SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 1p.1SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 2p.2SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 3p.3SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 4p.4SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 5p.5SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 6p.6SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 7p.7SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 8p.8SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 9p.9SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 10p.10SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 11p.11SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 12p.12SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 13p.13SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 14p.14SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 15p.15SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 16p.16SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 17p.17SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 18p.18SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 19p.19SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 20p.20SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 21p.21SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 22p.22SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23p.23SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24p.24SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 25p.25SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 26p.26SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 27p.27SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 28p.28SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 29p.29SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 30p.30SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 31p.31SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 32p.32SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 33p.33SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 34p.34SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 35p.35SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 36p.36SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 37p.37SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 38p.38SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 39p.39SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 40p.40SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 41p.41SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 42p.42SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 43p.43SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 44p.44SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 45p.45SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 46p.46SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 47p.47SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 48p.48SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 49p.49
Page 1 of the Hisense AUD-36 user manual — USE INSTALLATION INSTRUCTIONS
Page 1 · click to enlarge
Page 1
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 1 diagram (page 1)
Fig. 1

USE INSTALLATION INSTRUCTIONS

TYPE: AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1 AUD-18HX4SUNL AUD-24HX4SZLH AUD-36HX6SAHH AUD-48HX6SPHH AUD-60HX6SPHH

Thank you for buying this air conditioner. Please read these instructions carefully before installing and using this device, save it for later use.

Page 2 of the Hisense AUD-36 user manual — DC inverter integrated air conditioner
Page 2 · click to enlarge
Page 2

We warmly welcome you as a user of our product! We thank you for your trust in us. Read this manual carefully before installation. Keep this manual safe for later use after installation.

Characteristics of this air conditioner

Little space for installation is needed. The interior unit can easily be installed in the ceiling space.

Silent operation. The excellent fan design ensures a quiet and even airflow with little noise.

Optional static pressure 18 k: optional 10 Pa / 30 Pa, 24 k and 36 k: 50 Pa / 80 Pa

Meets various installation requirements. Often the type with air intake at the rear is applied depending on the actual space for installation. The unit is also supplied with air inlet at the bottom, with sound rising to about 5-6 dB.

(for the high-efficiency type a free choice of 1~80 Pa), 48 k / 60 k: 80 Pa / 120 Pa static pressure. One unit with multiple optional installation methods.

Highly efficient and environmentally friendly new coolant R410A. R410A protects the environment and can not harm the ozone layer.

Self-recovering after power failure. If the power supply is restored after a malfunction, all settings are still active and the air conditioner works according to the original settings.

On and off 24-hour timer. This timer can be set to automatically switch on or off the unit per day.

Self-diagnostic function in case of malfunction. If there is something wrong with the air conditioner, the microprocessor will examine the malfunction and then it can be read on screen for convenience in maintenance. MODEL DEVICE

DC inverter integrated air conditioner

On/off integrated air conditioner

AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH

AUD-18HX4SUNL AUD-24HX4SZLH AUD-36HX6SAHH AUD-48HX6SPHH AUD-60HX6SPHH

New DC inverter integrated air conditioner (high-efficiency model)

AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1

Page 3 of the Hisense AUD-36 user manual — Circuit diagram
Page 3 · click to enlarge
Page 3

CONTENTS

Composition of the air conditioner

Control manual remote control

1. Introduction Wired Remote 7 7
2. Control with the wired remote 9 9

2.1 Stand-up function

2.2 Sleep function

10 10 10 3. Installate wired remote 11 11

2.3 Timer Function

4. Introduction wireless remote control 12 12 12

4.1 Remote control H1

4.1.1 Operating status 14 14 14

4.1.2 Control of airflow 15 15 15

4.1.3 Smart stand 16 16 16

4.1.4 Clock setting 16 16 16

4.1.5 Timer stand 17 17 17

4.1.6 Sleep Mode 18 18 18

4.1.7 Super-stand 18 18 18

4.2 Remote control J1

4.2.1 Operating status

4.2.2 Airflow control

4.2.3 Smart Stand

4.2.4 Clock setting

4.2.5 Timer mode

4.2.6 Sleep Mode

4.2.7 Super-stand

4.3 Remote control E4-07

4.3.1 Operating status

4.3.2 Control of airflow

4.3.3 Smart stand

4.3.4 Clock setting

4.3.5 Timer mode

4.3.6 Sleep Mode

4.3.7 Super-stand

5. Special comments
6. Problem solving

Circuit diagram

1. Flow diagram coolant
2. Scheme of electrical wiring
Show 25 more labels / short text on this page
3 3 3 · 5 5 5 · 9 9 9 · 10 10 10 · 12 12 12 · 19 19 19 · 21 21 21 · 22 22 22 · 23 23 23 · 23 23 23 · 24 24 24 · 25 25 25 · 25 25 25 · 26 26 26 · 28 28 28 · 29 29 29 · 30 30 30 · 30 30 30 · 31 31 31 · 32 32 32 · 32 32 32 · 33 33 33 · 33 33 33 · 35 · 35
Page 4 of the Hisense AUD-36 user manual — CAREFUL
Page 4 · click to enlarge
Page 4

CONTENTS

Installation and maintenance

1. Safety instructions
2. Installation tools and instruments
3. Installation of the interior unit 3.1 The first check 3.2 Installation
4. Cooling lines 4.1 Guide material 4.2 Connection of the pipes
5. Drain

6. Electrical wiring

6.1 General control

6.2 Change static pressure

7. Installation of the external unit

44 7.1 Installation sites

7.2 Installation of the external unit

8. Cooling lines

45 8.1 Make flare coupling

8.2 Connecting line between indoor and outdoor units

45 8.3 Insulation of cooling pipes

45 8.5 Installation finishing 45 8.4 Taping pipes

9. Ventilation and test run

9.5 General 46 9.3 Finishing of the guides 46 9.2 Leakage test 45 9.1 Vacuum pump ventilation

47 9.4 Trying

DANGER

: This symbol refers to a risk that may lead to serious personal injury or death.

: This symbol refers to a risk or unsafe action that could lead to serious

WARNING

personal injury or death.

: This symbol refers to a risk or unsafe action that may lead to

CAREFUL

personal injury and damage to products and buildings. : This refers to comments and instructions on operation, maintenance and operation. WATCH THIS.

  • This air conditioner is designed for the following temperatures and must operate within this range.
Diagram . .
Diagram . .

New model DC inverter integrated (high-efficiency model) DC inverters integrated model (18 k, 24 k, 36 k)

External temperatures (°C) maximumminimum Cooling function48-15 Heating function24-10
External temperatures (°C) maximumminimum Cooling function4315 Heating function24-10

DC inverter integrated model (48 k, 60 k) On/off integrated model

External temperatures (°C) maximumminimum Cooling function4315 Heating function24-10
External temperatures (°C) maximumminimum Cooling function48-15 Heating function24-10
Show 13 more labels / short text on this page
36 · 37 · 37 · 37 38 · 40 · 40 · 40 · 41 · 42 · 44 · 44 · 45 · 46
Page 5 of the Hisense AUD-36 user manual — CAREFUL
Page 5 · click to enlarge
Page 5

Warnings

We recommend that the air conditioner be installed correctly by a qualified installer in accordance with the installation instructions provided for this unit. Before installation, check that the voltage of the power supply in your home or office corresponds to the voltage indicated on the label plate.

DANGER

This product must not be changed in any way, otherwise this may have consequences such as water leakage, failure, short circuit, electric shocks, fire etc. Work such as welding pipes, etc. must be far removed from vessels with flammable and explosive materials, including air conditioner coolant, to ensure safety at work. To protect the air conditioner from severe corrosion, the outer unit must not be mounted in a place where seawater can splash directly on it or in sulphuric air at a spa. Do not install the air conditioner in a place where there are also devices that generate high heat.

