runs at very low speed) stops and when a few minutes later the defrosting is ready, the heating will start again.
Blowing out of residual heating air. If the air conditioner stops working normally, the fan engine will run at low speed for a while to blow out the remaining air.
Self-recover after power failure If the power supply is restored following a malfunction, all settings are still active and the air conditioner works according to original settings.
If the power supply is restored after a malfunction, all settings are still active and the air conditioner works according to the original settings.
6.1 If problems persist... If problems persist after you have checked the following, please contact your supplier and provide the following information. (1) Model name unit (2) Description of the problem.
6.2 No action Check that SET TEMP is set to the right temperature.

6.3 No good cooling or heating Check that the air flow of external or internal units is blocked. Check that there is an additional heat source in the room. Check that the air filter is highly contaminated with dust. Check if windows and doors are open or not. Check that the temperature conditions are outside the scope of operation.
6.4 This is very normal Scent from the inner unit After a longer period of time, an odour can be secreted by the internal unit. Then clean the air filter and panels or let it ventilate properly. Sound due to distortion of parts During the startup or stop of the system, a abrasive sound can be heard. This is due to the thermal deformation of plastic parts. This is perfectly normal. Steam from the heat exchanger of the outer unit During thawing, ice is melted on the heat-exchanger of an external unit and thus steam is generated. Air vent condensation If cooled for a longer period of time under conditions with high humidity (higher than 27 °C/80% RV), condensation can form on the air grid. Sound flow coolant During the start-up or stopping of the system, a sound can be heard from the flow of the coolant.

1. Flow diagram coolant

Note: The EEV only applies to the DC inverter air conditioner, use for other air conditioners a fixed expansion valve. The accumulator only applies to the 48 k and 60 k air conditioners.
DC inverter integrated model:
On/off integrated model:
N
SI
SI
N N
N
N
Power supply 18 k/24 k/36 k
N
N
N
SI
SI
SI
SI
W
N
U
N
48 k/60 k Inside unit
N
SI
SI
W
U
N
36 k/48 k/60 k

1. Safety instructions
· The installation must be carried out by the dealer or another expert person. (Incorrect installation can cause water leakage, electric shocks, or fire.) Install the unit according to instructions in this manual. (Incomplete installation can cause water leakage, electric shocks, or fire.) Use only the standard included or specified installation components. (Use of other components can cause the unit to break down, water leakage, electric shocks or fire.) Install the air conditioner on a solid base that can carry the weight of the unit. (An unsuitable substrate or faulty installation may cause injury if the unit falls.) Electrical work must be carried out in accordance with the installation manual and local regulations and guidelines for electrical wiring. (Insufficient capacity or inadequate electrical work can cause electric shocks or fire.) Make sure to use a separate electrical group. (Never use a shared power supply with another device.) Use for the wiring a cable long enough to last all length without connecting and do not use an extension cord. Do not connect any other load on the power supply, use a separate group. (If you do not, this may lead to abnormal heat development, electric shocks or fire.) Use the required types of wiring for electrical connections between indoor and outdoor units. (Connect the connecting wires firmly so that there is no external voltage on the connection blocks.) Inappropriate fitting or clamping can result in overheating of the connector block or fire. After connecting connections and the power cable, they shall be securely secured so that no forces are applied to the covers or electrical panels. (Install a wire cover, incorrect installation of this device can cause overheating of the connection block, electric shocks or fire.) No other substances such as air may enter the cooling circuit when installed or moved than the prescribed coolant (R410A). (The presence of air or other undesirable substances in the cooling circuit causes an abnormal pressure increase or break, which can cause injury.) If coolant has leaked during installation work, space must be ventilated. (The coolant produces a toxic gas when exposed to flames.) When the entire installation is ready, it must be checked that no coolant leaks. (The coolant produces a toxic gas when exposed to flames.) When connecting the pipes, make sure that no air or other substances than the declared coolant enter the cooling circuit. (Otherwise this can reduce capacity, cause abnormally high pressure in the cooling circuit, explosion or injury.) Make sure to make a grounding. Do not connect the ground to a utility line, lightning distraction or phone earthing. Incorrect earthing can cause electrical shocks. (A high peak current due to lightning or other causes can cause damage to the air conditioner.) Depending on local conditions, an earth leak switch may be necessary to avoid electric shocks. (If you do not, this may lead to electric shocks.) Shut down the power supply before connecting the wiring or pipes or checking the unit. If the internal and external unit is moved, ensure that the outer unit is not tilted by more than 45°. Make sure you do not suffer any injury due to the sharp edge of the air conditioner. Install the remote. Make sure that the length of the wiring between inside unit and remote control is less than 50 m.
· Do not install the air conditioner in a place where there is a risk of exposure to flammable gases. (If gas leaks and collects around the device, this can cause fire. Install the drains according to instructions in this manual. (Incorrect pipes can cause water pollution.) Turn the nuts on with a torque wrench in accordance with the prescribed procedure. (If the screw nut is tightened too tight, it may break over time and cause coolant leakage.)