WARNING

If the power cable is damaged, it must be replaced by the factory or its service department in case of danger. A reliable grounding shall be provided at the location of installation to which the equipment can be connected. Do not connect the earthing of this product to various types of pipes, such as air lines, drains, lightning protection system etc. to avoid electric shocks or damage from other factors. The wiring must be carried out by a qualified electrician. All wiring must comply with local electrical standards. Before installation, check whether the electrical wiring, sockets and the kilowatt-hour meter are adequate. The electrical group to which this product is connected shall have a separate circuit breaker with overvoltage protection supplied for this product.

Please read this manual carefully before using the air conditioner. If you have any problems or difficulties after that, please consult your dealer for help. The air conditioner is designed to provide you with comfortable space conditions. Use the unit only for purpose as described in this instruction manual.

WARNING

Never use petrol or other flammable substances near the air conditioner, as this presents a major hazard.

CAREFUL

Do not turn the air conditioner on and off with the main circuit breaker. Use the ON/OFF button. Do not insert anything into the air intake or exhaust of both indoor and outdoor units. This is dangerous because the fan is running at high speed. Cool or heat the room not too much if there are babies or disabled.

Page 6 of the Hisense AUD-36 user manual — Composition of the air conditioner
Page 6 · click to enlarge
Page 6

Composition of the air conditioner

Inside unit (24 k, 36 k, 48 k, 60 k)

Diagram . .
Diagram . .

The internal and external units are connected to copper pipes, which causes the coolant to flow.

External unit (18 k / 24 k / 36 k)

Diagram . .
Diagram . .

External unit (48 k, 60 k)

Please note: The images are based on the exterior view of a standard model. The shape of the air conditioner you have chosen may therefore vary.

Inner unit (18 k) · Air intake · Cooling lines

Page 7 of the Hisense AUD-36 user manual — , Wired remote control Wireless remote control
Page 7 · click to enlarge
Page 7

Composition of the air conditioner

Diagram . .
Diagram . .
Diagram . .
Diagram . .

T IMER O FF S ET T IMER A

, Wired remote control Wireless remote control

It is used for controlling current ON/OFF, setting operating condition, temperature, fan speed and other functions.

It is used for control of the wired remote control, setting operating condition, temperature, fan speed and other functions.

NOTE: The standard channel model air conditioner is not supplied with a wireless remote control. If you need one, buy it.

You can control the air conditioner with both wired and wireless remote control.

,

Page 8 of the Hisense AUD-36 user manual — AUTO
Page 8 · click to enlarge
Page 8

Wired remote control

1. Introduction Wired Remote

Diagram . .
Diagram . .

1 Sensor room temperature: In the remote control, a temperature sensor is set to measure room temperature and this value is sent to the inner unit. If the inner unit does not connect to the remote control, the internal unit will switch to the temperature sensor incorporated into the interior unit.

2 Wireless receiver With this receiver you can use an additional wireless remote control to operate the inner unit. 3 ON/OFF button Press this button to turn the unit on or off. 4 Stand-chooser button Press this button for the selection of COOLS, UNSCHOOLS , VENTILATE, HEAT or AUTO-RUN.

In the COELEN position, the air conditioner will cool the room.

In the ONTV CHART mode, humidity in space is reduced.

In the VENTILEREN position, the air conditioner adjusts the temperature of the room with a gentle flow of air.

In the position WAITING, the air conditioner will warm up the room.

In the AUTO-RUN mode, the air conditioner shall operate according to room temperature.

A

Press this button to activate sleep mode and . . Press again to disable sleep mode. Press this button for 3 seconds to activate the Timer function. Press again 3 seconds to disable the Timer function. For the Timer functions, see chapter introduction Timer function.

6 FAN SPEED BUTTON: Press this button to change the current fan speed. You can choose between . . (automatic fan speed), .

AUTO

7 TEMP selector: Press both buttons simultaneously to set the desired room temperature. If you have pressed both buttons, .TEMPERATURE .SET appears on the LCD screen, press . .to lower the set temperature and to increase the set temperatures.

Show 9 more labels / short text on this page
LCD display · Wireless receiver · ON/OFF button · Adjuster button TEMP · stand button · VENTILATOR NICE / CLEPT button · TIMER/SLAP button · Sensor room temperature · 5 TIMER/SLAP button
Page 9 of the Hisense AUD-36 user manual — T IMER O N
Page 9 · click to enlarge
Page 9

Wired remote control

Diagram . .
Diagram . .

Screen area for indicating the state in which the unit works.

Display fan speed.

Display direction of the valve (in channel type this function is not available).

T IMER O FF S ET T IMER A

Display area for the position in which the unit is currently operating.

Display Timer setting.

Diagram . .
Diagram . .
Diagram . .
Diagram . .
Diagram . .
Diagram . .

T IMER O N

T IMER O FF

Diagram . .
Diagram . .
Show 4 more labels / short text on this page
8 LCD display · Timer ON · Timers OFF · Setting Timer
Page 10 of the Hisense AUD-36 user manual — A
Page 10 · click to enlarge
Page 10

Wired remote control

2. Control with the wired remote control

2.1 Stand-up function

2.1.1 Press the Stand-Selection button . . to select operating condition:

A

2.1.2 Press the ON/OFF . . button to switch on or off the unit. 2.1.3 Pressure on TEMPUS. INSTITUTION . . The temperature range can be set from 18 to 32 °C. 2.1.4 Press the VENTILATOR button . . to set the desired fan speed. Of course you can automatically set ventilation and the inner unit will automatically choose speed by the difference between room temperature and set temperature. 2.1.5 The unit can be turned off by pressing the ON/OFF button .

NOTE: The temperature setting is not available in the ventilation mode.

Show 5 more labels / short text on this page
Cooling function · Dehumidification function · Ventilation function · Heating function · Automatic mode
Page 11 of the Hisense AUD-36 user manual — Wired remote control
Page 11 · click to enlarge
Page 11

Wired remote control

2.2 Sleep function

Diagram . .
Diagram . .

Press the timer/sleep button once to activate sleep mode and the sleeping sign . . Press the timer/sleep button again to break this position and the sleep sign will disappear on the LCD screen. NOTE: During the ventilation and car position, sleep function is not available.

2.3 Timer Function

2.3.1 The timer OF 1 You can turn off the timer when the inner unit is working. By holding the TIMER/SLAP button pressed for 3 seconds, the timer will appear on the LCD screen and the ACTIVE OFF symbol will flash. 2 You can adjust the time when the unit automatically switches off by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER OFF-Tip Stopping the flashing and the timers work. 4 If you want to turn off the ACTIVE TIMER OFF, press the TIMER/SLAP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER OFF'S automatically broken down.

Diagram . .
Diagram . .

2.3.2 The TIMER ON 1 mode You can turn on the timer when the inner unit is not working. By holding the TIMER/SLAP button for 3 seconds, the timer will appear on the LCD screen and the . 2 You can adjust the time when the unit automatically switches on by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER ON-SHAKE indication stops blinking and the timers work. 4 If you want to turn off the ON-SHOT TERM, press the TIMER/SLEEP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER ON .She is automatically broken down.

Diagram . .
Diagram . .
Page 12 of the Hisense AUD-36 user manual — Wired remote control
Page 12 · click to enlarge
Page 12

Wired remote control

3. Installation Wired Remote Control

Before installing the wired remote control, please note:

Diagram . .
Diagram . .
Diagram . .
Diagram . .

The wired remote control shall be installed by a qualified installer in accordance with the installation drawings. For installation, the power must be switched off. Do not install the wired remote control directly in the air current or at heating. The installation process is as follows. 1 Insert a flat screwdriver into the openings at the bottom (2 pieces). Be careful not to damage the circuit board by screwdriver. 2 Remove the back plate. 3 Use two screws (Ø 4x16) to mount the metal back plate in the right place and then connect the wiring for communication. 4 Click the top of the back plate. 5 Then click on the bottom of the back plate.