2. Installation tools and instruments

During installation, the installation material on the surface of the interior unit shall not be damaged.
3.1 The first check
· If the unit is moved when unpacking or after, it must be lifted at the handles. Do not apply pressure to other components, in particular the cooling pipes, drain pipe and flanged parts. Wear protective clothing (gloves, etc.). ·
Model Capacity (Btu/h) h (mm)
Space for maintenance Fig. 3.2.1
36 k 48 k 60 k 350

Model Capacity (Btu/h) h (mm)
24 k 270 36 k
Afb. 3.2.2

When installing the unit make sure that: An optimal air distribution is ensured. The air passage is not blocked. Condensation water can be well disposed of. The ceiling is strong enough for the weight of the unit. A lowered ceiling does not run below a slope. There is sufficient space for maintenance and repair (see Fig.3.2.1 and. 3.2.2). The pipes between the inside and outside unit are within the permitted limits (see installation instructions of the outer unit). The inner unit, external unit, power cable and transmitters are at least 1 m away from television and radio to prevent interference in the image and sound of electrical devices. (Even if the limit of 1 m is maintained, noise disturbances can occur depending on the conditions under which electric waves are produced.) Hanging bolts are used for installation and that the ceiling is strong enough to account for the weight of the unit. If the ceiling does not appear to be strong enough, it must be reinforced before installing the unit.
3.2 Installation
3.2.1 Hanging bolts
(1) Carefully look at the direction of pipes, wiring and maintenance, and choose the right orientation and location for installation. (2) Install the hanging bolts as shown in Figure 3.3.1 below.

In the case of suction at the bottom, the air chamber cover and inlet flange shall be replaced on the side as indicated in Fig. 3.2.3 (1) Remove the inlet flange on the side. Remove the lid from the air chamber. (2) Re-connect the air chamber cover and inlet flange to orientation as indicated in Fig. 3.2.3. See Figure 3.2.4 for the orientation of the inlet flange.
Fig. 3.3.1 Confirmation of the hanging bolts
3.2.2 The position of the hanging bolts and pipes (1) Indicate the position of suspension bolts and the position for cooling pipes and drains. (2) The dimensions are shown below in Fig. 3.3.2 indicated.


Air Room Lid
Air Room Lid
a b c d e f g h i j k L m n
Filter (not available for this model)
DC-inverter model 1207 1170 154 447 971 117 1039 170 117 150 199 13 81 84
On/off integrated model 937 900 154 447 701 117 1235 170 117 150 199 13 81 84
Afb. 3.2.4

a b c d e f g h i j k L m n o p 24 k 934 900 669 720 805 222 835 228 242 294 378 405 25 156 202 214 36 k DC-inverter model 1334 1295 669 720 1205 222 1235 228 242 294 378 405 25 156 202 214 36 k Aan/Uit geïntegreerd 1334 1295 740 796 1205 222 1235 228 237 312 375 405 25 204 203 242 48 k & 60 k 1334 1295 740 796 1205 222 1235 228 237 312 375 405 25 204 203 242
(2) Installation of the inner unit Place the left hanging bracket on the nuts with a chain at the hang bolt, as shown in Figure 3.7. Make sure that the left hanging bracket is firmly attached to the nuts and studs, then install the right hanging mount on the screwed hanger with screws and rings.

(When installing the inner unit, you can unscrew the suspension bolts.)