Page 13 of the Hisense AUD-36 user manual — Remote control
Page 13 · click to enlarge
Page 13

Remote control

4. Wireless Remote
Diagram . .
Diagram . .

The remote control sends signals to the system.

ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.

Stand-KNOP Press this button to select the operating mode.

VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.

SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.

SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.

SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.

SLEEP KNOP To set or disable sleep mode. DIMMER-KNOP (not available for this model) The brightness of the screen is reduced every time the button is pressed and after four pushes the image disappears.

I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control must be located in a location where the signal can easily be received through the inner unit.) TEMP SCHAKEL-KNOP (not available for this model) Specifies the set temperature flashing when the button is pressed. Indicates the indoor temperature when pressing the button again. The indication can be terminated by pressing the button again.

KNOP KLOCK To set the current time.

ON/OFF TIMER button To set or disable the timer.

SUPER-KNOP (not available for heating mode) To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)

ZACHT-KNOP (only works with DC inverter models) To limit the maximum power consumption, so that you can use the unit together with other electrical devices if there is not enough current.

DEMPEN-KNOP To set or disable the DEMPE mode.

SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right. *Not all remote control models have this button.

Symbols shown on the LCD display:

Autom. fan speed

Set view timer Display current time

Gem. fan speed

Aborting view I FEEL

NOTE: Each position with the relevant functions is explained in more detail on the following pages.

Show 15 more labels / short text on this page
Remote control -H1 · 18* · Display cooling · Display Slim · Shipping signal · Display drying · High fan speed · Display Sleeping mode · Display only ventilation · Display damping · Display heating · Low fan speed• Display Super · Display set temperature · Display soft
Page 14 of the Hisense AUD-36 user manual — LET OP:
Page 14 · click to enlarge
Page 14

Remote control

Diagram . .
Diagram . .

Battery application

Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.

LET OP:

Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Diagram . .
Diagram . .

S ET C LOCK S ET T IMER A

Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.

Remote control · Usage · Receiver signal

Page 15 of the Hisense AUD-36 user manual — *HEATING/COOLING
Page 15 · click to enlarge
Page 15
Diagram . .
Diagram . .

Each time the stand button is pressed, the operating condition changes in order:

The heating mode is not available for air conditioners that can only cool.

Each time the VENTILATOR button is pressed, the fan speed changes in order:

In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.

Press once to increase temperature setting by 1 °C

Press once to lower the temperature setting by 1 °C

Range of available temperature setting

*HEATING/COOLING

18 °C ~ 32 °C

NOTE: The heating mode is not available for models that can only cool.

The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.

When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.

Operating conditions

Page 16 of the Hisense AUD-36 user manual — MODE CLOCK TIMER ON TIMER OFF
Page 16 · click to enlarge
Page 16

Control of the direction of airflow (not available for this model)

Control of the direction of airflow

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 16 diagram (page 16)
Fig. 22

The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.

The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.

COOLING, DRYING

*HEAT ONLY VENT.

Hisense AUD-36 — COOLING, DRYING diagram (page 16)
Fig. 23

MODE CLOCK TIMER ON TIMER OFF

I FEEL SOFT 4

DIMMER SMART

SLEEP

MUTE TEP SWITCH

Control of vertical airflow (with remote control)

Hisense AUD-36 — MODE CLOCK TIMER ON TIMER OFF diagram (page 16)
Fig. 24

Use the remote control to set alternate angles or, if desired, certain current corners.

Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.

By pressing the "SWING" button again, the air valve will swivel to the desired angle.

Control horizontal airflow (with remote control)

Use the remote control to set alternate angles or, if desired, certain current corners.

Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.

By pressing the "SWING" button again, the air valve will swivel to the desired angle.

Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.

It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Show 7 more labels / short text on this page
Operating condition Direction of airflow · horizontal · downward · alternating airflow * specific direction of air flow · alternating flow · certain direction of flow
Page 17 of the Hisense AUD-36 user manual — COOLING
Page 17 · click to enlarge
Page 17

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.

Operating condition and temperature are determined by the indoor temperature

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 17 diagram (page 17)
Fig. 25

Lower than T-3 °C

HEATING

T

T-3 °C ≤ Interior ≤ T+3 °C

ONLY VENTILATE

T

Higher than T+3 °C

COOLING

T

Models for cooling only

Hisense AUD-36 — COOLING diagram (page 17)
Fig. 26

MODE CLOCK TIMER ON TIMER OFF

DIMMER SMART

SLEEP

T+3 °C or less

ONLY VENTILATE

T

MUTE TEP SWITCH

T Higher than T+3 °C

COOLING

I FEEL SOFT

Hisense AUD-36 — COOLING diagram (page 17)
Fig. 27

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.

What can you do in SLIMME mode?

Uncomfortable due to incorrect air flow

Fan speed changes between high, gem. and down, every time the button is pressed.

Uncomfortable due to incorrect direction of flow

Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.

Uncomfortable due to incorrect direction of flow

Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.

The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

Show 11 more labels / short text on this page
SLIMME-position · Heat pump models · Indoor temperature · Operating condition · Target temperature · Inside temperature · Operation status · Feeling · Button Type of adjustment · CLOK button
Page 18 of the Hisense AUD-36 user manual — Disable TIMER ON
Page 18 · click to enlarge
Page 18

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.

Setting up TIMER ON

The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.

Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.

Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.

NOTE: If you do not set the time within 5 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.

Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.

After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.

Disable TIMER ON

Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.

NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.

Show 6 more labels / short text on this page
Timer mode · i) · Increase · Decrease · ii) · iii)
Page 19 of the Hisense AUD-36 user manual — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 19
Page 19 · click to enlarge
Page 19
Diagram . .
Diagram . .

The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:

will stop the unit automatically after it has been working for 8 hours.

NOTE: The heating mode is not available for air conditioners that can only cool.

(not available in heating mode)

Diagram . .
Diagram . .

The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.

The SUPER mode can be set when the device is working or on.

In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.

NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.

SUPER mode · SUPER position

Page 20 of the Hisense AUD-36 user manual — I FEEL
Page 20 · click to enlarge
Page 20

Remote control

Diagram . .
Diagram . .

The remote control sends signals to the system.

ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.

Stand-KNOP Press this button to select the operating mode.

VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.

SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time..

SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.

SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.

SLEEP KNOP To set or disable sleep mode. I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control shall be located in a location where the signal can easily be received through the internal unit.)

* Note: some remote control models do not have buttons in the square with dotted line.

KNOP KLOCK To set the current time.

DIMMER-KNOP (not available for this model) The brightness of the screen is reduced every time the button is pressed and after four pushes the image disappears.

ON/OFF TIMER button To set or disable the timer.

SUPER-KNOP For setting or turning off the fast cooling/heating. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C. Fast heating works with an automatic fan speed and a 32 °C temperature setting.)

SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right.

Symbols shown on the LCD display:

Autom. fan speed

Set view timer Display current time

OFF

Gem. fan speed

I FEEL

NOTE: Each position with the relevant functions is explained in more detail on the following pages.

Show 13 more labels / short text on this page
Remote -J1 · Display cooling · Display Slim · Shipping signal · Display drying · High fan speed · Display Sleeping mode · Display only ventilate · Display heating · Low fan speed• Display Super · Display set temperature · Display not available
Page 21 of the Hisense AUD-36 user manual — LET OP:
Page 21 · click to enlarge
Page 21

Remote control

Hisense AUD-36 — Remote control diagram (page 21)
Fig. 31 · Remote control

Battery application

Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.

LET OP:

Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Diagram . .
Diagram . .

Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.

S ET C LOCK S ET T IMER A

Remote control · Usage

Page 22 of the Hisense AUD-36 user manual — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 22
Page 22 · click to enlarge
Page 22
Diagram . .
Diagram . .