Fig. 3.4 Hanging bolts
Fig. 3.7
3.3.3 Installation of the inner unit 3.3.4 Horizontal adjustment of the interior unit (1) Make sure that the suspension bracket is attached with the nut and a tail ring. (2) Adjust the height of the unit. (3) Check that the unit is horizontal.
The installation of the inner unit is shown in Fig. 3.5
Hanging bolts (4 x M10) (third party delivery)
nuts and tracking rings (4 x M10) (third party supply)
Fig. 3.8
(4) After adjustment, tighten the nut and apply a threading device to the screw-on bolt to prevent nuts from loosening.
Fig. 3.5 Installation of the internal unit
(1) Attach the screw and nut suspension as shown in Fig 3.6, there are four nuts.
(1) Cover the unit during installation with a piece of plastic to keep it clean. (2) Make sure that the unit is mounted horizontally using a level or plastic tube filled with water. When using a plastic tube, the top of the unit must be kept equal to the top end of the water at both ends of the pipe and then the unit can be adjusted horizontally. (In particular, care should be taken to ensure that the unit is not tilted towards the drain line as this may cause leakage.)

Fig. 3.6 Hanging bolts and nuts
(mm) · Air intake · Suspension bracket

3.3.5 Installation of the channel

Make sure that the range of external static pressure of the unit is not exceeded. Connect the channel to the inlet and exhaust flange. See example in Fig. 3.9
Fig. 4.2 The pipe diameters
Pressure cabinet Flexible channel Pressure box
(2) Turn the nuts with two keys as shown in Fig. 4.3 is indicated.

Only use R410A coolant. When performing the leak control and test, you should ensure that oxygen, acetylene and other flammable and virulent gases do not mix together as they are dangerous and can cause an explosion. It is recommended to use compressed air, nitrogen or coolant for this purpose.
Fig. 4.3 Aging moment
(3) When the connections of the cooling line are rounded off, insulation material shall be provided to the pipes. See example in Fig. 4.4
4.1 Materials for pipes (1) Prepare the copper lines on site. (2) Use dust-free, dry and clean copper pipes. Blow these clean with nitrogen or dry air before installing the pipes to remove dust and impurities. (3) Select the copper pipes according to Fig. 4.2.

Side of the inner unit
4.2 Connections of the pipes
Fig 4.4 Insulation method of pipes
(1) The connection positions of the pipes are shown in Fig. 4.1.
Leads passing through a spar, kitten. Do not place the ends of the pipes directly on the floor as shown in Fig 4.5.
Do not place the ends of the pipes directly on the floor,
Protect it with tape or a plug.
Fig. 4.1 Connection positions of the pipes
Fig. 4.5

5. Drain
The two parts mentioned below should be isolated because condensation can form that may drizzle. a. Pipes fed through walls. b. Drain connections. Isolate the drain connection and drain hose with the supplied large insulation strip as shown in the picture below.
Connection of the drain pipe ·

Make sure the drain works properly. The diameter of the outlet connection shall be the same as that of the drain pipe itself. Keep the drain short and apply at least 1:100 discharge so that water is properly discharged. See image below.
Fig. 5.4
Connections drain pipe Do not directly connect the drainage to sewage pipes in which ammonia gas is present. The ammonia gas in the sewage system can enter the internal unit via the drain pipe and cause corrosion of the heat exchanger. Make sure that there are no blows or nods in the drain hose, so that no great forces are applied. This could cause leakage. After the pipework is finished, check that the pipes are properly removed. Pour about 1000 ml of water evenly into the condensate container to check that the drain works as indicated above. Pour about 1000 ml of water evenly through the drain hole into the condensate container to check the drainage. Check the drain as shown in picture below.

Water that can collect in the drain pipe may cause blockage of the pipe. To prevent the snake from going down, this one has to be h.o.h. Hanging 1 - 1,5 m. Use the drain hose and clamp. Slide the drain hose completely over the outlet and attach the hose together with the insulation material by means of the clamp.


6. Electric wiring
6.1 General control

Fig. 6.1 Remove the screws from the control cabinet
Cover cover electric control

6.2 Changing static pressure The static pressure outside the inner unit can be set.
6.2.1 Models 24 k & 36 k excluded (high-efficiency DC inverter model): You can change the static pressure by changing the connection block of the fan engine, as shown in Fig. 6.2.
Low static pressure 10 Pa
High static pressure 30 Pa
Fig. 6.2
18 k 30 Pa 10 Pa
24 k, 36 k 48 k, 60 k 80 Pa 120 Pa 50 Pa 80 Pa
NOTE: The default factory setting is the low static pressure. The noise level at high static pressure is higher than at low static pressure.
6.2.2 Models 24 k & 36 k (high-efficiency DC inverter model):
Standard static pressure is 30 Pa. The static pressure can be freely set between 1 and 80 Pa by using the wired remote control. For the setting details see the manual of the wired remote control. If you have any problems with this, please contact our local technical maintenance service for more information.