Each time the stand button is pressed, the operating condition changes in order:

The heating mode is not available for air conditioners that can only cool.

Each time the VENTILATOR button is pressed, the fan speed changes in order:

In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.

Press once to increase temperature setting by 1 °C

Press once to lower the temperature setting by 1 °C

NOTE: The heating mode is not available for models that can only cool.

The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.

When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.

Operating conditions

Page 23 of the Hisense AUD-36 user manual — SMART FAELE DIMMER
Page 23 · click to enlarge
Page 23

Control of the direction of airflow (not available for this model)

Control of the direction of airflow

The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 34
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 35
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 36
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 37
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 38
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 23 diagram (page 23)
Fig. 39

The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.

OFF

OFF

COOLING, DRYING

*HEAT ONLY VENT.

ON/OFF

MODE FAN

Control of vertical airflow (with remote control)

SLEEP SUPER

Use the remote control to set alternate angles or, if desired, certain current corners.

SMART FAELE DIMMER

TIMER ON TIMER OFF CLOCK

Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.

By pressing the "SWING" button again, the air valve will swivel to the desired angle.

Control horizontal airflow (with remote control)

Use the remote control to set alternate angles or, if desired, certain current corners.

Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.

By pressing the "SWING" button again, the air valve will swivel to the desired angle.

Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.

It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Show 7 more labels / short text on this page
Operating condition Direction of airflow · horizontal · downward · alternating airflow * specific direction of air flow · alternating flow · certain direction of flow
Page 24 of the Hisense AUD-36 user manual — FAN
Page 24 · click to enlarge
Page 24

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 40
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 41
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 42

Operating condition and temperature are determined by the indoor temperature

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 43
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 44
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 24 diagram (page 24)
Fig. 45

OFF

Lower than T-3 °C

HEATING

T

T-3 °C ≤ Interior ≤ T+3 °C

ONLY VENTILATE

T

ON/OFF

Higher than T+3 °C

COOLING

T

Models for cooling only

MODE FAN

SLEEP SUPER

T+3 °C or less

ONLY VENTILATE

T

SMART FAELE DIMMER

T Higher than T+3 °C

COOLING

TIMER ON TIMER OFF CLOCK

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.

What can you do in SLIMME mode?

Uncomfortable due to incorrect air flow

Fan speed changes between high, gem. and down, every time the button is pressed.

FAN

Uncomfortable due to incorrect direction of flow

Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.

Uncomfortable due to incorrect direction of flow

Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.

The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

Show 11 more labels / short text on this page
SLIMME-position · Heat pump models · Indoor temperature · Operating condition · Target temperature · Inside temperature · Operation status · Feeling · Button Type of adjustment · CLOK button
Page 25 of the Hisense AUD-36 user manual — Disable TIMER ON
Page 25 · click to enlarge
Page 25

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.

Setting up TIMER ON

The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.

Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.

Hisense AUD-36 — Setting up TIMER ON diagram (page 25)
Fig. 46 · Setting up TIMER ON

Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.

NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.

Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.

After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.

Disable TIMER ON

Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.

NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.

Show 6 more labels / short text on this page
Timer mode · i) · Increase · Decrease · ii) · iii)
Page 26 of the Hisense AUD-36 user manual — OFF
Page 26 · click to enlarge
Page 26
Diagram . .
Diagram . .

The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:

will stop the unit automatically after it has been working for 8 hours.

NOTE: The heating mode is not available for air conditioners that can only cool.

The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C. Fast heating works with an automatic fan speed, automatically changing the set temperature to 32 °C.

OFF

The SUPER mode can be set when the device is working or on.

In the SUPER mode, you can adjust the direction of the airflow or timer. To disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF, SLEEP or TEMPERATURE INSTITUTION.

OFF

NOTE: The SLIM button is not available in SUPER mode. The device will continue to work in SUPER mode if you do not break it down by pressing one of the buttons specified above.

Show 5 more labels / short text on this page
SLEEP-mode · SUPER-mode * SUPER mode · fast cooling · quick heating
Page 27 of the Hisense AUD-36 user manual — I FEEL
Page 27 · click to enlarge
Page 27

Remote control

The remote control sends signals to the system.

Diagram . .
Diagram . .

ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.

Stand-KNOP Press this button to select the operating mode.

VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.

SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.

SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.

SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.

SLEEP KNOP To set or disable sleep mode.

I FEEL-Button To set or disable the I FEel mode.

10 SUPER-KNOP To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)

KNOP KLOCK To set the current time.

ON/OFF TIMER button To set or disable the timer.

Symbols shown on the LCD display:

Shipping signal Display cooling

Autom. fan speed

Set view timer Display current time

OFF

Gem. fan speed

I FEEL

Display heating display temperature set

NOTE: When you put the batteries in your remote control for the first time, all indications appear on the LCD screen for a few seconds and then the "Cow" and "warming" indications are displayed sequentially, allowing you to choose "Heating" models and "Coulding" only for cooling models. Each position with the relevant functions is explained on the following pages.

Show 8 more labels / short text on this page
Remote -E4-07 · Display Slim · Display Drying · High fan speed · Display Sleep Mode · Display only Ventilation · Low fan speed· Display Super
Page 28 of the Hisense AUD-36 user manual — LET OP:
Page 28 · click to enlarge
Page 28

Remote control

Diagram . .
Diagram . .

Battery application

Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.

Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.

LET OP:

Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.

Diagram . .
Diagram . .

Point the remote to the wired remote control to control the air conditioner. The remote control can operate the wired remote up to 8 m distance, if it is directed towards the receiver of the wire-wired remote.

S ET C LOCK S ET T IMER A

Remote control · Usage

Page 29 of the Hisense AUD-36 user manual — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 29
Page 29 · click to enlarge
Page 29
Diagram . .
Diagram . .

Each time the stand button is pressed, the operating condition changes in order:

The heating mode is not available for air conditioners that can only cool.

Each time the VENTILATOR button is pressed, the fan speed changes in order:

In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, the fan speed is automatically on Autom. set, the VENTILATOR button does not work in this case.

Press once to increase temperature setting by 1 °C

Press once to lower the temperature setting by 1 °C

NOTE: The heating mode is not available for models that can only cool.

Diagram . .
Diagram . .

Press the button, once the signal is received by the device, the display that the inner unit works will light up. (This model has no display for operation.)

The positions SHOW, SLIM, TIMER ON, TIMEER OFF, SLEEP, KLOCK and SUPER are explained on the following pages.

When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. Always wait 3 minutes before restarting the device.

Operating conditions

Page 30 of the Hisense AUD-36 user manual — FAN MODE
Page 30 · click to enlarge
Page 30

Control of the direction of airflow (not available for this model)

Control of the direction of airflow

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 30 diagram (page 30)
Fig. 53

The vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 30 diagram (page 30)
Fig. 54

The direction of the airflow can also be adjusted to your own requirements by pressing the SWING button on the remote control.

OFF

COOLING, DRYING

SUPER

SMART

*HEAT ONLY VENT.

FAN MODE

TIMER ON

TIMER OFF

SLEEP

CLOCK

I FEEL

*The heating mode is only available for heat pump models.

Control of vertical airflow (with remote control)

Use the remote control to set alternate angles or, if desired, certain current corners.

By pressing the SWING button, the horizontal air valve will automatically swivel up and down.

By pressing the SWING button again, the air valve will swivel to the desired angle.

Do not adjust the horizontal valve manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.

It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Show 5 more labels / short text on this page
Operating condition Direction of airflow · horizontal · downward · alternating airflow * Certain direction of air flow
Page 31 of the Hisense AUD-36 user manual — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 31
Page 31 · click to enlarge
Page 31

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, regardless of whether the unit is on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.

Diagram . .
Diagram . .

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.

Diagram . .
Diagram . .

Fan speed changes between high, gem. and down, every time the button is pressed.

Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.

The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

SLIMME mode

Page 32 of the Hisense AUD-36 user manual — Disable TIMER ON
Page 32 · click to enlarge
Page 32

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.

Setting up TIMER ON

The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.

Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.

Press the button once to increase or decrease time by 1 minute. Press the or button for one and a half seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.

NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.

Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.

After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.

Disable TIMER ON

Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.

NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.

Show 6 more labels / short text on this page
Timer mode · i) · Increase · Decrease · ii) · iii)
Page 33 of the Hisense AUD-36 user manual — SUPER
Page 33 · click to enlarge
Page 33
Diagram . .
Diagram . .

The SLEEP mode can be set at the positions COOL, HEAR, DROGEN or SLIM. The function ensures a more comfortable environment during sleep. In SLAP mode:

will stop the unit automatically after it has been working for 8 hours.

NOTE: The heating mode is not available for air conditioners that can only cool.

The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.

Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 33 diagram (page 33)
Fig. 58
Hisense AUD-36 — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 33 diagram (page 33)
Fig. 59

The SUPER mode can be set when the device is working or on.

In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.

SUPER

SMART

FAN MODE

TIMER ON

TIMER OFF

SLEEP

CLOCK

I FEEL

NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.

SLEEP mode · SUPER mode ·Super mode

Page 34 of the Hisense AUD-36 user manual — CAREFUL
Page 34 · click to enlarge
Page 34

5. Special comments

3 minutes of protection after a stop from the compressor. To protect the compressor, after a stop the compressor cannot be switched on for at least 3 minutes.

Five minutes of protection. The compressor must operate at least 5 minutes after it is switched on. In these 5 minutes, the compressor will not stop even if the room temperature has reached its set value unless you switch off the unit using the remote control (all units disabled by the user).

Cooling function. In the cooling mode, temperature can be set between 18-32 °C. The fan of the inner unit will never stop working. It's gonna keep working even if the compressor stops.

Heating function. Because the air conditioner heats through outdoor heating (with the heat pump), it can reduce its heating capacity if the outside temperature is too low. If the effect of heating is not sufficient, an additional heater shall be used.

Anti-freeze function in cooling. If the temperature of the air outlet in the inner unit is too low, it will work with only the fan for some time to prevent freezing or ice forming inside the heat exchanger.

Prevention of cold air. The fan of the internal unit will not rotate for a few minutes after heating is switched on until the heat exchanger of the inner unit has reached an adequate temperature. The system to prevent a cold air flow is then in operation.

De-shooting. If the outside temperature is too low, freezing or ice formation can occur in the heat exchanger outside which reduces heating performance. The air conditioner defrosting system will then enter into force. At the same time, the fan of the indoor unit (or in some cases runs at very low speed) stops and when a few minutes later the defrosting is ready, the heating will start again.

Blowing out of residual heating air. If the air conditioner stops working normally, the fan engine will run at low speed for a while to blow out the remaining air.

Self-recover after power failure If the power supply is restored following a malfunction, all settings are still active and the air conditioner works according to original settings.

6. Troubleshooting

CAREFUL

If the power supply is restored after a malfunction, all settings are still active and the air conditioner works according to the original settings.

6.1 If problems persist... If problems persist after you have checked the following, please contact your supplier and provide the following information. (1) Model name unit (2) Description of the problem.

6.2 No action Check that SET TEMP is set to the right temperature.

Show 9 more labels / short text on this page
Page 35 of the Hisense AUD-36 user manual — SM AUD UX4SZKL1-UX4SALH1-UX4SAMH1-UX6SPHH 35
Page 35 · click to enlarge
Page 35

6.3 No good cooling or heating Check that the air flow of external or internal units is blocked. Check that there is an additional heat source in the room. Check that the air filter is highly contaminated with dust. Check if windows and doors are open or not. Check that the temperature conditions are outside the scope of operation.

6.4 This is very normal Scent from the inner unit After a longer period of time, an odour can be secreted by the internal unit. Then clean the air filter and panels or let it ventilate properly. Sound due to distortion of parts During the startup or stop of the system, a abrasive sound can be heard. This is due to the thermal deformation of plastic parts. This is perfectly normal. Steam from the heat exchanger of the outer unit During thawing, ice is melted on the heat-exchanger of an external unit and thus steam is generated. Air vent condensation If cooled for a longer period of time under conditions with high humidity (higher than 27 °C/80% RV), condensation can form on the air grid. Sound flow coolant During the start-up or stopping of the system, a sound can be heard from the flow of the coolant.

Show 10 more labels / short text on this page
● · ● · ● · ● · ● · ● · ● · ● · ● · ●
Page 36 of the Hisense AUD-36 user manual — N
Page 36 · click to enlarge
Page 36

Circuit diagram

1. Flow diagram coolant

INSIDE UNIT OUTSIDE UNIT

Diagram . .
Diagram . .

Note: The EEV only applies to the DC inverter air conditioner, use for other air conditioners a fixed expansion valve. The accumulator only applies to the 48 k and 60 k air conditioners.

2. Scheme of electrical wiring

DC inverter integrated model:

On/off integrated model:

N

N

SI

SI

N N

N

N

Power supply 18 k/24 k/36 k

N

N

N

N

SI

SI

SI

SI

W

N

U

N

48 k/60 k Inside unit

N

N

SI

SI

W

U

N

36 k/48 k/60 k

Show 19 more labels / short text on this page
External unit Inner unit · Outside unit Inside unit · Connection block Connecting block · Cable power supply · Cyber power supply * Power supply · Outdoor unit In-unit · External unit Within unit · Connector block In-house unit · Cylindrical power provision · Connectory block Connection block · Current supply · Electrical system 24 k · External part · Connection Block Connection block
Page 37 of the Hisense AUD-36 user manual — CAREFUL
Page 37 · click to enlarge
Page 37

Installation and maintenance

1. Safety instructions

WARNING

· The installation must be carried out by the dealer or another expert person. (Incorrect installation can cause water leakage, electric shocks, or fire.) Install the unit according to instructions in this manual. (Incomplete installation can cause water leakage, electric shocks, or fire.) Use only the standard included or specified installation components. (Use of other components can cause the unit to break down, water leakage, electric shocks or fire.) Install the air conditioner on a solid base that can carry the weight of the unit. (An unsuitable substrate or faulty installation may cause injury if the unit falls.) Electrical work must be carried out in accordance with the installation manual and local regulations and guidelines for electrical wiring. (Insufficient capacity or inadequate electrical work can cause electric shocks or fire.) Make sure to use a separate electrical group. (Never use a shared power supply with another device.) Use for the wiring a cable long enough to last all length without connecting and do not use an extension cord. Do not connect any other load on the power supply, use a separate group. (If you do not, this may lead to abnormal heat development, electric shocks or fire.) Use the required types of wiring for electrical connections between indoor and outdoor units. (Connect the connecting wires firmly so that there is no external voltage on the connection blocks.) Inappropriate fitting or clamping can result in overheating of the connector block or fire. After connecting connections and the power cable, they shall be securely secured so that no forces are applied to the covers or electrical panels. (Install a wire cover, incorrect installation of this device can cause overheating of the connection block, electric shocks or fire.) No other substances such as air may enter the cooling circuit when installed or moved than the prescribed coolant (R410A). (The presence of air or other undesirable substances in the cooling circuit causes an abnormal pressure increase or break, which can cause injury.) If coolant has leaked during installation work, space must be ventilated. (The coolant produces a toxic gas when exposed to flames.) When the entire installation is ready, it must be checked that no coolant leaks. (The coolant produces a toxic gas when exposed to flames.) When connecting the pipes, make sure that no air or other substances than the declared coolant enter the cooling circuit. (Otherwise this can reduce capacity, cause abnormally high pressure in the cooling circuit, explosion or injury.) Make sure to make a grounding. Do not connect the ground to a utility line, lightning distraction or phone earthing. Incorrect earthing can cause electrical shocks. (A high peak current due to lightning or other causes can cause damage to the air conditioner.) Depending on local conditions, an earth leak switch may be necessary to avoid electric shocks. (If you do not, this may lead to electric shocks.) Shut down the power supply before connecting the wiring or pipes or checking the unit. If the internal and external unit is moved, ensure that the outer unit is not tilted by more than 45°. Make sure you do not suffer any injury due to the sharp edge of the air conditioner. Install the remote. Make sure that the length of the wiring between inside unit and remote control is less than 50 m.