7. Installation of the external unit

7.1 Place of installation
Avoid:

Direct sunlight A corridor or sideways Thick oil mist installation Wet or irregular places Holder with flammable materials Near a heat source / fan
Do it:

Put it in a cool place. Put it in a place with good ventilation. Keep the desired distances for air intake, exhaust and maintenance. (Afb. 7.1) Make a strong base (10x40 cm2 of concrete or equivalent). The device must be placed at least 10 cm higher so that it does not get wet or corrosion occurs, otherwise this can cause damage to the appliance and reduce its lifespan. (Afb. 7.2) Attach the base with hae cancers or equivalent to reduce noise and vibration.
*For 24 k (high-efficiency DC inverter model): The line length between inside and outside unit is the same as for 36 k models.
If the total line length is between 5 and 50 m (max. The length of the test is equal to or greater than 1 mm. There is no need to add compressor oil. (Afb. 7.3)
Fig. 7.3
7.2 Installation of the external unit. First select the installation location and confirm the outer unit. If it needs to be attached to a wall, make sure that the wall and supporting rack is strong enough to carry the weight of the device.

Remove the fixing screws from the cover of the electrical connection box and remove it (if the cover is in the valve), remove them. Connect the wiring of the inner unit to the outer unit panel according to electrical wiring schematics. Make sure that each wire is 10 cm longer than the length required for wiring. Connect the unit to grounding according to local electrical regulations. Check the wiring with the schematics and make sure it's properly connected. Secure the wiring with clamps and re-enable the cover.
Fig. 7.1

Fig. 7.2

8. Cooling lines
The two cooling lines (and the electrical wiring if permitted by local standards) must be bound together with protective tape. The drain hose can also be carried and bundled with the pipes. Wrap the protective tape around the pipes from the bottom of the outer unit to where the pipes go through the wall. Wrap the tape around the pipes with each overlapping of half a width of the tape. (see Fig. 8.7) Attach the bundle against the wall with saddles h.o.h. approx. 120 cm.
8.1 Connecting Flare to flare tool
Note: A good flare connection has the following properties: The surface of the inside is shiny and smooth. The edge is smooth. The oblique sides are of equal length.
Remove the blackberries at the end of the copper tube with a larger or file. Keep the end of the tube down at fileting so that no filings will enter the tube. These operations are important and must be carefully performed to make a good flare connection (pict. 8.1 and 8.2). Remove the screw nut from the unit and slide it onto the copper tube. Make the flare connection at the end of the copper tube with the flare tool (fig. 8.3).
8.5 Finishing the installation
After completing taps and insulation, the hole in the wall should be sealed with a suitable kit against wind and rain.
8.2 Connecting line between indoor and outdoor units
Air and moisture remaining in the cooling system have undesirable effects. They should therefore be completely removed by performing the following steps.
Make sure to use a seal cap or waterproof tape to prevent any water or dust from entering the pipes before they are used. Ensure a thin layer of coolant is applied to the surfaces of the flare connection that are connected before they are coupled. This way gas leaks are reduced. For a good connection, apply both tubes in each other and then screw the nut manually to get a perfect connection. (Afb. 8.5) Turn the nuts with a torque wrench to prevent coolant leakage. Test carefully for leakage before the unit is put into operation.
9.1 Aeration with a vacuum pump (see Fig. 9.1, 9.2)
(1) Check that each pipe (both thin and thick pipes between indoor and outdoor units) is well connected, and all wiring for test turning is complete. Please note that all valves of the pipes on the outer unit are closed at this stage. (2) Remove the cap of the main valve using an English key or ring key. (3) Connect a vacuum pump to the main valve. (4) Turn on the vacuum pump until pressure is lower than 15 Pa (or 1,5×10-4 bar) for 5 minutes. (5) Remove the vacuum pump from the main valve while still running. Then stop the vacuum pump. (6) Re-apply the cover cap to the main valve and tighten it firmly with an English key or ring key. (7) Remove the cover cap of both small and large valve using an English key or ring key. (8) With a bus key, fully open the valve of the small and large pipe valve against the clock. (9) Re-apply the covers to the small and large valve and tighten them firmly with an English key or ring wrench.
8.3 Heat insulation of the cooling line
To prevent heat loss and wetness of the floor by condensation, all cooling pipes shall be insulated with an appropriate insulation material having a minimum thickness of 6 mm (see Fig. 8.6).
8.4 Taping of pipes
Note: Wind the protective tape not too tight to reduce the thermal insulation. Make sure that the condensate water drain hose runs separately from the beam at a given time and is discharged as described above.

9.2 Leakage test

Check all connections and valves of indoor and inner unit with liquid soap. The cover of the filling opening shall be checked for at least 30 seconds. Remove all soap residue after the test to prevent it from affecting copper pipes.
9.3 Finishing of the pipes

If the leakage test is satisfactory, the heat insulation shall be re-established at the connections. Apply the connecting lines straight and attach them tightly to the wall. Close the space around the pipes that run through the spar in the wall with a sealing material.
9.4 Test twisting
The test shall be carried out in accordance with the installation and maintenance manual.
Only after all checkpoints have been checked can the unit be put into operation. (1) Check that the resistance of the connection to earth is more than 1 MΩ, otherwise you cannot use the unit until the point where electricity leaks has been found and repaired. (2) Check that the valve is open before using the unit.

Make sure the outside unit is running properly and then switch on the inside unit. Turn the device on and set it to cooling, drying or heating depending on room temperature. Check that the device is working properly.
The installation of the device is usually completed when the above points are executed. If you have any problems with this, please contact our local technical maintenance service for more information.
Fig. 8.1
Fig. 8.2
For Na · Leader · Larger

9.5 General
Use an earth leak switch, otherwise this can cause electric shock or fire. Do not use the system until all checkpoints are resolved. (1) Check that the insulation resistance is more than 1 MΩ by measuring the resistance between earth and electrical components. If not, the system should not be switched on until the point where electricity leaks has been found and repaired. (2) Check that the valves of the outside unit are fully open and then start up the system. Note the following when the system is running. (1) Do not touch any of the components from the gas outlet side manually, as the compressor chamber and drain pipe are heated to a temperature above 90 °C. (2) DO NOT PRESS THE BUTTON OF THE MAGNETIC SWITCH(S). This could cause a serious accident.
Power supply EN60 335-1 EN60 3351
dimensions of power cable off. Control cable
18 k (On/off integrated model)
220~240 V, 50 Hz 3x1,5 mm2 5x1,5 mm2
18 k (DC inverter integrated model)
220~240 V, 50 Hz
24 k 36 k (DC inverter integrated model)
220~240 V, 50 Hz
5x1,5mm2 4x0,75 mm2
36 k (On/off integrated model)
380~418 V, 50 Hz
42 k/48 k/60 k
380~418 V, 50 Hz
NOTES: 1) Follow local standards and regulations when choosing the wiring. 2) The dimensions of the wiring specified in the table are determined at maximum flow rate for the unit according to European standard EN60 335-1. Use cables that are not lighter than the normal flexible cable with hard rubber mantle or regular flexible cable using polychloroprene cloak (type H07RN-F). 3) Use a shielded cable for the transmitter cable and connect it to the ground. 4) If power cables are connected in series, the maximum current of each unit must be added together and then the cable is selected from the table below.
Selection according to EN60 335-1 Current i (A) Wire size (mm2)
*If the current exceeds 63A, cables must not be switched in series. 5) To comply with the standard EN 61000-3-11, the system must be connected to a power supply with an impedance of: .Zsys≤0.247 Ω (for 18 k On\From integrated model) . Zsys =0,209 Ω ("for 24 k On" from integrated model). Before connecting the product to the public electricity grid, check with local energy companies if the network meets the above requirements.

INNER UNIT PACKAGING LIST
No. NAME NUMBER
INSIDE ACCESSORIES 1
INSIDE ACCESSORIES 2
INSIDE ACCESSORIES 3*
MANUAL
WIRED REMOTE CONTROL
* Not available for 18 k-models.
No. NAME NUMBER
DRAINAGE BEND
Correct removal of this product.
This indication indicates that this product must not be disposed of with ordinary household waste throughout the EU. In order to prevent damage to the environment or health caused by uncontrolled waste disposal, it should be recycled responsibly and promote sustainable reuse of materials. Return the used device by using return and collection systems or contact the dealer where the product was purchased. They can recycle this product in an environmentally friendly way.
Climate Solutions B. V. Exclusive Hisense Importer Benelux
HS Climate Solutions B. V. Carnelian 400 3316 KC Dordrecht
e. [email protected] w. www.hs-cs.nl t. 088-4355450 f. 088-4355451
SK No 60753986 IBAN No EN92ABNA0443804362 VAT NO. EN854044954B01
Version number 20150101-EN The design and specifications can be changed without further notice. Images and diagrams are for information purposes only, and may be modified without further notice.