CAREFUL

· Do not install the air conditioner in a place where there is a risk of exposure to flammable gases. (If gas leaks and collects around the device, this can cause fire. Install the drains according to instructions in this manual. (Incorrect pipes can cause water pollution.) Turn the nuts on with a torque wrench in accordance with the prescribed procedure. (If the screw nut is tightened too tight, it may break over time and cause coolant leakage.)

Show 20 more labels / short text on this page
Page 38 of the Hisense AUD-36 user manual — CAREFUL
Page 38 · click to enlarge
Page 38

Installation and maintenance

2. Installation tools and instruments

Diagram . .
Diagram . .

3. Installation of the internal unit

CAREFUL

During installation, the installation material on the surface of the interior unit shall not be damaged.

3.1 The first check

CAREFUL

· If the unit is moved when unpacking or after, it must be lifted at the handles. Do not apply pressure to other components, in particular the cooling pipes, drain pipe and flanged parts. Wear protective clothing (gloves, etc.). ·

DC inverter integrated modelDC inverter integrated model: DC inverters integrated model

Model Capacity (Btu/h) h (mm)

Space for maintenance Fig. 3.2.1

36 k 48 k 60 k 350

Diagram . .
Diagram . .
On/off integrated modelOn/off integrated model: On/Out of integrated model

Model Capacity (Btu/h) h (mm)

24 k 270 36 k

Afb. 3.2.2

Floor area (Length)mm)
Show 6 more labels / short text on this page
18 k 190 · 300 of meer · 24 k 270 · 18 k 190 · 48 k · 60 k 350
Page 39 of the Hisense AUD-36 user manual — Installation and maintenance
Page 39 · click to enlarge
Page 39

Installation and maintenance

When installing the unit make sure that: An optimal air distribution is ensured. The air passage is not blocked. Condensation water can be well disposed of. The ceiling is strong enough for the weight of the unit. A lowered ceiling does not run below a slope. There is sufficient space for maintenance and repair (see Fig.3.2.1 and. 3.2.2). The pipes between the inside and outside unit are within the permitted limits (see installation instructions of the outer unit). The inner unit, external unit, power cable and transmitters are at least 1 m away from television and radio to prevent interference in the image and sound of electrical devices. (Even if the limit of 1 m is maintained, noise disturbances can occur depending on the conditions under which electric waves are produced.) Hanging bolts are used for installation and that the ceiling is strong enough to account for the weight of the unit. If the ceiling does not appear to be strong enough, it must be reinforced before installing the unit.

3.2 Installation

3.2.1 Hanging bolts

(1) Carefully look at the direction of pipes, wiring and maintenance, and choose the right orientation and location for installation. (2) Install the hanging bolts as shown in Figure 3.3.1 below.

Diagram . .
Diagram . .

In the case of suction at the bottom, the air chamber cover and inlet flange shall be replaced on the side as indicated in Fig. 3.2.3 (1) Remove the inlet flange on the side. Remove the lid from the air chamber. (2) Re-connect the air chamber cover and inlet flange to orientation as indicated in Fig. 3.2.3. See Figure 3.2.4 for the orientation of the inlet flange.

Fig. 3.3.1 Confirmation of the hanging bolts

3.2.2 The position of the hanging bolts and pipes (1) Indicate the position of suspension bolts and the position for cooling pipes and drains. (2) The dimensions are shown below in Fig. 3.3.2 indicated.

Diagram . .
Diagram . .
Diagram . .
Diagram . .

Air Room Lid

Air Room Lid

a b c d e f g h i j k L m n

Filter (not available for this model)

DC-inverter model 1207 1170 154 447 971 117 1039 170 117 150 199 13 81 84

On/off integrated model 937 900 154 447 701 117 1235 170 117 150 199 13 81 84

Afb. 3.2.4

Show 4 more labels / short text on this page
e b · Inlet flange side · Intake flange side * 18 k
Page 40 of the Hisense AUD-36 user manual — CAREFUL
Page 40 · click to enlarge
Page 40

Installation and maintenance

a b c d e f g h i j k L m n o p 24 k 934 900 669 720 805 222 835 228 242 294 378 405 25 156 202 214 36 k DC-inverter model 1334 1295 669 720 1205 222 1235 228 242 294 378 405 25 156 202 214 36 k Aan/Uit geïntegreerd 1334 1295 740 796 1205 222 1235 228 237 312 375 405 25 204 203 242 48 k & 60 k 1334 1295 740 796 1205 222 1235 228 237 312 375 405 25 204 203 242

(2) Installation of the inner unit Place the left hanging bracket on the nuts with a chain at the hang bolt, as shown in Figure 3.7. Make sure that the left hanging bracket is firmly attached to the nuts and studs, then install the right hanging mount on the screwed hanger with screws and rings.

Diagram . .
Diagram . .

(When installing the inner unit, you can unscrew the suspension bolts.)

Diagram . .
Diagram . .

Fig. 3.4 Hanging bolts

Fig. 3.7

3.3.3 Installation of the inner unit 3.3.4 Horizontal adjustment of the interior unit (1) Make sure that the suspension bracket is attached with the nut and a tail ring. (2) Adjust the height of the unit. (3) Check that the unit is horizontal.

The installation of the inner unit is shown in Fig. 3.5

Hanging bolts (4 x M10) (third party delivery)

nuts and tracking rings (4 x M10) (third party supply)

Fig. 3.8

(4) After adjustment, tighten the nut and apply a threading device to the screw-on bolt to prevent nuts from loosening.

Fig. 3.5 Installation of the internal unit

(1) Attach the screw and nut suspension as shown in Fig 3.6, there are four nuts.

CAREFUL

(1) Cover the unit during installation with a piece of plastic to keep it clean. (2) Make sure that the unit is mounted horizontally using a level or plastic tube filled with water. When using a plastic tube, the top of the unit must be kept equal to the top end of the water at both ends of the pipe and then the unit can be adjusted horizontally. (In particular, care should be taken to ensure that the unit is not tilted towards the drain line as this may cause leakage.)

Diagram . .
Diagram . .

Fig. 3.6 Hanging bolts and nuts

(mm) · Air intake · Suspension bracket

Page 41 of the Hisense AUD-36 user manual — CAREFUL
Page 41 · click to enlarge
Page 41

Installation and maintenance

3.3.5 Installation of the channel

Diagram . .
Diagram . .

CAREFUL

Make sure that the range of external static pressure of the unit is not exceeded. Connect the channel to the inlet and exhaust flange. See example in Fig. 3.9

Fig. 4.2 The pipe diameters

Pressure cabinet Flexible channel Pressure box

(2) Turn the nuts with two keys as shown in Fig. 4.3 is indicated.

Diagram . .
Diagram . .

Only use R410A coolant. When performing the leak control and test, you should ensure that oxygen, acetylene and other flammable and virulent gases do not mix together as they are dangerous and can cause an explosion. It is recommended to use compressed air, nitrogen or coolant for this purpose.

Fig. 4.3 Aging moment

(3) When the connections of the cooling line are rounded off, insulation material shall be provided to the pipes. See example in Fig. 4.4

4.1 Materials for pipes (1) Prepare the copper lines on site. (2) Use dust-free, dry and clean copper pipes. Blow these clean with nitrogen or dry air before installing the pipes to remove dust and impurities. (3) Select the copper pipes according to Fig. 4.2.

Diagram . .
Diagram . .

Side of the inner unit

4.2 Connections of the pipes

Fig 4.4 Insulation method of pipes

(1) The connection positions of the pipes are shown in Fig. 4.1.

CAREFUL

Leads passing through a spar, kitten. Do not place the ends of the pipes directly on the floor as shown in Fig 4.5.

Do not place the ends of the pipes directly on the floor,

Protect it with tape or a plug.

Fig. 4.1 Connection positions of the pipes

Fig. 4.5

Show 5 more labels / short text on this page
Flexible channel · Clamp (supplied) Insulation(supplied). · Cooling gas pipeline Coolant pipe · 78 61 35 · Sparing connection drain
Page 42 of the Hisense AUD-36 user manual — CAREFUL
Page 42 · click to enlarge
Page 42

Installation and maintenance

5. Drain

The two parts mentioned below should be isolated because condensation can form that may drizzle. a. Pipes fed through walls. b. Drain connections. Isolate the drain connection and drain hose with the supplied large insulation strip as shown in the picture below.

Connection of the drain pipe ·

Diagram . .
Diagram . .

Make sure the drain works properly. The diameter of the outlet connection shall be the same as that of the drain pipe itself. Keep the drain short and apply at least 1:100 discharge so that water is properly discharged. See image below.

Fig. 5.4

CAREFUL

Connections drain pipe Do not directly connect the drainage to sewage pipes in which ammonia gas is present. The ammonia gas in the sewage system can enter the internal unit via the drain pipe and cause corrosion of the heat exchanger. Make sure that there are no blows or nods in the drain hose, so that no great forces are applied. This could cause leakage. After the pipework is finished, check that the pipes are properly removed. Pour about 1000 ml of water evenly into the condensate container to check that the drain works as indicated above. Pour about 1000 ml of water evenly through the drain hole into the condensate container to check the drainage. Check the drain as shown in picture below.

Diagram . .
Diagram . .

CAREFUL

Water that can collect in the drain pipe may cause blockage of the pipe. To prevent the snake from going down, this one has to be h.o.h. Hanging 1 - 1,5 m. Use the drain hose and clamp. Slide the drain hose completely over the outlet and attach the hose together with the insulation material by means of the clamp.

Diagram . .
Diagram . .
Show 15 more labels / short text on this page
· · Cooling lines · · · Insulation material Insulation materials · Drain pipe cooling pipes
Page 43 of the Hisense AUD-36 user manual — WARNING
Page 43 · click to enlarge
Page 43

Installation and maintenance

6. Electric wiring

6.1 General control

CAREFUL

  • Use the supplied saddles ed for securing the wiring. so that no forces are applied to the wiring connections and secure them firmly.
  • Make sure that the wiring is properly carried out and do not press up the lid of the control cabinet by means of the wire, then close the hood well. Make sure that no wires are pinched when fixing the lid.
  • Apply a minimum 50 mm separation between weak current wiring (remote control and transmitters) and normal wiring (earth and power supply cables) outside the unit so that they do not continue together. If they are close to each other, this can cause electrical interference, disturbance or breakage.

WARNING

  • If the fuses break, you should call the service company to replace them. Do not replace it yourself, because this can cause an accident like shocks. (1) Remove the screws from the cover cap of the electric control as indicated in Fig. 6.1. (2) Connect the power cable and earth wire to the main connector block. (3) Connect the remote control cable to the side-connection block. (4) Connect the power cable of the inner and outer units to the main connector block. (5) Attach the cables firmly with the saddles in the control cabinet. (6) After the wiring has been completed, close the wired through with sealing material (and lid) to prevent condensation and insects from entering.
Diagram . .
Diagram . .

Fig. 6.1 Remove the screws from the control cabinet

Cover cover electric control

Page 44 of the Hisense AUD-36 user manual — ROOD
Page 44 · click to enlarge
Page 44

Installation and maintenance

6.2 Changing static pressure The static pressure outside the inner unit can be set.

6.2.1 Models 24 k & 36 k excluded (high-efficiency DC inverter model): You can change the static pressure by changing the connection block of the fan engine, as shown in Fig. 6.2.

Low static pressure 10 Pa

WIT

High static pressure 30 Pa

ROOD

Fig. 6.2

18 k 30 Pa 10 Pa

24 k, 36 k 48 k, 60 k 80 Pa 120 Pa 50 Pa 80 Pa

NOTE: The default factory setting is the low static pressure. The noise level at high static pressure is higher than at low static pressure.

6.2.2 Models 24 k & 36 k (high-efficiency DC inverter model):

Standard static pressure is 30 Pa. The static pressure can be freely set between 1 and 80 Pa by using the wired remote control. For the setting details see the manual of the wired remote control. If you have any problems with this, please contact our local technical maintenance service for more information.

Show 4 more labels / short text on this page
Fan engine · Low static pressure · High static pressure· Model
Page 45 of the Hisense AUD-36 user manual — Installation and maintenance
Page 45 · click to enlarge
Page 45

Installation and maintenance

7. Installation of the external unit

Diagram . .
Diagram . .

7.1 Place of installation

Avoid:

Diagram . .
Diagram . .

Direct sunlight A corridor or sideways Thick oil mist installation Wet or irregular places Holder with flammable materials Near a heat source / fan

Do it:

Diagram . .
Diagram . .

Put it in a cool place. Put it in a place with good ventilation. Keep the desired distances for air intake, exhaust and maintenance. (Afb. 7.1) Make a strong base (10x40 cm2 of concrete or equivalent). The device must be placed at least 10 cm higher so that it does not get wet or corrosion occurs, otherwise this can cause damage to the appliance and reduce its lifespan. (Afb. 7.2) Attach the base with hae cancers or equivalent to reduce noise and vibration.

*For 24 k (high-efficiency DC inverter model): The line length between inside and outside unit is the same as for 36 k models.

If the total line length is between 5 and 50 m (max. The length of the test is equal to or greater than 1 mm. There is no need to add compressor oil. (Afb. 7.3)

Fig. 7.3

7.2 Installation of the external unit. First select the installation location and confirm the outer unit. If it needs to be attached to a wall, make sure that the wall and supporting rack is strong enough to carry the weight of the device.

Diagram . .
Diagram . .

Remove the fixing screws from the cover of the electrical connection box and remove it (if the cover is in the valve), remove them. Connect the wiring of the inner unit to the outer unit panel according to electrical wiring schematics. Make sure that each wire is 10 cm longer than the length required for wiring. Connect the unit to grounding according to local electrical regulations. Check the wiring with the schematics and make sure it's properly connected. Secure the wiring with clamps and re-enable the cover.

Fig. 7.1

Diagram . .
Diagram . .

Fig. 7.2

Show 6 more labels / short text on this page
Wiring instructions for outdoor unit · ● · • · − · · · ●
Page 46 of the Hisense AUD-36 user manual — 9. Ventilation and test run
Page 46 · click to enlarge
Page 46

Installation and maintenance

8. Cooling lines

The two cooling lines (and the electrical wiring if permitted by local standards) must be bound together with protective tape. The drain hose can also be carried and bundled with the pipes. Wrap the protective tape around the pipes from the bottom of the outer unit to where the pipes go through the wall. Wrap the tape around the pipes with each overlapping of half a width of the tape. (see Fig. 8.7) Attach the bundle against the wall with saddles h.o.h. approx. 120 cm.

8.1 Connecting Flare to flare tool

Note: A good flare connection has the following properties: The surface of the inside is shiny and smooth. The edge is smooth. The oblique sides are of equal length.

Remove the blackberries at the end of the copper tube with a larger or file. Keep the end of the tube down at fileting so that no filings will enter the tube. These operations are important and must be carefully performed to make a good flare connection (pict. 8.1 and 8.2). Remove the screw nut from the unit and slide it onto the copper tube. Make the flare connection at the end of the copper tube with the flare tool (fig. 8.3).

8.5 Finishing the installation

After completing taps and insulation, the hole in the wall should be sealed with a suitable kit against wind and rain.

9. Ventilation and test run

8.2 Connecting line between indoor and outdoor units

Air and moisture remaining in the cooling system have undesirable effects. They should therefore be completely removed by performing the following steps.

Make sure to use a seal cap or waterproof tape to prevent any water or dust from entering the pipes before they are used. Ensure a thin layer of coolant is applied to the surfaces of the flare connection that are connected before they are coupled. This way gas leaks are reduced. For a good connection, apply both tubes in each other and then screw the nut manually to get a perfect connection. (Afb. 8.5) Turn the nuts with a torque wrench to prevent coolant leakage. Test carefully for leakage before the unit is put into operation.

9.1 Aeration with a vacuum pump (see Fig. 9.1, 9.2)

(1) Check that each pipe (both thin and thick pipes between indoor and outdoor units) is well connected, and all wiring for test turning is complete. Please note that all valves of the pipes on the outer unit are closed at this stage. (2) Remove the cap of the main valve using an English key or ring key. (3) Connect a vacuum pump to the main valve. (4) Turn on the vacuum pump until pressure is lower than 15 Pa (or 1,5×10-4 bar) for 5 minutes. (5) Remove the vacuum pump from the main valve while still running. Then stop the vacuum pump. (6) Re-apply the cover cap to the main valve and tighten it firmly with an English key or ring key. (7) Remove the cover cap of both small and large valve using an English key or ring key. (8) With a bus key, fully open the valve of the small and large pipe valve against the clock. (9) Re-apply the covers to the small and large valve and tighten them firmly with an English key or ring wrench.

8.3 Heat insulation of the cooling line

To prevent heat loss and wetness of the floor by condensation, all cooling pipes shall be insulated with an appropriate insulation material having a minimum thickness of 6 mm (see Fig. 8.6).

8.4 Taping of pipes

Note: Wind the protective tape not too tight to reduce the thermal insulation. Make sure that the condensate water drain hose runs separately from the beam at a given time and is discharged as described above.

Show 13 more labels / short text on this page
● · ● · ● · ● · ● · ● · ● · ● · ● · ● · ● · ● · ●
Page 47 of the Hisense AUD-36 user manual — WARNING
Page 47 · click to enlarge
Page 47

Installation and maintenance

9.2 Leakage test

Diagram . .
Diagram . .

Check all connections and valves of indoor and inner unit with liquid soap. The cover of the filling opening shall be checked for at least 30 seconds. Remove all soap residue after the test to prevent it from affecting copper pipes.

9.3 Finishing of the pipes

Diagram . .
Diagram . .

If the leakage test is satisfactory, the heat insulation shall be re-established at the connections. Apply the connecting lines straight and attach them tightly to the wall. Close the space around the pipes that run through the spar in the wall with a sealing material.

9.4 Test twisting

The test shall be carried out in accordance with the installation and maintenance manual.

WARNING

Only after all checkpoints have been checked can the unit be put into operation. (1) Check that the resistance of the connection to earth is more than 1 MΩ, otherwise you cannot use the unit until the point where electricity leaks has been found and repaired. (2) Check that the valve is open before using the unit.

Diagram . .
Diagram . .

Make sure the outside unit is running properly and then switch on the inside unit. Turn the device on and set it to cooling, drying or heating depending on room temperature. Check that the device is working properly.

The installation of the device is usually completed when the above points are executed. If you have any problems with this, please contact our local technical maintenance service for more information.

Fig. 8.1

Fig. 8.2

For Na · Leader · Larger

Page 48 of the Hisense AUD-36 user manual — WARNING
Page 48 · click to enlarge
Page 48

Installation and maintenance

9.5 General

WARNING

Use an earth leak switch, otherwise this can cause electric shock or fire. Do not use the system until all checkpoints are resolved. (1) Check that the insulation resistance is more than 1 MΩ by measuring the resistance between earth and electrical components. If not, the system should not be switched on until the point where electricity leaks has been found and repaired. (2) Check that the valves of the outside unit are fully open and then start up the system. Note the following when the system is running. (1) Do not touch any of the components from the gas outlet side manually, as the compressor chamber and drain pipe are heated to a temperature above 90 °C. (2) DO NOT PRESS THE BUTTON OF THE MAGNETIC SWITCH(S). This could cause a serious accident.

Power supply EN60 335-1 EN60 3351

dimensions of power cable off. Control cable

18 k (On/off integrated model)

220~240 V, 50 Hz 3x1,5 mm2 5x1,5 mm2

18 k (DC inverter integrated model)

220~240 V, 50 Hz

24 k 36 k (DC inverter integrated model)

220~240 V, 50 Hz

5x1,5mm2 4x0,75 mm2

36 k (On/off integrated model)

380~418 V, 50 Hz

42 k/48 k/60 k

380~418 V, 50 Hz

NOTES: 1) Follow local standards and regulations when choosing the wiring. 2) The dimensions of the wiring specified in the table are determined at maximum flow rate for the unit according to European standard EN60 335-1. Use cables that are not lighter than the normal flexible cable with hard rubber mantle or regular flexible cable using polychloroprene cloak (type H07RN-F). 3) Use a shielded cable for the transmitter cable and connect it to the ground. 4) If power cables are connected in series, the maximum current of each unit must be added together and then the cable is selected from the table below.

Selection according to EN60 335-1 Current i (A) Wire size (mm2)

*If the current exceeds 63A, cables must not be switched in series. 5) To comply with the standard EN 61000-3-11, the system must be connected to a power supply with an impedance of: .Zsys≤0.247 Ω (for 18 k On\From integrated model) . Zsys =0,209 Ω ("for 24 k On" from integrated model). Before connecting the product to the public electricity grid, check with local energy companies if the network meets the above requirements.

Show 9 more labels / short text on this page
● · ● * · Capacity (Btu/h) · 3x1.5 mm2 · 3 x2.5mm2 · 5x2.5mm2. · , · .
Page 49 of the Hisense AUD-36 user manual — HS
Page 49 · click to enlarge
Page 49

PACKAGING LIST

INNER UNIT PACKAGING LIST

No. NAME NUMBER

INSIDE UNIT

INSIDE ACCESSORIES 1

INSIDE ACCESSORIES 2

INSIDE ACCESSORIES 3*

MANUAL

WIRED REMOTE CONTROL

* Not available for 18 k-models.

OUTER UNIT PACKAGING LIST

No. NAME NUMBER

OUTER UNIT

DRAINAGE BEND

Correct removal of this product.

This indication indicates that this product must not be disposed of with ordinary household waste throughout the EU. In order to prevent damage to the environment or health caused by uncontrolled waste disposal, it should be recycled responsibly and promote sustainable reuse of materials. Return the used device by using return and collection systems or contact the dealer where the product was purchased. They can recycle this product in an environmentally friendly way.

HS

Climate Solutions B. V. Exclusive Hisense Importer Benelux

HS Climate Solutions B. V. Carnelian 400 3316 KC Dordrecht

e. [email protected] w. www.hs-cs.nl t. 088-4355450 f. 088-4355451

SK No 60753986 IBAN No EN92ABNA0443804362 VAT NO. EN854044954B01

Version number 20150101-EN The design and specifications can be changed without further notice. Images and diagrams are for information purposes only, and may be modified without further notice.

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Hisense AUD-36

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Hisense AUD-36

Be the first to ask — other owners or our team will answer.

Original document

Hisense AUD-36 manual PDF

49 pages·15.5 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…